Actuators for three point control AMV 85, AMV 86
Description
The actuators AMV 85 and AMV 86 are used with VFM 2 (DN 150-250), VFS 2 (DN 65-100), VF2/3 (DN 125, 150) and AFQM (DN150-250) valves.
Features:
• “Self stroking” function
• Load related “Switch o“ function that prevents overloading
• Manual operation
• Diagnostic LED
Main data:
• Nominal voltage:
- 24 VAC, 230 VAC, 50 Hz/60 Hz
• Control input signal: 3-point
• Force: 5000 N
• Stroke: 40 mm
• Speed: 8 s/mm (AMV 85), 3 s/mm (AMV 86)
• Max. medium temperature: 200 °C
• Manual operation
Ordering Accessories
Actuator
Typ e
AMV 85
AMV 86
Power supply
(V~)
24
230 08 2G1451
24
230 082G14 61
Speed
(s/mm)
8
3
Code No.
08 2G1450
08 2G1460
Typ e for actuators Code No.
Additional switches (2×)
Additional switches (2×) and potentiometer (10 kΩ)
Stem heater 065Z7021
AMV 86/3/24 082H7050
AMV 85/8/24 082H7072
AMV 85/8/230 082H7071
AMV 86/3/24 082H7081
AMV 86/3/230 082H7080
AMV 85/8/24 082H7083
AMV 85/8/230 082H7082
Technical data
DEN-SMT/SI
Typ e AMV 85 AMV 86
Power supply V~ 24 AC, 230 AC ; +10 to –15%
Power consumption VA 10.5 23
Frequency Hz 50 / 60
Control input 3-point
Cl force N 5000
Max. stroke mm 40
Speed s/mm 8 3
Max. medium temperature
Ambient temperature 0 55
Storage and transport temperature –40 +7 0
Protection Class I (230 V); III (24 V)
Grade of enclosure IP 54
Weight kg 9.80 10.0
- marking in accordance with the standards
VD.AB.S5.02 © Danfoss 09/2015
°C
Low Voltage Directive 73/23/EEC and 93/68/EEC, EN 60730/2/14
EMC Directive 89/336/EEC, 92/31/EEC, 93/68/EEC, EN 50081-1 and EN 5008 2-1
200
1
Data sheet Actuators for three point control AMV 85, AMV 86
Installation
Disposal The actuator must be dismantled and the
elements sorted into various material groups before disposal.
Mechanical
The actuator should be mounted with the valve stem in either horizontal position or pointing upwards. Use the 57 mm castellated nut (supplied) to t the actuator to the valve body. While the actuator is being tted, a 8 mm Allen key can be used to tighten the pinch screw in the valve body ring to stop the valve turning.
Allow for necessary clearance for maintenance purposes.
Electrical
Electrical connections can be accessed by removing the cover. Two M16 x 1.5 cable entries are provided. Both entries are provided with a rubber grommet for use with exible cable. Note that in order to maintain the enclosure IP rating, appropriate cable glands must be used.
Wiring
230 VAC version:
Do not touch anything on the PCB! Do not remove the cover before the power supply is fully switched o.
Accessories
24 V, 230VAC, 50/60 Hz
1 0 V Neutral
2
24 VAC
230 VAC
3
4
5
2
4
3
5
Input power
supply
Output
Additional switches (2x) Additional switches (2x) and potentiometer