All rights reserved. While every precaution has been taken in the preparation of this manual,
the publisher assumes no responsibility for errors or omissions. No part of this book covered
by the copyrights hereon may be reproduced or copied in any form or by any means – graphic,
electronic, or mechanical, including photocopying, taping, or information storage and retrieval
systems – without written permission of the publisher.
®
is a registered trademark of Daktronics, Inc. All others are trademarks of their respective companies.
This manual explains the installation, maintenance, and troubleshooting of a
Daktronics Galaxy
®
AF-3112 34mm louvered LED Primary-Mirror display. For
questions regarding the safety, installation, operation, or service of this system,
please refer to the telephone numbers listed on the cover page of this manual.
The manual is divided into seven sections: Introduction, Mechanical Installation,
ectrical Installation, Maintenance and Tro ubl eshooting, Appendix A, Appen dix B ,
El
and Appendix C.
• Introduction covers the basic information needed to make the most of the
remainder of this manual. Take time to read the entire introduction as it
defines terms and explains concepts used throughout the manual.
• Mechanical Installati o n pr ov i des general guidance on display mounting.
• Electrical Installation gives general guidance on terminating power and
signal cable at the display.
• Maintenance and Trou bl eshooting addresses such things as removing
basic display components, troubleshooting the display, performing general
maintenance, and exchanging display components.
• Appendix A lists the drawings referenced within this manual.
• Appendix B provided information on the signal converter.
• Appendix C provided information on the optional temperature sensor.
Daktronics identifies manuals by an ED number located on the cover page of each
anual. For example, this manual would be referred to as ED-14212.
m
Listed below are a number of drawing types commonly used by Daktronics, along
the information that each is likely to provide. This manual might not contain all
with
these drawings.
• System Riser Diagrams: Overall system layout from control computer to
display, power, and phase requirements .
• Shop Drawings: Fan locations, mounting information, power and signal
entrance points, and access method (front and rear).
• Schematics: Power and signal wiring for various components.
• Component Placement Diagrams: Locations of critical internal display
components, such as power supply assemblies, controller boards,
thermostats, and light detectors.
Introduction
1-1
Page 8
Figure 1 below illustrates the Daktronics drawing label. The drawing number is
located in the lower-right corner of the drawing. Listing the last set of digits and the
letter preceding them identifies drawings in the manual. In the example below, the
drawing would be referred to as Drawing B-181287. Reference drawings are
inserted in Appendix A.
Figure 1: Drawing Label
All references to drawing numbers, appendices, figures, or other manuals are
presented in bold typeface, as shown below.
“Refer to Drawing B-181287 in Appendix A for the power supply location.”
Additionally, drawings referenced in a particular section are listed at the beginning
of that section as seen in the following example:
Daktronics displays are built for long life and require little maintenance. However,
from time to time, certain display components will need replacing. The
Replacement Parts List in Section 4.11 provides the names and numbers of
components that may need to be ordered during the life of the display. Most display
components have a white label that lists the part number. The component part
number is in the following format: 0P-_ _ _ _-_ _ _ _ (component) or
0A-_ _ _ _-_ _ _ _ multi-component assembly).
Following the Replacement Parts List is the Daktronics Exchange and Repair and Return Programs in Section 4.12. Refer to these instructions if any display
component needs replacement or repair.
1.2 Safety Precautions
Important Safeguards:
1. Read and understand these instructions before installing.
2. Be sure the display and other exterior enclosures are properly grounded
with an earth ground electrode at the display.
3. Disconnect power when servicing the display.
4. Do not modify the display structure or attach any panels or coverings to the
display without the written consent of Daktronics, Inc.
1-2
Introduction
Page 9
1.3 Network Concepts
The concept of using LED displays as a cost effective, high impact method of
communication is rapidly growing throughout many industries and businesses. The
need for additional features and the complexity of multiple display installatio ns has
emerged. Daktronics display system s have been desi g ne d to m eet those n eeds.
The common thread to most client requests is a means of programming and
ntrolling a group of displays from a central control point. Daktronics responded by
co
developing a powerful system of interconnecting and controlling displays.
Daktronics designs products with great care that satisfy a wide variety of
installations. Some of the design goals of these systems include the following:
• Easy transfer of messages
• The ability to tell a display or group of displays in the network which
message should run
• The ability to determine the status of any display on the network
• The ability to control multiple display technologies on the same network
There are five (5) network systems available: RS232, RS422, Modem, Fiber Optic,
Radio. Up to 240 displays can exist on one network.
and
RS232 Network
RS232 (EIA/TIA-232-E) is a standard communication interface that employs a
single-ended serial transmission scheme that uses a maximum cable length of 7.6
meters (approximately 25 feet). This interface was designed for computer
communication at short distances. All computers have an RS232 communications
port. Refer to Section 3 for additional information.
RS422 Network
RS422 (EIA/TIA-422-B) is a standard communication interface that utilizes a
differential balanced transmission scheme that uses a typical maximum cable length
of 1.2km (approximately 4,000 feet). The main advantage of RS422 over RS232 is
the longer cable length that is possible. A signal converter is needed to convert the
computer's RS232 to RS422. Refer to Section 3 for more information.
Modem Network
The modem is a standard communication interface that utilizes standard phone
transmission lines. The phone company assigns each phone line a number that the
modem uses to communicate between controller and display. Each modem network
needs to have a dedicated phone line assigned to it. Refer to Section 3 for additional
information.
Fiber Optic Network
A fiber optic network is a standard communication method transmitting light (signal)
through a glass fiber. Fiber optic cable has a maximum length of 600 meters
(approximately 2,000 feet). A signal converter is needed to convert the computer's
RS232 signal to fiber optic signal; a minimum of two fibers is required. Refer to
Section 3 for additional information.
Introduction
1-3
Page 10
Radio Network
The Radio network is a standard communication method that uses radio waves at
high frequencies to transmit signal. The Venus 1500 Radio network has a maximum
distance of 450 meters (approximately 1,500 feet) outdoor and 150 meters
(approximately 500) indoor. A nearly straight line-of-sight path must be maintained
between the Server Radio connected to the computer and the Client Radio connected
to the display. Refer to Section 3 and the Venus 1500 Radio manual, E D-13932, for
additional information.
Daktronics AF-3112 Galaxy
performance, reliability, easy maintenance, and long life. The pixels have a 34mm
center-to-center spacing and are illuminated using LEDs (light-emitting diodes). A
light sensor on the front of the display is used for automatic dimming of the LEDs
based on the ambient light levels. The configuration of pixels depends on the model
of display ordered.
Refer to D
rawing A-193720 or A-201993 for the approximate size, weight, and
power requirements for your display.
The Galaxy
®
model numbers are described as follows:
AF-3112-RRxCCC-34-X-X(X)
AF-3112 =
RR =
CCC =
34 =
R =
XX =
A typical display system consists of a Windows
running Venus
®
1500 software and one or more displays. The displays are offered as
single-face units, which are single-sided stand-alone displays. They can become
double-faced by mounting them back-to- back with a second unit.
®
Venus
1500 is a software package that runs under Windows® 98, ME™, NT® 4.0,
2000, or XP Home/Professional operating systems on an IBM
computer. Refer to the Venus
and operation of the Venus
®
displays are designed and manufactured for
Outdoor 34mm Louvered Galaxy® Display
Number of Pixel Rows High (8-32)
Number of Pixel Columns Long (32-112)
Monochrome Red or Amber LED Color
PM - Primary-Mirror and M – Mirror
®
1500 operator’s manual (ED-13530) for installation
®
1500 editing station.
-P/M................ Drawing A-193720
-P/M................ Drawing A-201993
34mm pixel to pixel spacing
®
based personal computer (PC)
®
-compatible
1-4
Introduction
Page 11
1.5 Component Identification
The following illustrations depict some of the more commonly accessed Galaxy®
display components. Because Daktronics occasionally alters standard design to meet
customer needs, the actual display design may vary slightly from the illustrations
below.
This is only a brief overview. Refer to Section 4 for additional information on
maintaining the various display components.
