Daikin FHQ35CAVEB, FHQ100CAVEB, FHQ50CAVEB, FHQ125CAVEB, FHQ60CAVEB Installation manuals

...
INSTALLATION MANUAL
SPLIT SYSTEM Air Conditioners
English
Deutsch
MODELS
(Ceiling Suspended type)
FHQ35CAVEB FHQ100CAVEB FHQ50CAVEB FHQ125CAVEB FHQ60CAVEB FHQ140CAVEB FHQ71CAVEB
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
VEUILLEZ LIRE ATTENTIVEMENT CES INSTRUCTIONS AVANT L'INSTALLATION. CONSERVEZ CE MANUEL EN LIEU SÛR POUR POUVOIR VOUS Y REPORTER ULTÉRIEUREMENT.
LEA DETENIDAMENTE ESTAS INSTRUCCIONES ANTES DE LA INSTALACIÓN CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS.
PRIMA DELL'INSTALLAZIONE, LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI. CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO.
ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ ΜΕΛΛΟΝΤΙΚΗ ΑΝΑΦΟΡΑ.
LEES DEZE INSTRUCTIES ZOGVULDIG DOOR VOORDAT MET DE INSTALLATIE WORDT BEGONNEN. BEWAAR DEZE HANDLEIDING VOOR TOEKOMSTIG GEBRUIK OP EEN GESCHIKTE PLAATS ONDER HANDBEREIK.
Français
Español
Italiano
ЕллзнйкЬ
Nederlands
Portugues
Русский
LEIA ATENTAMENTE ESTAS INSTRUÇÕES ANTES DA INSTALAÇÃO. MANTENHA ESTE MANUAL NUM LOCAL DE FÁCIL ACESSO PARA CONSULTA.
ПЕРЕД УСТАНОВКОЙ ВНИМАТЕЛЬНО ПРОЧИТАЙТЕ ДАННЫЕ ИНСТРУКЦИИ. ХРАНИТЕ ДАННОЕ РУКОВОДСТВО В ЛЕГКО ДОСТУПНОМ МЕСТЕ ДЛЯ ЕГО ПОСЛЕДУЮЩЕГО ИСПОЛЬЗОВАНИЯ.
MONTAJDAN ÖNCE BU YÖNERGELERÝ DÝKKATLÝCE OKUYUN. DAHA SONRA BAKMAK ÜZERE BU KILAVUZU SAKLAYIN.
FHQ35CAVEB FHQ50CAVEB FHQ60CAVEB FHQ71CAVEB
FHQ100CAVEB FHQ125CAVEB FHQ140CAVEB
SPLIT SYSTEM Air Conditioners Installation manual
CONTENTS
1. SAFETY PRECAUTIONS ....................................................................................1
2. BEFORE INSTALLATION ....................................................................................3
3. SELECTION OF INSTALLATION LOCATION .....................................................5
4. PREPARATION BEFORE INSTALLATION .........................................................6
5. INSTALLATION OF THE INDOOR UNIT.............................................................8
6. REFRIGERANT PIPING WORK ........................................................................10
7. DRAIN PIPING WORK.......................................................................................15
8. ELECTRIC WIRING WORK ...............................................................................18
9. HOW TO CONNECT WIRINGS AND WIRING EXAMPLE ................................ 18
10. MOUNTING SUCTION GRILLE · DECORATION SIDE PANEL........................25
11. FIELD SETTING.................................................................................................25
12. TEST OPERATION ............................................................................................28
13. WIRING DIAGRAM ............................................................................................33
The original instructions are written in English. All other languages are translations of the original instructions.

