Daikin RXYTQ8U7YF, RXYTQ10U7YF, RXYTQ12U7YF, RXYTQ14U7YF, RXYTQ16U7YF Operation manuals

Installation and operation manual
VRV IV+ heat pump for high ambient temperatures
RXYTQ8U7YF RXYTQ10U7YF RXYTQ12U7YF RXYTQ14U7YF RXYTQ16U7YF
Installation and operation manual
VRV IV+ heat pump for high ambient temperatures
English

Table of contents

Table of contents
1 About the documentation 3
1.1 About this document.................................................................. 3
2 Specific installer safety instructions 3
For the user 4
3 User safety instructions 4
3.1 General...................................................................................... 5
3.2 Instructions for safe operation ................................................... 5
4 About the system 6
4.1 System layout............................................................................ 7
5 User interface 7
6 Operation 7
6.1 Operation range ........................................................................ 7
6.2 Operating the system ................................................................ 7
6.2.1 About operating the system ........................................ 7
6.2.2 About cooling, heating, fan only, and automatic
operation ..................................................................... 7
6.2.3 About the heating operation........................................ 7
6.2.4 To operate the system (WITHOUT cool/heat
changeover remote control switch) ............................. 7
6.2.5 To operate the system (WITH cool/heat changeover
remote control switch)................................................. 7
6.3 Using the dry program............................................................... 8
6.3.1 About the dry program ................................................ 8
6.3.2 To use the dry program (WITHOUT cool/heat
changeover remote control switch) ............................. 8
6.3.3 To use the dry program (WITH cool/heat changeover
remote control switch)................................................. 8
6.4 Adjusting the air flow direction................................................... 8
6.4.1 About the air flow flap ................................................. 8
6.5 Setting the master user interface .............................................. 9
6.5.1 About setting the master user interface ...................... 9
7 Maintenance and service 9
7.1 About the refrigerant.................................................................. 9
7.2 After-sales service and warranty ............................................... 9
7.2.1 Warranty period .......................................................... 9
7.2.2 Recommended maintenance and inspection.............. 9
8 Troubleshooting 10
8.1 Error codes: Overview............................................................... 10
8.2 Symptoms that are NOT system malfunctions .......................... 11
8.2.1 Symptom: The system does not operate .................... 11
8.2.2 Symptom: Cool/Heat cannot be changed over ........... 11
8.2.3 Symptom: Fan operation is possible, but cooling and
heating do not work..................................................... 11
8.2.4 Symptom: The fan speed does not correspond to the
setting ......................................................................... 11
8.2.5 Symptom: The fan direction does not correspond to
the setting ................................................................... 11
8.2.6 Symptom: White mist comes out of a unit (Indoor
unit) ............................................................................. 11
8.2.7 Symptom: White mist comes out of a unit (Indoor
unit, outdoor unit) ........................................................ 11
8.2.8 Symptom: The user interface reads "U4" or "U5" and
stops, but then restarts after a few minutes ................ 11
8.2.9 Symptom: Noise of air conditioners (Indoor unit)........ 12
8.2.10 Symptom: Noise of air conditioners (Indoor unit,
outdoor unit)................................................................ 12
8.2.11 Symptom: Noise of air conditioners (Outdoor unit) ..... 12
8.2.12 Symptom: Dust comes out of the unit ......................... 12
8.2.13 Symptom: The units can give off odours..................... 12
8.2.14 Symptom: The outdoor unit fan does not spin ............ 12
8.2.15 Symptom: The display shows "88"............................... 12
8.2.16 Symptom: The compressor in the outdoor unit does
not stop after a short heating operation ....................... 12
8.2.17 Symptom: The inside of an outdoor unit is warm
even when the unit has stopped .................................. 12
8.2.18 Symptom: Hot air can be felt when the indoor unit is
stopped ........................................................................ 12
9 Relocation 12
10 Disposal 12
For the installer 12
11 About the box 12
11.1
About ............................................................................ 12
11.2 To remove the accessories from the outdoor unit ...................... 12
11.3 Accessory pipes: Diameters ....................................................... 13
11.4 To remove the transportation stay.............................................. 13
12 About the units and options 13
12.1 About the outdoor unit ................................................................ 13
12.2 System layout ............................................................................. 13
13 Unit installation 13
13.1 Preparing the installation site ..................................................... 13
13.1.1 Installation site requirements of the outdoor unit ......... 13
13.1.2 Additional installation site requirements of the
outdoor unit in cold climates ........................................ 14
13.2 Opening the unit ......................................................................... 14
13.2.1 To open the outdoor unit .............................................. 14
13.2.2 To open the electrical component box of the outdoor
unit ............................................................................... 14
13.3 Mounting the outdoor unit........................................................... 14
13.3.1 To provide the installation structure ............................. 14
14 Piping installation 15
14.1 Preparing refrigerant piping ........................................................ 15
14.1.1 Refrigerant piping requirements................................... 15
14.1.2 To select the piping size .............................................. 15
14.1.3 To select refrigerant branch kits................................... 16
14.1.4 Multiple outdoor units: Possible layouts ....................... 17
14.2 Connecting the refrigerant piping ............................................... 17
14.2.1 To route the refrigerant piping...................................... 17
14.2.2 To connect the refrigerant piping to the outdoor unit ... 18
14.2.3 To connect the multi connection piping kit ................... 18
14.2.4 To connect the refrigerant branching kit ...................... 18
14.2.5 To protect against contamination ................................. 18
14.2.6 Using the stop valve and service port .......................... 18
14.2.7 To remove the spun pipes ........................................... 19
14.3 Checking the refrigerant piping .................................................. 20
14.3.1 About checking the refrigerant piping .......................... 20
14.3.2 Checking refrigerant piping: General guidelines .......... 20
14.3.3 Checking refrigerant piping: Setup............................... 20
14.3.4 To perform a leak test .................................................. 21
14.3.5 To perform vacuum drying ........................................... 21
14.3.6 To insulate the refrigerant piping ................................. 21
14.4 Charging refrigerant ................................................................... 21
14.4.1 Precautions when charging refrigerant ........................ 21
14.4.2 About charging refrigerant ........................................... 22
14.4.3 To determine the additional refrigerant amount ........... 22
14.4.4 To charge refrigerant: Flow chart ................................. 23
14.4.5 To charge refrigerant ................................................... 24
14.4.6 Step 6: To manually charge refrigerant........................ 25
14.4.7 Error codes when charging refrigerant......................... 25
14.4.8 Checks after charging refrigerant................................. 25
15 Electrical installation 26
15.1 Safety device requirements ........................................................ 26
15.2 Field wiring: Overview ................................................................ 26
2
VRV IV+ heat pump for high ambient temperatures
RXYTQ8~16U7YF
4P546223-1B – 2020.10