Controller: The display’s controller is the “brains” of the display (refer to
below). The controller receives, translates, and activates the signal information from
the control computer to the appropriate pixels on the display accordingly.
Figure 2
Figure 2: Version 3 Controller
Display Address: The display address is an identification number assigned to each
display of a network. Rotating the address switches on the controller sets the display
address. The control software uses the address to locate and communicate with each
display. Displays that are on the same network cannot have the same address.
Driver/Pixel Board: The LED pixels are mounted directly onto the driver/pixel
board. This board is also responsible for the switching and intensity levels of the
LEDs.
Galaxy
matrix displays.
LED (light emitting diode): Low energy, high intensity lighting units.
Louver: Black plastic shade positioned horizontally above each pixel row. The
louvers increase the level of contrast on the display face and direct LED light. The
louvers are attached to the Plexiglas face on the door of the display.
Introduction
®
: Daktronics trademarked name for LED monochrome, tri-colored, or RGB
1-5
Page 12
Mirror: The second display in a Primary-Mirror configuration that does not have a
controller. All signal information to the display is received though a signal interconnect cable.
Module: 34mm Galaxy
®
modules are 8 pixels high by 16 pixels wide. Each is
individually removable from the inside of the door of the display. The module for the
AF-3112 is one unit with both the LEDs and the driver making up one module. Ref er
Figure 3 below.
to
Figure 3: 34mm Module
Network: A network consists of multiple displays connected to each other. Up to
240 displays can exist on one network.
Pixel: There are two LEDs per pixel. The number and color of the LED s depend on
display application.
Power Supply: Converts AC line voltage from the load center to low DC voltage for
one or more module driver boards.
Primary: The first display in a Primary-Mirror or Primary-Secondary configuration.
The communication inputs and the light sensor will be connected to this display.
Router: This device forwards data packets along networks and provides additional
security.
RS232: RS232 is a standard PC communication type with a
maximum cable length of 25 feet (7.6 meters)
RS422: RS422 is a standard differential communication
type with a maximum cable length of 4000 feet (1.2
kilometers).
Signal Converter: The signal converter, shown in Figure 4
on the right, is a Daktronics supplied unit that converts the
data from RS232 to RS422 or RS232 to fiber optic signal.
The signal converter is connected to the control PC via
straight through serial cable.
Venus 1500: Daktronics designed, Windows
software used to create and edit messages on the display.
®
based
Figure 4: RS232 to RS422 Signal
Converter
Refer to ED-13530 for the operation manual.
1-6
Introduction
Page 13
1.6 Daktronics Nomenclature
Figure 5: Numbering Example - 24x80 Front
To fully understand some Daktronics drawings, such as schematics, it is necessary to
know how various components are labeled in those drawings. This information is
also useful when trying to communicate maintenance or troubleshooting efforts.
A module is the building block of the
®
Galaxy
display. Each module measures 8
pixels high by 16 pixels wide. By placing
modules side-by-side and on top of one
another, a display of any size can be
designed and built. Individual modules can
be easily removed from the display if
required.
Daktronics numbers modules on a Galaxy
display.
Figure 5above illustrates how
Figure 6 on the right demonstrates
®
Figure 6: Module Numbering
the module numbering method.
In addition, the following labeling formats might be found on various Daktronics
drawings:
• “TB_ _” represents a termination block for power or signal cable.
• “F_ _” denotes a fuse.
• “E_ _” signifies a grounding point.
• “J_ _” indicates a power or signal jack.
• “P_ _” identifies a power or signal plug for the opposite jack.
Finally, Daktronics part numbers are commonly found on drawings. Those part
numbers can be used when requesting replacement parts from Daktronics Customer
Service. Take note of the following part number formats:
such as a circuit board and the plate or bracket
to which it is mounted. A collection of circuit
boards working as a single unit may also carry
0P-1195-0001
SN: 6343
05/19/99 REV.1
Figure 7: Typical Label
an assembly label.
Introduction
1-7
Page 14
• “W-_ _ _ _” represents a wire or cable. Cables may also carry the assembly
numbering format in certain circumstances. This is especially true of ribbon
cables.
Most circuit boards and components within this display carry a label that lists the
art number of the unit. If a circuit board or assembly is not listed in the
p
Replacement Parts List in Section 4, use the label to order a replacement. A typical
label is shown in
Figure 7. The part number is in bold.
1-8
Introduction
Page 15
Section 2: Mechanical Installation
Note: Daktronics does not guarantee the warranty in situations where the display is not
constantly in a stable environment.
Daktronics engineering staff must approve an
of the display. If any modifications are made, detailed drawings of the changes must be
submitted to Daktronics for evaluation and approval, or the warranty may be void.
Daktronics is not responsible for installations or the structural integrity of support
tures done by others. It is the customer’s responsibility to ensure that a qualified
struc
structural engineer has approved the structure and any additional hardware.
2.1 Mechanical Installation Overview
y changes that may affect the weather-tightness
Because every installation site is unique, there is no single Daktronics-approved
procedure for mounting the Galaxy
section is general information only and may or may not be appropriate for your
particular installation.
A qualified individual must make all decis
display.
Read both the mechanical and electrical installati
before beginning any installation procedures.
®
displays. The information contained in this
2.2 Support Structure Design
Support structure design depends on the mounting methods, display size, and weight.
The structure design is critical and should be done only by a qualified individual.
Display height and wind loading are also critical factors. It is the customer’s
responsibility to ensure that the structure and mounting hardware are adequate.
Daktronics is not responsible for the installations or the structural inte gri t y of
support structures done by others.
It is the installer’s responsibility to
hardware are capable of supporting the display, and will agree with local codes.
Before beginning the installation proces s, verify the following:
• The mounting structure will provide a straight and square-mounting frame
for the display.
• The mounting structure is capable of supporting the display and will not
yield at any unsupported points after mounting.
• Clearance:
• 3" of unobstructed space below the display for adequate ventilation.
• 2 3/8" of unobstructed space is available above the display to allow
door to hinge open.
• 3” of unobstructed space behind display for adequate ventilation.
Correct any deficiencies b
efore installation.
ensure the mounting structure and
ions regarding the mounting of this
on sections of this manual
Mechanical Installation
2-1
Page 16
There are nutserts provided on the back of the display for mounting of the display to
a structure. Use all the provided mounting nutserts when mounting the display.
If a mounting kit was ordered with the display, mount the channel to the display
using the nutserts on the back of the display.
For ventilation, fans are mounted in the back of the display. Maintain a minimum
distance of 3" (7.62cm) below the display to maintain proper airflow to the
ventilation inlets. Refer to Drawing A-193720 or A-201993 for your display size for
additional information.
If the display cabinet is completely enclosed:
• 13 square inches of unobstructed opening per module must be provided to
ensure adequate cooling.
• Allowances must be made to compensate for the percentage of material
covering the openings in the structure.
• For adequate cooling, forced ventilation may be required. If air is forced
into the enclosed structure, a minimum of 200 cfm is required for both inlet
and exhaust.
If these requirements are not met, the Galaxy
®
display warranty may be void.
2.4 Lifting the Display
The top of larger displays is equipped with eyebolts that are used to lift the unit.
Take special care to ensure that the rated load of the eyebolts is not exceeded. Refer
to the information at the end of this section labeled Eyebolts to determine the
allowable load of the eyebolts shipped with the display.
Figure 8 below illustrates both the correct (left example) and the incorrect (right
example) method of lifting a display. Lift the display as shown on the left, with the
lifting bar. Use every lifting point provided.
Figure 8: Lifting the Display (Correct, Left; Incorrect, Right)
Do not attempt to permanently support the display by the eyebolts.
2-2
Mechanical Installation
Page 17
If removing the eyebolts, adequately seal the ho
½ inch in size. Silicone along the threads to ensure that water does not enter the
display.
The method used to mount displays can vary greatly from location to location. For
is reason, only general mounting topics can be addressed in this manual.
th
It is the responsibility of the installer to
meet local codes and standards, as well as the mounting hardware and methods.
Before beginning the installation proces s, verify the following items:
• The mounting structure will provide a straight and square-mounting frame
for the display. Height variation in any fou r -f oo t hori zontal section may
not exceed ¼-inch.
