Daikin LREYQ16AY1, LREYQ16AY1E Installation manuals

INSTALLATION MANUAL
CONVENI-PACK
(LRYEQ16AY1(E))
Installation manual
CONVENI-PACK
Installationsanleitung
CONVENI-PACK
Manuel d’installation
CONVENI-PACK
Manual de instalación
CONVENI-PACK
Manuale di installazione
CONVENI-PACK
Installatiehandleiding
CONVENI-PACK
Manual de instalação
CONVENI-PACK
English
Deutsch
Français
Español
Italiano
Nederlands
Portugues
LRYEQ16AY1(E)
CONTENTS
1. FIRST OF ALL ......................................................................... 1
1-1 Safety Precautions ............................................................ 1
1-2 Special Notice of Product.................................................. 2
1-3 Disposal Requirements ..................................................... 2
2. BEFORE INSTALLATION........................................................2
2-1 Standard Supplied Accessories ........................................ 2
2-2 Example of System Configuration.....................................3
2-3 Indoor Unit Constraints ..................................................... 3
3. SELECTION OF LOCATION ...................................................3
4. HANDLING THE UNIT ............................................................. 4
5. PLACING THE UNIT................................................................5
6. REFRIGERANT PIPING .......................................................... 5
6-1 Selection of Piping Material .............................................. 6
6-2 Protection Against Contamination
when Installing Pipes ........................................................7
6-3 Pipe Connection................................................................7
6-4 Drier Installation ................................................................ 7
6-5 Connecting the Refrigerant Piping .................................... 7
7. FIELD WIRING ........................................................................ 9
7-1 Example of Wiring Entire System ................................... 11
7-2 Procedure for Incoming Wiring ....................................... 11
7-3 Procedure for Power Supply Wiring ................................ 12
7-4 Procedure for Wiring Inside Units ................................... 13
8. INSPECTION AND PIPE INSULATION.................................14
8-1 Air Tight Test/Vacuum Drying ......................................... 14
8-2 Thermal Insulation Work ................................................. 14
8-3 Checking of Device and Installation Conditions .............. 15
9. CHECKS AFTER WORK COMPLETION .............................. 15
10. REFRIGERANT REPLENISHMENT......................................15
11. TEST RUN ............................................................................. 16
1. FIRST OF ALL
• This document is an installation manual for the Daikin CONVENI­PACK. Before installing the unit, read this manual thoroughly, and following the instructions contained in it. After installation, do a test run to make sure the unit runs properly, and then explain how to operate and take care of the unit to the customer, using the operation manual.
• Lastly, make sure the customer keeps this manual, along with the operation manual, in a safe place.
This manual does not describe how to install the indoor unit. Refer to the installation manual included with the indoor unit for that.
1-1 Safety Precautions
Please read these “Safety precautions” carefully before installing the CONVENI-PACK and be sure to install it correctly. After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate the CONVENI­PACK and take care of it with the aid of the operation manual. Ask the customer to store the installation manual along with the operation manual for future reference.
Meaning of WARNING and CAUTION notices
WARNING .....Failure to follow these instructions properly may
result in personal injury or loss of life.
CAUTION......Failure to observe these instructions properly
may result in property damage or personal injury, which may be serious depending on the circumstances.
WARNING
• Ask your dealer or qualified personnel to carry out installation work. Do not attempt to install the CONVENI-PACK yourself. Improper installation may result in water leakage, electric shocks or fire.
CONVENI-PACK
• Maintenance personnel of the manufacturer or equivalent skilled personnel should install this unit.
• Install the CONVENI-PACK in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electric shocks or fire.
• When installing the unit in a small room, take measures against to keep refrigerant concentration from exceeding allowable safety limits in the event of refrigerant leakage. Contact the place of purchase for more information. Excessive refrigerant in a closed ambient can lead to oxygen deficiency.
• Be sure to use only the specified accessories and parts for instal­lation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.
• Install the CONVENI-PACK on a foundation strong enough to withstand the weight of the unit. A foundation of insufficient strength may result in the equipment falling and causing injury.
