Daikin RRGA04DAV3, RRGA06DAV3, RRGA08DAV3, RHBX04DA6V, RHBX04DA9W Installer reference guide

...
+
Installer reference guide
ROTEX HPSU Bi-Bloc Ultra
RRGA04DAV3 RRGA06DAV3 RRGA08DAV3
Installer reference guide
ROTEX HPSU Bi-Bloc Ultra
English

Table of contents

Table of contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the installer.......................................................................... 4
1.2.1 General ....................................................................... 4
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 4
1.2.4 Brine............................................................................ 5
1.2.5 Water .......................................................................... 5
1.2.6 Electrical ..................................................................... 6
2 About the documentation 6
2.1 About this document.................................................................. 6
2.2 Installer reference guide at a glance ......................................... 7
3 About the box 7
3.1 Overview: About the box ........................................................... 7
3.2 Outdoor unit............................................................................... 7
3.2.1 To unpack the outdoor unit ......................................... 7
3.2.2 To handle the outdoor unit.......................................... 7
3.2.3 To remove the accessories from the outdoor unit....... 8
3.3 Indoor unit ................................................................................. 8
3.3.1 To unpack the indoor unit ........................................... 8
3.3.2 To remove the accessories from the indoor unit......... 8
4 About the units and options 8
4.1 Overview: About the units and options...................................... 8
4.2 Identification .............................................................................. 8
4.2.1 Identification label: Outdoor unit ................................. 8
4.2.2 Identification label: Indoor unit .................................... 9
4.3 Combining units and options ..................................................... 9
4.3.1 Possible options for the outdoor unit........................... 9
4.3.2 Possible options for the indoor unit............................. 9
4.3.3 Possible combinations of indoor unit and outdoor
unit .............................................................................. 10
4.3.4 Possible combinations of indoor unit and domestic
hot water tank ............................................................. 10
5 Application guidelines 10
5.1 Overview: Application guidelines............................................... 10
5.2 Setting up the space heating/cooling system ............................ 10
5.2.1 Single room................................................................. 10
5.2.2 Multiple rooms – OneLWT zone ................................ 12
5.2.3 Multiple rooms – TwoLWT zones............................... 14
5.3 Setting up an auxiliary heat source for space heating............... 15
5.4 Setting up the domestic hot water tank ..................................... 16
5.4.1 System layout – Standalone DHW tank...................... 16
5.4.2 Selecting the volume and desired temperature for
the DHW tank.............................................................. 16
5.4.3 Setup and configuration – DHW tank.......................... 17
5.4.4 DHW pump for instant hot water................................. 17
5.4.5 DHW pump for disinfection ......................................... 17
5.4.6 DHW pump for tank preheating .................................. 18
5.5 Setting up the energy metering ................................................. 18
5.5.1 Produced heat............................................................. 18
5.5.2 Consumed energy....................................................... 18
5.5.3 Normal kWh rate power supply................................... 18
5.5.4 Preferential kWh rate power supply............................ 19
5.6 Setting up the power consumption control ................................ 19
5.6.1 Permanent power limitation ........................................ 19
5.6.2 Power limitation activated by digital inputs ................. 20
5.6.3 Power limitation process ............................................. 20
5.7 Setting up an external temperature sensor ............................... 20
6 Preparation 21
6.1 Overview: Preparation............................................................... 21
6.2 Preparing the installation site .................................................... 21
6.2.1 Installation site requirements of the outdoor unit ......... 21
6.2.2 Additional installation site requirements of the
outdoor unit in cold climates ........................................ 22
6.2.3 Installation site requirements of the indoor unit ........... 23
6.3 Preparing refrigerant piping........................................................ 25
6.3.1 Refrigerant piping requirements................................... 25
6.3.2 Refrigerant piping insulation ........................................ 25
6.4 Preparing water piping ............................................................... 25
6.4.1 Water circuit requirements ........................................... 25
6.4.2 Formula to calculate the expansion vessel pre-
pressure ....................................................................... 26
6.4.3 To check the water volume and flow rate .................... 26
6.4.4 Changing the pre-pressure of the expansion vessel.... 27
6.4.5 To check the water volume: Examples ........................ 28
6.5 Preparing electrical wiring .......................................................... 28
6.5.1 About preparing electrical wiring.................................. 28
6.5.2 About preferential kWh rate power supply ................... 28
6.5.3 Overview of electrical connections except external
actuators ...................................................................... 29
6.5.4 Overview of electrical connections for external and
internal actuators ......................................................... 29
7 Installation 29
7.1 Overview: Installation ................................................................. 29
7.2 Opening the units ....................................................................... 30
7.2.1 About opening the units ............................................... 30
7.2.2 To open the outdoor unit.............................................. 30
7.2.3 To open the indoor unit ................................................ 30
7.3 Mounting the outdoor unit........................................................... 31
7.3.1 About mounting the outdoor unit.................................. 31
7.3.2 Precautions when mounting the outdoor unit............... 31
7.3.3 To provide the installation structure ............................. 31
7.3.4 To install the outdoor unit............................................. 32
7.3.5 To provide drainage ..................................................... 33
7.3.6 To prevent the outdoor unit from falling over ............... 33
7.4 Mounting the indoor unit............................................................. 34
7.4.1 About mounting the indoor unit.................................... 34
7.4.2 Precautions when mounting the indoor unit................. 34
7.4.3 To install the indoor unit............................................... 34
7.4.4 To connect the drain hose to the drain ........................ 35
7.5 Connecting the refrigerant piping ............................................... 35
7.5.1 About connecting the refrigerant piping ....................... 35
7.5.2 Precautions when connecting the refrigerant piping.... 35
7.5.3 Guidelines when connecting the refrigerant piping...... 35
7.5.4 Pipe bending guidelines............................................... 36
7.5.5 To flare the pipe end .................................................... 36
7.5.6 To braze the pipe end .................................................. 36
7.5.7 Using the stop valve and service port .......................... 36
7.5.8 To connect the refrigerant piping to the outdoor unit ... 37
7.5.9 To connect the refrigerant piping to the indoor unit ..... 37
7.6 Checking the refrigerant piping .................................................. 37
7.6.1 About checking the refrigerant piping .......................... 37
7.6.2 Precautions when checking the refrigerant piping ....... 38
7.6.3 To check for leaks........................................................ 38
7.6.4 To perform vacuum drying ........................................... 38
7.7 Charging refrigerant ................................................................... 38
7.7.1 About charging refrigerant ........................................... 38
7.7.2 Precautions when charging refrigerant ........................ 39
7.7.3 To determine the additional refrigerant amount........... 39
7.7.4 To determine the complete recharge amount.............. 39
7.7.5 To charge additional refrigerant ................................... 39
7.7.6 To fix the fluorinated greenhouse gases label ............. 39
7.8 Connecting the water piping....................................................... 39
7.8.1 About connecting the water piping............................... 39
7.8.2 Precautions when connecting the water piping............ 40
7.8.3 To connect the water piping......................................... 40
7.8.4 To fill the water circuit .................................................. 40
7.8.5 To fill the domestic hot water tank ............................... 41
7.8.6 To insulate the water piping ......................................... 41
7.9 Connecting the electrical wiring.................................................. 41
Installer reference guide
2
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11

