1.1O tem dokumentu...........................................................................................................................................................4
1.1.1Pomen opozoril in simbolov ........................................................................................................................... 5
2.1.3Hladivo — v primeru R410A ali R32 ............................................................................................................... 11
2.1.4Električna dela ................................................................................................................................................ 13
3 Specifična varnostna navodila za monterja16
4 O škatli22
4.1Pregled: O škatli .............................................................................................................................................................. 22
4.2Zunanja enota ................................................................................................................................................................. 22
4.2.1Razpakiranje zunanje enote ........................................................................................................................... 22
4.2.2Prenašanje zunanje enote .............................................................................................................................. 23
4.2.3Odstranjevanje opreme iz zunanje enote...................................................................................................... 23
5.1.1Nazivna ploščica: zunanja enota .................................................................................................................... 25
6 Montaža enote26
6.1Priprava mesta namestitve............................................................................................................................................. 26
6.1.1Zahteve za namestitveno mesto za zunanjo enoto ....................................................................................... 27
6.1.2Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih.......................................... 29
6.2.1O odpiranju enote .......................................................................................................................................... 30
6.2.2Odpiranje zunanje enote................................................................................................................................ 30
6.3Nameščanje zunanje enote ............................................................................................................................................ 30
6.3.1O nameščanju zunanje enote......................................................................................................................... 30
6.3.2Varnostni ukrepi pri nameščanju zunanje enote ........................................................................................... 31
6.3.4Montaža zunanje enote ................................................................................................................................. 32
6.3.6Preprečevanje prevračanja zunanje enote .................................................................................................... 32
7 Montaža cevi34
7.1Priprava cevi za hladivo................................................................................................................................................... 34
7.1.1Zahteve za cevi za hladivo .............................................................................................................................. 34
7.1.2Izolacija cevi za hladivo................................................................................................................................... 35
7.1.3Dolžina cevi za hladivo in višinske razlike....................................................................................................... 35
7.2Povezovanje cevi za hladivo............................................................................................................................................ 35
7.2.1O priključevanju cevi za hladivo ..................................................................................................................... 35
7.2.2Varnostni ukrepi pri priključevanju cevi za hladivo ....................................................................................... 36
7.2.3Navodila pri priključevanju cevi za hladivo .................................................................................................... 37
7.2.4Napotki za upogibanje cevi ............................................................................................................................ 38
7.2.5Robljenje konca cevi ....................................................................................................................................... 38
7.2.6Uporaba zapornega ventila in servisnega priključka ..................................................................................... 38
7.2.7Priključevanje cevi za hladivo na zunanjo enoto ........................................................................................... 40
7.3Preverjanje cevi za hladivo ............................................................................................................................................. 40
7.3.1O preverjanju cevi za hladivo ......................................................................................................................... 40
7.3.2Napotki za varnost pri preverjanju cevi za hladivo ........................................................................................ 41
8.3Varnostni ukrepi pri polnjenju s hladivom ..................................................................................................................... 46
8.4Določanje dodatne količine hladiva................................................................................................................................ 46
8.5Določanje celotne količine ponovnega polnjenja .......................................................................................................... 46
9.2Da bi povezali električno ožičenje na zunanjo enoto..................................................................................................... 51
10 Zaključevanje montaže zunanje enote53
10.1Zaključevanje montaže zunanje enote........................................................................................................................... 53
10.2.1Zapiranje zunanje enote................................................................................................................................. 53
11.1.1Nastavitev načina obrata................................................................................................................................ 54
12.2Varnostni ukrepi pri začetku uporabe............................................................................................................................ 55
12.3Seznam preverjanj pred zagonom.................................................................................................................................. 56
12.4Seznam preverjanj med zagonom.................................................................................................................................. 56
12.6Zagon zunanje enote ...................................................................................................................................................... 57
13 Izročitev uporabniku58
14 Vzdrževanje in servisiranje59
14.1Pregled: Vzdrževanje in servisiranje............................................................................................................................... 59
14.2Varnostni ukrepi za vzdrževanje..................................................................................................................................... 59
14.3Seznam preverjanj za letno vzdrževanje zunanje enote................................................................................................ 60
15.2Varnostni ukrepi pri odpravljanju težav ......................................................................................................................... 61
15.3Reševanje težav na podlagi simptomov ......................................................................................................................... 61
15.3.1Simptom: Notranje enote padajo, vibrirajo ali oddajajo zvoke..................................................................... 61
15.3.2Simptom: Enota NE ogreva oziroma ne hladi po pričakovanjih .................................................................... 61
15.3.5Simptom: Enota NE deluje ali ožganine ......................................................................................................... 62
15.4Diagnosticiranje napak s svetlečo diodo na tiskanem vezju zunanje enote.................................................................. 62
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
3
1 | O dokumentaciji
1 O dokumentaciji
1.1 O tem dokumentu
INFORMACIJA
Prepričajte se, da ima uporabnik natisnjeno dokumentacijo in ga prosite, naj jo
shrani.
Ciljni prejemniki
Pooblaščeni monterji
OPOZORILO
Prepričajte se, da so materiali za namestitev, servisiranje, vzdrževanje, popravila in
sploh uporabljeni materiali v skladu z navodili iz Daikin ter da se skladajo z ustrezno
zakonodajo in da so vsa našteta dejanja izvedle kvalificirane osebe. V Evropi in na
območjih, kjer so v uporabi standardi IEC, je ustrezen standard EN/IEC 60335-2-40.
INFORMACIJA
V tem dokumentu so samo navodila za montažo, ki se nanašajo na zunanjo enoto. Za
nameščanje notranje enote (nameščanje notranje enote, priključevanje cevi za
hladivo na notranjo enoto, priključevanje električnega ožičenja na notranjo enoto …),
glejte priročnik za montažo notranje enote.
Komplet dokumentacije
Ta dokument je del kompleta dokumentacije. Celotno dokumentacijo sestavljajo:
▪ Splošni varnostni ukrepi:
- Varnostna navodila, ki jih morate prebrati pred montažo
- Format: Papirni izvod (v škatli zunanje enote)
▪ Priročnik za montažo zunanje enote:
- Navodila za montažo
- Format: Papirni izvod (v škatli zunanje enote)
▪ Vodnik za monterja:
- Priprava za namestitev, referenčni podatki …
- Format: Digitalne datoteke na naslovu http://www.daikineurope.com/support-
and-manuals/product-information/
V območnem spletnem mestu Daikin ali pri vašem prodajalcu so morda na voljo
najnovejše posodobitve priložene dokumentacije.
Vodnik za monterja
4
Izvorna dokumentacija je pisana v angleščini. Dokumentacija v drugih jezikih je
prevod.
Tehnično-inženirski podatki
▪ Povzetek najnovejših tehničnih podatkov je na voljo na regionalni Daikin spletni
strani (javno dostopna).
▪ Popolni tehnični podatki so na voljo na Daikin Business Portal (zahtevana
avtentikacija).
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
1.1.1 Pomen opozoril in simbolov
NEVARNOST
Označuje situacijo, ki vodi v smrt in hude telesne poškodbe.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Označuje situacijo, ki lahko povzroči smrt zaradi električnega udara.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Prikazuje situacijo, ki bi lahko povzročila ožganine/opekline zaradi izjemno visokih ali
nizkih temperatur.
NEVARNOST: NEVARNOST EKSPLOZIJE
Označuje situacijo, ki lahko povzroči eksplozijo.
OPOZORILO
Označuje situacijo, ki lahko povzroči smrt in hude telesne poškodbe.
1 | O dokumentaciji
OPOZORILO: VNETLJIV MATERIAL
OPOMIN
Označuje situacijo, ki lahko povzroči manjše ali srednje nevarne telesne poškodbe.
OPOMBA
Označuje situacijo, ki lahko povzroči poškodbe opreme ali lastnine.
INFORMACIJA
Označuje uporabne nasvete ali dodatne informacije.
Simboli, uporabljeni na enoti:
SimbolRazlaga
Pred namestitvijo preberite navodila za montažo in uporabo
ter shemo z navodili za ožičenje.
Preden začnete izvajati vzdrževalne in servisne postopke
preberite priročnik za servisiranje.
Za več informacij glejte vodnik za monterja in uporabnika.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Enota vsebuje vrtljive dele. Pri servisiranju in pregledovanju
bodite pazljivi.
Simboli, uporabljeni v dokumentaciji:
SimbolRazlaga
Pomeni naslov slike ali sklic nanjo.
Primer: " 1–3 naslov slike" pomeni "3. slika v 1. poglavju".
Vodnik za monterja
5
1 | O dokumentaciji
SimbolRazlaga
Pomeni naslov tabele ali sklic nanjo.
Primer: " 1–3 naslov tabele" pomeni "3. tabela v 1.
poglavju".
Vodnik za monterja
6
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2 Splošni varnostni ukrepi
2.1 Za monterja
2.1.1 Splošno
Če NISTE prepričani, kako montirati ali upravljati enoto, se obrnite na svojega
prodajalca.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
▪ NE dotikajte se cevi za hladivo, cevi za vodo in notranjih delov med delovanjem ali
neposredno po delovanju. Lahko so prevroči ali premrzli. Počakajte, da se njihova
temperatura normalizira. Če se jih morate dotikati, si nadenite zaščitne rokavice.
▪ Z golo kožo se NE dotikajte ponesreči razlitega hladiva.
OPOZORILO
Nestrokovna montaža ali priklop naprave in opreme lahko povzroči električni udar,
kratek stik, uhajanje tekočin ali požar ali drugače poškoduje napravo ali opremo.
Uporabljajte samo dodatke, opcijsko opremo in nadomestne dele, ki jih izdela ali
odobri Daikin.
2 | Splošni varnostni ukrepi
OPOZORILO
Montaža, preizkus in uporabljeni materiali morajo biti (razen z navodili, opisanimi v
dokumentaciji Daikin) skladni tudi z veljavno zakonodajo.
OPOMIN
Pri nameščanju, vzdrževanju ali servisiranju sistema uporabljajte ustrezno osebno
zaščitno opremo (zaščitne rokavice, varnostna očala…).
OPOZORILO
Raztrgajte in odvrzite plastične vreče, da se z njimi nihče ne bi mogel igrati, zlasti ne
otroci. Možna nevarnost: zadušitev.
OPOZORILO
Z zagotavljanjem primernih ukrepov preprečite, da bi enota postala zavetišče za
majhne živali. Majhne živali, ki se dotaknejo električnih delov, lahko povzročijo
okvare, dim ali požar.
OPOMIN
Ne dotikajte se odprtine za vstop zraka ali aluminijastih platic enote.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
OPOMIN
▪ Na vrh enote NE postavljajte predmetov ali opreme.
▪ NE sedite na napravi, ne plezajte nanjo in ne stojte na njej.
Vodnik za monterja
7
2 | Splošni varnostni ukrepi
V skladu z zadevno zakonodajo bo treba morda skupaj z izdelkom priskrbeti
dnevnik, v katerem se beležijo najmanj: podatki o vzdrževanju, popravila, rezultati
testov, obdobja pripravljenosti…
Najmanj naslednje informacije MORAJO biti zagotovljene na dostopnem mestu
izdelka:
▪ Navodila za izklop sistema v nujnem primeru
▪ Naziv in naslov gasilske službe, policije in bolnišnice
▪ Ime, naslov ter dnevna in nočna telefonska številka za servis
Potrebne smernice za tak dnevnik za Evropo podaja standard EN378.
2.1.2 Mesto namestitve
▪ Zagotovite dovolj prostora okoli enote za servisiranje in kroženje zraka.
▪ Prepričajte se, da mesto namestitve prenese težo in vibracije enote.
OPOMBA
Dela na zunanji enoti je najbolje opraviti v suhem vremenu, da bi se izognili vdoru
vode.
▪ Prepričajte se, da je območje dobro prezračeno. NE blokirajte prezračevalnih
odprtin.
▪ Pazite, da bo enota izravnana.
Enote NE nameščajte na naslednja mesta:
▪ V potencialno eksplozivnem okolju.
▪ Na mestih, kjer so stroji, ki oddajajo elektromagnetne valove. Elektromagnetni
valovi lahko motijo krmilni sistem in lahko povzročijo okvare na opremi.
▪ Na mestih, kjer obstaja nevarnost požara zaradi uhajanja vnetljivih plinov
(primer: razredčilo ali bencin), ogljikovih vlaken ali vnetljivega prahu.
▪ Na mestih, kjer nastajajo korozivni plini (primer: kisli žvepleni plin). Zaradi
korozije bakrenih cevi ali zvarov bi lahko začelo puščati hladivo.
Navodila za opremo, ki uporablja hladivo R32
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
OPOZORILO
▪ NE prebadajte in ne zažigajte.
▪ NE uporabite sredstev in načinov za pospeševanje odmrzovanja ali čiščenja
opreme, razen tistih, ki jih priporoča proizvajalec.
▪ Bodite pozorni na to, da je R32 BREZ vonja.
Vodnik za monterja
8
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro
prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (na primer: odprtega
plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega
mora biti prostor v izmeri, navedeni v nadaljevanju.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2 | Splošni varnostni ukrepi
OPOZORILO
Prepričajte se, da so namestitev, servisiranje, vzdrževanje in popravila izvedeni v
skladu z navodili Daikin in v skladu z veljavno zakonodajo (na primer predpisom o
plinu) in da jih izvajajo pooblaščene osebe.
OPOZORILO
Če je na enoto prek sistema cevovodov povezana ena ali več sob, se prepričajte:
▪ da ni delujočih virov vžiga (npr.: odprtega plamena, delujoče plinske naprave ali
delujočega električnega grelnika), če je površina tal manjša od minimalne
kvadrature prostora A (m²);
▪ da na cevovodu ni nameščenih pomožnih naprav, ki bi lahko bile morebitni vir
vžiga (npr.: vroče površine s temperaturo, višjo od 700°C, in električne stikalne
naprave);
▪ da so v cevovodu uporabljene le pomožne naprave, ki jih je odobril proizvajalec;
▪ da sta vstopna IN izstopna zračna odprtina neposredno povezani z istim
prostorom s cevmi. NE uporabljajte prostorov, kot so spuščeni strop, za dovodni
ali odvodni vod za zrak.