1 About the documentation

15.3 To route and fix the transmission wiring .................................... 26
15.4 To connect the transmission wiring ........................................... 27
15.5 To finish the transmission wiring ............................................... 27
15.6 To route and fix the power supply ............................................. 27
15.7 To connect the power supply .................................................... 28
15.8 To check the insulation resistance of the compressor .............. 28
16 Configuration 28
16.1 Making field settings .................................................................. 28
16.1.1 About making field settings ......................................... 28
16.1.2 Field setting components ............................................ 29
16.1.3 To access the field setting components ...................... 29
16.1.4 To access mode 1 or 2 ............................................... 29
16.1.5 To use mode 1 ............................................................ 30
16.1.6 To use mode 2 ............................................................ 30
16.1.7 Mode 1: Monitoring settings ........................................ 30
16.1.8 Mode 2: Field settings ................................................. 30
16.1.9 To connect the PC configurator to the outdoor unit .... 31
17 Commissioning 31
17.1 Precautions when commissioning ............................................. 31
17.2 Checklist before commissioning ................................................ 31
17.3 About the test run ...................................................................... 32
17.4 To perform a test run ................................................................. 32
17.5 Correcting after abnormal completion of the test run ................ 33
18 Hand-over to the user 33
19 Troubleshooting 33
19.1 Solving problems based on error codes .................................... 33
19.2 Error codes: Overview ............................................................... 33
20 Technical data 36
20.1 Service space: Outdoor unit ...................................................... 36
20.2 Piping diagram: Outdoor unit..................................................... 38
20.3 Wiring diagram: Outdoor unit .................................................... 38
21 Disposal 40
Installer and user reference guide:
▪ Preparation of the installation, reference data,…
▪ Detailed step-by-step instructions and background information
for basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
Business Portal (authentication required).
2 Specific installer safety
instructions
Always observe the following safety instructions and regulations.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
1 About the documentation

1.1 About this document

Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the outdoor unit)
Outdoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the outdoor unit)
CAUTION
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
DANGER: RISK OF BURNING/SCALDING
DANGER: RISK OF ELECTROCUTION
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas might be produced if refrigerant gas comes
into contact with fire.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
3

3 User safety instructions

WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
CAUTION
Do not vent gases into the atmosphere.
WARNING
Any gas or oil remaining inside the stop valve may blow off the spun piping.
If these instructions are NOT followed correctly it may result in property damage or personal injury, which may be serious depending on the circumstances.
WARNING
NEVER remove the spun piping by brazing.
Any gas or oil remaining inside the stop valve may blow off the spun piping.
WARNING
▪ ONLY use R410A as refrigerant. Other substances
may cause explosions and accidents.
▪ R410A contains fluorinated greenhouse gases. Its
global warming potential (GWP) value is 2087.5. Do NOT vent these gases into the atmosphere.
▪ When charging refrigerant, ALWAYS use protective
gloves and safety glasses.
CAUTION
Do NOT push or place redundant cable length in the unit.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
▪ When connecting the power supply: connect the earth
cable first, before making the current-carrying connections.
▪ When disconnecting the power supply: disconnect the
current-carrying cables first, before separating the earth connection.
▪ The length of the conductors between the power supply
stress relief and the terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
CAUTION
Do NOT perform the test operation while working on the indoor units.
When performing the test operation, NOT only the outdoor unit, but the connected indoor unit will operate as well. Working on an indoor unit while performing a test operation is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.

For the user

3 User safety instructions
Always observe the following safety instructions and regulations.
4
VRV IV+ heat pump for high ambient temperatures
RXYTQ8~16U7YF
4P546223-1B – 2020.10
3 User safety instructions

3.1 General

WARNING
If you are NOT sure how to operate the unit, contact your installer.
WARNING
Children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge can only use this appliance if they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.
Children MUST NOT play with the appliance.
Cleaning and user maintenance MUST NOT be carried out by children without supervision.
WARNING
To prevent electrical shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet
hands.
▪ Do NOT place any objects containing
water on the unit.
CAUTION
▪ Batteries are marked with the following symbol:
This means that the batteries may NOT be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.

