THANK YOU FOR PURCHASING THIS DAIKIN AIR
CONDITIONER. CAREFULLY READ THE CHAPTER
"OPERATING THE UNIT" ON PAGE 6 BEFORE USING
THE AIR CONDITIONER. IT WILL TELL YOU HOW TO
USE THE UNIT PROPERLY AND HELP YOU IF ANY
TROUBLE OCCURS. AFTER READING THE MANUAL,
FILE IT AWAY FOR FUTURE REFERENCE.
Installation and
operation manual
INSTALLINGTHEUNIT
READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNCERTAINTY ARISES ABOUT THE INSTALLATION
PROCEDURES OR USE, ALWAYS CONTACT YOUR
DAIKIN DEALER FOR ADVICE AND INFORMATION.
BEFOREINSTALLATION
■Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
■Refer to the installation manual of the outdoor unit for items not
described in this manual.
■Do not place objects in direct proximity of the outdoor unit and
do not let leaves and other debris accumulate around the unit.
Leaves are a hotbed for small animals which can enter the unit.
Once in the unit, such animals can cause malfunctions, smoke
or fire when making contact with electrical parts.
Precautions
■Do not install or operate the unit in rooms mentioned below.
• Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
• Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
• Where volatile flammable gas like thinner or gasoline is used.
• Where machines generating electromagnetic waves can be
found. (Control system may malfunction.)
• Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.
■Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.
Installation and operation manual
1
Optional accessories
Refer to catalogues and technical literature for selecting the remote
controller, and install it in an appropriate place.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Page 5
For the following items, take special care during
construction and check after installation is finished
Tick ✓
when
checked
Is the indoor unit fixed firmly?
■
■
■
■
■
■
■
■
■
■
The unit may drop, vibrate or make noise.
Is the gas leak test finished?
It may result in insufficient cooling.
Is the unit fully insulated?
Condensate water may drip.
Does drainage flow smoothly?
Condensate water may drip.
Does the power supply voltage correspond to that shown on the
name plate?
The unit may malfunction or components may burn out.
Are wiring and piping correct?
The unit may malfunction or components may burn out.
Is the unit safely grounded?
Dangerous at electric leakage.
Is the wiring size according to specifications?
The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or
outdoor units?
It may result in insufficient cooling.
Are refrigerant piping length and additional refrigerant charge
noted down?
The refrigerant charge in the system might not be clear.
This to avoid confusion for future maintenance and serving of
the installation.
Notes to the installer
■Be sure to instruct the customer how to properly operate the
system and show him/her the enclosed operation manual.
SELECTINGINSTALLATIONSITE(See figure 1 and 4)
1.Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate water can be properly drained.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can
be ensured.
• Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual of
the outdoor unit.)
•Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise
interference in those electrical appliances.
(Electric noise may be generated depending on the conditions
under which the electric wave is generated, even if 1 meter is
kept.)
•Never place anything under the indoor unit that you don't want to
get wet. The unit may sweat when the humidity is over 80% or
when the drain outlet is clogged.
•Never place other heating equipment directly beneath the indoor
unit. Subject to deformation caused by heat.
• The unit should be installed at least 2.5 m from the floor.
2.Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If
there is a risk, reinforce the ceiling before installing the unit.
1Service space ≥300
2Drain pipe
3Power supply wiring port
4Tr ansmission wiring port
5Gas pipe
6Liquid pipe
For other installation than standard installation, contact your
Daikin dealer for details.
3.The fan speed for this indoor unit is preset to provide high
external static pressure.
If lower external static pressure is required, reset the external
static pressure by changing the initial setting from the remote
controller.
Refer to "Setting of static pressure" on page 5.
4.Install the suspension bolts.
(Use M10 size bolt for the suspension bolt.) Use anchors for
existing ceilings, and a sunken insert, sunken anchors or other
field supplied parts for new ceilings to reinforce the ceiling in
order to bear the weight of the unit.
Installation example (See figure 5)
1Anchor
2Ceiling slab
3Long nut or turn-buckle
4Suspension bolt
5Indoor unit
NOTE
All the above parts are field supplied.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Installation and operation manual
2
Page 6
INDOORUNITINSTALLATION
When installing optional accessories read also the installation
manual of the optional accessories. Depending on the field
conditions, it may be easier to install optional accessories before the
indoor unit is installed.
1.Install the indoor unit temporarily.
• Attach the hanger bracket to the suspension bolt. Be sure to
fix it securely by using a nut and washer from the upper and
lower sides of the hanger bracket. (See figure 2)
For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.
NOTE
■Use a pipe cutter and flare suitable for the used refrigerant.