• Carry out the specified installation work after taking into account strong winds, typhoons or earthquakes. Failure to do so during installation work may result in the unit fall­ing and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qualified person­nel according to local laws and regulations and this installation manual. An insufficient power supply capacity or improper electrical con­struction may lead to electric shocks or fire.
• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal connections or wires. Improper connections or securing of wires may result in abnormal heat build-up or fire.
• When wiring the power supply and connecting transmission wir­ing, position the wires so that the control box lid can be securely fastened. Improper positioning of the control box lid may result in electric shocks, fire or the terminals overheating.
• If refrigerant gas leaks during installation, ventilate the area immediately. Toxic gas may be produced if the refrigerant gas comes into con­tact with fire.
• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
• Be sure to switch off the unit before touching any electrical parts.
• Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas, as there is a danger of frostbite.
• Do not allow children to climb on the outside unit and avoid plac­ing objects on the unit. Injury may result if the unit becomes loose and falls.
Be sure to earth the CONVENI-PACK. Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks or fire. A high surge current from lightning or other sources may cause damage to the CONVENI-PACK.
• Be sure to install an earth leakage breaker. Failure to install an earth leakage breaker may result in electric shocks or fire.
CAUTION
• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate piping to pre­vent condensation. Improper drain piping may result in indoor water leakage and property damage.
Installation manual
English 1
• Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions or radios to prevent picture interference and noise. (Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)
• Do not install the CONVENI-PACK in the following locations:
1. Where there is a high concentration of mineral oil spray or
vapor (e.g. a kitchen). Plastic parts will deteriorate, parts may fall off and water leak­age could result. Where corrosive gas, such as sulphurous acid gas, is produced.
2.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in a malfunction of the unit.
4. Where flammable gas may leak, where there is carbon fiber or
ignitable dust suspensions in the air, or where volatile flamma­bles such as paint thinner or gasoline are handled. Operating the unit in such conditions may result in fire.
5. Vehicles, ships, or other places that generate vibration or
cause the CONVENI-PACK to move. The CONVENI-PACK may malfunction or cause oxygen defi­ciency accidents as a result of refrigerant leakage.
6. Places with excessive voltage fluctuations.
The CONVENI-PACK may malfunction.
7. Places where fallen leaves accumulate or weeds grow thick.
8. Places that become small animals’ shelter.
Small animals coming in contact with electrical parts can cause malfunctions, smoke, or ignition.
• The CONVENI-PACK is not intended for use in a potentially explo­sive atmosphere.
1-2 Special Notice of Product
[CLASSIFICATION]
• This CONVENI-PACK comes under the term “appliances not accessible to the general public”.
• Follow the showcase to be connected for the climate class. (EN60335-2-89)
[EMC CHARACTERISTICS]
This System is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
[REFRIGERANT] This System use R410A refrigerant.
CAUTION
This unit is already filled with a certain amount of R410A. Never open liquid and gas shutoff valve until the step Specified in “9. CHECKS AFTER WORK COMPLETION”.
• The refrigerant R410A requires strict cautions for keeping the sys­tem clean, dry and tight. Read the chapter “REFRIGERANT PIPING” carefully and follow these procedures correctly. A. Clean and dry
Foreign materials (including mineral oils such as SUNISO oil or moisture) should be prevented from getting mixed into the system.
B. Tight
Take care to keep the system tight when installing. R410A does not contain any chlorine, does not destroy the ozone layer, and does not reduce the earth’s protection against harmful ultraviolet radiation. R410A can contribute slightly to the greenhouse effect if it is released.
• Since R410A is a mixed refrigerant, the required additional refrig­erant must be charged in its liquid state. If the refrigerant is charged in a state of gas, its composition changes and the system will not work properly.
• Be sure to perform refrigerant replenishment. Refer to “9. CHECKS AFTER WORK COMPLETION” and the label of instructions on refrigerant replenishment on the cover surface of the control box,
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type : R410A
(1)
GWP
value : 1975
(1)
GWP = global warming potential * Values are indicated in F-gas regulations (EC) No.842/2006, Annex I, Parts 1 and 2. Please fill in with indelible ink,
Q the factory refrigerant charge of the product, Q the additional refrigerant amount charged in the field and Q + the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the service cover).
