Daikin FCAHG71FVEB, FCAHG100FVEB, FCAHG125FVEB, FCAHG140FVEB Installer reference guide

Installer and user
reference guide
Split system air conditioners
FCAHG71FVEB FCAHG100FVEB FCAHG125FVEB FCAHG140FVEB
Installer and user reference guide
Split system air conditioners
English

Table of Contents

Table of Contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the user ............................................................................... 3
1.3 For the installer.......................................................................... 3
1.3.1 General ....................................................................... 3
1.3.2 Installation site ............................................................ 4
1.3.3 Refrigerant .................................................................. 4
1.3.4 Brine............................................................................ 5
1.3.5 Water .......................................................................... 5
1.3.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
For the installer 6
3 About the box 6
3.1 Overview: About the box ........................................................... 6
3.2 Indoor unit ................................................................................. 6
3.2.1 To unpack and handle the unit.................................... 6
3.2.2 To remove the accessories from the indoor unit......... 7
4 About the units and options 7
4.1 Overview: About the units and options...................................... 7
4.2 Identification .............................................................................. 7
4.2.1 Identification label: Indoor unit .................................... 7
4.3 About the indoor unit ................................................................. 7
4.4 System layout............................................................................ 8
4.5 Combining units and options ..................................................... 8
4.5.1 Possible options for the indoor unit............................. 8
4.5.2 Possible combinations of indoor unit and outdoor
unit .............................................................................. 8
5 Preparation 8
5.1 Overview: Preparation............................................................... 8
5.2 Preparing installation site .......................................................... 8
5.2.1 Installation site requirements of the indoor unit .......... 8
5.3 Preparing refrigerant piping....................................................... 9
5.3.1 Refrigerant piping requirements.................................. 9
5.3.2 Refrigerant piping insulation ....................................... 9
5.4 Preparing electrical wiring ......................................................... 10
5.4.1 About preparing electrical wiring................................. 10
6 Installation 10
6.1 Overview: Installation ................................................................ 10
6.2 Mounting the indoor unit............................................................ 10
6.2.1 Precautions when mounting the indoor unit................ 10
6.2.2 Guidelines when installing the indoor unit................... 10
6.2.3 Guidelines when installing the drain piping................. 11
6.3 Connecting the refrigerant piping .............................................. 13
6.3.1 About connecting the refrigerant piping ...................... 13
6.3.2 Precautions when connecting the refrigerant piping... 13
6.3.3 Guidelines when connecting the refrigerant piping..... 13
6.3.4 Pipe bending guidelines.............................................. 14
6.3.5 To flare the pipe end................................................... 14
6.3.6 To braze the pipe end................................................. 14
6.3.7 To connect the refrigerant piping to the indoor unit .... 14
6.4 Connecting the electrical wiring................................................. 15
6.4.1 About connecting the electrical wiring......................... 15
6.4.2 Precautions when connecting the electrical wiring ..... 15
6.4.3 Guidelines when connecting the electrical wiring ....... 15
6.4.4 Specifications of standard wiring components............ 15
6.4.5 To connect the electrical wiring on the indoor unit...... 15
7 Configuration 16
7.1 Field settings .............................................................................. 16
8 Commissioning 17
8.1 Overview: Commissioning.......................................................... 17
8.2 Precautions when commissioning .............................................. 17
8.3 Checklist before commissioning................................................. 17
8.4 To perform a test run.................................................................. 18
8.5 Error codes when performing a test run ..................................... 18
9 Hand-over to the user 19
10 Disposal 19
11 Technical data 20
11.1 Overview: Technical data ........................................................... 20
11.2 Dimensions: Indoor unit.............................................................. 20
11.3 Service space: Indoor unit .......................................................... 21
11.4 Components: Indoor unit ............................................................ 21
11.5 Piping diagram: Indoor unit ........................................................ 21
11.6 Wiring diagram: Indoor unit ........................................................ 22
11.7 Technical specifications: Indoor unit .......................................... 24
For the user 25
12 About the system 25
12.1 System layout ............................................................................. 25
13 User interface 25
14 Before operation 25
15 Operation 25
15.1 Operation range ......................................................................... 25
15.2 Operating the system ................................................................. 25
15.2.1 About operating the system ......................................... 25
15.2.2 About cooling, heating, fan only, and automatic
operation ...................................................................... 26
15.2.3 About the heating operation ......................................... 26
15.2.4 To operate the system ................................................. 26
15.3 Using the dry program ................................................................ 26
15.3.1 About the dry program ................................................. 26
15.3.2 To use the dry program................................................ 26
15.4 Adjusting the air flow direction.................................................... 26
15.4.1 About the air flow flap .................................................. 26
16 Energy saving and optimum operation 27
17 Maintenance and service 27
17.1 Cleaning the air filter, suction grille, air outlet and outside
panels ........................................................................................ 27
17.1.1 To clean the air filter .................................................... 27
17.1.2 To clean the suction grille ............................................ 28
17.1.3 To clean the air outlet and outside panels ................... 28
17.2 Maintenance after a long stop period ......................................... 28
17.3 Maintenance before a long stop period ...................................... 28
17.4 About the refrigerant................................................................... 28
17.5 After-sales service and warranty ................................................ 29
17.5.1 Warranty period ........................................................... 29
17.5.2 Recommended maintenance and inspection ............... 29
17.5.3 Recommended maintenance and inspection cycles .... 29
17.5.4 Shortened maintenance and replacement cycles ........ 29
18 Troubleshooting 30
18.1 Symptoms that are not air conditioner troubles .......................... 30
18.1.1 Symptom: The system does not operate ..................... 30
18.1.2 Symptom: The fan strength does not correspond to
the setting .................................................................... 30
18.1.3 Symptom: The fan direction does not correspond to
the setting .................................................................... 30
18.1.4 Symptom: White mist comes out of a unit (Indoor
unit) .............................................................................. 31
Installer and user reference guide
2
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12

