Daikin RVLQ05 08CA, RHYHBH05AA, RHYHBH/X08AA, RHYKOMB33AA Installer reference guide

+
Installer reference guide
ROTEX HPU hybrid
RVLQ05+08CA RHYHBH05AA RHYHBH/X08AA RHYKOMB33AA
Installer reference guide
ROTEX HPU hybrid
English

Table of contents

Table of contents
6.5.3 Overview of electrical connections except external
actuators ...................................................................... 22
6.5.4 Overview of electrical connections for external and
internal actuators ......................................................... 22
1 General safety precautions 4
1.1 About the documentation .......................................................... 4
1.1.1 Meaning of warnings and symbols.............................. 4
1.2 For the installer.......................................................................... 4
1.2.1 General ....................................................................... 4
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 5
1.2.4 Water .......................................................................... 5
1.2.5 Electrical ..................................................................... 6
1.2.6 Gas ............................................................................. 6
1.2.7 Gas exhaust................................................................ 7
1.2.8 Local legislation .......................................................... 7
2 About the product 7
3 About the documentation 8
3.1 About this document.................................................................. 8
3.2 Installer reference guide at a glance ......................................... 8
4 About the box 8
4.1 Overview: About the box ........................................................... 8
4.2 Outdoor unit............................................................................... 9
4.2.1 To unpack the outdoor unit ......................................... 9
4.2.2 To remove the accessories from the outdoor unit....... 9
4.3 Indoor unit ................................................................................. 9
4.3.1 To unpack the indoor unit ........................................... 9
4.3.2 To remove the accessories from the indoor unit......... 10
4.4 Gas boiler .................................................................................. 10
4.4.1 To unpack the gas boiler............................................. 10
4.4.2 To remove the accessories from the gas boiler.......... 11
5 About the units and options 11
5.1 Overview: About the units and options...................................... 11
5.2 Identification .............................................................................. 11
5.2.1 Identification label: Outdoor unit ................................. 11
5.2.2 Identification label: Indoor unit .................................... 11
5.2.3 Identification label: gas boiler...................................... 12
5.3 Combining units and options ..................................................... 12
5.3.1 Possible options for the outdoor unit........................... 12
5.3.2 Possible options for the indoor unit............................. 12
5.3.3 Possible options for the gas boiler.............................. 13
5.3.4 Possible combinations of indoor unit and outdoor
unit .............................................................................. 16
5.3.5 Possible combinations of indoor unit and domestic
hot water tank ............................................................. 16
6 Preparation 16
6.1 Overview: Preparation............................................................... 16
6.2 Preparing installation site .......................................................... 16
6.2.1 Installation site requirements of the outdoor unit ........ 16
6.2.2 Additional installation site requirements of the
outdoor unit in cold climates ....................................... 17
6.2.3 Installation site requirements of the indoor unit .......... 17
6.3 Preparing refrigerant piping....................................................... 18
6.3.1 Refrigerant piping requirements.................................. 18
6.3.2 Refrigerant piping insulation ....................................... 18
6.4 Preparing water piping .............................................................. 18
6.4.1 Water circuit requirements .......................................... 18
6.4.2 Formula to calculate the expansion vessel pre-
pressure ...................................................................... 19
6.4.3 To check the water volume and flow rate ................... 19
6.4.4 Changing the pre-pressure of the expansion vessel... 21
6.4.5 To check the water volume: Examples ....................... 21
6.5 Preparing electrical wiring ......................................................... 21
6.5.1 About preparing electrical wiring................................. 21
6.5.2 About preferential kWh rate power supply.................. 21
7 Installation 23
7.1 Overview: Installation ................................................................. 23
7.2 Opening the units ....................................................................... 23
7.2.1 About opening the units ............................................... 23
7.2.2 To open the outdoor unit.............................................. 23
7.2.3 To open the switch box cover of the indoor unit .......... 23
7.2.4 To open the gas boiler ................................................. 24
7.2.5 To open the switch box cover of the gas boiler............ 24
7.3 Mounting the outdoor unit........................................................... 24
7.3.1 About mounting the outdoor unit.................................. 24
7.3.2 Precautions when mounting the outdoor unit............... 24
7.3.3 To provide the installation structure ............................. 24
7.3.4 To install the outdoor unit............................................. 25
7.3.5 To provide drainage ..................................................... 26
7.3.6 To prevent the outdoor unit from falling over ............... 26
7.4 Mounting the indoor unit............................................................. 27
7.4.1 About mounting the indoor unit.................................... 27
7.4.2 Precautions when mounting the indoor unit................. 27
7.4.3 To install the indoor unit............................................... 27
7.5 Mounting the gas boiler .............................................................. 28
7.5.1 To install the gas boiler ................................................ 28
7.5.2 To install the condensate trap...................................... 28
7.6 Condensate pipe work................................................................ 29
7.6.1 Internal connections..................................................... 29
7.6.2 External connections.................................................... 30
7.7 Connecting the refrigerant piping ............................................... 30
7.7.1 About connecting the refrigerant piping ....................... 30
7.7.2 Precautions when connecting the refrigerant piping.... 30
7.7.3 Guidelines when connecting the refrigerant piping...... 30
7.7.4 Pipe bending guidelines............................................... 31
7.7.5 To flare the pipe end .................................................... 31
7.7.6 To braze the pipe end .................................................. 31
7.7.7 Using the stop valve and service port .......................... 31
7.7.8 To connect the refrigerant piping to the outdoor unit ... 32
7.7.9 To connect the refrigerant piping to the indoor unit ..... 32
7.8 Checking the refrigerant piping .................................................. 33
7.8.1 About checking the refrigerant piping .......................... 33
7.8.2 Precautions when checking the refrigerant piping ....... 33
7.8.3 To check for leaks........................................................ 33
7.8.4 To perform vacuum drying ........................................... 33
7.9 Charging refrigerant ................................................................... 34
7.9.1 About charging refrigerant ........................................... 34
7.9.2 Precautions when charging refrigerant ........................ 34
7.9.3 To determine the additional refrigerant amount........... 34
7.9.4 To determine the complete recharge amount.............. 34
7.9.5 To charge refrigerant ................................................... 34
7.9.6 To fix the fluorinated greenhouse gases label ............. 34
7.10 Connecting the water piping ....................................................... 35
7.10.1 About connecting the water piping ............................... 35
7.10.2 Precautions when connecting the water piping............ 35
7.10.3 Connecting the water piping of the indoor unit............. 35
7.10.4 Connecting the water piping of the gas boiler .............. 35
7.10.5 To fill the space heating circuit..................................... 36
7.10.6 To fill the domestic water circuit of the gas boiler ........ 36
7.10.7 To fill the domestic hot water tank ............................... 36
7.10.8 To insulate the water piping ......................................... 36
7.11 Connecting the electrical wiring.................................................. 37
7.11.1 About connecting the electrical wiring.......................... 37
7.11.2 Precautions when connecting the electrical wiring ...... 37
7.11.3 Guidelines when connecting the electrical wiring ........ 37
7.11.4 To connect the electrical wiring on the outdoor unit..... 37
7.11.5 To connect the electrical wiring on the indoor unit ....... 38
7.11.6 To connect the main power supply of the indoor unit .. 39
7.11.7 To connect the main power supply of the gas boiler.... 39
Installer reference guide
2
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
Table of contents
7.11.8 To connect the communication cable between gas
boiler and indoor unit .................................................. 40
7.11.9 To connect the user interface ..................................... 40
7.11.10 To connect the shut-off valve...................................... 41
7.11.11 To connect the electrical meter................................... 41
7.11.12 To connect the gas meter ........................................... 42
7.11.13 To connect the domestic hot water pump ................... 42
7.11.14 To connect the alarm output ....................................... 42
7.11.15 To connect the space cooling/heating ON/OFF
output .......................................................................... 42
7.11.16 To connect the power consumption digital inputs ....... 43
7.12 Connecting the gas piping ......................................................... 43
7.12.1 To connect the gas pipe.............................................. 43
7.13 Connecting the boiler to the flue gas system ............................ 43
7.13.1 To change the gas boiler to 80/125 concentric
connection................................................................... 43
7.13.2 To change the 60/100 concentric connection to a
dual pipe connection ................................................... 44
7.13.3 Calculate the total piping length .................................. 44
7.13.4 Appliance categories and pipe lengths ....................... 45
7.13.5 Applicable materials .................................................... 46
7.13.6 Flue pipe position ........................................................ 47
7.13.7 Insulation of the gas exhaust and air intake................ 47
7.13.8 Fitting a horizontal flue system ................................... 47
7.13.9 Fitting a vertical flue system........................................ 48
7.13.10 Plume management kit ............................................... 48
7.13.11 Flues in voids .............................................................. 48
7.14 Finishing the outdoor unit installation ........................................ 48
7.14.1 To finish the outdoor unit installation .......................... 48
7.14.2 To close the outdoor unit ............................................ 49
7.15 Finishing the indoor unit installation .......................................... 49
7.15.1 To close the indoor unit............................................... 49
7.16 Finishing the gas boiler installation ........................................... 49
7.16.1 To purge the gas supply ............................................. 49
7.16.2 To close the gas boiler ................................................ 49
7.16.3 To install the cover plate ............................................. 49
8 Configuration 49
8.1 Indoor unit ................................................................................. 49
8.1.1 Overview: Configuration.............................................. 49
8.1.2 Basic configuration...................................................... 52
8.1.3 Advanced configuration/optimization .......................... 60
8.1.4 Menu structure: Overview user settings...................... 71
8.1.5 Menu structure: Overview installer settings ................ 73
8.2 Gas boiler .................................................................................. 74
8.2.1 Overview: Configuration.............................................. 74
8.2.2 Basic configuration...................................................... 74
9 Operation 79
9.1 Overview: Operation.................................................................. 79
9.2 Heating ...................................................................................... 79
9.3 Domestic hot water.................................................................... 79
9.3.1 Flow resistance graph for appliance domestic hot
water circuit................................................................. 79
9.4 Operation modes....................................................................... 79
10 Commissioning 80
10.1 Overview: Commissioning ......................................................... 80
10.2 Precautions when commissioning ............................................. 80
10.3 Checklist before commissioning ................................................ 80
10.4 Checklist during commissioning ................................................ 81
10.4.1 To check the minimum flow rate ................................. 81
10.4.2 Air purge function ........................................................ 81
10.4.3 To perform a test run .................................................. 82
10.4.4 To perform an actuator test run .................................. 82
10.4.5 Underfloor heating screed dryout................................ 83
10.4.6 To perform an air purge on the gas supply ................. 84
10.4.7 To perform a test run on the gas boiler ....................... 84
11 Hand-over to the user 84
12 Maintenance and service 84
12.1 Overview: Maintenance and service .......................................... 85
12.2 Maintenance safety precautions................................................. 85
12.2.1 Opening the indoor unit................................................ 85
12.3 Checklist for yearly maintenance of the outdoor unit ................. 85
12.4 Checklist for yearly maintenance of the indoor unit.................... 85
12.5 To disassemble the gas boiler.................................................... 85
12.6 To clean the inside of the gas boiler........................................... 87
12.7 To assemble the gas boiler ........................................................ 87
13 Troubleshooting 88
13.1 Overview: Troubleshooting......................................................... 88
13.2 Precautions when troubleshooting ............................................. 88
13.3 Solving problems based on symptoms....................................... 88
13.3.1 Symptom: The unit is NOT heating or cooling as
expected ...................................................................... 88
13.3.2 Symptom: The compressor does NOT start (space
heating) ........................................................................ 89
13.3.3 Symptom: The pump is making noise (cavitation) ....... 89
13.3.4 Symptom: The pressure relief valve opens.................. 89
13.3.5 Symptom: The water pressure relief valve leaks ......... 89
13.3.6 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ............................................ 89
13.3.7 Symptom: The pressure at the tapping point is
temporarily unusual high.............................................. 90
13.3.8 Symptom: Tank disinfection function is NOT
completed correctly (AH-error)..................................... 90
13.3.9 Symptom: Boiler abnormality detection (HJ-11 error) .. 90
13.3.10 Symptom: Boiler/hydrobox combination abnormality
(UA52 error) ................................................................. 90
13.3.11 Symptom: The burner does NOT ignite ....................... 90
13.3.12 Symptom: The burner ignites noisily............................ 90
13.3.13 Symptom: The burner resonates ................................. 91
13.3.14 Symptom: No space heating by the gas boiler ............ 91
13.3.15 Symptom: The power is reduced ................................. 91
13.3.16 Symptom: Space heating does NOT reach the
temperature.................................................................. 91
13.3.17 Symptom: Hot water does NOT reach the
temperature (no tank installed) .................................... 91
13.3.18 Symptom: Hot water does NOT reach the
temperature (tank installed) ......................................... 91
13.4 Solving problems based on error codes ..................................... 91
13.4.1 Error codes: Overview ................................................. 92
14 Disposal 94
14.1 Overview: Disposal..................................................................... 94
14.2 To pump down............................................................................ 94
14.3 To start and stop forced cooling ................................................. 95
15 Technical data 95
15.1 Overview: Technical data ........................................................... 95
15.2 Dimensions and service space................................................... 96
15.2.1 Dimensions and service space: Outdoor unit .............. 96
15.2.2 Dimensions and service space: Indoor unit ................. 97
15.3 Center of gravity ......................................................................... 99
15.3.1 Center of gravity: Outdoor unit ..................................... 99
15.4 Components ...............................................................................100
15.4.1 Components: Outdoor unit ...........................................100
15.4.2 Components: Switch box (outdoor unit) .......................100
15.4.3 Components: Indoor unit.............................................. 100
15.4.4 Components: Switch box (indoor unit) .........................101
15.4.5 Components: Gas boiler ..............................................102
15.5 Piping diagram ........................................................................... 103
15.5.1 Piping diagram: Outdoor unit .......................................103
15.5.2 Piping diagram: Indoor unit ..........................................104
15.6 Wiring diagram ...........................................................................105
15.6.1 Wiring diagram: Outdoor unit .......................................105
15.6.2 Wiring diagram: Indoor unit ..........................................108
15.6.3 Wiring diagram: Gas boiler ..........................................112
15.7 Technical specifications ............................................................. 113
15.7.1 Technical specifications: Gas boiler............................. 113
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
3

