Daktronics AF-3150-20-R,A User Manual

Galaxy® Series AF-3150
Display Manual
ED-13745 Rev 2 16 March 2004
Rev 2 – 16 March 2004
ED-13745
Product 1289
DAKTRONICS, INC.
Copyright © 2003-2004
All rights reserved. While every precaution has been taken in the preparation of this manual, the publisher assumes no responsibility for errors or omissions. No part of this book covered by the copyrights hereon may be reproduced or copied in any form or by any means – graphic, electronic, or mechanical, including photocopying, taping, or information storage and retrieval systems – without written permission of the publisher.
®
is a registered trademark of Daktronics, Inc. All others are trademarks of their respective companies.
Galaxy
Table of Contents
Section 1: Introduction....................................................................................1-1
How to Use This Manual......................................................................................... 1-1
1.1 Safety Precautions..................................................................................... 1-2
1.2 Network Concepts..................................................................................... 1-3
RS232 Network.................................................................................. 1-3
RS422 Network.................................................................................. 1-3
Modem Network.................................................................................1-3
Fiber Optic Network........................................................................... 1-3
Radio Network ................................................................................... 1-4
1.3 Display Overview......................................................................................1-4
1.4 Component Identification..........................................................................1-5
1.5 Nomenclature ............................................................................................ 1-7
Section 2: Mechanical Installation.................................................................2-1
2.1 Mechanical Installation Overview............................................................. 2-1
2.2 Support Structure Design...........................................................................2-1
2.3 Ventilation Requirements.......................................................................... 2-2
2.4 Lifting the Display..................................................................................... 2-2
2.5 Display Mounting...................................................................................... 2-3
2.6 Optional Temperature Sensor Mounting ................................................... 2-3
Section 3: Electrical Installation.....................................................................3-1
3.1 Common Connectors in the Display..........................................................3-1
3.2 Control Cable Requirements......................................................................3-2
RS232................................................................................................. 3-2
RS422................................................................................................. 3-3
Modem ............................................................................................... 3-3
Fiber Optic.......................................................................................... 3-3
Radio .................................................................................................. 3-3
3.3 RJ Connector Cables ................................................................................. 3-3
Installing an RJ Connector ................................................................. 3-4
3.4 Conduit......................................................................................................3-4
3.5 Preparing for Power/Signal Connection.................................................... 3-5
3.6 Power.........................................................................................................3-5
Power Requirements........................................................................... 3-5
Grounding........................................................................................... 3-6
Power Installation...............................................................................3-7
Power Connection ..............................................................................3-8
Main Disconnect.................................................................................3-8
3.7
Signal Termination from Computer to Display......................................... 3-9
RS232................................................................................................. 3-9
RS422............................................................................................... 3-11
Modem ............................................................................................. 3-12
Table of Contents i
i
Fiber Optic........................................................................................3-14
Venus® 1500 Radio Client................................................................3-15
3.8 Signal Termination Between Two (or More) Signs................................. 3-17
RS422 Interconnection.....................................................................3-17
Fiber Interconnection........................................................................3-18
3.9 Optional Temperature Sensor..................................................................3-18
3.10 First Time Operation................................................................................3-18
Section 4: Maintenance and Troubleshooting............................................. 4-1
4.1 Maintenance and Troubleshooting Overview............................................4-1
4.2 Signal Summary.........................................................................................4-2
4.3 Power Summary.........................................................................................4-2
4.4 Service and Diagnostics.............................................................................4-3
Transformer and RFI Filter.................................................................4-4
Controller............................................................................................4-5
Modules and Drivers ..........................................................................4-7
Power Supplies................................................................................... 4-8
Light Detector.....................................................................................4-8
Modem................................................................................................4-8
Fiber Board.........................................................................................4-9
RS422 Surge Suppressor.................................................................. 4-10
Location of CAN termination Jumper ..............................................4-11
4.5 Ventilation Systems (With Fans and Filters)...........................................4-12
4.6 Thermostats ............................................................................................. 4-13
4.7 Weather Stripping.................................................................................... 4-13
4.8 Display Maintenance ...............................................................................4-13
4.9 Troubleshooting.......................................................................................4-14
4.10 Initial Operation Information...................................................................4-15
4.11 Replacement Parts List............................................................................4-16
4.12 Daktronics Exchange and Repair and Return Programs..........................4-17
Appendix A: Reference Drawings .....................................................................A-1
Appendix B: Signal Converter ...........................................................................B-1
Appendix C: Optional Temperature Sensor .....................................................C-1
i
Table of Contents
List of Figures
Figure 1: Drawing Label..................................................................................................1-2
Figure 2: Version 3 Controller ..........................................................................................1-5
Figure 3: 16x16 Module (Front and Back)...........................................................................1-6
Figure 4: Signal Converter (RS232 to RS422 Shown).............................................................1-7
Figure 5: Module Numbering Example – 48x160 Front...........................................................1-7
Figure 6: Module Numbering ............................................................................................1-7
Figure 7: Typical Label....................................................................................................1-8
Figure 8: Lifting the Display (Correct, Left; Incorrect, Right)...................................................2-2
Figure 9: Ribbon Cable Connector..................................................................................... 3-1
Figure 10: Termination Block............................................................................................3-1
Figure 11: Phoenix Connector...........................................................................................3-1
Figure 12: Mate-n-Loc Connector......................................................................................3-2
Figure 13: RJ11 Connector............................................................................................... 3-2
Figure 14: RS232/6-pin Quick Connect Jack........................................................................3-2
Figure 15: 6-Conductor RJ11 Connector and Cable...............................................................3-3
Figure 16: Flipped Cable with RJ Connectors.......................................................................3-4
Figure 17: Wire with Outer Jacket Stripped..........................................................................3-4
Figure 18: Opening the Display........................................................................................3-5
Figure 19: Display Grounding...........................................................................................3-6
Figure 20: Installation with Ground and Neutral Conductor Provided........................................3-7
Figure 21: Installation with only Neutral Conductor Provided..................................................3-8
Figure 22: Signal Termination at Display (Front View)...........................................................3-9
Figure 23: RS232 Display Layout.....................................................................................3-10
Figure 24: J-box to RS232 IN on Controller Board ..............................................................3-10
Figure 25: RS422 Display Layout.....................................................................................3-11
Figure 26: Signal Converter to Surge Suppresser in Display..................................................3-12
Figure 27: Modem Display Layout ................................................................................... 3-13
Figure 28: Modem/ Signal Connections.............................................................................3-13
Figure 29: Fiber Optic Display Controller.........................................................................3-14
Figure 30: Fiber Signal Connections.................................................................................3-15
Figure 31: Radio Display Layout .....................................................................................3-16
Figure 32: Radio Client Connection..................................................................................3-16
List of Figures iii
Figure 33: Quick Connect Cable ..................................................................................... 3-17
Figure 34: RS422 Signal Termination Panels .....................................................................3-17
Figure 35: Power Termination Box ....................................................................................4-4
Figure 36: Controller Component Layout............................................................................4-5
Figure 37: Removing a Module .........................................................................................4-7
Figure 38: Power/Control Corner.....................................................................................4-2
Figure 39: Modem.......................................................................................................... 4-8
Figure 40: Modem Jumper Location...................................................................................4-9
Figure 41: Fiber Optic Board ...........................................................................................4-9
Figure 42: Surge Suppressor, RS422 ................................................................................4-10
Figure 43: Displays with No External Temperature Sensor....................................................4-11
Figure 44: Displays with External Temperature Sensor ........................................................4-11
Figure 45: Quick Connect Boards.................................................................................... 4-12
iv
List of Figures
Section 1: Introduction

1.1 How to Use This Manual

This manual explains the installation, maintenance, and troubleshooting of a Daktronics Galaxy
®
AF-3150 20mm louvered LED display. For questions regarding the safety, installation, operation, or service of this system, please refer to the telephone numbers listed on the cover page of this manual.
The manual is divided into seven sections: Introduction, Mechanical Installation,
ectrical Installation, Maintenance and Tro ubl eshooting, Appendix A, Appen di x B
El and Appendix C.
Introduction covers the basic information needed to make the most of the
rest of this manual. Take time to read the entire introduction as it defines terms and explains concepts used throughout the manual.
Mechanical Installati o n pr ov i des general guidance on display mounting.
Electrical Installation gives general guidance on terminating power and
signal cable at the display.
Maintenance and Trou bl eshooting addresses such things as removing
basic display components, troubleshooting the display, performing general maintenance, and exchanging display components.
Appendix A lists the drawings referenced within this manual.
Appendix B includes general information on the signal converter.
Appendix C includes information on the optional temperature sensor.
Daktronics identifies manuals by an ED number located on the cover page of each
anual. For example, this manual would be referred to as ED-13745.
m
Listed below are a number of drawing types commonly used by Daktronics, along
the information that each is likely to provide. This manual might not contain all
with these drawings:
System Riser Diagrams: Overall system layout from control computer to
display, power, and phase requirements .
Shop Drawings: Fan locations, mounting information, power and signal
entrance points, and access method (front and rear).
Schematics: Power and signal wiring for various components.
Component Placement Diagrams: Locations of critical internal display
components, such as power supply assemblies, controller boards, thermostats, and light detectors.
Figure 1 below illustrates the Daktronics drawing label. The drawing number is
located in the lower-right corner of the drawing. Listing the last set of digits and the letter preceding them identifies drawings in the manual. In the example below, the drawing would be referred to as Drawing B-181287. Reference drawings are inserted in Appendix A.

Introduction

1-1
Figure 1: Drawing Label
All references to drawing numbers, appendices, figures, or other manuals are presented in bold typeface, as shown below.
“Refer to Drawing B-181287 in Appendix A for the power supply location.”
Additionally, drawings referenced in a particular section are listed at the beginning of that section as seen in the following example:
Reference Drawing:
Shop Drawing; VF-****-27x75-18-W............................ Drawing B-181287
Daktronics displays are built for long life, and require little maintenance. However, from time to time, certain display components will need replacing. The Replacement Parts List in Section 4.11 provides the names and numbers of components that may need to be ordered during the life of the display. Most display components have a white label that lists the part number. The component part number is in the following format: 0P-_ _ _ _-_ _ _ _ (component) or 0A-_ _ _ _-_ _ _ _ multi-component assembly).
Following the Replacement Parts List is the Daktronics Exchange and Repair and Return Programs in Section 4.12. Refer to these instructions if any display component needs replacement or repair.
1.2 Safety Precautions
Important Safeguards:
1. Read an d understand these instructions before installing.
2. Be sure the display and exterior enclosures are properly grounded with an
earth ground electrode at the display.
3. Disconn ect power when servicing the display.
4. Do not modify the display structure or attach any panels or coverings to the
display without the written consent of Daktronics, Inc.
1-2
Introduction
1.3 Network Concepts
The concept of using LED displays as a cost effective, high impact method of communication is rapidly growing throughout many industries and businesses. The reasons for this growth are many, but the need for additional features and the complexity of multiple display installations has emerged. Daktronics display systems have been designed to meet those needs.
The common thread to most client requests is a means of programming and
ntrolling a group of displays from a central control point. Daktronics responded by
co developing a powerful system of interconnecting and controlling displays. Great care has been taken to design products that will satisfy a wide variety of installations. Some of the design goals of these system
Easy transfer of messages
The ability to tell a display or group of displays in the network which
message should run
The ability to determine the status of any display on the network
The ability to control multiple display technologies on the same network
There are five (5) network systems available: RS232, RS422, modem, fiber, and
adio. Up to 240 displays can exist on one network.
r

RS232 Network

RS232 (EIA/TIA-232-E) is a standard communication interface that employs a single-ended serial transmission scheme that uses a maximum cable length of 7.6 meters (approximately 25 feet). This interface was designed for computer communication at short distances. A computer with a serial, RS232 communication port is required. Refer to Section 3 for additional information.
s include the following:

RS422 Network

RS422 (EIA/TIA-422-B) is a standard communication interface that utilizes a differential balanced transmission scheme that uses a typical maximum cable length of 1.2 km (approximately 4,000 feet). The main advantage to RS422 over RS232 is the longer cable length that is possible. A signal converter is needed to convert the computer’s RS232 serial signal to RS422. Refer to Section 3 for additional information.