3.2 Instructions for safe operation

CAUTION
▪ NEVER touch the internal parts of the
controller.
▪ Do NOT remove the front panel.
Some parts inside are dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
CAUTION
Do NOT operate the system when using a room fumigation-type insecticide. Chemicals could collect in the unit, and endanger the health of people who are hypersensitive to chemicals.
▪ Do NOT place any objects or
equipment on top of the unit.
▪ Do NOT sit, climb or stand on the
unit.
▪ Units are marked with the following symbol:
This means that electrical and electronic products may NOT be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
CAUTION
It is unhealthy to expose your body to the air flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently if equipment with burner is used together with the system.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been carried out correctly by an installer.
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
5

4 About the system

WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in operation. Fingers may become caught or the unit may break down.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
CAUTION: Pay attention to the fan!
It is dangerous to inspect the unit while the fan is running.
Be sure to turn off the main switch before executing any maintenance task.
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
WARNING
The refrigerant in the system is safe and normally does not leak. If the refrigerant leaks in the room, contact with a fire of a burner, a heater or a cooker may result in a harmful gas.
Turn off any combustible heating devices, ventilate the room and contact the dealer where you purchased the unit.
Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired.
CAUTION
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
WARNING
▪ Do NOT modify, disassemble,
remove, reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
▪ In case of accidental refrigerant
leaks, make sure there are no naked flames. The refrigerant itself is entirely safe, non-toxic and non­combustible, but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
NEVER expose little children, plants or animals directly to the airflow.
CAUTION
Do NOT touch the heat exchanger fins. These fins are sharp and could result in cutting injuries.
4 About the system
The indoor unit part of VRV IV heat pump system can be used for heating/cooling applications. The type of indoor unit which can be used depends on the outdoor units series.
NOTICE
Do NOT use the system for other purposes. In order to avoid any quality deterioration, do NOT use the unit for cooling precision instruments, food, plants, animals, or works of art.
NOTICE
For future modifications or expansions of your system:
A full overview of allowable combinations (for future system extensions) is available in technical engineering data and should be consulted. Contact your installer to receive more information and professional advice.
6
VRV IV+ heat pump for high ambient temperatures
RXYTQ8~16U7YF
4P546223-1B – 2020.10

5 User interface

a
b

4.1 System layout

5 User interface
CAUTION
▪ NEVER touch the internal parts of the controller.
▪ Do NOT remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen. For checking and adjusting the internal parts, contact your dealer.
This operation manual offers a non-exhaustive overview of the main functions of the system.

6 Operation

6.1 Operation range

Use the system in the following temperature and humidity ranges for safe and effective operation.
Cooling Heating
Outdoor temperature –5~52°CDB –20~21°CDB
–20~15.5°C WB
Indoor temperature 21~32°CDB
14~25°C WB
Indoor humidity ≤80%
(a)
To avoid condensation and water dripping out of the unit. If the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.
Above operation range is only valid in case direct expansion indoor units are connected to the VRV IV system.
Special operation ranges are valid in case of using AHU. They can be found in the installation/operation manual of the dedicated unit. Latest information can be found in the technical engineering data.

6.2 Operating the system

6.2.1 About operating the system

▪ Operation procedure varies according to the combination of
outdoor unit and user interface.
▪ To protect the unit, turn on the main power switch 6 hours before
operation.
▪ If the main power supply is turned off during operation, operation
will restart automatically after the power turns back on again.

6.2.2 About cooling, heating, fan only, and automatic operation

▪ Changeover cannot be made with a user interface whose display
shows "change-over under centralised control" (refer to installation and operation manual of the user interface).
▪ When the display "change-over under centralised control"
flashes, refer to "About setting the master user interface"[49].
▪ The fan may keep on running for about 1 minute after the heating
operation stops.
▪ The air flow rate may adjust itself depending on the room
temperature or the fan may stop immediately. This is not a malfunction.
15~27°CDB
(a)

6.2.3 About the heating operation

It may take longer to reach the set temperature for general heating operation than for cooling operation.
The following operation is performed in order to prevent the heating capacity from dropping or cold air from blowing.
Defrost operation
In heating operation, freezing of the outdoor unit's air cooled coil increases over time, restricting the energy transfer to the outdoor unit's coil. Heating capability decreases and the system needs to go into defrost operation to be able to remove frost from the outdoor unit’s coil. During defrost operation the heating capacity on the indoor unit side will temporarily drop until defrosting is completed. After defrosting, the unit will regain its full heating capacity.
The indoor unit will indicate defrost operation on the display .
Hot start
In order to prevent cold air from blowing out of an indoor unit at the start of heating operation, the indoor fan is automatically stopped.
The display of the user interface shows . It may take some time before the fan starts. This is not a malfunction.

6.2.4 To operate the system (WITHOUT cool/ heat changeover remote control switch)

1 Press the operation mode selector button on the user interface
several times and select the operation mode of your choice.
Cooling operation
Heating operation
Fan only operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system starts
operating.

