Daikin FTXS25D3VMW, FTXS25D3VMWL, FTXS35D3VMW, FTXS35D3VMWL, FTXS50D2V1W Service Manual

...
SiENBE18-621
E-Series
Service Manual
[Applied Models] !Super Multi Plus: Heat Pump
Table of Contents i
SUPER MULTI PLUS
E-Series
!Heat Pump Indoor Unit
FTXS20D3VMW(L) FDXS25CAVMB FLXS25BAVMB FFQ25B8V1B FTXS25D3VMW(L) FDXS35CAVMB FLXS35BAVMB FFQ35B8V1B FTXS35D3VMW(L) FDXS50CVMB FLXS50BAVMB FFQ50B8V1B FTXS50D2V1W(L) FDXS60CVMB FLXS60BAVMB FFQ60B8V1B FTXS20CAVMB FDXS25EAVMB FVXS25BAVMB FHQ35BVV1B FTXS25CAVMB FDXS35EAVMB FVXS35BAVMB FHQ50BVV1B FTXS35CAVMB FVXS50BAVMB FHQ60BVV1B FTXS50EV1B FTXS60EV1B FTXS71EV1B FTXS71BAVMB
Outdoor Unit
RMXS112E7V3B BPMKS967B2B RMXS140E7V3B BPMKS967B3B RMXS160E7V3B
SiENBE18-621
ii Table of Contents
1. Introduction ...........................................................................................vii
1.1 Safety Cautions......................................................................................vii
Part 1 List of Functions ................................................................ 1
1. List of Functions......................................................................................2
Part 2 Specifications .................................................................... 9
1. Specifications........................................................................................10
1.1 Outdoor Units.........................................................................................10
1.2 BP Unit...................................................................................................11
1.3 Indoor Units............................................................................................12
Part 3 Printed Circuit Board Connector Wiring Diagram ........... 23
1. Printed Circuit Board Connector Wiring Diagram..................................24
1.1 Outdoor Unit RMXS 112/140/160 E7V3B ..............................................24
1.2 Branch Provider Unit..............................................................................29
1.3 Wall Mounted Type 20/25/35/50 Class - D Series .................................30
1.4 Wall Mounted Type 20/25/35 Class - C Series ......................................33
1.5 Wall Mounted Type 50/60/71 Class - E(B) Series..................................35
1.6 Duct Connected Type.............................................................................37
1.7 Floor / Ceiling Suspended Dual Type.....................................................39
1.8 Floor Standing Type...............................................................................42
1.9 Ceiling Mounted Cassette 600×600 Type..............................................45
1.10 Ceiling Suspended Type........................................................................47
Part 4 Refrigerant Circuit ........................................................... 49
1. Refrigerant Circuit.................................................................................50
1.1 Outdoor Units.........................................................................................50
1.2 BP Units .................................................................................................52
2. Functional Parts Layout ........................................................................53
2.1 Outdoor Units.........................................................................................53
3. Refrigerant Flow for Each Operation Mode...........................................54
3.1 Cooling Operation ..................................................................................54
3.2 Heating Operation..................................................................................55
3.3 Cooling Oil Return Operation.................................................................56
3.4 Heating Oil Return Operation & Defrost Operation ................................57
Part 5 Function............................................................................ 59
1. Operation Mode ....................................................................................60
2. Basic Control.........................................................................................61
2.1 Normal Operation...................................................................................61
2.2 Compressor PI Control...........................................................................62
2.3 Electronic Expansion Valve PI Control...................................................65
2.4 Cooling Operation Fan Control...............................................................66
3. Special Control......................................................................................67
3.1 Startup Control.......................................................................................67
3.2 Oil Return Operation ..............................................................................68
3.3 Defrosting Operation..............................................................................70
Table of Contents iii
3.4 Pump-down Residual Operation ............................................................71
3.5 Restart Standby......................................................................................71
3.6 Stopping Operation ................................................................................72
4. Protection Control .................................................................................73
4.1 High Pressure Protection Control...........................................................73
4.2 Low Pressure Protection Control............................................................74
4.3 Discharge Pipe Protection Control.........................................................75
4.4 Inverter Protection Control .....................................................................76
4.5 Freeze-up Protection Control.................................................................77
4.6 Dew Condensation Prevention Control..................................................78
5. Other Control.........................................................................................79
5.1 Demand Operation.................................................................................79
5.2 Heating Operation Prohibition................................................................79
6. BP Unit Control .....................................................................................80
6.1 BP Unit Command Conversion ..............................................................80
6.2 BP Unit Electronic Expansion Valve Control..........................................81
6.3 SH Control in Cooling Operation............................................................83
6.4 SC Control in Heating Operation............................................................84
6.5 Heat Exchanger Isothermal Control in Heating Operation.....................84
7. Indoor Unit (RA Models)........................................................................85
7.1 Power-Airflow Dual Flaps, Wide Angle Louvers and Auto-Swing ..........85
7.2 Fan Speed Control for Indoor Units........................................................86
7.3 Programme Dry Function.......................................................................87
7.4 Automatic Operation...............................................................................88
7.5 Thermostat Control.................................................................................89
7.6 Night Set Mode.......................................................................................90
7.7 ECONO Mode........................................................................................91
7.8 INTELLIGENT EYE................................................................................92
7.9 HOME LEAVE Operation.......................................................................94
7.10 Inverter POWERFUL Operation.............................................................95
7.11 Other Functions......................................................................................96
8. Indoor Unit (SkyAir Models)..................................................................98
8.1 Function Outline.....................................................................................98
8.2 Electric Function Parts ...........................................................................99
8.3 Function Details....................................................................................100
Part 6 Test Operation ............................................................... 111
1. Test Operation ....................................................................................112
1.1 Procedure and Outline .........................................................................112
2. Outdoor Unit PCB Layout....................................................................117
3. Field Setting........................................................................................118
3.1 Field Setting from Outdoor Unit............................................................118
3.2 Detail of Setting Mode..........................................................................127
4. Field Setting for SkyAir Indoor Unit.....................................................136
4.1 Explanation...........................................................................................136
4.2 Field Setting .........................................................................................137
4.3 Initial Setting Contents .........................................................................138
4.4 Local Setting Mode Number.................................................................139
4.5 Detailed Explanation of Setting Modes ................................................140
4.6 Centralized Group No. Setting .............................................................144
4.7 Maintenance Mode Setting...................................................................145
SiENBE18-621
iv Table of Contents
5. Test Operation and Field Setting for RA Indoor Unit...........................146
5.1 Test Operation from the Remote Control.............................................146
5.2 Jumper Settings ...................................................................................147
Part 7 System Configuration..................................................... 149
1. System Configuration..........................................................................150
1.1 Operation Instructions..........................................................................150
2. Instruction............................................................................................151
2.1 RMXS Series........................................................................................151
2.2 Wall Mounted, Duct, Floor/Ceiling, Floor Standing Type .....................152
2.3 Ceiling Mounted Cassette Type...........................................................227
2.4 Ceiling Suspended Type......................................................................238
Part 8 Troubleshooting ............................................................. 249
