Danfoss APP 1.5, APP 1.8, APP 2.2, APP 2.5, APP 3.0 Operating guide

...
Operating guide
User manual
APP pumps
Installation, Operation and
Installation, Operation and
Maintenance Manual
Maintenance Manual
APP pumps (APP 1.5-3.5)
APP 1.5-3.5
hpp.danfoss.com
ro-solutions.com
Operating guide | APP 1.5-3.5 pumps
Table of Contents Contents
Table of Contents ..................................................................................2
Validity .........................................................................................4
1. Introduction ............................................................................5
1.1 General.................................................................................5
1.2 Symbols ................................................................................5
1.3 Manufacturer and customer service address .............................................6
1.4 Country specific information ............................................................6
1.4.1 United Kingdom ........................................................................6
2. Safety ..................................................................................6
2.1 General information.....................................................................6
2.2 Preferred system design.................................................................6
2.3 Commissioning and servicing the unit ...................................................7
2.4 Adhere to the following important points ...............................................7
2.5 In case of doubt .........................................................................7
3. Technical data ..........................................................................7
3.1 Approved applications and operational limits for the pumps .............................7
3.2 Application range .......................................................................7
3.3 Electric motor data......................................................................7
3.4 Noise and vibration .....................................................................7
3.5 Dimension drawings ....................................................................7
3.6 Space requirement......................................................................7
3.7 Filtration................................................................................8
3.8 Properties of water ......................................................................8
3.9 Air bubbles .............................................................................8
3.10 Chemicals...............................................................................8
4. Arrival inspection, transportation, handling, lifting and storage ..........................8
4.1 Arrival inspection .......................................................................8
4.2 Warning ................................................................................8
4.3 General safety information ..............................................................8
4.4 Transport and handling .................................................................8
4.5 Return to supplier .......................................................................9
4.6 Storage .................................................................................9
5. Installation and commissioning.........................................................10
5.1 Important dimensions .................................................................10
5.2 Cleanliness.............................................................................10
5.3 Fluid temperature......................................................................10
5.4 Electrical data..........................................................................10
5.5 Local regulations.......................................................................10
5.6 Pre mounting checklist, based on Danfoss preferred system design .....................11
5.7 Lifting and positioning.................................................................11
5.8 Mount the different equipment ........................................................11
5.9 Electrics ...............................................................................11
5.10 Instrumentation .......................................................................11
5.11 Connections ...........................................................................11
5.12 Ensure free flow .......................................................................12
5.13 Verify setting of safety/relief valves .....................................................12
5.14 Flush the pump ........................................................................12
5.15 Bleed and remove air from the pump...................................................12
5.16 Verify direction of rotation .............................................................12
5.17 Commissioning ........................................................................12
5.18 Check the filter condition...............................................................12
5.19 Instruct operator and maintenance personnel ..........................................12
6. Operation of pump unit ...............................................................13
6.1 General safety information.............................................................13
6.2 What to listen and look for .............................................................13
2
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
7. Maintenance and service of the pump unit .............................................13
7.1 General safety information .............................................................13
7.2 Service and inspection interval for the pump ...........................................13
7.3 Shut down of the system ...............................................................13
7.4 Disassembling and assembling the pump unit ..........................................14
7.5 Assembling the pump unit .............................................................14
7.6 Procedure for mounting the pump onto the electric motor..............................14
7.7 Getting the pump unit back into operation .............................................14
7.8 Storage of the pump ...................................................................14
8. Troubleshooting and scrapping criteria .................................................15
8.1 General safety information .............................................................15
8.2 Operational conditions which can cause pump failures..................................15
8.3 Mechanical failure......................................................................15
8.4 Electrical failure........................................................................15
8.5 Responsibility..........................................................................15
8.6 Scrapping criteria ......................................................................15
Appendices ......................................................................................17
Table of Contents .................................................................................18
1. Data sheet for APP 1.5-3.5 (AI274333290009en-000701) .................................19
2. Pump instruction APP 1.5-3.5 (180R9065) ...............................................33
3. IOM Electric motors (180R9230)..........................................................41
4. Recommended service intervals for APP pumps (AX290239527130en-000201)...........47
5. Parts list for APP 1.5-3.5 (AX274346749037en-000501)...................................51
6. Trouble shooting guide for APP, APP S and APP S 674 pumps ............................61
7. Right and wrong (180R9042) ...........................................................73
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
3
Operating guide | APP 1.5-3.5 pumps
Validity
This manual is valid for APP pumps both non ATEX and ATEX certified versions. An ATEX certified pumps are indicated by Ex in the designation - example APP 3.5 Ex.
APP 1.5
APP 1.8
APP 2.2
APP 2.5
APP 3.0
APP 3.5
Code no. 180B30 43
Serial no. XXXXXX02-XXX XXXXXX02-XXX
Code no. 180B30 44
Serial no. XXXXXX02-XXX XXXXXX02-XXX
Code no. 180B30 45
Serial no. XXXXXX02-XXX XXXXXX02-XXX
Code no. 180B30 46
Serial no. XXXXXX02-XXX XXXXXX02-XXX
Code no. 180B3030
Serial no. XXXXXX02-XXX XXXXXX02-XXX
Code no. 180B3032
Serial no. XXXXXX02-XXX XXXXXX02-XXX
In case the pump delivered is ATEX certified, the additional ATEX instruction must also be read.