• The mounting structure will not give way at any unsuppor ted points after
the display is mounted.
The back of the display has nutserts to which the mounting structure will be attached
as show
mounted displays inspected by a qualified structural engineer. It is the customer’s
responsibility to determine the proper wall mounting method and location.
Refer to D
number of attachment points needed and the wall structure must be reviewed by a
qualified structural engineer and meet all national and local codes. Daktronics
recommends attaching to all nutserts provided.
n in Drawing A-193720 or Drawing A-201993. Remember to have all
rawing A-193720 or A-201993 for a suggested wall mount method. The
1. Carefu
2. Fol
3. Use t
4. Refer t
5. After in
lly uncrate the display. Look each side of the display over for
damage during shipping.
lowing the guidelines described in Section 2.4, lift the display into
position on the support structure.
he provided nutserts in the display for mounting to the structure.
o Section 3 for information on routing power and signal.
stallation is complete, carefully inspect the display for any holes
that may allow water to seep into the display. Seal any openings with
silicone. If the eyebolts on the top of the display have been removed,
plug the holes with bolts and the rubber-sealing washers that were
removed with the eyebolts.
les using bolts and sealing washers,
-P/M................Drawing A-193720
-P/M................Drawing A-201993
ensure the installation will adequately
2.6 Optional Temperature Sensor Mounting
If a temperature sensor will be used with your display, see Appendix C for mounting
and signal connections.
Mechanical Installation
2-3
Page 18
Page 19
Eyebolts
Almost every display that leav es D ak tronics is equipped w ith ey ebolts for lifting the display . There are
two standard sizes of eyebolts: ½″ and A″.
Load Increase Factor: The load increases as the lift angle (θ) decreases. The allowable load on the
eyebolts also decreases with the lift angle due the bending stress on the eyebolts. In sum, the smaller
the angle between the cable and the top of the display, the lighter the sign must be to safely lift it. Do
NOT attempt to lift the display when the lift angle is less than 30 degrees.
A. Do not use eyebolts on angular lifts unless absolutely necessary. For angular lifts, the shoulder pattern
eyebolt is preferred.
B. Load should always be applied to eyebolts in the plane of the eye, not at some angle to this plane.
C. Shoulder eyebolts must be properly seated (should bear firmly against the mating part), otherwise the
working loads must be reduced to those indicated for regular eyebolts. A washer or spacer may be
required to put the plane of the eye in the direction of the load when the shoulder is seated.
D. No load greater than the safe working load listed in the data table should be used.
E. To obtain the greatest strength from the eyebolt, it must fit reasonably tight in its mounting hole to prevent
accidental unscrewing due to twist of cable.
F. Eyebolts should never be painted or otherwise coated when used for lifting. Such coatings may cover
potential flaws in the eyebolt.
G. To attain the safe working loads listed for regular eyebolts, 90% of the thread length must be engaged.
Copyright 1996-2001 ED-7244
Daktronics, Inc. Rev. 4 – 14 March 2001
Page 21
3: SectionElectrical Installation
Only a qualified individual should terminate power within this Daktronics display or
signal to the signal enclosure.
The Daktronics engineering staff must approve any changes made to the display. Before
altering the display, submit detailed drawings for the proposed modifications to the
Daktronics engineering staff for evaluation and approval, or the warranty will be rendered
null and void.
3.1 Common Connectors in the Display
The power and signal connections in the displays use many different types of
connectors. Take special care when disengaging any connector so as not to damage
the connector, the cable, or the circuit board.
When pulling a connector plug from a jack, do not pull on the wire or
cable; pull on the jack itself. Pulling on the wires may damage the
connector.
The following information presents some common connectors
encountered during display installation and maintenance.
1. Ribbon Cable Connectors:
Figure 9on the rightillustrates a typical ribbon connector. To
disconnect the ribbon cable, push the plastic clips on the sides
out to unlock and remove the jack.
Before replacing a ribbon cable connector, spray it with
DeoxIT
may cause signal problems. In addition, apply a generous
amount of CaiLube
™
contact cleaner to remove any foreign matter that
™
protector paste to the plug before
inserting it into the jack. This paste will protect both the
plug and the jack from corrosion.
2. Termination Blocks:
Termination blocks are usually used to connect internal
power and signal wires to wires of the same type coming
into the display from an external source. Power wires need
to have one-half inch of insulation stripped from the end of
the wire prior to termination. Tighten all screws firmly to
ensure a good electrical connection. Refer to
Figure 10 on
the right.
Figure 9: Ribbon
Cable Connector
Figure 10: Termination
Block
Electrical Installation
3-1
Page 22
3. Phoenix
™
-Style Connectors:
Phoenix-style connectors, which are usually green, are
often used for signal termination on circuit boards.
Refer to
Figure 11 on the right. Strip one-quarter inch
of insulation from the wire prior to termination. To
remove a wire, turn the above screw counterclockwise to loosen the connector's grip on the wire.
To insert a wire, push the bare wire into the connector
and turn the above screw clockwise to lock the wire
into place.
4. Mate-n-Lok
™
Connectors:
Figure 11: Phoenix Connector
The Mate-n-Lok connectors found in the displays are
white and come in a variety of sizes.
Figure 12 on the
right illustrates a four-pin Mate-n-Lok connector. To
remove the plug from the jack, squeeze the plastic
locking clasps on the side of the plug and pull it from the jack.
5. RJ11/RS45 Connectors:
RJ connectors, as seen in
Figure 13 on the lower right, are
similar to the telephone connectors found in homes. In order to
remove this plug from the jack, depress the small clip on the
underside of the plug. RJ11 connectors use six-conductor cable
and RJ45 connectors use eight-conductor cable.
Before replacing an RJ connector, spray it with DeoxIT
contact cleaner to remove any foreign matter that may cause
signal problems. In addition, apply a generous amount of
CaiLube
™
protector paste to the plug before inserting it into the
™
Figure 12: Maten-Lok Connector
jack. This paste will protect both the plug and the jack from
corrosion.
6. Six-Pin Insulation Displacement Connector:
The six-pin connectors found in the display are keyed
connectors, meaning that they will only go together one way
and should not be forced. To remove the connector, squeeze the
plastic tab and gently pull the plug from the jack.
Figure 13: RJ11
Connector
3-2
Electrical Installation
Page 23
3.2 Control Cable Requirements
RS232
A quick connect cable for an RS232 display will connect from the communication
enclosure to the display. The quick connect cable is provided by Daktronics.
RS422
This cable is a 4-conductor shielded cable used to transmit an RS422 signal
(Daktronics part number W-1234). This shielded cable consists of paired wires. They
should not be subjected to mechanical flexing after installation. This cable is not for
direct burial and should have one of the following routings:
• In d
• In
With interference signals, such as power c
foot separation is required. The maximum length of an RS422 signal cable is 4,000
feet (1.22km) from the signal converter to the enclosure at the display.
Modem
The modem option will use a standard telephone cable routed through conduit. The
local telephone company will need to assist in this installation. Ask the telephone
company which colors are used for the TIP wire and the RING wire for signal
connections to the modem enclosure at the display.
Note: T
board/communications system.
edicated, metallic conduit
side buildings – if cable is not in conduit, keep away from interference
signals.
onductors, intercom, etc., typically a two-
he telephone lines must be dedicated lines, and not run through a switch
Fiber Optic
This cable is a 4-fiber cable (Daktronics part number W-1376). Two fibers are used
for display communications and the other two are saved for spares. The cable may be
either direct burial or in conduit, but it should not be subjected to mechanical
flexing. The maximum length of a fiber optic cable is 2,000 feet (611.6 meters) from
the signal converter to the fiber enclosure at the display.
Radio
The Server radio connected to the computer requires an 18-gauge six-conductor
cable (Daktronics part number W-1370). Four-conductors will be used for the signal
and two for the power. These wires need to be in conduit when exposed to outdoor
conditions to the Server radio. The maximum distance from the J-box by the
computer and the Server radio is 1,000 feet (305.8 meters).
