12-1. Onsite Settings With the Power Off.............................. 26
12-2. Onsite Settings With the Power On.............................. 26
13. TEST RUN ............................................................................. 26
13-1. Before test run.............................................................. 26
13-2. Test Run....................................................................... 26
13-3. Checks After Test Run .................................................26
14. CAUTION FOR REFRIGERANT LEAKS............................... 26
The English text is the original instruction. Other languages are
translations of the original instructions.
1.FIRST OF ALL
• Use the BS unit with Heat Recovery series (RQCEQ).
• This document is an installation manual for the Daikin VRVIII-Q
Series VRV Inverter. Before installing the unit, read this manual
thoroughly, and following the instructions contained in it. After
installation, do a test run to make sure the unit runs properly, and
then explain how to operate and take care of the unit to the customer, using the operation manual.
• Lastly, make sure the customer keeps this manual, along with the
operation manual, in a safe place.
• This manual does not describe how to install the indoor unit.
Refer to the installation manual included with the indoor unit for that.
1-1 Safety precautions
Please read these “Safety precautions” carefully before installing air
conditioning equipment and be sure to install it correctly.
Meaning of WARNING and CAUTION notices.
Both are important notices for safety. Be sure to follow them.
WARNING.....Failure to follow these instructions properly may
result in personal injury or loss of life.
CAUTION......Failure to observe these instructions properly
may result in property damage or personal
injury, which may be serious depending on the
circumstances.
After completing installation, conduct a test operation to confirm that
the equipment operates without any problems. Then, explain to the
customer how to operate the equipment and take care of it following
the operation manual. Ask the customer to store the installation manual along with the operation manual for future reference.
This air conditioner comes under the term “appliances not accessible
to the general public”.
VRV System is a class A product. In a domestic environment this
product may cause radio interference in which case the user may be
required to take adequate measures.
WARNING
• Ask your dealer or qualified personnel to carry out installation
work.
Do not attempt to install the air conditioner yourself. Improper
installation may result in water leakage, electric shocks or fire.
• Install the air conditioner in accordance with the instructions in
this installation manual.
Improper installation may result in water leakage, electric shocks
or fire.
• When installing the unit in a small room, take measures so that
the refrigerant may not exceed the limiting concentration in the
event of refrigerant leakage.
Contact your dealer for further information. If the refrigerant leaks
and exceeds the limiting concentration, it may lead to oxygen deficiency.
• Be sure to use only the specified accessories and par ts for installation work.
Failure to use the specified parts may result in the unit falling,
water leakage, electric shocks or fire.
• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
If a foundation does not have sufficient strength, the equipment
may fall and cause injury.
• Carry out the required installation work in consideration of strong
winds, typhoons or earthquakes.
If the installation work is not properly carried out, the unit may fall
down and cause accidents.
• The electrical work must be carried out by the qualified electrician
in accordance with the local laws and regulations and this installation manual. Make sure to provide a dedicated power supply circuit and never connect additional wiring to the existing circuit.
An insufficient power supply capacity or improper electrical work
may lead to electric shocks or fire.
• Be sure to earth the air conditioner.
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead.
Imperfect earthing may result in electric shocks or fire.
A high surge current from lightning or other sources may cause
damage to the air conditioner.
• Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric
shocks or fire.
• Be sure to switch off the unit before touching any electrical parts.
Touching a live part may result in electric shock.
1English
• For wiring, use the specified wires and connect and fasten them
firmly so that no external force from the wires may be applied to
the terminal connections.
If the wires are not firmly connected and fastened, it may cause
heating, fire or the like.
• When wiring the power supply and connecting the remote controller wiring and transmission wiring, position the wires so that the
EL.COMPO.BOX lid can be securely fastened.
Improper positioning of the EL.COMPO.BOX lid may result in
electric shocks, fire or the terminals overheating.
• If refrigerant gas leaks during installation, ventilate the area
immediately.
Toxic gas may be produced if the refrigerant comes into contact
with fire.
• After completing installation, check for refrigerant gas leakage.
Toxic gas may be produced if the refrigerant gas leaks into the
room and comes into contact with a source of fire, such as a fan
heater, stove or cooker.
• Do not directly touch refrigerant that has leaked from refrigerant
pipes or other areas, as there is a danger of frostbite.
• Do not allow children to climb on the outdoor unit and avoid placing objects on the unit.
Injury may result if the unit becomes loose and falls.
CAUTION
• Carry out drain piping properly following this installation manual
and insulate the pipe to prevent condensation.
Improper drain piping may result in indoor water leakage and
property damage.