APP 1.5 Ex
APP 1.8 Ex
APP 2.2 Ex
APP 2.5 Ex
APP 3.0 Ex
APP 3.5 Ex
On request
On request
180 B3145
180 B3146
180B3130
180B3132
PUMP
Type APP 2.2 Code no. 180B3045
Serial no. XXXXXX02-XXX
MADE IN DENMARK
Danfoss A/S, 6430 Nordborg, Denmark
The serial number is referring to the Serial no. on the product label. The digits shown (03) indicate the version number of the pump. This documentation is compatible with previous pump versions.
4
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
1. Introduction
1.1 General
The APP pumps and pump units are manufac­tured by Danfoss A/S, and are sold and marketed by a net of authorized distributors world wide.
This manual contains the necessary instructions for the installation, operation and service of the pumps used in a Sea Water Reverse Osmosis (SWRO) system or Brackish Water Reverse Osmosis (BWRO) system.
In case the pump delivered is ATEX certified, the additional ATEX instruction must also be read.
The APP pumps must not be used for other purposes than those recommended and specified without first consulting your local pump distributor.
Use of the pump in other applications that are not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
• If any changes are made without written approval the warranty will automatically become void.
It is important that these instructions are always available to the personnel concerned.
1.2 Symbols
Indicates something to be noted by the
reader
Indicates a situation which will or could
result in damage to the pump and its function
Indicates a situation which will or could
result in personal injury and/or damage to the pump
Electrical hazard - Indicates a high-
voltage warning
All personnel being responsible for operation and maintenance of the pump unit must read and fully understand these instructions, especially the section “Safety”, before:
• Transportation of the pump unit
• Lifting the unit
• Installing the pump unit
• Connecting the pump unit to the water system
• Connecting the electric motor and instru­mentation
• Commissioning the unit
• Servicing the pump unit, mechanical and electrical parts
• Decommissioning the pump unit
The pump must always be installed and used in accordance with existing national/local sanitary, safety regulations and laws.
It is the responsibility of the safety officer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual.
Safety glasses required
Hearing protection required
Safety shoes required
Safety helmet required
!
Protective garments must be wor n
Protective garments
must be worn
Danger HOT.
Do not touch
Changing the pumps’ or pump units’ opera­tional limits and hardware:
• Changes to the delivered pump or motor pump unit may only be done with a written approval from Danfoss High Pressure Pumps.
• Operation outside the Danfoss specifications requires a written approval from Danfoss High Pressure Pumps.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
5
Operating guide | APP 1.5-3.5 pumps
2. Safety
1.3 Manufacturer and customer service address
Danfoss A/S
Danfoss High Pressure Pumps
Nordborgvej 81, DK-6430 Nordborg Denmark
Telephone: +45 7488 4024 Fax: +45 7445 3831 Email: highpressurepumps@danfoss.com Homepage: hpp.danfoss.com
2.1 General information
Dangers that can arise from not following the instructions:
When the pump or pump unit is managed by untrained personnel, there is a danger of:
• Death or fatal injuries
• Costly damages and claims
Your local Danfoss pump distributor can be found on our homepage.
Data sheets and instructions on all accessories are available on hpp.danfoss.com
1.4 Country specific information
1.4.1 United Kingdom
UK importer:
Danfoss Ltd. 22 Wycombe End HP9 1NB Beaconsfield United Kingdom
Under certain operational conditions the surface of the pump can be above 60°C / 140°F. Under these conditions the pump must be labelled with a “Danger Hot” sign.
When using an electric motor, the motor must always be supplied with adequate cooling ventilation.
When using an electric motor together with a VFD, the motor must be designed for operation with a VFD.
All electrical installation work must only be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
It is recommended to install a lockable circuit breaker to avoid inadvertent starting and/or electrical hazard. The lockable circuit breaker must be used during installation, operation and maintenance.
It is recommended to place a local safety switch nearby the pump, enabling service personnel to cut power for the electric motor.
Protect the motor and other electrical equip­ment from overloads with suitable equipment.
In case the pump delivered is ATEX certified, the additional ATEX instruction must also be read.
Protective garments
!
must be wor n
Always wear suitable safety clothing when handling the pump.
When working near the pump system, safety shoes, safety glasses, hearing protection and safety helmet must always be worn.
VFD operation may increase the temperature inside the electric motor if the motor is not designed for VFD operation. This can damage the motor and cause unintended breakdown.
Before start-up, the settings for all protective devices, such as sensors/switches and safety valves must be verified and free flow from safety valves must be ensured.
All pipe and hose connections must be stress­free mounted, securely fastened to the pump and well supported. Improper installation will or can result in personal injury and/or damage to the pump.
Use of this manual does not relieve operation and maintenance personnel of the responsibil­ity of applying good judgment when operating and maintaining the pump and its compo­nents.
2.2 Preferred system design
Danfoss recommends to build systems with a high degree of safety. Danfoss preferred system design and P&ID are found in appendix 1, Data sheet, and appendix 2, Instruction.
6
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
It is always the system builder´s responsibility that the system design does not cause any kind of hazard and is adapted to local regulations and standards.
Do not try to lift the pump unit manually; most of the pumps weigh more than 20 kilos, see specific weight for the pump in the appendix 1, Data sheet.
