deklaruje na własną i wyłączną odpowiedzialność, że modele klimatyzatorów, których dotyczy niniejsza deklaracja:
declară pe proprie răspundere că aparatele de aer condiţionat la care se referă această declaraţie:
z vso odgovornostjo izjavlja, da so modeli klimatskih naprav, na katere se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluvad kliimaseadmete mudelid:
декларира на своя отговорност, че моделите климатична инсталация, за които се отнася тази декларация:
visiška savo atsakomybe skelbia, kad oro kondicionavimo prietaisų modeliai, kuriems yra taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk uzskaitīto modeļu gaisa kondicionētāji, uz kuriem attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že tieto klimatizačné modely, na ktoré sa vzťahuje toto vyhlásenie:
tamamen kendi sorumluluǧunda olmak üzere bu bildirinin ilgili olduǧu klima modellerinin aşaǧıdaki gibi olduǧunu beyan eder:
17
18
19
20
21
22
23
24
25
megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi instrukcjami:
sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în conformitate cu
instrucţiunile noastre:
skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите инструкции:
atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade snašim
161718192021222324
návodom:
Directives, as amended.
Direktiven, gemäß Änderung.
ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
25
Directives, telles que modifiées.
010203040506070809
Değiştirilmiş halleriyle Yönetmelikler.
25
Direktiivejä, sellaisina kuin ne ovat muutettuina.
v platném znění.
Smjernice, kako je izmijenjeno.
irányelv(ek) és módosításaik rendelkezéseit.
z późniejszymi poprawkami.
17
както е изложено в <A> и оценено положително от <B>
съгласно Сертификата<C>.
kaip nustatyta <A> ir kaip teigiamai nuspręsta <B> pagal
Sertifikatą<C>.
kā norādīts <A> un atbilstoši <B> pozitīvajam vērtējumam
saskaņā ar sertifikātu<C>.
Richtlijnen, zoals geamendeerd.
Directivas, según lo enmendado.
Direttive, come da modifica.
Οδηγιών, όπως έχουν τροποποιηθεί.
Directivas, conforme alteração em.
Директив со всеми поправками.
21Забележка*
22Pastaba*
23Piezīmes*
*
**
Daikin Europe N.V. je pooblaščen za sestavo datoteke s tehnično mapo.
Daikin Europe N.V. on volitatud koostama tehnilist dokumentatsiooni.
Daikin Europe N.V. е оторизирана да състави Акта за техническа конструкция.
Daikin Europe N.V. yra įgaliota sudaryti šį techninės konstrukcijos failą.
Daikin Europe N.V. ir autorizēts sastādīt tehnisko dokumentāciju.
Spoločnosť Daikin Europe N.V. je oprávnená vytvoriť súbor technickej konštrukcie.
Daikin Europe N.V. Teknik Yapı Dosyasını derlemeye yetkilidir.
19**
20**
21**
22**
23**
24**
25**
ako bolo uvedené v <A> a pozitívne zistené <B> vsúlade
s osvedčením<C>.
<A>’da belirtildiği gibi ve <C>Sertifikasına göre <B>
tarafından olumlu olarak değerlendirildiği gibi.
24Poznámka*
25Not*
a(z) <A> alapján, a(z) <B> igazolta a megfelelést, a(z)
<C>tanúsítvány szerint.
zgodnie z dokumentacją <A>, pozytywną
opinią <B> i Świadectwem<C>.
aşa cum este stabilit în <A> şi apreciat pozitiv de<B>
în conformitate cu Certificatul<C>.
kot je določeno v <A> in odobreno s strani <B>
vskladu scertifikatom<C>.
nagu on näidatud dokumendis <A> ja heaks kiidetud
<B> järgi vastavalt sertifikaadile<C>.
Daikin Europe N.V. on valtuutettu laatimaan Teknisen asiakirjan.
Společnost Daikin Europe N.V. má oprávnění ke kompilaci souboru technické konstrukce.
Daikin Europe N.V. je ovlašten za izradu Datoteke o tehničkoj konstrukciji.
A Daikin Europe N.V. jogosult a műszaki konstrukciós dokumentáció összeállítására.
Daikin Europe N.V. ma upoważnienie do zbierania i opracowywania dokumentacji konstrukcyjnej.
13**
14**
15**
16**
16Megjegyzés*
17Uwaga*
18Notă*
19Opomba*
20Märkus*
Machinery 2006/42/EC
Low Voltage 2014/35/EU
enligt <A> och godkänts av <B> enligt
Certifikatet<C>.
som det fremkommer i <A> og gjennom positiv
bedømmelse av <B> ifølge Sertifikat<C>.
jotka on esitetty asiakirjassa <A> ja jotka <B>
on hyväksynyt Sertifikaatin<C> mukaisesti.
jak bylo uvedeno v <A> a pozitivně zjištěno
<B> vsouladu sosvědčením<C>.
kako je izloženo u <A> i pozitivno ocijenjeno odstrane
Electromagnetic Compatibility 2014/30/EU
заявляет, исключительно под свою ответственность, что модели кондиционеров воздуха, к которым относится настоящее заявление:
erklærer under eneansvar, at klimaanlægmodellerne, som denne deklaration vedrører:
deklarerar i egenskap av huvudansvarig, att luftkonditioneringsmodellerna som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at de luftkondisjoneringsmodeller som berøres av denne deklarasjon, innebærer at:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat ilmastointilaitteiden mallit:
prohlašuje ve své plné odpovědnosti, že modely klimatizace, k nimž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da su modeli klima uređaja na koje se ova izjava odnosi:
teljes felelőssége tudatában kijelenti, hogy a klímaberendezés modellek, melyekre e nyilatkozat vonatkozik:
09
10
11
12
13
14
15
16
estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
acordo com as nossas instruções:
соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим инструкциям:
overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore instrukser:
respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under förutsättning att
användning sker i överensstämmelse med våra instruktioner:
respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at disse brukes i
henhold til våre instrukser:
vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme mukaisesti:
za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
08091011121314
u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
15
ob upoštevanju določb:
vastavalt nõuetele:
следвайки клаузите на:
laikantis nuostatų, pateikiamų:
ievērojot prasības, kas noteiktas:
19202122232425
održiavajúc ustanovenia:
11Information*
12Merk*
13Huom*
bunun koşullarına uygun olarak:
delineato nel <A> e giudicato positivamente da<B>
secondo il Certificato<C>.
όπως καθορίζεται στο <A> και κρίνεται θετικά
από το <B> σύμφωνα με το Πιστοποιητικό<C>.
tal como estabelecido em <A> e com o parecer positivo
<B> prema Certifikatu<C>.
14Poznámka*
15Napomena*
de <B> de acordo com o Certificado<C>.
как указано в <A> и в соответствии сположительным
решением <B> согласно Свидетельству<C>.
som anført i <A> og positivt vurderet af <B> ihenhold til
Certifikat<C>.
17**
Η Daikin Europe N.V. είναι εξουσιοδοτημένη να συντάξει τον Τεχνικό φάκελο κατασκευής.
A Daikin Europe N.V. está autorizada a compilar a documentação técnica de fabrico.
Компания Daikin Europe N.V. уполномочена составить Комплект технической документации.
Daikin Europe N.V. er autoriseret til at udarbejde de tekniske konstruktionsdata.
Daikin Europe N.V. är bemyndigade att sammanställa den tekniska konstruktionsfilen.
07**
08**
09**
10**
11**
Daikin Europe N.V. este autorizat să compileze Dosarul tehnic de construcţie.
18**
Shigeki Morita
Director
Ostend, 1st of August 2017
Daikin Europe N.V. har tillatelse til å kompilere den Tekniske konstruksjonsfilen.
12**
declares under its sole responsibility that the air conditioning models to which this declaration relates:
erklärt auf seine alleinige Verantwortung daß die Modelle der Klimageräte für die diese Erklärung bestimmt ist:
CE - DECLARATION-OF-CONFORMITYCE - DECLARACION-DE-CONFORMIDADCE - DECLARAÇÃO-DE-CONFORMIDADECE - ERKLÆRING OM-SAMSVARCE - IZJAVA-O-USKLAĐENOSTICE - IZJAVA O SKLADNOSTICE - ATITIKTIES-DEKLARACIJA
CE - CONFORMITEITSVERKLARINGCE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSECE - DECLARAŢIE-DE-CONFORMITATECE - UYGUNLUK-BEYANI
déclare sous sa seule responsabilité que les appareils d'air conditionné visés par la présente déclaration:
Daikin Europe N.V.