The Client radio at the display comes with cable that is rated for outdoor use and
s not need to be in conduit. The cable should be secured to the structure to
doe
prevent it from being pulled loose from the display.
Electrical Installation
3-3
Page 24
Display Enclosures
In each communication method, the final termination will be from a provided
weather resistant enclosure to the display.
Note the following information when mounting the enclosure:
1. Be sure to mount the enclosure with the cable exiting from the bottom, to
prevent water from entering into the enclosure.
2. Mount the enclosure securely and if possible at a height inaccessible to
vandalism.
3. A quick connect cable will be connected to the enclosure and will terminate to
the back of the Primary display. The length of the cable is either 25 or 30 feet
depending on the communication method used.
4. The quick connect cable can be run from the enclosure though conduit or
through the display pole to the sign, but is not required. The cable is weather
and sunlight resistant.
5. Daktronics strongly recommends that the cable be secured to the display to
prevent it from being pulled loose by weather or vandalism.
6. Ground those enclosures that use wire signal cable, which includes the RS422
and modem. The resistance to ground should be 10 ohms or less. A wire is
attached to the enclosure to make the necessary ground connection.
3.3 RJ Connector Cables
The conductor connectors used in the network are
an industry standard 6-pin RJ11or 8-pin RJ45.
These connectors can be found on many networks
and LANs.
The cables used in a network are a standard eightconductor Cat-5 cable. Refer to
Figure 14 on the
right. This cable has one end that is the mirror
image of the other end (i.e. the cable is flipped).
Refer to
cable.
Figure 15 below for a standard flipped
Figure 14: Eight-Conductor Cable
Notice below in
Figure 15 that the color code on one connector must be made the
opposite on the other connector. When installing a network, it is not easy to
remember in which direction the previous end was oriented. One simple way to
avoid confusion is to standardize the color code, having one color for the connector
going into the output of a sign, and the opposite color for a connector going into the
input of a sign. This will help ensure correct cabling since cables are always installed
from the output jack of one sign to the input jack of the next sign.
3-4
Figure 15: Flipped Cable with RJ45 Connectors
Electrical Installation
Page 25
The Cat-5 cable used is an eight-conductor cable that has a special configuration for
use. See Section 3.7 for the signal cable configuration.
Daktronics does not provide the conduit. Refer to DrawingA-193720 or A-201993
for your display size for approximate locations for power and signal conduit.
Separate conduit must be used to route:
• Power
• Signal IN wires
• Signal OUT wires (if signal is required for another display)
Knockout holes for ½" conduit are located at the bottom right (rear view) of th e back
of the display (refer to Drawing A-193720 or A-201993).
For displays with more than one face, signal and temperature sensor wiring between
displays is done using a quick connect interconnect cable.
3.5 Preparing for Power/Signal Connection
Reference Drawings:
F. Assy, AF-3112-2480-34...........................................Drawing B-200259
Figure 17: Face Panel Latches
1. The display door has three face panel latches, see Figure 17. Release the
latches using a 5/32" Allen wrench as shown in
panel. Gas springs will hold the door open for servicing. Caution: The door
will swing up. Take extra precautions during windy conditions.
2. Punch or use 7/8" (0.875) conduit holes for the desired conduit openings.
Be careful that none of the internal components are damaged. Attach
the conduit.
3. Locate the controller and power termination panel for these displays in
Drawing B-200259
Figure 16. Lift the face
Figure 16: Use 5/32" Hex Wrench to ReleaseLatches
Electrical Installation
3-5
Page 26
4. An enclosure receives the signal from the
control computer and transfers it to the
display controller. The controller receives the
incoming signal and relays it to the individual
modules.
5. Route power to the display through a fused
disconnect switch capable of opening all
ungrounded power conductors. Install this
disconnect within the line-of-sight of any
personnel performing maintenance on the
display. If the disconnect is located out of
sight of the display, it must be capable of
being locked in the open position.
6. Power conductors from the disconnect to the
display should be routed through conduit in
agreement with local code.
7. You may also route the signal cable from the
display enclosure to the display at this time.
8. Note: Always use water resistant boxes for
signal/power termination enclosures to
prevent corrosion or other physical damage to
interior parts.
Refer to Drawing A-200044 or A-200045 for voltage and current requirements for
your display size. Each uses a 120VAC single-phase power source. Depending on
the module color and display size the power supply may vary.
Do not connect the displays to any voltage other than that listed on the
Daktronics product label.
Proper power installation is imperative for proper display operation. The following
sub-sections give details of display power installation.
Grounding
Displays must be grounded according to the provisions outl i ned in Article 250 of the
National Electrical Code
ohms or less.
The display system must be connected to earth-ground. Proper grounding is
necessary for reliable equipment operation. It also protects the equipment from
damaging electrical disturbances and lightning. It is recommended that an eight
gauge copper wire be connected to the ground rod. The display must be properly grounded or the warranty will be void.
®
. Daktronics recommends a resistance to ground of 10
3-6
Electrical Installation
Page 27
Figure 19: Ground Conductor
The material of an earth-ground electrode differs from region to region and from
conditions present at the site. Consult the National Electrical Code and any local
electrical codes that may apply. The support structure of the display cannot be used
as an earth-ground electrode. The support is generally embedded in concrete, and if
in earth, the steel is either primed or it corrodes, making it a poor ground.
A minimum of one grounding electrode must be installed for each display face. The
grounding electrode is typically one grounding rod for each display face. Other
grounding electrodes as described in Article 250 of the National Electric Code may
be used. Daktronics requires that the resistance to ground be 10 ohms or less. If the
resistance to ground is higher than 10 ohms, it will be necessary to install additional
grounding electrodes to reduce the resistance. The grounding electrode should be
installed within 25 feet of the base of the display. The grounding electrode must be
connected to the ground terminal in the display panel board.
Note: This display is intended to be installed in accordance with the
requirements of Articl 600 of the National Electrical Code and/or other
applicable local codes. This includes proper grounding and bonding of the sign.
Power Installation
There are two considerations for power installation: installation with ground and
neutral conductors provided, and installation with only a neutral conductor provided.
For these displays, installation with ground and neutral conductors provided is used.
For this type of installation, the power cable must contain an isolated earth-ground
conductor. Under this circumstance, do not connect neutral to ground at the
disconnect or at the display. This would violate electrical codes and void the
warranty. Use a disconnect so that all hot lines and neutral can be disconnected.
Refer to
Figure 20 for installation details. The National Electrical Code requires the
use of a lockable power disconnect within sight of or at the display.
Electrical Installation
rInstallation with Ground and Neutral Conducto s Provided
3-7
Page 28
Figure 20: Installation with Ground and Neutral Conductors Provided
Incoming power is connected to the power termination panel. Complete the
following steps to terminate the hot and neutral wires at the termination block within
the display. Refer to Drawing C-200002 for your display.
1. Access the panel by opening the display as described in Section 3.5.
2. Route the power cables through the power conduit in the rear of the display
and to the power term panel.
3. Connect the white neutral wire to termination block, TB41–2.
4. Connect the hot wire to termination block at TB41-1.
5. Connect the green grounding wire to the grounding bus, E41 . Refer to
Figure 20on the previous page.
Main Disconnect
The National Electrical Code requires the use of a lockable power disconnect near
the display. Provide a lockable disconnect switch (knife switch) at the display
location so that all power lines can be completely disconnected. Use a 3-conductor
disconnect so that both hot lines and the neutral can all be disconnected. The main
disconnect should be mounted at or near the point of power supply connection to the
display. A main disconnect is to be provided for each supply circuit to the display.
The disconnecting means must be located in a direct line of sight from the display or
outline lighting that it controls. This requirement provides protection by enabling a
worker to keep the disconnecting means within view while working on the display.
Exception: Disconnecting means that are capable of being locked in the open
position may be located elsewhere.
The AF-3112 is designed for quicker connection to the computer and to the Mirror
display. Refer to Drawing C-200002 for electrical terminations.
• Signal will terminate to a watertight enclosure, which connects to the
primary display using a quick connect cable.
• The temp sensor will mount to the display and terminate to the primary
display with a quick connect cable.