Always bleed the pump prior to initial
Proper installation, proper start up and shut­down devices as well as high-pressure protection equipment is essential.
start-up.
Do not mount the pump without the bell housing and a flexible coupling.
Do not try to start the unit before the system components are mounted, bleeded
2.3 Commissioning and servicing the unit
It is recommended that commissioning and servicing are carried out by a minimum of two people, where one is acting as a supervisor.
and adjusted.
Flush the system throughly before connecting the pump or pump unit.
Check rotation direction of the motor before mounting the pump.
2.4 Adhere to the following important points
2.5 In case of doubt
Please contact Danfoss A/S in case of doubt.
Before using the pump/pump unit it is very important to read and understand this user
Contact information is listed in section 1.3, Manufacturer and customer service address.
manual.
3. Technical data 3.2 Application range
See appendix 1, Data sheet.
3.1 Approved applications and operational limits for the pumps
The pump and the pump units are designed for the use in a Sea Water Reverse Osmosis (SWRO) or Brackish Water Reverse Osmosis (BWRO) systems and Brackish Water Reverse Osmosis (BWRO) system.
The APP pumps must not be used for other purposes than those recommended and specified without first consulting your local pump distributor.
3.3 Electric motor data
See recommended motor in appendix 1, Data sheet or appendix 3, IOM for motors. The motors mentioned are the most common used motors by Danfoss High Pressure Pumps.
3.4 Noise and vibration
Noise level for a pump unit with a ”standard” motor measured according to EN ISO 3744: 2010, see appendix 1, Data sheet. Possibilities to reduce noise and vibration are described in the same Data sheet.
3.5 Dimension drawings
Dimensions of the different pumps can be found in appendix 1, Data sheet.
3.6 Space requirement
When doing service or replacing the complete pump unit, it is recommended to have sufficient space available around the pump in order to ensure easy access. Sufficient space means at least 1 meter/40 inches around the pump. When working with high pressures, it is important to have the right space available around the pump as stated in the safety requirements.
Use of the pump in other applications not suitable for the pump unit can cause damages to the pump unit, with risk of personal injury.
For system integration of the pump, please see appendix 1, Data sheet and appendix 2, Instruction.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
7
Operating guide | APP 1.5-3.5 pumps
3.7 Filtration
(10µm absolute [ß10 ≥ 5000]) Requirements are specified in appendix 1, Data sheet and in appendix 2, Instruction.
Danfoss recommends not to build a filter bypass function or to use filters with an integrated bypass. If the above recommendation is not followed the warranty for the pump will automatically become void.
It should be possible to monitor the condition of the filter via the differential/delta pressure across the filter.
Using insufficient filtration or a filter bypass can cause a failure or decreased service life of the pump.
3.8 Properties of water
It is recommended NOT to use the pumps in feed water concentrations higher than 50,000 ppm TDS without consulting your local Danfoss pump distributor.
3.9 Air bubbles
Large bubbles in a pressurised RO system can result in damage to piping, equipment and the pump.
All air must be bleeded from both the low­pressure and high-pressure side before the RO system is pressurised. Special consideration should be given in order to minimize air bubbles in the feed flow. Air bubbles can cause cavitation.
3.10 Chemicals
The pump should not be exposed to any chemicals as it can result in damage to piping, equipment and internal parts in the pump.
4. Arrival inspection, transportation, handling, lifting and storage
4.1 Arrival inspection
The pump is packed in a cardboard or wood box with plugs in the port connections to protect the pumps from damage during transportation.
When the shipment has arrived it is important to check the pump for any damages. The name plate/type designation must be in accordance with the delivery note and your order.
In case of damage and/or missing parts, a report should be documented and presented to the carrier at once.
4.2 Warning
Before any lifting operation is performed, environmental conditions must be taken into consideration (Ex-rated areas, wind speed, wet/ dry conditions, lifting height, etc.).
4.3 General safety information
Personnel involved in lifting and transporting the equipment (see Safety, chapter 2) must be trained in handling and in safety procedures for lifting heavy loads. Many of the pumps and pump units weigh more than 20 kilos, which requires lifting slings and suitable lifting devices; e.g. an overhead crane or industrial truck to be used as minimum.
4.4 Transport and handling
Small pumps which have a weight below 20 kilos (weight can be found in appendix 1, Data sheet). can be handled by hand if they are not mounted together with an electric motor. The weight of a small pump with a motor will be above 20 kilos.
8
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
Pumps which have a weight above 20 kilos (see appendix 1, Data sheet) must be handled by using lifting eyes and slings.
Wrong lifting:
When the pump is mounted together with an electric motor, the pump unit always weigh more than 20 kilos and must be handled by using slings around the pump unit.
See below examples of where to/not to attach the lifting slings on the pump unit:
Correct lifting with 2 separate slings:
When lifting the pump unit, one sling must be attached to the electric motor and one sling around the pump.
Some motors and pumps have specific lifting eyes.
Do not use connections/nozzles for lifting! Do not use only one sling!
Make sure that the unit/load is balanced before lifting. The centre of the mass varies from pump/ pump unit size to pump/pump unit.
How to mount the pump and the electric motor correctly, see appendix 1, Data sheet or appendix 2, Instruction.