4
1 factory refrigerant charge
of the product : see unit name plate
1
2 additional refrigerant
2
amount charged in the field
3 total refrigerant charge
4 Contains fluorinated
3
5
6
greenhouse gases covered by the Kyoto Protocol
5 outdoor unit
6 refrigerant cylinder and
manifold for charging
[DESIGN PRESSURE]
Since design pressure is 3.8MPa or 38bar (for R407C units : 3.3MPa or 33bar), the wall thickness of pipes should be more carefully selected in accordance with the relevant local and national regula­tions.
1-3 Disposal Requirements
Dismantling of the unit, treatment of the refrigerant, oil and eventual other parts, should be done in accordance with the relevant local and national regulations.
2. BEFORE INSTALLATION
CAUTION
• When installing the indoor unit, refer to the installation manual provided for the indoor unit.
• Optional accessories are required for the installation of the prod­uct. Refer to the information on optional accessory.
2-1 Standard Supplied Accessories
The following accessories are included. The storage location of the accessories is shown in the figure.
Note
Do not throw away any of the accessories until installation is complete.
Gas side
accessory
pipe (2)
Name Clamp (1) Clamp (2)
Quantity
11 pcs. 2 pcs. 1 pc. 1 pc.
Shape
Small
Gas side
accessory
pipe (1)
2 English
Name
Quantity
Shape
Name
Quantity
Shape
Liquid side accessory
pipe (1)
1 pc. 1 pc.
Liquid side
accessory
pipe (3)
1 pc. 1 pc. 1 pc. about each item
Liquid side accessory
pipe (2)
Liquid side
accessory
pipe (4)
• Operation manual
• Installation manual
• Declaration of con­formity (PED)
• “ADDITIONAL REF. CHARGE” label
Others
2-2 Example of System Configuration
Name Outdoor unit Booster unit
Shape
Indoor unit
Name
Shape
Name
Shape
Air-conditioner
Indoor unit
Freezer
Blower coil
Blower coil Showcase
Showcase
1, 2, 3
Control
panel
(Defrost)
Refrigeration
Warning
panel
Remote
controller
(for air-
conditioner)
2-3 Indoor Unit Constraints (Refrigeration and
Freezer)
• The design pressure for the indoor unit is 2.5 MPa or more.
• Install an R410A mechanical thermostatic expansion valve on each indoor unit.
• Insulate the feeler block of the mechanical thermostatic expan­sion valve.
• Install an R410A solenoid valve on the primary side of the mechanical thermostatic expansion valve (Max. operating differ­ential pressure of 3.5 MPa [35 bars] or over) described above for each indoor unit.
• Install a filter on the primary side of the solenoid valve described above for each indoor unit. Determine the filter mesh count based on the size specified by the solenoid valve and mechanical ther­mostatic expansion valve being used.
• Route the path to the indoor unit heat exchanger so that the flow of refrigerant is from top to bottom.
• When installing a number of indoor units, be sure to install them at the same level.
• Use either off-cycle defrosting or electric heater defrosting as the defrosting type. Hot-gas defrosting models cannot be used.
3. SELECTION OF LOCATION
Select a location for installation that meets the following conditions. Get the customer’s permission.
1. There is no danger of fire due to leakage of inflammable gas.
2. Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.
3. The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.
4. The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. (Refer to “6. REFRIGERANT PIPING”)
5. Locations where the unit’s suction vent and outlet vent do not gen-
erally face the wind. Wind blowing directly into the suction or outlet vents will interfere with the unit’s operation. If necessary, install some kind of obstruction to block the wind.
6. The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available. (See the “Installation Space Examples” for the minimum space requirements.)
Installation Space Examples
• The installation space requirement shown in the following figure is a reference for cooling operation when the outdoor temperature is 32°C. If the design outdoor temperature exceeds 32°C or the heat load exceeds maximum capacity in all the outdoor unit, take an even large space on the intake shown in the following figure.