01
02
03
06Nota*
07Σημείωση*
08Nota*
09Примечание*
10Bemærk*
under iagttagelse af bestemmelserne i:
enligt villkoren i:
gitt i henhold til bestemmelsene i:
noudattaen määräyksiä:
za dodržení ustanovení předpisu:
prema odredbama:
követi a(z):
zgodnie z postanowieniami Dyrektyw:
101112131415161718
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de airconditioning units waarop deze verklaring betrekking heeft:
declara baja su única responsabilidad que los modelos de aire acondicionado a los cuales hace referencia la declaración:
dichiara sotto sua responsabilità che i condizionatori modello a cui è riferita questa dichiarazione:
δηλώνει με αποκλειστική της ευθύνη ότι τα μοντέλα των κλιματιστικών συσκευών στα οποία αναφέρεται η παρούσα δήλωση:
declara sob sua exclusiva responsabilidade que os modelos de ar condicionado a que esta declaração se refere:
04
05
06
FDA125A5VEB,
07
08
are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions:
der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung, daß sie gemäß
unseren Anweisungen eingesetzt werden:
sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig onze
instructies:
están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con nuestras
instrucciones:
sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle nostre istruzioni:
είναι σύμφωνα με το(α) ακόλουθο(α) πρότυπο(α) ή άλλο έγγραφο(α) κανονισμών, υπό την προϋπόθεση ότι χρησιμοποιούνται
01020304050607
σύμφωνα με τις οδηγίες μας:
following the provisions of:
gemäß den Vorschriften der:
conformément aux stipulations des:
EN60335-2-40,
overeenkomstig de bepalingen van:
010203040506070809
în urma prevederilor:
as set out in <A> and judged positively by <B>
according to the Certificate<C>.
wie in <A> aufgeführt und von <B> positiv
beurteilt gemäß Zertifikat<C>.
tel que défini dans <A> et évalué positivement par <B>
conformément au Certificat<C>.
zoals vermeld in <A> en positief beoordeeld door <B>
siguiendo las disposiciones de:
secondo le prescrizioni per:
με τήρηση των διατάξεων των:
de acordo com o previsto em:
в соответствии с положениями:
01Note*
02Hinweis*
03Remarque*
04Bemerk*
overeenkomstig Certificaat<C>.
como se establece en <A> y es valorado
positivamente por <B> de acuerdo con el
Certificado<C>.
05Nota*
Daikin Europe N.V. is authorised to compile the Technical Construction File.
01**
Daikin Europe N.V. hat die Berechtigung die Technische Konstruktionsakte zusammenzustellen.
Daikin Europe N.V. est autorisé à compiler le Dossier de Construction Technique.
Daikin Europe N.V. is bevoegd om het Technisch Constructiedossier samen te stellen.
Daikin Europe N.V. está autorizado a compilar el Archivo de Construcción Técnica.
Daikin Europe N.V. è autorizzata a redigere il File Tecnico di Costruzione.
02**
03**
04**
05**
06**
3P471028-10A
Table of Contents
Table of Contents
1 General safety precautions3
1.1About the documentation ..........................................................3
1.1.1Meaning of warnings and symbols..............................4
1.2For the user ...............................................................................4
1.3For the installer..........................................................................4
18.1.4 Symptom: Noise of air conditioners (indoor unit)......... 28
18.1.5 Symptom: Dust comes out of the unit.......................... 28
18.1.6 Symptom: The units can give off odours...................... 28
18.1.7 Symptom: The display shows "88"............................... 29
18.1.8 Symptom: The operation stopped suddenly
(Operation lamp is on) ................................................. 29
18.1.9 Symptom: The outdoor fan rotates while the air
conditioner is not in operation ...................................... 29
18.1.10 Symptom: The heating operation stops suddenly and
a flowing sound is heard .............................................. 29
19 Relocation29
20 Disposal29
21 Glossary29
1General safety precautions
1.1About the documentation
▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be
performed by an authorized installer.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
3
1 General safety precautions
1.1.1Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious
injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate
injury.
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
SymbolExplanation
Before installation, read the installation and
operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks,
read the service manual.
For more information, see the installer and user
reference guide.
▪ Units are marked with the following symbol:
This means that electrical and electronic products may not be
mixed with unsorted household waste. Do NOT try to dismantle
the system yourself: the dismantling of the system, treatment of
the refrigerant, of oil and of other parts must be done by an
authorized installer and must comply with applicable legislation.
Units must be treated at a specialized treatment facility for reuse,
recycling and recovery. By ensuring this product is disposed of
correctly, you will help to prevent potential negative consequences
for the environment and human health. For more information,
contact your installer or local authority.
▪ Batteries are marked with the following symbol:
This means that the batteries may not be mixed with unsorted
household waste. If a chemical symbol is printed beneath the
symbol, this chemical symbol means that the battery contains a
heavy metal above a certain concentration.
Possible chemical symbols are: Pb: lead (>0.004%).
Waste batteries must be treated at a specialized treatment facility
for reuse. By ensuring waste batteries are disposed of correctly,
you will help to prevent potential negative consequences for the
environment and human health.
1.3For the installer
1.3.1General
If you are not sure how to install or operate the unit, contact your
dealer.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
1.2For the user
▪ If you are not sure how to operate the unit, contact your installer.
▪ This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental
capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in
a safe way and understand the hazards involved. Children shall
not play with the appliance. Cleaning and user maintenance shall
not be made by children without supervision.
WARNING
To prevent electric shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
Installer and user reference guide
4
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It
could be too hot or too cold. Give it time to return to
normal temperature. If you must touch it, wear
protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
1 General safety precautions
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an
accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
1.3.2Installation site
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
WARNING
The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating ignition sources (example: open flames, an
operating gas appliance or an operating electric heater)
and have a room size as specified below.
NOTICE
▪ Do NOT reuse joints which have been used already.
▪ Joints made in installation between parts of refrigerant
system shall be accessible for maintenance purposes.
WARNING
Make sure installation, servicing, maintenance and repair
comply with instructions from Daikin and with applicable
legislation (for example national gas regulation) and are
executed only by authorised persons.
Installation space requirements
NOTICE
▪ Pipework shall be protected from physical damage.
▪ Installation of pipework shall be kept to a minimum.
WARNING
If appliances contain R32 refrigerant, then the floor area of
the room in which the appliances are installed, operated
and stored must be larger than the minimum floor area
defined in table below A (m2). This applies to:
▪ Indoor units without refrigerant leakage sensor; in
case of indoor units with refrigerant leakage sensor,
consult the installation manual
▪ Outdoor units installed or stored indoors (example:
winter garden, garage, machinery room)
▪ Pipework in unventilated spaces
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.
Instructions for equipment using R32 refrigerant
If applicable.
WARNING
▪ Do NOT pierce or burn.
▪ Do NOT use means to accelerate the defrosting
process or to clean the equipment, other than those
recommended by the manufacturer.
▪ Be aware that R32 refrigerant does NOT contain an
odour.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
2 Determine which graph or table to use.
▪ For indoor units: Is the unit ceiling-mounted, wall-mounted or
floor-standing?
▪ For outdoor units installed or stored indoors, and field piping
in unventilated spaces, this depends on the installation
height:
If the installation height is… Then use the graph or table for…
<1.8mFloor-standing units
1.8≤x<2.2mWall-mounted units
≥2.2mCeiling-mounted units
3 Use the graph or table to determine the minimum floor area.
Installer and user reference guide
5
1 General safety precautions
m (kg)
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1
1.2
1.4
1.6
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
7.956
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
Ceiling-mounted
unit
(a)
—
4.613.5
<1.224
<1.224—
4.6182
1.2250.956
4.814.7
1.22512.9
4.8198
1.41.25
5.016.0
1.416.8
5.0215
1.61.63
5.217.3
1.622.0
5.2232
1.82.07
5.418.6
1.827.8
5.4250
2.02.55
5.620.0
2.034.3
5.6269
2.23.09
5.821.5
2.241.5
5.8289
2.43.68
6.023.0
2.449.4
6.0309
2.64.31
6.224.5
2.658.0
6.2330
2.85.00
6.426.1
2.867.3
6.4351
3.05.74
6.627.8
3.077.2
6.6374
3.26.54
6.829.5
3.287.9
6.8397
3.47.38
7.031.3
3.499.2
7.0420
3.68.27
7.233.1
3.6111
7.2445
3.89.22
7.434.9
3.8124
7.4470
4.010.2
7.636.9
4.0137
7.6496
4.211.3
7.838.8
4.2151
7.8522
4.412.4
7.95640.8
4.4166
7.956549
m (kg)
A
min
(m2)
<1.224—
4.620.2
1.2251.43
4.822.0
1.41.87
5.023.8
1.62.44
5.225.8
1.83.09
5.427.8
2.03.81
5.629.9
2.24.61
5.832.1
2.45.49
6.034.3
2.66.44
6.236.6
2.87.47
6.439.1
3.08.58
6.641.5
3.29.76
6.844.1
3.411.0
7.046.7
3.612.4
7.249.4
3.813.8
7.452.2
4.015.3
7.655.1
4.216.8
7.858.0
4.418.5
7.95661.0
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
A
Minimum floor area
min
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)
1.3.3Refrigerant
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are not
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
Installer and user reference guide
6
m Total refrigerant charge in the system
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leakage in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
Always recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable
legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
1 General safety precautions
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when
pausing, close the valve of the refrigerant tank
immediately. If the valve is not closed immediately,
remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.
Charge with the cylinder upright.
down.