• The primary display will connect to the mirror display with a quick connect,
inter-connect cable.
RS232
Reference Drawings:
System Riser Diagram, RS232 Comm. Box................Drawing A-199104
A RS232 controlled display connections are in a weather resistant enclosure to be
mounted within 25 feet of the display, as shown below in
enclosure to the display, the signal will be connected to the primary using a quick
connect cable. Do not run signal and display power through the same conduit.
Figure 21. From the
Figure 21: RS232 Display Layout
Note: The cable from the enclosure to the display can be routed though conduit, or
should be secured to prevent being pulled lo ose fr om the display by weather or
vandalism.
1. Mount the enclosure within 25 feet of the display.
2. Connect the quick connect cable from the enclosure to the primary display
at J33.
3. The controlling laptop computer connects to the enclosure through the serial
cable (W-1249). Refer to Drawing A-199104 and
information.
Electrical Installation
Figure 22 for additional
3-9
Page 30
Figure 22: RS232 Enclosure Connection
RS422
Reference Drawings:
System Riser Diagram, RS422 Comm. Box................. Drawing A-199144
A RS422 controlled display requires the use of signal converter (0A-1127-0237) near
the computer. From the signal converter, cable is run to the surge board assembly in
a weather resistant enclosure at the display, as shown in
cable connects the enclosure to the display. The cable from the signal converter to
the display, must be routed though conduit. Do not run signal and display power
through the same conduit. Refer to Drawing A-199144 for system layout.
Figure 23. A quick connect
3-10
Figure 23: RS422 Display Layout
Electrical Installation
Page 31
Note: The cable from the enclosure to the display can be routed though conduit, or
should be secured to prevent being pulled lo ose fr om the display by weather or
vandalism.
1. Mount the enclosure within 30 feet of the display.
2. Route signal from the signal converter to the watertight enclosure at the
base of the display. Connect the cable to the signal converter and at the
enclosure as shown in
3. Figure 24.
4. Connect the quick connect cable from the enclosure to the primary display
at J32.
5. Ground the RS422 signal enclosure.
Figure 24: Signal Converter to Surge Board Assembly Enclosure
Pin 4 (TX-P) Green Pin 4 (RX-P)
Pin 5 (TX-N) White Pin 5 (RX-N)
Pin 6 (GND) Pin 6 (NC)
Field
Cabling
Electrical Installation
Surge Board
Assembly
TB1 (RS422 In)
3-11
Page 32
Modem
Reference Drawings:
System Riser Diagram, Modem Comm. Box............... Drawing A-199218
A modem-controlled display requires the use of an internal or external modem at the
computer. The local phone company must provide a dedicated phone line to the
display and identify the colors used for “Tip” and “Ring”. The telephone cable is
terminated to TB2 on the modem in the weather resistant enclosure at the display.
The phone cable must be routed though conduit. Do not run signal and display
power through the same conduit. Refer to Drawing A-199218 and
system layout.
Figure 25 for
Figure 25: Modem Display Layout
Note: The cable from the enclosure to the display can be routed though conduit, or
should be secured to prevent being pulled lo ose fr om the display by weather or
vandalism.
1. Mount the enclosure within 25 feet of the display.
2. Have the phone company route a dedicated phone line to the display and identify which wires are used for Tip and Ring.
3. The Tip and Ring phone wires will terminate to the modem, as shown in the
modem termination enclosure in
Figure 26.
4. Connect the quick connect cable from the enclosure to J33 on the back of the primary display.
5. Ground the modem enclosure.
Note: The jumper X1 on the controller board must be closed while the display
powers up to recognize that a modem is being used with the display. See
in Section 4 for jumper location.
Figure 40
3-12
Electrical Installation
Page 33
Figure 26: Modem Phone Line Termination Enclosure
Fiber Optic
Reference Drawings:
System Riser Diagram Fiber Comm. Box Term ..........Drawing A-187293
When fiber optic cable is used, a signal converter (0A-1127-0239), connected to the
computer, relays signal via fiber signal cable to the fiberboard (J4/J5) in the weather
resistant enclosure at the display. When connecting fiber cables, always connect
transmit to receive and receive to transmit. Refer to Drawing A-187293and
27
for the system layout.
Figure
Figure 27: Fiber Display Layout
Note: The cable from the enclosure to the display can be routed though conduit, or
should be secured to prevent being pulled lo ose fr om the display by weather or
vandalism.
Electrical Installation
3-13
Page 34
1. Mount the enclosure within 30 feet of the display.
2. Route fiber optic cable to the enclosure. Two fibers are required.
3.
Connect the fiber at the signal converter and to the fiberboard in the
enclosure. Connect transmit to receive and receive to transmit. Refer to
Figure 28 for fiber termination locations.
4.
Connect the quick connect cable from the enclosure to J33 on the back of
the primary display.
Figure 28: Signal Converter to Fiber Card Enclosure
Signal Converter to Fiber Board
Signal
Converter
J2 Transmit (TX1) (Color Varies) J5 Receive (RX2)
J3 Receive (RX1) (Color Varies) J4 Transmit (TX2)
Field Cabling
Fiber Control
Card
Venus 1500 Radio
Reference Drawings:
System Riser Diagram, QC Outdoor Radio, Gen 2..... Drawing A-185359
A radio-controlled display requires a Server radio connected to the control computer
and a Client radio at the display. The radios must be in line-of-site of each other. The
Client radio is provided with 25 feet of weather resistant pre-terminated cable. Refer
to Drawing A-185359 and
Figure 29 for the system layout.
3-14
Electrical Installation
Page 35
Figure 29: Radio Display Layout
Note: The cable from the Client radio to the display can be routed though conduit,
or should be secured to prevent being pulled loose from the display by weather or
vandalism.
1. Mount the Client radio at the display.
2. Connect the quick conn ect plug to J33 on the back of the primary display as
shown in
Ground the Server and Client Radio enclosures.
3.
Note: Additional drawings for the Server Connections are in the Venus 1500 Radio Manual (ED13932).
Figure 30: Client Radio Display Connection
Figure 30.
Electrical Installation
3-15
Page 36
3.8 Signal Termination Between Two (or More) Signs
RS422 Interconnection
The Primary – Mirror quick connect cable is used to terminate signal between two
displays. The six-foot cable goes from the Primary OUT (J34) on the Primary
display to the Mirror IN (J32) on the Mirror display.
Figure 31: Quick Connect Boards (Input and Output)
3.9 First Time Operation
When first operated, the display will run through an initialization or boot up
sequence in which it will display the following:
1. Product Name (Galaxy®)
2. Display Size (Row x Column)
3. Shading (32K RGB)
4. Bootloader Version (OS X.XX)
5. Firmware Number (ED13305)
6. Firmware Revision (Rev X.XX)
7. Hardware Address (HW:XX)
8. Software Address (SW:XX)
9. IP Address: (172.16.192.25)
10. Subnet Msk: (255.255.0.0)
11. COM1 Configuration (C1:V15) ((Modem C1:V15) If a Modem is present)
12. Line Frequency (CLK:60 Hz)
13. Display Name Description
Figure 32:Display Interconnect
3-16
Electrical Installation
Page 37
Section 4: Maintenance and
Troubleshooting
Important Notes:
1. Power must be turned off before any repair or maintenance
work is done on the display.
2. Qualified service personnel must make any access to internal
display electronics.
3. The Daktronics engineering staff must approve ANY changes
made to the display. Before altering the display, detailed
drawings for the proposed modifications must be submitted
to the Daktronics engineering staff for evaluation and
approval or the warranty will be rendered null and void.
4.1 Maintenance and Troubleshooting Overview
Daktronics Galaxy® series AF-3112 displays are front accessible; meaning access to
the internal components can be gained only from the front of the display.
This section provides the following Galaxy
• Signal Routing Summaries provide a basic explanation of the way signal
travels through the display.
• Power Routing Summaries offer a basic explanation of the way power
travels through the display.
• Service and Diagnostics give instructions for removing various display
components, and explain the functions of circuit board connectors and the
meanings of any diagnostic LEDs.