OPOMBA
▪ Uporabite varnostne ukrepe za izogibanje prevelikemu vibriranju ali utripanju cevi
za hladivo.
▪ Zaščitne naprave, cevovodi in spoji morajo biti čim bolj zaščiteni pred neugodnimi
okoljskimi vplivi.
▪ Poskrbite za prostor za raztezanje in krčenje dolgih cevi.
▪ Cevovodi in sistemi za hladivo morajo biti načrtovani in nameščeni tako, da je
verjetnost hidravličnega šoka, ki bi poškodoval sistem, kar se da majhna.
▪ Notranja oprema in cevi morajo biti varno nameščeni in zavarovani tako, da ne
more priti do pokov na opremi ali ceveh zaradi premikanja pohištva ali
obnavljanja prostorov.
OPOMIN
NE uporabite morebitnih virov vžiga pri iskanju ali beleženju puščanja hladiva.
OPOMBA
▪ Spojev in bakrenih tesnil, ki so že bili uporabljeni, NE uporabljajte znova.
▪ Spoji, ki so bili narejeni na inštalaciji med deli hladilnega sistema, morajo biti
dostopni za vzdrževanje.
Zahteve namestitve po prostoru
OPOZORILO
Če je v napravah hladivo R32, MORA biti kvadratura prostora, v katerega se namešča,
v katerem deluje ali je skladiščena naprava, večja od najmanjše kvadrature prostora,
določene v spodnji tabeli A (m2). To velja za:
▪ Notranje enote brez tipala za puščanje hladiva; v primeru notranjih enot s tipalom
za puščanje hladiva glejte priročnik za montažo
▪ Zunanje enote, nameščene ali skladiščene v notranjih prostorih (npr. zimski vrt,
garaža, strojnica)
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
9
2 | Splošni varnostni ukrepi
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
Da bi določili najmanjšo potrebno kvadraturo prostora
1Izračunajte skupno količino hladiva v sistemu (=tovarniška polnitev hladiva +
2Določite, kateri grafikon ali tabelo uporabiti.
Če je višina namestitve …Uporabite grafikon ali tabelo za …
OPOMBA
▪ Cevovod mora biti zaščiten pred fizičnimi poškodbami.
▪ Cevi mora biti najmanj, kar je mogoče.
dolito hladivo).
▪ Za notranje enote: Je enota nameščena na strop, na steno ali stoji na tleh?
▪ Za zunanje enote, nameščene ali shranjene notri, je to odvisno od višine
namestitve:
<1,8mStoječe enote
1,8≤x<2,2mEnote, nameščene na steno
≥2,2mEnote, nameščene na strop
3Uporabite grafikon ali tabelo za določanje minimalne kvadrature prostora.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2.1.3 Hladivo — v primeru R410A ali R32
Če se uporablja. Za več informacij glejte priročnik za montažo ali referenčni vodnik
za monterja za vašo uporabo.
m Skupna polnitev hladiva v sistemu
A
Najmanjša kvadratura prostora
min
(a) Ceiling-mounted unit (= Enota, nameščena na stropu)
(b) Wall-mounted unit (= Enota, nameščena na steni)
(c) Floor-standing unit (= Stoječi tip enote)
OPOMBA
Napeljava cevi mora biti skladna z veljavno zakonodajo. Zadevni standard za Evropo
je EN378.
OPOMBA
Poskrbite, da zunanje cevi in priključki NE bodo obremenjeni.
OPOZORILO
Med testiranjem v izdelku NIKOLI ne smete vzpostaviti tlaka, višjega od
maksimalnega dovoljenega tlaka (ki je naveden na nazivni ploščici enote).
Vodnik za monterja
11
2 | Splošni varnostni ukrepi
OPOZORILO
Poskrbite za ustrezne varnostne ukrepe za primer puščanja hladiva. Če med
nameščanjem izteče hladilno sredstvo v plinastem stanju, takoj prezračite prostor.
Možna tveganja:
▪ Prevelika koncentracija hladiva v zaprtem prostoru lahko privede do pomanjkanja
kisika.
▪ Če pride plinasto hladivo v stik z ognjem, lahko nastanejo strupeni plini.
NEVARNOST: NEVARNOST EKSPLOZIJE
Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati in nekje na tokokrogu
hladilnega sredstva pušča:
▪ NE uporabljajte funkcije za samodejno izčrpavanje na enoti, s katero lahko
zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje
in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
▪ Uporabite ločen sistem za izčrpavanje, tako da kompresorju enote NI treba
delovati.
OPOZORILO
Hladivo VEDNO zberite. NE izpuščajte jih neposredno v okolje. Uporabite vakuumsko
črpalko, da boste izpraznili napeljavo.
OPOMBA
Ko so vse cevi priključene, se prepričajte, da plin ne uhaja. S pomočjo dušika
preverite, ali plin uhaja.
OPOMBA
▪ Preprečevanje okvare kompresorja, NE dolijte več hladiva, kot je navedeno v
specifikaciji.
▪ Kadar je treba sistem hladiva odpreti, morate s hladivom ravnati v skladu z
zadevno zakonodajo.
OPOZORILO
Pazite, da v sistemu ni kisika. Hladivo lahko natočite šele, ko opravite preizkus
tesnjenja in vakuumsko praznjenje.
Možna posledica: Samovžig in eksplozija kompresorja zaradi vstopa kisika v delujoči
kompresor.
▪ Če je to potrebno, preverite napisno ploščico na enoti. Na njej sta navedena tip
hladiva in potrebna količina.
▪ Enota je tovarniško napolnjena s hladivom. Odvisno od velikosti in dolžine cevi je
treba v nekaterih sistemih dotočiti hladivo.
▪ Da bi zagotovili upornost tlaka in preprečili vdor drugih snovi v sistem,
uporabljajte samo orodje, zasnovano posebej za vrsto hladiva, uporabljeno v
sistemu.
Vodnik za monterja
12
▪ Hladivo točite upoštevaje naslednje:
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2 | Splošni varnostni ukrepi
ČePotem
Je prisotna sifonska cev
(tj., na jeklenki je oznaka “Liquid filling
Pri polnjenju mora biti jeklenka
postavljena pokonci.
siphon attached” (pritrjena sifonska cev
za tekoče hladivo))
Sifonska cev NI prisotnaPri polnjenju mora biti jeklenka
obrnjena na glavo.
▪ Počasi odprite vsebnike hladiva.
▪ Hladivo točite v tekočem stanju. Dodajanje hladiva v plinskem stanju lahko
onemogoči normalno delovanje.
OPOMIN
Ko je postopek dolivanja hladiva dokončan ali ga prekinete, takoj zaprite ventil
rezervoarja za hladivo. Če se ventil NE zapre takoj, lahko preostanek tlaka napolni
dodatno hladivo. Možna posledica: Nepravilna količina hladiva.
2.1.4 Električna dela
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Izključite vse napajanje, preden snamete pokrov stikalne omarice, priključujete
električno napeljavo ali se dotikate električnih delov.
▪ Odklopite napajanje za več kot 10 minut ter izmerite napetost na priključnih
sponkah kondenzatorjev glavnega tokokroga ali električnih sestavnih delih,
preden začnete servisiranje. Napetost mora biti nižja od 50VDC, preden se lahko
dotaknete električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno
shemo.
▪ Električnih sestavnih delov se NE dotikajte z mokrimi rokami.
▪ Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
OPOZORILO
Če NI nameščeno, JE NUJNO v fiksno ožičenje namestiti glavno stikalo ali druge
možnosti odklopa, ki imajo ločen stik na vseh polih in omogočajo popolni odklop v
pogojih previsoke napetosti kategorijeIII.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
13
2 | Splošni varnostni ukrepi
OPOZORILO
▪ Uporabljajte LE bakrene vodnike.
▪ Pazite, da bodo električne napeljave ustrezale veljavni zakonodaji.
▪ Vse lokalno ožičenje mora biti izvedeno skladno z vezalno shemo, priloženo
izdelku.
▪ NIKOLI ne stiskajte šopov kablov in pazite, da NE pridejo v stik s cevmi ali z ostrimi
robovi. Prepričajte se, da na priključne sponke ne pritiska nič z zunanje strani.
▪ Pazite, da boste zagotovo namestili ozemljitveni vodnik. Ne ozemljujte naprave s
pomočjo komunalne cevi, prenapetostnega odvodnika ali ozemljitve telefona.
Nepopolna ozemljitev lahko povzroči električni šok.
▪ Zagotovo uporabite ločeno električno vezje. NIKOLI ne delite vira napajanja z
drugo napravo.
▪ Pazite, da boste zagotovo namestili zahtevane varovalke ali prekinjala vezij.
▪ Zagotovo namestite odklopnik z uhajanjem toka. Če tega ne storite, lahko pride
do električnega udara ali požara.
▪ Ko nameščate zemljostično zaščito, pazite, da je združljiva z inverterjem (odporna
na visokofrekvenčne električne šume), da bi se izognili nepotrebnemu odpiranju
zaščite.
OPOMIN
▪ Ko priključujete napajanje: najprej povežite ozemljitev, nato pa izvedite povezave
za prenos električnega toka.
▪ Ko izključujete napajanje: najprej odklopite povezave za prenos električnega toka,
nato pa še ozemljitev.
▪ Dolžina vodnikov med oporo napajalnega kabla in samim prikjučnim blokom mora
biti taka, da so napajalni vodniki napeti pred ozemljitvenim vodnikom, za primer,
da bi se napajalni kabel snel z opore kabla.
OPOMBA
Varnostni ukrepi pri napeljavi napajalnih vodnikov:
▪ NE priključujte vodnikov različnih debelin na priključne sponke napajanja
(ohlapnost napajalnih vodnikov lahko povzroči neobičajno segrevanje).
▪ Pri priključevanju vodnikov enake debeline naredite tako, kot je prikazano na sliki
zgoraj.
▪ Za ožičenje uporabite predvideni napajalni vodnik in ga trdno priključite, nato pa
zavarujte, da bi preprečili, da se zunanja sila prenese na priključno ploščo.
▪ Uporabite ustrezen izvijač za privijanje vijakov na priključku. Izvijač z malim
nastavkom lahko poškoduje glavo vijaka in onemogoči ustrezno zategovanje.
▪ S premočnim zategovanjem lahko vijake na priključkih polomite.
Vodnik za monterja
14
OPOZORILO
▪ Ko zaključite napeljavo električnih kablov, se prepričajte, da so vsi električni
sestavni deli in vse priključne sponke v omarici z električnimi sestavnimi deli varno
pritrjeni.
▪ Obvezno zaprite vse pokrove, preden zaženete enoto.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2 | Splošni varnostni ukrepi
OPOMBA
Velja samo, če je napajanje trifazno in je način zagona kompresorja VKLOP/IZKLOP.
Če obstaja možnost, da bi do obrnjene faze prišlo po trenutnem izpadu in se
napajanje vklaplja in izklaplja med delovanjem izdelka, priključite vezje za zaščito
pred obrnjeno fazo lokalno. Delovanje izdelka z obrnjeno fazo lahko povzroči okvaro
kompresorja in drugih delov.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
15
3 | Specifična varnostna navodila za monterja
3 Specifična varnostna navodila za monterja
Vedno upoštevajte naslednje varnostne ukrepe in predpise.
Za ravnanje z zunanjo enoto (glejte
OPOMIN
Da se izognete telesnim poškodbam, se NE dotikajte dovoda zraka ali aluminijastih
reber na enoti.
Nameščanje enote (glejte
"6Montaža enote"[426]
OPOZORILO
Montažo mora izvesti monter, izbira materialov in montaža pa morata ustrezati
veljavni zakonodaji. Zadevni standard za Evropo je EN378.
Mesto nameščanja (glejte
"6.1Priprava mesta namestitve"[426]
OPOMIN
▪ Preverite, ali lahko mesto namestitve prenese težo enote. Neprimerna montaža
je nevarna. Lahko povzroči tudi vibracije in nenavadne zvoke med delovanjem.
▪ Poskrbite, da bo dovolj prostora za vzdrževanje.
▪ Enote NE nameščajte tako, da bo v stiku s stropom ali steno, saj to lahko povzroči
vibracije.
"4.2.2Prenašanje zunanje enote"[423]
)
)
)
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro
prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (npr.: odprtega
plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega
mora biti prostor v izmeri, navedeni v Splošnih varnostnih ukrepih.
Odpiranje enote (glejte
"6.2Odpiranje enote"[430]
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Povezovanje cevi za hladivo (glejte
OPOMIN
Cevi in spoji sistema split morajo biti narejeni s stalnimi spoji, ko so v zasedenem
prostoru, razen če so to spoji, ki povezujejo neposredno cevi z notranjimi enotami.
)
"7.2Povezovanje cevi za hladivo"[435]
)
Vodnik za monterja
16
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
3 | Specifična varnostna navodila za monterja
OPOMIN
▪ Enot, ki so pri pošiljanju že napolnjene s hladivom R32, ne smete spajkati ali variti
na mestu namestitve.
▪ Med nameščanjem hladilnega sistema morate pri spajanju delov, pri katerem je
vsaj v enem delu že hladivo, upoštevati naslednje zahteve: v obljudenih prostorih
niso dovoljeni nepermanentni spoji za hladivo R32, razen za spoje, ki jih na mestu
namestitve neposredno na notranjo enoto za priključevanje cevi. Spoji, narejeni
na mestu namestitve za neposredno povezovanje cevi na notranje enote, morajo
biti nepermanentnega tipa.
OPOMIN
▪ Uporabite holandsko matico, pritrjeno na enoto.