• Install the indoor, BS and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter
may not be sufficient to eliminate noise.)
• Install the indoor unit and BS unit as far as possible from fluorescent lamps.
If a wireless kit is installed in a room where the electronic lighting
type (inverter or rapid start types) fluorescent lamps exist, the
transmitting distance of a remote controller may be shorter.
• Make sure to provide for adequate measures in order to prevent
that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire.
Please instruct the customer to keep the area around the unit
clean.
• Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or
vapour (e.g. a kitchen).
Plastic parts may deteriorate and cause parts to fall off or
water to leak.
2. Where corrosive gas, such as sulphurous acid gas, is pro-
duced.
Corrosion of copper pipes or brazed parts may occur and
cause refrigerant leakage.
3. Where there is a machine that generates electromagnetic
wave and where voltage fluctuation often occurs such as a factory.
Control system may malfunction and as a result the unit may
not properly operate.
4. Where flammable gas may leak, where carbon fibre or ignit-
able dust is suspending in the air, or where volatile flammables
such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
• The air conditioner is not intended for use in a potentially explosive atmosphere.
1-2 Special notice of product
[CLASSIFICATION]
This air conditioner comes under the term “appliances not accessible
to the general public”.
[EMC CHARACTERISTICS]
VRVIII System is a class A product. In a domestic environment this
product may cause radio interference in which case the user may be
required to take adequate measures.
[REFRIGERANT]
VRVIII System use R410A refrigerant.
• The refrigerant R410A requires that strict precautions be
observed for keeping the system clean, dry and tightly sealed.
Read the chapter “REFRIGERANT PIPING” carefully and follow
these procedures correctly.
A.Clean and dry
Strict measures must be taken to keep impurities (including
fluid, dirt and dust) out of the system.
B.Tightly sealed
R410A contains no chlorine, does not destroy the ozone layer
and so does not reduce the earth’s protection against harmful
ultraviolet radiation. R410A will contribute only slightly to the
greenhouse effect if released into the atmosphere. Therefore,
sealing tightness is particularly important in installation. Carefully read the chapter “REFRIGERANT PIPING” and strictly
observe the correct procedures.
• As the design pressure for local connection piping (suction·HP/LP
gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possible to use existing piping (design pressure of at least 3.3 MPa,)
but refer to "6. REFRIGERANT PIPING" and check that existing
piping (including branch piping) is compatible with this unit in
terms of materials and thickness and that it does not appear to be
corroded.
Air tight test (3.3 MPa 24/h) to check the strength of existing piping
and that it has no gas leaks.
If it is not possible to perform a pressure test, replace existing piping with piping rated at least 3.3 MPa.
• Check that there has not been compressor malfunction, gas supply exhaustion, or similar issues that could be attributable to pipe
problems in the past. If there have been any such problems,
check that appropriate repairs were made, and if not, implement
such repairs.
• Existing power supply and transmission wiring is also designed to
be used with existing wiring, but check that specifications match
and that parts (especially terminals) do not appear to have aged,
and implement appropriate procedures (e.g. replacement).
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (If the system is charged
with refrigerant in its gaseous state, due to composition change,
the system will not function normally).
• The indoor unit is designed for R410A use. See the catalogue for
indoor unit models that can be connected. (Normal operation is
not possible when connecting units that are originally designed for
other refrigerants.)
• The Heat Recovery Series (RQCEQ) cannot be connected to
older BS units (BSVQ-M Type).
Total maximum refrigerant charge limits.
The total maximum refrigerant charge of a VRVIII system must be
below 100kg, this to be in accordance with CE requirement
(EN60335-2-40 standard).
This means that in case the total maximum refrigerant charge of the
system (factory and additional charge) is equal to or more than 100kg
you must divide your multiple outdoor system into smaller independent systems, each containing less than 100kg refrigerant charge.
For factory charge, refer to the unit name plate.
Important information regarding the refrigerant used.
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type : R410A
(1)
GWP
value : 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
the factory refrigerant charge of the product,
the additional refrigerant amount charged onsite and
+the total refrigerant charge on the refrigerant charge label
supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the service cover).
4
factory refrigerant charge of
the product : see unit name
1
(2)
plate
1
additional refrigerant amount
2
2
charged in the field
3 total refrigerant charge
Contains fluorinated green-
3
4
house gases covered by the
5
6
Kyoto Protocol
5 outdoor unit
refrigerant cylinder and man-
6
ifold for charging
English2
(2)
In case of multiple outdoor systems, only 1 label must be adhered,
mentioning the total factory refrigerant charge of all outdoor units
connected on the refrigerant system.