1. SAFETY PRECAUTIONS

Be sure to follow this “SAFETY PRECAUTIONS”. This product comes under the term “appliances not accessible to the general public”.
This manual classifies the precautions into WARNINGS and CAUTIONS. Be sure to follow all the precautions below: They are all important for ensuring safety.
WARNING .......... Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTION ........... Indicates a potentially hazardous situation which, if not avoided, may result in
minor or moderate injury. It may also be used to alert against unsafe practices.
After the installation is completed, test the air conditioner and check if the air conditioner operates properly. Give the user adequate instructions concerning the use and cleaning of the indoor unit according to the Operation Manual. Ask the user to keep this manual and the Operation Manual together in a handy place for future reference.
WARNING
Ask your local dealer or qualified personnel to carry out installation work.
Improper installation may result in water leakage, electric shocks or a fire.
Perform installation work in accordance with this installation manual. Improper installation may result in water leakage, electric shocks or a fire.
Consult your dealer regarding what to do in case of refrigerant leakage. When the air conditioner is installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen deficiency.
1 English
Be sure to use only the specified parts and accessories for installation work. Failure to use the specified parts may result in the air conditioner falling down, water leakage, electric shocks, a fire, etc.
Install the air conditioner on a foundation that can withstand its mass. Insufficient strength may result in the air conditioner falling down and causing injury. In addition, it may lead to vibration of indoor units and cause unpleasant chattering noise.
Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes. Improper installation may result in an accident such as air conditioner falling.
Make certain that all electrical work is carried out by qualified personnel according to the applicable legis­lation (note 1) and this installation manual, using a separate circuit. In addition, even if the wiring is short, make sure to use a wiring that has sufficient length and never connect additional wiring to make the length sufficient. Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or a fire. (note 1) applicable legislation means “All international, national and local directives, laws, regulations and/
or codes which are relevant and applicable for a certain product or domain”.
Earth the air conditioner. Do not connect the earth wiring to gas or water piping, lightning conductor or telephone earth wiring. Incomplete earthing may cause electric shocks or a fire.
Be sure to install an earth leakage breaker. Failure to do so may cause electric shocks and a fire.
Disconnect the power supply before touching the electric components. If you touch the live part, you may get an electric shocks.
Make sure that all wiring is secure, using the specified wirings and ensuring that external forces do not act on the terminal connections or wirings. Incomplete connection or fixing may cause an overheat or a fire.
When wiring between the indoor and outdoor units, and wiring the power supply, form the wirings orderly so that the control box lid can be securely fastened. If the control box lid is not in place, overheat of the terminals, electric shocks or a fire may be caused.
If refrigerant gas leaks during installation work, ventilate the area immediately. Toxic gas may be produced if refrigerant gas comes into contact with a fire.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas. Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of a fire, such as a fan heater, stove or cooker. Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
CAUTION
Install drain piping according to this installation manual to ensure good drainage, and insulate the piping to
prevent condensation. Improper drain piping may cause water leakage, make the furniture get wet.
Install the air conditioner, power supply wiring, remote controller wiring and transmission wiring at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Install the indoor unit as far as possible from fluorescent lamps. If a wireless remote controller kit is installed, the transmission distance may be shorter in a room where an electronic lighting type (inverter or rapid start type) fluorescent lamp is installed.
Do not install the air conditioner in places such as the following:
1. Where there is mist of oil, oil spray or vapour for example a kitchen.
Resin parts may deteriorate, and cause them to fall out or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is produced.
Corrosion of copper pipings or brazed parts may cause the refrigerant to leak.
3. Where there is machinery which emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
4. Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where
volatile flammables, such as thinner or gasoline, are handled. If the gas should leak and remained around the air conditioner, it may cause ignition.
The air conditioner is not intended for use in a potentionally explosive atomosphere.
English 2