1 General safety precautions

7.9.1 About connecting the electrical wiring......................... 41
7.9.2 About electrical compliance ........................................ 41
7.9.3 Precautions when connecting the electrical wiring ..... 41
7.9.4 Guidelines when connecting the electrical wiring ....... 41
7.9.5 Specifications of standard wiring components............ 41
7.9.6 To connect the electrical wiring on the outdoor unit.... 42
7.9.7 To connect the electrical wiring on the indoor unit...... 42
7.9.8 To connect the main power supply ............................. 43
7.9.9 To connect the backup heater power supply .............. 43
7.9.10 To connect the shut-off valve ...................................... 45
7.9.11 To connect the electrical meters ................................. 45
7.9.12 To connect the domestic hot water pump ................... 45
7.9.13 To connect the alarm output ....................................... 45
7.9.14 To connect the space cooling/heating ON/OFF
output .......................................................................... 45
7.9.15 To connect the changeover to external heat source ... 45
7.9.16 To connect the power consumption digital inputs ....... 46
7.9.17 To connect the safety thermostat (normal closed
contact) ....................................................................... 46
7.10 Finishing the outdoor unit installation ........................................ 46
7.10.1 To finish the outdoor unit installation .......................... 46
7.11 Finishing the indoor unit installation .......................................... 46
7.11.1 To close the indoor unit............................................... 46
8 Configuration 46
8.1 Overview: Configuration ............................................................ 46
8.1.1 To access the most used commands ......................... 47
8.2 Configuration wizard.................................................................. 47
8.3 Possible screens ....................................................................... 48
8.3.1 Possible screens: Overview........................................ 48
8.3.2 Home screen............................................................... 48
8.3.3 Main menu screen ...................................................... 49
8.3.4 Menu screen ............................................................... 49
8.3.5 Setpoint screen........................................................... 49
8.3.6 Detailed screen with values ........................................ 50
8.3.7 Detailed screen with weather-dependent curve.......... 50
8.3.8 Schedule screen: Example ......................................... 50
8.4 Settings menu ........................................................................... 52
8.4.1 Malfunction.................................................................. 52
8.4.2 Room .......................................................................... 52
8.4.3 Main zone ................................................................... 53
8.4.4 Additional zone ........................................................... 57
8.4.5 Space heating/cooling................................................. 59
8.4.6 Tank ............................................................................ 62
8.4.7 User settings ............................................................... 65
8.4.8 Information .................................................................. 67
8.4.9 Installer settings .......................................................... 67
8.5 Menu structure: Overview user settings .................................... 76
8.6 Menu structure: Overview installer settings............................... 77
11.5.3 To install the water filter ............................................... 83
12 Troubleshooting 84
12.1 Overview: Troubleshooting......................................................... 84
12.2 Precautions when troubleshooting ............................................. 84
12.3 Solving problems based on symptoms....................................... 84
12.3.1 Symptom: The unit is NOT heating or cooling as
expected ...................................................................... 84
12.3.2 Symptom: The compressor does NOT start (space
heating or domestic water heating).............................. 85
12.3.3 Symptom: The system is making gurgling noises
after commissioning ..................................................... 85
12.3.4 Symptom: The pump is making noise (cavitation) ....... 85
12.3.5 Symptom: The pressure relief valve opens.................. 85
12.3.6 Symptom: The water pressure relief valve leaks ......... 86
12.3.7 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ............................................ 86
12.3.8 Symptom: The pressure at the tapping point is
temporarily unusually high ........................................... 86
12.3.9 Symptom: Decoration panels are pushed away due
to a swollen tank .......................................................... 86
12.3.10 Symptom: Tank disinfection function is NOT
completed correctly (AH-error)..................................... 86
12.4 Solving problems based on error codes ..................................... 87
12.4.1 To display the help text in case of a malfunction ......... 87
12.4.2 Error codes: Overview ................................................. 87
13 Disposal 88
13.1 Overview: Disposal..................................................................... 88
13.2 To pump down............................................................................ 88
13.3 To start and stop forced cooling ................................................. 89
14 Technical data 90
14.1 Piping diagram: Outdoor unit...................................................... 90
14.2 Piping diagram: Indoor unit ........................................................ 91
14.3 Wiring diagram: Outdoor unit ..................................................... 92
14.4 Wiring diagram: Indoor unit ........................................................ 93
14.5 Table 1 – Maximum refrigerant charge allowed in a room:
indoor unit................................................................................... 96
14.6 Table 2 – Minimum floor area: indoor unit .................................. 96
14.7 Table 3 – Minimum venting opening area for natural
ventilation: indoor unit ................................................................ 97
14.8 ESP curve: Indoor unit ............................................................... 98
15 Glossary 98
16 Field settings table 99
1 General safety precautions
9 Commissioning 78
9.1 Overview: Commissioning......................................................... 78
9.2 Precautions when commissioning ............................................. 78
9.3 Checklist before commissioning................................................ 78
9.4 Checklist during commissioning ................................................ 78
9.4.1 To check the minimum flow rate ................................. 79
9.4.2 Air purge function........................................................ 79
9.4.3 To perform an operation test run ................................ 79
9.4.4 To perform an actuator test run .................................. 80
9.4.5 Underfloor heating screed dryout................................ 80
10 Hand-over to the user 81
11 Maintenance and service 81
11.1 Overview: Maintenance and service ......................................... 81
11.2 Maintenance safety precautions................................................ 81
11.3 Checklist for yearly maintenance of the outdoor unit ................ 81
11.4 Checklist for yearly maintenance of the indoor unit................... 82
11.5 About cleaning the water filter in case of trouble....................... 83
11.5.1 To remove the water filter ........................................... 83
11.5.2 To clean the water filter in case of trouble .................. 83
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide MUST be performed by an authorised installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
Installer reference guide
3
1 General safety precautions
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.

1.2 For the installer

1.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by ROTEX.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the ROTEX documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

1.2.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
Installer reference guide
4

1.2.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
1 General safety precautions
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the system into the outdoor unit. Possible consequence: Self-combustion and explosion of the compressor because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant MUST be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.
Charge with the cylinder upright.
down.

1.2.4 Brine

If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.2.5 Water

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
5

2 About the documentation

1.2.6 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply, the earth connection must be made before the current-carrying connections are established. When disconnecting the power supply, the current-carrying connections must be separated before the earth connection is. The length of the conductors between the power supply stress relief and the terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure above.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation

2.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
Installer reference guide
6
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11

3 About the box

1 2
2
1
1
Installer reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Format: Digital files on the ROTEX homepage
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
the ROTEX homepage
Latest revisions of the supplied documentation may be available on the regional ROTEX website or via your dealer.
The original documentation is written in English. All other languages are translations.

2.2 Installer reference guide at a glance

Chapter Description
General safety precautions
About the documentation What documentation exists for the
About the box How to unpack the units and remove
About the units and options
Application guidelines Various installation setups of the system
Preparation What to do and know before going
Installation What to do and know to install the
Configuration What to do and know to configure the
Commissioning What to do and know to commission the
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
Safety instructions that you must read before installing
installer
their accessories
▪ How to identify the units
▪ Possible combinations of units and
options
on‑site
system
system after it is installed
system after it is configured
kept for future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.
▪ Prepare the path along which you want to bring the unit inside in
advance.

3.2 Outdoor unit

3.2.1 To unpack the outdoor unit

3.2.2 To handle the outdoor unit

CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
1 Handle the unit using the sling to the left and the handle to the
right. Pull up both sides of the sling at the same time to prevent disconnection of the sling from the unit.
3 About the box

3.1 Overview: About the box

This chapter describes what you have to do after the boxes with the outdoor and indoor unit are delivered on-site.
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
2 While handling the unit:
Installer reference guide
7

4 About the units and options

ENERG
IJAY IAIE
ENERG
IJAY IAIE
da b c e f
1 2
a b c d
fe g
h
▪ Keep both sides of the sling level. ▪ Keep your back straight.
3 After mounting the unit, remove the sling from the unit by pulling
1 side of the sling.

3.2.3 To remove the accessories from the outdoor unit

1 Lift the outdoor unit. See "3.2.2 To handle the outdoor unit"on
page7.
2 Remove the accessories at the bottom of the package.

