Daikin RXYQ-PYLK Installation manuals

INSTALLATION MANUAL
RXYQ8P7Y1K RXYQ10P7Y1K RXYQ12P7Y1K
RXYQ8P7YLK RXYQ10P7YLK RXYQ12P7YLK
1 2
B
b
ac
AC
a e
AC
d
D
21 B
b
e
c a ce
AC
d
3 B
b
f
D
d
D
4 B
b
2
d
3
b
D
3
5
3
5
5 3
1
1
2
3
4
1
4
3 5
1
a 10 mm b 300 mm c 10 mm d 500 mm
a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm
a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm
a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm
A+B+C+D A+B
a 50 mm b 100 mm c 50 mm d 500 mm
a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm
a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm
a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm
3
5
5
1
a 200 mm b 300 mm
a 200 mm b 300 mm
e 400 mm
h
2
1500
a ce
AC
h
1
500
6
3 2
2 3
4
5
1000
1000
1500
1
1000
1500
1500
1500
(mm)
A
B
6767
67≥67
765
722-737
2
4
8
RXYQ8~12
A B
2
1
8 4
3
8 6
RXYQ16~32
A B
2
1
8 4
3
8 6
24
5
6
3 2
3
1
8 5
9
2
8 7 8
11 10
8
6
2
4 1 4
1
7
100
100
7
98
11
3
1
8 5
2
8 7 8
1
A
9
BA C
1
3
2
2
8
10
12456
3
7
10 11
90
150
25
1
AB
C
3
9
12
D
1
2 3
4 5
4 5
4
6 6
12
8
13
A
B
14
±
3
0
1
°
1
1 2
17
max
15°
A
1
B
345
1
13
15
1
B
2
2
3
B
1
4
5
6
3
6
15
18
1
1
19
A1P
A B C
1 267
ABC F1 F2 F1 F2 Q1 Q2
3
4
2
6 5
18
21
12345
3 4
19 20
22
5
1
2
21
24
5 3
4
1
2
6
3
4
22
25
RXYQ8 RXYQ10~12
14
16
111
AB
8
2 2
2
2
16
ABC F1 F1F2 F2 Q1 Q2
C/H SELECTOR
F1 F2 F1 F2 F1 F2
F1 F2 F1 F2 F1 F2
L1 L2 L3 N
TO IN/D UNIT
TO OUT/D UNIT TO MULTI UNIT
8
9
4
2
5 7
6 7
2
3
>120 mm
>500 mm
17
20
213
A1P
ABC F1F2F1F2Q1Q2 Q1Q2
6
7
23
TO IN/D
UNIT
5 6
F1 F2
445
ON
OFF
Q1 Q2
O U T
1234
I
N
DS1
7
10 11
F1 F2 P1 P2
P1 P2
1
23
26
A B C
ON
OFF
O U
T
1234
I
N
DS1
2
6
1 2 1 2
A B C
1
24 25 26
RXYQ8P7Y1K RXYQ8P7YLK RXYQ10P7Y1K RXYQ10P7YLK RXYQ12P7Y1K RXYQ12P7YLK
VRVIII System air conditioner
Installation manual
ONTENTS
C
P
1. Introduction................................................................................ 1
1.1. Combination.................................................................................1
1.2. Standard supplied accessories .................................................... 2
1.3. Optional accessories.................................................................... 2
1.4. Technical and Electrical specifications.........................................2
2. Main components...................................................................... 2
3. Selection of location .................................................................. 3
4. Inspecting and handling the unit................................................ 4
5. Unpacking and placing the unit ................................................. 4
6. Refrigerant piping...................................................................... 4
6.1. Installation tools ...........................................................................5
6.2. Selection of piping material..........................................................5
6.3. Pipe connection............................................................................5
6.4. Connecting the refrigerant piping.................................................5
6.5. Protection against contamination when installing pipes............... 7
6.6. Example of connection................................................................. 8
7. Leak test and vacuum drying .................................................. 10
8. Field wiring .............................................................................. 10
8.1. Internal wiring – Parts table........................................................ 11
8.2. Optional parts cool/heat selector................................................11
8.3. Power circuit and cable requirements ........................................12
8.4. General cautions........................................................................12
8.5. System examples....................................................................... 13
8.6. Leading power line and transmission line ..................................13
8.7. Field line connection: transmission wiring and
