Daikin RZQ-DV1 User Manual

technical data
Split Sky Air
air conditioning systems
RZQ-DV1
EEDEN09-100
EEDEN09-100 - 01/2009
Printed in Belgium by Goekint Graphics
Copyright © Daikin
Naamloze Vennootschap
Zandvoordestraat 300
B-8400 Ostend, Belgium
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende
Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin Europe N.V. is approve d by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
Daikin units comply with the European regulations that guarantee the safety of the product.
Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.
Daikin’s unique position as a man­ufacturer of air conditioning equip­ment, compressors and refrige­rants has led to its close involve­ment in environmental issues. For several years Daikin has had the in­tention to become a leader in the provision of products that have limited impact on the environ­ment. This challenge demands the eco design and development of a wide range of products and an en­ergy management system, result­ing in energy conservation and a reduction of waste.
“ The present publication is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular pur­pose of its content and the products and services presented therein. Specifications are subject to change without prior notic e. Daikin Eu­rope N.V. explicitly rejects any liability for any direct or indirect dam­age, In the broadest sense , arising from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”
EEDEN09- 10 0
technical data
Split Sky Air
air conditioning systems
RZQ-DV1
EEDEN09-100
• Split Sky Air • Outdoor Units
4
• Outdoor Units • R-410A • RZQ-DV1
TABLE OF CONTENTS
RZQ-DV1
1Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Electrical data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
4Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Combination table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 24
Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
8 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
9 Sound data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Sound power spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
10 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installation method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
• Outdoor Units • R-410A • RZQ-DV1
1
1
• Split Sky Air • Outdoor Units
5
1 Features
Outdoor Uni Split Sky RZQ-DV1R-410A
Outdoor units for pair, twin, triple, double twin application
The Sky Air Inverter is developed for use in shops, restaurants and small offices. This innovative Daikin unit provides a more comfortable environment and offers great savings in energy consumption to shop and office owners.
The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level
An inverter driven compressor allows the capacity to be adjusted precisely to match variations in room and outside temperatures.
During start up, the room can be cooled down or heated very quickly. Once the temperature in the room has reached its set point, the low power operation starts to save energy.
Daikin outdoor units are neat and sturdy and can be mounted easily on a roof or terrace or simply placed against an outside wall.
Outdoor units are fitted with either a swing or scroll compressor, renowned for low noise and high energy efficiency
A special acryl precoated fin for anti-corrosion treatment on the heat exchanger ensures greater resistance against severe weather conditions
3 1
2
• Split Sky Air • Outdoor Units
6
• Outdoor Units • R-410A • RZQ-DV1
2 Specifications
2-1 NOMINAL CAPACITY AND NOMINAL INPUT RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
For combination indoor units + outdoor units
Indoor Units FCQH71D7VEB FCQH100D7VEB FCQH125D7VEB FCQH140D7VEB
Cooling capacity Standard kW 7.1 10.0 12.5 14.0 Heating capacity Standard kW 8.0 11.2 14.0 16.0 Power Input Cooling Standard kW 1.88 2.50 3.48 4.36
Heating Standard kW 1.92 2.47 3.46 4.29
For combination indoor units + outdoor units
EER Nominal 3.78 4.00 3.59 3.21 COP Nominal 4.16 4.53 4.05 3.73 Energy Label Cooling A
Heating A Annual energy consumption kWh 940 1,250 1,740 2,180 Indoor Units FBQ71C7VEB FBQ100C7VEB FBQ125C7VEB FBQ140C7VEB
Cooling capacity Standard kW 7.1 10.0 12.5 13.4 Heating capacity Standard kW 8.0 11.2 14.0 15.0 Power Input Cooling Standard kW 2.09 2.70 3.59 4.45
Heating Standard kW 2.08 2.69 3.87 4.40
For combination indoor units + outdoor units
EER Nominal 3.39 3.70 3.48 3.01 COP Nominal 3.85 4.16 3.62 3.41 Energy LabelCooling AAAB
Heating AAAB Annual energy consumption kWh 1,047 1,351 1,796 2,226 Indoor Units FCQ71C7VEB FCQ100C7VEB FCQ125C7VEB FCQ140C7VEB