6.2.5 To operate the system (WITH cool/heat changeover remote control switch)

Overview of the changeover remote control switch
a FAN ONLY/AIR CONDITIONING
SELECTOR SWITCH
Set the switch to for fan only
operation or to for heating or cooling operation.
b COOL/HEAT CHANGEOVER SWITCH
Set the switch to for cooling or to for heating
Note: In case a cool/heat changeover remote control switch is used, the position of DIP switch 1 (DS1-1) on the main PCB needs to be switched to the ON position.
To start
1 Select operation mode with the cool/heat changeover switch as
follows:
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
7
6 Operation
1
1
1
1
1
1
1
Cooling operation
2 Press the ON/OFF button on the user interface.
Result: The operation lamp lights up and the system starts
operating.
To stop
3 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops
operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.
To adjust
For programming temperature, fan speed and air flow direction refer to the operation manual of the user interface.
Heating operation
Fan only operation

6.3 Using the dry program

6.3.3 To use the dry program (WITH cool/heat changeover remote control switch)

To start
1 Select cooling operation mode with the cool/heat changeover
remote control switch.
2 Press the operation mode selector button on the user interface
several times and select (program dry operation).
3 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts
operating.
4 Press the air flow direction adjust button (only for double-flow,
multi-flow, corner, ceiling-suspended and wall-mounted). Refer to "6.4Adjusting the air flow direction"[48] for details.
To stop
5 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops
operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

6.3.1 About the dry program

▪ The function of this program is to decrease the humidity in your
room with minimal temperature decrease (minimal room cooling).
▪ The micro computer automatically determines temperature and
fan speed (cannot be set by the user interface).
▪ The system does not go into operation if the room temperature is
low (<20°C).

6.3.2 To use the dry program (WITHOUT cool/ heat changeover remote control switch)

To start
1 Press the operation mode selector button on the user interface
several times and select (program dry operation).
2 Press the ON/OFF button of the user interface.
Result: The operation lamp lights up and the system starts
operating.
3 Press the air flow direction adjust button (only for double-flow,
multi-flow, corner, ceiling-suspended and wall-mounted). Refer to "6.4Adjusting the air flow direction"[48] for details.
To stop
4 Press the ON/OFF button on the user interface once again.
Result: The operation lamp goes out and the system stops
operating.
NOTICE
Do not turn off power immediately after the unit stops, but wait for at least 5 minutes.

6.4 Adjusting the air flow direction

Refer to the operation manual of the user interface.

6.4.1 About the air flow flap

Double flow+multi-flow units
Corner units
Ceiling suspended units
Wall-mounted units
For the following conditions, a micro computer controls the air flow direction which may be different from the display.
Cooling Heating
▪ When the room temperature is
lower than the set temperature.
▪ When operating continuously at horizontal air flow direction.
▪ When continuous operation with downward air flow is performed
at the time of cooling with a ceiling-suspended or a wall-mounted unit, the micro computer may control the flow direction, and then the user interface indication will also change.
▪ When starting operation.
▪ When the room temperature is
higher than the set temperature.
▪ At defrost operation.
8
VRV IV+ heat pump for high ambient temperatures
RXYTQ8~16U7YF
4P546223-1B – 2020.10

7 Maintenance and service

The air flow direction can be adjusted in one of the following ways:
▪ The air flow flap itself adjusts its position.
▪ The air flow direction can be fixed by the user.
▪ Automatic and desired position .
WARNING
Never touch the air outlet or the horizontal blades while the swing flap is in operation. Fingers may become caught or the unit may break down.
NOTICE
▪ The movable limit of the flap is changeable. Contact
your dealer for details. (only for double-flow, multi-flow, corner, ceiling-suspended and wall-mounted).
▪ Avoid operating in the horizontal direction . It may
cause dew or dust to settle on the ceiling or flap.

6.5 Setting the master user interface

6.5.1 About setting the master user interface

The displays of slave user interfaces show (change-over under centralised control) and slave user interfaces automatically follow the operation mode directed by the master user interface.
Only the master user interface can select heating or cooling mode.
7 Maintenance and service
NOTICE
NEVER inspect or service the unit by yourself. Ask a qualified service person to perform this work.
WARNING
NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out. Use of wire or copper wire may cause the unit to break down or cause a fire.
CAUTION
Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.
CAUTION
After a long use, check the unit stand and fitting for damage. If damaged, the unit may fall and result in injury.
NOTICE
Do NOT wipe the controller operation panel with benzine, thinner, chemical dust cloth, etc. The panel may get discoloured or the coating peeled off. If it is heavily dirty, soak a cloth in water-diluted neutral detergent, squeeze it well and wipe the panel clean. Wipe it with another dry cloth.

7.1 About the refrigerant

This product contains fluorinated greenhouse gases. Do NOT vent gases into the atmosphere.
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5
NOTICE
Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent.
Formula to calculate the quantity in CO2 equivalent tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Please contact your installer for more information.
WARNING
The refrigerant in the system is safe and normally does not leak. If the refrigerant leaks in the room, contact with a fire of a burner, a heater or a cooker may result in a harmful gas.
Turn off any combustible heating devices, ventilate the room and contact the dealer where you purchased the unit.
Do not use the system until a service person confirms that the portion where the refrigerant leaks is repaired.