[DESIGN PRESSURE]
• As the design pressure for local connection piping (suction·HP/LP
gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possible to use existing piping (design pressure of at least 3.3 MPa) but
refer to "6. REFRIGERANT PIPING" and check that existing piping (including branch piping) is compatible with this unit in terms
of materials and thickness and that it does not appear to be corroded.
Air tight test (3.3 MPa 24/h) to check the strength of existing piping
and that it has no gas leaks.
If it is not possible to perform a pressure test, place existing piping
with piping rated at least 3.3 MPa.
• Check that there has been no compressor malfunction, gas supply exhaustion, or similar issues that could be attributable to pipe
problems in the past. If there have been any such problems,
check that appropriate repairs were made, and if not, implement
such repairs.
1-3 Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
2.INTRODUCTION
•VRVIII-Q series are designed for outdoor installation and used for
cooling and heat pump applications. Outdoor units come in three
standard sizes, and with a single system through a multi system
combining up to three outdoor units (Heat Pump series), and up
to four outdoor units (Heat Recovery series). Rated capacity is
below.
RQ(C)YQ: Cooling 14.0~54.0 kW, Heating 16.0~60.0 kW
RQCEQ: Cooling 28.0~84.8 kW, Heating 32.0~89.6 kW
• The BS units that combined with RQCEQ system for changing the
refrigerant flow to indoor units are A type (BSQ-AV1, BS1QA7V1B, BS-Q14AV1) and P type (BSVQ-P, BSV-Q100P) only.
Combination with A type and P type cause malfunction.
• The VRV units can be combined with Daikin VRV series indoor
units for air conditioning purposes. Always use appropriate indoor
units compatible with R410A. To learn which models of indoor
units are compatible with R410A, refer to the product catalogs.
Combination with other indoor refrigerant units will cause malfunction.
2-1 Combination
The indoor units can be installed in the following range.
• Heat Pump series (RQ(C)YQ)
<Outdoor unit><Total capacity of indoor units><Total quantity of indoor units>
RQYQ140PY1 ....................7.0 ~ 18.28 units
RQYQ180PY1 ....................9.0 ~ 23.410 units
RQCYQ280PY1............... 14.0 ~ 36.416 units
RQCYQ360PY1................17.8 ~ 46.220 units
RQCYQ460PY1................22.5 ~ 58.526 units
RQCYQ500PY1................25.0 ~ 65.029 units
RQCYQ540PY1................28.0 ~ 72.833 units
• Heat Recovery series (RQCEQ)
<Outdoor unit><Total capacity of indoor units><Total quantity of indoor units>
RQCEQ280PY13..............14.0 ~ 36.416 units
RQCEQ360PY13..............17.8 ~ 46.220 units
RQCEQ460PY13..............22.5 ~ 58.526 units
RQCEQ500PY13..............25.0 ~ 65.029 units
RQCEQ540PY13..............28.0 ~ 72.833 units
RQCEQ636PY13..............30.8 ~ 80.036 units
RQCEQ712PY13..............34.5 ~ 89.740 units
RQCEQ744PY13..............36.5 ~ 94.943 units
RQCEQ816PY13..............40.0 ~ 10447 units
RQCEQ848PY13..............42.5 ~ 11150 units
Note
• Be sure to connect an R410A indoor unit.
See the catalog for indoor unit models which can be connected.
• Above is the total capacity and total number of units of the indoor
units when configured in a standard combination. See the technical reference for details on total capacity and total number of
indoor units when using a configuration other than the standard
combination. The standard combinations are as follows.
• Combinations other than those above are prohibited.
• If the total capacity of the connected indoor units exceeds the
capacity of the outdoor unit, cooling and heating performance
may drop when running the indoor units. See the capacity table in
the Engineering Data Book for details.
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
Install so that the following restrictions are satisfied.
<Restrictions>
The capacities of outdoor units A and B must fulfill the following
conditions.
The following accessories are included. The storage location of the
accessories is shown in figure 1.
• Heat Pump series (RQYQ)
Name
Quantity
Shape
NameClamp (1) Clamp (2) Clamp (3)Others
Quantity
Shape
Gas side
accessory
pipe (1)
1 pc.1 pc.1 pc.1 pc.1 pc.
(Long)(Short)
1 pc.8 pcs.1 pc.1 pc. each item
(Large)(Small)
Gas side
accessory
pipe (2)
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
• Operation manual
• Installation manual
• Declaration conformity (PED, EMC, MD)
• “REQUEST FOR
THE INDICATION”
label (Installation
records)
• “ADDITIONAL REF.
