Daikin RZQ100D9V1B user guide manual

INSTALLATION MANUAL
Split System air conditioners
RZQ71D3V1B
RZQ100D9V1B RZQ125D9V1B RZQ140D9V1B
RZQ100B9W1B RZQ125B9W1B RZQ140B9W1B
D2D2
L1
L2
B1
B2
D2D2
L1
L2
1
B2
B2
D2
D2D2
CC
L2
L2
AA
D1D1D1
EE
L1
L1
HH
B1B1B1
1
B2B2B2
D2
D2D2
EE
L1
L1
HH
B1
B1
1
2
CC
L2
L2
AA
D1D1D1
2
L1
H1
H2
6
E
A
B
C
H
D
3
L2
L3L1
H1
H2
4
H1
L2
L3
L4L1
H2
5
H1
L2
L3
L4
L5
L6
L7L1
7
8
1
3
R410A
24 5
1
3
R410A
24 59
8 9
3 4 5 6
AB
1324 5
6
6
8
7
9
1 2
3
V1-type
1~ 50 Hz
220-240 V
3N~ 50 Hz
L1 L3
L2
L1 L3L2
W1-type
400 V
IV
.
01
02
03
04
05
06
07
08
09
10
11
12
13
ATITIKTIES-DEKLARACIJA
ATBILSTĪBAS-DEKLARĀCIJA
VYHLÁSENIE-ZHODY
CE -
CE -
CE -
CE - UYUMLULUK-BİLDİRİSİ
ZJAVA O SKLADNOSTI
VASTAVUSDEKLARATSIOON
ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
CE - I
CE -
CE -
deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów, których dotyczy niniejsza deklaracja:
declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
m
r
IZJAVA-O-USKLAĐENOSTI
DEKLARACJA-ZGODNOŚCI
DECLARAŢIE-DE-CONFORMITATE
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE -
CE -
CE -
14
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
.
.
.
.
*
.
. 07
*
.
.
.
.
.
Direktive z vsemi spremembami.
Direktiivid koos muudatustega.
Директиви, с техните изменения.
Direktyvose su papildymais.
Direktīvās un to papildinājumos.
Smernice, v platnom znení.
Değiştirilmiş halleriyle Yönetmelikler.
Direktiver, med senere ændringer.
Direktiv, med företagna ändringar.
Direktiver, med foretatte endringer.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
v platném znění.
Smjernice, kako je izmijenjeno.
irányelv(ek) és módosításaik rendelkezéseit.
z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
декларира на своя отговорност, че моделите климатична инсталация, за които се отнася тази декларация:
visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeĮu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie:
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu klima modellerinin aşağıdaki gibi olduğunu beyan eder:
t
v
k
w
25
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
instrukcjami:
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
conformitate cu instrucţiunile noastre
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
инструкции:
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
s našim návodom:
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
Directives, as amended.
Direktiven, gemäß Änderung.
Directives, telles que modifiées.
Richtlijnen, zoals geamendeerd.
Directivas, según lo enmendado.
Direttive, come da modifica.
√‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
*
**
o
x
b
.
.
i
.
.
.
*
.
<A> DAIKIN.TCF.021F17/03-2010
v
<B>
<B>
pozitīvajam
и оценено
z późniejszymi poprawkami.
Directivelor, cu amendamentele respective.
<A>
<B>
a pozitívne zistené
съгласно
<B>
sertifikātu <C>
<A>
ir kaip teigiamai nuspręsta
un atbilstoši
<A>
<A>
Sertifikatą <C>
положително от
както е изложено в
21 Забележка *
Directivas, conforme alteração em.
Директив со всеми поправками.
igazolta a megfelelést,
<B>
szerint.
alapján, a(z)
<A>
<C> tanúsítvány
a(z)
a(z)
vērtējumam saskaņā ar
pagal
Cертификата <C>
kaip nustatyta
kā norādīts
ako bolo uvedené v
22 Pastaba *
23 Piezīmes *
24 Poznámka *
v
<B>
, pozytywną opinią
şi apreciat pozitiv
Certificatul <C>
<A>
<A>
in odobreno s strani
<A>
certifikatom <C>
în conformitate cu
Świadectwem <C>
<B>
de
zgodnie z dokumentacją
<B>
aşa cum este stabilit în
kot je določeno v
skladu s
.
.
.
.
*
01
02
03
04
05
<B> KEMA (NB0344)
<C> 2024351-QUA/EMC02-4565
<C> Sertifikasına
Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
**
**
**
**
20
21
22
19
tarafından olumlu olarak
<B>
osvedčením <C>
‘da belirtildiği gibi ve
değerlendirildiği gibi.
súlade s
<A>
göre
Not
25
ja heaks
<A>
sertifikaadile <C>
järgi vastavalt
<B>
kiidetud
nagu on näidatud dokumendis
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir.
**
**
**
23
24
25
PROHLÁŠENÍ-O-SHODĚ
CE - ERKLÆRING OM-SAMSVAR
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE -
заявляет, исключительно под свою ответственность, что модели кондиционеров воздуха, к которым относится настоящее заявление:
erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører:
u
q
CE - DECLARAÇÃO-DE-CONFORMIDADE СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - ¢H§ø™H ™YMMOPºø™H™
CE - DECLARACION-DE-CONFORMIDAD
CE - DICHIARAZIONE-DI-CONFORMITA
prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi:
deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon innebærer at:
s
n
teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit:
j
c
y
h
declaración:
referencia la
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) nor mativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
инструкциям:
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
instrukser:
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
förutsättning att användning sker i överensstämmelse med våra instruktioner:
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
disse brukes i henhold til våre instrukser:
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
mukaisesti:
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
Machinery 2006/42/EC
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC
ob upoštevanju določb:
vastavalt nõuetele:
следвайки клаузите на:
laikantis nuostatų, pateikiamų:
ievērojot prasības, kas noteiktas:
održiavajúc ustanovenia:
bunun koşullarına uygun olarak:
under iagttagelse af bestemmelserne i:
enligt villkoren i:
gitt i henhold til bestemmelsene i:
noudattaen määräyksiä:
za dodržení ustanovení předpisu:
prema odredbama:
követi a(z):
zgodnie z postanowieniami Dyrektyw:
în urma prevederilor:
Notă *
16 Megjegyzés *
17 Uwaga *
18
on
<B>
ja jotka
enligt
<B>
och godkänts av
<A>
enligt
11 Information *
e giudicato positivamente
<A>
delineato nel
mukaisesti.
<A>
Sertifikat <C>
og gjennom positiv
<A>
ifølge
<B>
Sertifikaatin <C>
hyväksynyt
Certifikatet <C>
som det fremkommer i
bedømmelse av
jotka on esitetty asiakirjassa
12 Merk *
13 Huom *
Certificado <C>
¶ИЫЩФФИЛЩИОfi <C>
e com o parecer
Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
<A>
<A>
Certificato <C>
de acordo com o
Û‡Ìʈӷ Ì ÙÔ
<B>
<B>
secondo il
<B>
positivo de
·fi ÙÔ
tal como estabelecido em
da
* fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ
™ËÌ›ˆÛË
06 Nota *
08 Nota
<B>
positiv
<B>
<C>
<C>
et évalué positivement par
Certificat <C>
<A>
Certificate
and judged positively by
Zertifikat
aufgeführt und von
<A>
<A>
conformément au
beurteilt gemäß
according to the
as set out in
wie in der
tel que défini dans
<B>
Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan.
Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce.
Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji.
**
**
**
14
19 Opomba *
20 Märkus
v
<B>
a pozitivně zjištěno
i pozitivno ocijenjeno od
<A>
Certifikatu <C>
<A>
prema
osvědčením <C>
<B>
strane
jak bylo uvedeno v
kako je izloženo u
souladu s
14 Poznámka *
15 Napomena *
i
<B>
согласно
<B>
и в соответствии с
og positivt vurderet af
<A>
<A>
Certifikat <C>
положительным решением
henhold til
как указано в
Свидетельству <C>
som anført i
09 Примечание *
10 Bemærk *
y es valorado
de acuerdo con el
<A>
Certificaat <C>
en positief beoordeeld door
<B>
<A>
overeenkomstig
zoals vermeld in
<B>
como se establece en
Certificado <C>
positivamente por
15
13
∏ Daikin Europe N.V. Â›Ó·È ÂÍÔ˘ÛÈÔ‰ÔÙË̤ÓË Ó· Û˘ÓÙ¿ÍÂÈ ÙÔÓ ∆¯ÓÈÎfi Ê¿ÎÂÏÔ Î·Ù·Û΢‹˜.
A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico.
Компания Daikin Europe N.V. уполномочена составить Комплект технической документации.
**
**
**
08
09
07
A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására.
Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej.
Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie.
**
**
**
16
18
17
Jean-Pierre Beuselinck
General Manager
Ostend, 1st of April 2010
Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata.
Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen.
Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen.
**
**
**
10
11
12
declares under its sole responsibility that the air conditioning models to which this declaration relates:
erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft:
declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace
dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione:
a
d
f
l
e
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
i
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Щ· МФУЩ¤П· ЩˆУ ОПИМ·ЩИЫЩИОТУ Ы˘ЫОВ˘ТУ ЫЩ· ФФ›· ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere:
g
p
RZQ71D3V1B*,
RZQ100D9V1B*, RZQ125D9V1B*, RZQ140D9V1B*,
RZQ100B9W1B*, RZQ125B9W1B*, RZQ140B9W1B*,
* = , , 1, 2, 3, ..., 9
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
instructions:
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
daß sie gemäß unseren Anweisungen eingesetzt werden:
sont conformes à la/aux norme(s) ou autre(s) document(s) nor matif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
onze instructies:
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) nor mativo(s), siempre que sean utilizados de acuerdo con
following the provisions of:
gemäß den Vorschriften der:
conformément aux stipulations des:
overeenkomstig de bepalingen van:
siguiendo las disposiciones de:
secondo le prescrizioni per:
Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
de acordo com o previsto em:
nuestras instrucciones:
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
nostre istruzioni:
В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
EN60335-2-40,
в соответствии с положениями:
01 Note *
02 Hinweis *
03 Remarque *
04 Bemerk *
05 Nota
Daikin Europe N.V. is authorised to compile the Technical Construction File.
** 01
Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen.
Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique.
Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen.
Daikin Europe N.V. está autorizado a compilar el Archivo de Construcción Técnica.
Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruzione.
**
**
**
**
** 06
3PW61025-1
02
03
04
05
RZQ71D3V1B RZQ100D9V1B RZQ100B9W1B RZQ125D9V1B RZQ125B9W1B RZQ140D9V1B RZQ140B9W1B
Split System air conditioners
CONTENTS Page
Safety considerations........................................................................ 1
Before installation.............................................................................. 2
Selecting installation site................................................................... 3
Precautions on installation ................................................................4
Installation servicing space ...............................................................4
Refrigerant pipe size and allowable pipe length................................ 5
Precautions on refrigerant piping ......................................................6
Refrigerant piping.............................................................................. 7
Evacuating......................................................................................... 9
Charging refrigerant ........................................................................10
Electrical wiring work....................................................................... 12
Test operation.................................................................................. 13
Disposal requirements .................................................................... 14
Wiring diagram ................................................................................ 15
READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.
The English text is the original instruction. Other languages are translations of the original instructions.