Incorrect lifting can result in personal injury and/or damage to the pump unit, see appendix 2, Instruction.
4.5 Return to supplier
Please see maintenance chapter 7.
4.6 Storage
Each pump is tested before shipment, and will therefore contain water. For storage temperature and frost protection see appendix 2, Instruction.
The pumps are NOT delivered frost protected from the factory.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
9
Operating guide | APP 1.5-3.5 pumps
5. Installation and commissioning
5.1 Important dimensions
Physical dimensions and connections of the pump unit are described in appendix 1, Data sheet.
5.2 Cleanliness
It is very important that the tubes and pipes are completely clean: no dirt, chips or burrs are allowed. Flush all piping before connecting the high-pressure pump to ensure the system is clean. Internal surfaces of the piping must not be corroded. If dirt or rust is not removed, the pump and the valves can be damaged. In worst case the pump can be damaged beyond repair!
5.3 Fluid temperature
Before start-up, the fluid and pump housing temperature must be within the specified temperature range listed see appendix 1, Data sheet.
5.4 Electrical data
Check voltage, current frequency and rated power on the electric motor and VFD settings on the name plate placed on both the motor and the VFD.
5.5 Local regulations
Commissioning must always be done in accordance with valid regulations and local standards.
Schematic 1: Recommended system design
Media filter
Feed
PI
PI
PI PI
Fresh water
permeat flush
PT
M
PI
Brine
Permeate
PI
10
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
5.6 Pre mounting checklist, based on Danfoss preferred system design
Table 1: Check points when assembling and commissioning system
CP1
CP2
CP3
CP4
CP5
CP6
CP7
CP8
CP9
CP10
CP 11
CP12
CP13
Check points Comment OK ?
Ensure that the environmental conditions are safe. See Arrival inspection,
Minimum and maximum start-up temperature for fluid and pump.
Filtration condition (10 µm absolute (ß10 ≥ 5000) See Danfoss requirements in
Power supply for electric motor and VFD. See Data sheet for the used
Safety circuit / breaker must be sized for the motor and environment (corrosion and humidity)
Bolts and screws must conform to environmental conditions as well as fluid and torque requirements.
Instrumentation, pressure switch should be designed to conform to the environment (corrosion and humidity).
Check the factory settings of the safety/relief valves or pressure relief valves (page 11).
Check the settings of the pressure transmitter/switch (3) set at min. inlet pressure (page 11).
Check that all pressure indicators (PI) are selected to be able to measure the system pressure range (page 11).
Check coupling distance ( air gab – movement of the spider ) 3-5 mm
Check correct connections on the pump ( in & outlet)
Check piping for possible air gaps.
transportation, handling, lifting and storage, chapter 4.
See Data sheet or Instruction, appendices 1 and 2.
Data sheet and Instruction, appendices 1 and 2
motor and VFD.
See Data sheet for the used safety circuit.
See Data sheet for the used equipment.
See Data sheets for the used valves.
See Data sheet or Instruction, appendices 1 and 2.
Scaling should at least be 1 bar or more precise.
5.7 Lifting and positioning
Lift the pump unit onto base (Remember vibration dampeners, if needed). Fasten the motor to the base.
See also chapter 4, Arrival inspection, transporta­tion, handling, lifting and storage.
5.8 Mount the different equipment
(connections, pipes, tubes, check and safety/relief valves, etc.)
• The hard piping and flexible hoses used, must be of proper design and must be installed in accordance with the manufactur­er’s recommendations. (see also Data sheet for Hose and hose fittings and Instruction for Assembling Hose kit - both available on www.ro-solutions.danfoss.com).
• Misalignment of the hard pipes may give unintended stress on the pump port connections and may damage the pump.
• Prevent excessive external pipe load.
• Do not connect piping by applying external force (use of wrenches, crane, etc.) Piping must be aligned without residual stress.
• Do not mount expansion joints so that their force applies internal pressure on the pump connections.
5.9 Electrics
All electrical installation work must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations (see also Safety, chapter 2).
Turn off the safety circuit breaker and lock it.
Mount the power cable on the electric motor.
If a VFD is used, adjust the protective motor switch/VFD to the current limits found on the name plate of the electric motor.
5.10 Instrumentation
The pressure switch/sensor should be mounted as close to the pump as possible. It is recom­mended to test the pressure/sensor switch via an instrumentation manifold.
Mount the pressure switch/sensors according to the manufacturer’s instructions.
5.11 Connections
Mount and tighten connections and check valve(s) as specified.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
11
Operating guide | APP 1.5-3.5 pumps
5.12 Ensure free flow
Ensure free flow from the safety/relief valves 8 and 9 (schematic 1, page 11). A blocked safety/ relief valve can cause excessive build-up of pressure and thereby cause dangerous situations and damage to the whole system.
5.13 Verify setting of safety/relief valves
Make sure, the safety/relief valves 8 and 9 are placed correctly.
Check the pressure settings on the name plates of the safety/relief valves. If they are within specifications, you can continue.
5.14 Flush the pump
Fully open the pressure valve at the brine outlet.
Close all the bleeding and draining plugs on the high-pressure pump.
Start the feed pump and ensure free flow to the high-pressure pump.
5.15 Bleed and remove air from the pump
Open the bleeding plugs. Keep the plugs open until the high-pressure pump is bleeded.