1 General safety precautions

18.1.5 Symptom: White mist comes out of a unit (Indoor
unit, outdoor unit) ........................................................ 31
18.1.6 Symptom: The user interface display reads "U4" or "U5" and stops, but then restarts after a few minutes. 31
18.1.7 Symptom: Noise of air conditioners (Indoor unit) ........ 31
18.1.8 Symptom: Noise of air conditioners (Indoor unit,
outdoor unit)................................................................ 31
18.1.9 Symptom: Noise of air conditioners (Outdoor unit) ..... 31
18.1.10 Symptom: Dust comes out of the unit ......................... 31
18.1.11 Symptom: The units can give off odours..................... 31
18.1.12 Symptom: The outdoor unit fan does not spin ............ 31
18.1.13 Symptom: The display shows "88".............................. 31
18.1.14 Symptom: The compressor in the outdoor unit does
not stop after a short heating operation ...................... 31
19 Relocation 31
20 Disposal 31
21 Glossary 31
1 General safety precautions

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be performed by an authorized installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
WARNING: FLAMMABLE MATERIAL
▪ This appliance can be used by children aged from 8 years and
above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
WARNING
To prevent electric shocks or fire:
▪ Do NOT rinse the unit.
▪ Do NOT operate the unit with wet hands.
▪ Do NOT place any objects containing water on the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
▪ Units are marked with the following symbol:
This means that electrical and electronic products may not be mixed with unsorted household waste. Do NOT try to dismantle the system yourself: the dismantling of the system, treatment of the refrigerant, of oil and of other parts must be done by an authorized installer and must comply with applicable legislation. Units must be treated at a specialized treatment facility for reuse, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. For more information, contact your installer or local authority.
▪ Batteries are marked with the following symbol:
This means that the batteries may not be mixed with unsorted household waste. If a chemical symbol is printed beneath the symbol, this chemical symbol means that the battery contains a heavy metal above a certain concentration. Possible chemical symbols are: Pb: lead (>0.004%). Waste batteries must be treated at a specialized treatment facility for reuse. By ensuring waste batteries are disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.
WARNING
Indicates a situation that could result in death or serious injury.
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.

1.2 For the user

▪ If you are not sure how to operate the unit, contact your installer.
FCAHG71~140FVEB Split system air conditioners 4P429475-1 – 2015.12

1.3 For the installer

1.3.1 General

If you are not sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer and user reference guide
3
1 General safety precautions
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminum fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

1.3.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

1.3.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
Installer and user reference guide
4
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12
1 General safety precautions
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.
Charge with the cylinder upright.
down.

