All rights reserved. While every precaution has been taken in the preparation of this manual,
the publisher assumes no responsibility for errors or omissions. No part of this book covered
by the copyrights hereon may be reproduced or copied in any form or by any means – graphic,
electronic, or mechanical, including photocopying, taping, or information storage and retrieval
systems – without written permission of the publisher.
®
is a trademark of Daktronics, Inc.
Galaxy
All others are trademarks of their respective companies.
Figure 42: Displays with No External Temperature Sensor..........................................................4-12
Figure 43: Displays with External Temperature Sensor................................................................4-13
Figure 44: Locations of Quick Connect Boards...........................................................................4-13
iv
List of Figures
Section 1: Introduction
This manual explains the installation, maintenance and troubleshooting of the 34mm AF-3165
RGB Galaxy
®
display. For questions regarding the safety, installation, operation or service of
this system, please refer to the telephone numbers listed on the cover page of this manual.
The manual is divided into seven sections: Introduction, Mechanical Installation, Electrical
Installation, Maintenance and Troubleshooting, Appendix A, Appendix B, and Appendix C.
• Introduction covers the basic information needed to make the most of the rest of
this manual. Take time to read the entire introduction as it defines terms and explains
concepts used throughout the manual
• Mechanical Installation provides general gu i dance o n di splay mounting
• Electrical Installation gives general guidance on terminating power and signal
cable at the display
• Maintenance and Troubleshooting addresses such things as removing basic display
components, troubleshooting the display, performing general maintenance and
exchanging display components
• Appendix A lists the drawings referenced within this manual
• Appendix B includes information on the signal converter
• Appendix C includes information about the optional temperature sensor
Daktronics identifies manuals by an ED number located on the cover page of each manual.
For example, this manual would be referred to as ED13797.
Listed below are a number of drawing types commonly used by Daktronics, along with the
information that each is likely to provide. This manual might not contain all these drawings.
• System Riser Diagrams: Overall system layout from control computer to display,
power and phase requirements
• Shop Drawings: Fan locations, mounting information, power and signal entrance
points and access method (front and rear)
• Schematics: Power and signal wiring for various components
• Component Placement Diagrams: Locations of critical internal display
components such as power supply assemblies, controller boards, thermostats and
light detectors
Figure 1 illustrates a Daktronics drawing label. The drawing number is located in the lower-
right corner of the drawing. Listing the last set of digits and the letter preceding them
identifies drawings in the manual. In the example below, the drawing would be referred to as
Drawing A-69945. Reference drawings are inserted in Appendix A.
Introduction
Figure 1: Drawing Label
1-1
All references to drawing numbers, appendices, figures, or other manuals are presented in
bold typeface, as shown below.
“Refer to Drawing A-69945 in Appendix A for the power supply location.”
Additionally, drawings referenced in a particular section are listed at the beginning of that
section as seen in the following example:
Daktronics builds displays for long life and that require little maintenance. However, from
time to time, certain display components will need replacing. The Replacement Parts List in
Section 4.11 provides the names and numbers of components that may need to be ordered
during the life of the display. Most display components have a white label that lists the part
number. The component’s part number is in the following format: 0P-_ _ _ _-_ _ _ _ (circuit
board) or 0A-_ _ _ _-_ _ _ _ multi-com ponent assembly).
Following the Replacement Parts List is the Daktronics Exchange and Repair and Return Programs in Section 4.12. Refer to these instructions if any display component needs
replacement or repair.
1.1 Safety Precautions
Important Safeguards:
1. Read and understand these instructions before installing.
2. Be sure the display and enclosures are properly grounded with an earth ground electrode at the display.
3. Disconnect power when servicing the display.
4. Do not modify the display structure or attach any panels or coverings to the display without the written consent of Daktronics, Inc.
1-2
Introduction
1.2 Network Concepts
The concept of using LED displays as a cost effective, high impact method of
communication is rapidly growing throughout many industries and businesses. The
reasons for this growth are many, but the need for additional features and complexity
of multiple display installations has emerged, and Daktronics display systems have
been designed to meet those needs.
The common thread to most client requests is a means of programming and
co
ntrolling a group of displays from a central control point. Daktronics responded by
developing a powerful system of interconnecting and controlling displays. Great care
has been taken to design products that will satisfy a wide variety of installations.