CHARGE” label
L type
accessory
joint
3English
• Heat Recovery series (RQEQ)
Name
Quantity
Shape
Name
Quantity
Shape
Note
Do not throw away any of the accessories until installation is complete.
Suction
gas side
accessory
pipe (1)
1 pc.1 pc.1 pc.1 pc.1 pc.1 pc.
Q140 type: φ15.9,
Q180·212 type:
L type
accessory
2 pcs.1 pc.8 pcs.1 pc.1 pc. each item
(Refer to figure 1)
1. Clamps, Operation manual, etc.
2. Accessory pipes
3. Installation manual
Suction
gas side
accessory
pipe (2)
Clamp (1) Clamp (2) Clamp (3)
joint
(Large) (Small)
φ
19.1
HP/LP
gas side
accessory
pipe (1)
Q140 type:
Q180·212 type:
HP/LP
gas side
accessory
pipe (2)
φ
12.7,
φ
15.9
Liquid side
accessory
pipe (1)
• Operation manual
• Installation manual
• Declaration con-
• “REQUEST FOR
• “ADDITIONAL
Liquid side
accessory
pipe (2)
Others
formity (PED,
EMC, MD)
THE INDICATION”
label (Installation
records)
REF. CHARGE”
label
2-3 Option accessory
To install the outdoor units, the following optional parts are also
required. To select an optimum kit, refer to “6-5 Example of connec-
tion”.
• Refrigerant branching kit
If it is not possible to use existing branch piping or if it is necessary to
install new piping when installing refrigerant piping to BS/indoor
units, the following parts are required. (Be sure to use branch piping
of at least the design pressure of 3.3 MPa.)
Kit name
2 unitsBHFP26P36C
3 unitsBHFP26P63C
4 unitsBHFP26P84C
2-4 Technical and Electrical specifications
Refer to the Engineering Data Book for the complete list of specifications.
2-5 Main components
For main components and function of the main components, refer to
the Engineering Data Book.
2-6 Installation Process
Figure 2 shows the installation process. Install in the order of the
steps shown.
(Refer to figure 2)
1. “3. SELECTION OF LOCATION”
2. “4. INSPECTING AND HANDLING THE UNIT”
3. “5. PLACING THE UNIT”
4. “6. REFRIGERANT PIPING”
5. “7. FIELD WIRING”
6. “8. AIR TIGHT TEST AND VACUUM DRYING”
7. “9. PIPE INSULATION”
8. “10. CHECKING OF DEVICE AND INSTALLATION
CONDITIONS”
9. “11. ADDITIONAL REFRIGERANT CHARGE AND
CHECK OPERATION”
10. “13. TEST RUN”
11. Operations which require the power to be turned on
3.SELECTION OF LOCATION
Select a location for installation that meets the following conditions.
Get the customer’s permission.
1.
There is no danger of fire due to leakage of flammable gas.
2.
Select the location of the unit in such a way that neither the discharged air nor the sound generated by the unit disturb anyone.
3.
The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
4.
The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. (Refer to
“6. REFRIGERANT PIPING”)
5.
Locations where the unit’s suction vent and outlet vent do not
directly face the wind.
Wind blowing directly into the suction or outlet vents will interfere
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.
6.
The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet is available.
(See the “Installation Space Examples” for the minimum space
requirements.)
Installation Space Examples.
• The installation space requirement shown in figure 3 is a reference for cooling operation when the outdoor temperature is 35°C.
If the design outdoor temperature exceeds 35°C or the heat load
exceeds maximum capacity in all the outdoor unit, take an even
large space on the intake shown in figure 3.
• During installation, install the units using the most appropriate of
the patterns shown in figure 3 for the location in question, taking
into consideration human traffic and wind.
• If the number of units installed is more than that is shown in the
pattern in figure 3, install the units so there are no short circuits.
• As regards space in front of the unit, consider the space needed
for the local refrigerant piping when installing the units.
• If the work conditions in figure 3 do not apply, contact your dealer
or Daikin directly.
(Refer to figure 3)
1. Front side
2. No limit to wall height
3. Service space of front side
4. Service space of suction side
For Patterns 1 and 2 in figure 3:
• Wall height for the front side should be no higher than 1500
mm.
• Wall height for the suction side should be no higher than 500
mm.
• Wall height for the sides – no limit.
English4
• If the height is exceeded the above, calculate h1 and h2 shown
in the figure below, and add h1/2 to the service space of front
side and h2/2 to the service space of suction side.
h1
A
1500
Front side
h1 = A (Actual height) – 1500
h2 = B (Actual height) – 500
Note
1.