Modem Network

The modem is a standard communication interface that utilizes standard phone transmission lines. The phone company assigns each phone line a number that the modem at the computer uses to communicate to the modem in the display. Refer to Section 3 for additional information.

Fiber Optic Network

A fiber optic network is a standard communication method transmitting light (signal) through a glass fiber. Fiber optic cable has a maximum length of 600 meters (approximately 2,000 feet). A signal converter is needed to convert the computer’s RS232 serial signal to fiber optic signal; a minimum of two fibers is required. Refer to Section 3 for additional information.
Introduction
1-3

Radio Network

The Radio network is a standard communication method that uses radio waves at high frequencies to transmit signal. The Venus distance of 450 meters (approximately 1,500 feet) outdoor and 150 meters (approximately 500 feet) indoor. A nearly straight line-of-sight path must be maintained between the Server Radio attached to the building and the Client Radio connected to the display. A computer with a serial, RS232 communication port is required. Refer to Section 3 and the Venus 1500 Gen 2 Radi o m a nual , ED13932, for additional information.
1.4 Display Overview
Reference Drawings:
Shop Drawing, AF-3150-**x**-20mm-R or Amber ...... Dra
Daktronics AF-3150 Galaxy performance, reliability, easy maintenance, and long life. The pixels have a 20mm center-to-center spacing, and are lit using LEDs (light emitting diodes). A light sensor on the front of the primary display is used for automatic dimming of the LEDs based on the ambient light levels. The configuration of pixels depends on the model of display ordered.
Refer to D
rawing B-183660 for the approximate size, weight, and power
requirements for your model of display.
The Galaxy
®
model numbers are described as follows:
AF-3150-RRCCC-20-X-X(X)
AF-3150 = RR = CCC =
20 = X = X(X) =
A typical display system consists of a Windows running Venus
®
1500 software, a communication system, and one or more displays. The displays are offered as single-face units, which are single-sided stand-alone displays. They can become double-faced by mounting them back-to-back with a second unit.
®
Venus
1500 is a software package that runs under Windows® 98, ME™, NT® 4.0, 2000, or XP Home/Professional operating systems on an IBM computer. Refer to the Venus installation and operation of the Venus
Refer to Sec
tions 4.2 and 4.3 for the summaries of how signal and power are routed
through the displays.
®
displays are designed and manufactured for
Outdoor 20 mm Louvered Galaxy Display Number of Rows High (16-48) Number of Columns Long (Up to 144
Columns Standard) 20 mm pixel to pixel spacing
LED Monochrome Color (Red or Amber) PS – Primary-Secondary or S - Secondary
®
1500 controller operator’s manual (ED13530) for
®
1500 Radio network has a maximum
®
based personal computer (PC)
®
1500 editing station.
wing B-183660
®
-compatible
1-4
Introduction
1.5 Component Identification
The following illustrations depict some of the more commonly accessed Galaxy® display components. Because Daktronics occasionally alters standard design to meet customer needs, the actual display design may vary slightly from the illustrations below.
This is only a brief overview. Refer to Section 4 for additional information on maintaining the various display components.
Com Port: A COM port is a connector on the back of the control computer. The COM port is used to control the display network through either a 9- or a 25-pin serial connector.
Controller: The display’s controller is the “brains” of the display (refer to below). The controller receives, translates, and activates the signal information from the control computer to the appropriate pixels on the display accordingly.
Figure 2
Figure 2: Version 3 Controller
Control Area Network: Serial Communication Protocol supporting distributed real­time control and multiplexing. The temperature and light sensors use this type of network.
Display Address: The display address is an identification number assigned to each display of a network. Rotating the address switches on the controller sets the display address. The control software uses the address to locate and communicate with each display. Displays that are on the same network cannot have the same address.
Galaxy
®
: Daktronics trademarked name for LED monochrome, tri-colored, or RGB
matrix displays.
Introduction
1-5
Driver/Pixel Board: The LED pixels are mounted directly onto the driver/pixel board. This board is also responsible for the switching and intensity levels of the LEDs.
LED (light emitting diode): Low energy, high intensity lighting units.
Louver: Black plastic shade positioned horizontally above each pixel row. The
louvers increase the level of contrast on the display face and direct LED light.
Module: 20mm Galaxy
®
modules are 16 pixels high by 16 pixels wide. Each is
individually removable from the front of the display.
Module Latch Assembly: Device utilizing a rotating retainer bar to hold the module firmly to the display frame. There are two per module: one near the top and one near the bottom. Use a 1/8" Allen wrench to turn the retaining bar.
Figure 3: 16x16 Module (Front and Back)
Network: A network consists of multiple displays connected to each other. Up to 240 displays can exist on one network.
Pixel: Cluster of LEDs. The number and color of the LEDs depends on display application.
Power Supply: Converts AC line voltage from the load center to low DC voltage for one or more module driver boards.
RS232: RS232 is a standard PC communication type with a maximum cable length of 25 feet (7.62 meters).
1-6
Introduction
RS422: RS422 is a standard differential communication type with a maximum cable length of 4000 feet (1.2 kilometers).
Serial Port: An actual serial port is required for direct connections through the j-box, signal converters or the radio j-box from the com puter. Certain USB adapters create an “actual” serial port.
Signal Converter: The signal converter, shown
Figure 4 on the right, is a Daktronics supplied
in unit that converts the data from RS232 to RS422, or RS232 to fiber optic signal. The signal converter is connected to the control PC via straight through serial cable.
1.6 Nomenclature
Figure 4: Signal Converter (RS232 to RS422 Shown)
Figure 5: Module Numbering Example – 48x160 Front
To fully understand some Daktronics drawings, such as schematics, it is necessary to know how various components are labeled in those drawings. This information is also useful when trying to communicate maintenance or troubleshooting efforts.
A module is the building block of the Galaxy pixels high by 16 pixels wide. By placing modules side-by-side and on top of one another, a display of any size can be designed and built. Individual modules can be easily removed from the display if required. Daktronics numbers modules on a Galaxy module numbering method.
In addition, the following labeling formats might be found on various Daktronics drawings:
Finally, Daktronics part numbers are commonly found on drawings. Those part numbers can be used when requesting replacement parts from Daktronics Customer Service. Take note of the following part number formats:
Introduction
®
display. Each module measures 16
Figure 5 above illustrates how
®
display. Figure 6 below breaks down the
“TB_ _” signifies a termination block for
power or signal cable.
“F_ _” represents a fuse.
“E_ _” shows a grounding point.
“J_ _” denotes a power or signal jack.
“P_ _” stands for a power or signal plug for
the opposite jack.
Figure 6: Module Numbering
1-7
“0P-_ _ _ _-_ _ _ _” indicates an individual circuit board, such as the
internal fiberboard.
“0A-_ _ _ _-_ _ _ _” stands for an assembly, such as a circuit board and the
plate or bracket to which it is mounted. A collection of circuit boards working as a single unit may also carry an assembly label.
“W-_ _ _ _” represents a wire or cabl e.
Cables may also carry the assembly numbering format in certain circumstances. This is especially true of ribbon cables.
0P-1195-0001
SN: 6343 05/19/99 REV.1
Figure 7: Typical Label
Most circuit boards and components within this display carry a label that lists the part number of the unit. If a circuit board or assembly is not listed in the Replacement Parts List in Section 4, use the label to order a replacement. A typical label is shown in
Figure 7. The part number is in bold.
1-8
Introduction
Section 2: Mechanical Installation
Note: Daktronics does not guarantee the warranty in situations where the display is not constantly in a stable environment.
Daktronics engineering staff must approve an of the display. If any modifications are made, detailed drawings of the changes must be submitted to Daktronics for evaluation and approval, or the warranty may be void.
Daktronics is not responsible for installations or the structural integrity of support
tures done by others. It is the customer’s responsibility to ensure that a qualified
struc
structural engineer approves the structure and any additional hardware.

2.1 Mechanical Installation Overview

y changes that may affect the weather-tightness
Because every installation site is unique, there is no single Daktronics-approved procedure for mounting the Galaxy section is general information only and may or may not be appropriate for your particular installation.
A qualified individual must make all decis display.
Read both the mechanical and electrical installati before beginning any installation procedures.
®
displays. The information contained in this

2.2 Support Structure Design

Support structure design depends on the mounting methods, display size, and weight. The structure design is critical and should be done only by a qualified individual. Display height and wind loading are also critical factors. It is the customer’s responsibility to ensure that the structure and mounting hardware are adequate.
Daktronics is not responsible for the installations or the structural inte gri t y of support structures done by others.
It is the installer’s responsibility to hardware are capable of supporting the display, and will agree with local codes.
Before beginning the installation proces s, verify the following:
The mounting structure will provide a straight and square-mounting frame
for the display.
The mounting structure is capable of supporting the display and will not
yield at any unsupported points after mounting.
Clearance: 3" of unobstructed space is available below the display for filter
removal from the display. 1-¼" of unobstructed space is available above the top of the display to remove the eyebolt and plug the hole properly.
Correct any deficiencies b
efore installation.
ensure the mounting structure and
ions regarding the mounting of this
on sections of this manual

Mechanical Installation

2-1
2.3 Ventilation Requirements
Reference Drawing:
Shop Drawing, AF-3150-**x**-20mm-R or A............... Drawing B-183660
Fans are mounted in the bottom of the display for ventilation. Maintain a minimum distance of 3" (7.62cm) below the display to maintain proper airflow. Refer to Drawing B-183660 for additional information.
If the display cabinet is completely enclosed:
12 square inches of unobstructed opening per module must be provided to
ensure adequate cooling.
Allowances must be made to compensate for the percentage of material
covering the openings in the structure.
For adequate cooling, forced ventilation may be required. If air is forced
into the enclosed cabinet, 110 cubic feet per minute must be provided per module (12.48" x 12.48" active area).
If these requirements are not met, the Galaxy