cool/heat selection .....................................................................13
8.8. Field line connection: power wiring ............................................ 15
8.9. Wiring example for wiring inside unit.......................................... 15
9. Pipe insulation......................................................................... 16
10. Checking of unit and installation conditions ............................ 16
11. Charging refrigerant ................................................................ 16
11.1. Precautions when adding R410A............................................... 16
11.2. Stop valve operation procedure ................................................. 17
11.3. How to check how many units are connected............................ 17
11.4. Additional refrigerant charge......................................................18
11.6. Checks after adding refrigerant.................................................. 23
12. Before operation...................................................................... 24
12.1. Service precautions.................................................................... 24
12.2. Checks before initial start-up...................................................... 24
12.3. Field setting................................................................................ 24
12.4. Test operation............................................................................. 26
13. Service mode operation .......................................................... 28
14. Caution for refrigerant leaks.................................................... 29
15. Disposal requirements............................................................. 29
READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY
DAIKIN
WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.
DAIKIN
EQUIPMENT IS DESIGNED FOR COMFORT APPLICATIONS. FOR USE IN OTHER APPLICATIONS, PLEASE CONTACT YOUR LOCAL
DAIKIN
DEALER.
IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DEALER FOR ADVICE AND INFORMATION.
THIS AIR CONDITIONER COMES UNDER THE TERM "APPLIANCES NOT ACCESSIBLE TO THE GENERAL PUBLIC".
age
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg you must divide your multiple outdoor system into smaller independent systems, each containing less than 95 kg refrigerant charge.
For factory charge, refer to the unit name plate.
The refrigerant R410A requires strict cautions for keeping the system clean, dry and tight.
Clean and dry Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting mixed into the system.
Tight R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth's protection against harmful ultraviolet radiation. R410A can contribute slightly to the greenhouse effect if it is released. Therefore we should take special attention to check the tightness of the installation.
Read "6. Refrigerant piping" on page 4 carefully and follow these procedures correctly.
Since design pressure is 4.0 MPa or 40 bar (for R407C units: 3.3 MPa or 33 bar), pipes of larger wall thickness may be required. The wall thickness of piping must be carefully selected, refer to paragraph "6.2. Selection of
piping material" on page 5 for more details.
1. I
NTRODUCTION
This installation manual concerns VRV inverters of the Daikin RXYQ-P7 series. These units are designed for outdoor installation and used for cooling and heat pump applications. The RXYQ-P7 series can be combined from 3 main units and has nominal cooling capacities ranging from 17.7 to 81.6 kW and nominal heating capacities ranging from 25.0 to 112.5 kW.
The RXYQ-P7 units can be combined with Daikin VRV indoor units for air conditioning purposes, and suitable for R410A.
The present installation manual describes the procedures for unpacking, installing and connecting the RXYQ-P7 units. Installation of the indoor units is not described in this manual. Always refer to the installation manual supplied with these units for their installation.