1. Caution for Diagnosis..........................................................................251
1.1 Troubleshooting with the Operation Lamp (RA Indoor Unit) ................251
1.2 Troubleshooting with the LED on the SkyAir Indoor Unit.....................252
1.3 Troubleshooting with the LED on the Outdoor Unit..............................253
1.4 Troubleshooting with the LED on the BP Unit......................................254
2. Service Check Function......................................................................255
2.1 RA Indoor Unit Infrared remote control ................................................255
2.2 SkyAir Indoor Unit INSPECTION/TEST Button....................................259
2.3 SkyAir Indoor Unit Wired Remote control.............................................260
2.4 SkyAir Indoor Unit Infrared remote control...........................................261
2.5 Sky Air Indoor Unit Error Codes and LED Indication............................263
2.6 Malfunction Code Indication by Outdoor Unit PCB ..............................264
3. List of Malfunction Code......................................................................268
4. Troubleshooting for RA Indoor Unit.....................................................270
4.1 Indoor Unit PCB Abnormality ...............................................................270
4.2 Freeze-up Protection Control or High Pressure Control.......................271
4.3 Fan Motor or Related Abnormality .......................................................273
4.4 Thermistor or Related Abnormality (Indoor Unit)..................................276
4.5 Shutter Drive Motor / Shutter Limit Switch Abnormality .......................277
4.6 Check...................................................................................................278
5. Troubleshooting for SkyAir Indoor Unit...............................................281
5.1 Indoor Unit PCB Abnormality ...............................................................281
5.2 Malfunction of Drain Water Level System (Float Type)........................282
5.3 Malfunction of Drain System ................................................................284
5.4 Indoor Unit Fan Motor Lock..................................................................285
5.5 Malfunction of Indoor Unit Fan Motor...................................................286
5.6 Swing Flap Motor Malfunction / Lock ...................................................288
5.7 Malfunction of Capacity Setting............................................................290
5.8 Malfunction of Heat Exchanger Thermistor (R2T)................................291
5.9 Malfunction of Heat Exchanger Thermistor (R3T)................................292
5.10 Malfunction of Suction Air Thermistor ..................................................293
5.11 Malfunction of Remote control Thermistor ...........................................294
5.12 Transmission Error (between Indoor Unit and Remote control)...........295
5.13 Transmission Error (between Main and Sub Remote control) .............296
5.14 Malfunction of Field Setting Switch ......................................................297
5.15 Check...................................................................................................298
Table of Contents v
6. Troubleshooting for BP Unit................................................................300
6.1 Malfunction of Electronic Expansion Valve ..........................................300
6.2 Faulty BP Unit PCB..............................................................................301
6.3 Faulty BP Liquid or Gas Pipe Thermistor.............................................302
6.4 Transmission Error between Indoor Unit and BP Unit..........................303
6.5 Transmission Error between Outdoor Unit and BP Unit.......................305
6.6 Check...................................................................................................306
7. Troubleshooting for Outdoor Unit........................................................307
7.1 Faulty Outdoor Unit PCB......................................................................307
7.2 Actuation of High Pressure Switch.......................................................308
7.3 Actuation of Low Pressure Sensor.......................................................310
7.4 Compressor Motor Lock.......................................................................312
7.5 Malfunction of Outdoor Unit Fan Motor................................................313
7.6 Malfunction of Moving Part of Electronic Expansion Valve
(Y1E, Y3E) ...........................................................................................314
7.7 Abnormal Discharge Pipe Temperature...............................................316
7.8 Refrigerant Overcharged......................................................................317
7.9 Malfunction of Thermistor for Outdoor Air (R1T)..................................318
7.10 Malfunction of Discharge Pipe Thermistor (R2T).................................319
7.11 Malfunction of Thermistor (R3T, R5T) for Suction Pipe1, 2 .................320
7.12 Malfunction of Thermistor (R4T) for Outdoor Unit Heat Exchanger.....321
7.13 Malfunction of Thermistor (R7T) for Outdoor Unit Liquid Pipe.............322
7.14 Malfunction of Subcooling Heat Exchanger Thermistor (R6T).............323
7.15 Malfunction of High Pressure Sensor...................................................324
7.16 Malfunction of Low Pressure Sensor....................................................325
7.17 Malfunction of PCB...............................................................................326
7.18 Malfunction of Inverter Radiating Fin Temperature Rise......................327
7.19 Inverter Compressor Abnormal............................................................328
7.20 Inverter Current Abnormal....................................................................329
7.21 Inverter Start up Error...........................................................................330
7.22 Malfunction of Transmission between Inverter and Control PCB.........331
7.23 High Voltage of Capacitor in Main Inverter Circuit ...............................332
7.24 Malfunction of Inverter Radiating Fin Temperature Rise Sensor .........333
7.25 Faulty Combination of Inverter and Fan Driver ....................................334
7.26 Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................335
7.27 Power Supply Insufficient or Instantaneous Failure.............................337
7.28 Check Operation not Executed ............................................................339
7.29 Malfunction of Transmission between Indoor Units and
Outdoor Units.......................................................................................340
7.30 Malfunction of Transmission between Remote control and
Indoor Unit............................................................................................342
7.31 Malfunction of Transmission between Main and Sub
Remote controls...................................................................................343
7.32 Malfunction of Transmission between Indoor and Outdoor Units
in the Same System.............................................................................344
7.33 Excessive Number of Indoor Units.......................................................346
7.34 Address Duplication of Central Remote control ...................................347
7.35 Malfunction of Transmission between Central Remote
Controller and Indoor Unit....................................................................348
7.36 System is not Set yet............................................................................350
7.37 Malfunction of System, Refrigerant System Address Undefined..........351
SiENBE18-621
vi Table of Contents
8. Check..................................................................................................352
9. Thermistor Resistance / Temperature Characteristics........................355
10.Pressure Sensor .................................................................................357
11.Method of Replacing The Inverter’s Power Transistors Modules........358
Part 9 Appendix......................................................................... 361
1. Piping Diagrams..................................................................................362
1.1 Outdoor Units.......................................................................................362
1.2 BP Units ...............................................................................................363
1.3 Indoor Units..........................................................................................364
2. Wiring Diagrams..................................................................................369
2.1 Outdoor Units.......................................................................................369
2.2 BP Units ...............................................................................................370
2.3 Indoor Units..........................................................................................371
Index ............................................................................................. i
Drawings & Flow Charts .............................................................. vii
vii
1. Introduction
1.1 Safety Cautions
Cautions and Warnings
" Be sure to read the following safety cautions before conducting repair work. " The caution items are classified into “ Warning” and “ Caution”. The “ Warning
items are especially important since they can lead to death or serious injury if they are not followed closely. The “ Caution” items can also lead to serious accidents under some conditions if they are not followed. Therefore, be sure to observe all the safety caution items described below.
" About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction. The instruction is shown inside or near the symbol. " After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the customer.
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before disassembling the equipment for a repair. Working on the equipment that is connected to a power supply can cause an electrical shook. If it is necessary to supply power to the equipment to conduct the repair or inspecting the circuits, do not touch any electrically charged sections of the equipment.
If the refrigerant gas discharges during the repair work, do not touch the discharging refrigerant gas. The refrigerant gas can cause frostbite.
When disconnecting the suction or discharge pipe of the compressor at the welded section, release the refrigerant gas completely at a well-ventilated place first. If there is a gas remaining inside the compressor, the refrig e ran t g as or refrigerating machine oil discharges when the pipe is disconnected, and it can cause injury.
If the refrigerant gas leaks during the repair work, ventilate the area. The refrigerant gas can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor can cause an electrical shock.