■Apply ether oil or ester oil around the flare portions before
■To prevent dust, moisture or other foreign matter from infiltrating
■The outdoor unit is charged with refrigerant.
■Be sure to use both a spanner and torque wrench together when
■Refer to Ta ble 1 for the dimensions of flare nut spaces and the
All field piping must be provided by a licensed
refrigeration technician and must comply with the
relevant local and national codes.
connecting.
the tube, either pinch the end, or cover it with tape.
connecting or disconnecting pipes to/from the unit.
1Torque wrench
2Spanner
3Piping union
4Flare nut
1
2
4
3
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)
Ta ble 1
Flare
Pipe
gauge
Ø9.5
Ø15.9
Tightening torque
32.7~39.9 N•m
(333~407 kgf•cm)
61.8~75.4 N•m
(630~770 kgf•cm)
dimension A
(mm)
12.0~12.4
18.6~19.0
Flare shape
±2
90°
45°
±2
A
R=0.4~0.8
■When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand
before tightening firmly.
Coat here with ether oil or ester oil
■Check the pipe connector for gas leaks, then insulate it.
1 Liquid pipe
2 Gas pipe
3 Insulation for fitting of liquid line (field
supply). The insulation should
withstand 80°C.
4 Insulation for fitting of gas line (field
supply). The insulation should
withstand 120°C.
5 Clamps (use 2 clamps per insulation)
3
5
4
12
DRAINPIPINGWORK
1Install the drain pipes.
-Keep piping as short as possible and slope it downwards so
that air may not remain trapped inside the pipe.
-Keep pipe size equal to or greater than that of the connecting
pipe.
-For connection to the drain socket: use a flexible hose (field
supply) and clamp it firmly. This to avoid leaks due to
operating vibration of the unit.
- After clamping, isolate the drain socket. This is to avoid leaks
-Execute the drain check before installing the duct
- Make sure that the drain hose is firmly connected
-Pour some water into the drain pan to check if the water flows
smoothly.
42
1
3
Installation and operation manual
3
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Page 7
ELECTRICWIRINGWORK
General instructions
■All field supplied parts and materials and electric works must
conform to local codes.
■Use copper wire only.
■Follow the "Wiring diagram" attached to the switch box cover to
wire the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".
■All wiring must be performed by an authorized electrician.
■A circuit breaker capable of shutting down power supply to the
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Installation and operation manual
4
Page 8
Precautions
1.Observe the notes mentioned below when wiring to the power supply
terminal board.
• Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
• When connecting wires of the same gauge, connect them
according to the figure.
2.Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
3.Remote controller cords and wires connecting the units should be
located at least 50 mm away from power supply wiring. Not following
this guideline may result in malfunction due to electrical noise.
4.For the remote controller wiring, refer to the "Installation manual of
the remote controller" supplied with the remote controller.
NOTE
The customer has the ability to select the remote
controller thermistor.
5.Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire system.
6.Use only specified wires and tightly connect wires to the terminals.
Be careful that wires do not place external stress on the terminals.
Keep wiring in neat order so that they do not obstruct other
equipment such as popping open the switch box cover. Make sure
the cover closes tight. Incomplete connections could result in
overheating, and in the worst case, electric shock or fire.
WIRINGEXAMPLE
■Fit the power supply wiring of each system with a switch and
fuse as shown in figure 7, 9 and 10.
1Power supply
2Main switch
3Fuse
4Outdoor unit
5Indoor unit (M=master, S=slave)
6Remote controller (optional accessory)
Precautions
1.A single switch can be used to supply power to units on the same
system. However, branch switches and branch circuit breakers must
be selected carefully.
2.Do not ground the equipment on gas pipes, water pipes, lightning
rods or crossground with telephones. Improper grounding could
result in electric shock.
FIELDSETTING
Field setting must be made from the remote controller in accordance
with the installation condition. Refer to the manual of the remote
controller.
Setting of static pressure
■Change the SECOND CODE No. according to Ta ble 2
depending on the resistance of the connection duct.
Ta ble 2
External static
pressure
Low: 50 Pa
High: 100 Pa 02
Mode No.FIRST CODE No.
13 (23)6
The unit is factory set for high static pressure (SECOND CODE No.
02) at the time of shipping.
Setting air filter sign
■Remote controllers are equipped with liquid crystal display air
filter signs to display the time to clean air filters.
■Change the SECOND CODE No. According to Ta ble 3
depending on the amount of dirt or dust in the room. (SECOND
CODE No. Is factory set to "01" for filter contamination-light.)