1.1. Combination

The indoor units can be installed in the following range.
Always use appropriate indoor units compatible with R410A. To learn which models of indoor units are compatible with R410A, refer to the product catalogs.
Pay attention when connecting outdoor units in multi combination. RXYQ-M units are NOT compatible with RXYQ-P units.
RXYQ_Y1K units are NOT compatible with RXYQ_YLK units.
Installation manual
1
RXYQ8~12P7Y1K + RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
Total capacity/quantity of indoor units
Tot al
capacity of
Standard combination of outdoor units
RXYQ8 RXYQ10 RXYQ12 RXYQ16 = RXYQ8 + RXYQ8 RXYQ18 = RXYQ8 + RXYQ10 RXYQ20 = RXYQ10 + RXYQ10 RXYQ22 = RXYQ10 + RXYQ12 RXYQ24 = RXYQ12 + RXYQ12 RXYQ26 = RXYQ8 + RXYQ8 + RXYQ10 RXYQ28 = RXYQ8 + RXYQ10 + RXYQ10 RXYQ30 = RXYQ8 + RXYQ10 + RXYQ12 RXYQ32 = RXYQ10 + RXYQ10 + RXYQ12 RXYQ34 = RXYQ10 + RXYQ12 + RXYQ12 RXYQ36 = RXYQ12 + RXYQ12 + RXYQ12 450~1170 58
NOTE
(a)
(a)
(a)
(a) Main unit
The table above shows the possible total capacity
indoor units
100~260 13 125~325 16 150~390 19 200~520 26 225~585 29 250~650 32 275~715 35 300~780 39 325~845 42 350~910 45
375~975 48 400~1040 52 425~1105 55
and number of possible indoor units when configured in a standard combination.
If the total capacity of the connected indoor units exceeds the capacity of the outdoor unit, cooling and heating performance may drop when running the indoor units. Refer to the section on performance charac­teristics in the Engineering Data Book for details.
There are restrictions on the refrigerant pipe connection order between outdoor units during installation in case of a multiple outdoor unit system. Install according to the following restrictions. The capacities of outdoor units A, B, and C must fulfill the following restriction conditions: A B C .
ABC
12 3
1 To indoor units 2 Outdoor unit multi connection piping kit (first
branch)
3 Outdoor unit multi connection piping kit
(second branch)
Tot al
quantity of
indoor units

1.2. Standard supplied accessories

See location 1 in figure 25 for reference to where following accessories are supplied with the unit.
Installation manual 1 Operation manual 1 Request for indication of additional
refrigerant charging and leak detection amount label
1
See location 2 in figure 25 for reference to where following accessories are supplied with the unit.
Unit type Item Quantity
8~12 Hp 1
8~12 Hp 1
Unit type Item Quantity
8~12 Hp 1
8~10 Hp 1 12 Hp 1
Gas side accessory pipe
Liquid side accessory pipe