Some of the design goals of these systems include the following:
• Easy transfer of messages
• The ability to tell a display or group of displays in the network which
message should run
• The ability to determine the status of any display on the network
• The ability to control multiple display technologies on the same network
There are five (5) network systems available: RS232, RS422, modem, fiber, and
r
adio. Up to 240 displays can exist on one network.
RS232 Network
RS232 (EIA/TIA-232-E) is a standard communication interface that employs a
single-ended serial transmission scheme that uses a maximum cable length of 7.6
meters (approximately 25 feet). This interface was designed for computer
communication at short distances. All computers have an RS232 communications
port. Refer to Section 3 for additional information.
RS422 Network
RS422 (EIA/TIA-422-B) is a standard communication interface that utilizes a
differential balanced transmission scheme that uses a typical maximum cable length
of 1.2 km (approximately 4000 feet). The main advantage to RS422 over RS232 is
the longer cable length that is possible. A signal converter is needed to convert the
computer’s RS232 to RS422. Refer to Section 3 for additional information.
Modem Network
The modem is a standard communication interface that utilizes standard phone
transmission lines. The phone company assigns each phone line a number that the
modem uses to communicate between controller and display. Each modem network
needs to have a dedicated phone line assigned to it. Refer to Section 3 for additional
information.
Introduction
1-3
Fiber Optic Network
A fiber optic network is a standard communication method transmitting light (signal)
through a glass fiber. Fiber optic cable has a maximum length of 600 meters
(approximately 2,000 feet). A signal converter is needed to convert the computers
RS232 signal to fiber optic signal; a minimum of two fibers is required. Refer to
Section 3 to additional information.
Radio Network
The Radio network is a standard communication method that uses radio waves at
high frequencies to transmit signal. The Venus
distance of 450 meters (approximately 1500 feet) outdoor and 150 meters
(approximately 500 feet) indoor. A nearly straight line-of-sight path must be
maintained between the Server Radio connected to the computer and the Client
Radio connected to the display. Refer to Section 3 and the Venus 1500 Radio
manual, ED-13932, for the additional information.
1.3 Display Overview
Reference Drawings:
Power Specs, 8x48-48x144 Display RGB
Shop Drawing; AF-3165-8-32 Hi
Shop Drawing; AF-3165-40-48 High-34-RGB
Daktronics AF-3165 Galaxy
performance, reliability, easy maintenance and long life. The pixels have a 34mm
center-to-center spacing, and are lit using LEDs (light emitting diodes). A light
sensor on the front of the first or primary display is used for automatic dimming of
the LEDs based on the ambient light levels. The configuration of pixels depends on
the model of display ordered.
Refer to D
rawings B-172745 and B-172746 for the approximate size and weight of
your display, and Drawing A-179873 for the power requirements.
The Galaxy
®
model numbers are described as follows:
AF-3165-RRCCC-34-RGB-X(X)
AF-3165
RR
CCC
34
RGB
X(X)
=
Outdoor 34mm Louvered Galaxy Display
=
Number of Rows High (8-48)
=
Number of Columns Long (Up to 144 Columns, Standard)
=
34mm pixel to pixel spacing
=
LED Color (32,000 RGB)
=
PM – Primary-Mirror and M – Mirror or
PS – Primary-Secondary and S - Secondary
A typical display system consists of a Windows
running Venus
®
1500 software and one or more displays. The displays are offered as
®
displays are designed and manufactured for
®
1500 Radio network has a maximum
................... Drawing A-179873
gh-34-RGB............... Drawing B-172745
............. Drawing B-172746
®
based personal computer (PC)
1-4
Introduction
single-face units, which are single-sided stand-alone displays. They can become
double-faced by mounting them back-to- back with a second unit.
®
Venus
1500 is a software package that runs under Windows® 98, ME, NT, 4.0,
2000, or XP Home/Professional operating systems on an IBM
computer. Refer to the Venus
operation of the Venus
®
®
1500 Software manual, ED13530, for installation and
1500 editing station.
1.4 Component Identification
The following illustrations depict some of the more commonly accessed Galaxy®
display components. Because Daktronics occasionally alters standard design to meet
customer needs, the actual display design may vary slightly from the illustrations
below.