2. BEFORE INSTALLATION

When unpacking and moving the indoor unit after unpacked, do not apply force to the piping (refrig­erant and drain) and resin parts.
Make sure to check in advance that the refrigerant to be used for installation work is R410A.
(The air conditioner will not properly operate if a wrong refrigerant is used.)
For installation of the outdoor unit, refer to the installation manual attached to the outdoor unit.
Do not throw away the accessories until the installation work is completed.
After the indoor unit is carried into the room, to avoid the indoor unit from getting damaged, take measures
to protect the indoor unit with packing materials. (1) Determine the route to carry the unit into the room. (2) Do not unpack the unit until it is carried to the installation location.
Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the indoor units.
Have the customer actually operate the air conditioner while looking at the manual. Instruct the customer how to operate the air conditioner (particularly cleaning of the air filters, operation pro­cedures, and temperature adjustment).
For selection of installation location, use the installation pattern paper (used in common with the packing case.) as reference.
Do not use the air conditioner where in the salty atmosphere such as coastal areas, vehicles, vessels or the voltage fluctuation is frequent such as factories.
Take off static electricity from the body when carrying out wiring and the control box lid is removed. The electric parts may be damaged.
2-1 ACCESSORIES
Check if the following accessories are attached to the indoor unit.
Name (1) Drain hose (2) Metal clamp (3) Washer for hanger (4) Clamp
Quantity 1 pc. 1 pc. 8 pcs. 7 pcs.
Shape
Name
Quantity 1 sheet 1 each 1 each 1 pc.
Shape
Name (11) Wiring fixture (12) Screw for wiring fixture
Quantity 2 pcs. 2 pcs.
Shape
(5) Installation pattern
paper
Joint insulating
material
(6) For gas piping
(7) For liquid piping
Sealing material (10) Resin bushing
(8) Large
(9) Small
(Miscellaneous)
• Operation manual
• Installation manual
• Declaration of for­mity
M4 × 12
3 English
2-2 OPTIONAL ACCESSORIES
For this indoor unit, the remote controller is separately required.
There are 2 kinds of remote controller; wired type and wireless type.
Install the remote controller to the place where the customer has given consent. Refer to the catalog for the applicable model. (Refer to the installation manual attached to the remote controller for how to install.)
CARRY OUT THE WORK GIVING CAUTION TO THE FOLLOWING ITEMS AND AFTER THE WORK IS COMPLETED CHECK THESE AGAIN.
1. Items to be checked after the installation work is completed
Items to be checked In case of defective
Are the indoor and outdoor units rigidly fixed?
Are the installation work of the outdoor and indoor units complete?
Have you carried out a leakage test with the test pressure specified in the outdoor unit installation manual?
Is the insulation of refrigerant piping and drain piping completely carried out?
Does the drain flow out smoothly? Water leakage Is the power supply voltage identical to that
stated in the manufacturer’s label on the air conditioner?
Are you sure that there is no wrong wiring or piping or no loose wiring?
Is earthing completed? Danger in case of leakage Are the sizes of electric wiring according to
the specification? Is any of air outlets or inlets of the indoor
and outdoor units blocked with obstacles? (It may lead to capacity drop due to fan speed drop or malfunction of equipment.)
Have you recorded the refrigerant piping length and the refrigerant charge added?
Drop · vibration · noise
Does not operate · burnout
Does not cool / Does not heat
Water leakage
Does not operate · burnout
Does not operate · burnout
Does not operate · burnout
Does not cool / Does not heat
Refrigerant charge amount is not clear
Check
column
*Make sure to recheck the items of “SAFETY PRECAUTIONS”
2. Items to be checked at delivery
Items to be checked
Have you carried out field setting? (if necessary) Are the control box lid, the air filter and the suction grille attached? Does the cool air discharge during the cooling operation and the warm air discharge during
heating operation? Have you explained how to operate the air conditioner showing the operation manual to the
customer? Have you explained the description of cooling, heating, program dry and automatic (cooling/
heating) given in the operation manual to the customer? If you set the fan speed at thermostat OFF, did you explain the set fan speed to the customer? Have you handed the operation manual and the installation manual to the customer?
English 4
Check
column
Points of the operation explanation
In addition to the general usage, since the items in the operation manual with the WARNING and
CAUTION marks are likely to result in human bodily injuries and property damages, it is neces­sary not only to explain these items to the customer but also to have the customer read them. It is also necessary to explain the items of “NOT MALFUNCTION OF THE AIR CONDITIONER” to the customer and have the customer read them carefully.

3. SELECTION OF INSTALLATION LOCATION

When unpacking and moving the indoor unit after unpacked, do not apply force to the piping (refrig­erant and drain) and resin parts. (1) Select the installation location that meets the following conditions and get approval of the cus-
tomer.
Where the cool and warm air spreads evenly in the room.
Where there is no obstacles in the air passage.
Where drainage can be ensured.
Where the ceiling lower surface is not inclined.
Where there is sufficient strength to withstand the mass of the indoor unit (if the strength is insufficient,
the indoor unit may vibrate and get in contact with the ceiling and generate unpleasant chattering noise).
Where a space sufficient for installation and service can be ensured. (Refer to Fig. 1 and Fig. 2)
Where the piping length between the indoor and the outdoor units is ensured within the allowable length.
(Refer to the installation manual attached to the outdoor unit.)
Where there is no risk of flammable gas leak.
[ Required installation space (mm) ]
*30 or more *30 or more
300 or more
Discharge
Fig. 1
Obstacles
Fig. 2
NOTE
If there is extra space required for * part, servicing can be conducted more easily if 200mm or more is secured.
CAUTION
Install the indoor and outdoor units, power supply wiring, remote controller wiring and transmission wiring
at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Install the indoor unit as far as possible from fluorescent lamps. If a wireless remote controller kit is installed, the transmission distance may be shorter in a room where an electronic lighting type (inverter or rapid start type) fluorescent lamp is installed.
Suction
Floor level
2500 or more from floor level
For high installation
(2) Use hanging bolts for installation. Investigate if the installation place can withstand the mass of the
indoor unit and, if necessary, hang the indoor unit with bolts after it is reinforced by beams etc. (Refer to the installation pattern paper (5) for the mounting pitch.).
(3) Ceiling height
This indoor unit can be installed up to 4.3m (for 35-71 model, 3.5m) of the ceiling.
5 English