SAFETY CONSIDERATIONS

The precautions listed here are divided into the following two types. Both cover very important topics, so be sure to follow them carefully.
WARNING
If the warning is not observed, it may cause serious casualties.
CAUTION
If the caution is not observed, it may cause injury or damage to the equipment.
Warning
For year round cooling applications with low indoor humidity conditions, such as Electronic Data Processing rooms, contact your dealer or see the engineering databook or the service manual.
The equipment is not intended for use in a potentially explosive atmosphere.
For use of air-conditioning units in applications with temperature alarm settings it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded. The air-conditioning unit may stop for several minutes during normal operation for "defrosting of the indoor unit" or when in "thermostat-stop" operation.
Installation manual
Ask your dealer or qualified personnel to carry out installation work Do not install the machine by yourself. Improper installation may result in water leakage, electric shocks or fire.
Perform installation work in accordance with this installation manual. Improper installation may lead to water leakage, electric shocks or fire.
Consult your local dealer regarding what to do in case of refrigerant leakage. When the air conditioner is to be installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen depletion.
Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in water leakage, electric shocks, fire, or the unit falling.
Install the air conditioner on a foundation that can withstand its weight. Insufficient strength may result in the fall of equipment and causing injury.
Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes. Improper installation work may result in accidents due to fall of equipment.
Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this installation manual, using a separate circuit. Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secure, using the specified wires and ensuring that external forces do not act on the terminal connections or wires. Incomplete connection or fixing may cause a fire.
When wiring between the indoor and outdoor units, and wiring the power supply, form the wires so that the frontside panel can be securely fastened. If the frontside panel is not in place, overheat of the terminals, electric shocks or a fire may be caused.
If refrigerant gas leaks during installation work, ventilate the area immediately. To xic gas may be produced if refrigerant gas comes into contact with fire.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas. To xic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
Before touching electric terminal parts, turn off power switch.
Live parts can be easily touched by accident.
Never leave the unit unattended during installation or servicing when the service panel is removed.
When planning to relocate former installed units, you must first recover the refrigerant after the pumping-down operation. Refer to chapter "Precaution for pumping-down operation" on page 11.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
.
Installation manual
1
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1
Caution

BEFORE INSTALLATION

Ground the air conditioner. Grounding resistance should be according to national regulations Do not connect the earth wire to gas or water pipes, lightning conductor or telephone earth wire. Incomplete grounding may cause electric shocks.
Gas pipe.
Ignition or explosion may occur if the gas leaks.
Water pipe.
Hard vinyl tubes are not effective grounds.
Lightning conductor or telephone ground wire.
Electric potential may rise abnormally if struck by lightning.
Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may cause electric shocks and fire.
Install drain piping according to this installation manual to ensure good drainage, and insulate the pipe to prevent condensation. Improper drain piping may cause water leakage, and make the furnitures get wet.
Install the indoor and outdoor units, power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not rinse the outdoor unit. This may cause electric shocks or fire.
Do not install the air conditioner in places such as the following:
Where there is mist of mineral oil, oil spray or vapour for
example a kitchen. Plastic parts may deteriorate, and cause them to fall out or
water to leak.
Where corrosive gas, such as sulphurous acid gas, is
produced. Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.
Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.
Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled.
Such gases may cause a fire.
Where the air contains high levels of salt such as that near
the ocean.
Where voltage fluctuates a lot, such as that in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.
Since maximum working pressure is 4.0 MPa or 40 bar, pipes of larger wall thickness may be required. Refer to paragraph "Selection of piping material" on page 5.