This is only a brief overview. Refer to Section 4 for additional information on
maintaining the various display components.
Com Port: A COM port is a connector on the back of the control computer. The
COM port is used to control the display network through either a 9- or a 25-pin serial
connector.
Controller: The display’s controller is the “brains” of the display (refer to Figure 2
below). The controller receives signal information from the control computer,
translates it, and activates the appropriate pixels on the display accordingly.
®
-compatible
Figure 2: Version 3 Controller
Control Area Network: Serial Communication Protocol supporting distributed realtime control and multiplexing. The light and temperature sensors use this type of
protocol.
Introduction
1-5
Galaxy
®
: Daktronics trademarked name for LED monochrome, tri-colored or RGB
matrix displays.
Network: A network consists of multiple displays connected to each other. Up to
240 displays can exist on one network.
Power Supply: converts AC line voltage from the load center to low DC voltage for
one or more module driver boards.
RS232: RS232 is a standard PC communication type with a maximum cable length
of 25 feet (7.6 meters).
RS422: RS422 is a standard differential communication
type with a maximum cable length of 4000 feet (1.2
kilometers).
Display Address: The display address is an identification
number assigned to each display of a network. Rotating the
address switches on the controller sets it. The control
software uses the address to locate and communicate with
each display. Displays that are on the same network cannot
have the same address.
Signal Converter: The signal converter, shown in
on the right, is a Daktronics supplied unit that converts the
data from RS232 to RS422, or RS232 to fiber optic signal.
The signal converter is connected to the control PC via
Figure 3
Figure 3: Signal Converter
(RS232 to RS422 Shown)
straight through serial cable.
Driver/Pixel Board: The LED pixels are mounted directly onto the driver/pixel
board. This board is also responsible for the switching and intensity levels of the
LEDs.
LED (light emitting diode): low energy, high intensity lighting units.
Louver: a black plastic shade positioned horizontally above each pixel row. The
louvers increase the level of contrast on the display face and direct LED light.
1-6
Introduction
Module: 34mm Galaxy
are individually removable from the front of the display. Refer to
Figure 4: AF-3165 LED Module
®
RGB modules are 8 pixels high by 8 pixels wide . Mo dul es
Figure 4.
Module Latch Assembly: device utilizing a rotating retainer bar to hold the module
firmly to the display frame. There are two per module: one near the top and one near
the bottom. Use a 1/8" Allen wrench to turn the retaining bar.
Pixel: a cluster of LEDs. Each cluster on the AF-3165 module contains two red, two
green, and two blue LED’s.
1.5 Daktronics Nomenclature
Figure 5: Module Numbering Example – 24x80 Front
Introduction
1-7
To fully understand some Daktronics drawings,
such as schematics, it is necessary to know how
various components are labeled in those
drawings. This information is also useful when
trying to communicate maintenance or
troubleshooting efforts.
A module is the building block of the Galaxy
display. Each module measures 8 pixels high
®
Figure 6: Module Numbering
by 8 pixels wide. By placing modules side-byside and on top of one another a display of any
size can be designed and built. Individual modules can be easily removed from the
display if required.
®
Galaxy
display. Figure 6on the right breaks down the module numbering method.
Figure 5 above illustrates how Daktronics numbers modules on a
In addition, the following labeling formats might be found on various Daktronics
drawings:
• “TB_ _” denotes a termination block for power or signal c abl e.
• “F_ _” denotes a fuse.
• “E_ _” denotes a grounding point.
• “J_ _” denotes a power or signal jack.
• “P_ _” denotes a power or signal plug for the opposite jack.
Finally, Daktronics part numbers are commonly found on drawings. Those part
numbers can be used when requesting replacement parts from Daktronics Customer
Service. Take note of the following part number formats:
• “0P-_ _ _ _-_ _ _ _” denotes an individual circuit board, such as the internal
fiberboard.
• “0A-_ _ _ _-_ _ _ _” denotes an assembly, such as a circuit board and the
plate or bracket to which it is mounted. A collection of circuit boards
working as a single unit may also carry an assembly label.
• “W-_ _ _ _” denotes a wire or cable. Cables may also carry the assembly
numbering format in certain circumstances. This is especially true of ribbon
cables.
