Daikin RQYQ140PY1, RQYQ180PY1, RQCYQ280PY1, RQCYQ360PY1, RQCYQ460PY1 Installation manuals

...
INSTALLATION MANUAL
System air conditioner
Series
MODELS
RQYQ140PY1 RQYQ180PY1 RQCYQ280PY1 RQCYQ360PY1 RQCYQ460PY1 RQCYQ500PY1 RQCYQ540PY1
RQEQ140PY13 RQEQ180PY13 RQEQ212PY13 RQCEQ280PY13 RQCEQ360PY13 RQCEQ460PY13 RQCEQ500PY13 RQCEQ540PY13 RQCEQ636PY13 RQCEQ712PY13 RQCEQ744PY13 RQCEQ816PY13 RQCEQ848PY13
Installation manual
III
VRV
Conditionneur d’air VRV
Sistema de acondicionador de aire VRV
Condizionatore d’aria a sistema VRV
Κλιìατιστικü ìε σýστηìα VRV
Airconditioner met VRV
System air conditioner
Installationsanleitung
III
VRV
System Klimaanlage
Manuel d’installation
III
System
Manual de instalación
Manuale di installazione
Εγχειρßδιο εγκατÜστασηò
Installatiehandleiding
III
Systeem
III
III
III
English
Deutsch
Français
Español
Italiano
Nederlands
Manual de instalação
III
Ar condicionado VRV
Рóêоводство по монтажó
Кондиционер системы VRV
Montaj elkitabý
III
VRV
System Klima
System
III
Português
Рóссêий
Türkçe
[Q140~212 type]
1
2
<
If installed as a single unit
(Pattern 1)
3
1
3
45
(Pattern 2)
6
7
8
(Pattern 3)
9
10
11
2
figure 1 figure 2 figure 3
10
50
200
>
<
If installed as a serial installation
(Pattern 1)
300 300
4
1
10
500
3
100
50
500
2
4
3
1
300
1
10
(Pattern 2)
50
(Pattern 3)
200
20
100
1
20
100
1
300
1
400 400
10
50
2
>
500
4
3
500
100
4
3
1
2
2
1500
5
1000
1000
3
1000
4
1500
1500
1500
(mm)
1
2
3
4
1
2
figure 4 figure 5 figure 6
3
1
2
100
100
1
100
figure 7 figure 8
1
1
2
3
figure 10.1
2
765
1
4
5
1
2
6
3
4
2
56
4
5
3
3
figure 9 figure 10.2 figure 11 figure 12
2
1
3
100
3
2
1
1
2
1
3
3
5
6
2
figure 13 figure 14.1 figure 14.2 figure 14.3
1
1
2
4
7
31
5
12
6
12
11
12
7
9
13
24
5
12
8
13
6
5
15
12
10
14
8
10
figure 15.1 figure 15.2
31
7
15
14
15
12
24
5
6
15
11
9
7
15
13
18-1
C
12
A-arrow view
A
3
4
1
figure 16
D
1
B-arrow view
B
1
18-2
figure 17 figure 18
1
1
2
4
3
1
2
5
3 4
6
7
8
2
4
3
1
2
figure 19.1 figure 19.2
1 2
12
9
10
8
7
3 4
5
11
8
12 13
3
ABC
6
figure 20 figure 21.1
2
(C-arrow view)
1
4
(D-arrow view)
5
A5P A1P
A
C
B
3
5
1
3
4
6
9
6
3
4
8
7
1
2
TO IN/D
TO OUT/D
TO MULTI
UNIT
UNIT
F1 F2 F1 F2 Q1 Q2
UNIT
1
1
4
F1 F2 F1 F2 F1 F2
5
18-3
8
6
7
4
1
A1P
TO IN/D
TO OUT/D
UNIT
UNIT
F1 F2 F1 F2
F1 F2 F1 F2
TO IN/D
TO OUT/D
UNIT
UNIT
5
F1F2F1
2
6
F1 F2 F1 F2
TO IN/D
TO OUT/D
UNIT
UNIT
5
F1F2F1
F2
F2
6
7
F1 F2
F1 F2
3
figure 21.2 figure 22
1
23
A5P A1P A1P
A
C
B
311
4
TO OUT/D
TO IN/D
UNIT
UNIT
F1 F2 F1 F2
TO MULTI
UNIT
Q1 Q2
2
6
5
TO MULTI
UNIT
Q1 Q2
1
2
22
5
22
3
2
4
22
6
11
10
99
22
22
22
22
7
5
4
8
6
figure 23 figure 24
2
5
3
1
5
4
1
3
4
figure 25.1
4
2
1
5
2
8
4
(A5P)
L1 L2 L3 N
2
1
(A1P)
(A5P)
2
6
7
4
8
3
4
6
figure 25.2 figure 26
9
1
2
3
4
11
5
10
8
13
7
2
6
5
4
6
6
figure 27 figure 29.1 figure 29.2
2
1
3
4
5
1
4
2
11 12 13
3
5
8
7
6
99 9
10
figure 28.1 figure 30
1
2
3
1
4
9
8
7
6
10 10 10 10
2
12 13 14
3
5
11
figure 28.2
7
6
1
3
2
10
4
5
8 88
9
1
11
4
figure 31.1 figure 31.2
3
4
1
1
5
6
7
3
2
figure 32 figure 33
8
7 6
3
2
5
5
1
4
999
10
2
3
RQYQ140PY1 RQYQ180PY1 RQCYQ280PY1 RQCYQ360PY1 RQCYQ460PY1 RQCYQ500PY1 RQCYQ540PY1
RQEQ140PY13 RQEQ180PY13 RQEQ212PY13 RQCEQ280PY13 RQCEQ360PY13 RQCEQ460PY13 RQCEQ500PY13
RQCEQ540PY13 RQCEQ636PY13 RQCEQ712PY13 RQCEQ744PY13 RQCEQ816PY13 RQCEQ848PY13
III
VRV
System air conditioner
III
-Q Series
VRV
Installation manual
CONTENTS
1. FIRST OF ALL ......................................................................... 1
1-1. Safety precautions.......................................................... 1