Precautions for R410A

The refrigerant requires strict cautions for keeping the system clean, dry and tight.
- Clean and dry Foreign materials (including mineral oils or moisture) should be prevented from getting mixed into the system.
- Tight Read "Precautions on refrigerant piping" on page 6 carefully and follow these procedures correctly.
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (If the refrigerant is in state of gas, its composition changes and the system will not work properly).
The connected indoor units must be indoor units designed exclusively for R410A.

Installation

For installation of the indoor unit(s), refer to the indoor unit installation manual.
Illustrations show class 125 outdoor unit type. Other types also follow this installation manual.
This outdoor unit requires the pipe branching kit (optional) when used as the outdoor unit for the simultaneous operation system. Refer to catalogues for details.
Never operate the unit with a damaged or disconnected discharge thermistor and suction thermistor, burning of the compressor may result.
Be sure to confirm the model name and the serial no. of the outer (front) plates when attaching/detaching the plates to avoid mistakes.
When closing the service panels, take care that the tightening torque does not exceed 4.1 N•m.

Accessories

Check if the following accessories are included with the unit
Installation manual 1
Clamp 2
Fluorinated greenhouse gases label
1

Provide a logbook

In accordance with the relevant national and international codes, it may be necessary to provide a logbook with the equipment containing at least
- info on maintenance,
- repair work,
- results of tests,
- stand-by periodes,
- etc...
In Europe, EN378 provides the necessary guidance for this logbook.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Multilingual fluorinated greenhouse gases label
1
Installation manual
2
See the figure below for the location of the accessories.
1 Accessories

Handling

As shown in the figure, bring the unit slowly by grabbing the left and right grips.
Place your hands on the corner instead of holding the suction inlet in the side of the casing, otherwise the casing could be deformed.
Ta ke care not to let hands or objects come in contact with rear fins.
2 When installing the unit in a place exposed to strong wind, pay
special attention to the following. Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air), and this may have the following consequences:
- Deterioration of the operational capacity.
-Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks. Refer to the figures for installation of this unit in a place where the wind direction can be foreseen.
Tu rn the air outlet side toward the building's wall, fence or screen.
Make sure there is enough room to do the installation
Set the outlet side at a right angle to the direction of the wind.

SELECTING INSTALLATION SITE

Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
1 Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and vibration and where the unit can be installed level.
- Places where there is no possibility of flammable gas or product leak.
- The appliance shall not be placed nor used in a potentially explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the indoor and outdoor units' piping and wiring lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Strong wind
Blown air Strong wind
3 Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
4 If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the foundation should be maximum 150 mm).
5 If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction.
6 When installing the unit in a place frequently exposed to snow,
pay special attention to the following:
- Elevate the foundation as high as possible.
- Remove the rear suction grille to prevent snow from accumulating on the rear fins.
7 If you install the unit on a building frame,
please install a waterproof plate (within 150 mm of the underside of the unit) or use a drain plug kit (option) in order to avoid the drainwater dripping. (See figure).
Installation manual
3
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1

PRECAUTIONS ON INSTALLATION

INSTALLATION SERVICING SPACE

Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installation.
In accordance with the foundation drawing in the figure, fix the unit securely by means of the foundation bolts. (Prepare four sets of M12 foundation bolts, nuts and washers each which are available on the market.)
It is best to screw in the foundation bolts until their length are 20 mm from the foundation surface.
A
140
117
219
289
47
A Discharge side B Bottom view (mm) C Drain hole
B
423
614

Installation method for prevention of falling over

If it is necessary to prevent the unit from falling over, install as shown in the figure.
prepare all 4 wires as indicated in the drawing
unscrew the top plate at the 4 locations indicated A and B
put the screws through the nooses and screw them back tight
140620
20
350
(345-355)
C
AA
B
The numerical figures used in here represent the dimensions for the 71-100-125-140 class models. Figures between ( ) indicate the dimensions for the 100-125-140 class models. (Unit: mm)
(Refer to "Precautions on installation" on page 4)
Precaution (A) In case of non-stacked installation (See figure 1)
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle
Obstacle is present
In these cases, close the
1
bottom of the installation frame to prevent the discharged air from being bypassed
In these cases, only 2
2
units can be installed.
This situation is not allowed
(B) In case of stacked installation
1. In case obstacles exist in front of the outlet side.
A
100
1000
2. In case obstacles exist in front of the air inlet.
C
A location of the 2 fixation holes on the front side of the unit B location of the 2 fixation holes on the rear side of the unit C wires: field supply

Drain pipe disposal

If drain pipe disposal from the outdoor unit causes trouble (for example, if the drain water may splash on people) provide the drain piping using a drain socket (optional).
Make sure the drain works properly.
A
100
200
(300)
Do not stack more than one unit. About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
(C) In case of multiple-row installation (for roof top use, etc.)
1. In case of installing one unit per row.
50
(100)
1000 (2000)
100
(200)
500
(1000)
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Installation manual
4
2. In case of installing multiple units (2 units or more) in lateral connection per row.
L
A
2000 (3000)
H
1000
(1500)
400 (600)
Relation of dimensions of H, A and L are shown in the table below.
L A
LH
H<L Installation impossible
0<L1/2H 150 (250) 1/2H<L 200 (300)
REFRIGERANT PIPE SIZE AND ALLOWABLE PIPE
LENGTH

Refrigerant pipe size

Refer to figure 3 for twin system, to figure 4 for triple system and to
figure 5 for double twin system.
Main pipe (pipe between outdoor and first branch). The pipes should have the same size as the outdoor connections.
Refrigerant pipe size
Gas pipe
Model Size-down Standard size Size-up
RZQ71 Ø12.7 RZQ100~140 Ø19.1
Model Size-down Standard size Size-up
RZQ71~140 Ø6.4 Ø9.5 Ø12.7
(a) In case of twin, triple and double twin applications, the listed refrigerant pipe
sizes relate to the main pipes only. (L1 = the pipes between the outdoor unit and the branch in figures 3~5).
Ø15.9
Liquid pipe
Pipe between first branch and second branch (L2+L3) (only for double twin).
Liquid Ø9.5 Gas Ø15.9
(a)
Installation shall be done by a licensed refrigeration technician, the choice of materials and installation shall comply with the applicable national and international codes. In Europe, EN378 is the applicable standard that shall be used.
To persons in charge of piping work:
Be sure to open the stop valve after piping installing and vacuming is complete. (Running the system with the valve closed may break the compressor.)
It is forbidden to discharge refrigerant into the atmosphere. Collect the refrigerant in accordance with the freon collection and destruction law.
Do not use flux when brazing the refrigerant piping. For brazing, use phosphor copper brazing filler metal (BCuP) which does not require a flux. (If a chlorine flux is used, the piping will corrode, and if the flux contains fluoride, it will cause the coolant oil to deteriorate, adversely affecting the coolant piping system.