7.2 After-sales service and warranty

7.2.1 Warranty period

▪ This product includes a warranty card that was filled in by the
dealer at the time of installation. The completed card has to be checked by the customer and stored carefully.
▪ If repairs to the product are necessary within the warranty period,
contact your dealer and keep the warranty card at hand.

7.2.2 Recommended maintenance and inspection

Since dust collects when using the unit for several years, performance of the unit will deteriorate to some extent. As taking apart and cleaning interiors of units requires technical expertise and in order to ensure the best possible maintenance of your units, we recommend to enter into a maintenance and inspection contract on top of normal maintenance activities. Our network of dealers has access to a permanent stock of essential components in order to keep your unit in operation as long as possible. Contact your dealer for more information.
When asking your dealer for an intervention, always state:
▪ The complete model name of the unit.
▪ The manufacturing number (stated on the nameplate of the unit).
▪ The installation date.
▪ The symptoms or malfunction, and details of the defect.
WARNING
▪ Do NOT modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire. Contact your dealer.
▪ In case of accidental refrigerant leaks, make sure there
are no naked flames. The refrigerant itself is entirely safe, non-toxic and non-combustible, but it will generate toxic gas when it accidentally leaks into a room where combustible air from fan heaters, gas cookers, etc. is present. Always have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation.
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
9

8 Troubleshooting

8 Troubleshooting
If one of the following malfunctions occur, take the measures shown below and contact your dealer.
WARNING
Stop operation and shut off the power if anything unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may cause breakage, electric shock or fire. Contact your dealer.
The system MUST be repaired by a qualified service person.
Malfunction Measure
If a safety device such as a fuse, a breaker or an earth leakage breaker frequently actuates or the ON/OFF switch does NOT properly work.
If water leaks from the unit. Stop the operation.
The operation switch does NOT work well.
If the user interface display indicates the unit number, the operation lamp flashes and the malfunction code appears.
If the system does NOT operate properly except for the above mentioned cases and none of the above mentioned malfunctions is evident, investigate the system in accordance with the following procedures.
Malfunction Measure
If the system does not operate at all.
If the system goes into fan only operation, but as soon as it goes into heating or cooling operation, the system stops.
The system operates but cooling or heating is insufficient.
▪ Check if there is no power failure. Wait
until power is restored. If power failure occurs during operation, the system automatically restarts immediately after power is restored.
▪ Check if no fuse has blown or breaker is
activated. Change the fuse or reset the breaker if necessary.
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles. Remove any obstacles and make sure the air can flow freely.
▪ Check if the user interface display shows
(time to clean the air filter). (Refer to
"7 Maintenance and service" [4 9] and
"Maintenance" in the indoor unit manual.)
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles. Remove any obstacles and make sure the air can flow freely.
▪ Check if the air filter is not clogged (refer
to "Maintenance" in the indoor unit manual).
▪ Check the temperature setting.
▪ Check the fan speed setting on your user
interface.
▪ Check for open doors or windows. Close
doors and windows to prevent wind from coming in.
▪ Check if there are too many occupants in
the room during cooling operation. Check if the heat source of the room is excessive.
▪ Check if direct sunlight enters the room.
Use curtains or blinds.
▪ Check if the air flow angle is proper.
Turn OFF the main power switch.
Turn OFF the power supply.
Notify your installer and report the malfunction code.
If after checking all above items, it is impossible to fix the problem yourself, contact your installer and state the symptoms, the complete model name of the unit (with manufacturing number if possible) and the installation date (possibly listed on the warranty card).

8.1 Error codes: Overview

In case a malfunction code appears on the indoor unit user interface display, contact your installer and inform the malfunction code, the unit type, and serial number (you can find this information on the nameplate of the unit).
For your reference, a list with malfunction codes is provided. You can, depending on the level of the malfunction code, reset the code by pushing the ON/OFF button. If not, ask your installer for advice.
Main code Contents
External protection device was activated
EEPROM failure (indoor)
Drain system malfunction (indoor)
Fan motor malfunction (indoor)
Swing flap motor malfunction (indoor)
Expansion valve malfunction (indoor)
Drain malfunction (indoor unit)
Filter dust chamber malfunction (indoor)
Capacity setting malfunction (indoor)
Transmission malfunction between main PCB and sub PCB (indoor)
Heat exchanger thermistor malfunction (indoor; liquid)
Heat exchanger thermistor malfunction (indoor; gas)
Suction air thermistor malfunction (indoor)
Discharge air thermistor malfunction (indoor)
Movement detector or floor temperature sensor malfunction (indoor)
User interface thermistor malfunction (indoor)
PCB malfunction (outdoor)
Current leakage detector was activated (outdoor)
High pressure switch was activated
Low pressure malfunction (outdoor)
Compressor lock detection (outdoor)
Fan motor malfunction (outdoor)
Electronic expansion valve malfunction (outdoor)
Discharge temperature malfunction (outdoor)
Abnormal suction temperature (outdoor)
Refrigerant overcharge detection
High pressure switch malfunction
Low pressure switch malfunction
Fan motor trouble (outdoor)
Ambient temperature sensor malfunction (outdoor)
Pressure sensor malfunction
Current sensor malfunction
Discharge temperature sensor malfunction (outdoor)
Heat exchanger gas temperature sensor malfunction (outdoor)
Suction temperature sensor malfunction (outdoor)
De-icing temperature sensor malfunction (outdoor)
Liquid temperature sensor (after subcool HE) malfunction (outdoor)
Liquid temperature sensor (coil) malfunction (outdoor)
Gas temperature sensor (after subcool HE) malfunction (outdoor)
10
VRV IV+ heat pump for high ambient temperatures
RXYTQ8~16U7YF
4P546223-1B – 2020.10
8 Troubleshooting
Main code Contents
High pressure sensor malfunction (S1NPH)
Low pressure sensor malfunction (S1NPL)
INV PCB abnormal
Fin temperature abnormal
Inverter PCB faulty
Compressor over current detected
Compressor lock (startup)
Transmission outdoor unit - inverter: INV transmission trouble
INV unbalanced power supply voltage
Autocharge operation related
Fin thermistor malfunction
Autocharge operation related
Autocharge operation related
Autocharge operation related
Capacity setting malfunction (outdoor)
Abnormal low pressure drop, faulty expansion valve
Reversed power supply phase malfunction
INV voltage power shortage
System test run not yet executed
Faulty wiring indoor/outdoor
Abnormal user interface - indoor communication
Faulty wiring to outdoor/outdoor
Abnormal main-sub user interface communication
System mismatch. Wrong type of indoor units combined. Indoor unit malfunction.
Connection malfunction over indoor units or type mismatch
Centralised address duplication
Malfunction in communication centralised control device - indoor unit
Auto address malfunction (inconsistency)
Auto address malfunction (inconsistency)