1.3.4Brine
If applicable. See the installation manual or installer reference guide
of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the
applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If
brine leaks, ventilate the area immediately and contact
your local dealer.
WARNING
The ambient temperature inside the unit can get much
higher than that of the room, e.g. 70°C. In case of a brine
leak, hot parts inside the unit can create a hazardous
situation.
1.3.6Electrical
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or
touching electrical parts.
▪ Disconnect the power supply for more than 1minute,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you
can touch electrical components. For the location of the
terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
WARNING
The use and installation of the application MUST comply
with the safety and environmental precautions specified in
the applicable legislation.
1.3.5Water
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure water quality complies with EU directive
98/83EC.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
7
2 About the documentation
NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
▪ Over-tightening the terminal screws may break them.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2About the documentation
2.1About this document
INFORMATION
Make sure that the user has the printed documentation and
ask him/her to keep it for future reference.
Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained
users in shops, in light industry, and on farms, or for
commercial and household use by lay persons.
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪ General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
▪ Indoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the indoor unit)
▪ Installer and user reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Detailed step-by-step instructions and background information
for basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
For the installer
3About the box
3.1Overview: About the box
This chapter describes what you have to do after the box with the
indoor unit is delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
(1)
Only for appliances using R32 refrigerant. Refer to the outdoor unit specifications for the type of refrigerant to be used.
Installer and user reference guide
8
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
3.2Indoor unit
WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable.
1
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
4 About the units and options
16×8×1×1×
3×
1×
1×
1×
1×
dcbaefg
hij
2×
b
f
a
h
c
d
e
g
3.2.1To unpack and handle the unit
Use a sling of soft material or protective plates together with a rope
when lifting the unit. This to avoid damage or scratches to the unit.
Lift the unit by holding on to the hanger brackets without exerting
any pressure on other parts, especially on refrigerant piping, drain
piping and other resin parts.
3.2.2To remove the accessories from the
indoor unit
a Installation manual and operation manual
b General safety precautions
c Washers for hanger bracket
d Screws for duct flanges
e Metal clamp
f Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe)
g Drain hose
h Insulation piece: Small (liquid pipe)
i Insulation piece: Large (gas pipe)
l Wire for common power supply
4About the units and options
4.1Overview: About the units and
options
This chapter contains information about:
▪ Combining outdoor and indoor units
▪ Combining the indoor unit with options
WARNING
Never use a flammable spray such as hair spray, lacquer
or paint near the unit. It may cause a fire.
4.2System layout
b Outdoor unit
c User interface
d Suction air
e Discharge air
f Refrigerant piping + interconnection cable
g Drain pipe
h Earth wiring
4.3Combining units and options
4.3.1Possible options for the indoor unit
Make sure you have the following mandatory options:
▪ User interface: Wired or wireless
▪ Air inlet panel and canvas connection for the air inlet panel (in
case of bottom suction).
5Preparation
5.1Overview: Preparation
This chapter describes what you have to do and know before going
on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the refrigerant piping
▪ Preparing the electrical wiring
5.2Preparing installation site
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Choose the installation location with sufficient place for carrying
the unit in and out of the site.
WARNING
Do NOT install the air conditioner at any place where
flammable gas may leak out. If the gas leaks out and stays
around the air conditioner, a fire may break out.
5.2.1Installation site requirements of the
indoor unit
INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
a Indoor unit
INFORMATION
The sound pressure level is less than 70dBA.
NOTICE
The equipment described in this manual may cause
electronic noise generated from radio-frequency energy.
The equipment complies to specifications that are
designed to provide reasonable protection against such
interference. However, there is no guarantee that
interference will not occur in a particular installation.
It is therefore recommended to install the equipment and
electric wires keeping proper distances away from stereo
equipment, personal computers, etc.
Installer and user reference guide
9
5 Preparation
≥300
a
e
bfg
dc
680
c
b
a
A
d
a
B
b
c
680
200<45
d
e
f
g
a
C
b
c
680
d
e
f
t
Ø
▪ Fluorescent lights. When installing a wireless user interface in a
room with fluorescent lights, mind the following to avoid
interference:
▪ Install the wireless user interface as close as possible to the
indoor unit.
▪ Install the indoor unit as far as possible from the fluorescent
lights.
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
▪ Choose a location where the hot/cold air discharged from the unit
or the operation noise, will NOT disturb anyone.
WARNING
Do NOT place objects below the indoor and/or outdoor unit
that may get wet. In this condition, condensation on the
main unit or refrigerant pipes, air filter dirt or drain blockage
may cause dripping. This results in fouling or failure of the
object which is located beneath the unit.
▪ Air flow. Make sure nothing blocks the air flow.
▪ Drainage. Make sure condensation water can be evacuated
properly.
▪ Ceiling insulation. When conditions in the ceiling exceed 30°C
and a relative humidity of 80%, or when fresh air is inducted into
the ceiling, then additional insulation is required (minimum 10mm
thickness, polyethylene foam).
▪ Protective guards. Make sure to install protective guards on the
suction and discharge side to prevent somebody from touching
the fan blades or heat exchanger.
Do NOT install the unit in the following places:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall
off or cause water leakage.
It is NOT recommended to install the unit in the following places
because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present
▪ Use suspension bolts for installation.
▪ Spacing. Mind the following requirements:
▪ Installation options:
A Standard rear suction
B Installation with rear duct and duct service opening
C Installation with rear duct, no duct service opening
a Ceiling surface
b Ceiling opening
c Service access panel (optional accessory)
d Air filter
e Air inlet filter
f Duct service opening
g Interchangeable plate
5.3Preparing refrigerant piping
5.3.1Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit
name plate), larger piping thickness might be required.
▪ Flare connections: Only use annealed material.
a Service space
Installer and user reference guide
10
b Drain pipe
c Power supply wiring port
d Transmission wiring port
e Maintenance drain outlet
g Liquid pipe
f Gas pipe
Split system air conditioners
(a)
FDA125A5VEB
4P495031-1 – 2017.06
6 Installation
ØiØ
i
t
ØpØ
p
1
2
4
3
5.3.2Refrigerant piping insulation
▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
Pipe outer diameter
(Øp)
9.5mm (3/8")10~14mm≥13mm
15.9mm (5/8")16~20mm≥13mm
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
Ambient
temperature
≤30°C75% to 80% RH15mm
>30°C≥80% RH20mm
Insulation inner
diameter (Øi)
HumidityMinimum thickness
Insulation thickness
(t)
5.4Preparing electrical wiring
6Installation
6.1Overview: Installation
This chapter describes what you have to do and know on-site to
install the system.
Typical workflow
Installation typically consists of the following stages:
▪ Mounting the outdoor unit.
▪ Mounting the indoor unit.
▪ Connecting the refrigerant piping.
▪ Checking the refrigerant piping.
▪ Charging refrigerant.
▪ Connecting the electrical wiring.
▪ Finishing the outdoor installation.
▪ Finishing the indoor installation.
INFORMATION
This chapter only describes installation instructions specific
to the indoor unit. For the other instructions, see:
▪ The installation manual of the outdoor unit
▪ The installation manual of the user interface
▪ The installation manual of the optional accessories
5.4.1About preparing electrical wiring
INFORMATION
Also read the precautions and requirements in the
"General safety precautions" chapter.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable
legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
6.2Mounting the indoor unit
6.2.1Precautions when mounting the indoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
6.2.2Guidelines when installing the indoor unit
INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment.
Depending on the field conditions, it might be easier to
install the optional equipment first.
▪ In case of installation with duct, but no duct service opening.
Modify the position of the air filters.
1 Remove the air filter(s) from the outside of the unit.
2 Remove the interchangeable plate.
3 Install the air filter(s) on the inside of the unit.
4 Reinstall the interchangeable plate.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
11
6 Installation
a
b
c
5 mm
b
b
a
c
c
a
A
B
180
4601460
1460
160
(160~300)
425
180
460
≥350
e
d
d
b
a
a
1400
1450
d
a
d
b
700
630
c
a1
b1
b1
a2
c1
4×
b
a
c
e
d
b
a
▪ When installing an air inlet duct, select fixing screws that stick out
5 mm on the inside of the flange to protect the air filter from
damage during maintenance of the filter.
a Air inlet duct
b Inside of the flange
c Fixing screw
▪ Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.
▪ Installation options:
A Mounting the air inlet with a canvas connection
B Mounting the air inlet panel directly
a Ceiling surface
b Ceiling opening
c Air inlet panel (optional accessory)
d Indoor unit (back side)
e Canvas connection for air inlet panel (optional accessory)
NOTICE
The unit can be used with bottom suction by replacing the
interchangeable plate by the air filter holding plate.
▪ Ceiling opening size. Make sure the ceiling opening is within the
following limits:
a1 Nut (field supply)
a2 Double nut (field supply)
b1 Washer (accessories)
c1 Hanger bracket (attached to the unit)
a Indoor unit
b Pipe
c Hanger bracket pitch (suspension)
d Suspension bolt spacing
INFORMATION
▪ The fan speed of the indoor unit is preset to ensure the
standard external static pressure.