3.3.2 To remove the accessories from the indoor unit

Some accessories are located inside the unit. To open the unit, see
"7.2.3To open the indoor unit"on page30.
a General safety precautions b Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut-off valve
f Shut-off valve g Overpressure bypass valve h Wall bracket
a Outdoor unit installation manual b Fluorinated greenhouse gases label c Multilingual fluorinated greenhouse gases label d Energy label e Unit mounting plate
f Bolts, nuts, washers, spring washers and wire clamp

3.3 Indoor unit

3.3.1 To unpack the indoor unit

4 About the units and options

4.1 Overview: About the units and options

This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the indoor unit
▪ Combining the outdoor unit with options
▪ Combining the indoor unit with options

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Outdoor unit

Location
Installer reference guide
8
Model identification
Example: RRGA06DAV3
Code Explanation
RR Split outdoor pair heat pump
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
4 About the units and options
Code Explanation
G Medium water temperature – ambient zone: −10~
−20°C
A Refrigerant R32
06 Capacity class
DA Model series
V3 Power supply

4.2.2 Identification label: Indoor unit

Location
Model identification
Example: RHBX04DA6V
Code Description
R ROTEX model
HB Wall-mounted indoor unit
X Heating/cooling
04 Capacity class
DA Model series
6V Backup heater model

4.3 Combining units and options

4.3.1 Possible options for the outdoor unit

Drain pan kit (EKDP008D)
The drain pan kit is required to gather the drain from the outdoor unit. The drain pan kit consists of:
▪ Drain pan
▪ Installation brackets
For installation instructions, see the installation manual of the drain pan.
Drain pan heater (EKDPH008CA)
The drain pan heater is required to avoid freezing-up of the drain pan.
It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the drain pan heater.
U-beams (EKFT008D)
The U-beams are installation brackets on which the outdoor unit can be installed.
It is recommended to install this option in colder regions with possible low ambient temperatures or heavy snowfall.
For installation instructions, see the installation manual of the outdoor unit.
Low sound cover (EKLN08A1)
In sound sensitive areas (e.g. near a bedroom), you can install the low sound cover to decrease the operation noise of the outdoor unit.
You can install the low sound cover:
▪ On mounting feet to the ground. This must withstand 200kg.
▪ On brackets to the wall. This must withstand 200kg.
If you install the low sound cover, you also need to install one of the following options:
▪ Recommended: Drain pan kit (with or without drain pan heater)
▪ U-beams
For installation instructions, see the installation manual of the low sound cover.

4.3.2 Possible options for the indoor unit

Room thermostat (RKRTWA, RKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (RKRTWA) or wireless (RKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (RKRTR1).
For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating/cooling On/OFF output
▪ Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor sensor.
PC cable (EKPCCAB)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable and "8Configuration"on page46.
Heat pump convector (RFWXV)
For providing space heating/cooling, it is possible to use heat pump convectors (RFWXV).
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
9

5 Application guidelines

B
A
a
For installation instructions, refer to the installation manual of the heat pump convectors, and the addendum book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter.

4.3.3 Possible combinations of indoor unit and outdoor unit

Indoor unit Outdoor unit
RRGA04 RRGA06 RRGA08
RHBX04 O
RHBX08 O O

4.3.4 Possible combinations of indoor unit and domestic hot water tank

Indoor unit Domestic hot water tank
HYC
RHBX04 O
RHBX08 O
5 Application guidelines

5.2 Setting up the space heating/ cooling system

The heatpump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
▪ How many rooms are heated or cooled by the ROTEX heatpump
system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating/cooling requirements are clear, ROTEX recommends to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set Emergency [9.5] to Automatic.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this valve might not be shown on the illustrations.