5.17 Commissioning
Close all the bleeding and draining plugs.
Open the pressure valve at the brine site.
Switch the safety circuit breaker on for both motor(s) and VFD(s).
Start the feed pump.
Start the high-pressure pump.
If a VFD or a soft starter is used, a ramp up time of minimum 10 seconds is required to avoid damage of the pump.
Monitor the inlet and outlet pressure of the high-pressure pump and look for leakages.
Check the function of the pressure indicators by slowly closing the valves. The pump unit should stop when the minimum inlet pressure and maximum outlet pressure has been reached.
Adjust the pressures to the specified inlet and outlet pressure for the system and let the pump unit run until the electric motor and pump temperature is stable.
If the system is running within the system design limits, the system is released for operation.
5.18 Check the filter condition
Evaluate contamination found in filter, replace filter elements, if necessary.
5.16 Verify direction of rotation
The direction of rotation must always follow the arrow. The arrow is placed on the pump or pump unit.
Check the direction of rotation before mounting the pump.
Unlock the safety circuit breaker. Start the motor for 1 second and observe the direction of rotation either looking at the fan of the motor or the coupling through the inspection hole in the bell housings (not available on all bell housings). If the motor is turning the wrong direction, switch two phases in the connection box of the motor or reprogram the direction in VFD.
When the motor is turning in the right direction, the pump can be mounted.
5.19 Instruct operator and maintenance personnel
Before using the pump/pump unit, the personnel must be instructed in using the pump/pump unit, its function, components, documentation and safety.
Danfoss offers commissioning and service at system manufacturer’s location. Rate quotes are offered upon request.
12
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
6. Operation of pump unit
6.1 General safety information
Before inspecting the pump unit, read the Safety chapter 2 in this user manual.
6.2 What to listen and look for
If one or more of the following examples are observed, please act as indicated:
A) Loose bolts – check all bolts and, if
necessary, contact the maintenance department in order to have all bolts tightened to the specified torque(s).
B) Leakage – if a small leakage from the bell
housing is observed. Contact the mainte­nance department.
C) Leakage – if there is a large leak, the unit
should be stopped immediately. Contact the maintenance department.
D) High frequency tones – safety/relief valves
are either damaged or running very close to their design pressure, stop the unit immediately. Contact the maintenance department.
E) Increased noise or vibration – requires the
unit to be stopped immediately. Contact the maintenance department.
F) Very high temperatures – may indicate that
one or more parts are damaged inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
G) Drop in flow and/or pressure – may indicate
wear on one or more parts inside the pump. The pump must be stopped immediately and inspected before it is restarted. Contact the maintenance department.
H) Other observations or troubles, please see
appendix 7, Right and Wrong or appendix 6, the Trouble shooting guide. Both appendices give good advises regarding design, installation, wiring and troubleshooting. See also service and warranty section in appendix 1, Data sheet and appendix 2, Instruction.
If the pump is not stopped for inspection as recommended, it can lead to damage of the pump or break-down. See also service and warranty section in the appendix 1, Data sheet, in appendix 2, Instruction or appendix 4, Instruction for recommended service intervals.
Danfoss offers service of the pump at the system manufacturer’s location as well as we offer training in how to service the pump. Quotes are offered upon request.
Danfoss recommends simultaneously to check the filter and membrane condition and to evaluate contamination; filter and membrane elements must be replaced if necessary.
7. Maintenance and service of the pump unit 7.1 General safety information
Before servicing the pump unit, it is necessary to read and understand this user manual, especially the Safety, chapter 2. Remember to wear suitable safety equipment according to Safety, chapter 2.
7.2 Service and inspection interval for the pump
Maintenance and service intervals are depending on the cleanliness level of the water, hydraulic load and temperature of the pump unit. The most important parameter is the filtration of the water.
See the section Service and warranty in the appendix 1, Data sheet, in appendix 2, Instruc­tion and appendix 4, Instruction for recom­mended service intervals.
For spare parts and service tools, please see appendix 3, Parts list.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Danfoss offers service of the pump at the system manufacturer’s location and training in how to service the pump. Quotes are offered upon request.
7.3 Shut down of the system
A) Open the pressure valves at the brine site
to release the pressure.
B) Stop the high-pressure pump.
C) Stop the feed pump.
D) Switch off the safety circuit breaker for
both the high-pressure pump, feed pump and VFD and lock them. Only personnel servicing the pump unit should be able to unlock/activate the switch again.
E) Open bleeding and drain plugs. Wait until
the pump and system are emptied for water.
13
Operating guide | APP 1.5-3.5 pumps
F) Slowly unscrew and remove the bolts and
gaskets from the inlet/outlet hoses or pipes, be careful about jets of water. Beware that the system can be pressurized!
G) Attach the lifting equipment to the pump
unit. For instructions on lifting the complete pump unit, see chapter 4, Arrival inspection, transportation, handling, lifting and storage.
H) For the small pumps, unscrew the bolts
holding the pump to the bell housing. For the bigger pumps, unscrew the bolts/nuts from the pump and bell housing to the motor. Afterwards unscrew the bolts/nuts holding the pump and bell housing.
I) Carefully pull the pump out of the bell
housing by using lifting equipment, if necessary.