Selection of piping material

Piping and other pressure containing parts shall comply with the national and international codes and shall be suitable for refrigerant, use phosphoric acid deoxidised seamless copper for refrigerant.
Temper grade: use piping with temper grade in function of the pipe diameter as listed in table below.
The pipe thickness of the refrigerant piping should comply with relevant local and national regulations. The minimal pipe thickness for R410A piping must be in accordance with the table below.
Temper grade
Pipe Ø
6.4 / 9.5 / 12.7 O 0.80
15.9 O
19.1 1/2H
O=Annealed 1/2H=Half hard
Only use annealed material for flare connections.
of piping material
Minimal thickness t (mm)
1.00
Pipe between branch and indoor units (L2~L3 for twin, L2~L4 for triple and L4~L7 for double twin). These pipe sizes must have the same size as the connected indoor units pipe sizes. Branch: see marking '' on figures 3, 4 and 5.
NOTE
For new installations, use the standard pipe sizes.
When using existing pipes, size-up is allowed as
mentioned in the table above. Size up is only allowed for pair combination (L1). Additional restrictions towards allowable pipe lengths, as mentioned in the table "Allowable pipe
length" on page 6, must be taken into account.
Not using the standard pipe size may result in capacity decrease. The installer must acknowledge this and judge this very carefully in function of the complete installation.

Selection of branch pipe

RZQ100~140B9W1B +
FCQ35~71C / FCQH71C/D
Twin KHRQ22M20TA KHRQ58T Tr iple KHRQ127H KHRQ58H Double twin KHRQ22M20TA (3x) KHRQ58T (3x)
Installation manual
5
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to figures
2, 3, 4 and 5. Assume that the longest line in the figure corresponds
with the actual longest pipe, and the highest unit in the figure corresponds with the actual highest unit.
Maximum total one-way piping length
Pair L1 size-down 10 m (15 m)
•Twin and triple
• Double twin
Maximum allowable piping length
Twin L1+L2+L3 Tr iple L1+L2+L3
Double twin L1+L2+L3
Maximum branch piping length
•Twin and triple
• Double twin
Maximum difference between branch lengths
Twin L2–L3 Tr iple L2–L4 Double twin • L2–L3
Maximum height between indoor and outdoor
All H1 30 m
Maximum height between indoors
Twin, triple and double twin
Chargeless length
All L1+L2+L3
(a) Parenthesized figure represents the equivalent length.
Allowable pipe length
• L1+L2
• L1+L2+ L4
+L4
+L4+L5+ L6+L7
•L2
• L2+L4
• L4–L5
• L6–L7
• (L2+L4)– (L3+L7)
H2
+L4+L5+ L6+L7
Allowable pipe length
Liquid pipe
size
standard
size-up
size-down 10 m (15 m)
standard
size-up
(a)
size-down 10 m
standard 30 m
size-up 15 m
71 100 125 140
50 m
(70 m)
25 m
(35 m)
50 m
(70 m)
25 m
(35 m)
60 m
10 m
Model
75 m
20 m
10 m
0.5 m
75 m (95 m)
35 m (45 m)
75 m (95 m)
35 m (45 m)
75 m
10 m

Existing or pre-installed piping can be used

1. Piping must comply with the criteria below.
• Pipe diameter must comply with the limitations as indicated in paragraph "Refrigerant pipe size" on page 5.
• Piping length must be within limits of the allowable piping length as in paragraph "Allowable pipe length and height difference" on
page 6.
• Piping must be designed for R410A. See paragraph "Selection of
piping material" on page 5.
2. Piping can be reused without cleaning when:
•Total 1-way piping length: <50 m.
• No compressor breakdown has occurred in the history of the unit to be replaced.
•A correct pump down operation can be executed:
- Operate the unit continuously for 30 minutes in cooling mode.
-Execute a pump down operation.
- Remove the air conditioning units to be replaced.
• Check the contamination inside the existing piping.
If you cannot meet all these requirements, the existing pipes must be cleaned or replaced after removing the air conditioning units to be replaced.
3. Prepare the flare connections for higher pressure. See paragraph
"Cautions for flare connection" on page 8.

PRECAUTIONS ON REFRIGERANT PIPING

Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
Use R410A only when adding refrigerant Installation tools: Make sure to use installation tools (gauge manifold charge hose, etc.) that are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system. Vacuum pump: Use a 2-stage vacuum pump with a non-return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working. Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
During tests never pressurize the appliances with a pressure higher than the maximum allowable pressure (see unit name plate: PS).
In order to prevent dirt, liquid or dust from entering the piping, cure the piping with a pinch or taping.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Place Installation period Protection method
Outdoor unit
Indoor unit
More than a month Pinch the pipe
Less than a month
Regardless of the
period
Pinch or tape the pipe
Great caution is needed when passing copper tubes through walls.
Installation manual
6
In case of simultaneous operating system
- Upward and downward piping should be performed at the main piping line.
- Use branch piping kit (optional) for branching refrigerant pipes.
Precautions to be taken. (For details, refer to the manual attached to branch piping kit.)
- Install the branch pipes horizontally (with a maximum inclination of 15°) or vertically.
- Length of branch pipe to the indoor unit should be as short as possible.
-Try to keep lengths of both branch pipes to the indoor unit equal.
When using existing refrigerant piping Pay attention to the following points when using existing refrigerant piping
Perform a visual check on quality of residual oil in existing
refrigerant piping. This check is extremely important because using existing
piping with deteriorated oil will cause compressor breakdown.
- Put some residual oil of the pipes you want to reuse on a piece of white paper or on the white surface of an oil checking reference card and compare that oil colour with the circled colour of the oil checking reference card.
- If oil colour is identical to the circled colour or darker, replace the piping, install new piping or clean the piping thoroughly.
- If oil colour is lighter, the pipes can be reused without cleaning.
An oil checking reference card is indispensable for such evaluation and can be obtained at your dealer.
In the following situations, the existing piping should not be re-used and new piping should be installed.
- If the previously used model had problems with its
compressor (this might cause oxidised coolant oil, scale residue and other adverse effects).
- If the indoor or outdoor units were disconnected from the
piping for a long period of time (water or dirt might have gotten into the piping).
- If copper piping is corroded.
Flares should not be re-used but rather new ones made in order to prevent leaks.
Check welded connections for gas leaks, if the local piping has welded connections.
Replace deteriorated insulation with new material.

REFRIGERANT PIPING

Field pipes can be installed in four directions.
321
44
5 6
10
Figure - Field pipes in four directions
1 Drill 2 Centre area around knockout hole 3 Knockout hole 4 Slit 5 Connecting pipe 6 Bottom frame 7 Front plate 8 Pipe outlet plate 9 Screw front plate
10 Pipe outlet plate screw
A Forward B Backward C Sideways D Downward
Cutting out the two slits makes it possible to install as shown in the figure "Field pipes in four directions". (Use a metal saw to cut out the slits.)
To install the connecting pipe to the unit in a downward direction, make a knockout hole by penetrating the centre area around the knockout hole using a Ø6 mm drill. (See figure "Field pipes in
four directions".)
After knocking out the knock-out, it is recommended to apply repair paint to the edge and the surrounding end surfaces to prevent rusting.