4. PREPARATION BEFORE INSTALLATION

(1) For the locations of indoor unit hanging bolts, piping outlet holes, drain piping outlet hole, and
electric wiring inlet hole. (Refer to Fig. 3)
GH
Left back drain piping outlet hole
210
260
Hanging bolt pitch
690 Unit dimension
200
J
View from the front
A Unit dimension
B Hanging bolt pitch
C
D
E
View from the ceiling
F
Discharge
5
175
Wall hole for back side piping outlet
(φ100 hole)
Back side wiring outlet location
87
30
Top panel drain piping connection position
Top panel gas side piping connection position
Top panel liquid side piping connection positions
163
189
Fig. 3
Unit : mm
Model name (FHQ-) A B C D E F G H J
Type 35 · 50 960 920 378 324 270 375 398 377 260 Type 60 · 71 1270 1230 533 479 425 530 553 532 415
Type 100 · 125 · 140 1590 1550 693 639 585 690 713 692 575
(2) Make holes for hanging bolts, piping outlet, drain piping outlet, and electric wiring inlet.
Use the installation pattern paper (5).
Determine the locations of hanging bolts, piping outlet, drain piping outlet and electric wiring inlet. And
make the hole.
Hanging bolt (4 pieces)
Top panel wiring outlet position
English 6
(3) Remove the parts of the indoor unit.
1) Remove the suction grille.
Slide the suction grille fixing knobs (35, 50 type: 2 places for each, 60~140 type: 3 places for each) toward backward direction (as shown by an arrow) to open the suction grille widely. (Refer to Fig. 4)
Keeping the suction grille opened, hold the knob at the back of the suction grille and at the same time, pull the suction grille forward to remove. (Refer to Fig. 5)
Rear knob
Fixing knob
Suction grille
Fig. 4 Fig. 5
2) Remove the decoration side panel (right, left).
Remove the fixture screw of the decoration side panel (one for each), pull forward (arrow direction) to remove. (Refer to Fig. 6)
Take out accessories. (Refer to Fig. 6)
Open the knock hole at the wiring inlet side at the rear surface or top surface, and install the attached
resin bushing (10).
Removable part (for leading in
Resin bushing (10)
from the upward-facing)
(accessory)
Removable part (for leading in from the rear-facing)
Resin bushing (10) (accessory)
Fixing screw for decoration
Accessories
side Panel (M4)
Decoration side panel
3) Remove the hanger.
Loosen 2 bolts for installing the hanger at both sides (M8) (4 places at left and right) within 10mm. (Refer to Fig. 7 and Fig. 8)
Remove the fixture screw for hanger at the back side (M5), pull the hanger backward (the arrow direction) to remove. (Refer to Fig. 8)
Bolt (M8)
Loosen within 10mm
Indoor unit
Hanger
Fig. 7 Fig. 8
Hanger fixing screw (M5)
Hanger installing bolt (M8)
Loosen
Fig. 6
Hanger
7 English
CAUTION
Do not remove the tape (milky white) applied to the outside of the indoor unit. It may cause electric shocks or a fire.
(4) Install the hanging bolts.
Use M8 or M10 bolts for hanging the indoor unit.
Adjust the length of the hanging bolt from the ceiling in advance. (Refer to Fig. 9)
Use hole-in-anchors for the existing bolts and embedded inserts or foundation bolts for new bolts, and
fix the unit firmly to the building so that it may withstand the mass of the unit. In addition, adjust the distance from the ceiling in advance.
CAUTION
If the hanging bolt is too long, it may damage or break the indoor unit or options.
Ceiling slab
Foundation bolt
25 - 55 mm
Fig. 9
NOTE
Parts shown Fig. 9 will be all field supply.
Ceiling surface
Hanging bolt