Most circuit boards and components within this display carry a label that lists the
part number of the unit. If a circuit board or assembly is not listed in the replacement
parts list in Section 4, use the label to order a replacement.
A typical label is shown in
bold.
Figure 7. The part number is in
0P-1195-0001
SN: 6343
05/19/99 REV.1
Figure 7: Typical Label
1-8
Introduction
Section 2: Mechanical Installation
Notes: Daktronics does not guarantee the warranty in situations where the display is not
constantly in a stable environment.
Daktronics engineering staff must approve an
of the display. If any modifications are made, detailed drawings of the changes must be
submitted to Daktronics for evaluation and approval, or the warranty will be void.
Daktronics is not responsible for installations or the structural integrity of support
struc
tures done by others. It is the customer’s responsibility to ensure that a qualified
structural engineer has approved the structure and any additional hardware.
2.1 Mechanical Installation Overview
y changes that may affect the weather-tightness
Because every installation site is unique, there is no single Daktronics-approved
procedure for mounting the Galaxy
section is general information only and may or may not be appropriate for your
particular installation.
A qualified individual must make all decis
display.
Read both the mechanical and electrical installati
before beginning any installation procedures.
®
displays. The information contained in this
2.2 Support Structure Design
Support structure design depends on the mounting methods, display size, and weight.
The structure design is critical and should be done only by a qualified individual.
Display height and wind loading are also critical factors. It is the customer’s
responsibility to ensure that the structure and mounting hardware are adequate.
Daktronics is not responsible for the installations or the structural inte gri t y of
support structures done by others.
It is the installer’s responsibility to
hardware are capable of supporting the display, and agrees with local codes.
ensure the mounting structure and
ions regarding the mounting of this
on sections of this manual
Mechanical Installation
2-1
Before beginning the installation proces s, verify the following:
• The mounting structure will provide a straight and square-mounting frame
for the display
• The mounting structure is capable of supporting the display and will not
yield at any unsupported points after mounting
• Clearance: 3" of unobstructed space is available below the display for filter
removal from the display. 1-¼" of unobstructed space is available above the
top of the display to remove the eyebolt and plug the hole properly
Correct any deficiencies b
efore installation.
2.3 Ventilation Requirements
Reference Drawings:
Shop Drawing, AF-3165-8-32 Hi
Shop Drawing, AF-3165-40-48 High-34-RGB;
Fans are mounted in the bottom of the display for 8-32 high displays and to the back
sh
eet for ventilation on the 40 and 48 high displays. Maintain a minimum distance of
3" (7.62cm) below the display to maintain proper airflow and for easy air filter
removal. Refer to Drawing B-172745 or B-172746 for additional information.
If the display cabinet is completely enclosed:
• 6 square inches of unobstructed opening per module must be provided to
ensure adequate cooling.
• Allowances must be made to compensate for the percentage of material
covering the openings in the structure.
• For adequate cooling, forced ventilation may be required. If air is forced
into the enclosed cabinet, 10 cubic feet per minute must be provided per
module (10.6" x 10.6" active area).
If these requirements are not met, the Galaxy
gh-34-RGB;..............................B-172745
............................B-172746
®
display warranty may be void.
2.4 Lifting the Display
The top of the larger displays is equipped with eyebolts that are used to lift the unit.
Take special care to ensure that the rated load of the eyebolts is not exceeded. Refer
to the information at the end of this section labeled Eyebolts to determine the
allowable load of the eyebolts shipped with the display.
Figure 8 below illustrates both the correct (left example) and the incorrect (right
example) method of lifting a display. Lift the display as shown on the left, with the
lifting bar. Use every lifting point provided.
2-2
Mechanical Installation
Figure 8: Lifting the Display (Correct, Left; Incorrect, Right)
Do not attempt to permanently support the display by the eyebolts.
If removing the eyebolts, adequately seal the holes using 13 bolts and sealing
washers, ½ inch in size. Silicone along the threads to ensure that water does not enter
the display.
The method used to mount displays can vary greatly from location to location. For
this reason, only general mounting topics can be addressed in this manual.
It is the responsibility of the installer to ensure the installation will adequately
meet local codes and standards. The mounting hardware and method is also the
responsibility of the installer.