Cooling capacity Standard kW 7.1 10.0 12.5 14.0 Heating capacity Standard kW 8.0 11.2 14.0 16.0 Power Input Cooling Standard kW 2.11 2.64 3.70 5.11
Heating Standard kW 2.21 2.96 3.88 4.89
For combination indoor units + outdoor units
EER Nominal 3.36 3.79 3.38 2.74 COP Nominal 3.62 3.78 3.61 3.27 Energy Label Cooling A A A D
Heating AAAC Annual energy consumption kWh 1,055 1,319 1,849 2,555 Indoor Units FHQ71BVV1B FHQ100BVV1B FHQ125BVV1B
Cooling capacity Standard kW 7.1 10.0 12.5 Heating capacity Standard kW 8.0 11.2 14.0 Power Input Cooling Standard kW 2.34 3.14 4.24
Heating Standard kW 2.58 3.43 4.28
For combination indoor units + outdoor units
EER Nominal 3.03 3.18 2.95 COP Nominal 3.10 3.27 3.27 Energy Label Cooling B B C
Heating DCC Annual energy consumption kWh 1,172 1,572 2,119 Indoor Units FAQ71BVV1B FAQ100BVV1B FDQ125B8V3B9
Cooling capacity Standard kW 7.1 10.0 12.5 Heating capacity Standard kW 8.0 11.2 14.0 Power Input Cooling Standard kW 2.28 3.29 3.96
Heating Standard kW 2.33 3.21 3.61
For combination indoor units + outdoor units
EER Nominal 3.11 3.04 3.16 COP Nominal 3.43 3.49 3.88 Energy Label Cooling B B B
Heating BBA Annual energy consumption kWh 1,141 1,645 1,978 Indoor Units FUQ71BVV1B FUQ100BVV1B FUQ125BVV1B
Cooling capacity Standard kW 7.1 10.0 12.5 Heating capacity Standard kW 8.0 11.2 14.0 Power Input Cooling Standard kW 2.21 2.97 3.96
Heating Standard kW 2.34 3.31 4.26
• Outdoor Units • R-410A • RZQ-DV1
1
2
• Split Sky Air • Outdoor Units
7
2 Specifications
For combination indoor units + outdoor units
EER Nominal 3.21 3.37 3.16 COP Nominal 3.42 3.38 3.29 Energy Label Cooling A A B
Heating B C C
Annual energy consumption kWh 1,105 1,484 1,978
2-2 TECHNICAL SPECIFICATIONS RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
Casing Colour Ivory White
Material Painted galvanised steel
Dimensions Unit Height mm 770 1,345 1,345 1,345
Width mm 900 900 900 900 Depth mm 320 320 320 320
Packing Height mm 900 1,524 1,524 1,524
Width mm 980 980 980 980 Depth mm 420 420 420 420
Weight Unit kg 67 109 109 109
Packed Unit kg 71 126 126 126
Heat Exchanger Dimensions Length mm 857 857 857 857
Nr of Rows 2222 Fin Pitch mm 1.4 1.4 1.4 1.4 Nr of Passes 8 10 10 10 Face Area
0.641 1.131 1.131 1.131
Nr of Stages 34 60 60 60 Tube type Hi-XSS(8) Fin Type WF fin
Treatment Anti-corrosion treatment (PE)
Fan Type Propeller
Discharge direction Horizontal Quantity 1222 Air Flow Rate
(nominal at 230V)
Cooling m³/min 52 96 100 97
Heatingm³/min48909090 Motor Quantity 1222
Model KFD-325-70-8A Brushless DC Motor
MotorSpeed (nominal)Steps 8888
Cooling
(Standard)
rpm 800 800 850 830
Heating
(Standard)
rpm 745 760 760 760
Fan Motor Output W 70 70 70 70
Drive Direct drive
CompressorQuantity 1111
Motor Model 2YC63DXD JT100G-VD JT100G-VD JT100G-VD
Type Hermetically sealed
swing compressor
Hermetically sealed scroll compressor
Motor Output W 1,700 2,200 2,200 2,200
Crankcase
Heater
W333333
Starting Method Inverter driven
Operation Range Cooling Min °CDB -15.0 -15.0 -15.0 -15.0
Max °CDB 50.0 50.0 50.0 50.0 Heating Min °CWB -20.0 -20.0 -20.0 -20.0
Max °CWB 15.5 15.5 15.5 15.5
Sound Level (nominal)
Cooling Sound Power dBA 64 65 67 68
Sound Pressure
(Standard)
dBA48505151
Heating
Sound Pressure
(Standard)
dBA50525353
Sound Level (Night quiet)
Sound Pressure dBA 43 45 45 46
2-1 NOMINAL CAPACITY AND NOMINAL INPUT RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
3 1
2
• Split Sky Air • Outdoor Units
8
• Outdoor Units • R-410A • RZQ-DV1
2 Specifications
Refrigerant Type R-410A
Charge kg 2.75 3.95 3.95 3.95 Control Expansion valve (electronic type) Nr of Circuits 1 1 1 1
Refrigerant Oil Type FVC50K Daphne FVC68D
Charged Volume l 0.75 1.0 1.0 1.0
Piping connections Liquid (OD) Quantity 1 1 1 1
Type Flare connection Diameter (OD)
mm 9.52 9.52 9.52 9.52
Gas Quantity 1 1 1 1
Type Flare connection Diameter (OD)
mm 15.9 15.9 15.9 15.9
Drain Quantity 3 3 3 3
Type Hole Diameter (OD)
mm 26 26 26 26
Piping Length Minimum m 5 5 5 5
Maximum m 50 75 75 75 Equivalent m 70 95 95 95
Chargeless m 30 30 30 30 Additional Refrigerant Charge kg/m See installation manual 4PW48323-1 Installation height
difference
Maximum m 30.0 30.0 30.0 30.0
Max. internunit level difference m 0.5 0.5 0.5 0.5 Heat Insulation Both liquid and gas pipes
Defrost Method Pressure equalising Defrost Control Temperature Capacity Control Method Inverter controlled Safety Devices High pressure switc h
Fan motor thermal protector
Fuse
Standard Accessories
Item Tie-wraps Quantity 2 2 2 2 Item Installation manual Quantity 1 1 1 1
Notes Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor
temperature : 35°CDB, equivalent refrigerant piping : 5m, level difference : 0m.