▪ To set a higher or lower external static pressure, reset
the initial setting with the user interface.
▪ Installation example:
a Anchor
b Ceiling slab
c Long nut or turn-buckle
d Suspension bolt
e Indoor unit
▪ Install the unit temporarily.
5 Attach the hanger bracket to the suspension bolt.
6 Fix it securely.
▪ Level. Make sure the unit is level at all four corners using a level
or a water-filled vinyl tube.
▪ Suspension bolts. Use M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely
using a nut and washer from the upper and lower sides of the
hanger bracket.
Installer and user reference guide
12
a Air filter holding plate with air filter(s)
b Interchangeable plate
a Water level
b Vinyl tube
7 Tighten the upper nut.
NOTICE
Do NOT install the unit tilted. Possible consequence: If
the unit is tilted against the direction of the condensate flow
(the drain piping side is raised), the float switch might
malfunction and cause water to drip.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
6 Installation
a bb a
eedd
c
1~1.5 m
a
≤625
≤300
0~75
1000~1500
(mm)
ba
baddc
≥100≤625
(mm)
a
6.2.3Guidelines when installing the ducting
The ducting is to be field supplied.
▪ Air inlet side. Attach the duct and intake-side flange (field
supply). For connecting the flange, use 7 accessory screws.
a Connection screw (accessory)
b Flange (field supply)
c Main unit
d Insulation (field supply)
e Aluminium tape (field supply)
▪ Filter. Be sure to attach an air filter inside the air passage on the
intake side. Use an air filter with dust collecting efficiency ≥50%
(gravimetric method). The included filter is not used when the
intake duct is attached.
▪ Air outlet side. Connect the duct according to the inside
dimension of the outlet-side flange.
▪ Air leaks. Wind aluminium tape around the intake side flange and
duct connection. Make sure there are no air leaks at any other
connection.
▪ Insulation. Insulate the duct to prevent condensation from
forming. Use glass wool or polyethylene foam 25mm thick.
▪ Rising piping. If necessary to make the slope possible, you can
install rising piping.
▪ Drain hose inclination: 0~75 mm to avoid stress on the piping
and to avoid air bubbles.
▪ Rising piping: ≤300 mm from the unit, ≤625 mm perpendicular
to the unit.
a Metal clamp (accessory)
b Drain hose (accessory)
c Rising drain piping (vinyl pipe of 25mm nominal diameter
and 32mm outer diameter) (field supply)
d Hanging bars (field supply)
▪ Combining drain pipes. You can combine drain pipes. Make
sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.
6.2.4Guidelines when installing the drain
piping
Make sure condensation water can be evacuated properly. This
involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪ Drain pump. For this "high lift type", the drainage sounds will be
reduced when the drain pump is installed in a higher location.
Recommended height is 300 mm.
▪ Pipe length. Keep drain piping as short as possible.
▪ Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 25 mm nominal diameter and
32mm outer diameter).
▪ Slope. Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
a T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
1 Push the drain hose as far as possible over the drain pipe
connection.
2 Tighten the metal clamp until the screw head is less than 4mm
from the metal clamp part.
3 Check for water leaks (see To check for water leaks).
4 Install the insulation piece (drain pipe).
5 Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with cable ties.
6 Connect the drain piping to the drain hose.
▪ Condensation. Take measures against condensation. Insulate
the complete drain piping in the building.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
a Hanging bar
O Allowed
X Not allowed
Installer and user reference guide
13
6 Installation
≤4 mm
A
A'
A-A'
A
A'
f
652
ce
4
ba
d
b
a
d
c
3
1
2~61
a
a
b
NL1 2 3
e
i
k
l
m
n
j
j
f
g
h
a
b
c
d
c
e
b
d
a
f
a Drain pipe connection (attached to the unit)
b Drain hose (accessory)
c Metal clamp (accessory)
d Large sealing pad (accessory)
e Insulation piece (drain pipe) (accessory)
f Drain piping (field supply)
NOTICE
▪ Do NOT remove the drain pipe plug. Water might leak
out.
▪ Use the drain outlet only to discharge the water if the
drain pump is not used or before maintenance.
▪ Insert and remove the drain plug gently. Excessive
force may deform the drain socket of the drain pan.
Pull out the plug.
▪ Do NOT wiggle the plug up and down.
Push in the plug.
▪ Set the plug and push it in using a Phillips screwdriver.
a Switch box cover
b Wiring diagram
c Power supply wiring port
d Transmission wiring port
e Indoor PCB 2
f Indoor PCB 3
g Indoor PCB 1
h Switch box
i Plastic clamp
j Power supply wiring
k Power supply terminal board
l Terminal board for unit transmission wiring
m User interface wiring
n Transmission wiring between units
5 Turn ON the power.
6 Start cooling operation (see To perform a test run).
7 Gradually pour approximately 1 l of water through the air
discharge outlet, and check for leaks.
a Drain plug
b Phillips screwdriver
To check for water leaks
The procedure differs depending on whether electrical wiring is
already finished. When electrical wiring is not finished yet, you need
to temporarily connect the user interface and power supply to the
unit.
When electrical wiring is not finished yet
1 Temporarily connect electrical wiring.
2 Remove the switch box cover (a).
3 Connect the single-phase power supply (50 Hz, 230 V) to
connections No. 1 and No. 2 on the terminal block for power
supply and earth.
4 Reattach the switch box cover (a).
Installer and user reference guide
14
a Water inlet
b Portable pump
c Water inlet cover
d Bucket (adding water through water inlet)
e Drain outlet for maintenance
f Refrigerant pipes
8 Turn OFF the power.
9 Disconnect the electrical wiring.
10 Remove the control box cover.
11 Disconnect the power supply and earth.
12 Reattach the control box cover.
When electrical wiring is finished already
1 Start cooling operation (see To perform a test run).
Split system air conditioners
FDA125A5VEB
4P495031-1 – 2017.06
2 Gradually pour approximately 1 l of water through the air
a
b
c
d
R=0.4~0.8
45°
±2
90°
±2
A
discharge outlet, and check for leaks (see When electrical
wiring is not finished yet).
6.3Connecting the refrigerant piping
6 Installation
6.3.1About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
▪ Connecting the refrigerant piping to the outdoor unit
▪ Connecting the refrigerant piping to the indoor unit
▪ Insulating the refrigerant piping
▪ Keeping in mind the guidelines for:
▪ Pipe bending
▪ Flaring pipe ends
▪ Brazing
▪ Using the stop valves
6.3.2Precautions when connecting the
refrigerant piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF BURNING
UnitInstallation periodProtection method
Outdoor unit>1monthPinch the pipe
<1monthPinch or tape the pipe
Indoor unitRegardless of the
period
INFORMATION
Do NOT open the refrigerant stop valve before checking
the refrigerant piping. When you need to charge additional
refrigerant it is recommended to open the refrigerant stop
valve after charging.
6.3.3Guidelines when connecting the
refrigerant piping
Take the following guidelines into account when connecting pipes:
▪ Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tightening firmly.
▪ Always use 2 wrenches together when loosening a flare nut.
▪ Always use a spanner and torque wrench together to tighten the
flare nut when connecting the piping. This to prevent nut cracking
and leaks.
CAUTION
▪ Do NOT use mineral oil on flared part.
▪ NEVER install a drier to this unit to guarantee its
lifetime. The drying material may dissolve and damage
the system.
NOTICE
Take the following precautions on refrigerant piping into
account:
▪ Avoid anything but the designated refrigerant to get
mixed into the refrigerant cycle (e.g. air).
▪ Only use R32 or R410A2 when adding refrigerant.
▪ Only use installation tools (e.g. manifold gauge set) that
are exclusively used for R32 or R410A2 installations to
withstand the pressure and to prevent foreign materials
(e.g. mineral oils and moisture) from mixing into the
system.
▪ Install the piping so that the flare is NOT subjected to
mechanical stress.
▪ Protect the piping as described in the following table to
prevent dirt, liquid or dust from entering the piping.
▪ Use caution when passing copper tubes through walls
(see figure below).
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size
(mm)
Tightening
torque (N•m)
Flare
dimensions (A)
Flare shape
(mm)
(mm)
Ø9.533~3912.8~13.2
Ø15.963~7519.3~19.7
6.3.4Pipe bending guidelines
Use a pipe bender for bending. All pipe bends should be as gentle
as possible (bending radius should be 30~40mm or larger).
(2)
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Refer to the outdoor unit specifications for the type of refrigerant to be used.
Installer and user reference guide
15
6 Installation
ab
A
ab
c
abcde
f
f
AB
adcefbb
adcefbb
2
4
3
g
1
23
4
g
AB
1
6.3.5To flare the pipe end
CAUTION
▪ Incomplete flaring may cause refrigerant gas leakage.
▪ Do NOT re-use flares. Use new flares to prevent
refrigerant gas leakage.
▪ Use flare nuts that are included with the unit. Using
different flare nuts may cause refrigerant gas leakage.
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the
chips do not enter the pipe.
a Cut exactly at right angles.
b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut
on the pipe.
4 Flare the pipe. Set exactly at the position as shown in the
following illustration.