Before beginning the installation proces s, verify the following items:
• The mounting structure will provide a straight and square-mounting frame
for the display. Height variation in any fou r -f oo t hori z ontal section may
not exceed ¼-inch.
• The mounting structure will not give way at any unsupported points after
the display is mounted.
The back of the display is equipped with 2 x 2 x ¼" steel clip angles at the locations
shown in Drawings B-172745 and B-172746. These angles may be used for
mounting purposes. Remember to have all mounted displays inspected by a qualified
structural engineer. It is the customer’s responsibility to determine the proper wall
mounting method and location.
Refer to Drawings B-172745 and B-172746 for a suggested wall mount method. The
number of attachment points needed and the wall structure must be reviewed by a
qualified structural engineer and meet all national and local codes. Daktronics
recommends using all clip angles as attachment points.
Mechanical Installation
2-3
1. Carefu
2. Fol
3. W
4. Refer t
5. After in
lly uncrate the display. Look each side of the display over for
possible damage during shipping.
lowing the guidelines described in Section 2.4, lift the display into
position on the support structure.
eld or use ½" Grade-5 bolts and hardware to secure the clip angles to the
support structure as shown in Drawing B-172745 or B-172746.
o Section 3 for information on routing power and signal.
stallation is complete, carefully inspect the display for any holes
that may allow water to seep into the display. Seal any openings with
silicone. If the eyebolts on the top of the display have been removed, plug
the holes with bolts and the rubber-sealing washer that was removed with
the eyebolt.
2.6 Optional Temperature Sensor
If a temperature sensor will be used with your display, see Appendix C for mounting
and signal connections.
2-4
Mechanical Installation
Eyebolts
Almost every display that leav es D ak tronics is equipped w ith ey ebolts for lifting the display . There are
two standard sizes of eyebolts: ½″ and A″.
Load Increase Factor: The load increases as the lift angle (θ) decreases. The allowable load on the
eyebolts also decreases with the lift angle due the bending stress on the eyebolts. In sum, the smaller
the angle between the cable and the top of the display, the lighter the sign must be to safely lift it. Do
NOT attempt to lift the display when the lift angle is less than 30 degrees.
A. Do not use eyebolts on angular lifts unless absolutely necessary. For angular lifts, the shoulder pattern
eyebolt is preferred.
B. Load should always be applied to eyebolts in the plane of the eye, not at some angle to this plane.
C. Shoulder eyebolts must be properly seated (should bear firmly against the mating part), otherwise the
working loads must be reduced to those indicated for regular eyebolts. A washer or spacer may be
required to put the plane of the eye in the direction of the load when the shoulder is seated.
D. No load greater than the safe working load listed in the data table should be used.
E. To obtain the greatest strength from the eyebolt, it must fit reasonably tight in its mounting hole to prevent
accidental unscrewing due to twist of cable.
F. Eyebolts should never be painted or otherwise coated when used for lifting. Such coatings may cover
potential flaws in the eyebolt.
G. To attain the safe working loads listed for regular eyebolts, 90% of the thread length must be engaged.
Copyright 1996-2001 ED-7244
Daktronics, Inc. Rev. 4 – 14 March 2001
3: SectionElectrical Installation
Only a qualified individual should terminate power and signal cable within this
Daktronics display.
The Daktronics engineering staff must approve any changes made to the display. Before
altering the display, submit detailed drawings for the proposed modifications to the
Daktronics engineering staff for evaluation and approval or the warranty will be rendered null
and void.
3.1 Common Connectors in the Display
The power and signal connections in the displays use many different types of
connectors. Take special care when disengaging any connector so as not to damage
the connector, the cable, or the circuit board.
When pulling a connector plug from a jack, do not pull on the wire or cable; pull on
the jack itself. Pulling on the wires may damage the connector.
The following information presents some common connectors
encountered during display installation and maintenance.
1. Ribbon Cable Connectors:
Figure 9illustrates a typical ribbon connector. To disconnect the
ribbon cable, push the plastic clips on the sides of the jack to
unlock and remove the cable.
Before replacing a ribbon cable connector, spray it with DeoxIT
contact cleaner to remove any foreign matter that may cause
signal problems. In addition, apply a generous amount of
CaiLube
™
protector paste to the plug before inserting it into the
jack. This paste will protect both the plug and the jack from
corrosion.