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material (procured locally) to stop up all gaps, as shown in the figure.
78
A
D
B
C
Installation manual
7
1 Putty or insulating material
(produced locally)
Insects or small animals entering the outdoor unit may cause a short circuit in the electrical box.

Cautions for handling stop valve

The stop valves for indoor-outdoor connecting piping are closed at shipment from the factory.
Make sure to keep the valve open during operation.
The names of parts of the stop valve are shown in the figure.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
1 Service port 2 stop valve 3 Field piping connection 4 Valve cover
Split System air conditioners
4PW60930-1
Since the side boards may be deformed if only a torque wrench is used when loosening or tightening flare nuts, always lock the stop valve with a wrench and then use a torque wrench. Do not place wrenches on the valve cover.
1 Spanner 2 Torque wrench
Applying an excessive torque may distort the interior stop valve surface causing gas to leak inside the valve and causing the flare nut to crack eventually.
Do not apply force on the valve cover, this may result in a refrigerant leak.
For cooling operation under low ambient temperature or any other operation under low pressure, apply silicon pad or similar to prevent freezing of the gas stop valve flare nut (see figure). Freezing of the flare nut may cause refrigerant leak.
Silicon sealing pad (Make sure there is no gap)

How to use the stop valve

Use hexagonal wrenches 4 mm and 6 mm.
Opening the valve
1. Place the hex wrench on the valve bar and turn counter-
clockwise.
2. Stop when the valve bar no longer turns. It is now open.
Closing the valve
1. Place the hex wrench on the valve bar and turn clockwise.
2. Stop when the valve bar no longer turns. It is now closed.
B
A
Closing direction
A Liquid side B Gas side

Cautions for handling the valve cover

Cautions for handling service port

Always use a flexible charge hose with a push-rod and valve to enable recovery of remaining refrigerant in the charge hose.
After the work, tighten the valve cover in place. Tightening torque: 11.5~13.9 N•m
Precautions when connecting field piping and regarding insulation
Be careful not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover. If the liquid-side piping insulation might come into contact with it, adjust the height as shown in the figure below. Also, make sure the field piping does not touch the bolts or outer panels of the compressor.
When the outdoor unit is installed above the indoor unit the following can occur: The condensated water on the stop valve can move to the indoor unit. To avoid this, please cover the stop valve with sealing material.
If the temperature is higher than 30°C and the humidity is higher than RH 80%, then the thickness of the sealing materials should be at least 20 mm in order to avoid condensation on the surface of the sealing.
Be sure to insulate the liquid and gas-side field piping and the refrigerant branch kit.
Any exposed piping may cause condensation or burns if touched.
(The highest temperature that the gas-side piping can reach is around 120°C, so be sure to use insulating material which is very resistant.)
1 Compressor 2 Ter minal cover
3 Indoor and outdoor
field piping
4 Corking, etc.
5 Insulation material
6 Bolts
A Be careful with pipe,
bolt and outer panel
A
connections
The valve cover is sealed where indicated by the arrow. Refer to the figure. Ta ke care not to damage it.
After operating the valve, be sure to tighten the valve cover properly.
Tightening torque
Liquid pipe 13.5~16.5 N•m Gas pipe 22.5~27.5 N•m
Check for refrigerant leakage after tightening the cap.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Cautions for flare connection
Please refer to the table for the dimensions for processing flares and for the tightening torques. (Too much tightening will end up in splitting of the flare.)
A dimensions for
Piping
size
Ø6.4 15~17 N•m 8.7~9.1
Ø9.5 33~39 N•m 12.8~13.2 Ø12.7 50~60 N•m 16.2~16.6 Ø15.9 63~75 N•m 19.3~19.7
Flare nut
tightening torque
processing flares
(mm)
Flare shape
±2
90°
45°
±2
A
R=0.4~0.8
Installation manual
8
If a torque wrench is not available, be aware that the tightening torque may increase suddenly. Do not tighten nuts any further than to the angle as listed.
Recommended arm
Piping size Further tightening angle
Ø6.4
Ø9.5 200 mm Ø12.7 Ø15.9 300 mm
60°~90°
30°~60°
length of tool
150 mm
250 mm
When connecting the flare nut, coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly.
After completing the installation, carry out a gas leak inspection of the piping connections with nitrogen and such.

Cautions for necessity of a trap

Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquid compression phenomenon, or cases of deterioration of oil return, it will be necessary to provide a trap at an appropriate place in the riser gas piping.
Tr ap installation spacing. (See figure 6)
A Outdoor unit B Indoor unit C Gas piping D Liquid piping E Oiltrap H Install trap at each difference in height of 10 m.
A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

EVACUATING

Do not purge the air with refrigerants. Use a vacuum pump to vacuum the installation. No additional refrigerant is provided for air purging.
Pipes inside the units were checked for leaks by the manufacturer. The refrigerant pipes fit on site are to be checked for leaks by the installer.
Confirm that the valves are firmly closed before leak test or vacuuming.

Set up for vacuuming and leak test: see figure 8

A Pair system B Simultaneous operation system
1 Pressure gauge 2 Nitrogen 3 Refrigerant 4 Weighing machine 5 Vacuum pump 6 Stop valve 7 Main pipe 8 Branched pipes 9 Pipe branching kit (optional)

Procedure for leak test

Leak test must satisfy EN378-2.
1 Evacuate the pipes and check vacuum
for 1 minute.)
2 Break the vacuum with a minimum of 2 bar of nitrogen. (Never
pressurize more than 4.0 MPa.)
3 Conduct leak test by applying soap water, etc. to the connecting
part of the pipes.
(1)
. (No pressure increase

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing. Brazing without carrying out nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidised film on the inside of the pipes, adversely affecting valves and compressors in the refrigerating system and preventing normal operation. When brazing pipes however, do not use oxidation preventers. Residue of such preventers may result in choking of pipes or malfunction of components.
When brazing while inserting nitrogen into the piping, nitrogen must be set to 0.02 MPa with a pressure-reducing valve (=just enough so that it can be felt on the skin).
12 345
1 Refrigerant piping 2 Part to be brazed 3 Taping 4 Hands valve 5 Pressure-reducing valve 6 Nitrogen
4 Discharge nitrogen.
5 Evacuate and check vacuum again
(1)
.
6 If the vacuum gauge no longer rises, the stop valves can be
opened.
Following should be executed if there is a possibility of moisture remaining in the pipe (if piping work is carried out during the raining season or over a long period of time, rainwater may enter the pipe during work). After evacuating the system for 2 hours, pressurize the system to 0.05 MPa (vacuum break) with nitrogen gas and evacuate the system again using the vacuum pump for 1 hour to –100.7 kPa (vacuum drying). If the system cannot be evacuated to –100.7 kPa within 2 hours, repeat the operation of vacuum break and vacuum drying. Then after leaving the system in vacuum for 1 hour, confirm that the vacuum gauge does not rise.
After air purging with a vacuum pump it may happen that the refrigerant pressure does not rise, not even if the stop valve is opened. Reason for this phenomenon is the closed state of for instance the expansion valve in the outdoor unit circuit, but this is not a problem for running the unit.
(1) Use a 2-stage vacuum pump with a non return valve which
can evacuate to –100.7 kPa (5 Torr, –755 mm Hg). Evacuate the system from the liquid and gas pipes by using a vacuum pump for more than 2 hours and bring the system to –100.7 kPa. After keeping the system under that condition for more than one hour, check if the vacuum gauge rises or not. If it rises, the system may either contain moisture inside or have leaks.
Installation manual
9
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1