1-2. Special notice of product ................................................ 2
1-3. Disposal requirements.................................................... 3
2. INTRODUCTION...................................................................... 3
2-1. Combination ................................................................... 3
2-2. Standard supplied accessories....................................... 3
2-3. Option accessory............................................................ 4
2-4. Technical and Electrical specifications ........................... 4
2-5. Main components ........................................................... 4
2-6. Installation Process ........................................................ 4
3. SELECTION OF LOCATION ................................................... 4
4. INSPECTING AND HANDLING THE UNIT ............................. 5
5. PLACING THE UNIT................................................................ 5
6. REFRIGERANT PIPING ..........................................................5
6-1. Selection of piping material and Refrigerant
branching kit ................................................................... 5
6-2. Protection against contamination
when installing pipes ...................................................... 6
6-3. Pipe connection .............................................................. 6
6-4. Connecting the refrigerant piping ................................... 6
6-5. Example of connection ...................................................9
7. FIELD WIRING ...................................................................... 15
7-1. Power circuit, safety device, and cable requirements .. 15
7-2. Wiring Connection Example for Whole System............ 16
7-3. Leading wire Procedure................................................ 16
7-4. Transmission Wiring Connection Procedure ................ 16
7-5. Power Wiring Connection Procedure ........................... 17
7-6. Procedure for Wiring Inside Units................................. 17
8. AIR TIGHT TEST AND VACUUM DRYING ........................... 17
8-1. Preparations ................................................................. 18
8-2. Air tight test and vacuum drying method ...................... 18
9. PIPE INSULATION ................................................................ 18
10. CHECKING OF DEVICE AND INSTALLATION
CONDITIONS ........................................................................ 19
11. ADDITIONAL REFRIGERANT CHARGE AND CHECK
OPERATION .......................................................................... 19
11-1. Before working.............................................................. 19
11-2. Procedure of check operation....................................... 20
12. ONSITE SETTINGS............................................................... 26
12-1. Onsite Settings With the Power Off.............................. 26
12-2. Onsite Settings With the Power On.............................. 26
13. TEST RUN ............................................................................. 26
13-1. Before test run.............................................................. 26
13-2. Test Run....................................................................... 26
13-3. Checks After Test Run .................................................26
14. CAUTION FOR REFRIGERANT LEAKS............................... 26
The English text is the original instruction. Other languages are translations of the original instructions.