J) Hold the pump in different positions above
a drip tray; this should allow most of the water trapped in the pump to drain. Clean and dry the pump surface and plug the bleeding and draining plugs.
K) Move the pump to a clean and safe location
where the pump can be inspected/ serviced.
7.4 Disassembling and assembling the pump unit
A) Remove all connections from the pump.
B) Disassemble the pump according to the
Disassembling and Assembling Instruction (available at www.ro-solutions.danfoss.com)
Clean all parts and surfaces with a fluid
compatible with the materials found in the pump. Wipe the parts clean and dry with a lint-free clothing.
Returns without a return number will be
rejected !!!
7.5 Assembling the pump unit
Assemble the pump according to the Dis­assembling and Assembling Instruction (available at www.ro-solutions.danfoss.com).
7.6 Procedure for mounting the pump onto the electric motor
Mount the flexible coupling and bell housing according to appendix 2, Instruction.
7.7 Getting the pump unit back into operation
Find instructions of how to put the pump unit back into operation in chapter 4, Arrival inspec­tion, transportation, handling, lifting and storage and Installation and commissioning, chapter 5.
7.8 Storage of the pump
If the pump has to be shut down for a longer period, instructions can be found in appendix 2, Instruction.
C) Inspect all parts including shaft seal and if
necessary, replace them; see appendix 3, Parts list.
D) If the pump is going to be returned to
Danfoss for repair or a warranty claim, it is important to contact Danfoss in order to receive a return number and a form to fill out with product information. A copy of the form together with contact information and reason for returning should be sent to the email address on the form. The same documents should be attached to the shipment.
14
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide | APP 1.5-3.5 pumps
8. Troubleshooting and scrapping criteria
8.1 General safety information
Before inspecting the pump unit, it is necessary to read and understand this user manual, especially the Safety chapter 2.
Remember to wear suitable safety equipment according to Safety chapter 2.
8.2 Operational conditions which can cause pump failures
The following conditions can cause a pump failure :
If water is leaking into the electric motor; it can cause electric shock, fire, short circuit or even death. When mounting the pump vertically always mount the motor above the pump to avoid water leaking into the electric motor.
8.4 Electrical failure
If the wiring of the electric motor is incorrect or the ground connection is missing, it can cause electric shock, burn damages, fire or even death.
The pump is running dry.
The inlet pressure is too high.
The inlet pressure is too low.
The temperature of the fluid is too high.
The ambient temperature is too high.
The pump is running against a blocked port/closed manual valve.
The pump is operating at a pressure out of specification.
The pump is running with a non-specified/ approved fluid.
The pump is running in the wrong direction.
The filtration is insufficient.
The pump is not being serviced according to Danfoss specifications (end of life).
There is excessive mechanical load on the shaft coupling and piping.
8.3 Mechanical failure
If the pump is running dry, the temperature will quickly increase which can cause burns.
If there is any leakage at start-up or during operation, a high-pressure jet can cause eye or skin damage.
Leakage can result in flooding, which can cause slipping, tripping or falling.
If a VFD is used and wrongly programmed, it can damage the pump and lead to high tempera­tures or other dangers.
All electrical installation must be carried out by authorized personnel in accordance with EN60204-1 and/or local regulations.
8.5 Responsibility
Danfoss takes no responsibility for any abnormal injuries, risks or damages that could arise caused by abnormal conditions, vibrations, corrosion, abrasives, foreign objects or excessive tempera­tures and shall not be liable for any consequen­tial or incidental damages.
8.6 Scrapping criteria
Whether the pump can be repaired or need to be scrapped, depends on in which conditions the internal parts are, or how damaged the whole unit is. Please use appendix 6, Trouble shooting guide as guideline or send the pump to Danfoss headquarter in Denmark for evaluation.
For other observations or troubles, please see appendix 7, Right and Wrong which gives good advises regarding design, installation, wiring and troubleshooting.
In case the pump needs to be scrapped, please follow your local environmental rules.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
15
User manual Installation, Operation and Maintenance APP Pumps (APP 1.5-3.5)
Danfoss A/S
High Pressure Pumps DK-6430 Nordborg Denmark
Danfoss ca n accept no respons ibility for pos sible errors in ca talogues, bro chures and other pr inted material. Da nfoss reserve s the right to alter its p roducts with out notice. This also a pplies to produc ts already on ord er provided that su ch alterations ca n be made without su bsequential cha nges being nece ssary in speci fications alread y agreed. All trade marks in this mate rial are proper ty of the respec tive companies . Danfoss and the Danf oss logotyp e are trademark s of Danfoss A/S. Al l rights reserv ed.