An inverter air conditioner may cause electronic noise generated from AM broadcasting. Examine where to install the main
air conditioner and electric wires, keeping proper distances
away from stereo equipment, personal computers, etc.
Particularly for locations with weak reception, ensure there is
a distance of at least 3 meters for indoor remote controllers,
place power wiring and transmission wiring in conduits, and
ground the conduits.
When installing in a locations where there is heavy snowfall,
implement the following snow measures.
• Ensure the base is high enough that intakes are not clogged
by snow.
• Remove the rear intake grille to prevent snow from accumulating on the fins.
3.
If condensate may drip downstairs (or walkway) depending on
the floor condition, take a measure such as the installation of
central drain pan kit (sold separately).
4.
The refrigerant R410A itself is nontoxic, nonflammable and is
safe. If the refrigerant should leak however, its concentration
may exceed the allowable limit depending on room size. Due to
this it could be necessary to take measures against leakage.
See “14. CAUTION FOR REFRIGERANT LEAKS” for details.
h2
B
Suction side
500
4.INSPECTING AND HANDLING THE UNIT
• At delivery, the package should be checked and any damage
should be reported immediately to the carrier claims agent.
• When handling the unit, take into account the following:
1.
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor damage.
2.
Decide on the transportation route.
3.
If a forklift is to be used, pass the forklift arms through the large
openings on the bottom of the unit. (Refer to figure 5)
4.
If hanging the unit, use a cloth sling to prevent damaging the unit.
Keeping the following points in mind, hang the unit following the
procedure shown in figure 6.
• Use a sling sufficiently strong to hold the mass of the unit.
• Use 2 belts of at least 8m long.
• Place extra cloth or boards in the locations where the casing
comes in contact with the sling to prevent damage.
• Hoist the unit making sure it is being lifted at its center of gravity.
5.
After installation, remove the transportation clasp attached to the
large openings. (Refer to figure 6)
6.
If carrying baggage the unit, hold hand top rear handle product
and basic front lower leg product, carry as shown in figure 7.
• Because the equipment break, the product do not slant than
60 degree.
• Regularly wear glove to work.
• Obey local law about work method, and work more than 4 per-
sons.
(Refer to figure 5)
1. For k
2. Hole (large)
3. Transportation clasp (yellow)
4. Fixed screws of transportation clasp
(Refer to figure 6)
1. Belt sling
2. Board
3. Hole (large)
(Refer to figure 7)
1. Cushion plate
2. Foundation leg
3. Hanger
Note
Apply a filler cloth on a fork to prevent coating of the bottom frame
from coming off and rust from occurring when bringing in the unit with
anti-corrosion treatment type using a forklift.
5.PLACING THE UNIT
• Make sure the unit is installed level on a sufficiently strong base to
prevent vibration and noise. (Refer to figure 8)
• The base should be bigger around than the width of the unit’s legs
(66 mm), and should support the unit. (Refer to figure 9)
If protective rubber is to be attached, attach it to the whole face of
the base.
• The height of the base should be at least 150mm from the floor.
• Secure the unit to its base using foundation bolts. (Use four commercially available M12-type foundation bolts, nuts, and washers.)
• The foundation bolts should be inserted 20 mm.
(Refer to figure 8)
1. The product can be supported with
four corners
(Refer to figure 9)
1. Foundation bolt point (φ15 dia. : 4 positions)
2. Depth of product
Note
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
See the Note in “2-1 Combination” for detail.
• When installing on a roof, make sure the roof floor is strong
enough and be sure to water-proof all work.
• Make sure the area around the machine drains properly by setting
up drainage grooves around the foundation.
Drain water is sometimes discharged from the outdoor unit when
it is running.
• For anti-corrosion type use nuts with resin washers. If the paint on
nut connections comes off, the anti-corrosion effect may
decrease.
Resin washers
20
6.REFRIGERANT PIPING
Note
• All field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations.
• After piping work is complete, do not under any circumstances
open the shutoff valve until “7. FIELD WIRING” and “10. CHECKING OF DEVICE AND INSTALLATION CONDITIONS” are complete.
•
Do not use flux when brazing the refrigerant piping. Use the phosphor copper brazing filler metal
710/795: ISO 3677)
(Flux has extremely harmful influence on refrigerant piping sys-
tems. For instance, if chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
damage the refrigerant oil.)
which does not require flux.
6-1 Selection of piping material and Refrigerant
branching kit
• Use only pipes which are clean inside and outside and do not
accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or
other contamination. (Foreign materials inside pipes including oils
for fabrication must be 30mg/10m or less.)
(BCuP-2: JIS Z 3264/B-Cu93P-
5English
Loading...
+ 23 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.