1. FIRST OF ALL

• Use the BS unit with Heat Recovery series (RQCEQ).
• This document is an installation manual for the Daikin VRVIII-Q Series VRV Inverter. Before installing the unit, read this manual thoroughly, and following the instructions contained in it. After installation, do a test run to make sure the unit runs properly, and then explain how to operate and take care of the unit to the cus­tomer, using the operation manual.
• Lastly, make sure the customer keeps this manual, along with the operation manual, in a safe place.
• This manual does not describe how to install the indoor unit. Refer to the installation manual included with the indoor unit for that.
1-1 Safety precautions
Please read these “Safety precautions” carefully before installing air conditioning equipment and be sure to install it correctly. Meaning of WARNING and CAUTION notices. Both are important notices for safety. Be sure to follow them.
WARNING.....Failure to follow these instructions properly may
result in personal injury or loss of life.
CAUTION......Failure to observe these instructions properly
may result in property damage or personal injury, which may be serious depending on the
circumstances. After completing installation, conduct a test operation to confirm that the equipment operates without any problems. Then, explain to the customer how to operate the equipment and take care of it following the operation manual. Ask the customer to store the installation man­ual along with the operation manual for future reference. This air conditioner comes under the term “appliances not accessible to the general public”. VRV System is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
WARNING
• Ask your dealer or qualified personnel to carry out installation work. Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.
• Install the air conditioner in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electric shocks or fire.
• When installing the unit in a small room, take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage. Contact your dealer for further information. If the refrigerant leaks and exceeds the limiting concentration, it may lead to oxygen defi­ciency.
• Be sure to use only the specified accessories and par ts for instal­lation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
• Install the air conditioner on a foundation strong enough to with­stand the weight of the unit. If a foundation does not have sufficient strength, the equipment may fall and cause injury.
• Carry out the required installation work in consideration of strong winds, typhoons or earthquakes. If the installation work is not properly carried out, the unit may fall down and cause accidents.
• The electrical work must be carried out by the qualified electrician in accordance with the local laws and regulations and this instal­lation manual. Make sure to provide a dedicated power supply cir­cuit and never connect additional wiring to the existing circuit. An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire.
• Be sure to earth the air conditioner. Do not earth the unit to a utility pipe, lightning conductor or tele­phone earth lead. Imperfect earthing may result in electric shocks or fire. A high surge current from lightning or other sources may cause damage to the air conditioner.
• Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks or fire.
• Be sure to switch off the unit before touching any electrical parts. Touching a live part may result in electric shock.
1 English
• For wiring, use the specified wires and connect and fasten them firmly so that no external force from the wires may be applied to the terminal connections. If the wires are not firmly connected and fastened, it may cause heating, fire or the like.
• When wiring the power supply and connecting the remote control­ler wiring and transmission wiring, position the wires so that the EL.COMPO.BOX lid can be securely fastened. Improper positioning of the EL.COMPO.BOX lid may result in electric shocks, fire or the terminals overheating.
• If refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant comes into contact with fire.
• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
• Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas, as there is a danger of frostbite.
• Do not allow children to climb on the outdoor unit and avoid plac­ing objects on the unit. Injury may result if the unit becomes loose and falls.
CAUTION
• Carry out drain piping properly following this installation manual and insulate the pipe to prevent condensation. Improper drain piping may result in indoor water leakage and property damage.
• Install the indoor, BS and outdoor units, power cord and connect­ing wires at least 1 meter away from televisions or radios to pre­vent picture interference and noise. (Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
• Install the indoor unit and BS unit as far as possible from fluores­cent lamps. If a wireless kit is installed in a room where the electronic lighting type (inverter or rapid start types) fluorescent lamps exist, the transmitting distance of a remote controller may be shorter.
• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals. Small animals making contact with electrical parts can cause mal­functions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
• Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or
vapour (e.g. a kitchen). Plastic parts may deteriorate and cause parts to fall off or water to leak.
2. Where corrosive gas, such as sulphurous acid gas, is pro-
duced. Corrosion of copper pipes or brazed parts may occur and cause refrigerant leakage.