1 General safety precautions

15.8 ESP curve ................................................................................. 117
15.8.1 ESP curve: indoor unit ................................................ 117
16 Glossary 118
17 Field settings table 119
1 General safety precautions

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be performed by an authorized installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
WARNING: FLAMMABLE MATERIAL
WARNING
Indicates a situation that could result in death or serious injury.
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
DANGER: RISK OF POISONING
Indicates a situation that could result in poisoning.
WARNING: PROTECT AGAINST FROST
Indicates a situation that could result in equipment or property damage.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by ROTEX.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the ROTEX documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminum fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

1.2 For the installer

1.2.1 General

If you are not sure how to install or operate the unit, contact your dealer.
Installer reference guide
4

1.2.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the total weight and
vibration of the installation.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
1 General safety precautions
Module Weight
Hybrid module 30kg
Gas module 36kg
Indoor part (Hybrid module + gas module)
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
▪ Make sure walls sensitive to heat (e.g. wood) are protected by
suitable insulation.
▪ ONLY operate the gas boiler if a sufficient supply of combustion
air is ensured. In case of a concentric air/flue gas system dimensioned according to the specifications of this manual, this is fulfilled automatically and there are no other conditions for the equipment installation room. This method of operation applies exclusively.
▪ This gas boiler is NOT designed for room air dependent operation.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
▪ In bathrooms.
▪ In places where frost is possible. The ambient temperature around
the indoor unit should be >5°C.
Total weight: 66kg
WARNING
Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
Charge with the cylinder upright.