Flare tool for
R410A or R32
(clutch type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A0~0.5mm1.0~1.5mm1.5~2.0mm
5 Check that the flaring is properly made.
a Flare’s inner surface must be flawless.
b The pipe end must be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
6.3.6To braze the pipe end
The indoor unit and outdoor unit have flare connections. Connect
both ends without brazing. If brazing should be needed, take the
following into account:
▪ When brazing, blow through with nitrogen to prevent creation of
large quantities of oxidised film on the inside of the piping. This
film adversely affects valves and compressors in the refrigerating
system and prevents proper operation.
▪ Set the nitrogen pressure to 20kPa (0.2 bar) (just enough so it
can be felt on the skin) with a pressure-reducing valve.
▪ Do NOT use flux when brazing copper-to-copper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP), which
does not require flux.
Flux has an extremely harmful influence on refrigerant piping
systems. For instance, if chlorine based flux is used, it will cause
pipe corrosion or, in particular, if the flux contains fluorine, it will
deteriorate the refrigerant oil.
6.3.7To connect the refrigerant piping to the
indoor unit
WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable.
1
▪ Pipe length. Keep refrigerant piping as short as possible.
▪ Flare connections. Connect refrigerant piping to the unit using
flare connections.
▪ Insulation. Insulate the refrigerant piping on the indoor unit as
follows:
A Gas piping
B Liquid piping
a Insulation material (field supply)
b Cable tie (accessory)
c Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)
d Flare nut (attached to the unit)
e Refrigerant pipe connection (attached to the unit)
f Unit
g Sealing pads: Medium 1 (gas pipe), medium 2 (liquid pipe)
(accessories)
1 Turn up the seams of the insulation pieces.
2 Attach to the base of the unit.
3 Tighten the cable ties on the insulation pieces.
4 Wrap the sealing pad from the base of the unit to the top of
the flare nut.
NOTICE
Make sure to insulate all refrigerant piping. Any exposed
piping might cause condensation.
6.4Connecting the electrical wiring
6.4.1About connecting the electrical wiring
a Refrigerant piping
b Part to be brazed
c Taping
d Manual valve
e Pressure-reducing valve
f Nitrogen
▪ Do NOT use anti-oxidants when brazing pipe joints.
Residue can clog pipes and break equipment.
(1)
Only for appliances using R32 refrigerant. Refer to the outdoor unit specifications for the type of refrigerant to be used.
Installer and user reference guide
16
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1Making sure the power supply system complies with the
electrical specifications of the units.
2Connecting the electrical wiring to the outdoor unit.
3Connecting the electrical wiring to the indoor unit.
4Connecting the main power supply.
Split system air conditioners
FDA125A5VEB
4P495031-1 – 2017.06
6 Installation
ba
c b
c
aa
A
AA´
A´
c bbac
a
B
B
1 2 3
aaa
b
c
1 2 3
P1P
2
P1P
2
d
1 2
L N
3
b
c
b
c
1 2 3
P1P
2
P1P
2
d
L NL N
L N
6.4.2Precautions when connecting the
electrical wiring
INFORMATION
Also read the precautions and requirements in the
following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
6.4.3Guidelines when connecting the electrical
wiring
Keep the following in mind:
▪ If stranded conductor wires are used, install a round crimp-style
terminal on the end of the wire. Place the round crimp-style
terminal on the wire up to the covered part and fasten the terminal
with the appropriate tool.
6.4.4To connect the electrical wiring on the
indoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located on the switch box cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wiring should always be at
least 50mm.
NOTICE
Be sure to keep the power line and transmission line apart
from each other. Transmission wiring and power supply
wiring may cross, but may not run parallel.
1 Remove the service cover.
2 User interface cable: Route the cable through the frame,
connect the cable to the terminal block, and fix the cable with a
cable tie.
3 Interconnection cable (indoor↔outdoor): Route the cable
through the frame, connect the cable to the terminal block
(make sure the numbers match with the numbers on the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.
4 Divide the small sealing (accessory) and wrap it around the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.
a Stranded conductor wire
b Round crimp-style terminal
▪ Use the following methods for installing wires:
Wire typeInstallation method
Single-core wire
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor
wire with round
crimp-style terminal
a Terminal
b Screw
c Flat washer
O Allowed
X Not allowed
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
5 Reattach the service cover.
▪ When using 1 user interface with 1 indoor unit.
▪ When using 2 user interfaces
3
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
(3)
Dashed line represents separate power supply.
Installer and user reference guide
17
7 Configuration
1 2 3
b
c
1 2 3
P
1
P
2
P1P
2
P1P
2
dd
a
L N
b
c
a
L N
b
c
P
1
P
2
d
P1P
2
P
1
P
2
P
1
P
2
a
1 2 3 L N
1 2 3
1 2 3 L N
1 2 3
1 2 3 L N
1 2 3
b
c
a
b
c
a
b
c
a
b
c
a
b
c
a
L N
L N
L N
NL213
L N213
a
▪ When using group control
▪ Otherwise, refer to the table with Ssc values for FDA125A on the
extranet.
▪ If the Ssc value is NOT mentioned in the table for the used
combination, use the common power supply wire delivered with
the unit.
▪ If the Ssc value is mentioned in the table, both the common
power supply wire or a separate power supply can be used, but
a separate power supply is preferred.
a Wire for common power supply (accessory)
3
INFORMATION
In case of group control it is not necessary to assign an
address to the indoor unit. The address is automatically set
when the power is activated.
6.4.5Specifications of standard wiring
components
a Power supply
b Main switch
c Fuse
d User interface
▪ Master unit: Be sure to connect the wiring when combining with a
simultaneously operating multi-type in group control.
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power Ssc is
greater than or equal to the minimum Ssc value at the interface
point between the user's supply and the public system.
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16A and ≤75A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power Ssc greater than or equal to the
minimum Ssc value.
To comply with EN/IEC 61000‑3‑12, following rules must be
considered:
▪ In case of combination of units 2x FDA125A + RZQ250, use
separate power supplies.
Installer and user reference guide
18
(3)
Dashed line represents separate power supply.
ComponentFDA125A
Power supply
cable
(a)
MCA
2.1 A
Voltage220~240V
Phase1~
Frequency50/60Hz
Wire sizesMust comply with applicable
legislation
Interconnection cableMinimum cable section of 2.5mm²
and applicable for 220~240V
User interface cableVinyl cord with 0.75 to 1.25mm
sheath or cables (2 core wires)
Maximum 500m
Recommended field fuse16A
Earth leakage circuit breakerMust comply with applicable
legislation
(a) MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).
7Configuration
7.1Field settings
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
▪ External static pressure setting using:
▪ Airflow automatic adjustment setting
▪ User interface
▪ Time to clean air filter
To set airflow automatic adjustment
▪ When the air conditioning unit is running in fan operation mode:
1 Stop the air conditioning unit.
2 Set second code number to 03.
Split system air conditioners
FDA125A5VEB
4P495031-1 – 2017.06
2
8 Commissioning
Setting content:Then
MC1C2
Airflow adjustment is OFF11(21)701
Press ON/OFF to return to normal operating
mode.
Possible consequence: The operation lamp
will light up and the unit will start the fan
operation for airflow automatic adjustment.
Operation stops after 1 to 8 minutes.
Possible consequence: Setting is finished
and the operation lamp will be off.
If there is no change after airflow adjustment, perform the setting
again.
User interface
Check the indoor unit setting: the second code number of mode
11(21) must be set to 01.
Change the second code number according to the external static
pressure of the duct to be connected as in table below.
This chapter describes what you have to do and know to
commission the system after it is installed.
Typical workflow
Commissioning typically consists of the following stages:
1Checking the "Checklist before commissioning".
2Performing a test run for the system.
8.2Checklist before commissioning
Do NOT operate the system before the following checks are OK:
You read the complete installation instructions, as
described in the installer reference guide.
The indoor units are properly mounted.
In case a wireless user interface is used: The indoor unitdecoration panel with infrared receiver is installed.
The outdoor unit is properly mounted.
There are NO missing phases or reversed phases.
The system is properly earthed and the earth terminals
are tightened.
The fuses or locally installed protection devices are
installed according to this document, and have not been
bypassed.
The power supply voltage matches the voltage on the
identification label of the unit.
There are NO loose connections or damaged electrical
components in the switchbox.
The insulation resistance of the compressor is OK.
There are NO damaged components or squeezedpipes on the inside of the indoor and outdoor units.
There are NO refrigerant leaks.
Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which the TIME TO CLEAN AIR FILTER
notification is displayed on the user interface. When using a wireless
user interface, you must also set the address (see the installation
manual of the user interface).
If you want an interval of…
(air contamination)
±2500h (light)10(20)001
±1250h (heavy)02
No notification302
▪ 2 user interfaces: When using 2 user interfaces, one must be set
to "MAIN" and the other to "SUB".
(4)
Field settings are defined as follows:
▪ M: Mode number – First number: for group of units – Number between brackets: for individual unit
▪ C1: First code number
▪ C2: Second code number
▪: Default
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
MC1C2
Then
4
The correct pipe size is installed and the pipes are
properly insulated.