1.3. Optional accessories

To install the above outdoor units, the following optional parts are also required.
Refrigerant branching kit (for R410A only: Always use an appropriate kit dedicated for your system.)
Refnet header Refnet joint
KHRQ22M29H KHRQ22M20T KHRQ22M64H KHRQ22M29T9 KHRQ22M75H KHRQ22M64T
KHRQ22M75T
Outdoor unit multi connection piping kit (For R410A only: Always use an appropriate kit dedicated for your system.)
Number of outdoor units connected
2 3
BHFQ22P1007 BHFQ22P1517
Pipe size reducer (For R410A only: Always use an appropriate kit dedicated for your system.)
RXYQ24~36
KHRQ22M75T KHRQ22M75H
To select an optimum refrigerant branching kit, refer to "6. Refrigerant
piping" on page 4.
RXYQ8~12P7Y1K + RXYQ8~12P7YLK VRVIII System air conditioner 4PW41760-1
1.4. Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of specifications.
AIN
2. M
For main components and function of the main components, refer to the Engineering Data Book.
COMPONENTS
Installation manual
2
1
2
3
4
5
6
7
8
9
10
3. S
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment. If installed as a house­hold appliance it could cause electromagnetic interference, in which case the user may be required to take adequate measures.
Obtain the customer's permission before installing. The inverter units should be installed in a location that meets the
following requirements:
ELECTION
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.
If not, the unit may fall over and cause damage or injury.
The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available. (Refer to
figure 1 and choose one of the possibilities).
A B C D Sides along the installation site with obstacles
In case of an installation site where sides A+B+C+D have obstacles, the wall heights of sides service space dimensions. Refer to figure 1 for impact of wall heights of sides B+D on service space dimensions.
In case of an installation site where only the sides A+B have obstacles, the wall heights have no influence on any indicated service space dimensions.
NOTE
Make sure that there is no danger of fire due to leakage of inflammable gas.
Ensure that water can not cause any damage to the location in case it drips out the unit (e.g. in case of a blocked drain pipe).
The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length. (Refer to
"6.6. Example of connection" on page 8)
Select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturbs anyone.
Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction. Frontal wind will disturb the operation of the unit. If necessary, use a windscreen to block the wind.
Do not install or operate the unit on locations where air contains high levels of salt, like e.g. in the vicinity of oceans. (Refer for further information to the engineering databook).
During installation, avoid the possibility that anybody can climb on the unit or place objects on the unit.
Falls may result in injury. When installing the unit in a small room, take measures in order
to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak.
OF
LOCATION
Suction side
A+C
have no impact on
The service space dimensions in figure 1 are based on cooling operation at 35°C.
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation. It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment, personal computers, etc...
(See figure 2).
1 Personal computer or radio 2 Fuse 3 Earth leakage breaker 4 Remote controller 5 Cool/heat selector 6 Indoor unit
In places with weak reception, keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines.
In heavy snowfall areas, select an installation site where snow will not affect the operation of the unit.
The refrigerant R410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed the allowable limit depending on room size. Due to this, it could be necessary to take measures against leakage. Refer to the chapter "14. Caution for refrigerant leaks" on
page 29.
Do not install in the following locations.
• Locations where sulfurous acids and other corrosive gases may be present in the atmosphere.
Copper piping and soldered joints may corrode, causing refrigerant to leak.
• Locations where a mineral oil mist, spray or vapour may be present in the atmosphere.
Plastic parts may deteriorate and fall off or causing water leakage.
• Locations where equipment that produces electro­magnetic waves is found.
The electromagnetic waves may cause the control system to malfunction, preventing normal operation.
• Locations where flammable gases may leak, where thinner, gasoline, and other volatile substances are handled, or where carbon dust and other incendiary substances are found in the atmosphere.
Leaked gas may accumulate around the unit, causing an explosion.
When installing, take strong winds, typhoons or earthquakes into account. Improper installation may result in fall over of the unit.
Installation manual
3
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
RXYQ8~12P7Y1K + RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
4. I
At delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.
When handling the unit, take into account the following:
5.1 From the moment you use a forklift to move the unit to its final
5.2 Once at final position, unpack the unit and pass the forklift arms
NSPECTING
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
Choose on beforehand the path along which the unit is to be brought in.
Bring the unit as close as possible to its final installation position in its original package to prevent damage during transport. (See
figure 4)
1 Packaging material 2 Opening (large) 3 Belt sling 4 Opening (small) (40x45) 5 Protector
Lift the unit preferably with a crane and 2 belts of at least 8 m long. (See figure 4)
Always use protectors to prevent belt damage and pay attention to the position of the unit's centre of gravity.
NOTE
If a forklift is to be used, preferably transport the unit with pallet first, then pass the forklift arms through the large rectangular openings on the bottom of the unit. (See figure 5)
position, lift the unit under the pallet.
through the large rectangular openings on the bottom of the unit.
NOTE
AND
HANDLING
Use a belt sling of 20 mm wide that adequately bears the weight of the unit.
Use filler cloth on the forklift arms to prevent damaging the unit. If the paint on the bottom frame peels off, the anti corrosion effect may decrease.
THE
UNIT
4
1
2
3
4
5
Fasten the unit in place using four foundation bolts M12. It is best to screw in the foundation bolts until their length remains 20 mm above the foundation surface.
Prepare a water drainage channel around the foundation to drain waste water from around the unit.
If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities first.
If the unit is to be installed on a frame, install the waterproofing board within a distance of 150 mm under the unit in order to prevent infiltration of water coming from under the unit.
When installed in a corrosive environment, use a nut with plastic washer (1) to protect the nut tightening part from rust.
20 mm
1

Method for removing transportation stays

(only for RXYQ10 and RXYQ12 units) The 4 yellow transportation stays installed over the compressor legs
for protecting the unit during transport must be removed. Proceed as shown in figure 9 and described below.
A Compressor B Fixing nut C Tr ansportation stay
1 Slightly loosen the fixing nut (B). 2 Remove the transportation stay (C) as shown in figure 9. 3 Tighten the fixing nut (B) again.
CAUTION
If the unit is operated with the transportation stay attached, abnormal vibration or noise may be generated.