1.2.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
A siphon tube is NOT present Charge with the cylinder upside
down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.

1.2.4 Water

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
5
1 General safety precautions
Avoid damages caused by deposits and corrosion. To prevent corrosion products and deposits, observe the applicable regulations of technology.
Measures for desalination, softening or hardness stabilization are necessary if the filling and top-up water have a high total hardness (>3 mmol/l–sum of the calcium and magnesium concentrations, calculated as calcium carbonate).
Using filling water and top-up water which does NOT meet the stated quality requirements can cause a considerably reduced service life of the equipment. The responsibility for this is entirely that of the user.

1.2.5 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.

1.2.6 Gas

The gas boiler is factory‑set to:
▪ the type of gas quoted on the type identification plate or on the
setting type identification plate,
▪ the gas pressure quoted on the type identification plate.
Operate the unit ONLY with the gas type and gas pressure indicated on these type identification plates.
Installation and adaptation of the gas system MUST be conducted by:
▪ personnel qualified for this work,
▪ in compliance with valid gas installation related guidelines,
▪ in accordance with applicable regulations of the gas supply
company,
▪ In accordance with local and national regulations.
Installer reference guide
6
Boilers that use natural gas MUST be connected to a governed meter.
Boilers that use liquid petroleum gas (LPG) MUST be connected to a regulator.
The size of the gas supply pipe should under no circumstance be less than 22mm.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02

2 About the product

The meter or regulator and pipe work to the meter MUST be checked preferably by the gas supplier. This is to ensure that the equipment works good and meets the gas flow and pressure requirements.
DANGER
If you smell gas:
▪ call immediately your local gas supplier and your
installer,
▪ call the suppliers's number on the side of the LPG tank
(if applicable),
▪ turn off the emergency control valve at the meter/
regulator,
▪ do NOT turn electrical switches ON or OFF,
▪ do NOT strike matches or smoke,
▪ put out naked flames,
▪ open doors and windows immediately,
▪ keep people away from the affected area.

1.2.7 Gas exhaust

Flue systems must NOT be modified or installed in any way other than as described in the fitting instructions. Any misuses or unauthorized modifications to the appliance, flue or associated components and systems could invalidate the warranty. The manufacturer accepts no liability arising from any such actions, excluding statutory rights.
It is NOT allowed to combine flue system parts purchased from different suppliers.

1.2.8 Local legislation

See the local and national regulations.
Local regulations for UK
It is law that all gas appliances are installed by a gas safe registered competent engineer and in accordance with the following recommendations:
▪ Current Gas Safety (Installation and Use) Regulations
▪ All current building regulations
▪ Building Standards (Scotland) Consolidated
▪ This appliance MUST be installed in accordance with the Gas
(Safety and Use) Regulations, current Building Regulations, Building Standards (Scotland), I.S.813 Installation of Gas Appliances (Ireland), IEE Wiring Regulations (BS 7671), Health and Safety Document No. 635 (Electricity at Work Regulations) and Local Water Authority Bye Laws
▪ UK Water Regulations and Bye Laws
▪ Health & Safety
The installation MUST comply with the following British Standards codes of practice:
▪ BS 5440: Flues and Ventilation for gas appliances of rated input
NOT exceeding 70kW (Part 1 Flues)
▪ BS 5440: Flues and Ventilation for gas appliances of rated input
NOT exceeding 70kW (Part 2 Air Supply)
▪ BS 5546: 2000 Installation of gas hot water supplies for domestic
purposes.
▪ BS 5549: 1990 Forced circulation hot water systems.
▪ BS 6700: 1997 Design, Installation, testing and maintenance of
services supplying hot water
▪ BS 6798: 2000 Specification for installation of gas fired hot water
boilers of rated input NOT exceeding 70kW
▪ BS 6891: 1998 Installation of low pressure gas pipe-work
installation up to 35mm (RI)
▪ BS 7593: 1992 Code of practice for treatment of water in heating
systems
▪ BS 7671: 2001 Requirements for electrical installations, IEE
Wiring regulations
▪ BS 7074: 1 Code of practice for domestic and hot water supply
▪ EN12828 Central heating for domestic premises
Potable water: all seals, joints and compounds (including flux and solder) and components used as part of the secondary domestic water system MUST be approved by WRAS.
2 About the product
Especially for UK:
The Benchmark Scheme
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit http://
www.centralheating.co.uk for more information.
Approvals
British Gas Service listing:
RHYKOMB33AA*: G.C.N. 47-464-01
The product (hybrid system) is composed of two modules:
▪ heat pump module,
▪ gas boiler module.
These modules MUST always be installed and used together.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
7

3 About the documentation

a b
a Heat pump module b Gas boiler module
3 About the documentation

3.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
Heat pump module installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
Gas boiler module installation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the gas boiler unit)
Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
Installer reference guide:
▪ Preparation of the installation, technical specifications,
reference data,…
▪ Format: Digital files on the ROTEX homepage
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
the ROTEX homepage
Latest revisions of the supplied documentation may be available on the regional ROTEX website or via your dealer.
The original documentation is written in English. All other languages are translations.

3.2 Installer reference guide at a glance

Chapter Description
General safety precautions
About the product Required combination of heat pump
About the documentation What documentation exists for the
About the box How to unpack the units and remove
About the units and options
Preparation What to do and know before going
Installation What to do and know to install the
Configuration What to do and know to configure the
Operation Operation modes of the gas boiler
Commissioning What to do and know to commission the
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
Safety instructions that you must read before installing
module and gas boiler module
installer
their accessories
▪ How to identify the units
▪ Possible combinations of units and
options
on‑site
system
system after it is installed
module
system after it is configured
kept for future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.

4 About the box

4.1 Overview: About the box

This chapter describes what you have to do after the boxes with the outdoor unit, the indoor unit and the gas boiler are delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
Installer reference guide
8
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
4 About the box
1
2
57kg
a db c

4.2 Outdoor unit

4.2.1 To unpack the outdoor unit

CAUTION
Only handle the outdoor unit as follows:
2 Remove the accessories at the bottom of the package.

4.2.2 To remove the accessories from the outdoor unit

1 Lift the outdoor unit.
a Outdoor unit installation manual b Fluorinated greenhouse gases label c Multilingual fluorinated greenhouse gases label d Unit mounting plate

4.3 Indoor unit

4.3.1 To unpack the indoor unit

RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
9
4 About the box
a
b
a b c d e
f g
1
2
a General safety precautions
b Addendum book for optional equipment
c Indoor unit installation manual
d Operation manual
e Quick installation guide
f Connection pieces for gas boiler
g Boiler communication cable

4.4 Gas boiler

4.4.1 To unpack the gas boiler

Before unpacking, move the gas boiler as close as possible to its installation position.
a Installation manual, operation manual, addendum book for
optional equipment, quick installation guide, general safety precautions, boiler communication cable
b Connection pieces for the gas boiler
INFORMATION
Do NOT throw away the upper cardboard cover. On the outside of the cardboard cover, the installation pattern is printed.