2.4 Lifting the Display

The top of the larger displays is equipped with eyebolts that are used to lift the unit. Take special care to ensure that the rated load of the eyebolts is not exceeded. Refer to the information at the end of this section labeled Eyebolts to determine the allowable load of the eyebolts shipped with the display.
Figure 8 below illustrates both the correct (left example) and the incorrect (right
example) method of lifting a display. Lift the display as shown on the left, with the lifting bar. Use every lifting point provided.
®
display warranty may be void.
2-2
Figure 8: Lifting the Display (Correct, Left; Incorrect, Right)
Do not attempt to permanently support the display by the eyebolts.
If removing the eyebolts, adequately seal the holes using 13 bolts and sealing washers, ½ inch in size. Silicone along the threads to ensure that water does not enter the display.
Mechanical Installation
2.5 Display Mounting
Reference Drawing:
Shop Drawing, AF-3150-**
The method used to mount displays can vary greatly from location to location. For
is reason, only general mounting topics can be addressed in this manual.
th
It is the responsibility of the installer to meet local codes and standards, as well as the mounting hardware and method.
Before beginning the installation proces s, verify the following items:
The mounting structure will provide a straight and square-mounting frame
for the display. Height variation in any fou r -f oo t hori zontal section may not exceed ¼-inch.
The mounting structure will not give way at any unsupported points after
the display is mounted.
The back of the display is equipped with 2 x 2 x 3 x ¼" steel clip angles. Refer to
rawing B-183660. These angles may be used for mounting purposes. Remember to
D
have all mounted displays inspected by a qualified structural engineer. Daktronics recommends using all clip angles as attachment points.
Refer to D attachment points needed and the wall structure must be reviewed by a quali fi e d structural engineer and meet all national and local codes. It is the customer’s responsibility to determine the proper wall mounting method and location.
rawing B-183660 for a suggested wall mount method. The number of
1. Carefu
2. Fol
3. W
4. Refer t
5. After in
lly uncrate the display. Look each side of the display over for
possible damage during shipping.
lowing the guidelines described in Section 2.4, lift the display into
position on the support structure.
eld or use ½" Grade-5 bolts and hardware to secure the clip angles to the
support structure as shown in Drawing B-183660.
o Section 3 for information on routing power and signal.
stallation is complete, carefully inspect the display for any holes that may allow water to seep into the display. Seal any openings with silicone. If the eyebolts on the top of the display have been removed, plug the holes with bolts and the rubber-sealing washer that was removed with the eyebolt.
x**-20mm-R or A...............Drawing B-183660
ensure the installation will adequately

2.6 Optional Temperature Sensor Mounting

If an optional temperature sensor will be used with this display, see Appendix C for connections, and other additional information.
Mechanical Installation
2-3
Eyebolts
Almost every display that leav es D ak tronics is equipped w ith ey ebolts for lifting the display . There are two standard sizes of eyebolts: ½ and A″.
Load Increase Factor: The load increases as the lift angle (θ) decreases. The allowable load on the eyebolts also decreases with the lift angle due the bending stress on the eyebolts. In sum, the smaller the angle between the cable and the top of the display, the lighter the sign must be to safely lift it. Do
NOT attempt to lift the display when the lift angle is less than 30 degrees.
Horizontal Load Angle
Angle Factor (L/H)
90 1.00 60 1.155 90 2600 2600 4000 4000 50 1.305 60 1500 1299 3300 2858 45 1.414 45 650 460 1000 707 30 2.00 30 520 260 800 400
θθθθ
½”
Line Weight/ Line Weight/
Load Anchor Load Anchor
A
A
AA
ED7244 Copyright 1996-2001 Rev. 4 – 14 March 2001 Daktronics, Inc.
Min.
A B C D E No.
Wx Wy Wz
1/4 1 3/4 1-3/16 25/32 21 600 2,000 Blank 1/4-20 7/8 400 100 80 3/8 1-1/4 1 1-21/32 1-3/16 23 2,100 5,000 Blank 3/8-16 1-1/8 1,400 350 250
1/2 1-1/2 1-3/16 2-1/16 1-13/32 25 3,900 9,200 Blank 1/2-13 1-11/32 2,600 650 520
9/16 1-5/8 1-9/32 2-13/16 1-17/32 26 4,500 11,830 Blank 9/16-12 1-3/8 3,000 750 600
5/8 1-3/4 1-3/8 2-1/2 1-11/16 27 6,000 14,700 Blank 5/8-11 1-9/16 4,000 1,000 800
3/4 2 1-1/2 2-13/16 1-13/16 28 9,000 21,700 Blank 3/4-10 1-5/8 6,000 1,500 1,200 7/8 2-1/4 1-11/16 3-1/4 2-1/16 29 10,000 30,000 Blank 7/8-9 1-13/16 6,600 1,670 1,330 1 2-1/2 1-13/16 3-9/16 2-5/16 30 12,000 39,400 Blank 1-8 2-1/16 8,000 2,000 1,600 1-1/2 3-1/2 2-9/16 5-1/2 3-5/32 34 27,000 91,300 Blank 1-1/2-6 3 17,800 4,500 3,600
Proof
Load (lbs.)
Min.
Break
Load (lbs.)
Stocked
Min.
Eff.
Thrd.
Length
Line Loads
A. Do not use eyebolts on angular lifts unless absolutely necessary. For angular lifts, the shoulder pattern
eyebolt is preferred.
B. Load should always be applied to eyebolts in the plane of the eye, not at some angle to this plane.
C. Shoulder eyebolts must be properly seated (should bear firmly against the mating part), otherwise the
working loads must be reduced to those indicated for regular eyebolts. A washer or spacer may be required to put the plane of the eye in the direction of the load when the shoulder is seated.
D. No load greater than the safe working load listed in the data table should be used.
E. To obtain the greatest strength from the eyebolt, it must fit reasonably tight in its mounting hole to prevent
accidental unscrewing due to twist of cable.
F. Eyebolts should never be painted or otherwise coated when used for lifting. Such coatings may cover
potential flaws in the eyebolt.
G. To attain the safe working loads listed for regular eyebolts, 90% of the thread length must be engaged.
Copyright 1996-2001 ED-7244 Daktronics, Inc. Rev. 4 – 14 March 2001
3: Section Electrical Installation
Only a qualified individual should terminate power and signal cable within this Daktronics display.
The Daktronics engineering staff must approve any changes made to the display. Before altering the display, submit detailed drawings for the proposed modifications to the Daktronics engineering staff for evaluation and approval, or the warranty will be rendered null and void.

3.1 Common Connectors in the Display

The power and signal connections in the displays use many different types of connectors. Tak e special care when disengaging any connector to prevent damage to the connector, cable, or circuit board.
When pulling a connector plug from a jack, do not pull on the wire or cable; pull on the jack itself. Pulling on the wires may damage the connector.
The following information presents some common connectors encountered during display installation and maintenance.
1. Ribbon Cable Connectors:
Figure 9 on the right illustrates a typical ribbon connector. To
disconnect the ribbon cable, push the plastic clips on the sides out to unlock and remove the jack.
Before replacing a ribbon cable connector, spray it with DeoxIT may cause signal problems. In addition, apply a generous amount of CaiLube
contact cleaner to remove any foreign matter that
protector paste to the plug before inserting it into the jack. This paste will protect both the plug and the jack from corrosion.
2. Termination Blocks:
Termination blocks are usually used to connect internal power and signal wires to wires of the same type coming into the display from an external source. Power wires need to have one-half inch of insulation stripped from the end of the wire prior to termination. Tighten all screws firmly to ensure a good electrical connection. Refer to
3. Phoenix
-Style Connectors:
Figure 10 on the right.
Phoenix-style connectors, which are usually green, are often used for signal termination on circuit boards . R e fer to
11
on the right. Strip one-quarter inch of insulation from the
Figure
wire prior to termination. To remove a wire, turn the above screw counter-clockwise to loosen the connector's grip on the wire. To insert a wire, push the bare wire into the connector and turn the above screw clockwise to lock the wire into place.
.
Figure 9: Ribbon Cable Connector
Figure 10: Termination
Block
Figure 11: Phoenix Connector

Electrical Installation

3-1
4. Mate-n-Lok Connectors:
The Mate-n-Lok connectors found in the displays are
white and come in a variety of sizes.
Figure 12 on the right
illustrates a four-pin Mate-n-Lok connector. To remove the plug from the jack, squeeze the plastic locking clasps on the side of the plug and pull it from the jack.
5. Phone Jacks (RJ Connectors):
RJ11 or RJ45 connectors, as seen in
Figure 13 on the lower
right, are similar to those on telephone and LAN connectors found in homes and businesses. They can be used on the ends of either flat cable or CAT5. In order to remove this plug from the jack, depress the small clip on the underside of the plug.
Before replacing an RJ connector, spray it with DeoxIT that may cause signal problems. In addition, apply a generous amount of CaiLube
contact cleaner to remove any foreign matter
protector paste to the plug before inserting it into the jack. This paste will protect both the plug and the jack from corrosion.
6. Quick Connect Jack:
The display uses quick connect jacks for the connection of such things as the temperature sensor, a client radio, and connection of the primary to the secondary or mirror display. The quick conne ct jacks are located on the back of the display and when not used the attached dust cover should be kept closed.
To attach the cable to a jack, make sure to line up the
plug to match the jack, push the plug in then turn the outer collar to lock in place. Figure 14 illustrates the 6­pin quick connect jack.
Figure 12: Mate­n-Loc Connector
Figure 13: RJ11
Figure 14: RS232/6-
pin Quick Connect Jack

3.2 Control Cable Requirements

RS232

This cable is a 2-conductor shielded cable used to transmit an RS232 signal (Daktronics part number W-1117). This shielded cable should not be subjected to mechanical flexing after installation. This cable is not for direct burial and should be routed in a dedicated, grounded metallic conduit from the j-box at the base of the sign structure to the display. This cable has a maximum length of 25 feet (7.6 meters).
3-2
Electrical Installation

RS422

This cable is a 4-conductor shielded cable used to transmit an RS422 signal (Daktronics part number W-1234). This shielded cable consists of paired wires. They should not be subjected to mechanical flexing after installation. This cable is not for direct burial and should have one of the following routings:
In dedicated metallic conduit
Inside buildings if cable is not in conduit, keep away from interference
signals
With interference signals, such as power conductors, intercom, etc., typically a two­foot separation is required. The maximum length of an RS422 signal cable is 4,000 feet (1.22 km).

Modem

The modem option will use standard telephone cable routed through conduit. The local telephone company will need to assist in this installation.
Ask the telephone company which colors are used for the tip wire and which for the ring wire for signal connections. Note: The telephone line to the display must be a dedicated line and not run through a switch board/communications system.

Fiber Optic

This cable is a 4-fiber cable (Daktronics part number W-1376). Two fibers are used for display communications and the other two are saved for spares. The cable may be either direct burial or routed in conduit, but it should not be subjected to mechanical flexing. The maximum length of a fiber optic cable is 2,000 feet (611.6 meters).

Radio

The Server radio, connected to the computer through a J-box, requires an 18-gauge six-conductor cable (Daktronics part number W-1370). Four-conductors will be used for the signal and two for power. This cable from the J-box to the Server radio, needs to be in conduit when exposed to outdoor conditions. The maximum distance from the J-box to the Server radio is 1000 feet (305.8 meters).
The Client radio at the display comes with cable that is rated for outdoor use and does not need to be in conduit. The cable should be secured to the structure so it cannot pulled loose from the display by weather or vandalism.