6. REFRIGERANT PIPING

Do not insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at high speed, it will cause injury.
5. U
The unit must be installed on a solid longitudinal foundation
Support the unit with a foundation of 67 mm wide or more. (The
NPACKING
Remove the four screws fixing the unit to the pallet. Make sure the unit is installed level on a sufficiently strong base
to prevent vibration and noise.
Do not use stands to only support the corners. (See
figure 7)
O Allowed (units: mm)
Make sure the base under the unit is larger than the 765 mm of the unit depth. (See figure 3)
The height of the foundation must at least be 150 mm from the floor.
(steelbeam frame or concrete) as indicated in figure 3.
Model A B
RXYQ8 930 792 RXYQ10+12 1240 1102
support leg of the unit is 67 mm wide, see figure 3).
AND
X Not allowed
PLACING
THE
UNIT
Use R410A to add refrigerant. All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and national regulations.
Caution to be taken when brazing refrigerant piping
Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.
Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.
Be sure to perform a nitrogen blow when brazing. Brazing without performing nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes, adversely affecting valves and compressors in the refrigerating system and preventing normal operation.
After completing the installation work, check that the refrigerant gas does not leak.
To xic gas may be produced if the refrigerant gas leaks into the room and comes in contact with a source of fire.
Ventilate the area immediately in the event of a leak. In the event of a leak, do not touch the leaked refrigerant
directly. Frostbite may be caused.
RXYQ8~12P7Y1K + RXYQ8~12P7YLK VRVIII System air conditioner 4PW41760-1
Installation manual

6.1. Installation tools

6.3. Pipe connection

Make sure to use installation tools (gauge manifold charge hose, etc.) that are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils such as SUNISO and moisture) from mixing into the system. (The screw specifications differ for R410A and R407C.)
Use a 2-stage vacuum pump with a non-return valve which can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
NOTE
Make sure the pump oil does not flow oppositely into the system while the pump is not working.

6.2. Selection of piping material

1. Foreign materials inside pipes (including oils for fabrication) must be 30 mg/10 m or less.
2. Use the following material specification for refrigerant piping:
Size: determine the proper size referring to chapter
"6.6. Example of connection" on page 8.
Construction material: phosphoric acid deoxidized seamless
copper for refrigerant.
Temper grade: use piping with temper grade in function of the
pipe diameter as listed in the table below.
Pipe Ø Temper grade of piping material
15.9 O19.1 1/2H
O = Annealed 1/2H = Half hard
Be sure to perform a nitrogen blow when brazing and to read the paragraph "Caution to be taken when brazing refrigerant piping" on
page 4 first.
NOTE
The pressure regulator for the nitrogen released when doing the brazing should be set to 0.02 MPa or less.
(See figure 10)
1 Refrigerant piping 2 Location to be brazed 3 Nitrogen 4 Taping 5 Manual valve 6 Regulator 7 Nitrogen
Do not use anti-oxidants when brazing the pipe joints. Residue can clog pipes and break equipment.