4.3.2 To remove the accessories from the indoor unit

The installation manual, operation manual, addendum book for optional equipment, general safety precautions, quick installation guide, and boiler communication cable are located in the upper part of the box. The connection pieces for the gas boiler are attached to the water piping.
1 Remove the accessories as described in "4.3.1To unpack the
indoor unit"on page9.
Installer reference guide
10
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
WARNING
a
b
c
a b c
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.

5 About the units and options

▪ Identifying the indoor unit
▪ Identifying the gas boiler
▪ Combining outdoor and indoor units
▪ Combining the outdoor unit with options
▪ Combining the indoor unit with options
▪ Combining the gas boiler with options

5.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

5.2.1 Identification label: Outdoor unit

Location

4.4.2 To remove the accessories from the gas boiler

1 Remove the accessories.
a Mounting strip b Condensate trap c Installation manual and operation manual
Model identification
Example: RVLQ05CAV3
Code Explanation
RV Split outdoor pair heat pump
L Low water temperature – ambient zone: −10~
−20°C
Q Refrigerant R410A
05 Capacity class
CA Model series
V3 Power supply

5.2.2 Identification label: Indoor unit

Location
5 About the units and options

5.1 Overview: About the units and options

This chapter contains information about:
▪ Identifying the outdoor unit
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Model identification
Example: RHYHBH05AAV3
Code Description
R ROTEX model
HY Hybrid indoor unit
Installer reference guide
11
5 About the units and options
No: Anno:
Type: NOx classe: PIN: G.C.:
Qnw(net)
PMW
kW
kW kW bar
Qn (net)
Pn
PMS
bar
°C
0063 2013
Tmax
Condensing boiler
b
i
j
a
c
d e
f
k
l
m
n o p
q
r
g
h
Code Description
HBH HBH=Hydrobox heating only
HBX=Hydrobox heating and cooling
05 Capacity class
AA Model series
V3 Power supply

5.2.3 Identification label: gas boiler

Location
Model identification
n Nominal power (kW) o Maximum space heating pressure (bar) p Maximum flow temperature (°C) q Electrical supply
r GCN gas council number

5.3 Combining units and options

5.3.1 Possible options for the outdoor unit

Drain pan (EKDP008CA)
The drain pan is required to gather the drain from the outdoor unit. The drain pan kit consists of:
▪ Drain pan
▪ Installation brackets
For installation instructions, see the installation manual of the drain pan.
Drain pan heater (EKDPH008CA)
The drain pan heater is required to avoid freezing-up of the drain pan.
It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the drain pan heater.
INFORMATION
In case the drain pan heater is used, the jumper JP_DP on the service PCB on the outdoor unit MUST be cut.
After cutting the jumper, you MUST reset the outdoor unit to activate this function.
U-beams (EKFT008CA)
The U-beams are installation brackets on which the outdoor unit can be installed.
It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the outdoor unit.

5.3.2 Possible options for the indoor unit

User interface (RKRUCBL*)
The user interface and a possible additional user interface are available as an option.
The additional user interface can be connected:
Installer reference guide
a Model b Serial number c Production year d Appliance type e NOx class
f PIN number: notified body reference g Destination country h Gas type
i Gas supply pressure (mbar) j Appliance category
k Domestic hot water heat output (kW)
l Maximum domestic hot water pressure (bar)
m Heat output (space heating) (kW)
12
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
▪ RKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ RKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ RKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ RKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ RKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
5 About the units and options
▪ RKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ RKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.
For installation instructions, see "7.11.9 To connect the user
interface"on page40.
Room thermostat (RKRTWA, RKRTR1, RTRNETA)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (RKRTWA) or wireless (RKRTR1and RTRNETA). Thermostat RTRNETA can only be used in heating-only systems.
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (RKRTR1).
For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide the following signals:
▪ Alarm output
▪ Space heating/cooling On/OFF output
For installation instructions, see the installation manual of the digital I/O PCB and the addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to upload different language files to the user interface and indoor parameters to the indoor unit. For the available language files, contact your local dealer.
The software and corresponding operating instructions are available on the ROTEX homepage.
For installation instructions, see the installation manual of the PC cable and "8Configuration"on page49.
Heat pump convector (RFWXV)
For providing space heating/cooling, it is possible to use heat pump convectors (RFWXV).
For installation instructions, refer to the installation manual of the heat pump convectors, and the addendum book for optional equipment.
Solar kit (EKSRPS3)
The solar kit is required to connect the solar application with the domestic hot water tank.
For installation, see the installation manual of the solar kit and addendum book for optional equipment.
Connection kit for the tank (EKEPHT3H)
Use the connection kit to connect the domestic hot water tank to the indoor unit.
For installation instructions, see the installation manual of the connection kit.
Drain pan kit (EKHYDP1)
The drain pan kit is required for heating/cooling units. It does NOT have to be used with heating only units.
For installation instructions, see the installation manual of the drain pan kit.
Mounting kit (EKHYMNT1A, EKHYMNT2A, EKHYMNT3A)
Mounting fixture for easy installation of the hybrid system (heat pump module + gas boiler module). For the selection of the correct kit, see the combination table.
For installation instructions, see the installation manual of the mounting kit.
Filling loop kit (EKFL1A)
Filling loop for easy filling of the water circuit. This kit can only be used in combination with mounting kit EKHYMNT1A.
For installation instructions, see the installation manual of the filling loop kit.
Valve kit (EKVK1A, EKVK2A, EKVK3A)
A set of valves for the easy connection of the field piping. For the connection of the correct kit, see the combination table.
For installation instructions, see the installation manual of the valve kit.
Recirculation thermistor (EKTH2)
Kit for recirculating the water on the gas boiler. Only use this kit when there is no domestic hot water tank installed.
Connection kit for 3rd‑party tank (EKHY3PART)
Use the connection kit to connect a 3rd‑party tank to the system. The connection kit exists of a thermistor and a 3-way valve.
Connection kit for 3rd‑party tank with built‑in thermostat (EKHY3PART2)
Kit for the connection of a 3rd‑party tank with built‑in thermostat to the system. The kit converts a thermostat demand from the tank to a domestic hot water request for the indoor unit.