3. Where there is a machine that generates electromagnetic
wave and where voltage fluctuation often occurs such as a fac­tory. Control system may malfunction and as a result the unit may not properly operate.
4. Where flammable gas may leak, where carbon fibre or ignit-
able dust is suspending in the air, or where volatile flammables such as paint thinner or gasoline are handled. Operating the unit in such conditions may result in fire.
• The air conditioner is not intended for use in a potentially explo­sive atmosphere.
1-2 Special notice of product
[CLASSIFICATION]
This air conditioner comes under the term “appliances not accessible to the general public”.
[EMC CHARACTERISTICS]
VRVIII System is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
[REFRIGERANT] VRVIII System use R410A refrigerant.
• The refrigerant R410A requires that strict precautions be observed for keeping the system clean, dry and tightly sealed. Read the chapter “REFRIGERANT PIPING” carefully and follow these procedures correctly.
A.Clean and dry
Strict measures must be taken to keep impurities (including fluid, dirt and dust) out of the system.
B.Tightly sealed
R410A contains no chlorine, does not destroy the ozone layer and so does not reduce the earth’s protection against harmful ultraviolet radiation. R410A will contribute only slightly to the greenhouse effect if released into the atmosphere. Therefore, sealing tightness is particularly important in installation. Care­fully read the chapter “REFRIGERANT PIPING” and strictly observe the correct procedures.
• As the design pressure for local connection piping (suction·HP/LP gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possi­ble to use existing piping (design pressure of at least 3.3 MPa,) but refer to "6. REFRIGERANT PIPING" and check that existing piping (including branch piping) is compatible with this unit in terms of materials and thickness and that it does not appear to be corroded. Air tight test (3.3 MPa 24/h) to check the strength of existing piping and that it has no gas leaks. If it is not possible to perform a pressure test, replace existing pip­ing with piping rated at least 3.3 MPa.
• Check that there has not been compressor malfunction, gas sup­ply exhaustion, or similar issues that could be attributable to pipe problems in the past. If there have been any such problems, check that appropriate repairs were made, and if not, implement such repairs.
• Existing power supply and transmission wiring is also designed to be used with existing wiring, but check that specifications match and that parts (especially terminals) do not appear to have aged, and implement appropriate procedures (e.g. replacement).
• Since R410A is a mixed refrigerant, the required additional refrig­erant must be charged in its liquid state. (If the system is charged with refrigerant in its gaseous state, due to composition change, the system will not function normally).
• The indoor unit is designed for R410A use. See the catalogue for indoor unit models that can be connected. (Normal operation is not possible when connecting units that are originally designed for other refrigerants.)
• The Heat Recovery Series (RQCEQ) cannot be connected to older BS units (BSVQ-M Type).
Total maximum refrigerant charge limits.
The total maximum refrigerant charge of a VRVIII system must be below 100kg, this to be in accordance with CE requirement (EN60335-2-40 standard). This means that in case the total maximum refrigerant charge of the system (factory and additional charge) is equal to or more than 100kg you must divide your multiple outdoor system into smaller indepen­dent systems, each containing less than 100kg refrigerant charge. For factory charge, refer to the unit name plate.
Important information regarding the refrigerant used.
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type : R410A
(1)
GWP
value : 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product, the additional refrigerant amount charged onsite and + the total refrigerant charge on the refrigerant charge label
supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).
4
factory refrigerant charge of the product : see unit name
1
(2)
plate
1
additional refrigerant amount
2
2
charged in the field
3 total refrigerant charge
Contains fluorinated green-
3
4
house gases covered by the
5
6
Kyoto Protocol
5 outdoor unit
refrigerant cylinder and man-
6
ifold for charging
English 2
(2)
In case of multiple outdoor systems, only 1 label must be adhered, mentioning the total factory refrigerant charge of all outdoor units connected on the refrigerant system.
