Danfoss 013G0372, 013G0373 Data sheet

4 (1)

Data Sheet

Integrated Presetting Valves

-type 013G0372 for normal volume flows

-type 013G0373 for small volume flows

Application

Ordering and

Technical Data

Integrated valves, type RA-N (013G0372) and RAU (013G0373), with built-in presetting are designed for incorporation into valve radiators from different radiator manufacturers.

The two valve types can be recognised by the colour of the presetting ring:

Red: RA-N

Yellow: RA-U

Integrated valves can be used in single and two pipe installations with circulating pump.

The gland seal of the valve can be replaced while the system is in operation.

To avoid calcification and corrosion, it is important for the composition of the circulating water to comply with the VDI 2035 guidelines.

Danfoss thermostatic sensors types RA 2000 and RAW with patented snap socket as well as Danfoss thermo-hydraulic actuators can be installed directly onto the integratred valve.

Approved to EN 215

Integrated presetting valves type RA-N 013G0372 and type RA-U 013G0373 are manufactured to the highest standards, and are approved to the European standard EN 215.

Connec-

 

 

 

 

Pre-setting

 

 

 

Max.

Diff. press.3)

Test

Work

 

 

 

 

 

 

 

 

 

 

 

water

 

 

 

 

 

 

kv-value1) 2)

 

 

 

kvs

 

 

 

tion

 

 

 

 

 

 

temp.

Rec.

Tech.

press.

press.

Code no.

thread

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

 

4

5

6

7

N

N

°C

bar

bar

bar

bar

 

 

 

 

G½A

0.14

0.21

0.26

 

0.32

0.46

0.59

0.73

0.87

1.05

120

0.05-

0.6

16

10

013G0372

 

 

 

 

 

 

 

 

 

 

 

 

G½A

0.04

0.05

0.07

 

0.09

0.13

0.18

0.24

0.34

0.55

0.2

013G0373

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Spare Parts and

Accessories

1)kv-values indicate the flow volume (Q) in m3/h at a pressure loss (Δp) across the valve of 1 bar. Kv = Q:√p. At setting N, the kv-value in accordance with EN 215 can be stated as Xp = 2 K. At lower preset values, Xp will be reduced until approximately Xp 0.5 at presetting 1. The table shows the average measured values for integrated valves with radiator. The kvs-values indicate the valve capacity, when the valve is fully open.

2)When using a liquid filled radiator thermostat e.g. RAW, RAS-D or remote setting element type RA5060 Xp will be increased by factor 1.6 (at setting “N”, ref. EN 215).

3)The technical differential pressure indicates the upper limit for a proper valve function. In most two-pipe systems the recommended differential pressure is sufficient. In order to achieve a noiseless function we recommend in smaller systems to apply automatic bypass valves or automatic balancing valves. If pump differential pressure exceeds the recommended max. valve differential pressure it is recommended that an automatic balancing valve type ASV-P/PV is added to the system.

Product

Code no.

 

 

Gland seal*, 10 pcs.

013G0290

 

 

Red protection cap for RA-N valve 013G0372

013G0951

 

 

Yellow protection cap for RA-U valve 013G0373

013G0952

 

 

Small O-ring

633B1427

 

 

Big O-ring

633B0387

 

 

* The gland seal of the valve can be replaced under pressure, i.e. while the installation is in operation.

VDVEB402

© Danfoss

11/2013

1

Danfoss 013G0372, 013G0373 Data sheet

Data Sheet

Integrated Presetting Valves for normal and small volume flows

Design and Dimensions

 

The dimensions stated may vary according to different radiator manufacturers (013M5058 E0002 001 047 97.03.25)

Materials

Part

013G0372

013G0373

 

 

 

Valve housing

Ms 58

Ms 58

 

 

 

Valve seat

PPS

Ms 58

 

 

 

Throttle nozzle

PPS

PPS

 

 

 

Setting dial

Plastic

Plastic

 

 

 

O-rings

NBR / EPDM

NBR / EPDM

 

 

 

Valve spindle

PPS

Ms 58

 

 

 

Valve cone

NBR

NBR

 

 

 

Pressure pin and valve spring

Chrome steel

Chrome steel

 

 

 

Pre-setting

1

1. Reference mark.

The presetting values of the integrated valves can be adjusted easily and accurately without the use of tools (factory setting: ‘N’):

Remove the protective cap or the thermostatic sensor.

Find the reference mark.

Turn the setting ring until the desired presetting aligns with the reference mark.

The presetting is controlled directly without use of equipment. After installation in the radiator, the reference mark of the valves will not always be positioned in the same place.

Presetting can be selected infinitely variably within the range of 1 to 7. At setting ‘N’ the valve

2

3

1

2.Presetting range.

3.Factory setting and one-pipe system.

is fully open. Setting in the shaded areas of the drawing should be avoided.

In a one-pipe installation, the setting ‘N’ must be used.

Setting ‘N’ can be used as a flushing position if the system has to be flushed out because of dirt problems.

When the radiator thermostat has been installed, the presetting is protected against unintended regulation.

For Danfoss elements RA 2000 and RAW, a theft protection device is available; this also provides added security against unwanted adjustment of the preset values.

2

VDVEB402

© Danfoss

11/2013

Loading...