CHARGING REFRIGERANT

For pair system

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A
(1)
GWP
value: 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
■➀ the factory refrigerant charge of the product,
■➁ the additional refrigerant amount charged in the field and
■➀+➁ the total refrigerant charge
on the fluorinated greenhouse gases label supplied with the product. The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the service cover).
1 factory refrigerant charge
4
of the product: see unit name plate
1
2 additional refrigerant
amount charged in the
2
field
3 total refrigerant charge
3
4 Contains fluorinated
greenhouse gases covered by the Kyoto Protocol
5 outdoor unit 6 refrigerant cylinder and
manifold for charging
NOTE
5
6
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. Therefore, an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.
Tab le 1: Additional charging of refrigerant <unit: kg>
Standard liquid pipe size
Connected piping length is between
Model 30~40 m 40~50 m 50~60 m 60~75 m
RZQ71 RZQ100~140
Model 15~20 m 20~25 m 25~30 m 30~35 m
RZQ71 RZQ100~140 1.5 2.0
0.5 1.0
Size up liquid pipe size
Connected piping length is between
0.5 1.0
1.5 2.0
For twin, triple, and double twin system
Please charge additional according to the following calculation. (additional amount is R1+R2)
1. G1: total length of Ø9.5 mm liquid piping G2: total length of
Ø6.4 mm liquid piping
2.a G1>30 m calculate length over 30 m (=G1–30 m) Based on this length decide R1, R2 in the table
b G130 m and G1+G2>30 m
calculate total length over
30 m (=G1+G2–30 m)
Based on this decide R2 in the table, R1=0
3. Total additional charge amount R=R1+R2 (kg)
Tab le 2: Length <unit: m>, additional charging of refrigerant <unit: kg>
Liquid
Model 0~10 10~20 20~30 30~45
RZQ71~140
piping
Main Branch Branch 6.4 0.3 0.6 0.9 1.2 R2
Length exceeding "Chargeless length"
Ø
9.5 0.5 1.0 1.5 2.0 R1
Example 1
L2=7 (Ø6.4)
50 type

Precaution for servicing

When performing service on the unit requiring the refrigerant system to be opened, refrigerant must be evacuated according to local regulations.
This unit requires additional charging of refrigerant according to the length of pipe connected at the site. Charge the refrigerant to the liquid pipe in its liquid state through the service port of the liquid stop valve. Since R410A is a mixed refrigerant, its composition changes if charged in a state of gas and normal system operation would no longer be assured.
On this model it is not necessary to charge additionally if the piping length 30 m.
<5 m: See "Total charging weight of the refrigerant (after a leak, etc.)"
on page 11.

Additional charging of refrigerant

The additional charging amounts relate to the refrigerant piping length as in "Maximum total one-way piping length" of the table in paragraph "Allowable pipe length and height difference" on
page 6. (E.g. twin: L1+L2+L3).
Over 30 m, please add refrigerant quantity according to following table.
For future servicing, mark with a circle the selected amount on the tables below
100 type
outdoor heat pump
1 G1=L1=35 m G2=L2+L3=7+5=12 2 Over 30 m
a G130=5 m Ø9.5 R1=0.5 kg b G2=12 m Ø6.4 R2=0.6 kg
3 Refrigerant charge amount=R=R1+R2=0.5+0.6=1.1 kg
L1=35 (Ø9.5) indoor
L3=5 (Ø6.4)
50 type
Example 2
L2=17 (Ø6.4)
125 type
outdoor heat pump indoor
1 G1=L1=5 m G2=L2+L3+L4=17+17+20=54 2 Over
a G1=5 m R1=0.0 kg b (G1+G2)
3 Refrigerant charge amount=R=R1+R2=0.0+0.9=0.9 kg
L1=5 (Ø9.5) L3=17 (Ø6.4)
L4=20 (Ø6.4)
30 m
30=(5+54)30=29 Ø6.4 R2=0.9 kg
50 type
indoor
50 type
50 type
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Installation manual
10
In case of complete recharge of the refrigerant, please first execute vacuuming. Execute this vacuuming from the service port. Do not use the port of the stop valve for vacuuming. Vacuuming can not be executed completely using such port.
Position of service port:
RZQ100~140B Outdoor units have 2 ports on the piping. One between the liquid receiver and the electronic expansion valve and another one between the heat exchanger and the 4-way valve.
RZQ71~140D Outdoor units have 1 port on the piping. It is between the heat exchanger and the 4-way valve.
Systems with sized-up liquid pipe
Replace 30 m by 15 m in calculations above and use the table below.
G1: total length of Ø12.7 mm liquid piping.
Length exceeding
"Chargeless length"
Liquid
Model
RZQ71 Main RZQ100~140 Main 1.5 2.0 RZQ71 Branch 6.4 0.3 0.6 RZQ100~140 Branch 9.5 0.5 1.0
piping
Ø
12.7 0.5 1.0
0~5 m
5~10 m
——
10~15 m

Total charging weight of the refrigerant (after a leak, etc.)