Do not start or stop the air conditioner operation by plugging or unplugging the power cable plug. Plugging or unplugging the power cable plug to operate the equipment can cause an electrical shock or fire.
Introduction SiENBE18-621
viii
1.1.2 Cautions Regarding Products after Repair
Caution
Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock.
Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
Be sure to turn off the power switch and unplug the power cable when cleaning the equipment. The internal fan rotates at a high speed, and cause injury.
Do not tilt the unit when removing it. The water inside the unit can spill and wet the furniture and floor.
Be sure to check that the refrigerating cycle section has cooled down sufficiently before conducting repair work. Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place. Using the welder in an enclosed room can cause oxygen deficiency.
Warning
Be sure to use parts listed in the service parts list of the applicable model and appropriate tools to conduct repair work. Never attempt to modify the equipment. The use of inappropriate parts or tools can cause an electrical shock, excessive heat generation or fire.
When relocating the equipment, make sure that the new installation site has sufficient strength to withstand the weight of the equipment. If the installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the provided standard installation frame. Incorrect use of the installation frame and improper install ation can cause the equipment to fall, resulting in injury.
For integral units only
Be sure to install the product securely in the installation frame mounted on a window frame. If the unit is not securely mounted, it can fall and cause injury.
For integral units only
ix
1.1.3 Inspection after Repair
Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
Be sure to use the specified cable to connect between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals. Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure that the terminal cover does not lift off or dismount because of the cable. If the cover is not mounted properly, the terminal connection section can cause an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable. Damaged or modified power cable can cause an electrical shock or fire. Placing heavy items on the power cable, and heating or pulling the power cable can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A ) in the refrigerant system. If air enters the refrigerating system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before charging the refrigerant. After charging refrigerant, make sure that there is no refrigerant leak. If the leak cannot be located and the repair work mu st be stopped, be sure to perform pump-down and close the service valve, to prevent the refrigerant gas from leaking into the room. The refrigerant gas itself is harmless, but it can generate toxic gases when it contacts flames, such as fan and other heaters, stoves and ranges.
When replacing the coin battery in the remote control, be sure to disposed of the old battery to prevent children from swallowing it. If a child swallows the coin battery, see a doctor immediately.
Warning
Caution
Installation of a leakage breaker is necessary in some cases depending on the conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of combustible gas leaks. If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. If the packing and seal are not installed properly, water can enter the room and wet the furniture and floor.
For integral units only
Warning
Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way. If the plug has dust or loose connection, it can cause an electrical shock or fire.
If the power cable and lead wires have scratches or deteriorated, be sure to replace them. Damaged cable and wires can cause an electrical shock, excessive heat generation or fire.
Introduction SiENBE18-621
x
1.1.4 Using Icons
Icons are used to attract the attention of the reader to specific information. The meaning of each icon is described in the table below:
1.1.5 Using Icons List
Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it can cause an electrical shock, excessive heat generation or fire.
Warning
Caution
Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock.
If the installation platform or frame has corroded, replace it. Corroded installation platform or frame can cause the unit to fall, resulting in injury.
Check the grounding, and repair it if the equipment is not properly grounded. Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure that the resistance is 1 Mohm or higher. Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage can cause the water to enter the room and wet the furniture and floor.
Icon Type of
Information
Description
Note:
Note A “note” provides information that is not indispensable, but may
nevertheless be valuable to the reader, such as tips and tricks.
Caution
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get an unexpected result or has to restart (part of) a procedure.
Warning
Warning A “warning” is used when there is danger of personal injury.
Reference A “reference” guides the reader to other places in this binder or
in this manual, where he/she will find additional information on a specific topic.
List of Functions 1
Part 1
List of Functions
1. List of Functions. .....................................................................................2
List of Functions SiENBE18-621
2 List of Functions
1. List of Functions
Category Functions
RMXS112·140·160E7V3B
Category Functions
RMXS112·140·160E7V3B
Basic Function
Inverter (with Inverter Power Control)
#
Health & Clean
Air Purifying Filter with Bacteriostatic & Virustatic Functions
Operation Limit for Cooling (°CDB)
–5
~
46
Photocatalytic Deodorizing Filter
Operation Limit for Heating (°CWB)
–15
~
15.5
Air Purifying Filter with Photocatalytic Deodorizing Function
PAM Control
Titanium Apatite Photocatalytic Air-Purifying Filter
Compressor
Oval Scroll Compressor # Longlife Filter (Option) Swing Compressor Mould Proof Air Filter — Rotary Compressor Wipe-clean Flat Panel — Reluctance DC Motor # Washable Grille
Comfortable Airflow
Power-Airflow Flap Filter Cleaning Indicator — Power-Airflow Dual Flaps Mold Proof Operation — Power-Airflow Diffuser Heating Dry Operation — Wide-Angle Louvers Good-Sleep Cooling Operation — Vertical Auto-Swing (Up and Down)
Timer
24-Hour On/Off Timer — Horizontal Auto-Swing (Right and Left) 72-Hour On/Off Timer — 3-D Airflow Night Set Mode — Comfort Airflow Mode
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) — 3-Step Airflow (H/P Only) Self-Diagnosis (Digital, LED) Display #
Comfort Control
Auto Fan Speed Wiring-Error Check — Indoor Unit Silent Operation Automatic Test Operation # Night Quiet Mode (Automatic) # Memory Function # Outdoor Unit Silent Operation
(Manual)
#
Anticorrosion Treatment of Outdoor
Heat Exchanger
#
Intelligent Eye
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
Quick Warming Function # Flexible Voltage Correspondence Hot-Start Function High Ceiling Application — Automatic Defrosting # Chargeless
Operation
Automatic Operation Either Side Drain (Right or Left) — Programme Dry Function Power-Selection
Fan Only
Remote Control
5-Rooms Centralized Controller
(Option)
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
Inverter Powerful Operation
Remote Control Adapter
(Normal Open Contact) (Option)
Priority-Room Setting
Dlll-NET Compatible (Adapter)
(Option)
Cooling / Heating Mode Lock