16
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Operating guide
Appendices APP 1.5 - 3.5 Installation, Operation and Maintenance Manual
hpp.danfoss.com
Operating guide | APP 1.5-3.5 pumps
Table of Contents
Contents
Appendices ......................................................................................17
1. Data sheet for APP 1.5-3.5 (AI274333290009en-000701) .................................19
2. Pump instruction APP 1.5-3.5 (180R9065) ...............................................33
3. IOM Electric motors (180R9230)..........................................................41
4. Recommended service intervals for APP pumps (AX290239527130en-000201)...........47
5. Parts list for APP 1.5-3.5 (AX274346749037en-000501)...................................51
6. Trouble shooting guide for APP, APP S and APP S 674 pumps ............................61
7. Right and wrong (180R9042) ...........................................................73
18
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Data sheet
Data sheet
APP Pumps APP 0.6-1.0 / APP 1.5-3.5 /
APP pumps
APP (W) 5.1-10.2 / APP 11-13 /
APP 0.6-1.0 / APP 1.5-3.5 / APP (W) 5.1-10.2 /
APP 16-22 / APP 21-46
APP 11-13 / APP 16-22 / APP 21-43
hpp.danfoss.com.
ro-solutions.com
Data sheet | APP 0.6-46 / APP (W) 5.1-10.2 pumps
Table of Contents
1. Introduction ...........................................................................21
2. Benefits................................................................................21
3. Application examples ..................................................................21
4 Technical data .........................................................................22
4.2 APP 1.5-3.5.............................................................................22
5. Flow at different rpm...................................................................23
5.2 APP 1.5-3.5 flow curves at 80 barg (1160 psig) ...........................................23
6 Flushing valve curves ..................................................................24
6.2 APP 1.5–3.5 integrated flushing valve ...................................................24
7. Motor requirements....................................................................25
7.2 Calculation factor for APP 1.5-3.5 .......................................................25
8. Temperature and corrosion.............................................................26
8.1 Temperature...........................................................................26
9. Installation.............................................................................26
9.1 Filtration...............................................................................27
9.2 RO system with direct supply: ..........................................................27
10. Dimensions and connections...........................................................29
10.2 APP 1.5-3.5.............................................................................29
11. Dimensions with motor unit ............................................................30
11.1 APP 0.6-3.5.............................................................................30
13. Ser vice.................................................................................31
20
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Data sheet | APP 0.6-46 / APP (W) 5.1-10.2 pumps
1. Introduction
This data sheet is valid for APP pumps both non ATEX and ATEX certified. ATEX certified pumps are indicated by Ex in the type designation ­example APP 0.6 Ex.
The Danfoss range of APP high-pressure pumps is designed according to EN 809 for use in RO applications with low viscosity and corrosive fluids such as:
Sea water
Brackish water
Waste water (APP W)
1: Shaft sealing 2: Port flange 3: Bleeding plug 4: Retainer plate 5: Piston/shoe 6: Valve plate 7: Swash plate 8: Cylinder barrel 9: Springs 10: Port plate 11: Flushing valve (not available on APP 5.1-10.2) 12: Housing 13: Tail stock screws 14: Drain plug
Danfoss APP pumps are positive displacement pumps with axial pistons that move a fixed amount of water in each cycle. Flow is propor­tional to the number of input shaft revolutions (rpm). Unlike centrifugal pumps, they produce the same flow at a given speed no matter what the discharge pressure.
Below sectional drawing is an example of an APP pump. The sectional drawing for the specific pump sizes are to be found in the pump instruction.
2. Benefits
Zero risk of lubricant contamination:
- Oil lubricants are replaced with the pumped medium, water, so there is no contamination risk from the pump.
Low maintenance costs:
- Efficient design and all-stainless steel
construction ensure exceptionally long life. When Danfoss specifications are met, service intervals of 8,000 hours can be expected. Service is easy, and can be carried out on-site due to the simple design and few parts.
Low energy costs:
- The highly efficient axial piston design provides the lowest energy consumption of any comparable pump on the market.
Easy installation:
- The most compact and lightest design
available.
- The pump can be installed vertically
and horizontally.
- No pulsation dampeners necessary due
to extremely low pressure pulsation.
3. Application examples Danfoss APP pumps are built into a broad range of RO desalination plants around the world:
Containerized solutions for hotels, resorts
and residences on islands and in coastal regions
- Powered directly by electric motors or combustion engines (with special coupling).
- All pumps except APP (W) 5.1 - 10.2 are supplied with an integrated flushing valve that allows the fluid to flow from inlet to the outlet, when the pump is not running.
High reliability:
- All parts are made of high corrosion resistant materials e.g. Duplex (EN1.4462/ UNS S31803) and Super Duplex (EN1.4410/UNS S32750) stainless steel and carbon reinforced PEEK.
Certified quality:
- Pumps available as ATEX certified.
- For other certifications, please see data sheets for APP S (all super duplex) and APP S 674 (API).
- Positive Material Identification (PMI) report available on request.
- IATF 16949, ISO 9001, ISO 14001.
Mobile systems for humanitarian and military organizations
Onboard systems for ships and yachts
Offshore platforms for the oil and gas industry
Municipal and regional waterworks
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
21
Data sheet | APP 0.6-46 / APP (W) 5.1-10.2 pumps
4 Technical data
4.2 APP 1.5-3.5
Pump size APP 1.5 APP 1.8 APP 2.2 APP 2.5 APP 3.0 APP 3.5
Code number APP 180B30 43 180B3044 180B3045 180B30 46 180B3030 180B3032
Code number APP ATEX4)180 B3143 180B3144 180B3145 180B3146 18 0B3130 18 0B3132
Geometric displacement
cm³/rev.
in³/rev.