5.2.1 Single room

Underfloor heating or radiators – Wired room thermostat
Setup

5.1 Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the ROTEX heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant
for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
▪ For more information about the configuration settings to
optimize heatpump operation, see "8Configuration"on
page46.
This chapter contains application guidelines for:
▪ Setting up the space heating/cooling system
▪ Setting up an auxiliary heat source for space heating
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption control
▪ Setting up an external temperature sensor
A Main leaving water temperature zone B One single room
a User interface used as room thermostat
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as a room thermostat (optional equipment EKRUDAS).
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
2 (Room thermostat): Unit operation is decided based on the ambient temperature of the user interface.
Installer reference guide
10
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
5 Application guidelines
B
A
b
a
B
A
a
Setting Value
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
Benefits
Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation). This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
Easy. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…c
0 (Single zone): Main
Underfloor heating or radiators – Wireless room thermostat
Setup
Benefits
Wireless. The ROTEX external room thermostat is available in a
wireless version.
Efficiency. Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heatpump system.
Heatpump convectors
Setup
A Main leaving water temperature zone B One single room
a Remote controller of the heatpump convectors
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/35 and X2M/30).
▪ The space operation mode is sent to the heatpump convectors by
one digital output on the indoor unit (X2M/4 and X2M/3).
A Main leaving water temperature zone B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment RKRTR1).
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main zone:
▪ #: [2.A]
▪ Code: [C-05]
1 (External room thermostat): Unit operation is decided by the external thermostat.
0 (Single zone): Main
1 (1 contact): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
INFORMATION
When using multiple heat pump convectors, make sure each one receives the infrared signal from the remote controller of the heatpump convectors.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main zone:
▪ #: [2.A]
▪ Code: [C-05]
Benefits
Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
Efficiency. Optimal energy efficiency because of the interlink
function.
Stylish.
1 (External room thermostat): Unit operation is decided by the external thermostat.
0 (Single zone): Main
1 (1 contact): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
11
5 Application guidelines
B
A
a
M1
T
B C
A
a
Combination: Underfloor heating + Heatpump convectors
▪ Space heating is provided by:
▪ The underfloor heating
▪ The heatpump convectors
▪ Space cooling is provided by the heatpump convectors only. The
underfloor heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone B One single room
a Remote controller of the heatpump convectors
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ A shut-off valve (field supply) is installed before the under floor
heating to prevent condensation on the floor during cooling operation.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on the indoor unit (X2M/35 and X2M/30).
▪ The space operation mode is sent by one digital output (X2M/4
and X2M/3) on the indoor unit to:
▪ The heatpump convectors
▪ The shut-off valve
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main zone:
▪ #: [2.A]
▪ Code: [C-05]
Benefits
Cooling. Heat pump convectors provide, besides heating
capacity, also excellent cooling capacity.
Efficiency. Under floor heating has the best performance with
ROTEX HPSU.
Installer reference guide
1 (External room thermostat): Unit operation is decided by the external thermostat.
0 (Single zone): Main
1 (1 contact): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
12
Comfort. The combination of the two heat emitter types provides:
▪ The excellent heating comfort of the underfloor heating
▪ The excellent cooling comfort of the heatpump convectors
5.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, you do NOT need a mixing valve station (cost effective).
Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters.
Underfloor heating or radiators – Thermostatic valves
If you are heating up rooms with under floor heating or radiators, a very common way is to control the temperature of the main room by using a thermostat (this can either be the user interface or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature.
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a User interface used as room thermostat
▪ The under floor heating of the main room is directly connected to
the indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as a room thermostat (optional equipment EKRUDAS).
▪ A thermostatic valve is installed before the under floor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source. Example: Fireplaces.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
Benefits
Easy. Same installation as for one room, but with thermostatic
valves.
2 (Room thermostat): Unit operation is decided based on the ambient temperature of the user interface.
0 (Single zone): Main
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
5 Application guidelines
M2M1
B C
A
a a
b
B
A
a a
C
b
B C
A
a
M1
M1
Underfloor heating or radiators – Multiple external room thermostats
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat
b Bypass valve
▪ For each room, a shut-off valve (field supplied) is installed to avoid
leaving water supply when there is no heating or cooling demand.
▪ A bypass valve must be installed to make water recirculation
possible when all shut-off valves are closed. To guarantee reliable operation, provide a minimum water flow as described in table "To check the water volume and flow rate" in "6.4 Preparing water
piping"on page25.
▪ The user interface connected on the indoor unit decides the space
operation mode. Mind that the operation mode on each room thermostat must be set to match the indoor unit.
▪ The room thermostats are connected to the shut-off valves, but do
NOT have to be connected to the indoor unit. The indoor unit will supply leaving water all the time, with the possibility to program a leaving water schedule.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
0 (Leaving water): Unit operation is decided based on the leaving water temperature.
0 (Single zone): Main
B Room 1 C Room 2
a Remote controller of the heatpump convectors
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The user interface connected on the indoor unit decides the space
operation mode.
▪ The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on the indoor unit (X2M/35 and X2M/30). The indoor unit will only supply leaving water temperature when there is an actual demand.
INFORMATION
To increase comfort and performance, ROTEX recommends to install the valve kit option EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
1 (External room thermostat): Unit operation is decided by the external thermostat.
▪ Code: [C-07]
Number of water temperature
0 (Single zone): Main
zones:
▪ #: [4.4]
▪ Code: [7-02]
Benefits
Compared with heatpump convectors for one room:
Comfort. You can set the desired room temperature, including
schedules, for each room via the remote controller of the heatpump convectors.
Combination: Underfloor heating + Heatpump convectors – Multiple rooms
Setup
Benefits
Compared with underfloor heating or radiators for one room:
Comfort. You can set the desired room temperature, including
schedules, for each room via the room thermostats.
Heatpump convectors – Multiple rooms
Setup
A Main leaving water temperature zone
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat b Remote controller of the heatpump convectors
▪ For each room with heat pump convectors: The heat pump
convectors are directly connected to the indoor unit.
▪ For each room with under floor heating: Two shut-off valves (field
supply) are installed before the underfloor heating:
▪ A shut-off valve to prevent hot water supply when the room has
no heating demand
▪ A shut-off valve to prevent condensation on the floor during
cooling operation of the rooms with heatpump convectors.
▪ For each room with heat pump convectors: The desired room
temperature is set via the remote controller of the heat pump convectors.
Installer reference guide
13
5 Application guidelines
B
A
a a
C
E
D
b
c
d
▪ For each room with under floor heating: The desired room
temperature is set via the external room thermostat (wired or wireless).
▪ The user interface connected to the indoor unit decides the space
operation mode. Mind that the operation mode on each external room thermostat and remote controller of the heat pump convectors must be set to match the indoor unit.
INFORMATION
To increase comfort and performance, ROTEX recommends to install the valve kit option EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
0 (Leaving water): Unit operation is decided based on the leaving water temperature.
▪ Code: [C-07]
Number of water temperature
0 (Single zone): Main
zones:
▪ #: [4.4]
▪ Code: [7-02]
5.2.3 Multiple rooms – TwoLWT zones
If the heat emitters selected for each room are designed for different leaving water temperatures, you can use different leaving water temperature zones (maximum 2).
In this document:
▪ Main zone = Zone with the lowest design temperature in heating,
and the highest design temperature in cooling
▪ Additional zone = Zone with the highest design temperature in
heating, and the lowest design temperature in cooling.
CAUTION
When there is more than one leaving water zone, you must ALWAYS install a mixing valve station in the main zone to decrease (in heating)/increase (in cooling) the leaving water temperature when the additional zone has demand.
Typical example:
Room (zone) Heat emitters: Design
Living room (main zone) Underfloor heating:
▪ In heating: 35°C
▪ In cooling: 20°C (only
Bed rooms (additional zone) Heatpump convectors:
▪ In heating: 45°C
▪ In cooling: 12°C
temperature
refreshment, no real cooling allowed)
Setup
A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone E Room 3
a Remote controller of the heatpump convectors b User interface used as room thermostat c Mixing valve station d Pressure regulating valve
INFORMATION
A pressure regulating valve should be implemented before the mixing valve station. This is to guarantee the correct water flow balance between the main leaving water temperature zone and the additional leaving water temperature zone in relation to the required capacity of both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the underfloor heating.
▪ The pump of the mixing valve station is controlled by the ON/
OFF signal on the indoor unit (X2M/29 and X2M/21; normal closed shut-off valve output).
▪ The room temperature is controlled by the user interface, which
is used as room thermostat (optional equipment EKRUDAS).
▪ For the additional zone:
▪ The heat pump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors for each room.
▪ The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on the indoor unit (X2M/35 and X2M/30). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
▪ The user interface connected to the indoor unit decides the space
operation mode. Mind that the operation mode on each remote controller of the heatpump convectors must be set to match the indoor unit.
Installer reference guide
14
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
5 Application guidelines
a b c d e f g h j
FHL1
FHL2
FHL3
M
h
i
il
k
f
m
n
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
2 (Room thermostat): Unit operation is decided based on the ambient temperature of the user interface.
Note:
▪ Main room = user interface
used as room thermostat functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature
1 (Dual zone): Main + additional
zones:
▪ #: [4.4]
▪ Code: [7-02]
In case of heatpump convectors:
External room thermostat for the additional zone:
▪ #: [3.A]
▪ Code: [C-06]
1 (1 contact): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition. No separation between heating or cooling demand.
Shut-off valve output Set to follow the thermo demand
of the main zone.
Shut-off valve If the main zone must be shut off
during cooling mode to prevent condensation on the floor, set it accordingly.
At the mixing valve station Set the desired main leaving
water temperature for heating and/or cooling.
INFORMATION
▪ During heating operation of the heat pump, the
heat pump operates to achieve the desired temperature set via the user interface. When weather­dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.
▪ During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water temperature set via the auxiliary boiler controller.
Setup
▪ Integrate the auxiliary boiler as follows:
Benefits
Comfort.
▪ The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the actual room temperature (modulation).
▪ The combination of the two heat emitter systems provides the
excellent heating comfort of the under floor heating, and the excellent cooling comfort of the heatpump convectors.
Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of the different heat emitters.
▪ Under floor heating has the best performance with ROTEX
HPSU.
5.3 Setting up an auxiliary heat source
▪ Space heating can be done by:
▪ The indoor unit
▪ An auxiliary boiler (field supply) connected to the system
▪ When the room thermostat requests heating, the indoor unit or the
auxiliary boiler starts operating depending on the outdoor temperature (status of the changeover to external heat source). When the permission is given to the auxiliary boiler, the space heating by the indoor unit is turned OFF.
▪ Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the indoor unit.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
for space heating
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve g Motorised 3‑way valve (delivered with DHW tank) h Non-return valve (field supply)
i Shut-off valve (field supply)
j Collector (field supply) k Auxiliary boiler (field supply)
l Aquastat valve (field supply)
m DHW tank
n Heat exchanger coil
FHL1...3 Underfloor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ ROTEX is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
▪ Make sure the return water to the heatpump does NOT exceed
55°C. To do so:
▪ Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
▪ Install an aquastat valve in the return water flow of the
heatpump.
▪ Set the aquastat valve to close above 55°C and to open below
55°C.
▪ Install non-return valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already pre-mounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HB).
Installer reference guide
15
5 Application guidelines
L
N
H
Com
A
K2AK1A
X2M
B
TI
K2AK1A
Indoor/Auto/Boiler
3530 X Y
Indoor
FHL1
FHL2
FHL3
M
a b c d e hf g
f
i j
▪ Connect X1 and X2 (changeover to external heat source) on the
digital I/O PCB to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see "5.2Setting up the space heating/
cooling system"on page10.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between indoor unit and auxiliary boiler.
▪ Because the outdoor temperature is measured by the
outdoor unit air thermistor, install the outdoor unit in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see "5.2 Setting up the space
heating/cooling system"on page10).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ …
▪ Setup: Connect the following field wiring:
BTIBoiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of indoor unit (field supply) K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between indoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.
Installer reference guide
16

5.4 Setting up the domestic hot water tank

5.4.1 System layout – Standalone DHW tank

a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve g Motorised 3‑way valve h Collector (field supply)
i DHW tank j Heat exchanger coil
FHL1...3 Underfloor heating