5. INSTALLATION OF THE INDOOR UNIT

〈〈It is easy to attach the optional parts before installing the indoor unit. Refer to also the installation manual attached to the optional parts.〉〉 For installation, use the attached installation parts and specified parts. (1) Fix the hanger to the hanging bolt. (Refer to Fig. 10)
CAUTION
For safety, make sure to use a washer for hanger (3) (accessory) and fix by double nuts firmly.
Hanging bolt
Nut (field supply)
Washer for hanger (3) (accessory)
Double nuts
Hanger
(2) Lift up the indoor unit, slide from the front and put the hanger installing bolt (M8) into the securely for tem-
porary hanging. (Refer to Fig. 11)
(3) Tighten the hanger fixing screws (M5) at 2 places, which were removed, as they were before.
(Refer to Fig. 11)
It is necessary to prevent misalignment of the indoor unit.
English 8
Fig. 10
(4) Tighten the hanger installing bolts (M8) at 4 places securely. (Refer to Fig. 11)
Attachement
Hanger
part
Hanger
Reinforcing plate (left/right) When carrying the indoor unit,
fixing screw (M5)
do not hold the reinforcing plates.
(5) When hanging the indoor unit, make sure to use the level to have better drainage and install it horizontally.
Also, if it is possible at the installation site, install so that the drain piping side is slightly lower.
(Refer to Fig. 12)
CAUTION
Setting the indoor unit at an angle opposite to the drain piping might cause a water leakage.
• Do not insert materials other than that specified into the clearance between the hanger and the washer for hanger (3).
Unless the washers are properly attached, the hanging bolts may come off from the hanger.
A
Hanger installing bolt (M8)
Fig. 11
A.B
B
Fig. 12
A. When the drain piping is tilted to the right, or to the right and back.
Place it level, or tilt it slightly to the right or the back. (Within 1°) When the drain piping is tilted to the left, or to the left and back.
B.
Place it level, or tilt it slightly to the left or the back. (Within 1°)
WARNING
The indoor unit must be securely installed on a place that can withstand the mass.
If the strength is insufficient, the indoor unit may fall down and cause injuries.
9 English

6. REFRIGERANT PIPING WORK

For the outdoor unit refrigerant piping, refer to the installation manual attached to the outdoor unit.
Carry out insulation of both gas and liquid refrigerant piping securely. If not insulated, it may cause water
leakage. For gas piping, use insulation material of which heat resistant temperature is not less than 120°C. For use under high humidity, strengthen the insulation material for refrigerant piping. If not strengthened, the surface of insulation material may sweat.
Before installation work, make sure that the refrigerant is R410A. (Unless the refrigerant is R410A, the nor­mal operation cannot be expected.)
CAUTION
This air conditioner is a dedicated model for new refrigerant R410A. Make sure to meet the requirements shown right and carry out installation work.
Use dedicated piping cutters and flaring tools for R410A.
When making a flare connection, coat the flared inner surface only with ether oil or ester oil.
Use only the flare nuts attached to the air conditioner. If other flare nuts are used, it may cause refrigerant
leakage.
To prevent contamination or moisture from getting into the piping, take measures such as pinching or tap-
ing the pipings. Do not mix substance other than the specified refrigerant such as air into the refrigeration circuit. If the refrigerant leaks during the work, ventilate the room.
Remove the stay for packing and delivering (reinforcing plate) before refrigerant piping work.
(Refer to Fig. 18)
The refrigerant is pre-charged in the outdoor unit.
When connecting the pipings to the air conditioner, make sure to use a spanner and a torque wrench as
shown in Fig.13. For the dimension of flared part, refer to the Table 1.
Torque wrench
Spanner
Flare nut
Union joint
When making a flare connection, coat the flared inner surface only with ether oil or ester oil.
Then, turn the flare nut 3 to 4 times with your hand and screw in the nut.
Coat the flared inner surface only with ether oil or ester oil.
Fig. 14
Fig. 13
(Refer to Fig. 14)
English 10
Loading...
+ 25 hidden pages