8.2 Symptoms that are NOT system malfunctions

The following symptoms are NOT system malfunctions:

8.2.1 Symptom: The system does not operate

▪ The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamp lights, the system is in normal condition. To prevent overloading of the compressor motor, the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before. The same starting delay occurs after the operation mode selector button was used.
▪ If "Under Centralized Control" is displayed on the user interface,
pressing the operation button causes the display to blink for a few seconds. The blinking display indicates that the user interface cannot be used.
▪ The system does not start immediately after the power supply is
turned on. Wait one minute until the micro computer is prepared for operation.

8.2.2 Symptom: Cool/Heat cannot be changed over

▪ When the display shows (change-over under centralized
control), it shows that this is a slave user interface.
▪ When the cool/heat changeover remote control switch is installed
and the display shows (change-over under centralized control), this is because cool/heat changeover is controlled by the cool/ heat changeover remote control switch. Ask your dealer where the remote control switch is installed.

8.2.3 Symptom: Fan operation is possible, but cooling and heating do not work

Immediately after the power is turned on. The micro computer is getting ready to operate and is performing a communication check with all indoor units. Please wait 12 minutes maximally until this process is finished.

8.2.4 Symptom: The fan speed does not correspond to the setting

The fan speed does not change even if the fan speed adjustment button is pressed. During heating operation, when the room temperature reaches the set temperature, the outdoor unit goes off and the indoor unit changes to whisper fan speed. This is to prevent cold air blowing directly on occupants of the room. The fan speed will not change even when another indoor unit is in heating operation, if the button is pressed.

8.2.5 Symptom: The fan direction does not correspond to the setting

The fan direction does not correspond with the user interface display. The fan direction does not swing. This is because the unit is being controlled by the micro computer.

8.2.6 Symptom: White mist comes out of a unit (Indoor unit)

▪ When humidity is high during cooling operation. If the interior of an
indoor unit is extremely contaminated, the temperature distribution inside a room becomes uneven. It is necessary to clean the interior of the indoor unit. Ask your dealer for details on cleaning the unit. This operation requires a qualified service person.
▪ Immediately after the cooling operation stops and if the room
temperature and humidity are low. This is because warm refrigerant gas flows back into the indoor unit and generates steam.

8.2.7 Symptom: White mist comes out of a unit (Indoor unit, outdoor unit)

When the system is changed over to heating operation after defrost operation. Moisture generated by defrost becomes steam and is exhausted.

8.2.8 Symptom: The user interface reads "U4" or "U5" and stops, but then restarts after a few minutes

This is because the user interface is intercepting noise from electric appliances other than the air conditioner. The noise prevents communication between the units, causing them to stop. Operation automatically restarts when the noise ceases.
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
11