5.4.2 Selecting the volume and desired temperature for the DHW tank

People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the volume and desired temperature for the DHW
tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using typical water volumes:
Question Typical water volume
How many showers are needed per day?
How many baths are needed per day?
How much water is needed at the kitchen sink per day?
Are there any other domestic hot water needs?
Example: If the DHW consumption of a family (4 persons) per day is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
1shower = 10min×10l/min = 100l
1bath = 150l
1sink = 2min×5l/min = 10l
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
5 Application guidelines
c f
a b
g
h
i
c a b
d f
e g
h
i
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
Determining the volume and desired temperature for the DHW tank
Formula Example
V1=V2+V2×(T2−40)/(40−T1) If:
▪ V2=180l
▪ T2=54°C
▪ T1=15°C
Then V1=280l
V2=V1×(40−T1)/(T2−T1) If:
▪ V1=480l
▪ T2=54°C
▪ T1=15°C
Then V2=307l
V1DHW consumption (equivalent hot water volume at 40°C) V2Required DHW tank volume if only heated once T2DHW tank temperature T1Cold water temperature
Possible DHW tank volumes
Type Possible volumes
Standalone DHW tank ▪ 150l
▪ 180l
▪ 200l
▪ 250l
▪ 300 l (polypropylene tank is
compatible with solar kit)
▪ 500l (compatible with solar kit)
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the desired DHW tank temperature.
▪ The heatpump itself can produce domestic hot water of maximum
55°C (50°C if outdoor temperature is low). The electrical resistance integrated in the heat pump can increase this temperature. However, this consumes more energy. ROTEX recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.
▪ The higher the outdoor temperature, the better the performance of
the heatpump.
▪ If energy prices are the same during the day and the night,
ROTEX recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, ROTEX
recommends to heat up the DHW tank during the night.
▪ When the heatpump produces domestic hot water, it cannot heat
up a space. In case you need domestic hot water and space heating at the same, ROTEX recommends to produce the domestic hot water during the night when there is lower space heating demand.

5.4.3 Setup and configuration – DHW tank

▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heatpump
▪ Electrical booster heater
▪ For more information about:
▪ Optimizing the energy consumption for producing domestic hot
water, see "8Configuration"on page46.
▪ Connecting the electrical wiring of the standalone DHW tank to
the indoor unit, see the installation manual of the DHW tank.
▪ Connecting the water piping of the standalone DHW tank to the
indoor unit, see the installation manual of the DHW tank.

5.4.4 DHW pump for instant hot water

Setup
a Indoor unit b DHW tank c DHW pump (field supply)
f Shower (field supply) g Cold water h Domestic hot water OUT
i Recirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For more information about connecting the recirculation
connection, see the installation manual of the domestic hot water tank.
Configuration
▪ For more information, see "8Configuration"on page46.
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference guide.

5.4.5 DHW pump for disinfection

Setup
a Indoor unit b DHW tank c DHW pump (field supply) d Heater element (field supply) e Non‑return valve (field supply)
f Shower (field supply) g Cold water h Domestic hot water OUT
i Recirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.
Configuration
The indoor unit can control DHW pump operation. For more information, see "8Configuration"on page46.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
17
5 Application guidelines
c a b
e
d
f
g
h

5.4.6 DHW pump for tank preheating

Setup
a Indoor unit b DHW tank c DHW pump (field supply) d Non‑return valve (field supply) e Shower (field supply)
f Cold water g Domestic hot water OUT h Recirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ For the standalone DHW tank: If there is no electrical backup
heater in the space heating circuit, you must install a DHW pump for tank preheating.
Configuration
The indoor unit can control DHW pump operation. For more information, see "8Configuration"on page46.

5.5 Setting up the energy metering

▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space heating
▪ For space cooling
▪ For domestic hot water production
▪ You can read out the energy data:
▪ Per month
▪ Per year

5.5.2 Consumed energy

You can use the following methods to determine the consumed energy:
▪ Calculating
▪ Measuring
INFORMATION
You cannot combine calculating the consumed energy (example: for backup heater) and measuring the consumed energy (example: for outdoor unit). If you do so, the energy data will be invalid.
Calculating the consumed energy
▪ The consumed energy is calculated internally based on:
▪ The actual power input of the outdoor unit
▪ The set capacity of the backup heater and booster heater (if
applicable)
▪ The voltage
▪ Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via the user interface for:
▪ The backup heater (step1 and step2) (if applicable)
▪ The booster heater
Measuring the consumed energy
▪ Applicable for all models.
▪ Preferred method because of higher accuracy.
▪ Requires external power meters.
▪ Setup and configuration: When using electrical power meters, set
the number of pulses/kWh for each power meter via the user interface.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters.
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy cannot be guaranteed.

5.5.1 Produced heat

INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪ Applicable for all models.
▪ The produced heat is calculated internally based on:
▪ The leaving and entering water temperature
▪ The flow rate
▪ The power consumption of the booster heater (if applicable) in
the domestic hot water tank
▪ Setup and configuration:
▪ No additional equipment needed.
▪ Only in case a booster heater is present in the system, measure
its capacity (resistance measurement) and set the capacity via the user interface. Example: If you measure a booster heater resistance of 17.1Ω, the capacity of the heater at 230 V is 3100W.

5.5.3 Normal kWh rate power supply

General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/5 and X5M/6.
Power meter type
In case of… Use a… power meter
▪ Single-phase outdoor unit
▪ Backup heater supplied from a
single-phase grid (i.e. the backup heater model is *6V connected to a single-phase grid)
▪ Three-phase outdoor unit
▪ Backup heater supplied from a
three-phase grid (i.e. the backup heater model is *9W or *6V connected to a three­phase grid)
Single-phase
(*6V (6V): 1N~230V)
Three-phase
(*6V (6T1): 3~230V)
(*9W: 3N~400V)
Installer reference guide
18
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
5 Application guidelines
b
5
8
0
1
5
0
0
0
c c
fed
g
A B C
a
b
5
8
0
1
5
0
0
0
gfe
h
A B C
c c d
a

e efe
ihg
j
A B C
b
a
d

c
5
8
0
1
5
0
0
0
5
8
0 1
5
0
0
0
P
i
t
DI
a
b
Example
Single-phase power meter Three-phase power meter
A Outdoor unit
B Indoor unit
C DHW tank
a Electrical cabinet (L1/N)
b Power meter (L1/N)
c Fuse (L1/N)
d Outdoor unit (L1/N)
e Indoor unit (L1/N)
f Backup heater (L1/N)
g Booster heater (L1/N)
A Outdoor unit
B Indoor unit
C DHW tank
a Electrical cabinet (L1/L2/L3/N)
b Power meter (L1/L2/L3/N)
c Fuse (L1/L2/L3/N)
d Fuse (L1/N)
e Outdoor unit (L1/L2/L3/N)
f Indoor unit (L1/L2/L3/N)
g Backup heater (L1/L2/L3/N)
h Booster heater (L1/N)
Exception
▪ You can use a second power meter if:
▪ The power range of one meter is insufficient.
▪ The electrical meter cannot easily be installed in the electrical
cabinet.
▪ 230 V and 400 V three-phase grids are combined (very
uncommon), because of technical limitations of power meters.
▪ Connection and setup:
▪ Connect the second power meter to X5M/3 and X5M/4.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which power consumption. You only need to set the number of pulses of each power meter.
▪ See "5.5.4 Preferential kWh rate power supply"on page 19 for
an example with two power meters.