6.4. Connecting the refrigerant piping

1Front connection or side connection
Installation of refrigerant piping is possible as front connection or side connection (when taken out from the bottom) as shown in the figure.
The pipe thickness of the refrigerant piping should comply
with relevant local and national regulations. The minimal pipe thickness for R410A piping must be in accordance with the table below.
Minimal thickness
Pipe Ø
6.4 0.80 22.2 0.80
9.5 0.80 28.6 0.99
12.7 0.80 34.9 1.21
15.9 0.99 41.3 1.43
19.1 0.80
t (mm)
Pipe Ø
Minimal thickness
t (mm)
3. Make sure to use the particular branches of piping that have
been selected referring to chapter "6.6. Example of connection"
on page 8.
4. In case the required pipe sizes (inch sizes) are not available, it is also allowed to use other diameters (mm sizes), taken the following into account:
select the pipe size nearest to the required size.
use the suitable adapters for the change-over from inch to
mm pipes (field supply).
5. Precautions when selecting branch piping When the equivalent pipe length between outdoor and indoor units is 90 m or more, the size of the main pipes (both gas side and liquid side) must be increased. Depending on the length of the piping, the capacity may drop, but even in such a case it is possible to increase the size of the main pipes. Refer to page 9. If the recommended pipe size is not available, stick to the original pipe diameter (which may result in a small capacity decrease).
12 3
1 Left-side connection 2 Front connection 3 Right-side connection
NOTE
Precautions when knocking out knock holes
Be sure to avoid damaging the casing
After knocking out the holes, we recommend you
remove the burrs and paint the edges and areas around the edges using the repair paint to prevent rusting.
When passing electrical wiring through the knock holes, wrap the wiring with protective tape to prevent damage.
2 Removing the pinched piping
When connecting refrigerant piping to the outdoor unit, first remove the pinched piping. Do not vent gases into the atmosphere. Removing of the pinched piping must be carried out according to the following procedure:
1. Make sure the stop valves are closed.
2. Connect a charge hose to the service ports of all stop
valves.
3. Recover the gas from the pinched piping.
4. When all the gas is recovered from the pinched piping,
dissolve the brazing using a burner and remove the pinched piping.
Installation manual
5
Any gas remaining inside the stop valve may blow off the pinched piping, causing damage or injury.
RXYQ8~12P7Y1K + RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1
See figure 6.
1 Pinched piping 2 Stop valve 3 Service port 4 Point of melting the brazing metal
NOTE
When connecting the piping on site, be sure to use the accessory piping.
Make sure the onsite piping does not come into contact with other piping, the bottom frame or side panels of the unit.
Precautions when connecting field piping.
Perform brazing at the gas stop valve before brazing at the liquid stop valve.
Add brazing material as shown in the figure.
Be sure to use the supplied accessory pipes
when carrying out piping work in the field.
Be sure that the field installed piping does not touch other pipes, the bottom panel or side panel. Especially for the bottom and side connection, be sure to protect the piping with suitable insulation, to prevent it from coming into contact with the casing.
3 One outdoor unit installed: In case of RXYQ8~12
(See figure 8)
Front connection: Remove the stop valve cover to connect.
Bottom connection: Remove the knock holes on the bottom frame and route the piping under the bottom frame.
A Front connection
Remove the stop valve cover to connect.
B Bottom connection:
Remove the knock holes on the bottom frame and route the piping under the bottom frame