Remote Control
Wireless — Home Leave Operation Wired — ECONO Mode — Indoor Unit On/Off Switch — Signal Reception Indicator — Temperature Display — Another Room Operation
Note: # : Holding Functions
— : No Functions
List of Functions 3
Category Functions
FTXS20-35D3VMW(L)
FTXS50D2V1W(L)
FTXS20-35CAVMB
Category Functions
FTXS20-35D3VMW(L)
FTXS50D2V1W(L)
FTXS20-35CAVMB
Basic Function
Inverter (with Inverter Power Control) ###
Health & Clean
Air Purifying Filter with Bacteriostatic,
Virustatic Functions
———
Operation Limit for Cooling (°CDB) — — — Operation Limit for Heating (°CWB) — — — Photocatalytic Deodorizing Filter — — —
PAM Control — — —
Air Purifying Filter with Photocatalytic
Deodorizing Function
——#
Compressor
Oval Scroll Compressor — — —
Titanium Apatite Photocatalytic
Air-Purifying Filter
##
Swing Compressor — — — Rotary Compressor — — — Long life Filter (Option) — — — Reluctance DC Motor — — — Mold Proof Air Filter ###
Comfortable Airflow
Power-Airflow Flap — — — Wipe-clean Flat Panel ### Power-Airflow Dual Flaps ### Washable Grille — — — Power-Airflow Diffuser — — — Filter Cleaning Indicator — — — Wide-Angle Louvers ### Mold Proof Operation — — — Vertical Auto-Swing (Up and Down) ### Heating Dry Operation — — — Horizontal Auto-Swing (Right and Left) — — — Good-Sleep Cooling Operation — — — 3-D Airflow — — —
Timer
24-Hour On/Off Timer ### Comfort Airflow Mode ## 72-Hour On/Off Timer — — — 3-Step Airflow (H/P Only) — — — Night Set Mode ###
Comfort Control
Auto Fan Speed ###
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) ### Indoor Unit Silent Operation ### Self-Diagnosis (Digital, LED) Display ### Night Quiet Mode (Automatic) — — — Wiring Error Check — — — Outdoor Unit Silent Operation
(Manual)
———
Anticorrosion Treatment of Outdoor
Heat Exchanger
———
Intelligent Eye ### Quick Warming Function — — —
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
###
Hot-Start Function ### Automatic Defrosting — — — Flexible Voltage Correspondence ###
Operation
Automatic Operation ### High Ceiling Application — — — Programme Dry Function ### Chargeless — — — Fan Only ### Either Side Drain (Right or Left) ###
Lifestyle Convenience
New Powerful Operation (Non­Inverter)
— — — Power Selection — — —
Inverter Powerful Operation
###
Remote Control
5-Rooms Centralized Controller
(Option)
###
Priority-Room Setting — — —
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
###
Cooling / Heating Mode Lock — — — Home Leave Operation — — #
Remote Control Adapter
(Normal Open Contact) (Option)
###
ECONO Mode ##— Indoor Unit On/Off Switch ###
DIII-NET Compatible (Adapter)
(Option)
###
Signal Reception Indicator ###
Remote Control
Wireless ### Temperature Display — — — Wired — — — Another Room Operation — — —
Note: # : Holding Functions
— : No Functions
List of Functions SiENBE18-621
4 List of Functions
Category Functions
FTXS50/60/71EV1B
FTXS71BAVMB
Category Functions
FTXS50/60/71EV1B
FTXS71BAVMB
Basic Function
Inverter (with Inverter Power Control) ##
Health & Clean
Air Purifying Filter with Bacteriostatic &
Virustatic Functions
—— Operation Limit for Cooling (°CDB) Photocatalytic Deodorizing Filter — Operation Limit for Heating (°CWB)
Air Purifying Filter with Photocatalytic Deodorizing Function
#
PAM Control
Titanium Apatite Photocatalytic Air-Purifying Filter
#
Compressor
Oval Scroll Compressor Long life Filter (Option) — Swing Compressor Mold Proof Air Filter ## Rotary Compressor Wipe-clean Flat Panel ## Reluctance DC Motor Washable Grille
Comfortable Airflow
Power-Airflow Flap Filter Cleaning Indicator — Power-Airflow Dual Flaps ## Mold Proof Operation — Power-Airflow Diffuser Heating Dry Operation — Wide-Angle Louvers ## Good-Sleep Cooling Operation — Vertical Auto-Swing (Up and Down) ##
Timer
24-Hour On/Off Timer ## Horizontal Auto-Swing (Right and Left) ## 72-Hour On/Off Timer 3-D Airflow ## Night Set Mode ## Comfort Airflow Mode
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) ## 3-Step Airflow (H/P Only) Self-Diagnosis (Digital, LED) Display ##
Comfort Control
Auto Fan Speed ## Wiring-Error Check — Indoor Unit Silent Operation ##
Anticorrosion Treatment of Outdoor
Heat Exchanger
——
Night Quiet Mode (Automatic)
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
##
Outdoor Unit Silent Operation (Manual)
Flexible Voltage Correspondence #
Intelligent Eye ## High Ceiling Application — Quick Warming Function Chargeless — Hot-Start Function ## Either Side Drain (Right or Left) ## Automatic Defrosting Power-Selection
Operation
Automatic Operation ##
Remote Control
5-Rooms Centralized Controller
(Option)
##
Programme Dry Function ##
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
##
Fan Only
##
Remote Control Adapter
(Normal Open Contact) (Option)
##
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
——
DIII-NET Compatible (Adapter)
(Option)
##
Inverter Powerful Operation ##
Remote Control
Wireless ## Priority-Room Setting Wired — Cooling / Heating Mode Lock — Home Leave Operation ## ECONO Mode — Indoor Unit On/Off Switch ## Signal Reception Indicator ## Temperature Display — Another Room Operation
Note: # : Holding Functions
— : No Functions
List of Functions 5
Category Functions
FDXS25/35CAVMB
FDXS50/60CVMB
FDXS25/35EAVMB
Category Functions
FDXS25/35CAVMB
FDXS50/60CVMB
FDXS25/35EAVMB
Basic Function
Inverter (with Inverter Power Control) ###
Health & Clean
Air Purifying Filter with Bacteriostatic &
Virustatic Functions
——— Operation Limit for Cooling (°CDB) — — — Photocatalytic Deodorizing Filter — — — Operation Limit for Heating (°CWB) — — —
Air Purifying Filter with Photocatalytic Deodorizing Function
———
PAM Control — — —
Titanium Apatite Photocatalytic Air-Purifying Filter
———
Compressor
Oval Scroll Compressor — — — Mold Proof Air Filter ### Swing Compressor — — — Wipe-clean Flat Panel — — — Rotary Compressor — — — Washable Grille — — — Reluctance DC Motor — — — Mold Proof Operation — — —
Comfortable Airflow
Power-Airflow Flap — — — Heating Dry Operation — — — Power-Airflow Dual Flaps — — — Good-Sleep Cooling Operation — — — Power-Airflow Diffuser — — —
Timer
24-Hour On/Off Timer ### Wide-Angle Louvers — — — Night Set Mode ### Vertical Auto-Swing (Up and Down) — — —
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) ### Horizontal Auto-Swing (Right and Left) — — — Self-Diagnosis (Digital, LED) Display ### 3-D Airflow — — — Wiring-Error Check — — —
3-Step Airflow (H/P Only) — — —
Anticorrosion Treatment of Outdoor
Heat Exchanger
———
Comfort Control
Auto Fan Speed ###
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
###
Indoor Unit Silent Operation ### Flexible Voltage Correspondence ### Night Quiet Mode (Automatic) — — — High Ceiling Application — — — Outdoor Unit Silent Operation
(Manual)
— — — Chargeless — — —
Intelligent Eye — — — Either Side Drain (Right or Left) — — — Quick Warming Function — — — Power-Selection — — —
Hot-Start Function ###
Remote Control
5-Rooms Centralized Controller
(Option)
###
Automatic Defrosting — — —
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
###
Operation
Automatic Operation ###
Remote Control Adapter
(Normal Open Contact) (Option)
###
Programme Dry Function ### DIII-NET Compatible (Adapter) (Option) ### Fan Only ###
Remote Control
Wireless ###
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
——— Wired ———
Inverter Powerful Operation ### Priority-Room Setting — — — Cooling / Heating Mode Lock — — — Home Leave Operation ### ECONO Mode — — — Indoor Unit On/Off Switch ### Signal Reception Indicator ### Temperature Display — — — Another Room Operation — — —