▪ Da bi preprečili uhajanje plina, hladilno olje nanesite samo na notranjo površino
razširitve. Uporabite hladilno olje za R32.
▪ Spojev NE uporabljajte znova.
OPOMIN
▪ V delu z razširitvijo NE uporabljajte mineralnih olj.
▪ NE smete uporabiti cevi iz prejšnjih namestitev.
▪ Da bi zagotovili dobo uporabnosti te enote R32, vanjo NIKOLI ne vstavljajte sušila.
Sušilni material se lahko raztopi in poškoduje sistem.
OPOZORILO
Varno povežite cevi za hladivo, preden zaženete kompresor. Če cevi za hladivo niso
priključene in je zaustavitveni ventil ob zagonu kompresorja odprt, se bo vanj vsesal
zrak, kar bo povzročilo previsok pritisk v zanki hladilnega sredstva, kar lahko povzroči
škodo na opremi ali poškodbe oseb.
OPOMIN
▪ Nepopolna razširitev lahko povzroči iztekanje hladiva.
▪ Priviha NE smete ponovno uporabiti. Uporabite nove razširitve, da preprečite
uhajanje plinastega hladiva.
▪ Uporabite holandske matice, ki so priložene enoti. Uporaba drugačnih holandskih
matic lahko povzroči puščanje plinastega hladiva.
OPOMIN
NE odpirajte ventilov, preden dokončate razširitev. To bi povzročilo puščanje
plinastega hladiva.
NEVARNOST: NEVARNOST EKSPLOZIJE
Enote NE zaženite, dokler ni ustvarjen vakuum.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
17
3 | Specifična varnostna navodila za monterja
Dolivanje hladiva (glejte
OPOZORILO
Hladivo v enoti je blago vnetljivo, vendar navadno NE pušča. Če hladivo uhaja v
prostor in pride v stik z ognjem z gorilnika, grelca ali štedilnika, lahko pride do požara
ali do nastajanja škodljivega plina.
Izključite vse vnetljive grelne naprave, prostor prezračite in stopite v stik s
prodajalcem, pri katerem ste kupili enoto.
Enote ne uporabljajte, dokler serviser ne potrdi, da je bil del, iz katerega je puščalo
hladivo, popravljen.
OPOZORILO
▪ Za hladivo uporabljajte samo R32. Druge snovi lahko povzročijo eksplozije in
nesreče.
▪ R32 vsebuje fluorirane toplogredne pline. Njegova vrednost potenciala
globalnega segrevanja (GWP) je 675. Teh plinov NE izpuščajte v ozračje.
▪ Pri točenju hladiva vedno uporabljajte zaščitne rokavice in zaščitna očala.
OPOMIN
Da preprečite okvaro kompresorja, NE točite večje količine hladiva od predpisane.
"8Polnjenje s hladivom"[444]
)
OPOZORILO
Nikoli se z golo kožo ne dotaknite ponesreči razlitega hladiva. To bi lahko povzročilo
rane zaradi ozeblin.
Nameščanje električnih sestavnih delov (glejte
OPOZORILO
▪ Ožičenje MORA v celoti opraviti pooblaščen električar, izvedba pa MORA ustrezati
veljavni zakonodaji.
▪ Izdelajte električne priključke na fiksno ožičenje.
▪ Vse komponente, ki se priskrbijo na mestu vgradnje, in vse električne napeljave
MORAJO biti skladne z veljavno zakonodajo.
OPOZORILO
▪ Če N-faza ni priključena ali pa je napačno priključena, lahko to povzroči okvaro
opreme.
▪ Vzpostavite primerno ozemljitev. Enote NE ozemljujte s pomočjo komunalne cevi,
prenapetostnega odvodnika ali telefonskega ozemljitvenega kabla. Nepopolna
ozemljitev lahko povzroči električni udar.
▪ Vgradite zahtevane varovalke ali odklopnike.
▪ Pritrdite električno ožičenje z vezicami za kable, tako da se kabli NE dotikajo ostrih
robov ali cevi, zlasti na strani visokega tlaka.
▪ NE uporabljajte sestavljenih vodnikov, pletenih žičnih vodnikov, podaljševalnih
kablov ali povezav iz zvezdišča. To lahko povzroči pregrevanje, električni udar ali
požar.
▪ NE nameščajte kondenzatorja za fazni premik, saj je ta enota opremljena z
inverterjem. Kondenzator za fazni premik bo zmanjšal zmogljivost in lahko
povzroči nesreče.
"9Električna napeljava"[448]
)
Vodnik za monterja
18
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
3 | Specifična varnostna navodila za monterja
OPOZORILO
Za napajalne kable VEDNO uporabite večžilni kabel.
OPOZORILO
Uporabite prekinjalo za odklop vseh polov z vsaj 3mm med kontaktnimi točkovnimi
režami, ki omogočajo popolni odklop v III. kategoriji previsoke napetosti.
OPOZORILO
Če je napajalni kabel poškodovan, ga MORAJO proizvajalec, serviser ali podobno
usposobljena oseba zamenjati, da ne bi prišlo do nevarne situacije.
OPOZORILO
NE povezujte napajalnega kabla na notranjo enoto. To lahko povzroči električni udar
ali požar.
OPOZORILO
▪ V enoto ne nameščajte električnih delov, kupljenih v lokalni trgovini.
▪ NE razpeljujte napajanja za odvodno črpalko itd. s priključnega bloka. To lahko
povzroči električni udar ali požar.
OPOZORILO
Pazite, da bodo kabli za medsebojne povezave stran od bakrenih cevi brez
termoizolacije, saj se te cevi zelo segrejejo.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Vsi električni deli (vključno s termistorji) se napajajo iz napajalnega omrežja. Ne
dotikajte s jih z golimi rokami.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Odklopite napajanje za več kot 10minut ter izmerite napetost na priključnih sponkah
kondenzatorjev glavnega tokokroga ali električnih sestavnih delih, preden začnete
servisiranje. Napetost mora biti nižja od 50 V DC, preden se lahko dotaknete
električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno shemo.
Končevanje nameščanja notranje enote (glejte
zunanje enote"[453]
)
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Prepričajte se, da je sistem ustrezno ozemljen.
▪ Pred servisiranjem izklopite napajanje.
▪ Namestite pokrov stikalne omarice, preden vključite napajanje.
"10Zaključevanje montaže
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Predaja v uporabo (glejte
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
"12Zagon"[455]
)
Vodnik za monterja
19
3 | Specifična varnostna navodila za monterja
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOMIN
Preizkusnega delovanja ne izvajajte med delom na notranjih enotah.
Ko izvajate preizkušanje, bodo delovale tudi priključene notranje enote, ne le zunanja
enota. Delo na notranji enoti med preizkušanjem je nevarno.
OPOMIN
Ne vtikajte prstov, paličic ali drugih predmetov v vstopno ali izstopno zračno
odprtino. NE odstranjujte varovalne rešetke ventilatorja. Ker se ventilator vrti zelo
hitro, lahko povzroči poškodbe.
Vzdrževanje in servisiranje (glejte
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOZORILO
▪ Preden pričnete z izvajanjem vzdrževanja ali popravila, vedno izklopite odklopnik
na napajalni plošči, odstranite varovalke oz. odprite zaščitne naprave enote.
▪ Ne dotikajte se delujočih delov 10 min po izključitvi napajanja, saj obstaja
možnost visoke napetosti.
▪ Pazite, ker je nekaj delov električne omarice izjemno vročih.
▪ Pazite, da se ne boste dotaknili prevodnega dela.
▪ NE izpirajte enote. To bi lahko povzročilo električni udar ali požar.
O kompresorju
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Kompresor uporabljajte le v ozemljenem sistemu.
▪ Izključite napajanje pred servisiranjem.
▪ Spet pritrdite pokrov stikalne omarice in servisni pokrov po servisiranju.
"14Vzdrževanje in servisiranje"[459]
)
Vodnik za monterja
20
OPOMIN
vedno uporabljajte zaščitna očala in rokavice.
NEVARNOST: NEVARNOST EKSPLOZIJE
▪ Uporabite cevni rezalnik, da bi odstranili kompresor.
▪ NE uporabljajte plamenskega spajkalnika.
▪ Uporabite le odobrena hladiva in maziva.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Kompresorja se Ne dotikajte z golimi rokami.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
3 | Specifična varnostna navodila za monterja
Odpravljanje težav (glejte
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOZORILO
▪ Ko pregledujete stikalno omarico enote, VEDNO preverite, ali je enota
odklopljena iz omrežnega napajanja. Izklopite ustrezen odklopnik.
▪ Če se je aktivirala varnostna naprava, zaustavite enoto in ugotovite vzrok za njeno
aktiviranje, preden jo ponastavite. NIKOLI ne zaobidite varnostnih naprav in ne
spreminjajte njihovih vrednosti na vrednost, ki se razlikuje od tovarniške
nastavitve. Če ne morete ugotoviti vzroka težave, pokličite svojega prodajalca.
OPOZORILO
Preprečite nevarnosti zaradi nehotene ponastavitve termičnega odklopa: napajanje
te naprave NE SME biti izvedeno preko zunanjega preklopnika, denimo časovnika, in
naprava ne sme biti priključena na tokokrog, ki ga vzdrževanje redno vklaplja in
izklaplja.
"15Odpravljanje težav"[461]
)
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Ko enota ne deluje, so svetleče diode na tiskanem vezju izključene zaradi
varčevanja z energijo.
▪ Tudi ko so svetleče diode izključene, sta priključna sponka in tiskano vezje lahko
pod napetostjo.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
21
4 | O škatli
2
1
3
4 O škatli
4.1 Pregled: O škatli
To poglavje opisuje, kaj morate narediti, potem ko vam dostavijo škatlo z zunanjo
enoto.
Vedno imejte v mislih naslednje:
▪ Ob dobavi je treba enoto NUJNO pregledati glede poškodb. Vsako poškodbo
MORATE takoj sporočiti prevoznikovemu agentu.
▪ Enoto postavite še zapakirano čim bližje mestu montaže, da bi preprečili
morebitne poškodbe med premikanjem.
▪ Ko upravljate enoto, upoštevajte naslednje:
Lomljivo, z enoto ravnajte pazljivo.
Enota naj bo postavljena pokonci, da se ne bi poškodovala.
▪ Vnaprej pripravite pot, po kateri nameravate vnesti enoto v prostor.
4.2 Zunanja enota
4.2.1 Razpakiranje zunanje enote
Vodnik za monterja
22
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
4.2.2 Prenašanje zunanje enote
1×1×1×1×1×
bcdae
Z zunanjo enoto ravnajte samo v skladu z naslednjim:
4 | O škatli
OPOMIN
Da se izognete telesnim poškodbam, se NE dotikajte dovoda zraka ali aluminijastih
reber na enoti.
Prepričajte se, da je enota postavljena na ravno podlago, da se ne bi poškodovala.
Če so aluminijaste platice enote zvite, jih poravnajte z glavnikom za platice (iz
lokalne dobave).
4.2.3 Odstranjevanje opreme iz zunanje enote
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
1Dvignite zunanjo enoto.
2Odstranite opremo iz spodnjega dela embalaže.
Vodnik za monterja
23
4 | O škatli
a Splošni varnostni ukrepi
b Priročnik za montažo zunanje enote
c Nalepka z informacijo o toplogrednih fluoriranih plinih
d Večjezična nalepka z informacijo o toplogrednih fluoriranih plinih
e Nalepka z informacijami o energiji
Vodnik za monterja
24
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
5 O enoti
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
5.1 Oznaka
OPOMBA
Če sočasno nameščate ali servisirate več enot, NE smete zamenjati servisnih plošč
med različnimi modeli.
5.1.1 Nazivna ploščica: zunanja enota
Mesto
5 | O enoti
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
25
6 | Montaža enote
6 Montaža enote
V tem poglavju
OPOZORILO
Montažo mora izvesti monter, izbira materialov in montaža pa morata ustrezati
veljavni zakonodaji. Zadevni standard za Evropo je EN378.
6.1Priprava mesta namestitve..................................................................................................................................................... 26
6.1.1Zahteve za namestitveno mesto za zunanjo enoto............................................................................................... 27
6.1.2Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih.................................................. 29
6.2.1O odpiranju enote .................................................................................................................................................. 30
6.2.2Odpiranje zunanje enote ....................................................................................................................................... 30
6.3Nameščanje zunanje enote .................................................................................................................................................... 30
6.3.1O nameščanju zunanje enote ................................................................................................................................ 30
6.3.2Varnostni ukrepi pri nameščanju zunanje enote................................................................................................... 31
6.3.4Montaža zunanje enote ......................................................................................................................................... 32
6.3.6Preprečevanje prevračanja zunanje enote ............................................................................................................ 32
6.1 Priprava mesta namestitve
Enote NE nameščajte na mesta, ki so pogosto v uporabi kot delovna mesta. Če
morate izvajati tudi gradbene posege (npr. brušenje, razbijanje zidov itd.), pri
katerih nastaja veliko prahu, MORATE enoto pokriti.
Izberite namestitveno mesto, ki omogoča dovolj prostora za prenos enote na
mesto namestitve in z njega.
OPOMIN
▪ Preverite, ali lahko mesto namestitve prenese težo enote. Neprimerna montaža
je nevarna. Lahko povzroči tudi vibracije in nenavadne zvoke med delovanjem.
▪ Poskrbite, da bo dovolj prostora za vzdrževanje.
▪ Enote NE nameščajte tako, da bo v stiku s stropom ali steno, saj to lahko povzroči
vibracije.
▪ Izberite mesto, kjer hrup zaradi delovanja ali izpust vročega/mrzlega zraka iz
enote ne bo nikogar motil.
▪ Zagotovite dovolj prostora okoli enote za servisiranje in kroženje zraka.
▪ Izogibajte se območjem, v katerih lahko uhaja plin ali izdelek.
