Daikin UAT150C, UAT180C, UAT240C, UAT300C Technical Manual

TECHNICAL MANUAL
Packaged Air Conditioner
Rooftop C Series
UAT-C series
— Cooling only [50Hz] —
R22
UAT-C_(i) Table of Contents
Table of Contents
Nomenclature......................................................................................................................1
Features...............................................................................................................................2
Fan Performance Chart ......................................................................................................6
Fan Performance Table ....................................................................................................10
Engineering & Physical Data ...........................................................................................11
Performance Data .............................................................................................................12
Outlines & Dimensions ....................................................................................................16
Wiring Diagrams ...............................................................................................................18
Installation .........................................................................................................................26
Specifi cation Guide .......................................................................................................... 28
Engineering & Physical Data (Arabic) ............................................................................29
Specifi cation Guide (Arabic) ...........................................................................................30
Nomenclature UAT-C_(i)
1
Nomenclature
Y UAT 300 CX1
Revision/Specification
9: Mechanical Control
“ ”: PCB Control
Power Supply
Y1: 50Hz / 3Ph / 380-415V
Product Type
UAT: Rooftop
Product Specification Variation
G: Gold Fin (Outdoor Coil) “ ”: Bare Fin (Outdoor Coil)
Size
150: 150,000 Btu/h 300: 300,000 Btu/h
Product series
C: C Series
G 9
Product Origin
X: OYLM
2
UAT-C_(i) Features
Features
Key Features
High Energy Effi ciency
In line with the market trend of moving towards high energy effi ciency products, the UAT-C series is developed with the target of high EER.
Model UAT150C UAT180C
Gross EER @ 35°C (
Btu/hr
/W)
11.5 11.4
Effi ciency @ 48°C (kW/TR)
1.51 1.55
Model UAT240C UAT300C
Gross EER @ 35°C (
Btu/hr
/W)
11.1 11.1
Effi ciency @ 48°C (kW/TR)
1.62 1.57
Note: Effi ciency at 48°C is in compliance with the Kuwait MEW
minimum requirement of 1.7kW/TR.
Wide Operating Range
The UAT-C series rooftops are specifi cally designed for High Ambient Application and capable of operating at an outdoor ambient of up to 54°C.
Lightweight and compact
The lightweight and compact design of UAT-C series allows for ease of transportation and installation.
Separate Service Panels
The unit is designed with two separate service panels for easy electrical box servicing.
Independent Refrigerant Circuit
Each unit is designed with two independent refrigerant circuits, where user can control each individual system separately.
This also allows the unit to run at part load when lower cooling capacity is required.
Air Discharge and Air Return
The UAT-C series is available in Horizontal Air Discharge only, designed with Air discharge on the top and return air on the bottom for easy duct design.
3
Features UAT-C_(i)
Component Features
Compressor
High effi ciency, low noise, and hermitically sealed SCROLL compressors are used in the UAT-C series to give a better performance.
All compressors are equipped with an internal overload protection. Crankcase heaters are installed as standard in each compressor.
Evaporator Coil
Evaporator coils are manufactured from seamless inner grooved copper tubes mechanically bonded to aluminium fi ns to ensure optimum heat transfer.
All coils are tested against leaks by Nitrogen holding at 609psig and highly precise Helium leak test at 235psig.
ALL standard coils are 3-4 rows / 14-16 FPI, 3/8” (9.52mm) O.D. tubes.
Evaporator Fan
The unit is designed with belt driven evaporator motor, which allows for change of pulley on site to accommodate different static pressure and air fl ow requirement.
Condenser Coil
Condenser coils are manufactured from seamless inner grooved copper tubes mechanically bonded to aluminium fi ns to ensure optimum heat transfer. All coils are tested against leaks by Nitrogen holding at 609psig and highly precise Helium leak test at 235psig.
ALL standard coils are up to 3 rows / 14-16 FPI, 3/8” (9.52mm) O.D. tubes.
Options:
Hydrophilic Gold Fin coating (NA549) condenser coil is offered as option, which has longer life span under corrosive environment.
Condenser Fan/Motor
Fans are of propeller type, direct driven by weatherproof electrical induction motors. Condenser fan motors are rated IP55 protection index with
class F insulation class and is designed with dust proof bearing to ensure the reliability of the motor
and smooth operation all year round.
Casing/Structure
The unit casing used in UAT-C series is made of zinc coated galvanized steel sheets. It is further coated with an electrostatic powder coat, oven-baked for a tough and lasting weather resistant fi nish. Zinc plated screws are used to further reduce the possibility of unit rusting.
4
UAT-C_(i) Features
Refrigerant Circuit
The UAT-C series is designed with the ability to operate at partial load depending on the requirement of the application.
Each refrigerant circuit has an independent Thermal
Expansion Valve (TXV), Filter Drier and High / Low Pressure Switch.
Additional valves are provided for site installation of Pressure Gauge and Low Ambient Kit.
Filter
Saranet pre-fi lter is available as standard in the unit to prevent foreign particles entry into the unit.
A 2” fi lter rail is installed in the unit to accommodate additional site installed fi lter.
Electrical Control Panel
The control panel is protected by a panel cover to prevent nuisance changes by unauthorized personnel.
Two control options are available as factory installed.
Mechanical Control
Mechanical Control option is suitable for wiring with eld installed thermostat or building management system. The unit is designed where each refrigerant system can be controlled separately, thus allowing
Features:
• 24 volts transformer is provided for fi eld installed thermostat
• Individual compressor, condenser fan motor and evaporator fan motor, with over current protection
• Anti recycle timer to prevent the compressor from rapid and short cycling
• Delay timer to prevent both compressor turning on the same time
• Control circuit fuses
5
Features UAT-C_(i)
Microprocessor Based Control
The control system consists of a microprocessor controller and a user interface remote controller. The controller offers the following features:
• Built in anti recycle timer to prevent compressor short cycling
• Sequential control of compressor, condenser motor and evaporator motor
• Intelligent control to ensure balance usage of compressor in the system
• Auto random restart and memory backup of last setting in case of interrupted power supply
• Energy saving function
• Sensor fault indication
With the remote wired controller connected, the following features can be performed:
• Temperature setting
• 7 days programmable timer
• Error indication on the remote controller for easy troubleshooting
6
UAT-C_(i) Fan Performance Chart
Fan Performance Chart
UAT150C
0
100
200
300
400
500
600
700
3600 4100 4600 5100 5600
Air Flow
Total Static Pressure (Pa)
800
700
1000
Internal Static Pressure
Standard Point
CFM
900
1.5 kW
3.0 kW
1700 1900 2100 2300 2500 2642 L/S
1100
1200
1300
1400
RPM
2.2 kW
7
Fan Performance Chart UAT-C_(i)
UAT180C
0
100
200
300
400
500
600
700
5200 5700 6200 6700 7200 7700
Air Flow
Total Static Pressure (Pa)
800
700
1000
Internal Static Pressure
Standard Point
CFM
900
3.7 kW
3.0 k
W
RPM
2454 2600 2800 3000 3200 3400 3630 L/S
1100
1200
1300
1400
2.2 kW
8
UAT-C_(i) Fan Performance Chart
0
100
200
300
400
500
600
700
6500 7000 7500 8000 8500 9000 9500
Total St atic Pressure (Pa)
Air Flow
UAT240C
800
700
600
Internal Static Pressure
Standard
Point
CFM
900
5.5 kW
3.7 kW
3.0 kW
RPM
3870
L/S
3270
3470
3070
3670
4480
4070
4270
Loading...