Nominal heating capacities are based on: indoor temperature: 20°CDB; outdoor temperature:
7°CDB, 6°CWB; equivalent refrigerant piping length: 5m; level difference: 0m
2-3 ELECTRICAL SPECIFICATIONS RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
Power Supply Name V1
Phase 1~ Frequency Hz 50 50 50 50 Voltage V 220-240 Voltage range Minimum V 198 198 198 198
Maximum V 264 264 264 264 Current Recomended fuses A 20 32 32 32 Wiring
connections
For Power Supply
Remark See installation manual 4PW48323-1
For connection with indoor
Remark See installation manual 4PW48323-1
Power Supply Intake Outdoor unit only Notes See separate drawings for electrical data
(1) European/international technical standard setting the limits for harmonic currents produced by equipment
connected to public low-voltage system with input current > 16A smaller than or equal to 75A per phase.
(2) Short-circuit power
Power supply to the FDQ
indoor unit is separate
2-2 TECHNICAL SPECIFICATIONS RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
• Outdoor Units • R-410A • RZQ-DV1
1
3
• Split Sky Air • Outdoor Units
9
3 Electrical data
3D063310
SYMBOLS
MCA : Min. Circuit Amps (A) TOCA : Total Over Current Amps (A) MFA : Max. Fuse Amps (A) (See note 7) MSC : MSC means the max. current during the
starting of compressor. (A) RLA : Rated Load Amps (A) OFM : Outdoor Fan Motor (A) IFM : Indoor Fan Motor FLA : Full Load Amps kW : Fan Motor Rated Output (kW)
RZQ71-140DV1
Unit combination Power supply Comp. OFM IFM
Indoor unit Outdoor unit
Hz-volts
Voltage range
MCA TOCA MFA MSC RLA kW FLA kW FLA
NOTES
1 RLA is based on the following conditions:
Power supply: 50Hz - 230V Cooling Indoor temperature 27°CDB/19°CWB Outdoor temperature 35°CDB Heating Indoor temperature 20.0°CDB
Outdoor temperature 7.0°CDB/6.0°CWB 2 TOCA means the total value of each OC set 3 Voltage range
Units are suitable for use on electrical systems where
voltage supplied to unit terminals is not below or
above listed operation range limits 4 Maximum allowable voltage unbalance between
phases is 2% 5 MCA represents maximum input current., MFA
represents capacity which may accept MCA
(next lower standard fuse rating, min.15A) 6 Select wire size based on the larger value of MCA or
TOCA 7 MFA is used to select the circuit breaker and the
ground fault circuit interrupter (earth leakage circuit
breaker)
3 1
4
• Split Sky Air • Outdoor Units
10
• Outdoor Units • R-410A • RZQ-DV1
4 Options
RZQ(S)71-140DV1
3TW26739-1F
Name of option
Kit name
RZQ71D7V1B RZQ100D7V1B RZQ125D7V1B RZQ140D7V1B
RZQS71D7V1B RZQS100D7V1B RZQS125D7V1B RZQS140D7V1B
- RZQ100B8W1B RZQ125B8W1B RZQ140B8W1B
Central drain plug EKDK04
Refrigerant branch piping
Twin KHRQ22M20TA (KHRQ58T): see note
Triple - KHRQ127H (KHRQ58H): see note
Double-twin - -
KHRQ22M20TA (KHRQ58T): see note
(3x)
Demand adapter kit KRP58M51
NOTE
1 For RZQ100-140B8W1B in combination with FCQ35-71C, FCQH71C or FCQH71D use the refrigerant branch piping mentioned between brackets.