3.3 RJ Connector Cables

The conductor connector used in the network is an industry standard, 6-pin RJ11or 8-pin RJ45. This connector can be found on many telephones and LANs.
The cable used in the network is a standard flat six-conductor telephone cable (standard flipped cable). Refer to
Figure 15 on the right. This cable has one
end that is the mirror image of the other end (i.e. the cable is flipped). Refer to
Figure 16 for a standard flipped cable.
Electrical Installation
Figure 15: 6-Conductor RJ11 Connector and Cable
3-3
Notice below in
Figure 16 that the color code on one connector must be made the
opposite on the other connector. When installing a network, it is not easy to remember in which direction the previous end was oriented. One simp le way to avoid confusion is to standardize the color code, having one color for the connector going into the output of a sign, and the opposite color for a connector going into the input of a sign. This will help ensure correct cabling since cables are always installed from the output jack of one sign to the input jack of the next sign.
Figure 16: Flipped Cable with RJ Connectors

Installing an RJ Connector

Installing an RJ connector on the end of the conductor cable is a simple task when the correct tools are used. The RJ crimping tool (Daktronics part number TH-1033) performs two separate steps.
First, use the crimping tool to strip the outer insulation from the inner wires. This does not result in bare wires since only the gray outer jacket is removed. After correct stripping, the wire will appear as shown in
17
on the right.
The crimping tool is then used to crimp the RJ connector onto the cable. The RJ connector is locked into a special socket in the tool. The stripped wire is inserted into the RJ connector. Finally, the tool is squeezed like a pliers to crimp the connector onto the wire. This completes the installation of an RJ connector onto the wire.
3.4 Conduit
Reference Drawings:
Shop Drawing; AF-3150-**x**-20mm-R or A............... Drawing B-183660
Daktronics does not include the conduit. Refer to Drawing B-183660 for your display size and approximate locations for power and signal conduit. Separate conduit must be used to route:
Power
Signal IN wires
Signal OUT wires (if signal is required for another display)
Knockout holes for ½" conduit are located at the bottom right (rear view) of th e back of the display (refer to Drawing B-183660).
For displays with more than one face, signal and temperature sensor wiring between displays is normally done using the quick co nnect i nt erconnect cable, which does not need to be in conduit. When not using the quick connect cable, the cables for signal and temperature can be routed through the same conduit.
Figure
Figure 17: Wire with Outer Jacket Stripped
3-4
Electrical Installation

3.5 Preparing for Power/Signal Connection

Reference Drawings:
Component Layout Drawings................................... Refer to Appendix A
1. Remove the two bottom left modules (AX01 and AX02) to expose the
power enclosure and controller. Use a access fasteners one-quarter turn. Turn the top latch clockwise and the bottom latch counter­clockwise. Lift each module away from the display; reach behind it, and disconnect all power and signal connections.
2. Locate the controller and
power termination box for these displays in the
Component Layout Diagram located within Appendix A.
3. Punch or use 7/8" (0.875)
holes for the desired ½" conduits. Be careful that
none of the internal components are damaged.
Attach the conduit.
4. The controller receives the incoming signal and relays it to the individual
modules.
5. Rou te power to the display through a fused disconnect switch capable of
opening all ungrounded power con d uct or s. Inst all thi s di sconnect within the line-of-sight of any personnel performing maintenance on the display. If the disconnect is located out of sight of the display, it must be capable of being locked in the open position.
6. Power conductors from the disconnect to the display should be routed
through conduit in agreement with local code.
7. You may route the signal cable from the control computer to the display at
this time also. Unless you are using fiber, be sure to run the power and signal cables in a separate conduit.
1
/8" Allen wrench to turn the latch
Figure 18: Opening the Display
3.6 Power
Reference Drawings:

Power Termination Box................................................Drawing A-129227

Power Specs, 16x144-48x144 Displays......................Drawing A-180190
Schematics AF-3150-16x***-20mm, Mono.............. Refer to Appendix A

Power Requirements

Refer to Drawing A-180190 for voltage and current requirements for your display size and pixel color. Each uses a 120VAC or 120/240 VAC si ngl e- p hase p ower source. Depending on the module color and display size, the power supply may vary.
Do not connect the displays to any voltage other than that listed on the Daktronics product label.
Electrical Installation
3-5
Proper power installation is imperative for proper display operation. The following sub-sections give details of display power installation.

Grounding

This display is intended to be installed in accordance with the requirements of Article 600 of the National Electrical Code and/or other applicable local codes. This includes proper grounding and bonding of the display.
Displays must be grounded according to the provisions outl i ned in Article 250 of the National Electrical Code less.
The display system must be connected to earth-ground. Proper grounding is necessary for reliable equipment operation. It also protects the equipment from damage from electrical disturbances and lightning. The display must be properly grounded or the warranty will be void.
®
. Daktronics requires a resistance to ground of 10 ohm s or
3-6
Figure 19: Display Grounding
The material of an earth-ground electrode differs from region to region, and from conditions present at the site. Consult the National Electrical Code and any local electrical codes that may apply. The support structure of the display cannot be used as an earth-ground electrode. The support is generally embedded in concrete, and if in earth, the steel is either primed or it corrodes, making it a poor ground.
A minimum of one grounding electrode must be installed for each display face. The grounding electrode is typically one grounding rod for each display face. Other grounding electrodes as described in Article 250 of the National Electric Code may be used. Daktronics requires that the resistance to ground be 10 ohms or less. If the resistance to ground in higher than 10 ohms, it will be necessary to install additional grounding electrodes to reduce the resistance. The grounding electrode should be installed within 25 feet of the base of the display. The grounding electrode must be connected to the ground terminal in the display panel board.
Electrical Installation

Power Installation

There are two considerations for power installation: installation with ground and neutral conductors provided, and installation with only a neutral conductor provided. These two power installations differ slightly, as described in the following paragraphs:
rInstallation with Ground and Neutral Conducto s Provided
For this type of installation, the power cable must contain an isolated earth-ground conductor. Under this circumstance, do not connect neutral to ground at the disconnect or at the display. This would violate electrical codes and void the warranty. Use a disconnect so that all hot lines and neutral can be disconnected. Refer to requires the use of a lockable power disconnect within sight of or at the sign.
Figure 20 below for installation details. The National Electrical Code
Figure 20: Installation with Ground and Neutral Conductor Provided
Installation with Only a Neutral Conductor Provided
Installations where no grounding conductor is provided must comply with article 250-32 of the National Electrical Code. If the installation in question meets all of the requirements of article 250-32, the followi n g guidelines must be observed:
Connect the grounding electrode cable at the local disconnect, never at the
sign panel board.
A disconnect that opens all of the ungrounded phase conductors should be
used.
The neutral and the ground conductors should be bonded in the sign panel
board.
Refer to
Figure 21 below for installation details.
Electrical Installation
3-7
Figure 21: Installation with only Neutral Conductor Provided

Power Connection

Reference Drawings:
Power Termination Box............................................... Drawing A-129227
Schematics...............................................................Refer to Appendix A
Incoming power is connected within the power termination enclosure. Complete the following steps to terminate the hot and neutral wires at the termination block within the enclosure. Refer to Drawing A-129227 and the Schematic listed within
Appendix A for your display size.
1. Access the enclosure by removing the left bottom two modules as described in Section 3.5.
2. Route the power cables through the power conduit in the rear of the sign
and to the enclosure.
3. Conn ect the white neutral wire to neutral bus.
4. If one power line is being terminated (120VAC), connect the black “hot”
wire to L1. Make sure the jumper from L1 to L2 is in place as shown on
Drawing A-129227.
5. If two power lines are being terminated (120/240VAC). Connect the second
“hot” wire to L2. Make sure to remove the jumper between L1 and L2.
6. Conn ect the green grounding wire to the grounding bus E41.
3-8

Main Disconnect

The National Electrical Code requires the use of a lockable power disconnect near the display. Provide a lockable disconnect switch (knife switch) at the display location so all power lines can be completely disconnected. Use a 3-conductor disconnect so both hot lines and the neutral can all be disconnected. The main disconnect should be mounted at or near the point of power supply connection to the display. A main disconnect is to be provided for each supply circuit to the display.
The disconnecting means must be located in a direct line of sight from the display or outline lighting that it controls. This requirement provides protection by enabling a worker to keep the disconnecting means within view while working on the display.
Exception: Disconnecting means that are capable of being locked in the open position may be located elsewhere.
Electrical Installation

3.7 Signal Termination from Computer to Display

Figure 22: Signal Termination at Display (Front View)
Figure 22 gives the general location of various control components of the display.
The location of the display controller and power termination panel may vary slightly depending on the height of the display. Note: The AF-3150 is designed for quicker connection to other displays, and to addition components such as a temperature sensor or a client radio. Connection of the communication equipment to the primary display can be done using a cable with a quick connect or can be wired directly to the controller in that display. Depending on the number of displays and the communication type ordered, the following cables may be provided with the displays:
1. Interconnect cable from primary display to secondary display, length 4 feet.
2. Temperature sensor with quick connect cable, length 25 feet.
3. Client radio with qu ick connect cable, length 25 feet.

RS232

Reference Drawings:
System Riser Diagram, RS232....................................Drawing A-174341
Schematic, Internal, W/Quick Connect........................Drawing B-177662
An RS232 controlled display requires the use of a J-box within 25 feet of the display as shown in using a quick connect cable or wired directly to the controller inside the disp lay. The non-quick connect cable from the J-box to the display must be routed though conduit. Do not run signal and display power through the same conduit.
1. If using a quick connect cable, connect from the J-box to the RS232 top
2. When connecting directly to the display, terminate the wire to the terminal
Figure 23. From the J-box to the display, the signal may be connected
jack (J33) on the back of the display.
block in the J-box and the other end to the 6-position Phoenix plug on the controller labeled “RS232 IN” (TB1). Drawing B-177662 and
Figure 24
below shows the terminal block wiring.
Electrical Installation
3-9
The controlling laptop computer connects to the J-box through a DB9 to DB25 serial cable (refer to Drawing A-174341).
Figure 23: RS232 Display Layout
Figure 24: J-box to RS232 IN on Controller Board
J-Box to Controller
J-box Wire Color Controller (TB1)
Pin 1 (TX-P) Black Pin 5 (RX1)
Pin 2 (RX-P) Clear or Red Pin 3 (TX1)
Pin 3 (GND) Shield Pin 4 (GND)
3-10
Electrical Installation

RS422

Reference Drawings:
System Riser Diagram, RS422....................................Drawing A-174135
Schematic, Internal, W/Quick Connect........................Drawing B-177662
An RS422 controlled display requires the use of signal converter near the computer. From the signal converter, cable is run to the surge board assembly in the display or to a junction box. The junction box has a quick connect plug, which will be connected to the display. In either case, the cable from the signal converter to the surge board must be routed though conduit. Do not run signal and display power through the same conduit. Refer to layout.
1. If using a quick connect cable, terminate the 4-conductor shielded cable at
the signal converter, and to the surge board in the junction box. A quick connect cable will then go to the RS422 middle jack (J32) on the back of the primary display.
2. When connecting directly to the display, terminate one end at the signal
converter and the other end of the 4-conductor shielded cable to the 6­position terminal block on the surge board labeled “RS422 IN” (TB1).
Drawing B-177662 and
3. The computer connects to the signal converter using a DB9 to DB25 serial
cable.
Figure 25 and Drawing A-174135 for system
Figure 26 below show the terminal block wiring.
Figure 25: RS422 Display Layout
Electrical Installation
3-11
i
g
y
F
ure 26: Signal Converter to Surge Suppresser in Displa
Signal Converter to Surge Suppressor Board
Signal Converter
(J4 or J5)
Pin 1 (GND) Shield Pin 1 (N.C.) Pin 2 (RX-P) Red Pin 2 (TX-P) Pin 3 (RX-N) Black Pin 3 (TX-N)
Pin 4 (TX-P Green Pin 4 (RX-P)
Pin 5 (TX-N) White Pin 5 (RX-N)
Pin 6 (GND) Pin 6 (N.C.)
Wire Color Surge Board Assembly
(TB1)