1 Gas pipe stop valve 2 Liquid pipe stop valve 3 Service port for adding refrigerant 4 Gas side accessory pipe (1) 5 Gas side accessory pipe (2) 6 Liquid side accessory pipe (1) 7 Liquid side accessory pipe (2) 8 Brazing
9 Gas side piping (field supply) 10 Liquid side piping (field supply) 11 Punch the knockout holes (use a hammer)
4 Outdoor units installed in a multiple outdoor unit system:
RXYQ16~36
Front connection: Remove the stop valve cover to connect. (See figure 8)
Bottom connection: Remove the knock holes on the bottom frame and route the piping under the bottom frame. (See figure 8)
4.1 Precautions when connecting piping between outdoor units (multiple outdoor unit system)
To connect the piping between outdoor units, an optional
multi connection piping kit BHFQ22P1007/1517 is always required. When installing the piping, follow the instructions in the installation manual that comes with the kit.
Only proceed with piping work after considering the
limitations on installing listed here and in the chapter
"6.4. Connecting the refrigerant piping" on page 5, always
referring to the installation manual delivered with the kit.
4.2 Possible installation patterns and configurations
The piping between the outdoor units must be routed level or
slightly upward to avoid the risk of oil retention into the piping side.
Pattern 1
1
1
1 To indoor unit
Pattern 2
1
1
1 To indoor unit
Prohibited patterns: change to pattern 1 or 2.
1
1
2
1 To indoor unit 2 Piping between outdoor units
2
Processing the gas side accessory pipe (2) Only in case of connecting at lateral side, cut the gas side accessory pipe (2) as shown in figure 11.
1 Gas side accessory pipe 2 Cutting location 3 Gas side piping (field supply) 4 Base
Unit type A B C D
8 Hp 10 Hp 12 Hp
RXYQ8~12P7Y1K + RXYQ8~12P7YLK VRVIII System air conditioner 4PW41760-1
(mm)
156 17 188 247
(mm)
150 29 192 247
(mm)
150 29 192 247
Installation manual
6
To avoid the risk of oil retention to the outmost outdoor unit,
h
always connect the stop valve and the piping between outdoor units as shown in the 4 correct possibilities of the figure below.
Prohibited patterns: change to pattern 1 or 2.
1
2 2
1 To indoor unit 2 Oil collects to the outmost outdoor unit.
1
22
Change to configuration as in figures below
11
22
1 To indoor unit 2 Oil collects to the outmost outdoor unit when the system
stops.
Correct configuration
200 mm
11
1 To indoor unit
If the piping length between the outdoor units exceeds 2 m, create a rise of 200 mm or more in the gas line within a length of 2 m from the kit.
- If 2 m
1
2
2 m
- If 2 m
200 mm
1
1 To indoor unit 2 Piping between outdoor units
2 m
2
2 m
5 Branching the refrigerant piping
For installation of the refrigerant branching kit, refer to the installation manual delivered with the kit.
(See figure 13)
1 Horizontal surface
Follow the conditions listed below:
- Mount the refnet joint so that it branches either horizontally or vertically.
- Mount the refnet header so that it branches horizontally.
Installation of the multi connection piping kit
(See figure 17)
- Install the joints horizontally, so that the caution label (1) attached to the joint comes to the top. Do not tilt the joint more than 15° (see view A). Do not install the joint vertically (see view B).
- Make sure that the total length of the piping connected to the joint is absolute straight for more than 500 mm. Only if a straight field piping of more than 120 mm is connected, more than 500 mm of straight section can be ensured.
- Improper installation may lead to malfunction of the outdoor unit.
6 Piping length restrictions
Make sure to perform the piping installation within the range of the maximum allowable pipe length, allowable level difference and allowable length after branching as indicated in
"6.6. Example of connection" on page 8.