The stop valves (gas and liquid) on the outdoor unit are
fully open.
8.3To perform a test run
This task is only applicable when using the BRC1E52 or BRC1E53
user interface. When using any other user interface, see the
installation manual or service manual of the user interface.
NOTICE
Do not interrupt the test run.
Installer and user reference guide
19
9 Hand-over to the user
AB
Cool
Set to
28°C
ReturnSetting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Cool
ReturnSetting
Test Operation
ReturnSetting
Service Settings 1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
INFORMATION
Backlight. To perform an ON/OFF action on the user
interface, the backlight does not need to be lit. For any
other action, it needs to be lit first. The backlight is lit for
±30seconds when you press a button.
1 Perform introductory steps.
#Action
1Open the liquid stop valve (A) and gas stop valve (B)
by removing the stem cap and turning
counterclockwise with a hex wrench until it stops.
2Close the service cover to prevent electric shocks.
3Turn ON power for at least 6hours before starting
operation to protect the compressor.
4On the user interface, set the unit to cooling operation
mode.
2 Start the test run
#ActionResult
1Go to the home menu.
2Press at least 4seconds.The Service Settings menu
is displayed.
3Select Test Operation.
4Press.Test Operation is
displayed on the home
menu.
#ActionResult
2Select Test Operation.
3Press.The unit returns to normal
operation, and the home
menu is displayed.
8.4Error codes when performing a
test run
If the installation of the outdoor unit has NOT been done correctly,
the following error codes may be displayed on the user interface:
Error codePossible cause
Nothing displayed
(the currently set
temperature is not
displayed)
E3, E4 or L8▪ The stop valves are closed.
E7There is a missing phase in case of three-
L4The air inlet or air outlet is blocked.
U0The stop valves are closed.
U2▪ There is a voltage imbalance.
U4 or UFThe inter-unit branch wiring is not correct.
UAThe outdoor and indoor unit are
▪ The wiring is disconnected or there is a
wiring error (between power supply and
outdoor unit, between outdoor unit and
indoor units, between indoor unit and
user interface).
▪ The fuse on the outdoor or indoor unit
PCB has blown.
▪ The air inlet or air outlet is blocked.
phase power supply units.
Note: Operation will be impossible. Turn
OFF the power, recheck the wiring, and
switch two of the three electrical wires.
▪ There is a missing phase in case of
three-phase power supply units. Note:
Operation will be impossible. Turn OFF
the power, recheck the wiring, and switch
two of the three electrical wires.
incompatible.
5Press within 10seconds.Test run starts.
3 Check operation for 3minutes.
4 Stop the test run.
#ActionResult
1Press at least 4seconds.The Service Settings menu
Installer and user reference guide
20
9Hand-over to the user
Once the test run is finished and the unit operates properly, please
make sure the following is clear for the user:
▪ Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can
find the complete documentation on the url as earlier described in
this manual.
▪ Explain the user how to properly operate the system and what to
do in case of problems.
▪ Show the user what to do in relation to maintaining the unit.
is displayed.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
10Disposal
NOTICE
Do not try to dismantle the system yourself: the dismantling
of the system, treatment of the refrigerant, oil and other
parts must comply with applicable legislation. Units must
be treated at a specialised treatment facility for reuse,
recycling and recovery.
11Technical data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
10 Disposal
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
21
11 Technical data
Unified Wiring Diagram Legend
For applied parts and numbering refer to the wiring diagram sticker supplied on the unit. Part numbering is realized by Arabic numbers in ascending order for each part and
is represented in the overview below by symbol “*” in the part code.
:CIRCUIT BREAKER: PROTECTIVE EARTH
:CONNECTION: PROTECTIVE EARTH (SCREW)
,
:CONNECTOR
A
: RECTIFIER
:EARTH: RELAY CONNECTOR
:FIELD WIRING: SHORT CIRCUIT CONNECTOR
:FUSE: TERMINAL
INDOOR
:INDOOR UNIT: TERMINAL STRIP
OUTDOOR
:OUTDOOR UNIT: WIRE CLAMP
BLK : BLACKGRN : GREENPNK: PINKWHT : WHITE
BLU : BLUEGRY : GREYPRP, PPL : PURPLEYLW : YELLOW
BRN : BROWNORG : ORANGERED: RED
A*P:PRINTED CIRCUIT BOARDPS: SWITCHING POWER SUPPLY
BS*:PUSH BUTTON ON / OFF, OPERATION SWITCHPTC*: THERMISTOR PTC
This appliance is intended to be used by expert or trained
users in shops, in light industry, and on farms, or for
commercial and household use by lay persons.
INFORMATION
The sound pressure level is less than 70dBA.
WARNING: FLAMMABLE MATERIAL
The R32 refrigerant (if applicable) in this unit is mildly
flammable.
WARNING
▪ Do not modify, disassemble, remove, reinstall or repair
▪ In case of accidental refrigerant leaks, make sure there
WARNING
Ask your dealer to install and reinstall the air conditioner.
Incomplete installation may result in a water leakage,
electric shock, and fire.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
12.1Components
INFORMATION
The following illustration is an example and might NOT
match your system layout.
1
the unit yourself as incorrect dismantling or installation
may cause an electric shock or fire. Contact your
dealer.
are no naked flames. The refrigerant itself is entirely
safe and non-toxic. R410A is a non-combustible
refrigerant, and R32 is a mildly flammable refrigerant,
but they will generate a toxic gas when they
accidentally leak into a room where combustible air
from fan heaters, gas cookers, etc. is present. Always
have qualified service personnel confirm that the point
of leakage has been repaired or corrected before
resuming operation.
12 About the system
a Indoor unit
b Outdoor unit
c User interface
d Air inlet
e Air outlet
f Refrigerant piping and electric wiring
g Drain pipe
h Earth wire to ground outdoor unit to prevent electric
shocks.
CAUTION
Do not insert fingers, rods or other objects into the air inlet
or outlet. Do not remove the fan guard. When the fan is
rotating at high speed, it will cause injury.
CAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen.
For checking and adjusting the internal parts, contact your
dealer.
NOTICE
Do not wipe the controller operation panel with benzine,
thinner, chemical dust cloth, etc. The panel may get
discoloured or the coating peeled off. If it is heavily dirty,
soak a cloth in water-diluted neutral detergent, squeeze it
well and wipe the panel clean. Wipe it with another dry
cloth.
NOTICE
Never press the button of the user interface with a hard,
pointed object. The user interface may be damaged.
NOTICE
Never pull or twist the electric wire of the user interface. It
may cause the unit to malfunction.
12.2Information requirements for fan
coil units
(1)
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Only for appliances using R32 refrigerant. Refer to the outdoor unit specifications for the type of refrigerant to be used.
ItemSymbolValueUnit
Cooling capacity (sensible)P
Cooling capacity (latent)P
Heating capacityP
Total electric power inputP
rated,c
rated,c
rated,h
elec
AkW
BkW
CkW
DkW
Installer and user reference guide
23
13 User interface
ItemSymbolValueUnit
Sound power level (per speed
setting, if applicable)
Contact details:
DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o. U Nové Hospody
1/1155, 301 00 Plzeň Skvrňany, Czech Republic
ABCDE
FDA125A7.834.2713.500.3566
L
WA
EdB
13User interface
CAUTION
Never touch the internal parts of the controller.
Do not remove the front panel. Some parts inside are
dangerous to touch and appliance problems may happen.
For checking and adjusting the internal parts, contact your
dealer.
This operation manual will give a non-exhaustive overview of the
main functions of the system.
For more information about the user interface, see the operation
manual of the installed user interface.
WARNING
Never use a flammable spray such as hair spray, lacquer
or paint near the unit. It may cause a fire.
CAUTION
It is not good for your health to expose your body to the air
flow for a long time.
CAUTION
To avoid oxygen deficiency, ventilate the room sufficiently
if equipment with burner is used together with the system.
CAUTION
Do not operate the system when using a room fumigationtype insecticide. This could cause the chemicals to
become deposited in the unit, which could endanger the
health of those who are hypersensitive to chemicals.
NOTICE
Do not place the user interface in a place exposed to direct
sunlight. The LCD display may get discoloured or fail to
display the data.
NOTICE
Do not place items which might be damaged by moisture
under the indoor unit. Condensation may form if the
humidity is above 80%, if the drain outlet is blocked or the
filter is polluted.
14Before operation
WARNING
Ask your dealer for improvement, repair, and maintenance.
Incomplete improvement, repair, and maintenance may
result in water leakage, electric shock and fire.
WARNING
Ask your dealer to move and reinstall the air conditioner.
Incomplete installation may result in a water leakage,
electric shock, and fire.
WARNING
Never let the indoor unit or the user interface get wet. It
may cause an electric shock or a fire.
WARNING
Do not place objects in direct proximity of the outdoor unit
and do not let leaves and other debris accumulate around
the unit. Leaves are a hotbed for small animals which can
enter the unit. Once in the unit, such animals can cause
malfunctions, smoke or fire when making contact with
electrical parts.