Modem

Reference Drawings:
System Riser Diagram, Modem .................................. Drawing A-174342
Schematic, Internal, W/Quick Connect........................ Drawing B-177662
A modem-controlled display requires the use of an internal or external modem at the computer. The local phone company must provide a dedicated phone line to the display and identify the colors used by the Tip wire and the Ring wire. The telephone cable is run to the modem board in the display or is connected to a junction box with a quick connect plug that connects to the display. The phone cable must be routed though conduit. Do not run signal and display power through the same conduit. Refer to
Figure 27 and Drawing A-174342 for the system layout.
3-12
Electrical Installation
1. If using a quick connect cable, connect the phone wires to the modem
board, at J2, in a junction box. A quick connect cable will then go to the RS232 top jack (J33) on the back of the primary display.
2. When connecting directly to the modem in the display, terminate the tip and
ring wires to TB2 on the modem board. If the phone company provided a phone termination box for the tip and ring wires in the display, a straight phone cable (Daktronics part number 0A-1137- 01 6 0) can b e connected from the box to the J5 Phone IN on the modem board in the display.
Drawing B-177662 and
Figure 28 shows the terminal block wiring.
3. For modems in the display, an 8-conductor cable with RJ45 connectors
(Daktronics part number 0A-1229-0054) relays the signal from J6 on the modem to J3 (RS232 IN) on the controller.
Figure 27: Modem Display Layout
Note: The jumper on the controller board must be closed to recognize that a modem is being used with the display. The jumper is recognized only on boot up.
Figure 28: Modem/ Signal Connections
Phone Line to Phone Termination Block
Field Cabling Phone Line (TB2)
Red Pin 1 (Tip)
Green Pin 2 Ring)
Electrical Installation
3-13

Fiber Optic

Reference Drawings:
System Riser Diagram Fiber ....................................... Drawing A-174344
Schematic, Internal, W/Quick Connect........................ Drawing B-177662
A fiber-controlled display requires the use of a signal converter near the computer. From the signal converter, cables are run to the fiberboard in the display or in a junction box. The fiber cables from the signal converter to the display can be routed through conduit. In the case of fiber only, signal and display power can be run through the same conduit. Refer to layout.
1. If using a junction box with a quick connect cable, connect the two fiber
cables from the signal converter (either J2 and J3, or J4 and J5) to J5 and J4 on the fiberboard. The quick connect cable will connect to the RS232 top jack (J33) on the back of the primary display.
2. When connecting directly to the fiberboard in the display, route the cable to
the fiberboard and connect the two fibers to J5 and J4. Always connect transmit (TX) at the signal converter to receive (RX) on the display’s fiberboard, and RX to TX as shown in
3. The fiberboard in the display, connects to the display’s controller via an 8-
pin RJ45 cable (Daktronics part number 0A-1229-0054) from J7 on the fiberboard to J3 (RS232 IN) on the controller.
4. The computer connects to the signal converter using a DB9 to DB25 serial cable.
Figure 29 and Drawing 174344 for the system
Figure 30 and Drawing B-177662.
3-14
Figure 29: Fiber Optic Display Controller
Electrical Installation
Figure 30: Fiber Signal Connections
Signal Converter to Display Fiber Board
Signal Converter Field Cabling Display Fiber
Board
J2 Transmit (TX1) (Color varies) J5 Receive (RX2)
J3 Receive (RX1) (Color varies) J4 Transmit (TX2)

Venus® 1500 Radio Client

Reference Drawings:
System Riser Diagram, QC Outdoor Radio, Gen 2.....Drawing A-185359
Schematic, Internal, W/Quick Connect........................Drawing B-177662
A radio-controlled display requires a Server radio connected via a J-box to the control computer, and a Client radio at the display. The radios must be within line­of-site of each other.
Figure 31 on the next page and Draw i ng A-185359 shows the layout to the Server
radio through a J-box. The Client radio is mounted near the display, and is supplied with 25 feet of weather resistant cable. One end of the cable is pre-terminated to TB1 inside the radio enclosure, and a quick connect plug is terminated at the other end of the cable. The quick connect cable connects to the primary display.
1. Connect the DB9M to DB9F serial cable from the computer’s serial port to
the J-box labeled “V1500 PC Connect”
2. Connect an 18 AWG, 6-conductor cable from the J-box near the computer
to the to the Server radio. The distance from the J-box to the Server cannot
Electrical Installation
3-15
exceed 1000 feet. Refer to the Venus 1500 Radio Manual, ED13932, for J­box and Server connections.
3. Using the quick connect cable, as shown in
Figure 32, connect from the
Client radio to the RS232 top jack (J33) on the back of the primary display. (Secure any additional cable to prevent it from being pulled loose by weather or vandalism.)
Figure 31: Radio Display Layout
Figure 32: Radio Client Connection
3-16
Electrical Installation

3.8 Signal Termination Between Two (or More) Signs

Reference Drawings:
Schematic, Internal, W/Quick Connect........................Drawing B-177662
Controller, Galaxy, 8-conn., J-1087.............................Drawing B-177838

RS422 Interconnection

The quick connect cable is the most common method of terminating signal between two displays. The four-foot cable goes from the RS422 OUT (J34) on the primary display to the RS422 IN (J32) on the secondary display.
If the displ a ys are not bac k-to-back, or are too far apart for the quick connect interconnect cable to reach, a 4-conductor shielded cable can be used. One end will connect at the “RS422 OUT” 6-position terminal block (TB3) on the controller of the primary display, and the other end of the cable will terminate on the “RS422 IN” 6­position terminal block (TB2) on the controller of the secondary display.
Figure 33: Quick Connect Cable
Figure 34: RS422 Signal Termination Panels
Pin 2 (D2OUT-N) Red Pin 5 (D1IN-N)
Electrical Installation
Primary
RS422 OUT
(TB3)
Pin 1 (GND) Shield Pin 6 (GND)
Pin 3 (D2OUT-P) Black Pin 4 (D1IN-P)
Pin 4 (D2IN-N) Green Pin 3 (D1OUT-N)
Pin 5 (D2IN-P) White Pin 2 (D1OUT-P)
Pin 6 (Shield) Pin 1 (Shield)
Field
Cabling
Secondary
RS422 IN
(TB2)
3-17

Fiber Interconnection

Reference Drawings: Sys
tem Riser Diagram, Fiber ...................................... Drawing A-174344
A four-conductor fiber cable is used in connecting two or more displays in the Fiber Interconnection method. Connect the fiber cable to the fiber cards of the display as described in Drawing A-174344 and on the following table:
Primary - Data Out
(A34)
J2 Transmit (TX1) (color varies) J5 Receive (RX2)
J3 Receive (RX1) (color varies) J4 Transmit (TX2)
Field
Cabling

3.9 Optional Temperature Sensor

If you are using an optional temperature sensor with your display, see Appendix C for mounting and signal information.
3.10 First Time Operation
When first operated, the display will run through an initialization in which it will display the following:
oduct Name (Galaxy®)
1. Pr
splay Size (Row x Column)
2. Di
3. Sha
4. Bootloa
5. Firm
6. Firm
7. Har
8. Soft
9. I
10. Su
11. C
12. Li
13. Display
ding (64 Mono)
der Version (OS X.XX)
ware Number (ED13305) ware Revision (Rev X.XX)
dware Address (HW:XX)
ware Address (SW:XX)
P Address: (172.16.192.25)
bnet Msk: (255.255.0.0)
OM1 Configuration (C1:V15) ((Modem C1:V15) If a Modem is present)
ne Frequency (CLK:60 Hz)
Name Description
Secondary - Data
In (A34)
3-18
Electrical Installation
Section 4: Maintenance and
Troubleshooting
Important Notes:
1. Power must be turned off before any repair or maintenance
work is done on the display.
2. Qualified service personnel must make any access to internal
display electronics.
3. The Daktronics engineering staff must approve ANY changes made to the display. Before altering the display, detailed drawings for the proposed modifications must be submitted to the Daktronics engineering staff for evaluation and approval or the warranty will be rendered null and void.

4.1 Maintenance and Troubleshooting Overview

Daktronics Galaxy® series AF-3150 displays are front accessible; meaning access to the internal components can be gained only from the front of the display.
This section provides the following Galaxy
Signal Routing Summaries provide a basic explanation of the way signal
travels through the display.
Power Routing Summaries explain the basic way power travels through
the display.
Service and Diagnostics give instructions for removing various display
components, and explains the functions of circuit board connectors and the use of any diagnostic LEDs.
Maintenance includes a number of steps to take to keep this Galaxy
display in a safe, working order.
Troubleshooting lists some possible display malfunctions, and provides a
number of possible causes for that malfunction.
Replacement Parts List provides the descript ion a n d part number of
display components that may need replacing during the life of this display.
Exchange and Repair and Return Programs explain Daktronics
component return policy.
®
display information.
®

Maintenance and Troubleshooting

4-1
4.2 Signal Summary
The signal routing for the display can be summarized as follows:
1. Data from the control computer, which runs Venus
via RS232, RS422, modem, fiber optic cable, or radio signal to the display.
2. For multiple face displays or a display network, an RS422 quick connect
cable (most typical) relays signal between the controller of the primary display and the controller in the secondary display. In the case of fiber, two fibers would connect from the fiberboard in the primary display to the fiberboard in the secondary display.
3. From the controller, the signal then travels over one or more 20-conductor
ribbon cables (J11 through J18 provide signal out) to J2 on the first row of modules in the display.
4. Data exits at J1 and is relayed to J2 of the next module and so on, traveling
down the entire row of modules. The modules use this display data to control the LEDs.
®
1500 software, travels
Figure 35: Power/Control Corner
4.3 Power Summary
Reference Drawings:
Schematics...............................................................Refer to Appendix A
The power routing for the display can be summarized as follows:
1. Incoming power terminates at the power termination enclosure. Before
leaving the enclosure, power is sent through a circuit breaker and an RFI electrical filter. See display Schematic for details.
2. Power for the controller board passes through a transformer located in the
power termination box.
4-2
Maintenance and Troubleshooting
e power supplies are set to 3.6 VDC. Power supplies are preset. Contact
3. Th
Daktronics Customer Service for the proper settings.
4.4 Service and Diagnostics
Reference Drawings: Power Termination Box Controller, Galaxy, 8-c
hematics............................................................... Refer to Appendix A
Sc
Comp. Layout Diagram;........................................... Refer to Appendix A
The following sub-sections address servicing of th
transformer, RFI filter
controller
modules, drivers and power supplies
The sub-sections also address any diagnostic LEDs, connectors found on the unit. On the Schematics and Component Layout Diagrams, the components are denoted as follows.
Component… Denoted As… Location…
Filter and Transformer
Controller 0A-1229-0005 Depends on the size of the display. (usually
Modules Squares A101 through A309
0A-1266-2004-Red
0A-1266-2005-Amber
Power Supplies 0A-1289-4011
Light Detector 0A-1247-0003 Behind\below the bottom left module Modem 0P-1279-0003 Close to the controller, usually in the left end
Fiber Board 0P-1127-0024 Close to the controller, usually in the left end
RS422 Surge Card
................................................Drawing A-129227
onn J-1087...............................Drawing B-177838
e following display components:
fuses and signal/power
0A-1289-4005 Inside the power termination box
behind the bottom left module, or module one row above)
Over entire face of the display (includes driver)
Behind modules (refer to your display’s
or
0A-1289-4012
0P-1146-0031 Close to the controller, usually in the left end
Schematic and Component Layout Diagram)
of the display. Refer to the display’s Schematic
of the display. Refer to the display’s Schematic
of the display. Refer to the display’s
Schematic
Maintenance and Troubleshooting
4-3