Note: # : Holding Functions
— : No Functions
List of Functions SiENBE18-621
6 List of Functions
Category Functions
FLXS25-60BAVMB
FVXS25-50BAVMB
Category Functions
FLXS25-60BAVMB
FVXS25-50BAVMB
Basic Function
Inverter (with Inverter Power Control) ##
Health & Clean
Air Purifying Filter with Bacteriostatic & Virustatic Functions
##
Operation Limit for Cooling (°CDB) Photocatalytic Deodorizing Filter ## Operation Limit for Heating (°CWB)
Air Purifying Filter with Photocatalytic Deodorizing Function
——
PAM Control
Titanium Apatite Photocatalytic Air-Purifying Filter
——
Compressor
Oval Scroll Compressor Long life Filter (Option) — Swing Compressor Mold Proof Air Filter ## Rotary Compressor Wipe-clean Flat Panel — Reluctance DC Motor Washable Grille #
Comfortable Airflow
Power-Airflow Flap Filter Cleaning Indicator — Power-Airflow Dual Flaps Mold Proof Operation — Power-Airflow Diffuser Heating Dry Operation — Wide-Angle Louvers # Good-Sleep Cooling Operation — Vertical Auto-Swing (Up and Down) ##
Timer
24-Hour On/Off Timer ## Horizontal Auto-Swing (Right and Left) — 72-Hour On/Off Timer — 3-D Airflow Night Set Mode ## Comfort Airflow Mode
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) ## 3-Step Airflow (H/P Only) # Self-Diagnosis (Digital, LED) Display ##
Comfort Control
Auto Fan Speed ## Wiring-Error Check — Indoor Unit Silent Operation ##
Anticorrosion Treatment of Outdoor
Heat Exchanger
——
Night Quiet Mode (Automatic)
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
##
Outdoor Unit Silent Operation (Manual)
Flexible Voltage Correspondence ##
Intelligent Eye High Ceiling Application — Quick Warming Function Chargeless — Hot-Start Function ## Either Side Drain (Right or Left) — Automatic Defrosting Power-Selection
Operation
Automatic Operation ##
Remote Control
5-Rooms Centralized Controller
(Option)
##
Programme Dry Function ##
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
##
Fan Only ##
Remote Control Adapter
(Normal Open Contact) (Option)
##
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
——
DIII-NET Compatible (Adapter)
(Option)
##
Inverter Powerful Operation ##
Remote Control
Wireless ## Priority-Room Setting Wired — Cooling / Heating Mode Lock — Home Leave Operation ## ECONO Mode — Indoor Unit On/Off Switch ## Signal Reception Indicator ## Temperature Display — Another Room Operation
Note: # : Holding Functions
— : No Functions
List of Functions 7
Category Functions
FFQ25-60B8V1B
FHQ35-60BVV1B
Category Functions
FFQ25-60B8V1B
FHQ35-60BVV1B
Basic Function
Inverter (with Inverter Power Control)
##
Health & Clean
Air Purifying Filter with Bacteriostatic & Virustatic Functions
—— Operation Limit for Cooling (°CDB) Photocatalytic Deodorizing Filter — Operation Limit for Heating (°CWB)
Air Purifying Filter with Photocatalytic Deodorizing Function
——
PAM Control
Titanium Apatite Photocatalytic Deodorizing Function
——
Compressor
Oval Scroll Compressor Longlife Filter (Option) ## Swing Compressor Mold Proof Air Filter ## Rotary Compressor Wipe-clean Flat Panel — Reluctance DC Motor Washable Grille ##
Comfortable Airflow
Power-Airflow Flap Filter Cleaning Indicator ## Power-Airflow Dual Flaps Mold Proof Operation — Power-Airflow Diffuser Heating Dry Operation — Wide-Angle Louvers Good-Sleep Cooling Operation — Vertical Auto-Swing (Up and Down) ##
Timer
24-Hour On/Off Timer — Horizontal Auto-Swing (Right and Left) 72-Hour On/Off Timer ## 3-D Airflow Night Set Mode — Comfort Airflow Mode
Worry Free “Reliability & Durability”
Auto-Restart (after Power Failure) ## 3-Step Airflow (H/P Only) Self-Diagnosis (Digital, LED) Display ##
Comfort Control
Auto Fan Speed Wiring-Error Check — Indoor Unit Silent Operation
Anticorrosion Treatment of Outdoor
Heat Exchanger
——
Night Quiet Mode (Automatic)
Flexibility
Multi-Split / Split Type Compatible
Indoor Unit
##
Outdoor Unit Silent Operation (Manual)
Flexible Voltage Correspondence
Intelligent Eye High Ceiling Application # Quick Warming Function Chargeless — Hot-Start Function ## Either Side Drain (Right or Left) — Automatic Defrosting Power-Selection
Operation
Automatic Operation ##
Remote Control
5-Rooms Centralized Controller
(Option)
——
Programme Dry Function ##
Remote Control Adapter
(Normal Open-Pulse Contact) (Option)
——
Fan Only ##
Remote Control Adapter
(Normal Open Contact) (Option)
——
Lifestyle Convenience
New Powerful Operation (Non-Inverter)
——
Dlll-NET Compatible (Adapter)
(Option)
##
Inverter Powerful Operation
Remote Control
Wireless
##
Priority-Room Setting Wired ## Cooling / Heating Mode Lock — Home Leave Operation — ECONO Mode — Indoor Unit On/Off Switch — Signal Reception Indicator — Temperature Display — Another Room Operation
Note: # : Holding Functions
— : No Functions
List of Functions SiENBE18-621
8 List of Functions
Specifications 9
Part 2
Specifications
1. Specifications........................................................................................10
1.1 Outdoor Units.........................................................................................10
1.2 BP Unit...................................................................................................11
1.3 Indoor Units............................................................................................12
Specifications SiENBE18-621
10 Specifications
1. Specifications
1.1 Outdoor Units
50Hz 230V
Note:
1. H Refrigerant charge is required. (Chargeless piping length 0m) Formula for calculation charge : R (kg) R = Total length (m) of liquid pipe size at φ9.5×0.054 + Total length (m) of liquid piping size at φ6.4×0.022
2. The data are based on the conditions shown in the table below.
Model RMXS112E7V3B RMXS140E7V3B RMXS160E7V3B
4HP 5HP 6HP
Cooling Capacity
kW
(kcal/h)
11.2 (9,630) 14.0 (12,040) 15.5 (13,330)
Heating Capacity
kW
(kcal/h)
12.5 (10,750) 16.0 (13,760) 17.5 (15,050)
Total Indoor Unit Capacity kW 5.5~14.5 7.0~18.2 8.0~20.8 Power Consumption W — Running Current A — Casing Color Ivory White
Compressor
Type Hermetically Sealed Scroll Type Model JT100G-VDL Motor Output
(2.2kW/60rps)
kW 2.5 3.0 3.5
Refrigerant Oil
Model DAPHNE FVC68D Charge L 1.5
Refrigerant
Type R-410A Charge kg 4.0
Air Flow Rate (H)
Cooling
m³/min
(cfm)
106 (3,742)
Heating
m³/min
(cfm)
106 (3,742)
Fan
Type Propeller Motor Output W 70+70 Running Current A 0.4+0.4
Power Consumption W 88+88 Starting Current A 19.2 23.7 25.2 Dimensions (H×W×D) mm 1,345×900×320 Weight kg 127
Operation Sound
Cooling dBA 51 52 54
Heating dBA 53 54 55
Piping Connection
Liquid mm φ9.5 (Flare Connection)
Gas mm φ19.1 (Brazing Connection)
Drain mm φ18 Heat Insulation Both Liquid and Gas Pipes No. of Wiring Connection 3 For Power Supply (Including Earth Wiring), 2 For Interunit Wiring (Outdoor Unit-BP)
Total piping length
O.U. - BP m 55
BP - I.U. m 60 80 90
System Total m 115 135 145 Max. piping
length
BP - I.U. m 15
1st Branch - I.U. m 40
Max. level difference
O.U. - BP m 30
O.U. - I.U. m 30
BP - BP, I.U. - I.U. m 15 Necessity of Additional Charge H kg/m Necessary
Cooling Heating Piping Length
Indoor ; 27°CDB / 19°CWB Outdoor ; 35°CDB
Indoor ; 20°CDB Outdoor ; 7°CDB / 6°CWB
Main Piping : 5m Branch Piping : 3m Level difference:0m
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Outdoor Unit
Main Piping
BP Unit
Indoor Unit
Branch Piping
(Q0143)
Specifications 11
1.2 BP Unit
50Hz 230V
Note:
1. BP or Indoor Unit Max. Height - BP or Indoor Unit Min. Height Max. 15m. Set up BP and indoor unit within 15m height difference.