• Maintenance includes a number of steps to take to keep this Galaxy
display in a safe, working order.
• Troubleshooting lists some possible display malfunctions, and provides a
number of possible causes for that malfunction.
• Replacement Parts List suggests the description and part number of
display components that could possibly need replacing during the life of this
display.
• Exchange and Repair and Return Programs explain Daktronics
component return policy.
®
display information:
®
Maintenance and Troubleshooting
4-1
Page 38
4.2 Signal Summary
1. Data from the control computer, which runs Ven us 1 50 0 software, travels
via RS232, RS422, modem, fiber optic cable, radio signal, or Ethernet
signal into the enclosure by the display.
2. From the display enclosure, signal is sent
to the display controller via a quick
connect cable.
3. From the controller, the signal then travels
over 20-conductor ribbon cables from the
controller (J11 through J16 provide signal
out) to J2 on the driver of the first column
of modules in the display.
4. Data exits at J1 and is relayed to J2 of the
next driver board and so on, traveling down
the entire row of modules. This display
data is used to control the LEDs.
5. At the last column of modules a 20conductor ribbon cable from the J1 output
connects to a 31-pin quick connect output
board. Refer to
6. For multiple face displays a quick connect
interconnect cable transfers data from the
primary display to the mirror display.
7. A 31-pin quick connect input board on the mi rro r di spl ay receives the signal
and transmits it to J2 on the first column of modules, via a 20-conductor
ribbon cable.
8. Data exits at J1 and is relayed to J2 of the next driver board and so on,
traveling down the entire row of modules in the Mirror face. This display
data is used to control the LEDs.
The power routing for the display can be summarized as follows:
1. Incoming power terminates at the power termination panel. Before leaving
the panel, power is sent through a circuit breaker and an RFI electrical filter.
2. Power for the controller board passes through a transformer located on the
controller/power panel.
3. Depending on pixel count and color, p ower supplies (6.5VDC or 9VDC) are
used to power the modules. Power supplies are preset. Contact Daktronics
Customer Service for the proper settings.
4. The AF-3112 Galaxy displays use either red or amber LEDs for a
monochrome display. See Drawing C-200002 for power supply wiring
information.
• Each 9VDC power supply (A-1 633) provides power to up to five
modules in a display that uses three amber LEDs per pixel.
• Each 6.5VDC (A-1591) power supply provides power to up to five
modules in a display that uses two red LEDs per pixel.
4-2
Maintenance and Troubleshooting
Page 39
4.4 Service and Diagnostics
Reference Drawings:
F. Assy, AF-3112-2480-34...........................................Drawing B-200259
Remember: Disconnect power before servicing any internal components.
The following sub-sections address servicing of the following display components:
• transformer, RFI filter
• controller
• modules, drivers and power supplies
The sub-sections also address any diagnostic LEDs, fuses, and signal/power
connectors found on the unit. A general display component layout is shown in
Figure 34. See the schematic, Drawing C-2000002, for exact number of fans and
power supplies used for your display size and see Drawing B-200259 for component
locations. Note: The controller, light sensor, and quick connect output board are
only loaded in the primary display.
Figure 34: General Display Component Layout
The table below give the part number for some of the various components used in
your display. In addition, the label on the part can also be used for further
identification.
Component Denoted As Location
Filter and Transformer
Controller
Modules 0P-1301-1000
Power Supplies
Light Detector 0A-1301-0500 In top left corner of door
0A-1301-0501(Primary)
0A-1301-0502 (Mirror)
0A-1229-0005
A-1591 (red)
A-1633 (amber)
Inside the power termination box
Inside the controller/power panel
The transformer is located in the upper portion of the power termination panel
(Primary display only). To replace the transformer, first disconnect and label all the
wires attached to it. Turn off power to the display before removing the wires.
Then release the hardware, securing it to the panel. Position the new transformer in
its place, and tighten it down. Re-connect all the wires using the display’s schematic
as a reference.
RFI Filter
The RFI electrical filters are mounted in the upper portion of the power termination
panel (Drawing A-200282). Like the transformer, first remove all connecting wires,
and then release the attachment hardware can replace the filters. Install the new filter
using Drawing C-200002 as a wiring reference.
The controller sends data to the modules. Refer to the signal summary in Section 4.2
and Drawing B-177838 for more information. Figure 36 illustrates a typical
controller.
Figure 36: Controller Component Layout
The rotary switches set the hardware address, which the software uses to identify that
particular display. When replacing a controller board, be sure to set the rotary
switches in the same address configuration as the defective controller. Each
controller in a network needs a unique address.
Note: Setting both rotary switches to address 0 (set the switches to 0 by rotating
them counter clockwise until the arrow points to 0) can activate a test mode. The
display’s power must be turned off, and then turned back on to run the test mode.
Complete the following steps to remove the controller from the display:
1. Disconnect power from J5.
2. Remove all power and signal connections from the board. “Locked”
connectors are released by pushing apart the latches then carefully pulling
them from the jack. When replacing the board, it is helpful to have the
cables labeled for easier replacement.
3. Remove the six screws holding the board in place with a 3/16” nut driver.
4. Follow the previous steps in reverse order to install a new controller board.
The following chart illustrates several common hexadecimal address.
Maintenance and Troubleshooting
4-5
Page 42
Controller Address Settings
Upper Lower Address
0 0 Test Mode
0 1 1
0 2 2
0 3 3
0 4 4
0 5 5
0 6 6
0 7 7
0 8 8
0 9 9
0 A 10
0 B 11
0 C 12
0 D 13
0 E 14
0 F 15
1 0 16
1 1 17
… … …
F 0 240
Four diagnostic LEDs are located on the controller; the table below tells what each
LED denotes:
CPU
LED Color Function Operation
DS1 Red CAN TxD Flashes when controller is transmitting CAN information.
DS2 Red CAN RxD Flashes when controller is receiving CAN information.
DS3 Red System Reset Off when controller is functioning properly. Flashes at 1.5-
second rate if controller is not resetting the watchdog timer.
DS4 Red Run A steady flash indicates the controller is running properly.
Normal flash rate is about once per second.
DS5 Red U15 Pro grammed On when U15 contains a valid logic program.
DS6 Red U7 Programmed On when U7 contains a valid logic program.
DS7 Red Link On when Ethernet interface is in the link-up condition. Flashes
when the Ethernet chip detects transmits or receives activity.
DS8 Red Speed On when the Ethernet interface is at 100Mbps. Off when the
Ethernet interface is at 10Mbps.
DS9 Red Duplex On when the Ethernet interface is at full duplex. Off when the
Ethernet interface is at half-duplex.
DS10 Red Collision Flashes when the Ethernet interface detects a collision in half-
duplex.
DS11 Red +5V On when +5V power supply is functioning.
DS12 Red +3.3V On when +3.3V power supply is functioning.
DS13 Red +2.5V On when +2.5V power supply is functioning.
4-6
Maintenance and Troubleshooting
Page 43
Product
Board
LED Color Function Operation
DS1 Green +5V On when +5V power supply is functioning.
DS2 Green +3.3V On when +3.3V power supply is functioning.
DS3 Yellow COM1 TxD Flashes when transmitting serial information.
DS4 Yellow COM1 RxD Flashes when receiving serial information.
Temp/Light
Sensor
LED Color Function Operation
DS1 Green +5V On when +5V power supply is functioning.
DS2 Red Run A steady flash indicates the controller is runni ng correctly.
Normal flash rate is about once a second. Flashes faster
when the sensor is transmitting temp or light information.
The module and driver board are a single functional unit. The LED power supplies
are identified as assemblies.
• In displays with 2 red LEDs per pixel, each power supply unit controls up to
five modules.
• In displays with 3 amber LEDs per pixel, each power supply unit controls
up to five modules.
To remove a module, complete the following steps:
1. Locate the latch access fasteners on the front of the display. With a 5/32”
hex wrench turn the
latch fasteners a
quarter turn as shown
in Section 3.5 for
opening the display
front.
2. Disconnect and label
the wires cables to the
module.
3. Remove the ten, 5/16”
nuts holding the
module to the face
panel and the louvers.