▪ Namestite enote, napajalne kable in ožičenje za prenos vsaj 3 m stran od
televizijskih ali radijskih sprejemnikov, da bi se izognili motnjam. Odvisno od
radijskih valov tudi 3m lahko niso dovolj, da bi se preprečil šum.
Vodnik za monterja
26
OPOMBA
Predmetov, ki se ne smejo zmočiti, NE postavljajte pod notranjo in/ali zunanjo enoto.
Sicer lahko kondenziranje na enoti ali na ceveh za hladivo, umazanija v zračnem filtru
ali zamašitev odvodnih cevi povzročijo kapljanje in se lahko predmeti pod enoto
zamažejo ali poškodujejo.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
OPOZORILO
>150
>50
>300
(mm)
b
a
>100
>50
>150
>50
b
b
a
>100
b
a
a
b
a
>100
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro
prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (npr.: odprtega
plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega
mora biti prostor v izmeri, navedeni v Splošnih varnostnih ukrepih.
6.1.1 Zahteve za namestitveno mesto za zunanjo enoto
INFORMACIJA
Preberite tudi naslednje zahteve:
▪ "2Splošni varnostni ukrepi"[47].
▪ "7.1.3Dolžina cevi za hladivo in višinske razlike"[435].
Upoštevajte naslednja prostorska navodila:
6 | Montaža enote
a Izstopna zračna odprtina
b Vstop zraka
OPOMBA
Višina zidu na strani za iztok zunanje enote MORA biti ≤1200mm.
OPOMBA
▪ Enot NE nameščajte eno na drugo.
▪ Enote NE obešajte na strop.
Močni vetrovi (≥18km/h), ki pihajo proti izpustu zraka na zunanji enoti, povzročajo
skrajšanje delovnega cikla (vsesavanje izpustnega zraka). Posledice so lahko:
▪ poslabšanje delovne zmogljivosti;
▪ pogosta hitra zaledenitev pri ogrevanju;
▪ motnje v delovanju zaradi padca nizkega tlaka, ali povečanja visokega tlaka;
▪ lomljenje ventilatorja (če močan veter neprekinjeno piha v ventilator, se
ventilator lahko začne vrteti zelo hitro, dokler se ne polomi).
Če je izstop zraka izpostavljen vetru, priporočamo, da namestite pregrado.
Priporočamo, da zunanjo enoto namestite tako, da bo vstop zraka obrnjen proti
steni in NE neposredno izpostavljen vetru.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
27
6 | Montaža enote
b
a
b
c
b
c
a
a Pregrada
b Pretežna smer vetra
c Izstopna zračna odprtina
Enote NE nameščajte na naslednja mesta:
▪ Izogibajte se občutljivim mestom (npr. blizu spalnice), tako da hrup pri delovanju
ne bo povzročal nevšečnosti.
Opomba: Če je zvok izmerjen v dejanskih pogojih nameščanja, bo izmerjena
vrednost višja od stopnje zvočnega tlaka, navedene v poglavju Zvočni spekter v
knjižici s tehničnimi podatki, zaradi okoljskega hrupa in odbojev zvoka.
INFORMACIJA
Raven zvočnega tlaka je manj kot 70dBA.
▪ Na mestih, kjer so lahko v atmosferi pare mineralnih olj, razpšeno olje ali oljne
pare. Plastični deli lahko propadejo in odpadejo ter povzročijo puščanje vode.
Enote NI priporočljivo nameščati na naslednjih mestih, saj to lahko skrajša
življenjsko dobo enote:
▪ Kjer napetost močno niha
▪ V vozilih ali plovilih
▪ Kjer so prisotne kisle ali alkalne pare
Pri namestitvi na ob morski obali. Prepričajte se, da, zunanja enota NI neposredno
izpostavljena morskim vetrovom. Tako boste preprečili korozijo zaradi visoke
vsebnosti soli v zraku, ki bi lahko skrajšala življenjsko dobo enote.
Zunanjo enoto namestite stran od morskih vetrov.
Primer: Za stavbo.
Vodnik za monterja
28
Če je zunanja enota izpostavljena neposrednim morskim vetrovom, namestite
vetrno zaščito.
▪ Višina vetrne zaščite≥1,5×višina zunanje enote
▪ Ko nameščate vetrno zaščito, bodite pozorni na prostor, ki ga morate pustiti za
servisiranje.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
4P518023-11H – 2021.03
R32 serija split
6 | Montaža enote
a
b
c
d
c
d
a
b
c
c
d
a Morski veter
b Stavba
c Zunanja enota
d Vetrna zaščita
Zunanja enota je načrtovana samo za zunanjo namestitev ter za temperature v
naslednjih obsegih:
HlajenjeOgrevanje
–10~46°C DB–25~24°C DB
6.1.2 Dodatne zahteve za namestitveno mesto za zunanjo enoto v hladnih predelih
Zaščitite zunanjo enoto pred neposrednim sneženjem in pazite, da zunanja enota
ne bo NIKOLI zasnežena.
a Snežna streha ali lopa
b Podstavek
c Pretežna smer vetra
d Izstopna zračna odprtina
Priporočamo, da poskrbite za vsaj 150 mm prostora pod enoto (300 mm za
območja z veliko snega). Dodatno lahko poskrbite za to, da bo enota vsaj 100mm
nad maksimalno pričakovano višino zapadlega snega. Če je treba, naredite
podstavek. Za več podrobnosti glejte "6.3Nameščanje zunanje enote"[430].
V krajih z močnim sneženjem je zelo pomembno, da si izberete takšno mesto
montaže, kjer sneg NE BO vplival na delovanje enote. Če so možni snežni zameti,
pazite, da na tuljavo izmenjevalnika toplote sneg NE BO vplival. Če je to potrebno,
namestite pokrov za sneg ali lopo in podstavek.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
29
6 | Montaža enote
1×
2
2
1
6.2 Odpiranje enote
6.2.1 O odpiranju enote
6.2.2 Odpiranje zunanje enote
V določenih primerih morate enoto odpreti. Primer:
▪ Ko priključujete cevi za hladivo
▪ Pri priključevanju električnega ožičenja
▪ Pri vzdrževanju ali servisiranju enote
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Enote NE puščajte brez nadzora, če ste z nje odstranili servisni pokrov.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
6.3 Nameščanje zunanje enote
6.3.1 O nameščanju zunanje enote
Kdaj
Zunanjo in notranjo enoto je treba namestiti, preden se nanju priključijo cevi za
hladivo.
Vodnik za monterja
30
Običajen potek
Namestitev zunanje enote običajno obsega naslednje faze:
1Priprava montažne konstrukcije.
2Montaža zunanje enote.
3Priprava odvoda vode.
4Preprečevanje padca enote.
5Zaščita enote pred snegom in vetrom z namestitvijo snežne strehe in pregrad.
Glejte "6.1Priprava mesta namestitve"[426].
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
6.3.2 Varnostni ukrepi pri nameščanju zunanje enote
20 mm
330
524
211
(mm)
211
a
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
▪ "2Splošni varnostni ukrepi"[47]
▪ "6.1Priprava mesta namestitve"[426]
6.3.3 Priprava montažne konstrukcije
Preverite nosilnost in izravnanost namestitvenih temeljev, da enota ne bi
povzročala vibracij med delovanjem ali hrupa.
Uporabite antivibracijsko gumijasto podlogo (iz lokalne dobave) v primerih, kjer bi
se vibracije lahko prenesle na stavbo.
Enoto varno pritrdite s pomočjo temeljnih vijakov v skladu s sliko.
Pripravite 4 komplete temeljnih vijakov, matic in podložk M8 ali M10 (iz lokalne
dobave).
6 | Montaža enote
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
a 100mm nad pričakovano višino zapadlega snega
Vodnik za monterja
31
6 | Montaža enote
4× M8/M10
6.3.4 Montaža zunanje enote
6.3.5 Priprava drenaže
▪ Poskrbite za pravilno odvajanje kondenzata.
▪ Enoto namestite na podstavek, da zagotovite pravilno drenažo, ki bo preprečila
nabiranje ledu.
▪ Okoli temeljev pripravite drenažni kanal, v katerem se bodo zbirale odpadne
vode iz okolice enote.
▪ Preprečite prelivanje odvodne vode čez pohodno pot, da pot ne bi postala
spolzka v primeru zunanjih temperatur pod lediščem.
▪ Če enoto nameščate na okvir, montirajte vodotesno ploščo na razdalji 150mm
od spodnje strani enote, da bi preprečili vdor vode v enoto in kapljanje odvodne
vode (glejte naslednjo ilustracijo).
OPOMBA
Če je enota nameščena v hladnem podnebju, naredite, kar je treba, da iztekajoči
kondenzat NE bo mogel zmrzniti.
INFORMACIJA
Za informacije o razpoložljivih možnostih se obrnite na svojega prodajalca.
6.3.6 Preprečevanje prevračanja zunanje enote
Vodnik za monterja
32
Če je enota nameščena na mestu, kjer bi jo lahko močan veter nagnil ali prevrnil,
izvedite naslednje varnostne ukrepe:
1Pripravite 2 kabla, kot je prikazano na naslednji risbi (iz lokalne dobave).
2Postavite 2 kabla čez zunanjo enoto.
3Med kabla in zunanjo enoto vstavite plast gume, da kabli ne bi opraskali barve
(iz lokalne dobave).
4Pritrdite končnike kablov.
5Zategnite kable.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
6 | Montaža enote
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
33
7 | Montaža cevi
t
Ø
7 Montaža cevi
V tem poglavju
7.1Priprava cevi za hladivo .......................................................................................................................................................... 34
7.1.1Zahteve za cevi za hladivo ...................................................................................................................................... 34
7.1.2Izolacija cevi za hladivo .......................................................................................................................................... 35
7.1.3Dolžina cevi za hladivo in višinske razlike .............................................................................................................. 35
7.2Povezovanje cevi za hladivo ................................................................................................................................................... 35
7.2.1O priključevanju cevi za hladivo ............................................................................................................................. 35
7.2.2Varnostni ukrepi pri priključevanju cevi za hladivo ............................................................................................... 36
7.2.3Navodila pri priključevanju cevi za hladivo ............................................................................................................ 37
7.2.4Napotki za upogibanje cevi .................................................................................................................................... 38
7.2.5Robljenje konca cevi............................................................................................................................................... 38
7.2.6Uporaba zapornega ventila in servisnega priključka ............................................................................................. 38
7.2.7Priključevanje cevi za hladivo na zunanjo enoto ................................................................................................... 40
7.3Preverjanje cevi za hladivo ..................................................................................................................................................... 40
7.3.1O preverjanju cevi za hladivo ................................................................................................................................. 40
7.3.2Napotki za varnost pri preverjanju cevi za hladivo................................................................................................ 41
Preberite tudi varnostne ukrepe in zahteve v "2Splošni varnostni ukrepi"[47].
OPOMIN
Cevi in spoji sistema split morajo biti narejeni s stalnimi spoji, ko so v zasedenem
prostoru, razen če so to spoji, ki povezujejo neposredno cevi z notranjimi enotami.
OPOMBA
Cevi in deli pod tlakom morajo ustrezati delovanju s hladivom. Uporaba fosforne
kisline deoksidira brezšivni baker za hladivo.
▪ Tujki v ceveh (vključno z olji za izdelovanje) smejo dosegati največ ≤30mg/10m.
Premer cevi za hladivo
Cevi za tekočineCevi za plin
Ø6,4mmØ9,5mm
Material cevi za hladivo
▪ Material za cevi: Fosforna kislina deoksidira brezšivni baker.
▪ Prirobnični spoji: Uporabljajte le kaljen material.
▪ Stopnja trdote materiala za cevi in debelina sten:
Outer diameter (Ø)Temper gradeThickness (t)
(a)
6.4mm (1/4")Annealed (O)≥0.8mm
9.5mm (3/8")Annealed (O)
Vodnik za monterja
34
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
(a)
ØiØ
i
t
ØpØ
p
Odvisno od veljavne zakonodaje in maksimalnega delovnega tlaka enote (glejte "PS High"
na identifikacijski ploščici enote) bodo morda potrebne širše cevi.
7.1.2 Izolacija cevi za hladivo
▪ Za izolacijski material uporabite polietilensko peno:
- s toplotno prevodnostjo od 0,041 do 0,052W/mK (od 0,035 do 0,045kcal/mh
°C),
- s toplotno obstojnostjo najmanj 120°C.
▪ Debelina izolacije
7 | Montaža cevi
Zunanji premer cevi (Øp)Notranji premer izolacije
6,4mm8~10mm≥10mm
9,5mm10~14mm≥13mm
Če je temperatura višja od 30°C in je vlažnost višja od RH80%, mora biti debelina
izolativnega materiala vsaj 20mm, da se prepreči nastajanje kondenzata na površju
izolacije.
7.1.3 Dolžina cevi za hladivo in višinske razlike
Kaj?Razdalja
Maksimalna dovoljena dolžina cevi20m
Minimalna dovoljena dolžina cevi1,5m
Maksimalna dovoljena višinska razlika15m
Debelina izolacije (t)
(Øi)
7.2 Povezovanje cevi za hladivo
OPOMIN
▪ Enot, ki so pri pošiljanju že napolnjene s hladivom R32, ne smete spajkati ali variti
na mestu namestitve.
▪ Med nameščanjem hladilnega sistema morate pri spajanju delov, pri katerem je
vsaj v enem delu že hladivo, upoštevati naslednje zahteve: v obljudenih prostorih
niso dovoljeni nepermanentni spoji za hladivo R32, razen za spoje, ki jih na mestu
namestitve neposredno na notranjo enoto za priključevanje cevi. Spoji, narejeni
na mestu namestitve za neposredno povezovanje cevi na notranje enote, morajo
biti nepermanentnega tipa.
7.2.1 O priključevanju cevi za hladivo
Pred priključevanjem cevi za hladivo
Prepričajte se, da sta zunanja in notranja enota nameščeni.