• During installation, install the units using the most appropriate of the patterns shown in the following figure for the location in ques­tion, taking into consideration human traffic and wind.
• If the number of units installed is more than that shown in the pat­tern in the following figure, install the units so there are no short circuits.
• As regards space in front of the unit, consider the space needed for the local refrigerant piping when installing the units.
• If the work conditions in the following figure do not apply, contact your dealer or Daikin directly.
4
1 Operation manual 2 Installation manual 3 Clamps 4 Accessory pipes (Installed on bottom frame)
English 3
<
When installed as a single unit
(Pattern 1) NOTE)
300
10 10
Front
side
(Pattern 2) NOTE) (Pattern 2) NOTE)
50 50
Front
side
(Pattern 3) (Pattern 3)
300
200
Front side
500≥100≥500
No limit to wall height
>
<
When installed in serial
(Pattern 1) NOTE)
Service space
of suction side
1020
Service space
of front side
Service space
of suction side
50100
Service space
of front side
Front side
Front side
1020
50100
No limit to wall height
300
200400 400
Front side
NOTE) For Patterns 1 and 2
• Wall height for front side no higher than 1500 mm.
• Wall height on the suction side no higher than 500 mm.
• Wall height for sides – no limit
• If the height is exceeded the above, calculate h1 and h2 shown in the figure on next page, and add h1/2 to the service space of front side and h2/2 to the service space of suction side.
>
300≥500
Service space
of suction side
Service space
of front side
Service space
of suction side
100≥500
Service space
of front side
power wiring and transmission wiring in conduits, and ground the conduits.
2. When installing in a locations where there is heavy snowfall,
implement the following snow measures.
• Ensure the base is high enough that intakes are not clogged by snow.
• Mount a snow protection hood (optional accessory)
• Remove the rear intake grille to prevent snow from accumulat­ing on the fins.
3. If condensate may drip on downstairs (or walkway) depending on
the floor condition, take a measure such as the installation of cen­tral drain pan kit (sold separately).
4. The refrigerant R410A itself is nontoxic, nonflammable and is
safe. If the refrigerant should leak however, its concentration may exceed the allowable limit depending on room size. Due to this it could be necessary to take measures against leakage. See “Engineering Data” for details.
4. HANDLING THE UNIT
1. Decide on the transportation route.
2. If a forklift is to be used, pass the forklift arms through the large
openings on the bottom of the unit.
1
h1
A
1500
Service space
Service space
h1 = A (Actual height) – 1500 h2 = B (Actual height) – 500 X = 500 + h1/2 or over Y = 300 + h2/2 or over (Y = 100 + h2/2 or over) [Values in parentheses are for pattern 2]
CAUTION
Branch switch, overcurrent breaker (Earth leakage breaker)
Front side
Control panel Warning panel
B
Suction side
500 h2
Branch switch, overcurrent breaker (Earth leakage breaker)
4
2
3
1 Opening (large) 2 Fork 3 Fixed screws of transportation clasp 4 Transportation clasp (yellow)
If hanging the unit, use a cloth sling to prevent damaging the unit. Keeping the following points in mind, hang the unit following the procedure shown in the following figure.
• Use a sling sufficiently strong to hold the mass of the unit.
• Use 2 belts of at least 8m long.
• Place extra cloth in the locations where the casing comes in contact with the sling to prevent damage.
Hoist the unit making sure it is being lifted at its center of gravity.
1
2
3
4
5
1500
1500
1500
1500
Showcase
1500
(mm)
1. An inverter CONVENI-PACK may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the main CONVENI-PACK and electric wires, keeping proper distances away from stereo equipment, personal computers, etc. Particularly for locations with weak reception, ensure there is a distance of at least 3 meters for indoor remote controllers, place
1 Belt sling 2 Patch cloth 3 Belt sling 4 Patch cloth 5 Opening
3. After installation, remove the transportation clasp (yellow)
attached to the large openings.