Transformer and RFI Filter

Remember: Disconnect power before servicing any internal components.
Figure 36: Power Termination Box
fTrans ormer
The transformer is located in the upper portion of the power termination box. Turn off power to the display before removing the wires.
To replace the transformer:
1. Disconnect and label all the wires attached to it.
2. Release the hardware securing it to the inside of the enclosure.
3. Position the new transformer in its place, and tighten it down.
4. Re-connect all the wires using the display’s Schematic as a reference.
RFI Filter
The RFI electrical filters are mounted above and to the side of the power termination box (Z1 and Z2 in Drawing A-129227).
To replace the RFI filter:
1. Remove all connecting wires.
2. Releasing the attachment hardware.
3. Replace the filter.
4. Install the new filter using the display’s Schematic as a wiring reference.
4-4
Maintenance and Troubleshooting

Controller

The controller sends data to the modules. Refer to the signal summary in Section 4.2 for more information and to the Component Layout Diagrams for the position of the controller board.
Figure 37 below illustrates a typical controller.
Figure 37: Controller Component Layout
The rotary switches set the hardware address, which the software uses to identify that particular display. When replacing a controller board, be sure to set the rotary switches to the same address configuration as the defective controller. Each controller in a network needs a unique address.
Note: Setting both rotary switches to address 0 (set the switches to 0 by rotating them counter clockwise until the arrow points to 0) can set a test mode. The display’s power must be turned off and then turned back on to recognize a change in address. The display can also be put into test mode using the software.
Complete the following steps to remove the controller from the display:
Tools required: 1/8" hex wrench and 3/16" nut driver
1. Remove the module directly in front of the controller.
2. Label the cables before removing them from the controller.
3. Disconnect pow er from J5.
4. Remove all signal connections from the board. Pushing apart the latches
and carefully pulling them from the jack will release the “Locked” connectors
5. The board is held in place using six screws. Remove the screws using a
3/16" nut driver.
6. Follow the previous steps in reverse order to install a new controller board.
Maintenance and Troubleshooting
4-5
Controller Address Settings
S2
Upper
0 0 Test Mode 0 1 1 0 2 2 0 3 3 0 4 4 0 5 5 0 6 6 0 7 7 0 8 8 0 9 9 0 A 10 0 B 11 0 C 12 0 D 13 0 E 14 0 F 15 1 0 16 1 1 17
… … …
F 0 240
S1
Lower
Four diagnostic LEDs are located on the controller; the LED denotes:
CPU LED Color Function Operation
DS1 Red CAN TxD Flashes when controller is transmitting CAN
DS2 Red CAN RxD Flashes when controller is receiving CAN
DS3 Red System
Reset
DS4 Red Run A steady flash indicates the controller is running
DS5 Red U15
Programmed
DS6 Red U7
Programmed
DS7 Red Link On when Ethernet interface is in the link-up
DS8 Red Speed On when the Ethernet interface is at 100Mbps.
DS9 Red Duplex On when the Ethernet interface is at full duplex.
Address
table below tells what each
information.
information. Off when controller is functioning properly.
Flashes at 1.5-second rate if controller is not resetting the watchdog timer.
properly. Normal flash rate is about once per second.
On when U15 contains a valid logic program.
On when U7 contains a valid logic program.
condition. Flashes when the Ethernet chip detects transmits or receives activity.
Off when the Ethernet interface is at 10Mbps.
-
4-6
Maintenance and Troubleshooting
duplex.
DS10 Red Collision Flashes when the Ethernet interface detects a
collision in half-duplex. DS11 Red +5V On when +5V power supply is functioning. DS12 Red +3.3V On when +3.3V power supply is functioning. DS13 Red +2.5V On when +2.5V power supply is functioning.
Product Board LED Color Function Operation
DS1 Green +5V On when +5V power supply is functioning. DS2 Green +3.3V On when +3.3V power supply is functioning. DS3 Yellow COM1 TxD Flashes when transmitting serial information. DS4 Yellow COM1 RxD Flashes when receiving serial information.
Temp/Light Sensor LED Color Function Operation
DS1 Green +5V On when +5V power supply is functioning. DS2 Red Run A steady flash indicates the controller is running
correctly. Normal flash rate is about once a
second. Flashes faster when the sensor is
transmitting temp or light information.

Modules and Drivers

The module and driver board are a single functional unit.
To remove a module, complete the following steps:
Tools required: 1/8" hex wrench
1. Locate the latch access fasteners on the
module. One is centered below the second row of pixels and one is centered above the bottom row.
2. With a 1/8"hex wrench, turn the latch
access fasteners a quarter turn as seen in
Figure 38. The top one should be turned
clockwise and the bottom one counter­clockwise.
3. Pull the display module far enough to
reach around the back and disconnect the ribbon and power cables.
When installing a module, reverse the previous steps and take note of the following points:
The weather-stripping on the back edge
Figure 38: Removing a Module
of the module must be intact and in good condition if it is to prevent water from seeping into the display.
The module latches must be fully engaged to create a watertight seal around
the edge of the module. The module should be firmly seated against the display when the latches are fully engaged.
Each module assembly is made up of a module housing (containing LEDs and the driver) and a louver assembly.
Maintenance and Troubleshooting
4-7

Power Supplies

The LED power supplies are identified as assemblies. Each power supply unit controls four modules; a power supply assembly (two power supply units) controls eight. The LED power supplies are identified as assemblies 0A-1289-4011 and 0A­1289-4012 in the Component Layout Diagram.
Complete the following steps to remove a power supply from the display:
Tools required: 1/8" hex wrench and #2 Phillips screwdriver
1. Remove the module directly in front of the failed power supply.
2. Disconnect and label all the wires connected to the power supply.
3. Remove the hardware holding the power supply in place to free the unit.
4. Follow these steps in reverse order to install a new power supply. Refer to the display’s Schematic when reconnecting the wires.

Light Detector

The light detector is internally mounted and wired at Daktronics. It is located in the bottom left corner on the front of the primary display (identified as assembly 0A­1241-4013 (LT) in the Component Layout Diagram). A 4-conductor cable connects the light detector to J9 on the controller (refer to your display’s Schematic). When the displays are mounted back-to-back, only the primary side has a light sensor.

Modem

If a modem was included with the display, it is located inside the display next to the controller board.
Complete the following steps to replace a modem in the display: Tools required: 1/8" hex wrench and
3/16" nut driver
1. Remove the module directly in front of the modem.
2. First disconn e ct and label all the wires
connected to the modem (refer to on the right for the cable locations).
3. The modem is held in place with four screws. Remove the screws using a 3/16" nut driver and lift the modem out of the display.
4. Follow these steps in reverse order to install a new modem.
The modem module has five LEDs.
1. The Power LED should remain lit while power is applied to the modem.
2. The Carrier Detect LED will light when the modem is in the process of communicating.
3. The modem RX and TX will flash when communicating with another modem.
4. The PC Connect LED is not used when this modem is mounted in a display.
Figure 39
Figure 39: Modem
4-8
Maintenance and Troubleshooting
The modem board also has several input and output jacks:
1. J3 is the power input for 12 VAC
2. TB2 is a pho enix connector to terminate the Tip and Ring wires
3. J5 is an RJ11 jack for termination of a pre-terminated phone line
4. J6 is the RS232, RJ45 output to the controller
5. J2, TB1, and TB3 are not used in this display application
A modem system requires a jumper (X1) to be set on the controller board. For a modem system the jumper must jump both pins. The jumper position is only recognized on power-up. Refer to the
Figure 40 below for the location, and the
jumper settings.
Figure 40: Modem Jumper Location

Fiber Board

If a fiberboard was included with the display, it is located inside the display next to the controller board.
Complete the following steps to replace a fiber optic board: Tools required: 1/8" hex
wrench and 3/16" nut driver
1. Remove the module directly in front
of the modem.
2. Disconnect and label the power and
signal connections (refer to
41 on the right for disconnection of
wires).
3. The fiber optic board is held in
place with four 3/16" screws. Carefully remove them.
4. Install the new fiberboard, replace
the screws, and reconnect power and signal cables.
Figure
Figure 41: Fiber Optic Board
Maintenance and Troubleshooting
4-9
The fiber module has three LEDs.
1. The power LED (DS1) shou ld remain lit while power is applied to the board.
2. The receive LED (DS2) will flash when the display fiberboard is accepting
signals from the signal converter.
3.
The transmit LED (DS3) will flash when the display fiberboard is sending signals to the signal converter.
In addition, the fiber module has several input and output jacks:
1. J6 is the power input for 12VAC.
2. J5 and J4 are the inputs from the signal converter by the computer, or the previous display connects.
3. J3 and J2 are the outputs to the fiberboard in the next display, if necessary.
4.
J7 is the RS232 output that connects to the J3 on the controller board via an 8-conductor, RJ45 cable (Daktronics part number 0A-1229-0054).
5.
J1 is used when the fiberboard is mounted in an enclosure.