Običajen potek
Priključevanje cevi za hladivo zajema:
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
35
7 | Montaža cevi
7.2.2 Varnostni ukrepi pri priključevanju cevi za hladivo
▪ Priključevanje cevi za hladivo na notranjo enoto
▪ Priključevanje cevi za hladivo na zunanjo enoto
▪ Izoliranje cevi za hladivo
▪ Upoštevajte navodila za:
- Upogibanje cevi
- Izdelavo razširitev na koncih cevi
- Uporabo zapornih ventilov
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
▪ "2Splošni varnostni ukrepi"[47]
▪ "7.1Priprava cevi za hladivo"[434]
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOMIN
▪ Uporabite holandsko matico, pritrjeno na enoto.
▪ Da bi preprečili uhajanje plina, hladilno olje nanesite samo na notranjo površino
razširitve. Uporabite hladilno olje za R32.
▪ Spojev NE uporabljajte znova.
OPOMIN
▪ V delu z razširitvijo NE uporabljajte mineralnih olj.
▪ NE smete uporabiti cevi iz prejšnjih namestitev.
▪ Da bi zagotovili dobo uporabnosti te enote R32, vanjo NIKOLI ne vstavljajte sušila.
Sušilni material se lahko raztopi in poškoduje sistem.
OPOMBA
Pri napeljavi cevi za hladivo ravnajte v skladu z naslednjimi varnostnimi ukrepi:
▪ Pazite, da v krog hladiva razen predpisanega hladiva ne vstopijo nobene druge
snovi (npr. zrak).
▪ Pri dodajanju hladiva uporabljajte samo R32.
▪ Uporabljajte samo montažno orodje (npr. komplet z manometrskim priključkom),
ki je zasnovano posebej za napeljavo R32 in je tlačno obstojno, da bi preprečili, da
se tuje snovi (npr. mineralno olje in vlaga) primešajo v sistem.
▪ Cevi montirajte tako, da razširitev NE bo izpostavljena mehanski obremenitvi.
▪ Cevi zaščitite, kot je opisano v naslednji tabeli, da bi preprečili vstop umazanije,
tekočine ali prahu v cevi.
▪ Bodite previdni pri napeljavi bakrenih cevi skozi stene (glejte naslednjo sliko).
Vodnik za monterja
36
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
7 | Montaža cevi
a
b
c
d
R=
0.4~0.8
±2
45°
90°
±2
ØA
EnotaNamestitveno obdobjeNačin zaščite
Zunanja enota>1mesecZatisnite cev
<1mesecZatisnite ali zalepite cev
Notranja enotaNe glede na obdobje
INFORMACIJA
Zapornega ventila za hladivo NE odpirajte, dokler ne preverite cevi za hladivo. Kadar
dodajate hladivo, priporočamo, da po polnjenju odprete zaporni ventil za hladivo.
OPOZORILO
Varno povežite cevi za hladivo, preden zaženete kompresor. Če cevi za hladivo niso
priključene in je zaustavitveni ventil ob zagonu kompresorja odprt, se bo vanj vsesal
zrak, kar bo povzročilo previsok pritisk v zanki hladilnega sredstva, kar lahko povzroči
škodo na opremi ali poškodbe oseb.
7.2.3 Navodila pri priključevanju cevi za hladivo
Pri priključevanju cevi upoštevajte naslednje napotke:
▪ Ko priključujete holandsko matico, premažite razširitev z notranje strani z etrskim
ali esterskim oljem. Privijte jo ročno za 3 ali 4 obrate, preden jo zategnete.
▪ Ko odvijate holandsko matico, VEDNO uporabljajte dva ključa hkrati.
▪ Ko priključujete cevi, za zategovanje holandske matice vedno uporabite sočasno
viličasti in momentni ključ. S tem boste preprečili pokanje matic in puščanje.
a Momentni ključ
b Viličasti ključ
c Cevna spojka
d Holandska matica
Premer cevi (mm)Navojni moment
(N•m)
Premer razširitve
(A) (mm)
Oblika razširitve
(mm)
Ø6,415~178,7~9,1
Ø9,533~3912,8~13,2
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
37
7 | Montaža cevi
ab
A
ab
c
7.2.4 Napotki za upogibanje cevi
7.2.5 Robljenje konca cevi
Za krivljenje cevi uporabite orodje za krivljenje cevi. Vse krivine cevi naj bodo kar se
da blage (polmer krivine naj bo 30~40mm ali večji).
OPOMIN
▪ Nepopolna razširitev lahko povzroči iztekanje hladiva.
▪ Priviha NE smete ponovno uporabiti. Uporabite nove razširitve, da preprečite
uhajanje plinastega hladiva.
▪ Uporabite holandske matice, ki so priložene enoti. Uporaba drugačnih holandskih
matic lahko povzroči puščanje plinastega hladiva.
1Odrežite konec cevi z rezalnikom za cevi.
2Odstranite srh z roba cevi in jo pri tem držite obrnjeno navzdol, tako da opilki
NE zaidejo v cev.
a Režite točno pod pravim kotom.
b Odstranite srh.
3Odstranite holandsko matico z zapornega ventila in jo namestite na cev.
4Zarobite cev. Postavite jo natanko v položaj, prikazan v naslednji sliki.
Orodje za robljenje
cevi za R32 (sklopni tip)
Običajno orodje za razširitev cevi
Sklopni tip
(Tip Ridgid)
Tip s krilno matico
(Tip Imperial)
A0~0,5mm1,0~1,5mm1,5~2,0mm
5Preverite, ali je razširitev pravilno izvedena.
a Notranja površina razširitve MORA biti brezhibna.
b Konec cevi mora biti enakomerno zarobljen v popoln krog.
c Prepričajte se, da ste namestili holandsko matico.
7.2.6 Uporaba zapornega ventila in servisnega priključka
Vodnik za monterja
38
OPOMIN
NE odpirajte ventilov, preden dokončate razširitev. To bi povzročilo puščanje
plinastega hladiva.
Ravnanje z zapornim ventilom
Upoštevajte naslednje napotke:
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
7 | Montaža cevi
c
d
a
b
a
b
▪ Zaporni ventili so tovarniško zaprti.
▪ Naslednja slika prikazuje dele zapornega ventila, potrebne pri rokovanju z
ventilom.
a Servisni priključek in pokrov servisnega priključka
b Steblo ventila
c Priključek na cevi, nameščene na licu mesta
d Pokrovček stebla
▪ Oba zaporna ventila naj bosta med delovanjem odprta.
▪ Na steblo zapornega ventila ne delujte s preveliko silo. To bi lahko polomilo
ohišje ventila.
▪ Zaporni ventil morate VEDNO priviti z viličastim ključem, in nato odviti ali priviti
holandsko matico z momentnim ključem. Viličastega ključa NE postavljajte na
pokrov stebla ventila, ker bi s tem lahko povzročili uhajanje hladiva.
a Viličasti ključ
b Momentni ključ
▪ Če pričakujete nizek delovni tlak (npr. kadar se bo pri nizki zunanji temperaturi
izvajalo hlajenje), v zadostni meri zatesnite holandsko matico na zapornem
ventilu na plinskem vodu s silikonskim tesnilom, da bi preprečili zamrznitev.
V nasprotni smeri urinega kazalca za odpiranje
V smeri urinega kazalca za zapiranje
3Ko zapornega ventila ni več mogoče vrteti, se zaustavite.
4Namestite pokrov zapornega ventila.
Rezultat: Ventil je zdaj odprt/zaprt.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
39
7 | Montaža cevi
a
bc
Ravnanje s pokrovom stebla ventila
▪ Pokrov stebla ventila je zatesnjen na mestu, ki ga prikazuje puščica. NE
poškodujte ga.
▪ Po delu z zapornim ventilom privijte pokrov stebla in preverite puščanje
hladilnega sredstva.
Pokrovček steblaŠirina ploščatega ključa
Visokotlačni del (tekočina)1715~17
Nizkotlačni del (plin)2221~28
Ravnanje s servisnim pokrovom
▪ Vedno uporabljajte cev za polnjenje, opremljeno z zatičem za zniževanje tlaka, saj
je to servisni priključek za ventil tipa Schrader.
▪ Po delu s servisnim priključkom zategnite pokrovček servisnega priključka in
preverite, ali kje pušča hladivo.
ElementNavojni moment (N•m)
Pokrov servisnega priključka11~14
7.2.7 Priključevanje cevi za hladivo na zunanjo enoto
▪ Dolžine cevi. Cev na mestu namestitve naj bodo kolikor je mogoče kratke.
▪ Zaščita cevi. Zaščitite cevi na mestu namestitve pred fizičnimi poškodbami.
1Priključite priključek notranje enote za hladivo v tekočem stanju na zaporni
ventil zunanje enote za tekočino.
Navojni moment (N•m)
(mm)
Vodnik za monterja
40
a Zaporni ventil za tekočino
b Zaporni ventil za plin
c Servisni priključek
2Priključite priključek za plin notranje enote na zaporni ventil za plin zunanje
enote.
OPOMBA
Priporočamo, da cevi za hladivo med notranjo in zunanjo enoto namestite v kanal ali
da cevi za hladivo ovijete z zaključnim trakom.
7.3 Preverjanje cevi za hladivo
7.3.1 O preverjanju cevi za hladivo
Notranje cevi za hladivo v zunanji enoti so tovarniško preizkušene glede puščanja.
Preveriti morate samo zunanje cevi za hladivo zunanje enote.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Pred preverjanjem cevi za hladivo
Cev za hladivo mora biti priključena med zunanjo in notranjo enoto.
Običajen potek
Preverjanje cevi za hladivo običajno obsega naslednje faze:
1preverjanje, ali cevi za hladivo puščajo, in
2izvajanje vakuumskega praznjenja, da odstranite vso tekočino iz cevi za hladivo.
Če je možno, da je vlaga v ceveh za hladivo (na primer če vanje zaide voda), najprej
izvedite postopek vakuumskega sušenja, tako da odstranite vso vlago.
7.3.2 Napotki za varnost pri preverjanju cevi za hladivo
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
▪ "2Splošni varnostni ukrepi"[47]
▪ "7.1Priprava cevi za hladivo"[434]
OPOMBA
Uporabite 2-stopenjsko vakuumsko črpalko z nepovratnim ventilom, ki lahko sistem
izprazni do tlaka na manometru −100,7kPa (−1,007 bar) (5Torr absolutno). Pazite,
da olje črpalke ne bo teklo v nasprotni smeri v sistem, kadar črpalka ne deluje.
7 | Montaža cevi
7.3.3 Preverjanje puščanja
OPOMBA
To vakuumsko črpalko uporabljajte izključno za R32. Uporaba iste črpalke za druga
hladiva lahko povzroči poškodbe črpalke in enote.
OPOMBA
▪ Priključite vakuumsko črpalko na servisni priključek plinskega zapornega ventila.
▪ Pazite, da bosta plinski zaporni ventil in tekočinski zaporni ventil tesno zaprta,
preden izvajate preizkus tesnjenja ali vakuumsko praznjenje.
OPOMBA
NE smete preseči maksimalnega delovnega tlaka enote (glejte “PS High” na nazivni
ploščici enote).
OPOMBA
VEDNO uporabite priporočeno raztopino za preverjanje puščanja, ki jo dobite pri
svojem dobavitelju.
NIKOLI ne uporabljajte milnice:
▪ Milnica lahko povzroči razpoke na komponentah, kot so holandske matice in
pokrovi zapornih ventilov.
▪ Milnica lahko vsebuje sol, ki bo vpila vlago, ki bo zamrznila, ko se cevi shladijo.
▪ Milnica vsebuje amoniak, ki lahko povzroči korozijo razširjenih spojev (med
medeninasto in bakreno holandsko matico).
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
41
7 | Montaža cevi
ihj
abc
h
k
d
f
f
e
g
7.3.4 Vakuumsko praznjenje
1Sistem napolnite z dušikovim plinom, do tlaka na manometru najmanj 200kPa
(2 bar). Priporočamo, da zaradi prepoznavanja manjših puščanj vzpostavite
tlak 3000kPa (30barov).
2Tesnjenje preizkusite tako, da na vse povezave nanesete testno raztopino, ki
se peni.
3Izpustite ves dušikov plin.
NEVARNOST: NEVARNOST EKSPLOZIJE
Enote NE zaženite, dokler ni ustvarjen vakuum.
Priključite vakuumsko črpalko in zbiralnik, kot sledi:
a Merilni instrument za prenizek tlak
b Zbiralnik manometra
c Merilni instrument za previsok tlak
d Nizkotlačni ventil (Lo)
e Visokotlačni ventil (Hi)
f Cevi za polnjenje
g Vakuumska črpalka
h Pokrovčki ventilov
i Servisni priključek
j Zaporni ventil za plin
k Zaporni ventil za tekočino
1Sistem praznite, dokler ni tlak na manometru −0,1MPa (−1bar).
2Počakajte 4–5minut in preverite tlak:
Če tlak…Potem…
Se ne spremeniV sistemu ni vlage. Postopek je
končan.
NarasteV sistemu je vlaga. Pojdite na
naslednji korak.
3Vakuumsko praznjenje sistema izvajajte najmanj 2 uri, dokler ni tlak na
manometru −0,1MPa (−1bar).
4Tlak preverjajte še najmanj 1uro po izklopu črpalke.
5Če ciljnega vakuuma NE dosežete ali ga NE MORETE obdržati 1uro, naredite
naslednje:
▪ Znova preverite puščanje.
▪ Ponovite vakuumsko praznjenje.
Vodnik za monterja
42
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
7 | Montaža cevi
OPOMBA
Zagotovo odprite zaporni ventil, ko namestite cevi za hladivo in izvedete vakuumsko
sušenje. Če boste sistem pognali, ko bodo zaporni ventili zaprti, se lahko kompresor
pokvari.