5.5.4 Preferential kWh rate power supply

General rule
▪ Power meter1: Measures the outdoor unit.
▪ Power meter2: Measures the rest (i.e. indoor unit, backup heater
and optional booster heater).
Setup
▪ Connect power meter1 to X5M/5 and X5M/6.
▪ Connect power meter2 to X5M/3 and X5M/4.
Power meter types
▪ Power meter1: Single- or three-phase power meter according to
the power supply of the outdoor unit.
▪ Power meter2:
▪ In case of a single-phase backup heater configuration, use a
single-phase power meter.
▪ In other cases, use a three-phase power meter.
Example
Single-phase outdoor unit with a three-phase backup heater:
A Outdoor unit B Indoor unit C DHW tank
a Electrical cabinet (L1/N): Preferential kWh rate power
supply
b Electrical cabinet (L1/L2/L3/N): Normal kWh rate power
supply
c Power meter (L1/N) d Power meter (L1/L2/L3/N) e Fuse (L1/N)
f Fuse (L1/L2/L3/N) g Outdoor unit (L1/N) h Indoor unit (L1/N)
i Backup heater (L1/L2/L3/N)
j Booster heater (L1/N)

5.6 Setting up the power consumption control

▪ The power consumption control:
▪ Allows you to limit the power consumption of the entire system
(sum of outdoor unit, indoor unit, backup heater and optional booster heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (inA)
▪ Maximum power input (inkW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs

5.6.1 Permanent power limitation

Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
PiPower input
Installer reference guide
19
5 Application guidelines
a
b
c
A B C
D
1
2
3
4
5
A8P
P
i
t
DI4
DI3
DI1
a
b
P
h
C
e
a
b
c
d
e
A B C
t Time
DI Digital input (power limitation level)
a Power limitation active b Actual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings in [9.9] via the user
interface (for the description of all settings, see
"8Configuration"on page46):
▪ Select continuous limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level

5.6.2 Power limitation activated by digital inputs

Power limitation is also useful in combination with an energy management system.
The power or current of the entire ROTEX system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation of a certain power limitation level. Example: To limit the maximum power of the entire house (lighting, domestic appliances, space heating…).
Configuration
▪ Set the power consumption control settings in [9.9] via the user
interface (for the description of all settings, see
"8Configuration"on page46):
▪ Select limitation by digital inputs.
▪ Select the type of limitation (power in kW or current in A).
▪ Set the desired power limitation level corresponding to each
digital input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority is fixed: DI4 priority>…>DI1.

5.6.3 Power limitation process

The outdoor unit has better efficiency than the electrical heaters. Therefore, the electrical heaters are limited and turned OFF first. The system limits power consumption in the following order:
1 Limits certain electrical heaters.
If… has priority Then set the priority heater
via the user interface to…
Domestic hot water production Booster heater (if applicable)
Result: The backup heater will be turned OFF first.
Space heating Backup heater
Result: The booster heater (if applicable) will be turned OFF first.
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
▪ Maximum four digital inputs are used to activate the
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specifications of the digital inputs, and for where to
connect them, refer to the wiring diagram.
Installer reference guide
20
A Outdoor unit B Indoor unit C DHW tank D Energy management system
a Power limitation activation (4 digital inputs) b Backup heater c Booster heater
PiPower input
t Time
DI Digital inputs (power limitation levels)
a Power limitation active b Actual power input
2 Turns OFF all electrical heaters.
3 Limits the outdoor unit.
4 Turns OFF the outdoor unit.
Example
If the configuration is as follows:
▪ Power limitation level does NOT allow operation of both booster
heater and backup heater (step1 and step2).
▪ Priority heater = Booster heater (if applicable).
Then power consumption is limited as follows:
PhProduced heat CeConsumed energy
A Outdoor unit B Booster heater C Backup heater
a Limited outdoor unit operation b Full outdoor unit operation c Booster heater turned ON d Backup heater step1 turned ON e Backup heater step2 turned ON

5.7 Setting up an external temperature sensor

You can connect one external temperature sensor. It can measure the outdoor ambient temperature. ROTEX recommends to use an external temperature sensor in the following cases:
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11

6 Preparation

≤1200
>250
>250
>250
>350
>350
(mm)(mm)
a
b
b
a
>100
>350
(mm)
>100
a
a
Outdoor ambient temperature
▪ In the outdoor unit, the outdoor ambient temperature is measured.
Therefore, the outdoor unit must be installed on a location:
▪ At the north side of the house or at the side of the house where
the most heat emitters are located
▪ That is NOT exposed to direct sunlight
▪ If this is NOT possible, ROTEX recommends to connect a remote
outdoor sensor (option EKRSCA1).
▪ Setup: For installation instructions, see the installation manual of
the remote outdoor sensor.
▪ Configuration: Select outdoor sensor [9.B].
▪ When the power saving functionality of the outdoor unit is active
(see "8 Configuration" on page 46), the outdoor unit is turned down to reduce standby energy losses. As a result, the outdoor ambient temperature is NOT read out.
▪ If the desired leaving water temperature is weather dependent, the
full time outdoor temperature measurement is important. This is another reason to install the optional outdoor ambient temperature sensor.
INFORMATION
The external outdoor ambient sensor data (either averaged or instantaneous) is used in the weather-dependent control curves and in the automatic heating/cooling changeover logic. To protect the outdoor unit, the internal sensor of the outdoor unit is always used.

6.2.1 Installation site requirements of the outdoor unit

INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
Mind the following spacing guidelines:
a Air outlet b Air inlet
INFORMATION
In sound sensitive areas (e.g. near a bedroom), you can install the low sound cover (EKLN08A1) to decrease the operation noise of the outdoor unit. If you install it, mind the following spacing guidelines:
6 Preparation

6.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the water piping
▪ Preparing the electrical wiring

6.2 Preparing the installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the unit in and out of the site.
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
a Low sound cover
NOTICE
▪ Do NOT stack the units on each other.
▪ Do NOT hang the unit on a ceiling.
Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in:
▪ deterioration of the operational capacity;
▪ frequent frost acceleration in heating operation;
▪ disruption of operation due to decrease of low pressure or
increase of high pressure;
▪ a broken fan (if a strong wind blows continuously on the fan, it
may start rotating very fast, until it breaks).
It is recommended to install a baffle plate when the air outlet is exposed to wind.
It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind.
WARNING
DO NOT reuse refrigerant piping that has been used with any other refrigerant. Replace the refrigerant pipes or clean thoroughly.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
21
6 Preparation
b
b
c
a
b
c
a
a
b
c
d
c
d
2
1
3
a
c
c
d
b e
a
a Baffle plate b Prevailing wind direction c Air outlet
Do NOT install the unit in the following places:
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea winds. This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit.
Cooling mode 10~43°C
Heating mode –25~25°C

6.2.2 Additional installation site requirements of the outdoor unit in cold climates

In areas with low ambient temperatures and high humidity, or in areas with heavy snowfall, remove the suction grille to ensure proper operation.
Non-exhaustive list of areas: Austria, Czech Republic, Denmark, Estonia, Finland, Germany, Hungary, Latvia, Lithuania, Norway, Poland, Romania, Serbia, Slovakia, Sweden, …
1 Remove the screws holding the suction grille.
2 Remove the suction grille, and dispose of it.
3 Reattach the screws to the unit.
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
▪ Height of windbreaker≥1.5×height of outdoor unit
▪ Mind the service space requirements when installing the
windbreaker.
a Sea wind b Building
The outdoor unit is designed for outdoor installation only, and for the following ambient temperatures:
Installer reference guide
22
c Outdoor unit d Windbreaker
a Suction grille
Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up.
a Snow cover or shed b Pedestal c Prevailing wind direction d Air outlet e EKFT008D option kit
In any case, provide at least 300mm of free space below the unit. Additionally, make sure the unit is positioned at least 100mm above the maximum expected level of snow. See "7.3 Mounting the
outdoor unit"on page31 for more details.
In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
6 Preparation
H1150
200
200
500
(mm)
≥450
See also
2 7.3 Mounting the outdoor unit [}31]