WARNING
Avoid placing the user interface in a place where it can be
splashed with water. Water entering the machine may
cause an electric leak or may damage the internal
electronic parts.
WARNING
This unit contains electrical and hot parts.
WARNING
Before operating the unit, be sure the installation has been
carried out correctly by an installer.
NOTICE
Arrange the drain hose to ensure smooth drainage.
Incomplete drainage may cause the building, furniture, etc.
to get wet.
This operation manual is for the following systems with standard
control. Before initiating operation, contact your dealer for the
operation that corresponds to your system type and mark. If your
installation has a customised control system, ask your dealer for the
operation that corresponds to your system.
15Operation
15.1Operation range
For combination with R410A outdoor unit, refer to the following table:
Outdoor unitsCoolingHeating
RR125Outdoor
temperature
Indoor
temperature
RQ125Outdoor
temperature
Indoor
temperature
RZQG125Outdoor
temperature
Indoor
temperature
RZQSG125Outdoor
temperature
Indoor
temperature
–15~46°CDB—
18~37°CDB
12~28°CWB
–5~46°CDB–9~21°CDB
18~37°CDB
12~28°CWB
–15~50°CDB–19~21°CDB
18~37°CDB
12~28°CWB
–15~46°CDB–14~21°CDB
20~37°CDB
14~28°CWB
—
–10~15°CWB
10~27°CDB
–20~15.5°CWB
10~27°CDB
–15~15.5°CWB
10~27°CDB
Installer and user reference guide
24
Split system air conditioners
FDA125A5VEB
4P495031-1 – 2017.06
16 Energy saving and optimum operation
Outdoor unitsCoolingHeating
RZQ250Outdoor
temperature
Indoor
temperature
Indoor humidity≤80%
For combination with R32 outdoor unit, refer to the following table:
Outdoor unitsCoolingHeating
RZAG125Outdoor
temperature
Indoor
temperature
RZASG125Outdoor
temperature
Indoor
temperature
Indoor humidity≤80%
(a) To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
–5~46°CDB–14~21°CDB
–15~15°CWB
20~37°CDB
14~28°CWB
–20~52°CDB–19.5~21°CDB
18~37°CDB
12~28°CWB
–15~46°CDB–14~21°CDB
20~37°CDB
14~28°CWB
10~27°CDB
(a)
–20~15.5°CWB
10~27°CDB
–15~15.5°CWB
10~27°CDB
(a)
15.2Operation procedure
▪ Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the user interface display appears.
▪ If there was a power failure during operation, the system
automatically restarts immediately after the power supply is
recovered.
▪ The setting temperature range of the user interface is described in
chapter "Operation range".
▪ If you select a function which is not available, the message NOT
AVAILABLE appears on the user interface.
▪ Read the documentation carefully before operating the user
interface to ensure the best possible performance.
CAUTION
Do not operate the system when using a room fumigationtype insecticide. This could cause the chemicals to
become deposited in the unit, which could endanger the
health of those who are hypersensitive to chemicals.
WARNING
Do not place a flammable spray bottle near the air
conditioner and do not use sprays. Doing so may result in
a fire.
Observe the following precautions to ensure the system operates
properly.
▪ Prevent direct sunlight from entering a room during cooling
operation by using curtains or blinds.
▪ Ventilate often. Extended use requires special attention to
ventilation.
▪ Keep doors and windows closed. If the doors and windows remain
open, air will flow out of your room causing a decrease in the
cooling or heating effect.
▪ Be careful not to cool or heat too much. To save energy, keep the
temperature setting at a moderate level.
▪ Never place objects near the air inlet or the air outlet of the unit. It
may cause deterioration in the effect or stop the operation.
▪ Turn off the main power supply switch to the unit when the unit is
not used for longer periods of time. If the switch is on, it consumes
electricity. Before restarting the unit, turn on the main power
supply switch 6 hours before operation to ensure smooth running.
▪ When the display shows (time to clean the air filter), clean the
filters (see "17.2.2To clean the air filter"on page26).
▪ Condensation may form if the humidity is above 80% or if the
drain outlet gets blocked.
▪ Adjust the room temperature properly for a comfortable
environment. Avoid excessive heating or cooling. Notice that it
may take some time for the room temperature to reach the set
temperature. Consider using the timer setting options.
▪ Adjust the air flow direction to avoid cool air from gathering on the
floor or warm air against the ceiling. (Up during cooling or dry
operation to the ceiling and down during heating operation.)
▪ Avoid direct air flow to room inhabitants.
16Energy saving and optimum
operation
CAUTION
Never expose little children, plants or animals directly to
the air flow.
WARNING
Do NOT place objects below the indoor and/or outdoor unit
that may get wet. In this condition, condensation on the
main unit or refrigerant pipes, air filter dirt or drain blockage
may cause dripping. This results in fouling or failure of the
object which is located beneath the unit.
NOTICE
Do not use the system for other purposes. In order to avoid
any quality deterioration, do not use the unit for cooling
precision instruments, food, plants, animals or works of art.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
17Maintenance and service
17.1Overview: Maintenance and
service
The installer has to perform a yearly maintenance.
About the refrigerant
This product contains fluorinated greenhouse gases. Do NOT vent
gases into the atmosphere.
Refrigerant type: R32
Global warming potential (GWP) value: 675
Refrigerant type: R410A
Global warming potential (GWP) value: 2087.5
Installer and user reference guide
25
17 Maintenance and service
NOTICE
In Europe, the greenhouse gas emissions of the total
refrigerant charge in the system (expressed as tonnes
CO2-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
Please contact your installer for more information.
WARNING
R410A is a non-combustible refrigerant, and R32 is a
mildly flammable refrigerant; they normally don’t leak. If the
refrigerant leaks in the room and comes in contact with fire
from a burner, a heater, or a cooker, this may result in a
fire (in case of R32), or the formation of a harmful gas.
Turn off any combustible heating devices, ventilate the
room, and contact the dealer from where you purchased
the unit.
Do not use the unit until a service person confirms that the
part from which the refrigerant leaked has been repaired.
WARNING
▪ Do NOT pierce or burn refrigerant cycle parts.
▪ Do NOT use cleaning materials or means to accelerate
the defrosting process other than those recommended
by the manufacturer.
▪ Be aware that the refrigerant inside the system is
odourless.
NOTICE
Maintenance must be done by an authorised installer or
service agent.
We recommend to do maintenance at least once a year.
However, applicable legislation might require shorter
maintenance intervals.
CAUTION
Before accessing terminal devices, make sure to interrupt
all power supply.
DANGER: RISK OF ELECTROCUTION
To clean the air conditioner or air filter, be sure to stop
operation and turn all power supplies off. Otherwise, an
electric shock and injury may result.
WARNING
To prevent electric shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
NOTICE
When cleaning the heat exchanger, make sure to remove
the switch box and fan motor. Water or detergent might
deteriorate the insulation of electronic components and
result in burnout of these components.
WARNING
Be carefull with ladders when working in high places.
17.2Cleaning the air filter, suction
grille, air outlet and outside panels
17.2.1To clean the air outlet and outside panels
WARNING
Do NOT let the indoor unit get wet. Possible
consequence: Electric shock or fire.
NOTICE
▪ Do NOT use gasoline, benzene, thinner polishing
powder or liquid insecticide. Possible consequence:
Discoloration and deformation.
▪ Do NOT use water or air of 50°C or higher. Possible
consequence: Discoloration and deformation.
▪ Do NOT scrub firmly when washing the blade with
water. Possible consequence: The surface sealing
peels off.
Clean with a soft cloth. If it is difficult to remove stains, use water or
neutral detergent.
17.2.2To clean the air filter
When to clean the air filter:
▪ Rule of thumb: Clean every 6 months. If the air in the room is
extremely contaminated, increase the cleaning frequency.
▪ Depending on the settings, the user interface can display the
TIME TO CLEAN AIR FILTER notification. Clean the air filter
when the notification is displayed.
▪ If the dirt becomes impossible to clean, change the air filter
(=optional equipment).
How to clean the air filter:
1 Remove the air filters by pulling their cloth upward (in case of
rear suction) or backward (in case of bottom suction).
rear suctionbottom suction
CAUTION
After a long use, check the unit stand and fitting for
damage. If damaged, the unit may fall and result in injury.
CAUTION
Do not touch the heat exchanger fins. These fins are sharp
and could result in cutting injuries.
Installer and user reference guide
26
2 Clean the air filter. Use a vacuum cleaner or wash with water. If
the air filter is very dirty, use a soft brush and neutral detergent.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
3 Dry the air filter in the shadow.
4 Reattach the air filter. Align the 2 hanger brackets and push the
2 clips in their place and pull the cloth if necessary.
rear suctionbottom suction
5 Confirm that 4 hangers are fixed.
6 In case of bottom suction, close the air inlet grille.
7 Turn ON the power.
8 Press the FILTER SIGN RESET button.
Result: The TIME TO CLEAN AIR FILTER notification disappears
from the user interface.
17.3Maintenance before a long stop
period
E.g., at the end of the season.