Note
Apply a filler cloth on a fork to prevent coating of the bottom frame from coming off and rust from occurring when bringing in the unit with anti-corrosion treatment type using a forklift.
4 English
5. PLACING THE UNIT
• Make sure the unit is installed level on a sufficiently strong base to prevent vibration and noise.
• The base should be bigger around than the width of the unit’s legs (66 mm), and should support the unit. If protective rubber is to be attached, attach it to the whole face of the base.
• The height of the base should be at least 150mm from the floor.
Secure the unit to its base using foundation bolts. (Use four com­mercially available M12-type foundation bolts, nuts, and washers.)
• The foundation bolts should be inserted 20 mm.
Corner-hole foundation
Independent foundation
100
100
100
Center of the product
Beam foundation (horizontal)
Center of the product
Base form
Foundation bolt point
1240
(4-15 × 22.5)
1102
729
765
(Depth of product)
Base width and base bolt positions
Note
• When installing on a roof, make sure the roof floor is strong enough and be sure to water-proof all work.
• Make sure the area around the machine drains properly by setting up drainage grooves around the foundation. Drain water is sometimes discharged from the outdoor unit when it is running.
• If the CONVENI-PACK is of brine damage resistant or heavy brine dam­age resistant type, use nuts provided with resin washers to secure the prod­uct to the foundation bolts (see the illustration on the right-hand side). The rustproof effect of the nut will be lost if the coatings on the tightening portions of the nuts come off.
Beam foundation (vertical)
100
100
631
of the base)
765 or more
(Inner dimension
(Unit : mm)
Resin washers
100
of the base)
(Outer dimension
6. REFRIGERANT PIPING
To Piping Work Contractors
• Never open the shutoff valve until the steps specified in “7. FIELD WIRING” and “8-3 Checking of Device and Installation Condi­tions” of piping.
• Do not use flux at the time of brazing and connecting refrigerant pipes. Use phosphorous copper brazing filler metal (BCuP-2), which does not require flux. Chlorine-based flux causes piping corrosion. Furthermore, if fluoride is contained, the flux will have adverse influences on the refrigerant piping line, such as the dete-
20
rioration of refrigerating machine oil.
CAUTION
• All field piping must be installed by a licensed refrigeration tech­nician and must comply with relevant local and national regula­tions.
[Precautions for reuse of existing refrigerant piping / heat exchangers]
Keep the following points in mind for the reuse of existing refrig­erant piping / heat exchangers. A malfunction may result if there is deficiency.
• Do not use the existing piping in the following cases. Perform new piping instead.
• The piping is different in size.
• The strength of the piping is insufficient.
• The compressor of the CONVENI-PACK previously used
caused a malfunction. An adverse influence of residual substances, such as the oxi­dation of refrigerant oil and the generation of scale, is consid­ered.
• If the indoor unit or outdoor unit is disconnected from the piping
for a long time. The intrusion of water and dust into the piping is considered.
• The copper pipe is corroded.
• The refrigerant of the CONVENI-PACK previously used was
other than R410A (e.g., R404A / R507 or R407C). The contamination of the refrigerant with heterogeneity is con­sidered.
• If there are welded connections midway on the local piping, make gas leakage checks on the welded connections.
• Be sure to insulate the connection piping. The liquid and gas pipe temperatures are as follows: Liquid pipe arrival minimum temperature
20°C (Air-conditioning side) 5°C (Refrigeration side)
Gas pipe arrival minimum temperature:
0°C (Air-conditioning side)
–20°C (Refrigeration side) In the case of thickness insufficiency, add additional insulation material or renew the existing insulation material.
• Renew the insulation material if the insulation material is degraded.
Keep the following points in mind for the reuse of existing heat exchangers
• Units with insufficient design pressure (since this product is an R410A unit) require a lower-stage design pressure of 2.5 MPa [25 bars].
• Units for which the path to the heat exchanger has been routed so that the flow of refrigerant is from bottom to top.
• Units with copper tubing or fan corrosion.
• Units that may be contaminated with foreign matter such as rub­bish or other dirt.
English 5
Loading...
+ 14 hidden pages