5.3.3 Possible options for the gas boiler

Main options
Boiler cover plate (EKHY093467)
Cover plate to protect the gas boiler’s piping and valves.
For installation instructions, see the installation manual of the cover plate.
Gas conversion kit G25 (EKPS076227)
Kit for the conversion of the gas boiler for use with gas type G25.
Gas conversion kit G31 (EKHY075787)
Kit for the conversion of the gas boiler for use with gas type G31 (propane).
Dual pipe conversion kit (EKHY090707)
Kit for the conversion of a concentric flue gas system to a dual pipe system.
For installation instructions, see the installation manual of the dual pipe conversion kit.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
13
5 About the units and options
80/125 concentric connection kit (EKHY090717)
Kit for the conversion of 60/100 concentric flue gas connections to 80/125 concentric flue gas connections.
For installation instructions, see the installation manual of the concentric connection kit.
Flue gas flap valve (EKFGF1A)
Non-return flap valve for use in multi-boiler flue gas systems. This valve can only be used in systems using natural gas (G20, G25), and CANNOT be used in systems using propane (G31).
Other options
Accessories Part number Description
EKFGP6837 Roof terminal PP/GLV 60/100
AR460
EKFGS0518 Weather slate steep Pb/GLV
60/100 18°-22°
EKFGS0519 Weather slate steep Pb/GLV
60/100 23°-17°
EKFGP7910 Weather slate steep PF 60/100
25°-45°
EKFGS0523 Weather slate steep Pb/GLV
60/100 43°-47°
EKFGS0524 Weather slate steep Pb/GLV
60/100 48°-52°
EKFGS0525 Weather slate steep Pb/GLV
60/100 53°-57°
EKFGP1296 Weather slate flat Aluminum
60/100 0°-15°
EKFGP6940 Weather slate flat Aluminum
60/100
EKFGP2978 Wall terminal kit PP/GLV
60/100
EKFGP2977 Wall terminal kit low profile PP/
GLV 60/100
EKFGP4651 Extension PP/GLV
60/100×500mm
Accessories Part number Description
EKFGP1295 Flue deflector 60 (UK only)
EKFGP1284 PMK elbow 60 90 (UK only)
EKFGP1285 PMK elbow 60 45° (2pieces)
(UK only)
EKFGP1286 PMK extension 60 L=1000
includes bracket (UK only)
EKFGW5333 Weather slate flat aluminum
80/125
EKFGW6359 Wall terminal kit PP/GLV
80/125
EKFGP4801 Extension PP/GLV
80/125×500mm
EKFGP4802 Extension PP/GLV
80/125×1000mm
EKFGP4814 Elbow PP/GLV 80/125 30°
EKFGP4811 Elbow PP/ALU 80/125 45°
EKFGP4810 Elbow PP/ALU 80/125 90°
EKFGP4820 Inspection elbow Plus PP/ALU
80/125 90° EPDM
EKFGP6864 Roof Terminal PP/GLV 80/125
AR300 RAL9011
EKFGP4652 Extension PP/GLV
EKFGP4664 Elbow PP/GLV 60/100 30°
EKFGP4661 Elbow PP/GLV 60/100 45°
EKFGP4660 Elbow PP/GLV 60/100 90°
EKFGP4667 Meas. tee with inspection panel
EKFGP4631 Wall bracket Ø100
EKFGP1292 Wall terminal Kit PP/GLV
EKFGP1293 Wall terminal kit low profile PP/
EKFGP1294 Plume management kit 60 (UK
Installer reference guide
14
60/100×1000mm
PP/GLV 60/100
60/100
GLV 60/100
only)
EKFGT6300 Weather slate steep Pb/GLV
80/125 18°-22°
EKFGT6301 Weather slate steep Pb/GLV
80/125 23°-27°
EKFGP7909 Weather slate steep PF 80/125
25°-45° RAL9011
EKFGT6305 Weather slate steep Pb/GLV
80/125 43°-47°
EKFGT6306 Weather slate steep Pb/GLV
80/125 48°-52°
EKFGT6307 Weather slate steep Pb/GLV
80/125 53°-57°
EKFGP1297 Weather slate flat aluminum
80/125 0°-15°
EKFGP6368 Tee flex 100 boiler connection
set 1
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
5 About the units and options
Accessories Part number Description
EKFGP6354 Flex 100-60 + support elbow
EKFGP6215 Tee flex 130 boiler connection
set 1
EKFGS0257 Flex 130-60 + support elbow
EKFGP4678 Chimney connection 60/100
EKFGP5461 Extension PP 60×500
EKFGP5497 Chimney top PP 100 with
included flue pipe
Accessories Part number Description
EKFGP6366 Connector flex-flex PP130
EKFGP1856 Flex kit PPØ60-80
EKFGP4678 Chimney connection 60/100
EKFGP2520 Flex kit PP Ø80
EKFGP4828 Chimney connection 80/125
EKFGP6340 Extension Flex PP80 L=10m
EKFGP6316 Adapter flex-fixed PP 100
EKFGP6337 Support bracket top inox Ø100
EKFGP6346 Extension flex PP100 L=10m
EKFGP6349 Extension flex PP100 L=15m
EKFGP6347 Extension flex PP100 L=25m
EKFGP6325 Connector flex-flex PP100
EKFGP5197 Chimney top PP 130 with
included flue pipe
EKFGS0252 Adapter flex-fixed PP130
EKFGP6344 Extension Flex PP80 L=15m
EKFGP6341 Extension Flex PP80 L=25m
EKFGP6342 Extension Flex PP80 L=50m
EKFGP6324 Connector-flex-flex PP80
EKFGP6333 Spacer PP80-100
EKFGP4481 Fixation Ø100
EKFGV1101 Chimney connection 60/10
airintake Dn.80 C83
EKFGV1102 Connection set 60/10-60 Flue/
Air intake Dn.80 C53
EKFGP6353 Support bracket top inox Ø130
EKFGS0250 Extension flex PP130 L=130m
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
EKFGW4001 ExtensionPBM-Air 80×500
EKFGW4002 ExtensionPBM-Air 80×1000
Installer reference guide
15

6 Preparation

≤1200
>250
>250
>250
>350
>350
(mm)(mm)
a
b
b
a
b
a
b
c
Accessories Part number Description
EKFGW4004 ExtensionPBM-Air 80×2000
EKFGW4085 ElbowPPBM-Air8090°
EKFGW4086 ElbowPPBM-Air8045°
INFORMATION
For extra configuration options regarding the flue gas system, visit http://fluegas.rotex-heating.com/.

5.3.4 Possible combinations of indoor unit and outdoor unit

Outdoor unit Indoor unit
RHYHBH05 RHYHBH08 RHYHBX08
RVLQ05CAV3 O
RVLQ08CAV3 O O

5.3.5 Possible combinations of indoor unit and domestic hot water tank

Indoor unit Domestic hot water tank
HYC 343/19/0-DB + HYC 544/32/0-DB
RHYHBH05 O
RHYHBH08 O
RHYHBX08 O
Mind the following spacing guidelines:
a Air outlet
b Air inlet
See "15.2 Dimensions and service space" on page 96 for more detailed information about spacing guidelines.
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind.
6 Preparation

6.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring

6.2 Preparing installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.

6.2.1 Installation site requirements of the outdoor unit

INFORMATION
Also read the following requirements:
Installer reference guide
16
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
a Baffle plate
b Prevailing wind direction
c Air outlet
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea winds. This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
6 Preparation
b
c
a
a
b
c
d
c
d
a
b
c
c
d
>500
200
200
10 350 500
(mm)
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a Sea wind
b Building
c Outdoor unit
d Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient temperatures ranging 10~43°C in cooling mode and – 25~25°C in heating mode.
▪ In any case, provide at least 300mm of free space below the unit.
Additionally, make sure the unit is positioned at least 100 mm above the maximum expected level of snow. See "7.3 Mounting
the outdoor unit"on page24 for more details.
In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.

6.2.3 Installation site requirements of the indoor unit

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
▪ Mind the measurement guidelines:
Maximum refrigerant piping length between indoor unit and outdoor unit
Minimum refrigerant piping length between indoor unit and outdoor unit
Maximum height difference between indoor unit and outdoor unit
Maximum equivalent piping length between the 3‑way valve and the indoor unit (for installations with domestic hot water tank)
Maximum equivalent piping length between the domestic hot water tank and the indoor unit (for installations with domestic hot water tank)
(a) Piping diameter 0.75".
▪ Mind the following spacing installation guidelines:
20m
3m
20m
3m
10m
(a)
(a)

6.2.2 Additional installation site requirements of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up.
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full of water into account. Make sure, in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
Installer reference guide
17
6 Preparation
t
Ø
ØiØ
i
t
ØpØ
p
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging 5~35°C in cooling mode and 5~30°C in heating mode.

