2.1Indoor Units ..........................................................................................167
2.2Outdoor Units .......................................................................................167
Index............................................................................................. i
Drawings & Flow Charts ................................................................ v
ivTable of Contents
SiBE06-514AIntroduction
1. Introduction
1.1Safety Cautions
Be sure to read the following safety cautions before conducting repair work.
Cautions and
Warnings
The caution items are classified into “Warning” and “Caution”. The “Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer.
1.1.1Caution in Repair
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the
welded section, release the refrigerant gas completely at a well-ventilated
place first.
If there is a gas remaining inside the compressor, the refrigerant gas or
refrigerating machine oil discharges when the pipe is disconnected, and it can
cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The
refrigerant gas can generate toxic gases when it contacts flames.
Warning
The step-up capacitor supplies high-voltage electricity to the electrical
components of the outdoor unit.
Be sure to discharge the capacitor completely before conducting repair work.
A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
v
IntroductionSiBE06-514A
Warning
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water.
Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or
wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it.
The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
1.1.2Cautions Regarding Products after Repair
Warning
Be sure to use parts listed in the service parts list of the applicable model and
appropriate tools to conduct repair work. Never attempt to modify the
equipment.
The use of inappropriate parts or tools can cause an electrical shock,
excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has
sufficient strength to withstand the weight of the equipment.
If the installation site does not have sufficient strength and if the installation
work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard
installation frame.
Incorrect use of the installation frame and improper installation can cause the
equipment to fall, resulting in injury.
Be sure to install the product securely in the installation frame mounted on a
window frame.
If the unit is not securely mounted, it can fall and cause injury.
Be sure to use an exclusive power circuit for the equipment, and follow the
technical standards related to the electrical equipment, the internal wiring
regulations and the instruction manual for installation when conducting
electrical work.
Insufficient power circuit capacity and improper electrical work can cause an
electrical shock or fire.
For integral units
only
For integral units
only
vi
SiBE06-514AIntroduction
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A / R22) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the remote controller, be sure to disposed
of the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly.
If the packing and seal are not installed properly, water can enter the room and
wet the furniture and floor.
1.1.3Inspection after Repair
Check to make sure that the power cable plug is not dirty or loose, then insert
the plug into a power outlet all the way.
If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Caution
For integral units
only
Warning
vii
IntroductionSiBE06-514A
Warning
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
1.1.4Using Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each
icon is described in the table below:
1.1.5Using Icons List
IconType of
Note:
Caution
Warning
Information
Description
NoteA “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
CautionA “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
an unexpected result or has to restart (part of) a procedure.
WarningA “warning” is used when there is danger of personal injury.
viii
ReferenceA “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a
specific topic.
SiBE06-514A
Part 1
List of Functions
1. List of Functions ......................................................................................2
3.15 Facility Setting Jumper (cooling at low outdoor temperature) ................47
Function and Control17
Main FunctionsSiBE06-514A
1. Main Functions
Note:See the list of functions for the functions applicable to different models.
1.1Frequency Principle
Main Control
Parameters
Additional
Control
Parameters
The compressor is frequency-controlled during normal operation. The target frequency is set by
the following 2 parameters coming from the operating indoor unit:
The load condition of the operating indoor unit
The difference between the room temperature and the set temperature
The target frequency is adapted by additional parameters in the following cases:
Frequency restrictions
Initial settings
Forced cooling operation
Inverter PrincipleTo regulate the capacity, a frequency control is needed. The inverter makes it possible to vary
the rotation speed of the compressor. The following table explains the conversion principle:
PhaseDescription
1The supplied AC power source is converted into the DC power source for the present.
2The DC power source is reconverted into the three phase AC power source with variable
frequency.
When the frequency increases, the rotation speed of the compressor increases resulting
in an increased refrigerant circulation. This leads to a higher amount of the heat
exchange per unit.
When the frequency decreases, the rotation speed of the compressor decreases
resulting in a decreased refrigerant circulation. This leads to a lower amount of the heat
exchange per unit.
Drawing of
Inverter
The following drawing shows a schematic view of the inverter principle:
Refrigerant circulation rate (high)
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
AC
power
freq=
constant
high f
DC
power
low f
50 Hz
freq=variable
60 Hz
Refrigerant circulation rate (low)
high speed
low speed
capacity=
variable
Amount of heat
exchanged air (large)
Amount of heat
exchanged air (small)
(R2812)
18Function and Control
SiBE06-514AMain Functions
Inverter FeaturesThe inverter provides the following features:
The regulating capacity can be changed according to the changes in the outdoor air
temperature and cooling / heating load.
Quick heating and quick cooling
The compressor rotational speed is increased when starting the heating (or cooling). This
enables a quick set temperature.
Air discharge
temperature
45˚C
inverter
normal heat pump
Start
Even during extreme cold weather, the high capacity is achieved. It is maintained even when
60120300
seconds
(R1187)
the outdoor air temperature is 2°C.
Comfortable air conditioning
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency LimitsThe following table shows the functions that define the minimum and maximum frequency:
Frequency limitsLimited during the activation of following functions
Low Four way valve operation compensation. Refer to page 36.
Forced Cooling
High Input current control. Refer to page 38.
For more information, refer to “Forced operation mode” on page
Compressor protection function. Refer to page 37.
Heating peak-cut control. Refer to page 39.
Freeze-up protection control. Refer to page 39.
Defrost control. Refer to page 41.
.
46
Operation
Function and Control19
Main FunctionsSiBE06-514A
1.2Flap Control
Wide-angle FlapThe large flaps send a large volume of air all over the room. The flap provides an optimum
control in cooling, heating and dry mode.
LouvresThe louvres, made of elastic synthetic resin, provide a wide range of airflow that guarantees a
comfortable air distribution.
Auto-swingThe following table explains the auto-swing process for heating and cooling:
ItemDescriptionDrawing
heating
cooling /
dry
The flap swings up and down as shown
in the drawing alongside.
(R1194)
The flap swings up and down as shown
in the drawing alongside.
(R1195)
20Function and Control
SiBE06-514AMain Functions
1.3Air Flow Selection
Air conditioner automatically decides the appropriate blowing pattern depending on the
When setting the
air flow selection
switch to.
operating mode / situation.
Operating modeSituationBlowing pattern
When the room has become
fully cool, or when one hour has
passed since turning on the air
conditioner.
So that air does not come into direct contact
with people, air is blown upper air outlet,
room temperature is equalised.
When setting the
air outlet
selection switch
to.
Cool mode
Heat mode
During Dry mode, so that cold air does not come into direct contact with people, air is blown
At start of operation or other
times when the room is not fully
cooled.
At times other than below.
(Normal time.)
At start or when air temperature
is low.
So that air does not come into direct contact
with people. Air is blown upper air outlet.
Air is blown
from the upper
and lower air
outlets for high
speed cooling
during Cool
mode, and for
filling the room
with warm air
during Heat
mode.
upper air outlet.
Regardless of the operating mode or situation, air blows from the upper air outlet.
Use this switch when you do not want air coming out of the lower air outlet. (While sleeping
etc..)
Function and Control21
Loading...
+ 154 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.