[DESIGN PRESSURE]
• As the design pressure for local connection piping (suction·HP/LP gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possi­ble to use existing piping (design pressure of at least 3.3 MPa) but refer to "6. REFRIGERANT PIPING" and check that existing pip­ing (including branch piping) is compatible with this unit in terms of materials and thickness and that it does not appear to be cor­roded. Air tight test (3.3 MPa 24/h) to check the strength of existing piping and that it has no gas leaks. If it is not possible to perform a pressure test, place existing piping with piping rated at least 3.3 MPa.
• Check that there has been no compressor malfunction, gas sup­ply exhaustion, or similar issues that could be attributable to pipe problems in the past. If there have been any such problems, check that appropriate repairs were made, and if not, implement such repairs.
1-3 Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.

2. INTRODUCTION

•VRVIII-Q series are designed for outdoor installation and used for cooling and heat pump applications. Outdoor units come in three standard sizes, and with a single system through a multi system combining up to three outdoor units (Heat Pump series), and up to four outdoor units (Heat Recovery series). Rated capacity is below. RQ(C)YQ: Cooling 14.0~54.0 kW, Heating 16.0~60.0 kW RQCEQ: Cooling 28.0~84.8 kW, Heating 32.0~89.6 kW
• The BS units that combined with RQCEQ system for changing the refrigerant flow to indoor units are A type (BSQ-AV1, BS1Q­A7V1B, BS-Q14AV1) and P type (BSVQ-P, BSV-Q100P) only. Combination with A type and P type cause malfunction.
• The VRV units can be combined with Daikin VRV series indoor units for air conditioning purposes. Always use appropriate indoor units compatible with R410A. To learn which models of indoor units are compatible with R410A, refer to the product catalogs. Combination with other indoor refrigerant units will cause malfunc­tion.
2-1 Combination
The indoor units can be installed in the following range.
• Heat Pump series (RQ(C)YQ) <Outdoor unit> <Total capacity of indoor units> <Total quantity of indoor units>
RQYQ140PY1 ....................7.0 ~ 18.2 8 units
RQYQ180PY1 ....................9.0 ~ 23.4 10 units
RQCYQ280PY1............... 14.0 ~ 36.4 16 units
RQCYQ360PY1................17.8 ~ 46.2 20 units
RQCYQ460PY1................22.5 ~ 58.5 26 units
RQCYQ500PY1................25.0 ~ 65.0 29 units
RQCYQ540PY1................28.0 ~ 72.8 33 units
• Heat Recovery series (RQCEQ) <Outdoor unit> <Total capacity of indoor units> <Total quantity of indoor units>
RQCEQ280PY13..............14.0 ~ 36.4 16 units
RQCEQ360PY13..............17.8 ~ 46.2 20 units
RQCEQ460PY13..............22.5 ~ 58.5 26 units
RQCEQ500PY13..............25.0 ~ 65.0 29 units
RQCEQ540PY13..............28.0 ~ 72.8 33 units
RQCEQ636PY13..............30.8 ~ 80.0 36 units
RQCEQ712PY13..............34.5 ~ 89.7 40 units
RQCEQ744PY13..............36.5 ~ 94.9 43 units
RQCEQ816PY13..............40.0 ~ 104 47 units
RQCEQ848PY13..............42.5 ~ 111 50 units
Note
• Be sure to connect an R410A indoor unit. See the catalog for indoor unit models which can be connected.
• Above is the total capacity and total number of units of the indoor units when configured in a standard combination. See the techni­cal reference for details on total capacity and total number of indoor units when using a configuration other than the standard combination. The standard combinations are as follows.
• Heat Pump series (RQ(C)YQ) <Combination unit> <Independent unit> RQYQ140PY1 RQYQ140PY1 RQYQ180PY1 RQYQ180PY1 RQCYQ280PY1 RQYQ140PY1+RQYQ140PY1 RQCYQ360PY1 RQYQ180PY1+RQYQ180PY1 RQCYQ460PY1 RQCYQ500PY1 RQCYQ540PY1
• Heat Recovery series (RQCEQ) <Combination unit> <Independent unit> RQCEQ280PY13 RQEQ140PY13+RQEQ140PY13 RQCEQ360PY13 RQEQ180PY13+RQEQ180PY13 RQCEQ460PY13 RQCEQ500PY13 RQCEQ540PY13 RQCEQ636PY13 RQCEQ712PY13 RQCEQ744PY13 RQCEQ816PY13 RQCEQ848PY13
Note
• Combinations other than those above are prohibited.