6.2.3 Installation site requirements of the indoor unit

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
▪ The indoor unit is designed for indoor installation only and for the
following ambient temperatures:
▪ Space heating operation: 5~30°C
▪ Space cooling operation: 5~35°C
▪ Domestic hot water production: 5~35°C
▪ Mind the measurement guidelines:
Maximum refrigerant piping length between indoor unit and outdoor unit
Minimum refrigerant piping length between indoor unit and outdoor unit
Maximum height difference between indoor unit and outdoor unit
Maximum distance between the 3‑way valve and the indoor unit (for installations with domestic hot water tank)
Maximum distance between the domestic hot water tank and the indoor unit (for installations with domestic hot water tank)
▪ Mind the following spacing installation guidelines:
30m
3m
20m
3m
10m
Special requirements for R32
WARNING
▪ Do NOT pierce or burn.
▪ Do NOT use means to accelerate the defrosting
process or to clean the equipment, other than those recommended by the manufacturer.
▪ Be aware that R32 refrigerant does NOT contain an
odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.
NOTICE
▪ Do NOT re-use joints which have been used already.
▪ Joints made in installation between parts of refrigerant
system shall be accessible for maintenance purposes.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from ROTEX and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
NOTICE
▪ Pipework shall be protected from physical damage.
▪ Installation of pipework shall be kept to a minimum.
H Height measured from the bottom of the casing to the floor
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom), so that the
operation noise will cause no trouble.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit must be >5°C.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
23
6 Preparation
Input from installer:
▪ Total refrigerant charge (m
c
) (kg) ▪ Installation height (H) (m) ▪ Area of room A (A
room A
) (m2)
Start
Use table 1 in chapter "Technical data" to calculate the maximum refrigerant charge (m
max
) (kg) allowed for room A.
Contact your dealer.
Use table 3 in chapter "Technical data" and dm to calculate the minimum opening area for natural ventilation between room A and
room B (VA
min
) (cm2).
Unit can be installed at room A if: ▪ 2 ventilation openings (permanently open) are provided between room A and B, 1 at the top and 1 at the bottom. ▪ Bottom opening: The bottom opening must meet the minimum area requirements (VA
min
). It must be as close as possible to the floor and lower than H. If the ventilation opening starts from the floor, the height must be ≥20 mm. The bottom of the opening must be situated ≤100 mm from the floor. At least 50% of the required opening area must be situated <200 mm from the floor. The entire area of the opening must be situated <300 mm from the floor.
Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m
above the top of the bottom opening.
▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold).
The unit can be installed in room A at the specified installation height, and without further room size or ventilation requirements.
Determine the refrigerant amount that exceeds
m
max
(dm) (kg). (dm=mc–m
max
)
m
max≥mc
?
Yes
No
No
Use table 2 in chapter "Technical data" to calculate the total minimum floor area (A
min total
) (m2) required for the total refrigerant
charge (m
c
) at the selected installation height
(H).
a Indoor unit A Room where the indoor unit is installed. B Room adjacent to room A.
A
min total≤Aroom A+Aroom B
?
Yes
Input from installer:
▪ Area of adjacent room B (A
room B
) (m2)
A
a
B
≥1.5 m
If the total refrigerant charge in the system is ≥1.84kg (i.e. if the piping length is ≥27m), you need to comply with the minimum floor area requirements as described in the following flow chart. The flow chart uses the following tables: "14.5Table 1 – Maximum refrigerant charge
allowed in a room: indoor unit" on page 96, "14.6 Table 2 – Minimum floor area: indoor unit" on page96 and "14.7 Table 3 – Minimum venting opening area for natural ventilation: indoor unit"on page97.
INFORMATION
Systems with a total refrigerant charge (mc) <1.84kg (i.e. if the piping length is <27 m) are NOT subjected to any requirements to the installation room.
INFORMATION
Multiple indoor units. If two or more indoor units are
installed in a room, you must consider the maximum refrigerant charge that can be released in the room when a SINGLE leak occurs. Example: If two indoor units are installed in the room, each with its own outdoor unit, then you have to consider the refrigerant charge of the largest indoor-outdoor combination.
Installer reference guide
24
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
6 Preparation
t
Ø
ØiØ
i
t
ØpØ
p

6.3 Preparing refrigerant piping

6.3.1 Refrigerant piping requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Piping material: Phosphoric acid deoxidised seamless copper.
Piping diameter:
Liquid piping Ø6.4mm (1/4")
Gas piping Ø15.9mm (5/8")
Piping temper grade and thickness:
Outer diameter
(Ø)
6.4mm (1/4") Annealed (O) ≥0.8mm
15.9mm (5/8") Annealed (O) ≥1.0mm
(a) Depending on the applicable legislation and the unit's
Temper grade Thickness (t)
maximum working pressure (see "PS High" on the unit name plate), larger piping thickness might be required.
(a)

6.3.2 Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
6.4mm (1/4") 8~10mm 10mm
15.9mm (5/8") 16~20mm 13mm
If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.
Insulation inner
diameter (Øi)
Insulation thickness
(t)

6.4 Preparing water piping

Valve towards expansion vessel. The valve towards the
expansion vessel (if equipped) MUST be open.
Connecting piping – Force. Do NOT use excessive force when
connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get damaged.
Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
Closed circuit. Use the indoor unit ONLY in a closed water
system. Using the system in an open water system will lead to excessive corrosion.
Glycol. For safety reasons, it is NOT allowed to add any kind of
glycol to the water circuit.
Piping diameter. Select the water piping diameter in relation to
the required water flow and the available external static pressure of the pump. See "14 Technical data"on page90 for the external static pressure curves of the indoor unit.
Water flow. You can find the minimum required water flow for
indoor unit operation in the following table. In all cases, this flow needs to be guaranteed. When the flow is lower, the indoor unit will stop operation and display error 7H.
Minimum required flow rate
12l/min
Field supply components – Water. Only use materials that are
compatible with water used in the system and with the materials used in the indoor unit.
Field supply components – Water pressure and temperature.
Check that all components in the field piping can withstand the water pressure and water temperature.
Water pressure. The maximum water pressure is 4 bar. Provide
adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Water temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following temperatures:
INFORMATION
The following illustration is an example and might NOT match your system layout.

6.4.1 Water circuit requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
NOTICE
In case of plastic pipes, make sure they are fully oxygen diffusion tight according to DIN 4726. The diffusion of oxygen into the piping can lead to excessive corrosion.
Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
25
6 Preparation
M
FCU1
FCU2
FCU3
i
M
FHL1
FHL2
FHL3
j
l k
fd ecba
f
g
h
i
i
i
T
65°C
89°C
c d
a b
a Outdoor unit b Indoor unit c Heat exchanger d Backup heater e Pump
f Shut-off valve
g Motorised 3-way valve (supplied with the domestic hot
water tank)
h Motorised 2-way valve (field supply)
i Collector j Domestic hot water tank
k Heat exchanger coil
l Booster heater
FCU1...3 Fan coil unit (optional) (field supply)
FHL1...3 Floor heating loop (field supply)
T Room thermostat (optional) (field supply)
Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the water circuit.
Drainage – Pressure relief valve. Connect the drain hose
properly to the drain to avoid water dripping out of the unit. See
"7.4.4To connect the drain hose to the drain"on page35.
Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. Two automatic air purges are provided in the indoor unit. Check that the air purges are NOT tightened too much, so that automatic release of air in the water circuit is possible.
Zn-coated parts. Never use Zn-coated parts in the water circuit.
Because the unit's internal water circuit uses copper piping, excessive corrosion may occur.
Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Valve – Separating circuits. When using a 3-way valve in the
water circuit make sure that the domestic hot water circuit and the floor heating circuit is fully separated.
Valve – Change‑over time. When using a 2-way valve or a 3-way
valve in the water circuit, the maximum change-over time of the valve must be 60seconds.
Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water.
Domestic hot water tank – After installation. Immediately after
installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the equipment MUST be flushed with fresh water before usage.
Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "8.4.6 Tank" on
page62.
Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing valves.
Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic installation measures.
Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.
a Recirculation connection b Hot water connection c Shower d Recirculation pump
Valve towards expansion vessel. The valve towards the
expansion vessel (if equipped) MUST be open.