9 Relocation

a
e
3P328191-1
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
REQUEST FOR THE INDICATION OF INSTALLATION INFORMATION
1. RECORD OF INDOOR UNIT MODEL AND INSTALLATION SITE
2. RECORD FOR SETTINGS (CONTENTS SEE INSTALLATION MANUAL)
SETTING
40
30
10
2019
9
29
3938
28
8
1817
7
27
3736
26
6
1615
5
25
3534
23 24
4321
INSTALLATION
MODELNAME
No.
12 13 14
504948474645
6059585756
64636261
11
2221
333231
44434241
5554535251
SITE
INSTALLATION
MODELNAME
No.
SITE
INSTALLATION
MODELNAME
No.
SITE
INSTALLATION
MODELNAME
No.
SITE
INSTALLATION
MODELNAME
No.
SITE
INSTALLATION
MODELNAME
No.
SITE
INSTALLATION
MODELNAME
No.
SITE
3. RECORD OF INSTALLATION DATE
6. AFTER EQUIPPING, PLEASE PUT IT ON THE BACK SIDE OF THE FRONT PLATE.
DAY MONTH YEAR
4. MODEL NAME 5. MANUFACTURING NUMBER
VALUE
REMARK DATE SETTING VALUE REMARK DATE
c
b
d
3P328192-1
3. FOR DETAILS CONCERNING PIPING SELECTION AND CALCULATION OR HOW TO OPERATE THE LEAK DETECTION FUNCTION, PLEASE REFER TO THE INSTALLATION MANUAL.
2. RECORD OF ADDITIONAL REFRIGERANT CHARGE AMOUNT AND RESULT OF LEAK CHECK OPERATION
REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
1. CALCULATION OF ADDITIONAL REFRIGERANT CHARGING AMOUNT
4. AFTER FILLING IN THIS TABLE, PLEASE PUT IT ON THE SWITCH BOX COVER.
(m) x 0.18(m) x 0.37
kg
OUTDOOR UNIT
(m) x 0.26
(m) x 0.12 (m) x 0.059
(m) x 0.022
ADDITIONAL CHARGING AMOUNT
TOTAL LENGTH OF LIQUID PIPE SIZE O22.2 x 0.37
TOTAL LENGTH OF LIQUID PIPE SIZE O19.1 x 0.26
TOTAL LENGTH OF LIQUID PIPE SIZE O15.9 x 0.18
TOTAL LENGTH OF LIQUID PIPE SIZE O12.7 x 0.12
TOTAL LENGTH OF LIQUID PIPE SIZE O9.5 x 0.059
TOTAL LENGTH OF LIQUID PIPE SIZE O6.4 x 0.022
105%< CR < 130%
50%< CR < 105%
50%< CR < 70% 70%< CR < 85% 85%< CR < 105% 105%< CR < 130%
8HP
Total indoor unit capacity connection ratio (CR)
10-12HP
14-16HP
18-20HP
2.0
1.5
1.5
1.2
1.5
1
1
0.7
1.0
0.5
0.5
0.3
0.5
0
0
0
1.0
0.5
0.5
0.5
0.5
0
0
0
Total indoor unit capacity when piping length <30m
Total indoor unit capacity when piping length >30m
kg
1.3
1.1
0.9
RYYQ18-20
RYYQ14-16
RYYQ8~12
kg
ONLY FOR RYYQ8~20 MODELS
DATE
AMOUNT
CALCULATE THE ADDITIONAL REFRIGERANT CHARGING AMOUNT BASED ON THE FORMULA BELOW BEFORE CHARGING.
SHIPMENT (INDICATED ON THE MACHINE NAMEPLATE) AND THE ADDITIONAL AMOUNT SHOWN AS FOLLOWS :
WHEN RE-CHARGING TOTAL AMOUNT OF REFRIGERANT , CHARGE THE TOTAL OF THE AMOUNT CHARGED AT
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK

8.2.9 Symptom: Noise of air conditioners (Indoor unit)

▪ A "zeen" sound is heard immediately after the power supply is
turned on. The electronic expansion valve inside an indoor unit starts working and makes the noise. Its volume will reduce in about one minute.
▪ A continuous low "shah" sound is heard when the system is in
cooling operation or at a stop. When the drain pump (optional accessories) is in operation, this noise is heard.
▪ A "pishi-pishi" squeaking sound is heard when the system stops
after heating operation. Expansion and contraction of plastic parts caused by temperature change make this noise.
▪ A low "sah", "choro-choro" sound is heard while the indoor unit is
stopped. When another indoor unit is in operation, this noise is heard. In order to prevent oil and refrigerant from remaining in the system, a small amount of refrigerant is kept flowing.

8.2.10 Symptom: Noise of air conditioners (Indoor unit, outdoor unit)

▪ A continuous low hissing sound is heard when the system is in
cooling or defrost operation. This is the sound of refrigerant gas flowing through both indoor and outdoor units.
▪ A hissing sound which is heard at the start or immediately after
stopping operation or defrost operation. This is the noise of refrigerant caused by flow stop or flow change.

8.2.11 Symptom: Noise of air conditioners (Outdoor unit)

When the tone of operating noise changes. This noise is caused by the change of frequency.

8.2.12 Symptom: Dust comes out of the unit

When the unit is used for the first time in a long time. This is because dust has gotten into the unit.

8.2.13 Symptom: The units can give off odours

The unit can absorb the smell of rooms, furniture, cigarettes, etc., and then emit it again.

8.2.15 Symptom: The display shows "88"

This is the case immediately after the main power supply switch is turned on and means that the user interface is in normal condition. This continues for 1minute.

8.2.16 Symptom: The compressor in the outdoor unit does not stop after a short heating operation

This is to prevent refrigerant from remaining in the compressor. The unit will stop after 5 to 10 minutes.

8.2.17 Symptom: The inside of an outdoor unit is warm even when the unit has stopped

This is because the crankcase heater is warming the compressor so that the compressor can start smoothly.

8.2.18 Symptom: Hot air can be felt when the indoor unit is stopped

Several different indoor units are being run on the same system. When another unit is running, some refrigerant will still flow through the unit.
9 Relocation
Contact your dealer for removing and reinstalling the total unit. Moving units requires technical expertise.

10 Disposal

This unit uses hydrofluorocarbon. Contact your dealer when discarding this unit.
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.