INFORMACIJA
Ko odprete zaporni ventil, se tlak v cevni napeljavi hladiva morda NE bo zvišal. To
lahko povzroči npr. zaprt ekspanzijski ventil v krogotoku zunanje enote, vendar to NE
ovira pravilnega delovanja enote.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
43
8 | Polnjenje s hladivom
8 Polnjenje s hladivom
V tem poglavju
8.1 O polnjenju s hladivom
8.1O polnjenju s hladivom........................................................................................................................................................... 44
8.3Varnostni ukrepi pri polnjenju s hladivom ............................................................................................................................. 46
8.4Določanje dodatne količine hladiva ....................................................................................................................................... 46
8.5Določanje celotne količine ponovnega polnjenja .................................................................................................................. 46
8.7Pritrjevanje nalepke o fluoriranih toplogrednih plinih .......................................................................................................... 47
Zunanja enota je tovarniško napolnjena s hladivom, vendar je v nekaterih primerih
morda potrebno naslednje:
KajKdaj
Dolivanje dodatnega hladivaKo je skupna dolžina cevi večja od
določene (glejte v nadaljevanju).
Polnjenje celotnega hladivaPrimer:
▪ Pri selitvi sistema.
▪ Po puščanju.
Dolivanje dodatnega hladiva
Prepričajte se, da so bile zunanje cevi za hladivo zunanje enote pregledane
(preizkus tesnosti, vakuumsko sušenje).
INFORMACIJA
Odvisno od enot in/ali od pogojev nameščanja bo morda treba povezati električno
ožičenje, preden lahko napolnite hladivo.
Običajni potek dela – Dolivanje dodatnega hladiva navadno sestoji iz naslednjih
stopenj:
1Določanje, ali je treba doliti hladivo in koliko.
2Če je to potrebno, doliti dodatno hladivo.
3Izpolnjevanje nalepke z informacijo o toplogrednih fluoriranih plinih in
prilepljanje nalepke na notranjo stran zunanje enote.
Polnjenje celotnega hladiva
Vodnik za monterja
44
Pred polnjenjem celotnega hladiva se prepričajte, da je bilo narejeno naslednje:
1Vse hladivo je bilo izčrpano iz sistema.
2Zunanje cevi za hladivo zunanje enote so bile pregledane (preizkus tesnosti,
vakuumsko sušenje).
3Vakuumsko sušenje notranjih cevi za hladivo zunanje enote je bilo izvedeno.
OPOMBA
Pred vnovičnim polnjenjem s hladivom opravite tudi vakuumsko praznjenje notranje
cevi za hladivo v zunanji enoti.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
8.2 O hladivu
8 | Polnjenje s hladivom
Običajni potek dela – Polnjenje celotnega hladiva navadno sestoji iz naslednjih
stopenj:
1Določanje, koliko hladiva doliti.
2Polnjenje s hladivom.
3Izpolnjevanje nalepke z informacijo o toplogrednih fluoriranih plinih in
prilepljanje nalepke na notranjo stran zunanje enote.
Izdelek vsebuje fluorirane toplogredne pline. Plinov NE izpuščajte v ozračje.
Tip hladiva: R32
Vrednost potenciala globalnega segrevanja (GWP): 675
OPOZORILO: BLAGO VNETLJIV MATERIAL
Hladivo v enoti je blago vnetljivo.
OPOZORILO
Naprava mora biti skladiščena tako, da se prepreči mehanske poškodbe, in v dobro
prezračenem prostoru, kjer ni neprestano prisotnih virov vžiga (npr.: odprtega
plamena, delujoče naprave na plin ali delujočega električnega grelnika). Poleg tega
mora biti prostor v izmeri, navedeni v Splošnih varnostnih ukrepih.
OPOZORILO
▪ NE luknjajte in ne sežigajte delov hladilnega kroga.
▪ NE uporabljajte čistilnih snovi ali sredstev za pospeševanje postopka
odmrzovanja, razen tistih, ki jih priporoča proizvajalec.
▪ Zavedajte se, da hladivo v sistemu nima nikakršnega vonja.
OPOZORILO
Hladivo v enoti je blago vnetljivo, vendar navadno NE pušča. Če hladivo uhaja v
prostor in pride v stik z ognjem z gorilnika, grelca ali štedilnika, lahko pride do požara
ali do nastajanja škodljivega plina.
Izključite vse vnetljive grelne naprave, prostor prezračite in stopite v stik s
prodajalcem, pri katerem ste kupili enoto.
Enote ne uporabljajte, dokler serviser ne potrdi, da je bil del, iz katerega je puščalo
hladivo, popravljen.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
OPOZORILO
Nikoli se z golo kožo ne dotaknite ponesreči razlitega hladiva. To bi lahko povzročilo
rane zaradi ozeblin.
Vodnik za monterja
45
8 | Polnjenje s hladivom
8.3 Varnostni ukrepi pri polnjenju s hladivom
8.4 Določanje dodatne količine hladiva
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v naslednjih poglavjih:
▪ "2Splošni varnostni ukrepi"[47]
▪ "7.1Priprava cevi za hladivo"[434]
Če je skupna dolžina cevi za
tekočino…
≤10mNE dodajajte hladiva.
>10mR=(skupna dolžina (m) tekočinskih cevi–10m)×0,020
R=dodatno polnjenje (kg) (zaokroženo na enote po
0,01kg)
INFORMACIJA
Dolžina cevi je dolžina tekočinskih cevi v eni smeri.
8.5 Določanje celotne količine ponovnega polnjenja
INFORMACIJA
Če je potrebno ponovno polnjenje, je skupna količina ponovnega polnjenja hladiva:
tovarniško polnjenje s hladivom (glejte nazivno ploščico enote) + ugotovljena
dodatna količina.
Potem…
8.6 Dolivanje dodatnega hladiva
Vodnik za monterja
46
OPOZORILO
▪ Za hladivo uporabljajte samo R32. Druge snovi lahko povzročijo eksplozije in
nesreče.
▪ R32 vsebuje fluorirane toplogredne pline. Njegova vrednost potenciala
globalnega segrevanja (GWP) je 675. Teh plinov NE izpuščajte v ozračje.
▪ Pri točenju hladiva vedno uporabljajte zaščitne rokavice in zaščitna očala.
OPOMIN
Da preprečite okvaro kompresorja, NE točite večje količine hladiva od predpisane.
Predpogoj: Pred polnjenjem s hladivom se prepričajte, da so cevi za hladivo
priključene in preverjene (preverjanje puščanja in vakuumsko izčrpavanje).
1Priključite vsebnik hladiva na servisni priključek.
2Natočite dodatno količino hladiva.
3Odprite zaporni ventil za plin.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
8 | Polnjenje s hladivom
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
Če je zaradi demontaže ali prestavljanja potrebno izčrpavanje sistema, za
podrobnosti glejte "16.2Izčrpavanje"[463].
8.7 Pritrjevanje nalepke o fluoriranih toplogrednih plinih
1Nalepko izpolnite na naslednji način:
a Če je z enoto dobavljena večjezična nalepka z informacijo o toplogrednih fluoriranih
plinih, odlepite del nalepke z ustreznim jezikom in ga nalepite na vrh a.
b Tovarniško polnjenje hladiva: glejte identifikacijsko ploščico enote
c Količina dodatno dolitega hladiva
d Skupno polnjenje hladiva
e Količina toplogrednih fluoriranih plinov skupnega polnjenja hladiva, izražena v
enakovrednih tonah CO2.
f GWP = potencial globalnega segrevanja
OPOMBA
Zadevna zakonodaja o toplogrednih fluoriranih plinih zahteva, da je polnitev hladiva
na enoti označena v teži in enakovredni vrednosti CO2.
Formula za izračun enakovredne vrednosti v tonah CO2: GWP vrednost hladiva ×
Skupno polnjenje hladiva [v kg] / 1000
Uporabite omenjeno vrednost GWP na nalepki za dolivanje hladiva.
2Nalepko prilepite v notranjščino zunanje enote poleg zapornih ventilov za plin
in tekočino.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
9.2Da bi povezali električno ožičenje na zunanjo enoto............................................................................................................. 51
Pred priključevanjem električnega ožičenja
Prepričajte se, da:
▪ So cevi za hladivo priključene in pregledane
▪ So vodovodne cevi priključene
Običajen potek
Priključevanje električnega ožičenja običajno obsega naslednje faze:
1Prepričajte se, da napajalni sistem ustreza električnim specifikacijam enot.
2Priključevanje električnega ožičenja na zunanjo enoto.
3Priključevanje električnega ožičenja na notranjo enoto.
4Priključitev glavnega napajanja.
9.1.1 Napotki za varnost pri priključevanju električnega ožičenja
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
OPOZORILO
Za napajalne kable VEDNO uporabite večžilni kabel.
INFORMACIJA
Preberite tudi varnostne ukrepe in zahteve v "2Splošni varnostni ukrepi"[47].
INFORMACIJA
Preberite tudi "9.1.3Specifikacije standardnih komponent ožičenja"[451].
Vodnik za monterja
48
OPOZORILO
▪ Ožičenje MORA v celoti opraviti pooblaščen električar, izvedba pa MORA ustrezati
veljavni zakonodaji.
▪ Izdelajte električne priključke na fiksno ožičenje.
▪ Vse komponente, ki se priskrbijo na mestu vgradnje, in vse električne napeljave
MORAJO biti skladne z veljavno zakonodajo.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
9 | Električna napeljava
OPOZORILO
▪ Če N-faza ni priključena ali pa je napačno priključena, lahko to povzroči okvaro
opreme.
▪ Vzpostavite primerno ozemljitev. Enote NE ozemljujte s pomočjo komunalne cevi,
prenapetostnega odvodnika ali telefonskega ozemljitvenega kabla. Nepopolna
ozemljitev lahko povzroči električni udar.
▪ Vgradite zahtevane varovalke ali odklopnike.
▪ Pritrdite električno ožičenje z vezicami za kable, tako da se kabli NE dotikajo ostrih
robov ali cevi, zlasti na strani visokega tlaka.
▪ NE uporabljajte sestavljenih vodnikov, pletenih žičnih vodnikov, podaljševalnih
kablov ali povezav iz zvezdišča. To lahko povzroči pregrevanje, električni udar ali
požar.
▪ NE nameščajte kondenzatorja za fazni premik, saj je ta enota opremljena z
inverterjem. Kondenzator za fazni premik bo zmanjšal zmogljivost in lahko
povzroči nesreče.
OPOZORILO
Uporabite prekinjalo za odklop vseh polov z vsaj 3mm med kontaktnimi točkovnimi
režami, ki omogočajo popolni odklop v III. kategoriji previsoke napetosti.
OPOZORILO
Če je napajalni kabel poškodovan, ga MORAJO proizvajalec, serviser ali podobno
usposobljena oseba zamenjati, da ne bi prišlo do nevarne situacije.
OPOZORILO
NE povezujte napajalnega kabla na notranjo enoto. To lahko povzroči električni udar
ali požar.
OPOZORILO
▪ V enoto ne nameščajte električnih delov, kupljenih v lokalni trgovini.
▪ NE razpeljujte napajanja za odvodno črpalko itd. s priključnega bloka. To lahko
povzroči električni udar ali požar.
OPOZORILO
Pazite, da bodo kabli za medsebojne povezave stran od bakrenih cevi brez
termoizolacije, saj se te cevi zelo segrejejo.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Vsi električni deli (vključno s termistorji) se napajajo iz napajalnega omrežja. Ne
dotikajte s jih z golimi rokami.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Odklopite napajanje za več kot 10minut ter izmerite napetost na priključnih sponkah
kondenzatorjev glavnega tokokroga ali električnih sestavnih delih, preden začnete
servisiranje. Napetost mora biti nižja od 50 V DC, preden se lahko dotaknete
električnih sestavnih delov. Za mesto priključnih sponk glejte vezalno shemo.
Vodnik za monterja
49
9 | Električna napeljava
DC+
DC-
h
cge d f
a
b
ba
c b
c
aa
A
AA´
A´
9.1.2 Napotki za priključevanje električnega ožičenja
a Multimeter (enosmerno napetostno območje)
b S80 – glavni vodnik navitja povratnega elektromagnetnega ventila
c S70 – glavni vodnik motorja ventilatorja
d Svetleča dioda
e S90 – glavni vodnik termistorja
f S20 – glavni vodnik elektronske ekspanzijske posode
g S40 – glavni vodnik termične preobremenitve
h DB1 - premostitev diode
Ves čas upoštevajte naslednje:
▪ Če uporabite večžilni vodnik, namestite cevni kabelski čeveljček z ušesom na
konec vodnika. Okrogle priključke z ušesom postavite na vodnike na pokritih delih
in pritrdite priključne sponke z ustreznim orodjem.
a Standardni vodnik
b Okrogla obrobljena ferula
▪ Pri nameščanju vodnikov uporabite naslednji postopek:
Tip vodnikaNačin montaže
Enožilni vodnik
a Spiralni enožilni vodnik
b Vijak
c Ploska podložka
Vodnik za monterja
50
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
9 | Električna napeljava
c bbac
a
B
B
1-3
Tip vodnikaNačin montaže
Pleteni žični vodnik z
okroglim obrobljenim
priključkom
a Priključek
b Vijak
c Ploska podložka
Dovoljeno
NI dovoljeno
Navojni momenti
PredmetNavojni moment (N•m)
M4 (X1M)1,5~1,6
M4 (zemlja)1,4~1,5
▪ Ozemljitveni vodnik med zadrževalnikom vodnika in priključkom mora biti daljši
9.2 Da bi povezali električno ožičenje na zunanjo enoto
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
1Odstranite servisni pokrov. Glejte "6.2.2Odpiranje zunanje enote"[430].
2Odstranite izolacijo (20mm) z vodnikov.
Vodnik za monterja
51
9 | Električna napeljava
ab
50 Hz
220-240 V
cd
f
abe
3×
a Izolacijo odstranite do te točke
b Predolg ogoljeni del žice lahko povzroči električni šok ali uhajanje toka
3Odprite objemko za kabel.