RS422 Surge Suppressor

The surge suppressor is an inline device that is used to filter the RS422 data line. It suppresses surges down to a low voltage in order to protect the display controller’s RS422 input. If a fiberboard was included with the display, it is located inside the display next to the controller board.
To replace the RS422 Surge suppressor board: Tools
required: 1/8" hex wrench and 3/16" nut driver
1. Remov e the module directly in front of the surge
board.
2. Disconnect and label the signal connections (Refer
Figure 42 on the right).
to
3. The surge suppressor is held in place with four 3/16" screws. Carefully remove them.
4. Install the new surge suppressor, replace the screws, and reconnect power and signal cables.
The surge suppression board has two inputs and two outputs.
1. The cable from the signal converter by the display will connect to TB1.
2. The signal from the RS422 output (TB2) on the surge board connects to the RS422 input (TB2) on the controller.
3. J2 will used to connect to the controller board when the surge board is mounted in an enclosure.
4. J1 and J2 are more often used when the board is part of an indoor display application.
Note: The surge suppressor must be firmly connected to the display chassis in order to be effective. The mounting hardware used to secure the surge suppressor is sufficient if it is fastened properly.
Figure 42: Surge Suppressor, RS422
4-10
Maintenance and Troubleshooting

Location of CAN Termination Jumper

Temperature and light sensors are controlled as part of a CAN network. For the CAN network to work correctly, the network must be terminated at both ends of the network. This is true for a single display, or for multiple displays. The correct terminations are completed during the building process. However, if the order or number of displays is changed on-site, the terminating jumper (W1) may need to be relocated.
Figure 43: Displays with No External Temperature Sensor
In the case of those displays that utilize a temperature sensor, the sensor is internally terminated. Therefore, only one other termination needs to be made at the output of the last sign in the network. The most common input location for the temperature sensor is to the primary display in the network.
Figure 44: Displays with External Temperature Sensor
The terminating jumper is located on the quick connect board on the inside of the display. Most displays have both an input and an output quick connect board. When no output board is available, the terminating jumper (W1) will be placed on the input board of the last display. Therefore, both boards are shown in above.
Figure 43 and Figure 44
Maintenance and Troubleshooting
4-11
Figure 45: Quick Connect Boards

4.5 Ventilation Systems (With Fans and Filters)

Ventilation fans should be checked after 1,500 hours of operation and every 1,500 hours after that to ensure the display is being cooled properly. Fans should be checked more often if the display is located in a dusty or harsh weather environment (i.e. along a gravel road with dust laden air).
1,500 hours is equivalent to 83 days if the display is operated for 18 hours a
day, and the power to the display is turned off when not in use.
1,500 hours is equi val ent t o 6 2 day s if t he displ a y is ru nning non-stop for 24
hours a day.
Each time a module is removed, for whatever reason, take a minute to
inspect the fans.
Check the fan blades for dirt and debris. If the fan blades have a large
accumulation of dirt and debris, this indicates that the filters must be changed more often. Fan blades must be kept clean to maintain fan efficiency and ensure proper cooling.
Spin the fan blades with a pen or pencil to ensure that the bearings are free
and the fan is still in balance.
To check the operation of the fans, push the bypass button (momentary contact) on the thermostat enclosure to temporarily turn the fans on: (The bypass button is located behind A102, top row, and second module from the left, as shown in
35
.)
Figure
4-12
Maintenance and Troubleshooting
Hold your hand or a piece of light paper beneath the display to detect air
movement.
If the fan does not turn or does not operate smoothly, replace it.
Filters must be checked once a year or after whichever comes first.
Filters can be cleaned with water and a mild detergent, such as dish soap.
mpressed air can also be used to clean the filters provided the nozzle is held at
Co least six inches away from the filter, the pressure is no greater than 60 psi, and the air is blown through the filter in the opposite direction from which air normally flows. The arrow stamped on the frame filter indicates airflow direction.
4.6 Thermostats
Reference Drawing:
Comp. Layout Diagram;
A thermostat controls when the ventilation fans are turned on in the display. Refer to
e Component Layout Diagram and
th The ventilation fans turn on when the inside of the display reaches 85° F (29° C), and turn off at 70° F (21° C).
every 1,500 hours of operation,
...........................................Refer to Appendix A
Figure 35 for the location of the thermostat.
4.7 Weather Stripping
To ensure that the display is waterproof, weather stripping has been provided around the entire display and around each module. It is important that the weather stripping is installed properly at all times or water may leak into the display and damage the components.
4.8 Display Maintenance
A yearly inspection should be completed to maintain safe and dependable display operation. This inspection should address the follo wing issues.
Loose Hardware
Verify fasteners, such as bolts and riv
should be checked, tightened, or replaced as required.
Excessive Dust Buildup
Occasionally it may be necessary to vacuum the inside of the display
inet to remove dust/dirt buildup that may interfere with airflow.
cab
Water Intrusion – Water Stain Marks
Water can enter the display where weather stripping has come loose or
eriorated, where fasteners have come loose allowing gaps in the panels,
det or where moisture may be entering around hardware. Be sure to check around the lift eyes and bolts to ensure that water has not entered there. If so, replace hardware immediately to prevent more water from entering the display. Also, check electronic components for possible corrosion.
ets, have not come loose. Fasteners
Maintenance and Troubleshooting
4-13
Corrosion
Check the paint, and look for possible corrosion especially at footings,
ructural tie points and ground rods.
st
If any of the above conditions are noticed, ac situation.
4.9 Troubleshooting
This sub-section contains some symptoms that may be encountered in the displays. This list does not include every possible symptom, but does represent common situations that may occur.
Symptom/Condition Possible Cause/Remedy
One or more LEDs on a single module fail to light.
One or more LEDs on a single module fail to turn off.
A section of the display is not working. The section extends all the way to the right side of the display.
One row of modules does not work or is distorted.
A group of modules, (a column of block) which share the same power supply assembly, fail to work.
Entire display fails to work. Check for proper line voltage into the power
Temperature always reads –196F/­127C degrees F/0 degrees C.
4-14
tion must be taken to correct the
Replace/check ribbon cables on the module.
Replace the module.
Replace/check ribbon cables on module.
Replace the module.
Note: LED in bottom right hand corner will flash
indicating the display has power and firmware, but no message has been sent.
Check/replace the ribbon cable to the first non-
working module.
Check power to the modules.
Move or replace the first module to the left of the
first module that is not working.
Move or replace the second module that is not
working.
Check or replace the power supply assembly on
the first module that is not working.
Check/replace ribbon cable to first module.
Replace or move first module.
Check for bent pins on module and controller.
Try the output from a different row on the
controller.
Replace controller.
Check the fuses in the power termination box.
Check the wire connections at the power supply.
Measure the power (3.6 VDC) to the first module.
Replace the power supply assembly.
termination panel.
Check fuse in power termination box
Check for correct power to controller (10 VAC)
and modules (3.6 VDC).
Disconnect signal cables to the controller, and
check for power to controller.
Check/replace the ribbon cable from the controller
to the modules.
Check the voltage settings on the power supplies.
Check/replace the signal cable to the controller.
Replace the controller.
Verify proper use of the software in the operation
manual (ED13530).
Check temperature sensor connections.
Check for bent pins or misconnection on quick
connect cable.
Maintenance and Troubleshooting
Check for address 1 on the temperature sensor.
Replace the temperature sensor.
Replace the controller.
Display is stuck on bright or dim. Check Manual/Auto dimming in Venus 1500
software.
Check light detector cable connections.
Check light detector for obstructions.
Check for bent pins on controller connection.
Check for address 2 on the light sensor.
Replace the light detector.
Replace the controller.
4.10 Initial Operation Information
Every time the display is operated, the display will run through an initialization in which it will display the following:
oduct Name (Galaxy®)
1. Pr
splay Size (Row x Column)
2. Di
3. Sha
4. Bootloa
5. Firm
6. Firm
7. Har
8. Soft
9. I
10. Su
11. C
12. Li
13. Display
ding (64 Mono)
der Version (OS X.XX)
ware Number (ED13305) ware Revision (Rev X.XX)
dware Address (HW:XX)
ware Address (SW:XX)
P Address: (172.16.192.25)
bnet Msk: (255.255.0.0)
OM1 Configuration (C1:V15) ((Modem C1:V15) If a Modem is present)
ne Frequency (CLK:60 Hz)
Name Description
Maintenance and Troubleshooting
4-15
4.11 Replacement Parts List
The following tables contain some of the items that may need to be replaced in these displays over a period of time. Many of the parts within the display also list their part numbers on labels affixed to them.
To prevent theft, Daktronics recommends purchasi manuals and replacement/spare parts.
Part Description Part Number
Controller II, 48x256, Louvered Galaxy 0A-1229-0005 Module, 1R (1:1) 16x16 (30x70), Coated, Type 2 0A-1266-2004 Module, 1A (1:1) 16x16 (30x70), Coated, Type 2 0A-1266-2005 Digital Temp Sensor 0P-1247-0007 Light Level Detector 0P-1247-0003 Filter; Air, Gasket, 7.50” x 13.50” x .88” EN-1774 Fan; 110 CFM @120V, 60HZ, 29-24 watts B-1006 Transformer; Pri 115V, Sec 10VCT@3A (120V
Displays) Filter, RFI Line 10 AMP 120 VAC Z-1007 Fan Finger Guard (for B-1006 fan) HS-1036 Power Supply w/Harness (2, A-1620) Calibrated 0A-1289-4011 Power Supply w/Harness (1, A-1620) Calibrated 0A-1289-4012 Modem Board; 232 Coated 0P-1279-0003 Fiber Board; RS232 to Fiber, 12V 0P-1127-0024 Surge Suppression Board 0P-1146-0031 Cable; 18” RJ45; 8-Cond., Straight 0A-1229-0054 Cable; 18” RJ11; 6-Cond., Straight 0A-1137-0160 Signal Converter (RS232/RS422) 0A-1127-0 23 7 Signal Converter (RS232/Fiber) 0A-1127-0239 Cable Assy; 20 pos Ribbon, 18”, Dual Row W-1387 Ribbon Assy; 20 Pos, 24” 0A-1000-0016 Ribbon Assy; 20 Pos, 30” 0A-1000-0017 Ribbon Assy; 20 Pos, 36” 0A-1000-0018 Quick Connect Interface, Input 0P-1229-2001 Quick Connect Interface, Output 0P-1229-2002 10ft, RJ45; 4-pair Twisted/Black, Cat 5 W-1383 20ft, RJ45; 4-pair, Twisted, Cat 5 W-1406 Cable; 22 AWG (Light Sensor/Temp Sensor to
Controller) Electrical Contact Cleaner Lubricant / Cal-Lube CH-1019 Hex Wrench, T-Handle 1/8” RT TH-1062 Manual; Venus 1500 Radio, Gen 2 Manual; Venus 1500 Operator’s, Version 3.0
ng a lockable cabinet to store
T-1119
W-1234
ED-13932 ED-13530
4-16
Maintenance and Troubleshooting
4.12 Daktronics Exchange and Repair and Return Programs
To serve customers' repair and maintenance needs, Daktronics offers both an Exchange Program and a Repair and Return Program.
Daktronics' unique Exchange Program is a quick, economical service for replacing
components in need of repair. If a component fails, Daktronics sends the
key customer a replacement, and the customer, in turn, sends the failed component to Daktronics. This not only saves money, but also decreases display downtime.
Daktronics provides these plans to ensure users get the most from their Daktronics
roducts, and it offers the service to qualified customers who follow the program
p guidelines explained below. Please call the Help Desk – 877-605-1113 – if you have questions regarding the Exchange Program or any other Daktronics service.
When you call the Help Desk, a trained service technician will work with you to
lve the equipment problem. You will work together to diagnose the problem and
so determine which replacement part to ship. If, after you make the exchange, the equipment still causes problems, please contact our Help Desk immediately.
If the replacement part fixes the problem, package and packaging in which the replacement part arrived, fill out and attach the enclosed UPS shipping document, and return the part to Daktronics. In most circumstances, you will be invoiced for the replacement part at the time it is shipped. This bill, which represents the exchange price, is due when you receive it.
Daktronics expects immediate return of an exchange part if it does not solve the problem damaged due to acts of nature or causes other than normal wear and tear.
If you do not ship the defective equipment Daktronics within 30 working days from the invoice outright (with no exchange), and you will be invoiced for it. This second invoice represents the difference between the exchange price and the full purchase price of the equipment. The balance is due when you receive the second invoice. If you return the exchange equipment after 30 working days from the invoice date, you will be credited for the amount on the second invoice, minus a restocking fee. To avoid a
restocking charge, you must return the defective equipment within 30 days from the invoice date.
Daktronics also offers a Repair and Return Program for items not subject to excha
Return Materials Authorization: To representative prior to shipment to acquire a Return Material Authorization (RMA) number. If you do not have a local representative, call the Daktronics Help Desk for the RMA. This expedites repair of your component when it arrives at Daktronics.
Packaging for Return: Pac shipment. Electronic components, such as printed circuit boards, should be installed in an enclosure or placed in an antistatic bag before boxing. Please enclose your name, address, phone number, and a clear description of symptoms.
. The company also reserves the right to refuse equipment that has been
date, Daktronics assumes you are purchasing the replacement part
nge.
return parts for service, contact your local
kage and pad the item well to prevent damage during
the defective part in the same box
Maintenance and Troubleshooting
4-17
This is how to reach us: Mail:
Customer Service, Daktronics Inc.
PO Box 5128
331 32nd Ave Brookings SD 57006
Phone:
Daktronics Help Desk: 877-605-1113 (toll free) or 605-697-4034
Fax: 6
05-697-4444
E-mail: h
elpdesk@daktronics.com
4-18
Maintenance and Troubleshooting