▪ Let the indoor units run in fan only operation for about half a day in
order to dry the interior of the units.
▪ Turn off the power. The user interface display disappears. When
the main power is turned on, the air conditioner will use some
power, even if it is not operating.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
▪ Remove the batteries from the user interface.
17.4Maintenance after a long stop
period
E.g., at the beginning of the season.
▪ Check and remove everything that might be blocking inlet and
outlet vents of indoor units and outdoor units.
▪ Check if the earth is connected properly.
▪ Check if there is somewhere a broken wire. Contact your dealer in
case of problems.
▪ Clean air filters and casings of indoor units. Contact your installer
or maintenance person to clean air filters and casings of the
indoor unit. Maintenance tips and procedures for cleaning are
provided in the installation/operation manuals of dedicated indoor
units. Make sure to install cleaned air filters back in the same
position.
18 Troubleshooting
▪ Turn on the power at least 6 hours before operating the unit in
order to ensure smoother operation. As soon as the power is
turned on, the user interface display appears.
18Troubleshooting
If one of the following malfunctions occur, take the measures shown
below and contact your dealer.
WARNING
Stop operation and shut off the power if anything
unusual occurs (burning smells etc.).
Leaving the unit running under such circumstances may
cause breakage, electric shock or fire. Contact your dealer.
The system must be repaired by a qualified service person:
MalfunctionMeasure
If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does not properly work.
If water leaks from the unit.Stop the operation.
The operation switch does not work
well.
If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.
If the system does not properly operate except for the above
mentioned cases and none of the above mentioned malfunctions is
evident, investigate the system according to the following
procedures.
MalfunctionMeasure
If the system does not
operate at all.
The system stops
immediately after
starting operation.
▪ Check if there is no power failure. Wait
until power is restored. If a power failure
occurs during operation, the system
automatically restarts immediately after
power is restored.
▪ Check if no fuse has blown or breaker is
activated. Change the fuse or reset the
breaker if necessary.
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacles and make sure
the air can flow freely.
▪ Check if the air filter is clogged. Contact
your dealer to clean the air filter.
Turn off the main power
switch.
Turn off the power.
Notify your installer and
report the malfunction
code.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
27
18 Troubleshooting
MalfunctionMeasure
The system operates
but cooling or heating
is insufficient.
If after checking all above items, it is impossible to fix the problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacles and make sure
the air can flow freely.
▪ Check if the air filter is clogged. Contact
your dealer to clean the air filter (refer to
"Maintenance" in the indoor unit manual).
▪ Check the temperature setting. Refer to
the manual of the user interface.
▪ Check if the fan speed setting is set to
low speed. Refer to the manual of the
user interface.
▪ Check if the air flow angle is proper.
Refer to the manual of the user interface.
▪ Check for open doors or windows. Close
doors and windows to prevent wind from
coming in.
▪ Check if direct sunlight enters the room.
Use curtains or blinds.
▪ Check if there are too many occupants in
the room during cooling operation. Check
if the heat source of the room is
excessive.
▪ If the heat source of the room is
excessive (when cooling). Cooling effect
decreases if heat gain of the room is too
large.
▪ Check if the air filter is clogged. Contact
your dealer to clean the air filter (refer to
"Maintenance" in the indoor unit manual).
▪ Check if air inlet or outlet of outdoor or
indoor unit is not blocked by obstacles.
Remove any obstacles, turn the breaker
OFF and back ON. If the lamp still blinks,
contact your dealer.
▪ Check if all indoor units connected to
outdoor unit in the multi-system are
operating in the same mode.
▪ The air conditioner may malfunction
because of lightning or radio waves. Turn
the breaker OFF and back ON.
18.1Symptoms that are NOT system
malfunctions
The following symptoms are NOT system malfunctions:
18.1.1Symptom: The system does not operate
▪ The air conditioner does not start immediately after the ON/OFF
button on the user interface is pressed. If the operation lamp
lights, the air conditioner is in normal condition. It does not restart
immediately because one of its safety devices actuates to prevent
the air conditioner from being overloaded. The air conditioner will
turn on again automatically after 3minutes.
▪ The air conditioner does not start immediately after the power
supply is turned on. Wait 1 minute until the microcomputer is
prepared for operation.
▪ The air conditioner does not restart immediately when the
temperature setting button is returned to its former position after
pushing. It does not restart immediately because one of its safety
devices actuates to prevent the air conditioner from being
overloaded. The air conditioner will turn on again automatically
after 3minutes.
▪ The outdoor unit has stopped. This is because the room
temperature has reached the set temperature. The unit switches
to fan operation. "" (external control icon) is displayed on
the user interface and the actual operation is different from the
user interface setting. For multi-split models, the microcomputer
executes the following control depending on the operation mode
of other indoor units.
▪ The fan speed is different from the setting. Pressing the fan speed
control button does not change the fan speed. When the room
temperature reaches the set temperature in heating mode or the
unit’s maximum capacity is reached, the outdoor unit will stop
operation and the indoor unit will operate in fan only mode (low
fan speed). In case of multi-split, the indoor unit alternately
operates in fan stop mode and fan only mode (LL= low fan
speed). This is to prevent the cool air from being blown directly
onto anyone present in the room.
18.1.2Symptom: Air blow direction is not as
specified
Actual air blow direction is not as shown on the user interface.
Automatic swing setting does not work.
Refer to the manual of the user interface.
18.1.3Symptom: White mist comes out of a unit
(Indoor unit)
▪ When humidity is high during cooling operation (in oily and dusty
places). If the interior of an indoor unit is extremely contaminated,
the temperature distribution inside a room becomes uneven. It is
necessary to clean the interior of the indoor unit. Ask your dealer
for details on cleaning the unit. This operation requires a qualified
service person.
▪ When the air conditioner is changed over to heating operation
after defrost operation. Moisture generated by defrost becomes
steam and exits.
18.1.4Symptom: Noise of air conditioners
(indoor unit)
▪ A "ringing" sound is heard after the unit is started. This sound is
generated by the temperature regulator working. It will quiet down
after about a minute.
▪ A continuous low "hissing" sound is heard when the system is in
cooling or defrost operation. This is the sound of refrigerant gas
flowing through both indoor and outdoor units.
▪ A hissing sound which is heard at the start or immediately after
stopping operation or defrost operation. This is the noise of
refrigerant caused by flow stop or flow change.
▪ A "squeaking" sound is heard when the system is in operation or
after the stop of operation. Expansion and contraction of plastic
parts caused by temperature change makes this noise.
18.1.5Symptom: Dust comes out of the unit
When the unit is used for the first time in a long time. This is
because dust has gotten into the unit.
18.1.6Symptom: The units can give off odours
The unit can absorb the smell of rooms, furniture, cigarettes, etc.,
and then emit it again.
Installer and user reference guide
28
Split system air conditioners
FDA125A5VEB
4P495031-1 – 2017.06
19 Relocation
18.1.7Symptom: The display shows "88"
This is the case immediately after the main power supply switch is
turned on and means that the user interface is in normal condition.
This continues for 1minute.
18.1.8Symptom: The operation stopped
suddenly (Operation lamp is on)
The air conditioner may stop for system protection due to large
voltage fluctuation. It automatically resumes operation after about 3
minutes.
18.1.9Symptom: The outdoor fan rotates while
the air conditioner is not in operation
▪ After operation has stopped. The outdoor fan continues to
rotate for another 30 seconds for system protection.
▪ While the air conditioner is not in operation. When the outdoor
temperature is very high, the outdoor fan starts to rotate for
system protection.
18.1.10 Symptom: The heating operation stops
suddenly and a flowing sound is heard
The system is removing frost on the outdoor unit. You should wait for
about 3 to 8minutes.
Operation manual
Instruction manual specified for a certain product or
application, explaining how to operate it.
Maintenance instructions
Instruction manual specified for a certain product or
application, which explains (if relevant) how to install,
configure, operate and/or maintain the product or
application.
Accessories
Labels, manuals, information sheets and equipment that are
delivered with the product and that need to be installed
according to the instructions in the accompanying
documentation.
Optional equipment
Equipment made or approved by Daikin that can be
combined with the product according to the instructions in
the accompanying documentation.
Field supply
Equipment not made by Daikin that can be combined with
the product according to the instructions in the
accompanying documentation.
19Relocation
Contact your dealer for removing and reinstalling the total unit.
Moving units requires technical expertise.
20Disposal
NOTICE
Do not try to dismantle the system yourself: the dismantling
of the system, treatment of the refrigerant, oil and other
parts must comply with applicable legislation. Units must
be treated at a specialised treatment facility for reuse,
recycling and recovery.
21Glossary
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to install the
product.
User
Person who is owner of the product and/or operates the
product.
Applicable legislation
All international, European, national and local directives,
laws, regulations and/or codes that are relevant and
applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the
required service to the product.
Installation manual
Instruction manual specified for a certain product or
application, explaining how to install, configure and maintain
it.
FDA125A5VEB
Split system air conditioners
4P495031-1 – 2017.06
Installer and user reference guide
29
4P495031-1 2017.06
Copyright 2017 Daikin
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.