4Priključite kabel za medsebojno povezavo in napajanje na naslednji način:
a Kabel za medsebojno povezavo
b Kabel za električno napajanje
c Prekinjalo vezja
d Naprava za tokovni ostanek
e Napajanje
f Ozemljitev
5Dobro privijte vijake priključkov. Priporočamo uporabo križnega izvijača.
Vodnik za monterja
52
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
4P518023-11H – 2021.03
R32 serija split
10 | Zaključevanje montaže zunanje enote
g
b
a
f
e
cd
1×
1
1
2
10 Zaključevanje montaže zunanje enote
10.1 Zaključevanje montaže zunanje enote
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Prepričajte se, da je sistem ustrezno ozemljen.
▪ Pred servisiranjem izklopite napajanje.
▪ Namestite pokrov stikalne omarice, preden vključite napajanje.
OPOMBA
Priporočamo, da cevi za hladivo med notranjo in zunanjo enoto namestite v kanal ali
da cevi za hladivo ovijete z zaključnim trakom.
1Izolirajte in pritrdite cevi za hladivo in kable, kot sledi:
2Namestite servisni pokrov.
10.2 Zapiranje enote
10.2.1 Zapiranje zunanje enote
a Cev za hladivo v plinastem stanju
b Izolacija cevi za hladivo v plinastem stanju
c Kabel za medsebojno povezavo
d Zunanje ožičenje (če je na voljo)
e Cev za hladivo v tekočem stanju
f Izolacija cevi za hladivo v tekočem stanju
g Ovojni trak
OPOMBA
Ko zapirate pokrov zunanje enote, pazite, da pritezni moment NE bo večji od
1,3N•m.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
53
11 | Konfiguracija
1
2
3
J5
J6
J8
J9
J11
J12
+6V
R714
R713
R712
R711
R710
R721
R612
R613
D204
D202
C207
D203
ID201
C211
D206
J12
J11
J9
J8
J6
J5
11 Konfiguracija
11.1 Nastavitev obrata
11.1.1 Nastavitev načina obrata
To funkcijo uporabite za hlajenje pri nizki zunanji temperaturi. Ta funkcija je
načrtovana za obrate, kot so strežniške sobe. NIKOLI jih ne uporabljajte v
stanovanjskih prostorih ali pisarnah, kjer se zadržujejo ljudje.
Ko prerežete mostiček J6 na tiskanem vezju, se bo delovno območje razširilo do –
15°C. Infrastrukturni način delovanja se bo samodejno izklopil, če bo temperatura
padla pod –20°C, in se bo samodejno zagnal, ko se bo temperatura spet dvignila.
INFORMACIJA
▪ Notranja enota lahko občasno proizvaja zvoke zaradi vklapljanja in izklapljanja
ventilatorja zunanje enote.
▪ Ko uporabljate infrastrukturni način delovanja, v prostoru NE uporabljajte
vlažilnikov ali elementov, ki bi lahko povečali vlažnost v prostoru.
▪ Ko prerežete mostiček J6, nastavite ventilator notranje enote na največjo možno
hitrost.
▪ Te nastavitve NE uporabljajte v prebivališčih ali pisarnah, kjer se zadržujejo ljudje.
12.2Varnostni ukrepi pri začetku uporabe.................................................................................................................................... 55
12.3Seznam preverjanj pred zagonom.......................................................................................................................................... 56
12.4Seznam preverjanj med zagonom.......................................................................................................................................... 56
12.6Zagon zunanje enote.............................................................................................................................................................. 57
12.1 Pregled: zagon
12 | Zagon
OPOMBA
Splošni kontrolni seznam za zagon. Poleg navodil za zagon v tem poglavju je v
spletišču Daikin Business Portal (potrebna je prijava) na voljo splošni kontrolni
seznam za zagon.
Splošni kontrolni seznam za zagon je dopolnilo navodilom v tem poglavju in se lahko
uporabi kot smernica ter predloga za poročanje med zagonom in predajo
uporabniku.
To poglavje opisuje, kaj morate narediti in vedeti, da poženete sistem, potem ko je
bil nameščen.
Običajen potek
Zagon običajno obsega naslednje faze:
1Preverjanje "Seznama preverjanj pred začetkom uporabe".
2Izvajanje preizkusa delovanja sistema.
12.2 Varnostni ukrepi pri začetku uporabe
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
OPOMIN
Preizkusnega delovanja ne izvajajte med delom na notranjih enotah.
Ko izvajate preizkušanje, bodo delovale tudi priključene notranje enote, ne le zunanja
enota. Delo na notranji enoti med preizkušanjem je nevarno.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
OPOMIN
Ne vtikajte prstov, paličic ali drugih predmetov v vstopno ali izstopno zračno
odprtino. NE odstranjujte varovalne rešetke ventilatorja. Ker se ventilator vrti zelo
hitro, lahko povzroči poškodbe.
Vodnik za monterja
55
12 | Zagon
12.3 Seznam preverjanj pred zagonom
Med testnim delovanjem se bodo zagnale zunanja in notranje enote. Prepričajte
se, da je so bile vse priprave notranjih enot dokončane (priključne cevi, električno
ožičenje, izpust zraka ...). Glejte priročnik za montažo notranje enote za
podrobnosti.
Po namestitvi enote najprej preverite elemente s seznama. Ko preverite vse
elemente, je treba enoto zapreti. Zaganjanje enote po zaprtju.
Notranja enota je pravilno nameščena.
Zunanja enota je pravilno nameščena.
Sistem je pravilno ozemljen in ozemljitvene priključne sponke so čvrsto pritrjene.
Napajalna napetost mora ustrezati napetosti, navedeni na identifikacijski nalepki enote.
Spoji v stikalniomarici NISO zrahljani in električni sestavni deli NISO poškodovani.
Sestavni deli v notranji in zunanji enoti NISO poškodovani in cevi NISO stisnjene.
Hladivo NE uhaja.
Cevi za hladivo (plinasto in tekoče) so toplotno izolirane.
Montirane so cevi ustrezne velikosti, cevi so tudi primerno izolirane.
Zaporna ventila na zunanji enoti (za plin in tekočino) sta popolnoma odprta.
Kondenzat
Prepričajte se, da kondenzat nemoteno odteka.
Možna posledica: Vodni kondenzat bi lahko kapljal.
Notranja enota sprejema signale z uporabniškega vmesnika.
Za kabelske povezave med enotami so uporabljeni predpisani kabli.
Varovalke, prekinjala vezij ali lokalno nameščene zaščitne naprave so nameščene v skladu
s tem dokumentom in NISO premoščene.
12.4 Seznam preverjanj med zagonom
Odzračevanje
Izvajanje testnega zagona
12.5 Izvajanje testnega zagona
Vodnik za monterja
56
INFORMACIJA
Če se med predajo v uporabo na enoti pojavi napaka, glejte servisni priročnik za
podrobna navodila o odpravljanju težav.
Predpogoj: Napajanje MORA biti v navedenem območju.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Predpogoj: Preizkus delovanja je mogoče izvesti v načinu hlajenja ali ogrevanja.
Predpogoj: Preizkus mora biti izveden v skladu s priročnikom za delovanje notranje
enote, da zagotovite, da pravilno delujejo vse funkcije in vsi deli.
1V načinu hlajenje izberite najnižjo temperaturo, ki jo lahko nastavite. V načinu
ogrevanje izberite najvišjo temperaturo, ki jo lahko nastavite. Preizkus
delovanja je mogoče onemogočiti, če je to potrebno.
2Ko je preizkus delovanja končan, temperaturo nastavite na normalno
vrednost. V načinu hlajenje: 26~28°C, v načinu ogrevanje: 20~24°C.
3Sistem neha delovati 3minute po izklopu enote.
INFORMACIJA
▪ Tudi če je enota izključena, troši elektriko.
▪ Ko je po izpadu elektrike spet vzpostavljeno napajanje, se bo vključil prej izbrani
12.6 Zagon zunanje enote
12 | Zagon
način delovanja.
Glejte priročnik za montažo notranje enote za konfiguracijo in začetek uporabe za
sistem.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
57
13 | Izročitev uporabniku
13 Izročitev uporabniku
Ko se testni zagon konča in enota pravilno deluje, preverite in potrdite naslednje
točke za uporabnika:
▪ Preverite, ali je uporabnik prejel natisnjeno dokumentacijo, in ga prosite, da jo
shrani za uporabo v prihodnje. Uporabnika obvestite, da je celotna
dokumentacija na voljo na spletnem naslovu, prej omenjenem v tem priročniku.
▪ Uporabniku pojasnite pravilno uporabo sistema in kaj mora storiti, če se pojavijo
težave.
▪ Pokažite uporabniku, kaj mora narediti za vzdrževanje enote.
▪ Uporabniku pojasnite nasvete za varčno rabo energije, opisane v priročniku za
uporabo.
Vodnik za monterja
58
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
14 Vzdrževanje in servisiranje
OPOMBA
Splošni kontrolni seznam za vzdrževanje/pregled. Poleg navodil za vzdrževanje v
tem poglavju je v spletišču Daikin Business Portal (potrebna je prijava) na voljo
splošni kontrolni seznam za vzdrževanje/pregled.
Splošni kontrolni seznam za vzdrževanje/pregled je dopolnilo navodilom v tem
poglavju in se lahko uporabi kot smernica ter predloga za poročanje med
vzdrževanjem.
OPOMBA
Vzdrževanje MORA opraviti pooblaščen monter ali servisni zastopnik.
Priporočamo, da vzdrževanje izvedete vsaj enkrat letno. Je pa mogoče, da veljavna
zakonodaja zahteva krajša vzdrževalna obdobja.
14.1 Pregled: Vzdrževanje in servisiranje
14 | Vzdrževanje in servisiranje
V tem poglavju so informacije:
▪ Varnostni ukrepi za vzdrževanje
▪ Vsakoletno vzdrževanje zunanje enote
14.2 Varnostni ukrepi za vzdrževanje
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
Pred izvajanjem vzdrževalnih ali servisnih del se dotaknite kovinskega dela enote, da
bi odvedli statično elektriko in tako zaščitili tiskano vezje.
OPOZORILO
▪ Preden pričnete z izvajanjem vzdrževanja ali popravila, vedno izklopite odklopnik
na napajalni plošči, odstranite varovalke oz. odprite zaščitne naprave enote.
▪ Ne dotikajte se delujočih delov 10 min po izključitvi napajanja, saj obstaja
možnost visoke napetosti.
▪ Pazite, ker je nekaj delov električne omarice izjemno vročih.
▪ Pazite, da se ne boste dotaknili prevodnega dela.
▪ NE izpirajte enote. To bi lahko povzročilo električni udar ali požar.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
59
14 | Vzdrževanje in servisiranje
14.3 Seznam preverjanj za letno vzdrževanje zunanje enote
Naslednje točke preverite vsaj enkrat letno:
▪ Izmenjevalnik toplote
Izmenjevalnik toplote zunanje enote se lahko zamaši zaradi prahu, umazanije,
listov itd. Priporočamo, da izmenjevalnik toplote očistite letno. Zamašen
izmenjevalnik toplote lahko povzroči prenizek ali previsok tlak, kar vodi v
poslabšanje zmogljivosti.
14.4 O kompresorju
Pri servisiranju kompresorja upoštevajte naslednja varnostna priporočila:
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Kompresor uporabljajte le v ozemljenem sistemu.
▪ Izključite napajanje pred servisiranjem.
▪ Spet pritrdite pokrov stikalne omarice in servisni pokrov po servisiranju.
14.5 Zimski letni čas
OPOMIN
vedno uporabljajte zaščitna očala in rokavice.
NEVARNOST: NEVARNOST EKSPLOZIJE
▪ Uporabite cevni rezalnik, da bi odstranili kompresor.
▪ NE uporabljajte plamenskega spajkalnika.
▪ Uporabite le odobrena hladiva in maziva.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
Kompresorja se Ne dotikajte z golimi rokami.
OPOMBA
Če se na zunanji enoti naredijo ledene sveče, jih MORATE odstraniti. Uporabite
rokavice, da se ne bi poškodovali in da ne bi poškodovali enote.
Vodnik za monterja
60
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
15 Odpravljanje težav
15.1 Pregled: Odpravljanje težav
To poglavje opisuje, kaj morate narediti v primeru težav.
Vsebuje informacije za reševanje težav na podlagi simptomov.
Pred odpravljanjem težav
Preglejte stikalno omarico in pri tem iščite očitne okvare, kot so zrahljane povezave
ali okvarjeno ožičenje.
15.2 Varnostni ukrepi pri odpravljanju težav
OPOZORILO
▪ Ko pregledujete stikalno omarico enote, VEDNO preverite, ali je enota
odklopljena iz omrežnega napajanja. Izklopite ustrezen odklopnik.
▪ Če se je aktivirala varnostna naprava, zaustavite enoto in ugotovite vzrok za njeno
aktiviranje, preden jo ponastavite. NIKOLI ne zaobidite varnostnih naprav in ne
spreminjajte njihovih vrednosti na vrednost, ki se razlikuje od tovarniške
nastavitve. Če ne morete ugotoviti vzroka težave, pokličite svojega prodajalca.
15 | Odpravljanje težav
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
OPOZORILO
Preprečite nevarnosti zaradi nehotene ponastavitve termičnega odklopa: napajanje
te naprave NE SME biti izvedeno preko zunanjega preklopnika, denimo časovnika, in
naprava ne sme biti priključena na tokokrog, ki ga vzdrževanje redno vklaplja in
izklaplja.
NEVARNOST: TVEGANJE ZA OŽGANINE/OPEKLINE
15.3 Reševanje težav na podlagi simptomov
15.3.1 Simptom: Notranje enote padajo, vibrirajo ali oddajajo zvoke
Možni vzrokiRešitev
Notranje enote niso varno nameščeneVarno namestite notranje enote.
15.3.2 Simptom: Enota NE ogreva oziroma ne hladi po pričakovanjih
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Možni vzrokiRešitev
Nepravilne povezave električnih kablovPravilno povežite električne kable.