Appendix A: Reference Drawings

Refer to the Section on How to Use This Manual for information on reading drawing numbers. The following drawings are listed in numerical order by size (A, B, etc.).
Power Termination Box System Riser Diagram, RS System Riser Diagram, RS
System Riser Diagram, Modem.......................................................Dra
System Riser Diagram, Fiber Comp. Layout, AF-3150-16/32/48x48-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x64-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x80-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x96-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x112-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x128-20-Mono-G2 Comp. Layout, AF-3150-16/32/48x144-20-Mono-G2 Symbols, AF-3150 Component Layout Power Specs, 16X144-48X Schematic; Power Supply Configurations System Riser Diagram; QC Outdoor Radio, Gen 2
Schematic, Internal, W/Quick Connect............................................Dra
Controller, Galaxy, 8 conn., J1087 W/Quick Connect Schematic, AF-3150-16x***-20mm, Mono Schematic, AF-3150-32x***-20mm, Mono Schematic, AF-3150-48x***-20mm, Mono Shop Drawing, AF-3150-**
...................................................................Drawing A-129227
422........................................................Drawing A-174135
232........................................................Drawing A-174341
wing A-174342
..........................................................Drawing A-174344
........................Drawing A-178259
........................Drawing A-178261
........................Drawing A-178262
........................Drawing A-178263
......................Drawing A-178264
......................Drawing A-178265
......................Drawing A-178266
...........................................Drawing A-179505
144 Displays.........................................Drawing A-180190
.......................................Drawing A-180225
.........................Drawing A-185359
wing B-177662
.....................Drawing B-177838
......................................Drawing B-180095
......................................Drawing B-180096
......................................Drawing B-180097
x**-20mm-R or A...................................Drawing B-183660
Appendix A: Signal Converter
A-1

Appendix B: Signal Converter

Appendix B: Reference Drawings
B-1
Signal Converters and Loop-back Testing for Direct Connections
The following table gives the typical state of the signal converter when the LEDs are either on or off. Refer to converters and the locations of the various components.
LED
Indicators
Power
TX
RX
TX/RX
Figure 1 and Figure 2 on next the page for an illustration of the signal
Typical States Troubleshooting
ON
OFF
On Steady
OFF Steady
Brief Flicker SC is transmitting data
ON Steady
OFF Steady Normal state, SC is not receiving data
Brief Flicker SC is receiving data
ON Steady (If serial cable is connected) Bad SC Replace SC
Signal Converter (SC) is receiving power SC is not receiving power Check power/Replace fuse Internal 1 AMP fuse is bad Replace fuse SC is not connected to a serial port Connect to open computer
1. Serial port or serial cable is bad
2. Computer COM port is in sleep mode
Normal state, SC is not transmitting data
1. Field cabling between SC and display is bad
2. Is connected to display output jack or terminated inc
3. Bad COM port is on display controller
orrectly
COM port (COM port could be sleep mode.)
1. Try another port or replace seri
2. Communicate with display
1. Eliminate cabling by discon from SC to display controller
2. Check connections and terminatio
3. Eliminate by disconnecting wire/ controller
al cable
necting wire/cable
ns
cable to display
6/30/2004 ED-14413 Page 1
RS422 Wire Signal Converter
following tables list the jack pin-outs for a wire signal converter:
The
Figure 1: RS232/RS422 Signal Converter
Fiber Signal Converter
The following tables give the jack pin­outs for a fiber signal converter.
JACK OPERATION
J2 TX1 (out) J3 RX1 (in) J4 TX2 (out) J5 RX2 (in)
J1 - 25 Pin DB-F
PIN OPERATION
2 TX-P (out) 3 RX-P (in) 7 GND
J4 and J5 –
Phoenix
PIN OPERATION
1 GND 2 RX-P (in) 3 RX-N (in) 4 TX-P (out) 5 TX-N (out) 6 GND
J2 and J3 –
RJ/11
PIN OPERATION
1 GND 2 TX-N (out) 3 TX-P (out) 4 RX-N (in) 5 RX-P (in) 6 GND
J1 – 25 Pin DB-F
PIN OPERATION
2 TX-P (out) 3 RX-P (in) 7 GND
Figure 2: RS232/Fiber Signal Converter
6/30/2004 ED-14413 Page 2
RS422 Loop-Back Test (Outdoor Displays)
Note: This test should be performed with only one jack at a time. Do not connect a loop-back to more than one jack at a time.
Serial Cable (W-1249)
To complete the test, the serial cable must be plugged into the signal converter. The table below lists the pin connections when using a serial cable (Daktronics part# -1249).
DB9-F DB25-F
Pin 3 – TX Pin 2 – TX Pin 2 – RX Pin 3 – RX Pin 5 – GND Pin 7 - GND
Loop-Back Test: To perform a loop-back for testing purposes only, use the spare plug in the signal converter and connect the copper conductor jumpers using the following table. Refer to
Figure 3. (To eliminate the display, pull out the
phoenix plug with the signal wires connected into it.)
J2 and J3 J4 and J5
(Pin 5) TX-N to
(Pin 3) RX-N
(Pin 4) TX-P to
(Pin 2) RX-P
When the wires are connected, perform the loop-back test using the Venus 1500 software as described in Conducting the Venus 1500
Software Test
This test can also be done at the signal termination enclosure on the surge board assembly, as shown in controller board input. In that case, the wires coming from the signal converter must remain connected, and the jumpers will be inserted along with them. Leave the plug disconnected from the surge board while conducting the test.
TB1 - RS422 In
(Pin 4) RX-P to
(Pin 2) TX-P
(Pin 5) RX-N to
(Pin 3) TX-N
When the wires are connected, perform the loop-back test using the Venus 1500 software as described in Conducting the Venus 1500 Software Test
(Pin 2) RX-P to
OR
(Pin 3) RX-N to
(Pin 4) TX-P (Pin 5) TX-N
Figure 4, or, on some displays, at the
Figure 3: Jumpers at RS232/RS422 Signal Converter
Figure 4: Jumpers at Surge
Board
6/30/2004 ED-14413 Page 3
RS422 Loop-Back Test (Indoor/Outdoor Displays)
All indoor displays and some outdoor displays (AE-3010, AF-3010, AF-3020, and X-1000) use RJ11 plugs or connectors. In those cases, a “Network Cable Tester” ( to conduct the test.
The Network cable tester is used to test for two things:
1. A flipped RJ11 cable used instead of a straight through cable.
2. A good connection from a computer or signal converter to a through the connecting
cable.
The use of a flipped (reversed) or straight cable can be determined visually. Use the figures below as a guide, or use the Network Cable Tester box for assistance.
Figure 7) is provided
Figure 5: Flipped Cable (Reversed)
Figure 6: Straight Cable
1. Plug one end of the flipped cable into the output from the computer or signal
converter.
2. Plug one end of the flipped
cable into J2 (Loopback Connector) on the Network cable tester box.
3. When both ends are connected,
perform the loop-back test using the Venus 1500 software as described in Conducting
the Venus 1500 Software Test.
Figure 7: Network Cable Tester
6/30/2004 ED-14413 Page 4
4. For AE-3010, AF-3010, AF-3020, and X-1000 displays
only, disconnect the cable going into the COM module input (J3) on the controller and connect to J2 on the loop-back box. See connector.
Figure 8 for location of the RJ11
Loop-Back test with Fiber
1. Locate the signal termination enclosure or open the bottom left
corner of the display
2. Locate the fiberboard, as shown in Figure 9, and label the fiber
ends connected to the board.
3. Remove the ends from the board that are in jacks J5 and J4.
4. Connect the ends into the fiber splice (Daktronics part# P-1197),
as shown in
Figure 10.
Figure 8: AF-3010/X-1000 COM Module
Figure 10: Connecting TX and RX Fibers with Fiber Splice
5. When the fibers are connected, perform the loop-back test using
the Venus 1500 software as described in Conducting the Venus 1500 Software Test
6. For AF-3010 and X-1000 displays only, the cable that connects
the fiberboard to the controller board input uses a RJ11 jack at the controller and can be connected to a loop-back box at J2 to run the test as usual.
Figure 9: Fiber Optic Board
6/30/2004 ED-14413 Page 5
Conducting the Venus 1500 Software Test
1. Open Venus 1500 Administrator.
2. Click Network Configuration and open the direct network by clicking on the [+] in
front of Direct Network.
3. Right click the network you want to test.
6/30/2004 ED-14413 Page 6
4. Click [TEST].
5. If the Transmit LED on the signal converter flickers, the signal is getting to the
signal converter. That means that the right Com port is being used. However, if it does not flicker, the computer has either a software or hardware problem.
6. If you get the same message in the “Received” box as in the “Sent” box, the loop-
back test was successful, implying that the cable has continuity to the point of the connection. Note: Flipped and straight cables will provide the same results. Check for correct order of the wires.
7. If “No Response” appears in the “Received” box, the test failed due to one of the
following problems:
a. The correct computer COM port is not being used, or USB port is not
configured as a “serial” port. (If the Transmit LED flickered, this was not the problem.)
b. A communication problem exists:
The fiber or the ends on the fiber are bad.
(or) The wire or the terminations are bad.
c. There was a problem conducting the test:
The serial cable to the signal converter is bad or not plugged in.
The signal converter is not plugged in.
8. If the words “It appears as if this port has a modem attached” appear, the modem will
need to be moved, or you need to use a different COM port.
After the test is complete:
1. Remove the wire jumpers and make sure terminations are correct.
2. (or) Remove the fiber splice, and reconnect fiber to fiberboard.
3. Run the test again without the jumpers, splice, or loop-back box. The test should
fail.
4. Use Venus 1500 Display Manager to receive the status to ensure communication
now works correctly.
6/30/2004 ED-14413 Page 7
Loading...