6.4.2 Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)

6.4.3 To check the water volume and flow rate

The indoor unit has an expansion vessel of 10litre with a factory-set pre-pressure of 1bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Check that the total water volume in the installation is minimum 10litres, the internal water volume of the indoor unit NOT included.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required.
NOTICE
When circulation in each space heating/cooling loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
Installer reference guide
26
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
6 Preparation
FHL1
FHL2
FHL3
M1
T1
M2T2M3
T3
fdcba
f
g h
e
0.3
0.5
1
1.5
2
2.4
5020 100 150 200 250 290
a
b
a Outdoor unit
b Indoor unit
c Heat exchanger
d Backup heater
e Pump
f Shut-off valve g Collector (field supply) h Overpressure bypass valve (delivered as accessory)
FHL1...3 Floor heating loop (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3 (field
supply)
Maximum water volume
Use the following graph to determine the maximum water volume for the calculated pre-pressure.
Installation
height
difference
(a)
≤200l >200l
>7m Do the following:
▪ Increase the pre-
pressure according to the required installation height difference. The pre­pressure should
Water volume
The expansion vessel of the indoor unit is too small for the installation. In this case, it is recommended to install an extra vessel outside the unit.
increase by 0.1 bar for each metre above 7 m.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
(a) This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is at the highest point of the installation, the installation height is 0m.
Minimum flow rate
Check that the minimum flow rate in the installation is guaranteed in all conditions. This minimum flow rate is required during defrost/ backup heater operation. For this purpose, use the overpressure bypass valve delivered with the unit, and respect the minimum water volume.
NOTICE
When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating or operation).
Minimum required flow rate
12l/min
See the recommended procedure as described in "9.4 Checklist
during commissioning"on page78.
6.4.4 Changing the pre-pressure of the
a Pre-pressure (bar)
b Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre­pressure
Installation
height
difference
(a)
≤200l >200l
≤7m No pre-pressure
adjustment is required.
Water volume
Do the following:
▪ Decrease the pre-
pressure according to the required installation height difference. The pre-pressure should decrease by 0.1 bar for
When changing the default pre-pressure of the expansion vessel (1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the Schrader valve of the expansion vessel.
each metre below 7 m.
▪ Check if the water
volume does NOT exceed the maximum allowed water volume.
expansion vessel
NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
27
6 Preparation
a
1
2
3
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
a Schrader valve

6.4.5 To check the water volume: Examples

Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 250l.
Actions:
▪ Because the total water volume (250l) is more than the default
water volume (200l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 290 l.
(See the graph in the chapter above).
▪ Because 250 l is lower than 290 l, the expansion vessel is
appropriate for the installation.

6.5 Preparing electrical wiring

6.5.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable legislation.
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by the safety devices required by the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.

6.5.2 About preferential kWh rate power supply

Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available, if any.
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the outdoor unit compressor will not operate.
Whether the power supply is interrupted or not, the wiring to the unit is different.
Installer reference guide
28
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11

7 Installation

1
5
8
0
1
5
0
0
0
2
a
3
1
4
5
8
0 1
5
0
0
0
2
b
3
5 3
a
b
14
5
8
0
1
5
0
0
0
5
8
0 1
5
0
0
0
2

6.5.3 Overview of electrical connections except external actuators

Normal power
supply
Preferential kWh rate power supply
Power supply is NOT interrupted
Power supply is
interrupted
Item Description Wires Maximum
running
current
9 Domestic hot water
2
(d)
tank thermistor
10 User interface used as
2
(f)
room thermostat
11 Room thermostat 3 or 4 100mA
12 Outdoor ambient
2
(b)
(b)
temperature sensor
13 Indoor ambient
2
(b)
temperature sensor
14 Heat pump convector 2 100mA
(b)
Field supplied components
(b)
(b)
(b)
(b)
(b)
(b)
(b)
(e)
During preferential kWh rate power supply activation, power supply is NOT interrupted. The outdoor unit is turned off by the control.
Remark: The electricity company must always allow the power consumption of the indoor unit.
a Normal power supply
b Preferential kWh rate power supply
1 Power supply for outdoor unit 2 Power supply and interconnection cable to indoor unit 3 Power supply for backup heater 4 Preferential kWh rate power supply (voltage free contact) 5 Normal kWh rate power supply (to power the indoor unit
PCB in the event of power supply interruption of the preferential kWh rate power supply)
kWh rate power supply activation, power supply is interrupted immediately or after some time by the electricity company. In this case, the indoor unit must be powered by a separate normal power supply.

6.5.4 Overview of electrical connections for external and internal actuators

During preferential
Item Description Wires Maximum
Outdoor unit and indoor unit power supply
1 Power supply for
2+GND
outdoor unit
2 Power supply and
3
interconnection cable to
running
current
(a)
(g)
15 Shut-off valve 2 100mA
16 Electricity meter 2 (per meter)
17 Domestic hot water
2
pump
18 Alarm output 2
19 Changeover to external
2
heat source control
20 Space cool/heat
2
operation control
21 Power consumption
digital inputs
2 (per input signal)
22 Safety thermostat 2
(a) Refer to name plate on outdoor unit. (b) Minimum cable section 0.75mm². (c) Cable section 2.5mm². (d) The thermistor and connection wire (12m) are delivered
with the domestic hot water tank.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum applicable load of 15VDC, 10mA.
(f) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual user interface connection.
(g) Cable section 1.5mm².
NOTICE
More technical specifications of the different connections are indicated on the inside of the indoor unit.
Backup heater
type
Power supply Required number of
conductors
*6V 1N~ 230V (6V) 2+GND
3~ 230V (6T1) 3+GND
*9W 3N~ 400V 4+GND
indoor unit
3 Power supply for
backup heater
4 Preferential kWh rate
power supply (voltage free contact)
5 Normal kWh rate power
supply
See table below. —
2
(e)
2 6.3A
7 Installation

7.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Optional equipment
6 3‑way valve 3 100mA
7 Power supply for
4+GND
(b)
(c)
booster heater and
8 Power supply for
thermal protection (from indoor unit)
2+GND 13A booster heater (to indoor unit)
RRGA04~08DAV3 + RHBX04+08DA ROTEX HPSU Bi-Bloc Ultra 4P495262-1A – 2018.11
Installer reference guide
29
7 Installation
2
2
1
3
1
2
1
2
3
Typical workflow
Installation typically consists of the following stages:
1 Mounting the outdoor unit.
2 Mounting the indoor unit.
3 Connecting the refrigerant piping.
4 Checking the refrigerant piping.
5 Charging refrigerant.
6 Connecting the water piping.
7 Connecting the electrical wiring.
8 Finishing the outdoor installation.
9 Finishing the indoor installation.
INFORMATION
Depending on the units and/or the installation conditions, it might be necessary to connect electrical wiring before you can charge refrigerant.

7.2 Opening the units

7.2.1 About opening the units

At certain times, you have to open the unit. Example:
▪ When connecting the refrigerant piping
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.

7.2.2 To open the outdoor unit

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
See "7.5.8To connect the refrigerant piping to the outdoor unit" on
page 37 and "7.9.6 To connect the electrical wiring on the outdoor unit"on page42.

7.2.3 To open the indoor unit

1 Remove the front panel.
3 If you have to do work behind the switch box, open the switch
box.
4 If you have to do work behind the user interface panel or upload
new software into the user interface, open the user interface panel.
2 If you have to connect electrical wiring, remove the switch box
cover.
Installer reference guide
30
5 Optional: Remove the user interface panel.
NOTICE
If you remove the user interface panel, also disconnect the cables from the back of the panel to prevent damage.
RRGA04~08DAV3 + RHBX04+08DA
ROTEX HPSU Bi-Bloc Ultra
4P495262-1A – 2018.11
Loading...
+ 82 hidden pages