Ta ble 3
Spacing time of
display air filter
sign (long life
Setting
Air filter
contamination -
light
Air filter
contamination -
heavy
type)
±2500 hrs
±1250 hrs02
Mode No.
10 (20)0
CODE No.
FIRST
SECOND
CODE No.
01
SECOND
CODE No.
01
Complete system example (3 systems)
When using 1 remote controller for 1 indoor unit. (Normal
operation) (See figure 10)
For group control (See figure 7)
For group control, cut the jumper indicated as “master/slave” on the
PCB of the “slave” indoor units (=slave PCB). Do not cut the jumper
on the PCB of the indoor unit to which the remote controller is
connected (=master PCB).
MasterSlave
Use with 2 remote controllers (See figure 9)
NOTE
It is not necessary to designate an indoor unit address
when using group control. The address is automatically set when the power is activated.
Installation and operation manual
5
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
Refer to the manual of the remote controller.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Page 9
Computerised control (forced off and on/off operation)
1Wire specifications and how to perform wiring
- Connect the input wire (option) to connector X40A on the
indoor PCB.
Wire specifications (to extend the optional wire):
Wire specificationSheathed vinyl cord or cable (2 wire)
Gauge
LengthMax. 100 m
External terminalContact that can ensure the minimum
0.75-1.25 mm
applicable load of 15 V DC, 10 mA
2
(See figure 8)
1Input A (Input “ON”=closed contact)
2Actuation
- The following table explains "forced off" and "on/off
operations" in response to input A.
Forced offon/off operation
Input "on" stops operation +
disables control
Input "off" enables control input on ➜ off: stops operation remote,
input off ➜ on: starts operation remote,
control is still enabled
control is still enabled
3How to select forced off and on/off operation
Change the second code No. according to Ta ble 4. (Second
code No. is factory set to “01” for forced off.)
Ta ble 4
SettingMode No.FIRST CODE No. SECOND CODE No.
Forced off
ON/OFF
operation
12 (22)1
01
02
TESTOPERATION
Refer to the section of "For the following items, take special care
during construction and check after installation is finished" on page 2.
■After finishing the construction of refrigerant piping, drain piping,
and electric wiring, conduct test operation accordingly to protect
the unit.
1Open the gas side stop valve.
2Open the liquid side stop valve.
3Electrify crank case heater for 6 hours. (Not necessary for the
straight cooling type.)
4Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.
5Press Inspection/Test Operation button 4 times and operate at
Test Operation mode for 3 minutes.
OPERATINGTHEUNIT
NAMESANDFUNCTIONSOFPARTS(See figure 14)
1
Indoor unit
2
Outdoor unit
3
Remote controller
4
Inlet air
5
Discharged air
6
Refrigerant piping
7
Drain pipe
8Ground wire
Wire to ground outdoor unit to prevent electrical shocks.
9
Air filter
10
Connection electric wire
■Never let the indoor unit and the remote controller get
wet.
It may cause an electric shock or a fire.
■Never use flammable spray such as hair spray,
lacquer or paint near the unit.
It may cause a fire.
■Never replace a fuse with that of a wrong ampere
rating or other wires when the fuse blows out.
Use of wire or copper wire may cause the unit to
break down or cause a fire.
■Never insert objects such as sticks into the air inlet or
outlet. It is dangerous for an object to touch the fan
when it is turning at high speed.
■Never remove the fan grill of the outdoor unit.
The rotating fan at high speed without the guard is
very dangerous.
■Never inspect or service the unit by yourself.
Ask a qualified service person to perform this work.
IMPORTANTINFORMATIONREGARDINGTHE
REFRIGERANTUSED
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.
Refrigerant type:R410A
(1)
GWP
value:1975
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.
6Press Inspection/Test Operation button and operate normally.
7Confirm function of unit during operation. Refer to the manual of
the remote controller on how to operate.
NOTE
If the main power supply is turned off during operation,
operation will restart automatically after the power
turns back on again.
Precautions
In case something is wrong with the unit and it does not operate,
refer to the malfunction diagnosis label attached to the unit.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
OPERATIONRANGE(See figure 11)
If operating outside the following conditions, safety devices may
activate, rendering the air conditioner inoperable or may cause the
indoor unit to sweat.
The setting temperature range of the remote controller is 16°C - 32°C.
■If a function that is not available is selected, the
message NOT AVAILABLE will appear.
■Operating procedure varies with heat pump type and
straight cooling type. Contact your Daikin dealer to
confirm your system type.
■To protect the unit, turn on the main power switch
6 hours before operation.
■If the main power supply is turned off during
operation, operation will restart automatically after the
power turns back on again.