6.3 Preparing refrigerant piping

6.3.1 Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Piping material: Phosphoric acid deoxidised seamless copper.
Piping diameter:
Liquid piping Ø6.4mm (1/4")
Gas piping Ø15.9mm (5/8")
Piping temper grade and thickness:
Outer diameter
(Ø)
6.4mm (1/4") Annealed (O) ≥0.8mm
15.9mm (5/8") Annealed (O) ≥1.0mm
(a) Depending on the applicable legislation and the unit's
Temper grade Thickness (t)
maximum working pressure (see "PS High" on the unit name plate), larger piping thickness might be required.
(a)

6.3.2 Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
6.4mm (1/4") 8~10mm 10mm
15.9mm (5/8") 16~20mm 13mm
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.
Insulation inner
diameter (Øi)
Insulation thickness
(t)

6.4 Preparing water piping

6.4.1 Water circuit requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.
Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get damaged.
Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
Closed circuit. Use the indoor unit ONLY in a closed water
system. Using the system in an open water system will lead to excessive corrosion.
Glycol. For safety reasons, it is NOT allowed to add any kind of
glycol to the water circuit.
Piping length. It is recommended to avoid long runs of piping
between the domestic hot water tank and the hot water end point (shower, bath,…) and to avoid dead ends.
Piping diameter. Select the water piping diameter in relation to
the required water flow and the available external static pressure of the pump. See "15 Technical data"on page95 for the external static pressure curves of the indoor unit.
Water flow. You can find the minimum required water flow for
indoor unit operation in the following table. In all cases, this flow needs to be guaranteed. When the flow is lower, the indoor unit will stop operation and display error 7H.
Minimum required flow rate
05 models 7l/min
08 models 8l/min
Field supply components – Water. Only use materials that are
compatible with water used in the system and with the materials used in the indoor unit.
Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the water pressure and water temperature.
Water pressure. The maximum water pressure is 3bar. Provide
adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Water temperature – Heat pump convectors. In case heat
pump convectors are connected, the temperature of the water in the convectors should NOT exceed 65°C. If necessary, install a thermostatic controlled valve.
Water temperature – Underfloor heating loops. In case
underfloor heating loops are connected, install a mixing station to prevent water that is too hot from entering the underfloor heating circuit.
Water temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following temperatures:
INFORMATION
The following illustration is an example and might NOT match your system layout.
Installer reference guide
18
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
M
89°C
RAD1 RAD2 RAD3
95°C
65°C
a b d e
j k
i
c f g
FCU1
FCU2
FCU3
hg
RAD1…3 Radiator (field supply)
c d
a b
Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
Drainage – Pressure relief valve. Provide a proper drain for the
pressure relief valve to avoid water coming into contact with electrical parts.
Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. An automatic air purge is provided in the indoor unit. Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible.
Zn-coated parts. Never use Zn-coated parts in the water circuit.
Because the unit's internal water circuit uses copper piping, excessive corrosion may occur.
Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Valve – Separating circuits. When using a 3-way valve in the
water circuit make sure that the domestic hot water circuit and the floor heating circuit is fully separated.
Valve – Change‑over time. When using a 2-way valve or a 3-way
valve in the water circuit, the maximum change-over time of the valve must be 60seconds.
Filter. It is strongly recommended to install an additional filter on
the heating water circuit. Especially to remove metallic particles from foul heating piping, it is recommended to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.
Dirt separator – Old heating installations. In case of old heating
installations, it is recommended to use a dirt separator. Dirt or sediment from the heating installation can damage the unit and reduce its lifetime. The domestic hot water circuit can also be protected by a filter to prevent failure during domestic hot water operation.
a Outdoor unit
b Indoor unit
c Heat exchanger
d Boiler
e Bypass valve
f Pump g Shut-off valve (field supply) h Motorised 3-way valve (in option kit)
i Collector
j Domestic hot water tank (optional)
k Heat exchanger coil
FCU1...3 Fan coil unit (optional)
6 Preparation
Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water.
Domestic hot water tank – After installation. Immediately after
installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the equipment MUST be flushed with fresh water before usage.
Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "Domestic hot water
control: advanced"on page65.
Domestic hot water tank – 3rd party tank installation. When
installing a 3rd party tank, take following requirements into account:
▪ coil size should be ≥0.45m2,
▪ water piping is ≥3/4" to avoid high pressure drops,
▪ a sensor pocket is foreseen at a correct place (above the
heating coil). The tank sensor should not be in contact with water.
▪ maximum tank set point for a 3rd party tank is 60°C,
▪ in case of an electrical heater in the tank, make sure it is
installed correctly (above the heating coil). Refer to the installation manual of EKHY3PART for more information.
Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing valves.
Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic installation measures.
Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.
a Recirculation connection b Hot water connection c Shower d Recirculation pump

6.4.2 Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)

6.4.3 To check the water volume and flow rate

The indoor unit has an expansion vessel of 10litre with a factory set pre-pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
19
6 Preparation
RAD1 RAD2 RAD3
T
95°C
a b d e
hg
c f
g i
50
0.3
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
2
2.2
2.4
2.6
100 150 200 250 300 350 400 4500
a
b
Minimum water volume
Check that the total water volume in the installation is minimum
13.5litre, the internal water volume of the indoor unit NOT included.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required.
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
a Outdoor unit b Indoor unit c Heat exchanger d Boiler e Bypass valve
f Pump g Shut‑off valve (field supply) h Collector
i Bypass valve (field supply)
RAD1…3 Radiator (field supply)
Maximum water volume
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
Installation
height
difference
(a)
≤280l >280l
≤7m No pre-pressure
adjustment is required.
Water volume
Do the following:
▪ Decrease the pre-
pressure.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
>7m Do the following:
▪ Increase the pre-
pressure.
▪ Check if the water
volume does NOT exceed the maximum
The expansion vessel of the indoor unit is too small for the installation. In this case, it is recommended to install an extra vessel outside the unit.
allowed water volume.
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0m.
Example in case of a radiator application: Maximum water volume and expansion vessel pre-pressure in case of 80°C
Installation
height
difference
(a)
≤140l >140l
≤7m No pre-pressure
adjustment is required.
Water volume
Do the following:
▪ Decrease the pre-
pressure.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
>7m Do the following:
▪ Increase the pre-
pressure.
▪ Check if the water
volume does NOT exceed the maximum
The expansion vessel of the indoor unit is too small for the installation. In this case, it is recommended to install an extra vessel outside the unit.
allowed water volume.
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0m.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup heater operation) in the installation is guaranteed in all conditions.
Example in case of an underfloor heating application: Maximum water volume and expansion vessel pre-pressure in case of 55°C
Installer reference guide
20
a Pre-pressure (bar) b Maximum water volume (l)
Maximum leaving water temperature of 55°C for underfloor heating applications
Maximum leaving water temperature of 80°C for radiator applications
NOTICE
When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating/operation).
Minimum required flow rate
05 models 7l/min
08 models 8l/min
See the recommended procedure as described in "10.4 Checklist
during commissioning"on page81.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
6 Preparation
a

6.4.4 Changing the pre-pressure of the expansion vessel

NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
When changing the default pre-pressure of the expansion vessel (1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel.
a Schräder valve

6.4.5 To check the water volume: Examples

Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required for either underfloor heating loops or radiators.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l. Radiators are installed, so use the graph of 80°C.
Actions:
▪ Because the total water volume (350 l) is more than the default
water volume (140l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 205 l.
(See the graph in the chapter above).
▪ Because 350 l is more than 205l, the expansion vessel is too
small for the installation. Therefore install an extra vessel outside the installation.

6.5 Preparing electrical wiring

WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.

6.5.2 About preferential kWh rate power supply

Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available.
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the gas boiler can still operate to provide heating, but the outdoor unit compressor will NOT operate.
Whether the power supply is interrupted or not, the wiring to the unit is different.