• If the total capacity of the connected indoor units exceeds the capacity of the outdoor unit, cooling and heating performance may drop when running the indoor units. See the capacity table in the Engineering Data Book for details.
• There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system. Install so that the following restrictions are satisfied. <Restrictions> The capacities of outdoor units A and B must fulfill the following conditions.
A B
to indoor unit
Outdoor unit multi connection piping kit
RQYQ180PY1+RQYQ140PY1+RQYQ140PY1 RQYQ180PY1+RQYQ180PY1+RQYQ140PY1 RQYQ180PY1+RQYQ180PY1+RQYQ180PY1
RQEQ180PY13+RQEQ140PY13+RQEQ140PY13 RQEQ180PY13+RQEQ180PY13+RQEQ140PY13 RQEQ180PY13+RQEQ180PY13+RQEQ180PY13 RQEQ212PY13+RQEQ212PY13+RQEQ212PY13 RQEQ212PY13+RQEQ180PY13+RQEQ180PY13+RQEQ140PY13 RQEQ212PY13+RQEQ212PY13+RQEQ180PY13+RQEQ140PY13 RQEQ212PY13+RQEQ212PY13+RQEQ212PY13+RQEQ180PY13 RQEQ212PY13+RQEQ212PY13+RQEQ212PY13+RQEQ212PY13
Outdoor
unit A
Outdoor
unit B
2-2 Standard supplied accessories
The following accessories are included. The storage location of the accessories is shown in figure 1.
• Heat Pump series (RQYQ)
Name
Quantity
Shape
Name Clamp (1) Clamp (2) Clamp (3) Others Quantity
Shape
Gas side
accessory
pipe (1)
1 pc. 1 pc. 1 pc. 1 pc. 1 pc.
(Long) (Short)
1 pc. 8 pcs. 1 pc. 1 pc. each item
(Large) (Small)
Gas side
accessory
pipe (2)
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
• Operation manual
• Installation manual
• Declaration confor­mity (PED, EMC, MD)
• “REQUEST FOR THE INDICATION” label (Installation records)
• “ADDITIONAL REF. CHARGE” label
L type
accessory
joint
3 English
• Heat Recovery series (RQEQ)
Name
Quantity
Shape
Name
Quantity
Shape
Note
Do not throw away any of the accessories until installation is com­plete.
Suction
gas side
accessory
pipe (1)
1 pc. 1 pc. 1 pc. 1 pc. 1 pc. 1 pc.
Q140 type: φ15.9,
Q180·212 type:
L type
accessory
2 pcs. 1 pc. 8 pcs. 1 pc. 1 pc. each item
(Refer to figure 1)
1. Clamps, Operation manual, etc.
2. Accessory pipes
3. Installation manual
Suction
gas side
accessory
pipe (2)
Clamp (1) Clamp (2) Clamp (3)
joint
(Large) (Small)
φ
19.1
HP/LP
gas side
accessory
pipe (1)
Q140 type:
Q180·212 type:
HP/LP
gas side
accessory
pipe (2)
φ
12.7,
φ
15.9
Liquid side
accessory
pipe (1)
• Operation manual
• Installation manual
• Declaration con-
• “REQUEST FOR
• “ADDITIONAL
Liquid side accessory
pipe (2)
Others
formity (PED, EMC, MD)
THE INDICATION” label (Installation records)
REF. CHARGE” label
2-3 Option accessory
To install the outdoor units, the following optional parts are also required. To select an optimum kit, refer to “6-5 Example of connec-
tion”.
• Refrigerant branching kit
If it is not possible to use existing branch piping or if it is necessary to install new piping when installing refrigerant piping to BS/indoor units, the following parts are required. (Be sure to use branch piping of at least the design pressure of 3.3 MPa.)
• Heat Pump series (RQ(C)YQ)
REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H REFNET joint KHRP26A22T KHRP26A33T KHRP26A72T KHRP26A73T
• Heat Recovery series (RQCEQ)
for 3 piping for 2 piping
REFNET header
REFNET joint
• Outdoor unit multi connection piping kit
• Heat Pump series (RQ(C)YQ)
• Heat Recovery series (RQCEQ)
Note
Make sure that any separately purchased accessories are designed for use with R410A.