2. The piping connection must be cut so as to suit the piping sizes of the indoor unit which will be connected. The same sizes should be used for the piping on the outdoor unit.
3. ( )* : including auxiliary piping length
Model BPMKS967B2B BPMKS967B3B
Connectable Indoor Units 1~2 Units 1~3 Units Casing Color Paintingless Power Consumption W 10 10 Running Current A 0.05 0.05 Refrigerant Type R-410A Dimension (H×W×D) mm 180×294(650)*×350 Package Dimension (H×W×D) mm 257×738×427 Machine Weight kg 7.5 8 Gross Weight kg 11 12 Number of Wiring Connections 4 for Interunit Wiring
Piping Connection (Brazing)
Liquid mm Main : φ9.5×1 / Branch : φ6.4×2 Main : φ9.5×1 / Branch : φ6.4×3 Gas mm Main : φ19.1×1 / Branch : φ15.9×2 Main : φ19.1×1 / Branch : φ15.9×3
Drain mm Drain Processingless Heat Insulation Both Liquid and Gas Pipes Max. Piping Length m — Amount of Additional Charge g/m — Max. Height Difference m — Max. Combination kW 14.2 20.8 Min. Combination kW 2.0 2.0
Accessories
Installation Manual pc. 1
L Shape Reducer pc.
For Main
Liquid 1 (For I.D. φ6.4)
Gas 1 (For I.D. φ12.7) Gas 1 (For I.D. φ15.9, 19.1)
For Branch
Gas 2 (For I.D. φ12.7, 9.5) 3 (For I.D. φ12.7, 9.5)
Liquid 1 (For I.D. φ9.5) Hanger Metal pc. 4 Screws pc. 8 (M4×8) Heat Insulation (2pc. is 1 set) 3 Set 4 Set Binding Band pc. 2
Drawing No. C : 4D050058B
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiENBE18-621
12 Specifications
1.3 Indoor Units
Wall Mounted Type
50Hz 230V
Model
FTXS20D3VMW FTXS20D3VML
Cooling Heating Cooling Heating Rated Capacity 2.0kW Class 2.0kW Class Front Panel Color White Silver Line
Air Flow Rates
m³/min
(cfm)
H 8.7 (307) 9.4 (332) 8.7 (307) 9.4 (332)
M 6.7 (237) 7.6 (268) 6.7 (237) 7.6 (268)
L 4.7 (166) 5.8 (205) 4.7 (166) 5.8 (205)
SL 3.9 (138) 5.0 (177) 3.9 (138) 5.0 (177)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 40 40
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.16 0.16 0.16 0.16 Power Consumption (Rated) W 35 35 35 35 Power Factor % 95.1 95.1 95.1 95.1 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 283×800×195 283×800×195 Packaged Dimensions (H×W×D) mm 265×855×340 265×855×340 Weight kg 9 9 Gross Weight kg 12 12 Operation
Sound
H/L/SL dBA 38/25/22 38/28/25 38/25/22 38/28/25 Sound Power H dBA 56 56 56 56
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D051085 3D051086
Model
FTXS25D3VMW FTXS25D3VML
Cooling Heating Cooling Heating Rated Capacity 2.5kW Class 2.5kW Class Front Panel Color White Silver Line
Air Flow Rates
m³/min
(cfm)
H 8.7 (307) 9.4 (332) 8.7 (307) 9.4 (332)
M 6.7 (237) 7.6 (268) 6.7 (237) 7.6 (268)
L 4.7 (166) 5.8 (205) 4.7 (166) 5.8 (205)
SL 3.9 (138) 5.0 (177) 3.9 (138) 5.0 (177)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 40 40
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.16 0.16 0.16 0.16 Power Consumption (Rated) W 35 35 35 35 Power Factor % 95.1 95.1 95.1 95.1 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 283×800×195 283×800×195 Packaged Dimensions (H×W×D) mm 265×855×340 265×855×340 Weight kg 9 9 Gross Weight kg 12 12 Operation
Sound
H/L/SL dBA 38/25/22 38/28/25 38/25/22 38/28/25 Sound Power H dBA 56 56 56 56
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D051087 3D051088
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications 13
50Hz 230V
Model
FTXS35D3VMW FTXS35D3VML
Cooling Heating Cooling Heating Rated Capacity 3.5kW Class 3.5kW Class Front Panel Color White Silver Line
Air Flow Rates
m³/min
(cfm)
H 8.9 (314) 9.7 (342) 8.9 (314) 9.7 (342)
M 6.9 (244) 7.9 (279) 6.9 (244) 7.9 (279)
L 4.8 (169) 6.0 (212) 4.8 (169) 6.0 (212)
SL 4.0 (141) 5.2 (184) 4.0 (141) 5.2 (184)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 40 40
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.18 0.18 0.18 0.18 Power Consumption (Rated) W 40 40 40 40 Power Factor % 96.6 96.6 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 283×800×195 283×800×195 Packaged Dimensions (H×W×D) mm 265×855×340 265×855×340 Weight kg 9 9 Gross Weight kg 12 12 Operation
Sound
H/L/SL dBA 39/26/23 39/29/26 39/26/23 39/29/26 Sound Power H dBA 57 57 57 57
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D051089 3D051090
Model
FTXS50D2V1W FTXS50D2V1L
Cooling Heating Cooling Heating Rated Capacity 5.0kW Class 5.0kW Class Front Panel Color White White
Air Flow Rates
m³/min
(cfm)
H 11.4 (402) 11.4 (402) 11.4 (402) 11.4 (402)
M 9.3 (328) 9.4 (332) 9.3 (328) 9.4 (332)
L 7.1 (251) 7.4 (261) 7.1 (251) 7.4 (261)
SL 6.2 (219) 6.3 (222) 6.2 (219) 6.3 (222)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 40 40
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.21 0.21 0.21 0.21 Power Consumption (Rated) W 48 48 48 48 Power Factor % 99.4 99.4 99.4 99.4 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 283×800×195 283×800×195 Packaged Dimensions (H×W×D) mm 265×855×340 265×855×340 Weight kg 9 9 Gross Weight kg 12 12 Operation
Sound
H/M/L/SL dBA 46/41/35/32 46/40/34/31 46/41/35/32 46/40/34/31 Sound Power H dBA 62 62 62 62
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ12.7 φ12.7
Drain mm
φ18.0 φ18.0
Drawing No. 3D051814 3D051815
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiENBE18-621
14 Specifications
50Hz 230V
Model
FTXS20CAVMB FTXS25CAVMB
Cooling Heating Cooling Heating Rated Capacity 2.0kW Class 2.5kW Class Front Panel Color White White
Air Flow Rates
m³/min
(cfm)
H 7.7 (272) 7.8 (275) 7.7 (272) 7.8 (275)
M 5.9 (208) 6.5 (230) 5.9 (208) 6.5 (230)
L 4.2 (148) 5.3 (187) 4.2 (148) 5.3 (187)
SL 3.6 (127) 4.6 (162) 3.6 (127) 4.6 (162)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 18 18