6.5.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
21
6 Preparation
1
5
8
0
1
5
0
0
0
2
a
3
1
4
5
8
0
1
5
0
0
0
2
b
3
5 3
a
b
14
5
8
0
1
5
0
0
0
5
8
0 1
5
0
0
0
2
M
6 10
11 12 13 14 18 20
15
2
7
8
16
c
a
d
b
17 19
3
1 4 5
9

6.5.3 Overview of electrical connections except external actuators

Normal power
supply
Preferential kWh rate power supply
Power supply is NOT interrupted
Power supply is
interrupted
INFORMATION
The following illustration is an example and might NOT match your system layout.
During preferential During preferential kWh rate power supply activation, power supply is NOT interrupted. The outdoor unit is turned off by the control. The gas boiler can still operate.
Remark: The electricity company must always allow the power consumption of the indoor unit.
a Normal power supply b Preferential kWh rate power supply 1 Power supply for outdoor unit 2 Power supply and interconnection cable to indoor unit 3 Power supply for gas boiler 4 Preferential kWh rate power supply (voltage free contact) 5 Normal kWh rate power supply (to power the indoor unit
PCB in the event of power supply interruption of the preferential kWh rate power supply)
The following applies ONLY for the French market: "Bleu Ciel tarif"
In France there is a preferential kWh rate called "Bleu Ciel tarif". This rate divides the days of the year in:
▪ blue days (preferential electricity rate, ideal for heat pump
operation),
▪ white days (ideal for heat pump and hybrid operation),
▪ and red days (high electricity rate, boiler operation preferred).
It is recommended to use the preferential kWh rate power supply contact (4) to force boiler operation during red days. Note that sometimes it is required to set the meter on such that, it only closes the contact on red days. Please refer to the manual of the applicable meter.
The indoor unit and gas boiler are NOT compatible with other combinations of contacts (e.g., closed contacts on white/blue days). Connect the indoor unit and gas boiler as follows: see illustration in column "Power supply is NOT interrupted" in the table above.
6.5.4 Overview of electrical connections for
The following illustration shows the required field wiring.
Installer reference guide
22
external and internal actuators
kWh rate power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
indoor unit must be
powered by a
separate normal
power supply. The
outdoor unit
CANNOT operate,
but the gas boiler can
operate.
a Outdoor unit
b Indoor unit
c Gas boiler
d Domestic hot water tank
Item Description Wires Maximum
running
current
Outdoor unit and indoor unit power supply
1 Power supply for
2+GND
(a)
outdoor unit
2 Power supply and
3+GND
(g)
interconnection cable to indoor unit
3 Power supply gas
2+GND
(c)
boiler
4 Preferential kWh rate
2
(e)
power supply (voltage free contact)
5 Normal kWh rate power
2 6.3A
supply
User interface
6 User interface 2
(f)
Optional equipment
7 3‑way valve 3 100mA
8 Domestic hot water
2
(d)
tank thermistor
9 Power supply for drain
2
(b)
pan heater
10 Room thermostat/heat
3 or 4 100mA
pump convector
11 Outdoor ambient
2
(b)
temperature sensor
12 Indoor ambient
2
(b)
temperature sensor
Field supplied components
13 Shut-off valve 2 100mA
14 Electricity meter 2
15 Domestic hot water
2
(b)
(b)
pump
16 Alarm output 2
17 Changeover to external
2
(b)
(b)
heat source control
18 Space cool/heat
2
(b)
operation control
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
(b)
(b)
(b)

7 Installation

1
2
2
2
4
5
3
Item Description Wires Maximum
19 Power consumption
digital inputs
20 Gas meter 2
(a) Refer to name plate on outdoor unit. (b) Minimum cable section 0.75mm². (c) Use the cable supplied with the boiler. (d) The thermistor and connection wire (12m) are delivered
with the domestic hot water tank.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum applicable load of 15VDC, 10mA.
(f) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual use interface connection.
(g) Cable section 1.5mm2; maximum length: 50m.
NOTICE
More technical specifications of the different connections are indicated on the inside of the indoor unit.
2 (per input signal)
running
current
(b)
(b)
7 Installation

7.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
1 Mounting the outdoor unit.
2 Mounting the indoor unit.
3 Mounting the gas boiler.
4 Connecting the condensate pipe.
5 Connecting the refrigerant piping.
6 Checking the refrigerant piping.
7 Charging refrigerant.
8 Connecting the water piping.
9 Connecting the electrical wiring.
10 Connecting the gas piping.
11 Connecting the boiler to the flue gas system.
12 Finishing the outdoor installation.
13 Finishing the indoor installation.
14 Finishing the gas boiler installation.

7.2.2 To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING

7.2.3 To open the switch box cover of the indoor unit

1 Remove the side panel at the right side of the indoor unit. The
side panel is fixed at the bottom with 1 screw.
2 Remove the upper and lower screw on the side panel of the
switch box.
3 The right panel of the switch box will open.
4 Remove the upper and lower screw on the front panel of the
switch box.
5 The front panel of the switch box will open.
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.

7.2 Opening the units

7.2.1 About opening the units

At certain times, you have to open the unit. Example:
▪ When connecting the refrigerant piping
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
When the boiler is installed and access to the switch box is required, please follow the steps below.
6 Remove the upper and lower screw on the side panel of the
switch box.
7 Remove the switch box from the unit.
8 Hook the switch box to the side of the unit with the hooks
foreseen on the switch box.
Installer reference guide
23
7 Installation
6
6
7
8
1
2
a

7.3 Mounting the outdoor unit

7.2.4 To open the gas boiler

1 Open the display cover.
2 Unscrew both screws.
3 Tilt the front panel towards you and remove the front panel.

7.2.5 To open the switch box cover of the gas boiler

1 Open the gas boiler, see "7.2.4 To open the gas boiler" on
page24.
2 Pull the boiler controller unit forwards. The boiler controller will
tip downwards to provide access.

7.3.1 About mounting the outdoor unit

When
You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping.
Typical workflow
Mounting the outdoor unit typically consists of the following stages:
1 Providing the installation structure.
2 Installing the outdoor unit.
3 Providing drainage.
4 Preventing the outdoor unit from falling over.
5 Protecting the unit against snow and wind by installing a snow
cover and baffle plates. See "Preparing installation site" in
"6Preparation"on page16.

7.3.2 Precautions when mounting the outdoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.3.3 To provide the installation structure

Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise.
Fix the unit securely by means of foundation bolts in accordance with the foundation drawing.
If the unit is installed directly on the floor, prepare 4 sets of M8 or M10 anchor bolts, nuts and washers (field supply) as follows:
INFORMATION
The maximum height of the upper protruding part of the bolts is 15mm.
Installer reference guide
24
NOTICE
Fix the outdoor unit to the foundation bolts using nuts with resin washers (a). If the coating on the fastening area is stripped off, the nuts rust easily.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
283
580
<100
(mm)
<100
>300
In any case, provide at least 300mm of free space below the unit.
283
580
<150
<150
(mm)
>300
100
a
b
>250
>300
>250
(mm)
a
b
Additionally, make sure the unit is positioned at least 100mm above the maximum expected level of snow. In this case, it is recommended to construct a pedestal, and on this pedestal install the EKFT008CA option kit.
7 Installation
a Maximum snowfall height
b EKFT008CA option kit
If the unit is installed on brackets to the wall, it is recommended to use the EKFT008CA option kit and to install the unit as follows:
a Maximum snowfall height b EKFT008CA option kit
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02