2. Termination Blocks:
Termination blocks are usually used to connect internal power
and signal wires to wires of the same type coming into the
display from an external source. Power wires need to have onehalf inch of insulation stripped from the end of the wire prior to
termination. Tighten all screws firmly to ensure a good
electrical connection. Refer to
Figure 10.
™
Figure 9: Ribbon
Cable Connector
Figure 10: Termination
Block
Electrical Installation
3-1
3. Phoenix
™
-Style Connectors:
Phoenix-style connectors, which are usually green, are often used for
signal termination on circuit boards. Refer to
Figure 11. Strip one-
quarter inch of insulation from the wire prior to termination. To
remove a wire, turn the above screw counter-clockwise to loose the
connectors grip on the wire. To insert a wire, push the bare wire into
the connector and turn the above screw clockwise to lock the wire into
place.
4. Mate-n-Lok™ Connectors:
The Mate-n-Lok connectors found in the displays are white and come
in a variety of sizes.
Figure 12 illustrates a four-pin Mate-n-Lok
connector. To remove the plug from the jack, squeeze the plastic
locking clasps on the side of the plug and pull it from the jack.
5. Phone Jacks (RJ11/RJ45 Connectors):
RJ connectors, as seen in
Figure 13, are similar to the telephone connectors
found in homes and are used on the ends of flat RJ11 cable. In order to
remove this plug from the jack, depress the small clip on the underside of
the plug.
Before replacing an RJ connector, spray it with DeoxIt
™
contact cleaner to
remove any foreign matter that may cause signal problems. In addition,
apply a generous amount of CaiLube
™
protector paste to the plug before
inserting it into the jack. This paste will protect both the plug and the jack
from corrosion.
6. Six-Pin Insulation Displacement Connector
The six-pin connectors found in the display are keyed connectors, meaning
that they will only go together one way and should not be forced. To
remove the connector squeeze the plastic tab and gently pull the plug from
the jack.
Figure 11: Phoenix
Connector
Figure 12: Maten-Loc Connector
3.2 Control Cable Requirements
RS232
This cable is a 2-conductor shielded cable used to transmit an RS232 signal
(Daktronics part number W-1117). This shielded cable should not be subjected
to mechanical flexing after installation. This cable is not for direct burial and
should be routed in a dedicated, grounded metallic conduit from the base of the
sign structure. Power and signal cable cannot be run in the same conduit. This
cable has a maximum length of 25 feet (7.6 meters).
3-2
Figure 13: RJ45
Connector
Electrical Installation
RS422
This cable is a 4-conductor shielded cable used to transmit an RS422 signal
(Daktronics part number W-1234). This shielded cable consists of paired wires. They
should not be subjected to mechanical flexing after installation. This cable is not for
direct burial and should have one of the following routings:
• Dedicated metallic conduit – power and signal cable cannot be run in the
same conduit
• Inside buildings − if cable is not in conduit, keep away from interference
signals
With interference signals (such as power conductors, intercom, etc.) typically a twofo
ot separation is required. The maximum length of an RS422 signal cable is 4,000
feet (1.22 km).
Modem
The modem option will use standard telephone cable routed through conduit. Power
and phone cable cannot be run in the same conduit. The local telephone company
will need to assist in this installation. Ask the telephone company which color is used
for the TIP wire and which color for the RING wire for signal hook up.
Note: T
board/communications system.
he telephone lines must be dedicated lines and not run through a switch
Fiber Optic
This cable is a 4-fiber cable (Daktronics part number W-1376). Two fibers are used
for display communications and the other two are saved for spares. The cable may be
either direct burial or routed in conduit but it should not be subjected to mechanical
flexing. The fiber can be routed in the same conduit as the power. The maximum
length of a fiber optic cable is 2,000 feet (611.6 meters).
Radio
The Server radio connected to the computer requires an 18-gauge six-conductor
cable (Daktronics part number W-1370). Four conductors will be used for the signal
and a two for the power. These wires need to be in co nduit when exposed to outdoor
conditions to the Server radio. The maximum distance from the J-box to the Server
radio is 1000 feet (305.8 meters).
The Client radio at the display comes with cable that is rated for outdoor use and
doe
s not need to be in conduit. Note: Secure excess cable to prevent it from being
pulled loose by weather or vandalism.
