Danfoss 013G8070 Installation guide

Instructions
013G8070
RA to RA2000 Operator Adapter
RA to RA 2000:
In order to use current RA 2000 operators on existing systems with Danfoss RA valves, the adapter 013G8070 must be installed to allow the new operator to fit onto the valve. The older Danfoss RA valve is distinguished by the large silver threaded nut that connects the operator to the valve.
There are two versions of RA operators:
a) Operator mounts directly on valve with remote bulb/sensor (not shown) b) Separate remote mounted operator and remote bulb/sensor (shown at left)
Crossover Replacement Operator Guide: RA to RA2000
013-7001: RA-6 013-7101: RA-6 (armored)
013-70 02: RA-33 013-70 03: RA-36 013-70 04: RA-66
Installation:
= +
013G 8070:
Adapter
= +
013G 8070:
Adapter &
included grey
spring
with remote sensor
013G 856 4: Dual 6 ft. capillary,
wall mounted dial with remote
sensor
1) Remove the existing RA operator (RA-33 shown) from the valve by turning nut counter clockwise. Although the valve should backseat, for safety, the system should be off.
2) Remove any existing gasket material from the face of the threads.
013G2922: Tamper resistant valve mounted dial
with remote sensor
Alternative option
013G8562, 013G8565, 013G8568: Single 6, 16,
or 26 ft. capillary, wall mounted dial with sensor
VIUHA322
3) Assemble the adapter (with included gasket) to the valve as shown in the diagram. The gasket should be placed between the valve and the adapter. Tighten the nut sufficiently to prevent leakage.
© Danfoss | 09.2019 | 1
013G8070 RA to RA2000 Operator Adapter
Installation Continued:
Valve Mounted Operators:
Installation - Wall Mount Operator:
013G 8252
Align the base of the RA2000 operator with the notches on the adapter. Press firmly until an audible “click” is heard.
013G2922
For tamper resistant operators the Allen screw on the operator must be tightened to secure to the valve.
Mounted operators 013G8564, 013G8562, 013G8565 and 013G8568 are factory configured for use with an RA 2000 valve. Included with the 013G8070 adapter kit is a loose grey spring that is required in the combination of these thermostatic operators and the RA adapter kit.
Installation of Grey Spring in Socket Body:
1) RA2000 Socket Body, 013G8564/ 013G8562/
Allen Screw
013G8565/ 013G8568 Remove bellows holder from RA 2000 socket body (Socket base has an Allen screw) by pushing the top in and turning counter clockwise.
2) With a screwdriver and pushing from the opposite side of the bellows holder, remove the spring from the RA2000 socket body. The removed black spring can be discarded.
Installation Instructions:
3) Replace the removed black spring with the
provided grey spring within the adapter kit by inserting it within the socket body. (The grey spring
Included grey spring
is stiffer than the one removed.)
4) Properly align the plastic holder to the socket body and with the screwdriver push in the plastic holder.
5) Reinstall the bellows holder by pushing all the way down and turning clockwise.
6) Fully seat the RA2000 socket body onto the RA adapter and tighten the socket body to the adapter with the Allen screw.