8.2.14 Symptom: The outdoor unit fan does not spin

During operation. The speed of the fan is controlled in order to optimise product operation.

For the installer

11 About the box

11.1 About

is part of Daikin's wider commitment to reduce our environmental footprint. With we want to create a circular economy for refrigerants. One of the actions to achieve this, is the reuse of reclaimed refrigerant in VRV units produced and sold in Europe. For more information about the countries that are in scope, visit: http://www.daikin.eu/loop-by-daikin.
12

11.2 To remove the accessories from the outdoor unit

Make sure that all accessories are available in the unit.
a General safety precautions b Installation manual and operation manual c Additional refrigerant charge label d Installation information sticker
RXYTQ8~16U7YF
VRV IV+ heat pump for high ambient temperatures
4P546223-1B – 2020.10

12 About the units and options

ID Øa
ID Øb
ID Øa
OD Øb
ID Øb
ID Øa
ID Øb
ID Øa
1
3 (12.3 N·m)
2
1
3 (12.3 N·m)
2
a
b
e
d
c c
b
f
a
e Piping accessory bag

11.3 Accessory pipes: Diameters

Accessory pipes (mm) HP Øa Øb
Gas pipe
▪ Front connection
▪ Bottom connection
Liquid pipe
▪ Front connection
▪ Bottom connection
8 25.4 19.1
10 22.2
12 28.6
14
16
8 9.5
10
12 9.5 12.7
14 12.7
16

11.4 To remove the transportation stay

Only for 14+16 HP
Model Description
RXYTQ8~16 Single non-continuous heating model.
RXYTQ18~48 Multi non-continuous heating model
(consisting of 2 or 3 RXYTQ modules).
These units are intended for outdoor installation and aimed for heat pump air to air applications.
These units have (in single use) heating capacities ranging from 25 to 50kW and cooling capacities rating from 22.4 to 45kW. In multi combination the heating capacity can go up till 150 kW and in cooling till 135kW.
The outdoor unit is designed to work in heating mode at ambient temperatures from –20°CWB to 15.5°CWB and in cooling mode at ambient temperatures from –5°CDB to 52°CDB.
Unit weights
Model Total net weight (kg) Total gross weight (kg)
RXYTQ8 198 211
RXYTQ10 234 251
RXYTQ12 234 251
RXYTQ14 283 300
RXYTQ16 283 300

12.2 System layout

NOTICE
Design of the system must not be done at temperatures below –15°C.
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or noise may be generated.
The transportation stay installed over the compressor leg for protecting the unit during transport must be removed. Proceed as shown in the figure and procedure below.
1 Slightly loosen the fixing nut (a).
2 Remove the transportation stay (b) as shown in the figure
below.
3 Tighten the fixing nut (a) again.
a VRV IV Heat pump outdoor unit b Refrigerant piping c VRV direct expansion (DX) indoor unit d User interface (dedicated depending on indoor unit type) e User interface (wireless, dedicated depending on indoor
unit type)
f Cool/Heat changeover remote control switch

13 Unit installation

13.1 Preparing the installation site

13.1.1 Installation site requirements of the outdoor unit

Mind the spacing guidelines. See the "Technical data" chapter.
CAUTION
12 About the units and options

12.1 About the outdoor unit

This installation manual concerns the VRV IV, full inverter driven, heat pump system.
Model line up:
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
RXYTQ8~16U7YF VRV IV+ heat pump for high ambient temperatures 4P546223-1B – 2020.10
13
13 Unit installation
T
AO
(°C WB)
a b
20
15.5 15
10
5
0
–5
–10
–15
–20
10 15 20 25
27
30
T
AI
(°C DB)
14×14×
8 HP 10~16 HP
8 HP
SW8
10~16 HP
SW8
a b
c
d
e
NOTICE
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

13.1.2 Additional installation site requirements of the outdoor unit in cold climates

NOTICE
When operating the unit in a low outdoor ambient temperature with high humidity conditions, make sure to take precautions to keep the drain holes of the unit free by using proper equipment.
In heating:
For service purposes, the pushbuttons on the main PCB need to be accessed. To access these pushbuttons, the electrical component box cover does not need to be opened. See "To access the field
setting components"[429].

13.2.2 To open the electrical component box of the outdoor unit

NOTICE
Do NOT apply excessive force when opening the electronic component box cover. Excessive force can deform the cover, resulting in entering of water to cause equipment failure.
a Warming up operation range
b Operation range
TAI Ambient indoor temperature
TAO Ambient outdoor temperature

13.2 Opening the unit

13.2.1 To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
Once the front plates open, the electrical component box can be accessed. See "To open the electrical component box of the outdoor
unit"[414].
14
NOTICE
When closing the electrical component box cover, make sure that the sealing material on the lower back side of the cover is NOT caught and bent towards the inside (see figure below).
a Electrical component box cover b Front side c Power supply terminal block d Sealing material e Moisture and dirt could enter
NOT allowed Allowed

13.3 Mounting the outdoor unit

13.3.1 To provide the installation structure

Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
NOTICE
▪ When the installation height of the unit needs to be
increased, do NOT use stands to only support the corners.
▪ Stands under the unit must be at least 100mm wide.
RXYTQ8~16U7YF
VRV IV+ heat pump for high ambient temperatures
4P546223-1B – 2020.10
Loading...
+ 30 hidden pages