Electrical Installation
3-3
3.3 RJ Connector Cables
Two types of RJ connectors are used in
the display. There is the 6-pin RJ11 and
the 8-pin RJ45.
typical RJ11 connector. These
connectors can be found on many
telephones and LANs.
The cable used in the display are straight
through cables meaning that the wire to
pin one at one end is the same as pin one
at the other end, and so forth. When
installing a network, and on cables
exterior to the display, flipped cables are
often used. This cable has one end that is
the mirror image of the other end (i.e. the
cable is flipped). Refer to
standard flipped cable.
Notice in
on the other connector. When installing a network, it is not easy to remember in
which direction the previous end was oriented. One simple way to avoid confusion is
to standardize the color code, having one color for the connector going into the
output of a sign and the opposite color for a connector going into the input of a sign.
This will help ensure correct cabling since cables are always installed from the
output jack of one sign to the input jack of the next sign.
Figure 14 illustrates a
Figure 15for a
Figure 15 that the color code on one connector must be made the opposite
Figure 14: 6-Conductor RJ11 Connector and Cable
3-4
Figure 15: Flipped Cable with RJ Connectors
Electrical Installation
Installing an RJ Connector
Installing an RJ connector on the end of the conductor cable is a
simple task when the correct tools are used. The RJ crimping tool
(Daktronics part number TH-1033) performs two separate steps.
First, use the crimping tool to strip the outer insulation from the
inner wires. This does not result in bare wires since only the gray
outer jacket is removed. After correct stripping, the wire will appear
as shown in
Figure 16.
The crimping tool is then used to crimp the RJ connector onto the cable. The RJ
connector is locked into a special socket in the tool. The stripped wire is inserted into
the RJ connector. Finally, the tool is squeezed like pliers to crimp the connector onto
the wire. This completes the installation of an RJ connector onto the wire.
Daktronics does not include the conduit. Refer to Drawings B-172745 and B172746 for your display size for approximate locations for pow er and signal conduit.
Separate conduit must be used to route:
• Power
• Signal IN wires, including phone line
• Signal OUT wires (if signal is required for another display)
Knockout holes for ½" conduit are located at the bottom right (rear view) of th e back
of the display (refer to Drawings B-172745 and B-172746).
For displays with more than one face, signal and temperature sensor wiring between
displays is normally completed using the quick connect interconnect cable. If not
using the interconnect cable, the separate signal and temperature sensor cables can be
routed through the same conduit.
Figure 16: Wire with Outer
Jacket Stripped
Electrical Installation
3-5
3.5 Preparing for Power/Signal Connection
Reference Drawings:
Component Layout Drawings...................................Refer to Appendix A
1. Punch or use 1/2" (0.875" in diameter)
conduit holes for the desired conduit
openings. Be careful that none of the internal components are damaged. Attach
the conduit
2. Remove the bottom left two modules (AX01
and AX02) to expose the power enclosure
and signal panel. To do this, use a
wrench to turn the latch access fasteners onequarter turn. Turn the top latch clockwise and
the bottom latch counter-clockwise. Lift each
module away from the display; reach behind
it and disconnect all power and signal
connections. Refer to Figure 17
3. Locate the controller and power termination
box for these displays in the Component
Layout Diagram for your sign
4. The controller receives the incoming signal
and relays it to the individual modules
5. Route power to the display through a fused
disconnect switch capable of opening all ungr o un ded power conductors.
Install this disconnect within the line of sight of any personnel performing
maintenance on the display. If the disconnect is located out of sight of the
display, it must be capable of being locked in the open position
6. Power conductors from the disconnect to the display should be routed
through conduit in agreement with local code
7. You may route the signal cable from the control computer to the display at
this time – Be sure to run the power and signal cables in separate
conduit
1
/8" Allen
Figure 17: Removing a Module
3-6
Electrical Installation
3.6 Power
Reference Drawings:
Power Specs, 8x48-48X144 Display RGB...................Dra
Power Requirements
Refer to Drawing A-179873 for voltage and current requirements for your display
size. Each uses a 120VAC or 120/240 VAC single-phase power source . D epen di ng
on the display size the number of power supplies may vary.
Do not connect the displays to any voltage other than that listed on the
Daktr
onics product label.