Precautions for group control system or two remote
controller control system
This system provides two other control systems beside individual
control (one remote controller controls one indoor unit) system.
Confirm the following if your unit is of the following control system
type.
■Group control system
One remote controller controls up to 16 indoor units.
All indoor units are equally set.
■Tw o remote controller control system
Tw o remote controllers control one indoor unit (In case of group
control system, one group of indoor units). The unit is
individually operated.
NOTE
Contact your Daikin dealer in case of changing the
combination or setting of group control and two remote
controller control systems.
OPTIMUMOPERATION
Observe the following precautions to ensure the system operates
properly.
■Adjust the air outlet properly and avoid direct air flow to room
inhabitants.
■Adjust the room temperature properly for a comfortable
environment. Avoid excessive heating or cooling.
■Prevent direct sunlight from entering a room during cooling
operation by using curtains or blinds.
■Keep doors and windows closed. If the doors and windows
remain open, room air will flow out and decrease the effect of
cooling and heating.
■Never place objects near the air inlet and the air outlet of the
unit. It may retard effectiveness or cause operation to stop.
■Tu rn off the main power supply switch when not using for long
periods of time. Electricity is consumed as long as the switch is
on. Turn off the main power supply switch in order to save
energy. Turn on the main power supply switch 6 hours before
restarting operation in order to ensure smooth operation. (Refer
to "Maintenance" on page 8.)
■When the display shows "" (TIME TO CLEAN AIR
FILTER), have a qualified service person to clean the filters.
(Refer to "Maintenance" on page 8.)
The following symptoms do not indicate air conditioner malfunction.
The system does not operate
■The system does not restart immediately after the ON/OFF
button is pressed.
If the OPERATION lamp lights, the system is in its normal
operating condition.
It does not restart immediately because one of its safety devices
actuates to prevent the system from being overloaded.
The system will turn on again automatically after three minutes.
■The system does not restart immediately when the
TEMPERATURE SETTING button is returned to its former
position after pushing.
It does not restart immediately because one of its safety devices
actuates to prevent the system from being overloaded.
The system will turn on again automatically after three minutes.
■The system does not start when the display shows ""
(EXTERNAL CONTROL ICON) and it flashes for a few seconds
after pressing an operation button.
This is because the system is controlled or disabled by another
controller with a higher priority.
When the display flashes, it indicates that the system cannot be
controlled by this indoor unit.
■The system does not start immediately after the power supply is
turned on.
Wait one minute until the micro computer is prepared for
operation.
White mist comes out of a unit
■When humidity is high during cooling operation (In oily or dusty
places).
If the inside of an indoor unit is extremely contaminated, the
temperature distribution inside a room becomes uneven. It is
necessary to clean the inside of the indoor unit. Ask your Daikin
dealer for details on cleaning the unit. This operation requires a
qualified service person.
■When the system is changed over to HEATING OPERATION
after DEFROST OPERATION.
Moisture generated by DEFROST becomes steam and exits.
Noise of air conditioners
■A continuous low "hissing" sound is heard when the system is in
COOLING or DEFROST OPERATION.
This is the sound of refrigerant gas flowing through both indoor
and outdoor units.
■A "hissing" sound which is heard at the start or immediately after
the stop of operation or which is heard at the start or
immediately after the stop of DEFROST OPERATION.
This is the noise of refrigerant caused by flow stop and flow
change.
■A "squeaking" sound is heard when the system is in operation or
after the stop of operation.
Expansion and contraction of plastic parts caused by
temperature change makes this noise.
Dust from the units
■Dust may blow out from the unit after starting operation from
long resting time. Dust absorbed by the unit blows out.
The units give off odours
■The unit absorbs the smell of rooms, furniture, cigarettes, etc.,
and then emits them.
Installation and operation manual
7
The liquid crystal display of the remote controller shows ""
■Happens immediately after the main power supply switch is
turned on.
Shows that the remote controller is in normal condition.
Continues temporarily.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Page 11
TROUBLESHOOTING
MAINTENANCE
If one of the following malfunctions occurs, take the measures shown
below and contact your Daikin dealer.
The system must be repaired by a qualified service person.
■If a safety device such as a fuse, a breaker, or an earth leakage
breaker frequently actuates, or ON/OFF switch does not
properly work.
Measure: Turn off the main power switch.
■If water leaks from unit.
Measure: Stop the operation.
■If the display "" (INSPECTION), "UNIT No.", and the
OPERATION lamp flashes and the "MALFUNCTION CODE"
appears.
Measure: Notify your Daikin dealer and inform him/her of the
display.