15~20 m

Precaution for pumping-down operation

The outdoor unit is equipped with a low pressure switch or a low pressure sensor to protect the compressor.
Never short-circuit the low pressure switch or low pressure sensor during pump-down operation.
Ta ke the following steps to perform the pumping-down operation.
Preliminary measures
• Make sure to cut off power supply. Open the front panel and cover the PCB and terminal board with insulation sheet to avoid electric shock by accidental touching of live parts.
• Close the front panel before leaving the outdoor unit. You cannot leave the unit unattended in case the front panel remains opened.
•Turn on the power supply and carry out pumping-down operation according to the following procedure.
Pump down operation
RZQ100~140B
Procedure Precaution
1 Make sure that stop valves
both on liquid and on gas side are open.
2 Push the BS1 pumping-down
operation button on the PC board of the outdoor unit.
3 Once compressor operation
stops after 3 or 5 minutes close the stop valve on the liquid side and gas side securely. (See "How to use
the stop valve" on page 8)
4 Tu rn off the power supply.
Compressor and outdoor fan will start operation automatically. The indoor unit fan may automatically start running. Please pay attention to this.
Never leave the outdoor unit
(a)
,
unattended with opened front panel when power supply is on.
The total charging amounts relate to the refrigerant piping length as in "Maximum total one-way piping length" of the table in paragraph
"Allowable pipe length and height difference" on page 6. (E.g. twin:
L1+L2).
Tab le 3: Total charging amount <unit: kg>
Refrigerant piping length
m
Liquid pipe
Model
RZQ100~140B
RZQ71D
RZQ100~140D
Model
RZQ100~140B RZQ71D 2.25 2.25 2.75 3.25 3.75 — RZQ100~140D 3.45 3.45 3.95 4.45 4.95 5.45 5.95
(a) When piping length is less than 5 m, a complete recharging of the unit is required.
Charge the unit with the refrigerant charge as indicated.
size
size-down 3.30 3.30
standard 3.30 3.30 3.80 4.30 4.80 5.30 5.80 6.30
size-down 1.75 1.75
standard 1.75 1.75 2.25 2.75 3.25 3.75
size-down 2.95 2.95
standard 2.95 2.95 3.45 3.95 4.45 4.95 5.45 5.95
Liquid pipe
size
size-up
(a)
5~10 m
3~5
m
(a)
3~5
3.80 3.80 4.30 4.80 5.30 5.80 6.30
10~20 m
20~30 m
30~40 m
Refrigerant piping length
5~10 m
10~15 m
15~20 m
20~25 m
40~50 m
25~30 m
50~60 m
60~75 m
30~35 m
RZQ71~140D
Procedure Precaution
1 Make sure that stop valves
both on liquid and on gas side are open.
2 Push the BS4 pumping-down
operation button on the PC board of the outdoor unit (±8 seconds).
3 Close the stop valve on the
liquid side securely about 2 minutes after the compressor started operation. (See "How
to use the stop valve" on page 8)
4 Once compressor operation
stops after 2 to 5 minutes close the stop valve on the gas side securely. (See "How
to use the stop valve" on page 8)
5 Tu rn off the power supply.
(a) If after finishing pumping-down operation the outdoor unit does not operate,
not even when the remote controller switch is turned on, the remote controller may or may not indicate "
U4
". But this is not a malfunction.
Compressor and outdoor fan will start operation automatically. The indoor unit fan may automatically start running. Please pay attention to this.
Never leave the outdoor unit unattended with opened front panel when power supply is on. In case the stop valve on the liquid side is not securely closed during compressor operation, pumping-down
(a)
,
operation cannot be executed.
• After finishing the pumping-down operation, make sure to
have removed the insulation sheet that was placed in the switch box as a protective measure like in chapter
"Preliminary measures" on page 11.
• When in need of operation, turn off the main power supply
and turn it on again. Make sure that stop valves both on liquid and gas side are open and be sure to operate the unit in cooling operation during test run.
Installation manual
11
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1

ELECTRICAL WIRING WORK

All field wiring and components must be installed by a licensed electrician and must comply with relevant European and national regulations.
All components procured on the site and all electric construction should comply with the applicable local and national codes.
High voltage To avoid electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, make sure that those voltages are 50 V DC or less.
To persons in charge of electrical wiring work:
Do not operate the unit until the refrigerant piping is complete. (Running it before the piping is ready will break the compressor.)

Precautions on electrical wiring work

Before obtaining access to terminal devices, all supply circuits must be interrupted.
Use only copper wires.
The wiring between the indoor unit and outdoor unit must be for
220~240 V.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local and national legislation. Do not turn on the main switch until all the wiring is completed.
For W1 Make sure to connect power supply cables in normal phase. If connected in reverse phase, the remote controller of the indoor unit indicates "U1" and the equipment cannot operate. Change any two of the three power supply cables (L1, L2, L3) to correct phase. If the contact in the magnetic switch should be forcibly turned on while the equipment is inoperative, the compressor will burn out. Never try to forcibly turn on the contact.
Never squeeze bundled cables into a unit.
Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).
Secure the electrical wiring with clamping material as shown in the figure below so that it does not come in contact with the piping, particularly on the high-pressure side. Make sure no external pressure is applied to the terminal connectors.
When installing the earth leakage breaker make sure that it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the earth leakage breaker.
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phase advancing capacitor.
Secure the wiring in the order shown below.
1 Secure the ground wire to the stop valve attachment plate so
that it does not slide.
2 Secure the ground wire to the stop valve attachment plate one
more time along with the electric wiring and the inter-unit wiring.
Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely.
V1
1 Switch box 2 Stop valve mounting plate 3 Ground 4 Tie-wrap 5 Wiring between units 6 Power supply and ground wiring
W1
1 Power supply wiring and earth wire 2 Wiring between unit
When cables are routed from the unit, a protection sleeve for the conduits (PG-insertions) can be inserted at the knock-out hole.
(See figure 7)
1 Wire 2 Bush 3 Nut 4 Frame
5 Hose A Inside B Outside
When you do not use a wire conduit, be sure to protect the wires with vinyl tubes to prevent the edge of the knock-out hole from cutting the wires.
Follow the electric wiring diagram for electrical wiring works.
Form the wires and fix the cover firmly so that the cover may be
fit in properly.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1
Installation manual
12

Precautions on wiring of power supply and inter-unit wiring

Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to unavoidable reasons, be sure to observe the following instruction.
1 Round pressure terminal 2 Cut out section 3 Cup washer
123
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause overheating.)
- When connecting wires of the same gauge, connect them
according to the below figure.
Specifications of standard wiring components
RZQ
Minimum circuit amps (MCA)
Recommended field fuse (A)
(b)
Wire type
Size
Wire type of wiring between the units
(a) Stated values are maximum values (see electrical data of combination with indoor
units for exact values).
(b) Only in protected pipes, use H07RN-F when protected pipes are not used.
NOTE
71V1 100V1 125V1 140V1 100W1 125W1 140W1
18.9 27.6 28.8 17.1 18.3
(a)
20 32 20
H05VV-U3G H05VV-U5G
Wiring size must comply with the applicable local and
national code
H05VV-U4G2.5
The earth leakage breaker must be a high-speed type breaker of 30 mA (<0.1 s).
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent appropriate tightening.
Over-tightening the terminal screws can damage the screws.
See the table below for tightening torques for the terminal
screws.
Tightening torque (N•m)
M4 (X1M) 1.2~1.8 M4 (EARTH) 1.2~1.4 M5 (X1M) 2.0~3.0 M5 (EARTH) 2.4~2.9
Refer to the installation manual attached to the indoor unit for wiring of indoor units, etc.
Attach an earth leakage breaker and fuse to the power supply line. (See figure 9)
I Pair
II Twin III Triple IV Double twin M Master
S Slave
1 Earth leakage breaker
2 Fuse
3 Remote controller
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside forces are not applied to the terminals.
Only for RZQ71~140D: Equipment complying with EN/IEC 61000-3-12

TEST OPERATION

WARNING
Live parts can be easily touched by accident. Never leave the unit unattended during installation or
servicing when the service panel is removed.
NOTE

Pre-run checks

Electrical wiring Inter-unit wiring Ground wire
Refrigerant piping Is the size of the piping appropriate?
Extra refrigerant Did you write down the extra refrigerant and the
Note that during the first running period of the unit, required power input may be higher. This phenomenon originates from the compressor that requires a 50-hour run-in period before reaching smooth operation and stable power consumption.
Items to check
Is the wiring as mentioned on the wiring diagram? Make sure no wiring has been forgotten and that there are no missing phases or reverse phases.
Is the unit properly grounded?
Is the wiring between units connected in series
correct?
Are any of the wiring attachment screws loose?
Is the insulation resistance at least 1 M?
- Use a 500 V mega-tester when measuring
insulation.
- Do not use a mega-tester for low-voltage
circuits.
Is the insulation material for the piping attached securely? Are both the liquid and gas pipes insulated?
Are the stop valves for both the liquid side and the gas side open?
refrigerant piping length?
(1)
.
Installation manual
13
(1) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1
Be sure to perform a test run.
Be sure to fully open the liquid-side and gas-side stop valves. If
you operate the unit with stop valves closed, the compressor will break down.
Be sure to execute the first test run of the installation in cooling mode operation.
Never leave the unit unattended with an open front panel during test run.
5 In case the panels of indoor units are not yet installed to the
indoor units, make sure to shut off the power supply after finishing the complete test run.
6 A complete test run surely includes shutting off power after
having performed a normal operation stop on the remote controller. Do not stop operation by turning circuit breakers off.
Failure diagnosis at the moment of first installation