Puščanje plinaPreverite, ali kje pušča plin.
Vodnik za monterja
61
15 | Odpravljanje težav
15.3.3 Simptom: Iztekanje vode
Možni vzrokiRešitev
Nepravilna termoizolacija (cevi za plin in
tekočino, notranji deli podaljška gibljive
odtočne cevi)
Prepričajte se, da sta termoizolacija cev
in gibljive odtočne cevi popolnoma
izdelani.
Nepravilno priključen odtokZavarujte odtok.
15.3.4 Simptom: Električno puščanje
Možni vzrokiRešitev
Enota NI pravilno ozemljenaPreverite in popravite povezavo
ozemljitvenega vodnika.
15.3.5 Simptom: Enota NE deluje ali ožganine
Možni vzrokiRešitev
Ožičenje NI bilo izvedeno v skladu s
Popravite ožičenje.
specifikacijo
15.4 Diagnosticiranje napak s svetlečo diodo na tiskanem vezju zunanje
enote
Svetleča diodaDiagnoza
utripaObičajno.
▪ Preverite delovanje notranje enote.
Vključen▪ Izključite in vključite napajanje in v času 3 minut še
enkrat preverite svetlečo diodo.
Če sveti, je prišlo do okvare na tiskanem vezju.
Izključeno1Napetost napajanja (zaradi varčevanja z energijo).
2Težave so z napajanjem.
3Izključite in vključite napajanje in v času 3 minut še
enkrat preverite svetlečo diodo.
Če je dioda spet ugasnila, je prišlo do okvare na
tiskanem vezju zunanje enote.
NEVARNOST: TVEGANJE SMRTI ZARADI ELEKTRIČNEGA UDARA
▪ Ko enota ne deluje, so svetleče diode na tiskanem vezju izključene zaradi
varčevanja z energijo.
▪ Tudi ko so svetleče diode izključene, sta priključna sponka in tiskano vezje lahko
pod napetostjo.
Vodnik za monterja
62
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
16 Odstranjevanje
OPOMBA
Sistema nikar NE poskušajte razstaviti sami: razstavljanje sistema, delo s hladivom,
oljem in drugimi deli MORA biti izvedeno v skladu z zadevno zakonodajo. Enote je
treba obravnavati v specializiranem obratu za ponovno uporabo in reciklažo.
16.1 Pregled: odstranjevanje
Običajen potek
Odstranjevanje sistema običajno obsega naslednje faze:
1Izčrpavanje sistema.
2Odvoz sistema v poseben obrat za obdelavo.
INFORMACIJA
Za več podrobnosti glejte priročnik za servisiranje.
16 | Odstranjevanje
16.2 Izčrpavanje
Primer: Zaradi zaščite okolja morate pred prestavljanjem ali odstranjevanjem
enote opraviti izčrpavanje.
NEVARNOST: NEVARNOST EKSPLOZIJE
Izčrpavanje – Puščanje hladiva. Če želite sistem izčrpati in nekje na tokokrogu
hladilnega sredstva pušča:
▪ NE uporabljajte funkcije za samodejno izčrpavanje na enoti, s katero lahko
zberete vse hladivo iz sistema v zunanji enoti. Možna posledica: Samoizgorevanje
in eksplozija kompresorja zaradi zraka, ki pride v delujoč kompresor.
▪ Uporabite ločen sistem za izčrpavanje, tako da kompresorju enote NI treba
delovati.
OPOMBA
Med izčrpavanjem zaustavite kompresor, preden odstranjujete cevi za hladivo. Če
kompresor še vedno deluje in je zaporni ventil med izčrpavanjem odprt, se bo v
sistem vsesal zrak. Posledica so lahko okvara kompresorja in poškodbe sistema zaradi
neobičajnega tlaka v krogu hladiva.
Med izčrpavanjem se bo vse hladivo izločilo iz sistema v zunanjo enoto.
1Odstranite pokrov z zapornega ventila za tekočino in zapornega ventila za plin.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
2Izvedite postopek prisilnega hlajenja. Glejte "16.3 Zagon in zaustavitev
prisilnega hlajenja"[464].
3Po 5 do 10minutah (po samo 1 do 2minutah, če so zunanje temperature zelo
nizke (<−10°C)), zaprite zaporni ventil za tekočino s šestkotnim ključem.
4Na manometru preverite, ali je dosežen vakuum.
5Po 2–3minutah zaprite plinski zaporni ventil in zaustavite prisilno hlajenje.
Vodnik za monterja
63
16 | Odstranjevanje
a
c
b
d
d
e
16.3 Zagon in zaustavitev prisilnega hlajenja
a Zaporni ventil za plin
b Smer zapiranja
c Šestrobi ključ
d Čep ventila
e Zaporni ventil za tekočino
Obstajata 2načina za izvajanje prisilnega hlajenja.
▪ 1. način. S stikalom ON/OFF na notranji enoti (če je nameščeno na notranji
enoti).
▪ 2. način. Z uporabniškim vmesnikom notranje enote.
16.3.1 Da bi zagnali in zaustavili prisilno hlajenje s stikalom za vklop/izklop na notranji enoti
1Pritisnite stikalo ON/OFF in ga držite vsaj 5sekund.
Rezultat: Naprava se vklopi.
INFORMACIJA
Prisilno hlajenje se bo samodejno zaustavilo po 15minutah.
2Da bi prej zaustavili delovanje, pritisnite stikalo ON/OFF.
16.3.2 Da bi zagnali in zaustavili prisilno hlajenje z uporabniškim vmesnikom notranje enote
1Nastavite način delovanja na hlajenje. Glejte poglavje "Da bi izvedli preizkus
delovanja" v priročniku za montažo notranje enote.
Opomba: Prisilno hlajenje se bo samodejno zaustavilo po približno
30minutah.
2Da bi prej zaustavili delovanje, pritisnite stikalo ON/OFF.
INFORMACIJA
Če uporabite prisilno hlajenje, ko je zunanja temperatura <−10°C, bo varnostna
naprava morda preprečila delovanje. Ogrejte termistor zunanje temperature na
notranji enoti na ≥−10°C. Rezultat: Delovanje se bo sprožilo.
Vodnik za monterja
64
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
17 Tehnični podatki
,
A
INDOOR
OUTDOOR
▪ Povzetek najnovejših tehničnih podatkov je na voljo na regionalni Daikin spletni
strani (javno dostopna).
▪ Popolni tehnični podatki so na voljo na Daikin Business Portal (zahtevana
avtentikacija).
17.1 Vezalna shema
Shema povezav je dobavljena z enoto in je v notranjosti zunanje enote (spodnja
stran zgornje plošče).
17.1.1 Poenotena legenda za vezalno shemo
Za uporabljene dele in oštevilčevanje glejte shemo povezav na enoti.
Oštevilčevanje delov se izvede z arabskimi številkami naraščajoče za vsak del in je v
spodnji preglednici predstavljeno s "*" kodo dela.
SimbolPomenSimbolPomen
17 | Tehnični podatki
Prekinjalo vezjaZaščitna ozemljitev
PovezavaOzemljitvena zaščita (vijak)
Konektor
Pretvornik
OzemljitevPriključek za rele
Zunanje ožičenjePriključek kratkega stika
VarovalkaPriključna sponka
Notranja enotaPovezavna letvica
Zunanja enotaŽična sponka
Naprava za tokovni
ostanek
SimbolBarvaSimbolBarva
BLKČrnaORGOranžna
BLUModraPNKRožnata
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
BRNRjavaPRP, PPLVijolična
GRNZelenaREDRdeča
GRYSivaWHTBela
YLWRumena
SimbolPomen
A*PPloščica s tiskanim vezjem
BS*Gumb ON/OFF, stikalo za delovanje
Vodnik za monterja
65
17 | Tehnični podatki
SimbolPomen
BZ, H*OBrenčač
C*Kondenzator
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*,
Povezava, priključek
MR*_A, MR*_B, S*, U, V, W, X*A,
K*R_*, NE
D*, V*DDioda
DB*Premostitev diode
DS*DIP-stikalo
E*HGrelnik
FU*, F*U, (za lastnosti glejte tiskano
Varovalka
vezje v vaši enoti)
FG*Priključek (ozemljitev okvirja)
H*Varovalni pas
H*P, LED*, V*LPilotska lučka, svetlobna dioda
HAPSvetlobna dioda (servisni monitor -
zelena)
HIGH VOLTAGEVisoka napetost
IESTipalo Intelligent-eye
IPM*Inteligentni napajalni modul
K*R, KCR, KFR, KHuR, K*MMagnetni rele
LNapetostni vodnik
L*Tuljava
L*RReaktanca
M*Koračni motor
M*CMotor kompresorja
M*FMotor ventilatorja
M*PMotor črpalke za odtok
M*SNihajni motor
MR*, MRCW*, MRM*, MRN*Magnetni rele
NNevtralna
n=*, N=*Število prehodov skozi feritno jedro
PAMModulacija amplitude pulziranja
PCB*Ploščica s tiskanim vezjem
PM*Napajalni modul
PSPreklopno napajanje
Vodnik za monterja
66
PTC*Termistor PTC
Q*Bipolarni tranzistor izoliranih vrat (IGBT)
Q*CPrekinjalo vezja
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
17 | Tehnični podatki
SimbolPomen
Q*DI, KLMZemljostični odklopnik
Q*LPreobremenitvena zaščita
Q*MTermično stikalo
Q*RNaprava za tokovni ostanek
R*Upor
R*TTermistor
RCSprejemnik
S*COmejevalno stikalo
S*LStikalo s plovcem
S*NGZaznavalo puščanja hladiva
S*NPHTlačno tipalo (visoki tlak)
S*NPLTlačno tipalo (nizki tlak)
S*PH, HPS*Tlačno stikalo (visoki tlak)
S*PLTlačno stikalo (nizki tlak)
S*TTermostat
S*RHSenzor vlažnosti
S*W, SW*Stikalo za delovanje
SA*, F1SPretokovni zaustavljalnik
SR*, WLUSprejemnik signala
SS*Izbirno stikalo
SHEET METALMontažna ploščica povezavne letvice
T*RTransformator
TC, TRCOddajnik
V*, R*VVaristor
V*RPremostitev diode, Napajalni modul
bipolarnega tranzistorja izoliranih vrat
(IGBT)
WRCBrezžični daljinski upravljalnik
X*Priključna sponka
X*MPovezavna letvica (blok)
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Y*ENavitje elektronskega ekspanzijskega
ventila
Y*R, Y*STuljava obračalnega elektromagnetnega
ventila
Z*CFeritno jedro
ZF, Z*FProtišumni filter
Vodnik za monterja
67
17 | Tehnični podatki
M
p
l
q
c
d
a
b
o
n
g
m
m
m
r
·6x7.0· CuT
·7.9· CuT
·6.4· CuT
·6.4· CuT
·9.5· CuT
·7.9· CuT
·9.5· CuT
·9.5· CuT
·12.7· CuT
·9.5· CuT
·9.5· CuT
·9.5· CuT
·6x7.0· CuT
HPS
·6.4· CuT
k
·12.7· CuT
·6x3.2· CuT
·6.4· CuT
f
h
i
j
e
17.2 Shema napeljave cevi
17.2.1 Shema napeljave cevi: zunanja enota
Kategorije PED za opremo – Visokotlačno stikalo: kategorija IV; Kompresor:
kategorija II; Druga oprema: člen 4§3.
Vodnik za monterja
68
a Lokalne cevi (tekočina)l Akumulator
b Lokalne cevi (plin)m Dušilka
c Zaporni ventil za tekočinon ON: 4-potni ventil za ogrevanje
d Zaporni ventil za plino Termistor izpustne cevi
e Filterp Termistor temperature zraka zunanje enote
f Elektronska ekspanzijska posodaq Kompresor
g Dušilka s filtromr Ventilator propelerja
h RazdelilnikP Motor ventilatorja
i Kapilarna cevHPS Visokotlačno stikalo (Samodejna ponastavitev)
j Izmenjevalnik toploteHlajenje
k Termistor toplotnega izmenjevalnikaOgrevanje
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
18 Slovar
18 | Slovar
Prodajalec
Dobavitelj izdelka.
Pooblaščen monter
Tehnično usposobljena oseba, ki je kvalificirana za namestitev izdelka.
Uporabnik
Oseba, ki je lastnik izdelka in/ali izdelek uporablja.
Zadevna zakonodaja
Vse mednarodne, evropske, nacionalne in lokalne direktive, zakoni, predpisi
in/ali pravilniki, ki se nanašajo na določen izdelek ali področje.
Servisno podjetje
Kvalificirano podjetje, ki lahko izvaja ali vodi potrebne servisne posege na
izdelku.
Priročnik za montažo
Priročnik za namestitev za določen izdelek ali uporabo, ki podaja navodila za
namestitev, nastavitev in vzdrževanje.
Priročnik za uporabo
Priročnik za določen izdelek ali uporabo, ki podaja navodila za uporabo.
Navodila za vzdrževanje
Priročnik za določen izdelek ali uporabo, ki podaja navodila za namestitev,
nastavitev, uporabo in/ali vzdrževanje (če so upoštevna) za izdelek oziroma
uporabo.
Oprema
Nalepke, priročniki, tehnični listi in oprema, priloženi izdelku ob dobavi, ki jih
je treba namestiti v skladu z navodili v spremni dokumentaciji.
Opcijska oprema
Oprema, ki jo izdela ali odobri Daikin, in se lahko uporablja s tem izdelkom v
skladu z navodili v spremni dokumentaciji.
Lokalna dobava
Oprema, ki je NE izdeluje Daikin in se lahko uporablja s tem izdelkom v
skladu z navodili v spremni dokumentaciji.
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 serija split
4P518023-11H – 2021.03
Vodnik za monterja
69
Verantwortung für Energie und Umwelt
Copyright 2021 Daikin
4P518023-11H 2021.03