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.18 0.18 0.18 0.18 Power Consumption (Rated) W 40 40 40 40 Power Factor % 96.6 96.6 96.6 96.6 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 273×784×195 273×784×195 Packaged Dimensions (H×W×D) mm 258×834×325 258×834×325 Weight kg 7.5 7.5 Gross Weight kg 11 11 Operation
Sound
H/M/L/SL dBA 38/32/25/22 38/33/28/25 38/32/25/22 38/33/28/25 Sound Power H dBA 56 56 56 56
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D050941 3D050943
Model
FTXS35CAVMB FTXS50EV1B
Cooling Heating Cooling Heating Rated Capacity 3.5kW Class 5.0kW Class Front Panel Color White White
Air Flow Rates
m³/min
(cfm)
H 7.7 (272) 8.1 (286) 14.7 (519) 16.1 (569)
M 6.0 (212) 6.7 (237) 12.4 (438) 13.9 (491)
L 4.4 (155) 5.3 (187) 10.3 (364) 11.5 (406)
SL 3.8 (134) 4.6 (162) 9.5 (335) 10.2 (360)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 18 43
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable- Mildew Proof Running Current (Rated) A 0.18 0.18 0.15 0.16 Power Consumption (Rated) W 40 40 34 36 Power Factor % 96.6 96.6 98.6 97.8 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 273×784×195 290×1,050×238 Packaged Dimensions (H×W×D) mm 258×834×325 337×1,147×366 Weight kg 7.5 12 Gross Weight kg 11 17 Operation
Sound
H/M/L/SL dBA 39/33/26/23 39/34/29/26 43/39/34/31 42/38/33/30 Sound Power H dBA 57 57 59 58
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ12.7
Drain mm
φ18.0 φ18.0
Drawing No. 3D050945 3D051645
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications 15
50Hz 230V
Model
FTXS60EV1B FTXS71EV1B
Cooling Heating Cooling Heating Rated Capacity 6.0kW Class 7.1kW Class Front Panel Color White White
Air Flow Rates
m³/min
(cfm)
H 16.2 (572) 17.4 (614) 17.4 (614) 19.7 (695)
M 13.6 (480) 15.1 (533) 14.6 (515) 16.6 (586)
L 11.4 (402) 12.7 (448) 11.6 (409) 13.5 (477)
SL 10.2 (360) 11.4 (402) 10.6 (374) 12.1 (427)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 43 43
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.18 0.20 0.20 0.22 Power Consumption (Rated) W 40 45 45 50 Power Factor % 96.6 97.8 97.8 98.8 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 290×1,050×238 290×1,050×238 Packaged Dimensions (H×W×D) mm 337×1,147×366 337×1,147×366 Weight kg 12 12 Gross Weight kg 17 17 Operation
Sound
H/M/L/SL dBA 45/41/36/33 44/40/35/32 46/42/37/34 46/42/37/34 Sound Power H dBA 61 60 63 63
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ12.7 φ15.9
Drain mm
φ18.0 φ18.0
Drawing No. 3D051646 3D052803
Model
FTXS71BAVMB
Cooling Heating Rated Capacity 7.1kW Class Front Panel Color White
Air Flow Rates
m³/min
(cfm)
H 16.7 (590) 18.5 (653)
M 14.2 (501) 15.1 (533)
L 11.6 (409) 13.5 (477)
SL 10.6 (374) 12.1 (427)
Fan
Type Cross Flow Fan Motor Output W 43
Speed Steps 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Running Current (Rated) A 0.20 0.22 Power Consumption (Rated) W 45 50 Power Factor % 96.4 97.6 Temperature Control Microcomputer Control Dimensions (H×W×D) mm 290×1,050×238 Packaged Dimensions (H×W×D) mm 337×1,147×366 Weight kg 12 Gross Weight kg 17 Operation
Sound
H/M/L/SL dBA 46/42/37/34 46/42/37/34 Sound Power H dBA 63 63
Heat Insulation Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
Gas mm
φ15.9
Drain mm
φ18.0
Drawing No. 3D050880
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiENBE18-621
16 Specifications
Duct Connected Type
50Hz 230V
Note: The operating sound is based on the rear side suction inlet and the external static pressure 40 Pa.
Operating sound for under side suction inlet : [operating sound for rear side suction inlet] +5 dB. However, when installation to which the external static pressure becomes low is carried out, 5 dB or more may go up.
Model
FDXS25CAVMB FDXS35CAVMB
Cooling Heating Cooling Heating Rated Capacity 2.5kW Class 3.5kW Class Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 9.5 (335) 9.5 (335) 10.0 (353) 10.0 (353)
M 8.8 (311) 8.8 (311) 9.3 (328) 9.3 (328)
L 8.0 (282) 8.0 (282) 8.5 (300) 8.5 (300)
SL 6.7 (237) 6.7 (237) 7.0 (247) 7.0 (247)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 62 62
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.47 0.47 0.47 0.47 Power Consumption (Rated) W 100 100 100 100 Power Factor % 92.5 92.5 92.5 92.5 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 200×900×620 200×900×620 Packaged Dimensions (H×W×D) mm 266×1,106×751 266×1,106×751 Weight kg 25 25 Gross Weight kg 31 31 Operation
Sound
H/M/L/SL dBA 35/33/31/29 35/33/31/29 35/33/31/29 35/33/31/29 External Static Pressure Pa 40 40
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm VP20 (O.D.
φ 26 / I.D. φ 20) VP20 (O.D. φ 26 / I.D. φ 20)
Drawing No. 3D048945C 3D048946C
Model
FDXS50CVMB FDXS60CVMB
Cooling Heating Cooling Heating Rated Capacity 5.0kW Class 6.0kW Class Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 12.0 (424) 12.0 (424) 16.0 (565) 16.0 (565)
M 11.0 (388) 11.0 (388) 14.8 (523) 14.8 (523)
L 10.0 (353) 10.0 (353) 13.5 (477) 13.5 (477)
SL 8.4 (297) 8.4 (297) 11.2 (395) 11.2 (395)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 130 130
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.64 0.64 0.74 0.74 Power Consumption (Rated) W 140 140 160 160 Power Factor % 95.1 95.1 94.0 94.0 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 200×900×620 200×1,100×620 Packaged Dimensions (H×W×D) mm 266×1,106×751 266×1,306×751 Weight kg 27 30 Gross Weight kg 34 37 Operation
Sound
H/M/L/SL dBA 37/35/33/31 37/35/33/31 38/36/34/32 38/36/34/32 External Static Pressure Pa 40 40
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ12.7 φ12.7
Drain mm VP20 (O.D.