- KHRP25M33H KHRP26M22H KHRP26M33H
KHRP25M72H KHRP25M73H KHRP26M72H KHRP26M73H
KHRP25A22T KHRP25A33T KHRP26A22T KHRP26A33T KHRP25A72T KHRP25A73T KHRP26A72T KHRP26A73T
Kit name 2 units BHFP22P36C 3 units BHFP22P54C
Kit name 2 units BHFP26P36C 3 units BHFP26P63C 4 units BHFP26P84C
2-4 Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of specifica­tions.
2-5 Main components
For main components and function of the main components, refer to the Engineering Data Book.
2-6 Installation Process
Figure 2 shows the installation process. Install in the order of the steps shown.
(Refer to figure 2)
1. “3. SELECTION OF LOCATION”
2. “4. INSPECTING AND HANDLING THE UNIT”
3. “5. PLACING THE UNIT”
4. “6. REFRIGERANT PIPING”
5. “7. FIELD WIRING”
6. “8. AIR TIGHT TEST AND VACUUM DRYING”
7. “9. PIPE INSULATION”
8. “10. CHECKING OF DEVICE AND INSTALLATION
CONDITIONS”
9. “11. ADDITIONAL REFRIGERANT CHARGE AND
CHECK OPERATION”
10. “13. TEST RUN”
11. Operations which require the power to be turned on

3. SELECTION OF LOCATION

Select a location for installation that meets the following conditions. Get the customer’s permission.
1.
There is no danger of fire due to leakage of flammable gas.
2.
Select the location of the unit in such a way that neither the dis­charged air nor the sound generated by the unit disturb anyone.
3.
The foundation is strong enough to support the weight of the unit and the floor is flat to prevent vibration and noise generation.
4.
The piping length between the outdoor unit and the indoor unit may not exceed the allowable piping length. (Refer to
“6. REFRIGERANT PIPING”)
5.
Locations where the unit’s suction vent and outlet vent do not directly face the wind. Wind blowing directly into the suction or outlet vents will interfere with the unit’s operation. If necessary, install some kind of obstruction to block the wind.
6.
The space around the unit is adequate for servicing and the min­imum space for air inlet and air outlet is available. (See the “Installation Space Examples” for the minimum space requirements.)
Installation Space Examples.
• The installation space requirement shown in figure 3 is a refer­ence for cooling operation when the outdoor temperature is 35°C. If the design outdoor temperature exceeds 35°C or the heat load exceeds maximum capacity in all the outdoor unit, take an even large space on the intake shown in figure 3.
• During installation, install the units using the most appropriate of the patterns shown in figure 3 for the location in question, taking into consideration human traffic and wind.
• If the number of units installed is more than that is shown in the pattern in figure 3, install the units so there are no short circuits.
• As regards space in front of the unit, consider the space needed for the local refrigerant piping when installing the units.
• If the work conditions in figure 3 do not apply, contact your dealer or Daikin directly.
(Refer to figure 3)
1. Front side
2. No limit to wall height
3. Service space of front side
4. Service space of suction side
For Patterns 1 and 2 in figure 3:
• Wall height for the front side should be no higher than 1500
mm.
• Wall height for the suction side should be no higher than 500
mm.
• Wall height for the sides – no limit.
English 4
• If the height is exceeded the above, calculate h1 and h2 shown in the figure below, and add h1/2 to the service space of front side and h2/2 to the service space of suction side.
h1
A
1500
Front side
h1 = A (Actual height) – 1500 h2 = B (Actual height) – 500
Note
1.
An inverter air conditioner may cause electronic noise gener­ated from AM broadcasting. Examine where to install the main air conditioner and electric wires, keeping proper distances away from stereo equipment, personal computers, etc. Particularly for locations with weak reception, ensure there is a distance of at least 3 meters for indoor remote controllers, place power wiring and transmission wiring in conduits, and ground the conduits.
(Refer to figure 4)
1. Indoor unit
2. Branch switch, overcurrent breaker, earth leakage circuit
breaker
3. Remote controller
4. COOL/HEAT selector
5. Personal computer or radio
2.