6.5. Protection against contamination when installing pipes

-Take measures to prevent foreign materials like moisture and contamination from mixing into the system.
Installation period Protection method
More than a month Pinch the pipe Less than a month Pinch or tape the pipe Regardless of the period
- Great caution is needed when passing copper tubes through walls.
- Block all gaps in the holes for passing out piping and wiring using sealing material (field supply). (The capacity of the unit will drop and small animals may enter the machine.)
Example: passing piping out through the front
1 To indoor unit 2 Piping between outdoor units
Installation manual
7
1 Plug the areas marked with "
(When the piping is routed from t front panel.)
2 Gas side piping 3 Liquid side piping
123
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak check.
RXYQ8~12P7Y1K + RXYQ8~12P7YLK
VRVIII System air conditioner
4PW41760-1

6.6. Example of connection

H1
i
8
H2
h
g
f
cde
a
123 4567
b
H1
i
8
H2
h
g
H3
f
a
cde
123 4567
b
r≤10 m (Approximate length:
max. 13 m)
s≤10 m (Approximate length:
max: 13 m)
rs t
t≤10 m (Approximate length:
max: 13 m)
(a)
[Example]
in case of refnet header;
indoor units 1+2+3+4+5+6+7+8
H2
k
78
j
B
h
g
i
b
A
123456
a
cde f
H1
p
H1
8
H2
g
Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
1234567
hijklmn
ABCDEFG
ab c d e f
H3
H3
k
B
i
b
A
a
H1
H1
g
abcdef
j
p
EFG
D
ABC
H2
78
gh
de f
c
H2
7
123 456
hi j kl mn
8
123456
Pipe length between outdoor(*) and indoor units 165 m
[Example] unit 8: a+b+c+d+e+f+g+p165 m [Example] unit 6: a+b+h165 m, unit 8: a+i+k165 m [Example] unit 8: a+i165 m
Equivalent pipe length between outdoor(*) and indoor units 190 m (Assume equivalent pipe length of refnet joint to be 0.5 m and of the refnet header to be 1.0 m. (for
calculation purposes))
Total piping length from outdoor unit* to all indoor units 1000 m
(a) See note 2 on next page
units connected below the refnet header.
<290 KHRQ22M29H (Max. 8 branch)
290x<640 KHRQ22M64H (Max. 8 branch)
Indoor capacity type Refrigerant branch kit name
• Choose from the following table in accordance with the total capacity of all the indoor
• Note: 250 type cannot be connected below the refnet header.
How to select the refnet header
640 KHRQ22M75H (Max. 8 branch)
How to choose an outdoor multi connection piping kit (needed if the outdoor
[Example] unit 6: b+h40 m, unit 8: i+k40 m [Example] unit 8: i40 m
Choose from the following table in accordance with the capacity of the outdoor unit.
Outdoor unit capacity type Refrigerant branch kit name
RXYQ8 KHRQ22M20T
Difference in height between outdoor and indoor units (H1)50 m (40 m if outdoor unit is located in a lower
position).
Difference in height between adjacent indoor units (H2)15 m
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3)5 m
[Example] unit 8: b+c+d+e+f+g+p40 m
Pipe length from first refrigerant branch kit (either refnet joint or refnet header) to indoor unit 40 m (See note 1 on next page)
How to select the refnet joint
•When using refnet joints at the first branch counted from the outdoor unit side.
RXYQ8+10 KHRQ22M29T9
the total capacity index.
RXYQ12 + RXYQ16~22 KHRQ22M64T
RXYQ24~36 KHRQ22M75T
•For refnet joints other than the first branch, select the proper branch kit model based on
Number of outdoor units Branch kit name
• Choose from the following table in accordance with the number of outdoor units.
unit capacity type is RXYQ16 or more.)
Indoor capacity type Refrigerant branch kit name
<200 KHRQ22M20T
2 BHFQ22P1007
3 BHFQ22P1517
[Example]
200x<290 KHRQ22M29T9
290x<640 KHRQ22M64T
640 KHRQ22M75T
[Example]
in case of refnet joint B; indoor units 7+8,
in case of refnet header; indoor units 1+2+3+4+5+6
in case of refnet joint C; indoor units 3+4+5+6+7+8
One outdoor unit
installed
(RXYQ8~12)
• Use the outdoor unit multi connection piping kit that is sold separately as an option
Example of connection
(Connection of 8 indoor units Heat pump system)
RXYQ8~12P7Y1K + RXYQ8~12P7YLK VRVIII System air conditioner 4PW41760-1
Outdoor units
installed in a
multiple outdoor
unit system
(RXYQ16~36)
indoor unit
refnet joint
(BHFQ22P1007+1517) for the multi installation of outdoor units. Selection method is
as shown in the right table.
are sold separately as an option of the M-type series and do not use T-joints.
• Do not use the outdoor unit multi connection piping kit (BHFQ22M909+1359) that
refnet header
outdoor multi connection piping kit
Install the joint part ( part in the figure) of the outdoor unit multi connection piping kit
horizontally with attention to the installation restrictions described in "connecting the
refrigerant piping".
Actual pipe length
Equivalent length
Between outdoor and indoor units
(*) If the system capacity is RXYQ16 or more, re-read to the first outdoor branch as
seen from the indoor unit.
Maximum allowable length
Total extension
length
Actual pipe length Piping length from outdoor branch to outdoor unit 10 m. Approximate length: max. 13 m
Difference in
height
Difference in
height
Between outdoor branch and outdoor unit (Only for
RXYQ16 or more)
Between outdoor and indoor units
Between indoor and indoor units
Allowable height
Difference in
height
Between outdoor and outdoor units
Allowable length after the branch Actual pipe length
Refrigerant branch kit selection
Refrigerant branch kits can only be used with R410A.
Example of downstream indoor units
Installation manual
8
Loading...
+ 23 hidden pages