φ 26 / I.D. φ 20) VP20 (O.D. φ 26 / I.D. φ 20)
Drawing No. 3D052132 3D0452133
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications 17
50Hz 230V
Note: The operating sound is based on the rear side suction inlet and the external static pressure 30 Pa.
Operating sound for under side suction inlet : [operating sound for rear side suction inlet] +6 dB. However, when installation to which the external static pressure becomes low is carried out, 6 dB or more may go up.
Model
FDXS25EAVMB FDXS35EAVMB
Cooling Heating Cooling Heating Rated Capacity 2.5kW Class 3.5kW Class Front Panel Color
——
Air Flow Rates
m³/min
(cfm)
H 8.7 (307) 8.7 (307) 8.7 (307) 8.7 (307)
M 8.0 (282) 8.0 (282) 8.0 (282) 8.0 (282)
L 7.3 (258) 7.3 (258) 7.3 (258) 7.3 (258)
SL 6.2 (219) 6.2 (219) 6.2 (219) 6.2 (219)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 62 62
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.48 0.48 0.48 0.48 Power Consumption (Rated) W 71 71 71 71 Power Factor % 64.3 64.3 64.3 64.3 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 200×700×620 200×700×620 Packaged Dimensions (H×W×D) mm 274×906×751 274×906×751 Weight kg 21 21 Gross Weight kg 29 29 Operation
Sound
H/M/L/SL dBA 35/33/31/29 35/33/31/29 35/33/31/29 35/33/31/29 External Static Pressure Pa 30 30
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm VP20 (O.D.
φ 26 / I.D. φ 20) VP20 (O.D. φ 26 / I.D. φ 20)
Drawing No. 3D051881A 3D051883A
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications SiENBE18-621
18 Specifications
Floor / Ceiling Suspended Dual Type
50Hz 230V
Model
FLXS25BAVMB FLXS35BAVMB
Cooling Heating Cooling Heating Rated Capacity 2.5kW Class 3.5kW Class Front Panel Color Almond White Almond White
Air Flow Rates
m³/min
(cfm)
H 7.6 (268) 9.2 (325) 8.6 (304) 9.8 (346)
M 6.8 (240) 8.3 (293) 7.6 (268) 8.9 (314)
L 6.0 (212) 7.4 (261) 6.6 (233) 8.0 (282)
SL 5.2 (184) 6.6 (233) 5.6 (198) 7.2 (254)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 34 34
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.32 0.34 0.36 0.36 Power Consumption (Rated) W 70 74 78 78 Power Factor % 95.1 94.6 94.2 94.2 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 490×1,050×200 490×1,050×200 Packaged Dimensions (H×W×D) mm 566×1,100×280 566×1,100×280 Weight kg 16 16 Gross Weight kg 22 22 Operation
Sound
H/M/L/SL dBA 37/34/31/28 37/34/31/29 38/35/32/29 39/36/33/30 Sound Power H dBA 53 54
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D050866 3D050868
Model
FLXS50BAVMB FLXS60BAVMB
Cooling Heating Cooling Heating Rated Capacity 5.0kW Class 6.0kW Class Front Panel Color Almond White Almond White
Air Flow Rates
m³/min
(cfm)
H 11.4 (402) 12.1 (427) 12.0 (424) 12.8 (452)
M 10.0 (353) 9.8 (346) 10.7 (378) 10.6 (374)
L 8.5 (300) 7.5 (265) 9.3 (328) 8.4 (297)
SL 7.5 (265) 6.8 (240) 8.3 (293) 7.5 (265)
Fan
Type Sirocco Fan Sirocco Fan Motor Output W 34 34
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Downward Right, Left, Horizontal, Downward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.45 0.45 0.47 0.45 Power Consumption (Rated) W 96 96 98 96 Power Factor % 92.8 92.8 90.7 92.8 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 490×1,050×200 490×1,050×200 Packaged Dimensions (H×W×D) mm 280×1,100×566 280×1,100×566 Weight kg 17 17 Gross Weight kg 24 24 Operation
Sound
H/M/L/SL dBA 47/43/39/36 46/41/35/33 48/45/41/39 47/42/37/34 Sound Power H dBA 63 32 64 63
Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ12.7 φ12.7
Drain mm
φ18.0 φ18.0
Drawing No. 3D050897 3D050882
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3
Specifications 19
Floor Standing Type
50Hz 230V
Model
FVXS25BAVMB FVXS35BAVMB
Cooling Heating Cooling Heating Rated Capacity 2.5kW Class 3.5kW Class Front Panel Color Almond White Almond White Air Flow Rates
m³/min
(cfm)
H 8.1 (286) 9.2 (325) 8.3 (293) 9.2 (325)
M 6.2 (219) 7.0 (247) 6.3 (222) 7.1 (251)
L 4.3 (152) 4.8 (169) 4.3 (152) 5.0 (177)
SL 3.4 (120) 3.5 (124) 3.4 (120) 3.6 (127)
Fan
Type Cross Flow Fan Cross Flow Fan Motor Output W 14+14 14+14
Speed Steps 5 Steps, Silent, Auto 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Upward Right, Left, Horizontal, Upward Air Filter Removable-Washable-Mildew Proof Removable-Washable-Mildew Proof Running Current (Rated) A 0.14 0.14 0.14 0.14 Power Consumption (Rated) W 32 32 32 32 Power Factor % 99.4 99.4 99.4 99.4 Temperature Control Microcomputer Control Microcomputer Control Dimensions (H×W×D) mm 600×650×195 600×650×195 Packaged Dimensions (H×W×D) mm 714×770×294 714×770×294 Weight kg 13 13 Gross Weight kg 19 19 Operation
Sound
H/M/L/SL
dBA
38/32/26/23 38/32/26/23 39/33/27/24 39/34/29/26
Sound Power H dBA 54 55 — Heat Insulation Both Liquid and Gas Pipes Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
φ
6.4
Gas mm
φ 9.5 φ 9.5
Drain mm
φ18.0 φ18.0
Drawing No. 3D050874 3D050876
Model
FVXS50BAVMB
Cooling Heating Rated Capacity 5.0kW Class Front Panel Color Almond White
Air Flow Rates
m³/min
(cfm)
H 10.8 (381) 13.2 (466)
M 9.2 (325) 11.3 (399)
L 7.7 (272) 9.4 (332)
SL 6.7 (237) 8.3 (293)
Fan
Type Cross Flow Fan Motor Output W 14+14
Speed Steps 5 Steps, Silent, Auto Air Direction Control Right, Left, Horizontal, Upward Air Filter Removable-Washable-Mildew Proof Running Current (Rated) A 0.26 0.32 Power Consumption (Rated) W 55 70 Power Factor % 92.0 95.1 Temperature Control Microcomputer Control Dimensions (H×W×D) mm 600×650×195 Packaged Dimensions (H×W×D) mm 714×770×294 Weight kg 13 Gross Weight kg 19 Operation
Sound
H/M/L/SL
dBA
44/40/36/33 45/40/36/33
Sound Power H dBA 56 57 Heat Insulation Both Liquid and Gas Pipes
Piping Connection
Liquid mm
φ
6.4
Gas mm
φ12.7
Drain mm
φ20.0
Drawing No. 3D050895
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/min×35.3