If the system does not operate properly, except for the above
mentioned case, and none of the above mentioned malfunctions is
evident, investigate the system according to the following
procedures.
If the system does not operate at all.
■Check if there is a power failure.
Wait until power is restored. If power failure occurs during
operation, the system automatically restarts immediately after
the power supply recovers.
■Check if the fuse has blown or breaker has been tripped.
Change the fuse or set the breaker.
If the system stops operating after operation is complete.
■Check if the air inlet or outlet of outdoor or indoor unit is blocked
by obstacles.
Remove the obstacle and make it well-ventilated.
■Check if the air filter is clogged.
Ask a qualified service person to clean the air filter.
The system operates but it does not sufficiently cool or heat.
■If the air inlet or outlet of the indoor or the outdoor unit is blocked
with obstacles.
Remove the obstacle and make it well-ventilated.
■If the air filter is clogged.
Ask a qualified service person to clean the air filter.
■If the set temperature is not proper. (Refer to the manual of the
remote controller.)
■If the FAN SPEED CONTROL button is set to LOW SPEED.
(Refer to the manual of the remote controller.)
■If the doors or the windows are open. Shut doors or windows to
prevent wind from coming in.
■If direct sunlight enters the room (when cooling).
Use curtains or blinds.
■When there are too many inhabitants in the room. Cooling effect
decreases if heat gain of the room is too large.
■If the heat source of the room is excessive (when cooling).
Cooling effect decreases if heat gain of the room is too large.
■Only a qualified service person is allowed to perform
maintenance.
■Before obtaining access to terminal devices, all power
supply circuits must be interrupted.
■Do not use water or air of 50°C or higher for cleaning
air filters and outside panels.
■When cleaning the heat exchanger, be sure to remove
the switchbox and fan motor. Water or detergent may
deteriorate the insulation of electronic components
and result in burn-out of these components.
How to clean the air filter
Clean the air filter when the display shows "" (TIME TO CLEAN
AIR FILTER).
Increase the frequency of cleaning if the unit is installed in a room
where the air is extremely contaminated.
(As a yardstick for yourself, consider cleaning the filter once a half
year.)
If the dirt becomes impossible to clean, change the air filter. (Air filter
for exchange is optional.)
(See figure 12)
1Remove the filter holding plate (1) from the bottom plate.
2Remove the air filter (2) by sliding it downwards.
3Clean the air filter. (Refer to figure 13air flow direction over
filter.)
Use vacuum cleaner or wash the air filter with water.
When the air filter is very dirty, use soft brush and neutral
detergent.
Remove water and dry in the shade.
4Replace the air filter by sliding it between the guiding plates.
5Replace the filter holding plate to the bottom plate.
6After turning on the power, press FILTER SIGN RESET button.
The “TIME TO CLEAN AIR FILTER” display is turned off.
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Installation and operation manual
8
Page 12
How to clean air outlet
■Clean with soft cloth.
■When it is difficult to remove stains, use water or neutral
detergent.
NOTES
NOTE
Do not use gasoline, benzene, thinner, polishing
powder, liquid insecticide. It may cause discoloring or
warping.
Do not let the indoor unit get wet. It may cause an
electric shock or a fire.
Start-up after a long stop
■Confirm the following.
- Check that the air inlet and outlet are not blocked. Remove
any obstacle.
- Check if the earth is connected.
■Clean the air filter.
- After cleaning the air filter, make sure to attach it.
■Tu rn on the main power supply switch.
- The control panel display lights when the power is turned on.
-To protect the unit, turn on the main power switch at least
6 hours before operation.
What to do when stopping the system for a long period
■Tu rn on FAN OPERATION for a half day and dry the unit.
- Refer to the manual of the remote controller.
■Cut off the power supply.
- When the main power switch is turned on, some wattage is
being consumed even if the system is not operating.
- The remote controller display is turned off when the main
power switch is turned off.
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
Your air conditioning product is marked with this symbol.
This means that electrical and electronic products shall
not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air
conditioning system, treatment of the refrigerant, of oil and of other
parts must be done by a qualified installer in accordance with
relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for
re-use, recycling and recovery. By ensuring this product is disposed
of correctly, you will help to prevent potential negative consequences
for the environment and human health. Please contact the installer or
local authority for more information.
Batteries must be removed from the remote controller and disposed
of separately in accordance with relevant local and national
legislation.
Installation and operation manual
9
FDEQ71~125B8V3B
Split System air conditioners
4PW23693-1A
Page 13
NOTES NOTES
Page 14
Zandvoordestraat 300, B-8400 Oostende, Belgium
4PW23693-1A
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.