Proper power installation is imperative for proper display operation. The following
su
b-sections give details of display power installation.
Grounding
This sign is intended to be installed in accordance with the requirements of
Article 600 of the National Electrical Code and/or other applicable local codes.
This includes proper grounding and bonding of the sign.
Displays mu
National Electrical Code
less.
The display system must b
necessary for reliable equipment operation. It also protects the equipment from
damaging electrical disturbances and lightning. The display must be properly
grounded or the warranty will be void.
The material of an earth-ground electrode differs from region to region and from
co
nditions present at the site. Consult the National Electrical Code and any local
electrical codes that may apply. The support structure of the display cannot be used
as an earth-ground electrode. The support is generally embedded in concrete, and if
in earth, the steel is either primed or it corrodes, making it a poor ground.
wing A-179873
st be grounded according to the provisions outlined in Article 250 of the
®
. Daktronics requires a resistance to ground of 10 ohm s or
e connected to earth-ground. Proper grounding is
Electrical Installation
3-7
Figure 18: Grounding
A minimum of one grounding electrode must be installed for each display face. The
grounding electrode is typically one grounding rod for each display face. Other
grounding electrodes as described in Article 250 of the National Electric Code may
be used. Daktronics requires that the resistance to ground be 10 ohms or less. If the
resistance to ground in higher than 10 ohms it will be necessary to install additional
grounding electrodes to reduce the resistance. The grounding electrode should be
installed within 25 feet of the base of the display. The grounding electrode must be
connected to the ground terminal in the display panel board.
Power Installation
There are two considerations for power installation: installation with ground and
neutral conductors provided and installation with only a neutral conductor provided.
These two power installations differ slightly, as described in the following
paragraphs:
3-8
Electrical Installation
Installation with Ground and Neutral Conductors Provided
For this type of installation, the power cable must contain an isolated earth-ground
conductor. Under this circumstance, do not connect neutral to ground at the
disconnect or at the display. This would violate electrical codes and void the
warranty. Use a disconnect so that all hot lines and neutral can be opened. Refer to
Figure 19 for installation details. The National Electrical Code requires the use of a
lockable power disconnect within sight of or at the sign.
Figure 19: Installation with Ground and Neutral Conductors Provided
Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article
250-32 of the National Electrical Code. If the installation in question meets all of the
requirements of article 250-32, the followi n g guidelines must be observed:
• Connect the grounding electrode cable at the local disconnect, never at the
sign panel board.
• A disconnect that opens all of the ungrounded phase conductors should be
used.
• The neutral and the ground conductors should be bonded in the sign panel
board.
Refer to
Figure 20 for installation details.
Figure 20: Installation with Only A Neutral Conductor Provided
Electrical Installation
3-9
Power Connection
Reference Drawings:
Power Term Box, AF-3X65, 8- Pos
Power Term Box 2-Pos
following steps to terminate the hot and neutral wires at the termination block within
the enclosure. Refer to Drawing A- 154965 or A-175131 and the appropriate
Schematic for your display size.
1. Access t
he enclosure by removing the left bottom two modules as described
in Section 3.5
2. Route t
he power cables through the power conduit in the rear of the sign
and to the enclosure
3. Co
nnect the white neutral wire to neutral bus
4. If on
e power line is being terminated (120VAC), connect the black “hot”
wire to L1. Install a jumper per note one on Drawing A-154965
5. I
f two power lines are being terminated (120/240VAC). Connect the second
“hot” wire to L2 and do not install the jumper
6. Co
nnect the green grounding wire to the grounding bus E41. Refer to
20
Figure
Main Disconnect
The National Electrical Code requires the use of a lockable power disconnect near
the display. Provide a lockable disconnect switch (knife switch) at the display
location so that all power lines can be completely disconnected. Use a 3-conductor
disconnect so that both hot lines and the neutral can all be disconnected. The main
disconnect should be mounted at or near the point of power supply connection to the
display. A main disconnect is to be provided for each supply circuit to the display.
The disconnecting means must be located in a di
outline lighting that it controls. This requirement provides protection by enabling a
worker to keep the disconnecting means within view while working on the display.
Exception:
Disconnecting means that are capable of being locked in the open
position may be located elsewhere.
rect line of sight from the display or
3-10
Electrical Installation
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.