When installing in a locations where there is heavy snowfall, implement the following snow measures.
• Ensure the base is high enough that intakes are not clogged by snow.
• Remove the rear intake grille to prevent snow from accumu­lating on the fins.
3.
If condensate may drip downstairs (or walkway) depending on the floor condition, take a measure such as the installation of central drain pan kit (sold separately).
4.
The refrigerant R410A itself is nontoxic, nonflammable and is safe. If the refrigerant should leak however, its concentration may exceed the allowable limit depending on room size. Due to this it could be necessary to take measures against leakage. See “14. CAUTION FOR REFRIGERANT LEAKS” for details.
h2
B
Suction side
500

4. INSPECTING AND HANDLING THE UNIT

• At delivery, the package should be checked and any damage should be reported immediately to the carrier claims agent.
• When handling the unit, take into account the following:
1.
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2.
Decide on the transportation route.
3.
If a forklift is to be used, pass the forklift arms through the large openings on the bottom of the unit. (Refer to figure 5)
4.
If hanging the unit, use a cloth sling to prevent damaging the unit. Keeping the following points in mind, hang the unit following the procedure shown in figure 6.
• Use a sling sufficiently strong to hold the mass of the unit.
• Use 2 belts of at least 8m long.
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
5.
After installation, remove the transportation clasp attached to the large openings. (Refer to figure 6)
6.
If carrying baggage the unit, hold hand top rear handle product and basic front lower leg product, carry as shown in figure 7.
• Because the equipment break, the product do not slant than
60 degree.
• Regularly wear glove to work.
• Obey local law about work method, and work more than 4 per-
sons.
(Refer to figure 5)
1. For k
2. Hole (large)
3. Transportation clasp (yellow)
4. Fixed screws of transportation clasp
(Refer to figure 6)
1. Belt sling
2. Board
3. Hole (large)
(Refer to figure 7)
1. Cushion plate
2. Foundation leg
3. Hanger
Note
Apply a filler cloth on a fork to prevent coating of the bottom frame from coming off and rust from occurring when bringing in the unit with anti-corrosion treatment type using a forklift.

5. PLACING THE UNIT

• Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise. (Refer to figure 8)
• The base should be bigger around than the width of the unit’s legs
(66 mm), and should support the unit. (Refer to figure 9) If protective rubber is to be attached, attach it to the whole face of the base.
• The height of the base should be at least 150mm from the floor.
• Secure the unit to its base using foundation bolts. (Use four com­mercially available M12-type foundation bolts, nuts, and washers.)
• The foundation bolts should be inserted 20 mm.
(Refer to figure 8)
1. The product can be supported with
four corners
(Refer to figure 9)
1. Foundation bolt point (φ15 dia. : 4 positions)
2. Depth of product
Note
• There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system. See the Note in “2-1 Combination” for detail.
• When installing on a roof, make sure the roof floor is strong enough and be sure to water-proof all work.
• Make sure the area around the machine drains properly by setting up drainage grooves around the foundation. Drain water is sometimes discharged from the outdoor unit when it is running.
• For anti-corrosion type use nuts with resin washers. If the paint on nut connections comes off, the anti-corrosion effect may decrease.
Resin washers
20

6. REFRIGERANT PIPING

Note
• All field piping must be installed by a licensed refrigeration tech­nician and must comply with relevant local and national regula­tions.
• After piping work is complete, do not under any circumstances open the shutoff valve until “7. FIELD WIRING” and “10. CHECK­ING OF DEVICE AND INSTALLATION CONDITIONS” are com­plete.
Do not use flux when brazing the refrigerant piping. Use the phos­phor copper brazing filler metal 710/795: ISO 3677) (Flux has extremely harmful influence on refrigerant piping sys-
tems. For instance, if chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant oil.)
which does not require flux.
6-1 Selection of piping material and Refrigerant
branching kit
• Use only pipes which are clean inside and outside and do not accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or other contamination. (Foreign materials inside pipes including oils for fabrication must be 30mg/10m or less.)
(BCuP-2: JIS Z 3264/B-Cu93P-
5 English
Loading...
+ 23 hidden pages