Gently pull the module
away from the face
panel.
4. When installing a
module, reverse the
previous steps.
Figure 37: Removing a Module
Maintenance and Troubleshooting
4-7
Page 44
Power Supplies
The LED power supplies are identified as A-1591 or A-1633.
Complete the following steps to remove a power supply from the display:
1. Locate the latch access fasteners on the front of the display. With a 5/32”
hex wrench turn the latch fasteners a quarter turn as shown in Section 3.5
for opening the display front.
2. Disconnect and label all the wires connected to the power supply.
3. Remove the hardware holding the power supply in place to free the unit.
4. Follow these steps in reverse order to install a new power supply. Refer to
the Drawing C-200002 when reconnecting the wires.
Light Detector
The light detector is internally mounted and wired at
Daktronics. It is located in the top left corner of the
display door on the primary display as shown in Figure
38. A 4-conductor cable connects the light detector to
the controller. Only the Primary display has a light
sensor.
Figure 38: Light Sensor In Display
4-8
Modem
If a modem was included with the display, it is located in the modem enclosure
mounted at the display. Refer to the modem information
in Section 3.7 for modem enclosure location.
1. To replace a modem, first disconnect the power
and signal connections (refer to
the right for the location of the connectors).
2. The modem is held in place with four screws.
Remove the screws using a 3/16” nut driver,
and lift the modem out of the display.
3. Install the new modem, replace the screws, and
reconnect power and signal cables.
The modem module has five LEDs.
• The power LED should remain lit while power is
applied to the modem.
• The modem RX and TX LEDs will flash when
communicating.
• The carrier detect LED will light when the modem
has established communication to another modem.
• The PC connect LED is not used when this modem is mounted in a display.
Figure 39on
Maintenance and Troubleshooting
Figure 39: Modem
Page 45
The modem board also has several input and output jacks:
1. J3 is the power input for 12VAC
2. TB2 is a phoenix connector to terminate the Tip and Ring wires
3. J5 is an RJ11 jack for termination of a pre-terminated phone line
4. J6 is the RS232 RJ45 output to the controller
5. J2, TB1, and TB3 are not used in this display application
A modem system requires a jumper (X1) to be set on the controller board. Refer to
Figure 40 below for the location of the jumper settings.
Figure 40: Modem Jumper Location
Fiber Board
If a fiberboard is included with the display, it is located in the fiber enclosure
mounted at the display. Refer to the fiber information in
Section 3.7 for fiberboard enclosure location.
1. To replace a fiber optic board, first disconnect
the power and signal connections (refer to
Figure 41 for disconnection of power).
2. The fiber optic board is held in place with four
screws. Carefully remove them using a 3/16”
nut driver.
3. Install the new fiberboard, replace the screws
and reconnect power and signal cables.
The fiber module has three LEDs.
• The power LED (DS1) should remain lit while
power is applied to the module.
• The receive LED (DS2) will flash when the display
fiberboard is accepting signal from the signal
converter.
• The transmit LED (DS3) will flash when the display
fiberboard is sending to the signal converter.
In addition, the fiber module has two input fiber
connectors, which the computer or the previous display connects to, and two output
fiber connectors that connect to the next display. A straight through RJ45 cable
connects from J7 on the fiberboard to J3 on the controller board.
Figure 41: Fiber Optic Board
Maintenance and Troubleshooting
4-9
Page 46
RS422 Surge Suppressor
If a surge board was included with the display, it is located
inside the RS422 enclosure mounted at the display. Refer to
the RS422 information in Section 3.7 for surge board
enclosure location.
1. To replace the surge board, first disconnect the
signal connections (refer to Fi gure 42 on the right).
2. The surge suppressor is held in place with four
screws. Carefully remove them using a 3/16” nut
driver.
3. Install the new surge suppressor, replace the screws,
and reconnect power and signal cables.
The surge suppressor is an inline device that is used to filter
the RS422 data line. It suppresses surges down to a low
voltage in order to protect the display controller’s RS422
input.
Note: The surge suppressor must be firmly connected to the
enclosure, and the enclosure must be properly grounded in
order to be effective. The mounting hardware used to secure
Figure 42: RS422 Surge Suppressor
the surge suppressor is sufficient if it is fastened properly.
4.5 Ventilation Systems (With Fans and Filters)
Ventilation fans should be checked after 1,500 hours of operation and every 1,500
hours after that to ensure the display is being cooled properly. Fans should be checked
more often if the display is located in a dusty or harsh weather environment (i.e. along
a gravel road with dust laden air).
• 1,500 hours is equivalent to 83 days if the display is operated for 18 hours a
day and the power to the display is turned off when not in use.
• 1,500 hours is equivalent to 62 days if the display is running non-st o p fo r 24
hours a day.
• Each time a module is removed, for whatever reason, take a minute to
inspect the fans.
• Check the fan blades for dirt and debris. If the fan blades have a large
accumulation of dirt and debris, this indicates that the filters must be
cleaned/changed more often. Fan blades must be kept clean to maintain fan
efficiency and ensure proper cooling.
• Spin the fan blades with a pen or pencil to ensure that the bearings are free
and the fan is still in balance.
To check the operation of the fans, push the bypass button (momentary contact) on
the thermostat enclosure to temporarily turn the fans on (The bypass button is located
behind A102, top row, and second module from the left).
• Hold your hand or a piece of light paper beneath the display to detect air
movement.
• If the fan does not turn or does not operate smoothly, replace it.
4-10
Maintenance and Troubleshooting
Page 47
4.6 Thermostats
A thermostat controls when the ventilation fans are turned on in the display. Refer to
Figure 34 for the location of the thermostat. The ventilation fans turn on when the
inside of the display reaches 85° F (29° C), and turn off at 70° F (21° C).
4.7 Weather Stripping
To ensure that the display is waterproof, weather stripping has been provided around
the entire display and around each module. It is important that the weather stripping
is installed properly at all times or water may leak into the display and damage the
components.
4.8 Display Maintenance
A yearly inspection should be completed to maintain safe and dependable display
operation. This inspection should address the follo wing issues:
• Loose Hardware
Verify fasteners, such as bolts and riv
should be checked and tightened or replaced as required.
• Excessive Dust Buildup
Occasionally it may be necessary to vacuum the inside of the display
inet to remove dust/dirt buildup that may interfere with airflow.
cab
• Water Intrusion – Water Stain Marks
Water can enter the display where weather stripping has come loose or
eriorated, where fasteners have come loose allowing gaps in the panels,
det
or where moisture may be entering around hardware. Be sure to check
around the lift eyes or replacement bolts to ensure that water has not entered
there. If so, replace hardware immediately to prevent more water from
entering the display. Also, check electronic components for possible
corrosion.
• Corrosion
Check the paint, and look for possible corrosion especially at footings,
uctural tie points, and ground rods.
str
If any of the above conditions are noticed, action must be taken immediately to
correct the
situation.
ets, have not come loose. Fasteners
Maintenance and Troubleshooting
4-11
Page 48
4.9 Troubleshooting
This sub-section contains some symptoms that may be encountered in the displays.
This list does not include every possible symptom, but does represent common
situations that may occur.
Symptom/Condition Possible Cause/Remedy
One or more LEDs on a single module
fail to light.
One or more LEDs on a single module
fail to turn off.
A section of the display is not working.
The section extends all the way to the
right side of the display.
One row of modules does not work or is
garbled.
A group of modules, (a column or block)
which share the same power supply
assembly, fail to work.
Entire display fails to work. • Check for proper line voltage into the power
Temperature always reads –196F/-127C
degrees F/ C
Display is stuck on bright or dim. • Check Manual/Auto dimming in Venus 150 0
• Replace/check ribbon cables on the module.
• Replace the module.
• Replace/check ribbon cables on module.
• Replace the module.
• Replace/check the ribbon cable to the first
module.
• Check that the first module has power.
• Replace the first module/driver on the left side
of the first module that is not working.
• Replace the second module that is not
working.
• Replace the power supply assembly on the
first module that is not working.
• Replace/check ribbon cable to first module.
• Check for bent pins on module and controll er.