Test run

1 Be sure to turn power on at least 6 hours before starting
operation in order to protect the compressor.
2 Make sure the liquid and gas stop valves are open.
B
A
3 Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.
4 Be sure to set the unit to cooling operation mode.
5 Press the inspection/test operation button of the remote
controller 4 times (2 times in case of a wireless remote controller) to go into the test run mode.
6 Press the ON/OFF button within 10 seconds to start the test run
and check the operation status for about 6 minutes. The refrigerant pressure may not rise immediately, even if the stop valve is opened after an air purge is performed using a vacuum pump. This is because the indoor unit refrigerant piping is closed off with electric valves inside. This will not create any problems during operation.
7 Push the air flow direction adjust button and check if the unit is
responding to the new air flow direction position.
8 Press the inspection/test operation button of the remote
controller 2 times to go into check mode and to make sure that the malfunction code displays " malfunction code does not display "00", refer to "Failure
diagnosis at the moment of first installation" on page 14.
9 If the inspection/test operation button is pressed 4 times during
a test run, the unit returns to normal operation.
10 Check all functions according to the operation manual.
Opening direction
A Liquid side B Gas side
Remove the cap and turn counterclockwise with a hex wrench until it stops
00
" (=normal). In case the
In case nothing is displayed on the remote controller (the current set temperature does not display), check for any of the following abnormalities before you can diagnose possible malfunction codes.
Disconnection or wiring error (between power supply and
outdoor unit, between outdoor unit and indoor units, between indoor unit and remote controller).
The fuse on the outdoor unit PCB may have run out.
If the remote controller shows "E3", "E4" or "L8" as an error code,
there is a possibility that either the stop valves are closed, or that air inlet or air outlet are blocked.
U2
If the error code "
" is displayed on the remote controller, check
for voltage imbalance.
If the error code "U4" or "UF" is displayed on the remote controller, check the inter-unit branch wiring connection.
If the error code
"L4"
is displayed on the remote controller, it is
possible that air inlet or air outlet are blocked.
The reversed phase protection detector of this product only works during the initialisation stage after a power reset. The reversed phase protection detector is designed to stop the product in case of an abnormality when the product is started up.
When the reversed phase protection circuit forced the unit to
stop, check if all phases are existing. If this is the case, shut off the power supply to the unit and replace two of three phases. Turn on power again and start the unit.
Reversed phase detection is not performed while the product
is operating.
In case of possible reversal of phases after a momentary
black out of power and the power goes on and off while the product is operating, install a reversed phase protection circuit on site. Such situation is not unimaginable when using generators. Running the product in reversed phase can break the compressor and other parts.
For a missing phase in case of W1 units, "E7" or "U2" will be displayed on the remote controller of the indoor unit. Operation will be impossible with either one of these phenomena. If this happens, turn off the power, re-check the wiring and switch the position of two of the three electrical wires. (If operation is not possible, do not under any circumstances force the electromagnetic contactor on.)

Precautions regarding test-runs

1 In order to detect stop valves failing to open, operation of the
unit is compulsorily performed in cooling for 2-3 minutes during the first test run, even if the remote controller was set to heating operation. In this case, the remote controller will have kept displaying the heating symbol all the time and the unit will switch to heating operation automatically after elapse of that time.
2 In case you cannot operate the unit in test run mode for any
unusual reason, refer to "Failure diagnosis at the moment of first
installation" on page 14.
3 In case you cannot operate the unit in test run mode, the unit
usually returns to its normal state after 30 minutes.
4 In case of a wireless remote controller, execute the test run only
after having installed the indoor unit decoration panel with infra­red receiver first.
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B Split System air conditioners 4PW60930-1

DISPOSAL REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.
Installation manual
14

WIRING DIAGRAM

: Wire clamp BLK : Black : Te r minal GRN : Green : Connector BRN : Brown : Relay connector BLU : Blue : Field wiring ORG : Orange
RED : Red WHT : White YLW : Yellow
: Refer to the service manual for connecting wiring to X6A. : The position of the selector switches (DS1) indicate the
factory setting. For details, refer to the service manual.
A1P~A4P................Printed circuit board
BS1~BS4................Push button switch
C1~C4....................Capacitor
DS1 ........................DIP switch
E1HC......................Crankcase heater
F1U~F6U................Fuse
HAP (A1P)..............Service monitor (green)
HAP (A2P)..............Service monitor (green)
H1P (A1P) ..............Service monitor (red)
H1P~H7P (A2P).....Service monitor (orange)
K1M........................Magnetic contactor (for W1 models only)
K1R ........................Magnetic relay (Y1S)
K2R ........................Magnetic relay (for W1 models only)
K3R ........................Magnetic relay (E1HC) (for W1 models only)
K4R ........................Magnetic relay (E1HC) (for V1 models only)
K4R•K5R................Magnetic relay (for W1 models only)
K10R•K11R............Magnetic relay
L1R.........................Reactor
M1C........................Motor (compressor)
M1F•M2F................Motor (fan)
PS ..........................Power circuit
Q1DI.......................Earth leakage breaker (field supply)
R1•R2.....................Resistor
R1T ........................Thermistor (air)
R2T ........................Thermistor (coil) (for W1 models only)
R2T ........................Thermistor (discharge) (for V1 models only)
R3T........................ Thermistor (discharge pipe) (for W1 models only)
R3T........................ Thermistor (suction pipe) (for V1 models only)
R4T........................ Thermistor (suction pipe) (for W1 models only)
R4T........................ Thermistor (coil) (for V1 models only)
R5T........................ Thermistor (power module) (for W1 models only)
R5T........................ Thermistor (coil middle) (for V1 models only)
R6T........................ Thermistor (liquid)
R10T...................... Thermistor (fin)
RC ......................... Signal receiver circuit
S1NPL ................... Pressure sensor (low)
S1NPH................... Pressure sensor (high)
S1PH ..................... Pressure switch (high)
S1PL...................... Pressure switch (low)
TC.......................... Signal transmission circuit
V1R........................ Power module
V2R•V3R ............... Diode module
V1T........................ Insulated gate bipolar transistor
X1M ....................... Terminal strip
X6A........................ Connector (option)
Y1E........................ Expansion valve
Y1S........................ 4 way valve
Y2S........................ Solenoid valve
Z1C~Z5C............... Noise filter
Z1F~Z4F................ Noise filter
Installation manual
15
RZQ71D3V1B + RZQ100~140D9V1B + RZQ100~140B9W1B
Split System air conditioners
4PW60930-1
NOTES NOTES
4PW60930-1