Pressure
Max. outlet pressure continuous
Min. outlet pressure
Inlet pressure continuous
Max. inlet pressure peak
1)
barg 83 83 83 83 83 83
psig 120 0 1200 12 00 12 00 120 0 120 0
1)
barg 20 20 20 20 20 20
psig 290 290 290 290 290 290
barg 0.5 - 5
psig 7.3 - 72.5
barg 10 10 10 10 10 10
psig 145 145 145 145 145 145
Speed
Min. speed continuous
Max. speed continuous
rpm 700 700 700 700 700 700
rpm 3450
Typical flow - Flow curves available in item 5
1000 rpm at max. pressure
1500 rpm at max. pressure
1200 rpm at max. pressure
1800 rpm at max. pressure
m³/h 0.53 0.57 0.73 0.90 1.02 1.19
m³/h 0.79 0.86 1.09 1.34 1.54 1.79
gpm 2.80 3.03 3.83 4.73 5.41 6.30
gpm 4.19 4.55 5.75 7. 09 8.12 9.46
Technical specifications
Media 3) temperature
Ambient temperature
Weight (dry)
Sound pressure level
Footprint with IEC motor
°C 2 - 50 2 - 50 2 - 50 2 - 50 2 - 50 2 - 50
°F 36 - 122 36 - 122 36 - 122 36 - 122 36 - 122 36 - 122
°C 0 - 50 0 - 50 0 - 50 0 - 50 0 - 50 0 - 50
°F 32 - 122 32 - 122 32 - 122 32 - 122 32 - 122 32 - 122
kg 8.6 8.6 8.6 8.6 8.6 8.6
lb 17 17 17 17 17 17
dB(A) 77 77 77 81 81 81
5)
0.15 0.16 0.21 0. 21 0.30 0.30
6)
foot² 1.61 1.72 2.26 2.26 3.23 3.23
Typical motor size
Max. speed at max. pressure
3000 rpm at max. pressure
Torque at max. outlet pressure
kW 5.5 5.5 7.5 7. 5 11 11
HP 7.5 7.5 10.0 15 .0 15. 0 15.0
Nm 13.0 13.9 17. 4 21.3 24.5 28.7
lbf-ft 9.6 10.3 12 .8 15.7 18.1 21.2
9.31 10.0 4 12.52 15.35 17.70 20.54
0.57 0.61 0.76 0.94 1.08 1.25
2)
2)
7.3 - 72.5 2)7.3 - 72.5
2)
0.5 - 5
3450
2)
2)
0.5 - 5
3450
2)
2)
2)
0.5 - 5 0.5 - 5
7.3 - 72.5 7.3 - 72.5
3000 3450
2)
2)
2)
7.3 - 72.5
0.5 - 5
3000
22
1)
For lower an d higher pressure , please contact D anfoss.
2)
For spee ds above 3000 rpm t he pump must be boo sted at a pressure
of 2-5 barg (29 - 72.5 psig).
3)
Depend ent on the NaCI conce ntration - see chap ter 8.
4)
Category 2, Zone 1 or Category 3, Zone 2.
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
5)
A-weigh ted sound pressur e level at 1 m from the pum p unit surfa ces (reference box) a cc. to EN ISO 20361 section 6 .2. The noise measurem ents are perf ormed acc. to EN ISO 3744:2010 on a mot or- pump unit a t max. pressure an d speed.
6)
Max. area covered with recommended motor configuration (excl. of spa ce to service pump)
Data sheet | APP 0.6-46 / APP (W) 5.1-10.2 pumps
APP 1.5
APP 1.8
APP 2.2
APP 2.5
APP 3.0
APP 3.5
rpm
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0
0.5
1300
1500
1100
1900
2100
1700
2500
2700
2300
3100
3300
3450
2900
900
700
m3/h
5. Flow at different rpm
If the flow required and the rotation speed (rpm) of the pump is known, it is easy to select the pump fitting the application best by using the diagrams below.
5.2 APP 1.5-3.5 flow curves at 80 barg (1160 psig)
m3/h
4.5
4.0
3.5
3.0
2.5
2.0
1.5
Furthermore, these diagrams shows that the flow can be changed by changing the rotation speed of the pump. The flow/rpm ratio is constant, and the “required” flow can be obtained by changing the rotation speed to a corresponding value. Thus, the required rpm can be determined as:
Required flow x Rated rpm
Required rpm = Rated flow
APP 3.5
APP 2.5
APP 3.0
APP 2.2
APP 1.8 APP 1.5
1.0
0.5
3450
3450
rpm
APP 3.0
APP 2.2
APP 1.8 APP 1.5
rpm
0
700
900
1100
1300
gpm
1100
1300
18.0
16.0
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0
700
900
1500
1500
1700
1700
1900
1900
2100
2100
2300
2300
2500
2500
2700
2700
2900
2900
3100
APP 3.5
APP 2.5
3100
3300
3300
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
23
Data sheet | APP 0.6-46 / APP (W) 5.1-10.2 pumps
Pressure [barg]
ow [l/min]
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
10
12
14
16
18
6 Flushing valve curves
All pumps except APP (W) 5.1 - 10.2 are supplied with an integrated flushing valve that allows the fluid to flow from inlet to the outlet, when the pump is not running.
6.2 APP 1.5–3.5 integrated flushing valve
0
0
2
4
6
8
Fl
24
180R9267 | AQ291128576527en-000901 IOM APP 1.5-3.5 Pumps | 12.2021
Loading...
+ 56 hidden pages