7.3.4 To install the outdoor unit

CAUTION
Do NOT remove the protective cardboard before the unit is installed properly.
Installer reference guide
25
7 Installation
2
a a
1
b
a
a
b
283 mm
580 mm
1 Lift the outdoor unit as described in "4.2.2 To remove the
accessories from the outdoor unit"on page9.
2 Install the outdoor unit as follows:
a Air outlet
NOTICE
The pedestal MUST be aligned with the backside of the U‑beam.
3 Remove the protective cardboard and instruction sheet.
An additional drain pan kit (EKDP008CA) can be used to gather the drain water. The drain pan kit consists of:
a Drain pan
b U-beams
a Protective cardboard b Instruction sheet

7.3.5 To provide drainage

▪ Avoid installation places where water leaking from the unit due to
a blocked drain pan, cause damage to the location.
▪ Make sure that condensation water can be evacuated properly.
▪ Install the unit on a base to make sure that there is a proper
drainage in order to avoid ice accumulation.
▪ Prepare a water drainage channel around the foundation to drain
waste water surrounding the unit.
▪ Avoid drain water flowing over the footpath, so that it does not
become slippery in case of ambient freezing temperatures.
▪ If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent the invasion of water in the unit and to avoid the drain water dripping (see the following illustration).
NOTICE
If the drain holes of the outdoor unit are blocked up, provide space of at least 300mm below the outdoor unit.

7.3.6 To prevent the outdoor unit from falling over

In case the unit is installed in places where strong wind can tilt the unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.
Installer reference guide
26
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
7 Installation
21 3
30kg

7.4 Mounting the indoor unit

7.4.1 About mounting the indoor unit

When
You have to mount the outdoor and indoor unit before you can connect the refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1 Installing the indoor unit.

7.4.2 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.4.3 To install the indoor unit

1 Put the installation pattern (see box) on the wall and follow the
steps as shown below.
3 Lift the unit.
4 Tilt the top of the unit against the wall at the position of the wall
bracket.
5 Slide the bracket on the back of the unit over the wall bracket.
Make sure the unit is fixed properly. You can additionally fix the bottom side of the unit with 2 M8 bolts.
6 The unit is mounted to the wall.
2 Fix the wall bracket to the wall with 2 M8 bolts.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
27
7 Installation
36kg

7.5 Mounting the gas boiler

6 Slide the boiler downwards to fix the boiler bracket onto the
indoor unit mounting bracket.
INFORMATION
Removing the top plate of the indoor unit makes it easier to install the gas boiler.

7.5.1 To install the gas boiler

1 Lift the unit from the package.
2 Remove the top plate from the indoor unit.
3 The bracket to mount the boiler on the heat pump module is
already mounted to the backside of the gas boiler.
4 Lift the boiler. One person lifts the gas boiler on the left side (left
hand on the top and right hand on the bottom) and another person lift the gas boiler on the right side (left hand on the bottom and right hand on the top).
5 Tilt the top of the unit at the position of the indoor unit mounting
bracket.
7 Make sure the gas boiler is fixed properly and well aligned with
the indoor unit.

7.5.2 To install the condensate trap

INFORMATION
The boiler is provided with a 25mm flexible pipe on the condensate trap.
Prerequisite: The boiler MUST be opened before installing the condensate trap.
1 Fit the flexible tube (accessory) to the condensate trap outlet.
2 Fill the condensate trap with water.
3 Slide the condensate trap as far as possible upwards onto the
condensate drain connector below the gas boiler.
Installer reference guide
28
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
4 Connect the flexible tube (where applicable with the overflow
Ø22 mm
a
b
c
a
b
c
d
≥75 mm
Ø22 mm
100 mm
pipe from the pressure relief valve) to the drain via an open connection.
7 Installation

7.6 Condensate pipe work

INFORMATION
The condensate discharge system MUST be made of plastic, no other materials may be used. The discharge duct MUST have a minimum gradient of 5~20 mm/m. Condensate discharge via the gutter is NOT allowed due to risk of frost and the possible damage to the materials.

7.6.1 Internal connections

If possible, the condensate drain pipe should be routed and terminated so that the condensate drains away from the boiler under gravity to a suitable internal foul water discharge point such as an internal soil and vent stack. A suitable permanent connection to the foul waste pipe should be used.
a Condensate discharge from boiler b Soil and vent stack c Minimum 450mm and up to 3 storeys
If the first option is NOT possible, an internal kitchen or bathroom
WARNING
▪ ALWAYS fill the condensate trap with water and place
it on the boiler before powering up the boiler. See illustration below.
▪ NOT placing or filling up the condensate trap may
cause flue gases to come into the installation room and can lead to dangerous situations!
▪ In order to place the condensate trap, the front cover
MUST be pulled forward or removed entirely.
NOTICE
It is recommended that any external condensate pipe is insulated and increased to Ø32mm in order to prevent the condensate from freezing.
waste pipe, washing machine pipe can be used. Make sure that the condensate drain pipe is connected downstream of the waste trap.
a Condensate discharge from boiler b Soil and vent stack c Sink or basin with integrate overflow d 75mm waste trap and air break
Condensate pump
Where gravity discharge to an internal termination is NOT physically possible or where very long internal runs of drainage pipe would be required to reach a suitable discharge point, condensate should be removed by using a proprietary condensate pump (field supply).
The pump outlet pipe should discharge to a suitable internal foul water discharge point such as an internal soil and vent stack, internal kitchen, bathroom waste pipe, or washing machine waste pipe. A suitable permanent connection to the foul waste pipe should be used.
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA + RHYKOMB33AA ROTEX HPU hybrid 4P355635-1A – 2016.02
Installer reference guide
29
7 Installation
Ø22 mm
c
≥75 mm
a
b
d
e
a Condensate discharge from boiler b Soil and vent stack c Sink or basin with integrated overflow d 75mm waste trap and air break e Condensate pump

7.7.2 Precautions when connecting the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ Do NOT reuse piping from previous installations.
▪ NEVER install a drier to this R410A unit to guarantee
its lifetime. The drying material may dissolve and damage the system.

7.6.2 External connections

If an externally condensate drainage pipe is used, following measures should be made to prevent freezing:
▪ The pipe should be run internally as far as possible before going
to the outside. The pipe diameter should be increased to a minimum inner diameter of 30 mm (typically outer diameter of 32mm) before it goes through the wall.
▪ The external run should be kept as short as possible, taking the
most vertical route possible to the discharge point. Take into account that there are no horizontal section in which condensate might collect.
▪ The external pipe should be insulated. Use a suitable waterproof
and weather proof insulation ("ClassO" pipe insulation is suitable for this purpose).
▪ The use of fittings and elbows should be kept to a minimum. Any
internal burrs should be removed so that the internal pipe section is as smooth as possible.

7.7 Connecting the refrigerant piping

7.7.1 About connecting the refrigerant piping

Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the outdoor unit
▪ Connecting the refrigerant piping to the indoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Brazing
▪ Using the stop valves
NOTICE
Take the following precautions on refrigerant piping into account:
▪ Avoid anything but the designated refrigerant to get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R410A when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
▪ Install the piping so that the flare is NOT subjected to
mechanical stress
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use caution when passing copper tubes through walls
(see figure below).
Unit Installation period Protection method
Outdoor unit >1month Pinch the pipe
<1month Pinch or tape the pipe
Indoor unit Regardless of the
period
INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging.

7.7.3 Guidelines when connecting the refrigerant piping

Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before tightening firmly.
Installer reference guide
30
RVLQ05+08CAV4 + RHYHBH05AA + RHYHBH/X08AA +
RHYKOMB33AA
ROTEX HPU hybrid
4P355635-1A – 2016.02
Loading...
+ 98 hidden pages