• Replace controller.
• Replace first module.
• Check the fuses in the power termination box.
• Check the wire connections at the power
supply.
• Check power to modules.
• Replace the power supply assembly.
termination panel.
• Check for correct power to controller and
modules.
• Check fuse in power termination pan el.
• Check/replace the ribbon cable from the
controller to the modules.
• Check the voltage settings on the po wer
supplies.
• Verify proper use of the soft ware in the V150 0
Controller manual (ED13530).
• Replace the controller.
• (For direct displays) Check the signal cable to
the controller using the loopback test.
• Check temperature sensor connections.
• Replace the temperature sens or.
• Replace the controller.
software.
• Check light detector cable.
• Check the address on the Light Sensor.
• Check light detector for obstructions.
• Replace the light detector.
• Replace the controller.
4-12
Maintenance and Troubleshooting
Page 49
4.10 Initialization Operation Information
Every time the display is operated, the display will run through an initialization in
which it will display the following:
oduct Name (Galaxy®)
14. Pr
splay Size (Row x Column)
15. Di
ading (32K RGB)
16. Sh
otloader Version (OS X.XX)
17. Bo
18. Firm
19. Firm
20. Har
21. Soft
22. I
23. Su
24. C
25. Li
ware Number (ED13305)
ware Revision (Rev X.XX)
dware Address (HW:XX)
ware Address (SW:XX)
P Address: (172.16.192.25)
bnet Msk: (255.255.0.0)
OM1 Configuration (C1:V15) ((Modem C1:V15) If a Modem is present)
ne Frequency (CLK:60 Hz)
26. Display Name Description
4.11 Replacement Parts List
The following tables contain some of the items that may need to be replaced in these
displays over a period of time. Many of the parts within the display also list their part
numbers on labels affixed to them.
To prevent theft Daktronics recommends purchasi
manuals and replacement/spare parts.
Part Description Part Number
Controller Galaxy 8 Conn 0A-1229-0005
Module, 2R (1:1) 8x16 (30x70) 0P-1301-1004
Module, 3A (1:1) 8x16 (30x70) 0P-1301-1003
Digital Light Sensor 0P-1247-0003
Digital Temperature Sensor 0P-1247-0007
Temperature Sensor w/Enclosure, Cable 25’ w/QC 0A-1151-0005
Thermostat Enclosure 85-70-9L 0A-1213-4024
Fan; 110, CFM@120V, 29-24 watt, 4.5” B-1006
Fan finger guide (for B-1006 fan) HS-1036
Transformer; Pri 115V, Sec 10VCT, 3Amp, Primary only T-1119
Filter, RFI Line 10 AMP 115/250 VAC Z-1007
Types of Signal boards found in the Enclosure:
• Surge Suppression Board, RS422 0P-1146-0031
• Modem Board; 232 Coated 0P-1279-0003
• F iber Board; RS232 to Fiber, 12V 0P-1127-0024
Radio Client 0A-1146-0078
Radio Server (outdoor) 0A-1146-0079
Signal Converter (RS232/RS422) 0A-1127-0237
ng a lockable cabinet to store
Maintenance and Troubleshooting
4-13
Page 50
Signal Converter (RS232/Fiber) 0A-1127-0239
Quick Connect Cable from Enclosure:
• QC Enclosure Cable (RS232, Fiber, and Modem) W-1484
• QC Enclosure Cable (RS422) W-1504
Ribbon Cables; 20 Position
• Cable Assy; 20 pos. Ribbon 18”, Dual Row W-1387
• Ribbon Assy; 20 pos, 30” 0A-1000-0017
• Ribbon Assy; 20 pos, 36” 0A-1000-0018
• Ribbon Assy; 20 pos, 60” 0A-1000-0021
Cable; 22 AWG, 2-pair, (Light or Temp Sensor to Controller) W-1234
Cable; 31-pin male to 31-pin male, 6’, QC W-1503
31-pin, Quick Connect Input/Output Board 0P-1229-2005
Power Supply (2 Red, A-1591) A-1591
Power Supply (3 Amber, A-1633) A-1633
Electrical Contact Cleaner Lubricant / Cal-Lube CH-1019
Hex Wrench, T-Handle 1/8” RT TH-1062
Manual; Venus 1500 Operator’s, Version 3.0
ED13530
4.12 Daktronics Exchange and Repair and Return
Programs
To serve customers' repair and maintenance needs, Daktronics offers both an
Exchange Program and a Repair and Return Program.
Daktronics' unique Exchange Program is a quick, economical service for replacing
key
components in need of repair. If a component fails, Daktronics sends the
customer a replacement, and the customer, in turn, sends the failed component to
Daktronics. This not only saves money, but also decreases display downtime.
Daktronics provides these plans to ensure users get the most from their Daktronics
p
roducts, and it offers the service to qualified customers who follow the program
guidelines explained below. Please call the Help Desk – 877-605-1113 – if you have
questions regarding the Exchange Program or any other Daktronics service.
When you call the Help Desk, a trained service technician will work with you to
so
lve the equipment problem. You will work together to diagnose the problem and
determine which replacement part to ship. If, after you make the exchange, the
equipment still causes problems, please contact our Help Desk immediately.
If the replacement part fixes the problem, package
the defective part in the same box
and packaging in which the replacement part arrived attach the enclosed UPS
shipping document, and return the part to Daktronics. In most circumstances, you
will be invoiced for the replacement part at the time it is shipped. This bill, which
represents the exchange price, is due when you receive it.
Daktronics expects immediate return of an exchange part if it does not solve the
problem
. The company also reserves the right to refuse equipment that has been
4-14
Maintenance and Troubleshooting
Page 51
damaged due to acts of nature or causes
other than normal wear and tear.
, fill out
and
If you do not ship the defective equipment Daktronics within 30 working days from
the invoice date, Daktronics assumes you are purchasing the replacement part
outright (with no exchange), and you will be invoiced for it. This second invoice
represents the difference between the exchange price and the full purchase price of
the equipment. The balance is due when you receive the second invoice. If you
return the exchange equipment after 30 working days from the invoice date, you will
be credited for the amount on the second invoice, minus a restocking fee. To avoid a
restocking charge, you must return the defective equipment within 30 days
from the invoice date.
Daktronics also offers a Repair and Return Program for items not subject to
excha
nge.
Return Materials Authorization: To
representative prior to shipment to acquire a Return Material Authorization (RMA)
number. If you do not have a local representative, call the Daktronics Help Desk for
the RMA. This expedites repair of your component when it arrives at Daktronics
return parts for service, contact your local
.
Packaging for Return: Package and pad the item well so that it will not be damaged
in shipment. Electronic components such as printed circuit boards should be installed
in an enclosure or placed in an antistatic bag before boxing. Please enclose your
name, address, phone number, and a clear description of symptoms.
This is how to reach us:
Mail:
Phone:
Fax: 6
Customer Service, Daktronics Inc.
PO Box 5128
331 32nd Ave
Brookings SD 57006
Daktronics Help Desk: 877-605-1113 (toll free)
or 605-697-4034
05-697-4444
E-mail: helpdesk@daktronics.com
Maintenance and Troubleshooting
4-15
Page 52
Page 53
Appendix A: Reference Drawings
Refer to Section 1.1 for information on reading drawing numbers. The following
drawings are listed in numerical order by size (A, B, C, etc.)
System Riser Diagram, QC Outdoor Radio, Gen 2
System Riser Diagram, Fiber Comm Box Term
Shop Drawing, AF-3112-2480-34-SF-*
System Riser Diagram, RS
System Riser Diagram, RS
System Riser Diagram, Modem Comm Box
Power Specs, 8x144 – 32x144, AF-3112, Amber
Power Specs, 8x144 – 32x144, AF-3112, Red
Assy, Electrical Plate, AF-3112-*****
Shop Drawing, AF-3112-1680-34-SF-*
Controller, Galaxy, 8 Conn, J1087
F Assy, AF-3112-2480-34mm
Schem, AF-3112-8-32***
232 Comm Box.....................................Drawing A-199104
422 Comm Box.....................................Drawing A-199144