1.3.4 Brine

If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.3.6 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.

1.3.5 Water

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
FCAHG71~140FVEB Split system air conditioners 4P429475-1 – 2015.12
Installer and user reference guide
5

2 About the documentation

NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation

2.1 About this document

Target audience
Authorised installers + end users
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
Indoor unit installation and operation manual:
▪ Installation and operation instructions
▪ Format: Paper (in the box of the indoor unit)
Installer and user reference guide:
▪ Preparation of the installation, technical specifications,
reference data,…
▪ Detailed step-by-step instructions and background information
for basic and advanced usage
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Wiring instruction sheet
▪ Instructions on how to connect the optional sensor kit and
decoration panels
▪ Format: Paper (in the box of the indoor unit)
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.

For the installer

3 About the box

3.1 Overview: About the box

This chapter describes what you have to do after the box with the indoor unit is delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
Installer and user reference guide
6

3.2 Indoor unit

3.2.1 To unpack and handle the unit

Use a sling of soft material or protective plates together with a rope when lifting the unit. This to avoid damage or scratches to the unit.
Lift the unit by holding on to the hanger brackets without exerting any pressure on other parts, especially on refrigerant piping, drain piping and other resin parts.
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12
1 2
3.2.2 To remove the accessories from the
a
e fdcb
h ji
g
k
l m on
indoor unit

4 About the units and options

INFORMATION
For year‑round cooling applications with low indoor humidity conditions, such as Electronic Data Processing rooms, contact your dealer or see the engineering databook or the service manual.

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Indoor unit

Location
a Paper pattern for installation (upper part of packing) b General safety precautions c Indoor unit installation and operation manual d Installation guide e Washers for hanger brackets
f Screws (to temporarily attach the paper pattern for
installation to the indoor unit)
g Cable ties h Metal clamp
i Insulation piece (drain pipe) j Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
k Drain hose
l Insulation piece: Small (liquid pipe)
m Insulation piece: Large (gas pipe)
n Wiring instruction sheet (for the connection of the optional
sensor kit and decoration panels)
o Wire harness for the self‑cleaning decoration panel
4 About the units and options
Model identification
Example: F C A HG 100 F VE B
Code Explanation
F Air-cooled split indoor unit
C Cassette (multi flow)
A Refrigerant R32
HG H=High-performance
G=GQI-Eco series
71~140 Capacity class
F Model series
VE Power supply
B European market
Symbols
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
Refrigerant used: R32
4.1 Overview: About the units and
This chapter contains information about:
▪ Identifying the indoor unit
▪ Combining outdoor and indoor units
▪ Combining the indoor unit with options
FCAHG71~140FVEB Split system air conditioners 4P429475-1 – 2015.12
options

4.3 About the indoor unit

Use the system in the following temperature and humidity ranges for safe and effective operation.
Cooling Heating
Outdoor temperature
Indoor temperature
Indoor humidity ≤80%
–15~50°CDB –19~21°CDB
–20~15.5°CWB
18~35°CDB
10~27°CDB
12~28°CWB
(a)
Installer and user reference guide
7

5 Preparation

f
g
b
h
i
a
d
e
c
b
a
c
df e
(mm)
1500
1500
1000
1000
(a) To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions, safety devices may be put in action and the air conditioner may not operate.

4.4 System layout

NOTICE
Design of the system must not be done at temperatures below –15°C.
a Indoor unit b Outdoor unit c User interface d Suction air e Discharge air
f Refrigerant piping + interconnection cable g Drain pipe h Earth wiring
i Suction grille and air filter

4.5 Combining units and options

4.5.1 Possible options for the indoor unit

Make sure you have the following mandatory options:
▪ User interface: Wired or wireless
▪ Decoration panel: Standard or self-cleaning
▪ Preparing the refrigerant piping
▪ Preparing the electrical wiring

5.2 Preparing installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.

5.2.1 Installation site requirements of the indoor unit

INFORMATION
Also read the following requirements:
▪ General installation site requirements. See the
"General safety precautions" chapter.
▪ Refrigerant piping requirements (length, height
difference). See further in this "Preparation" chapter.
INFORMATION
The sound pressure level is less than 70dBA.
CAUTION
Appliance not accessible to the general public, install it in a secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for installation in a commercial and light industrial environment.
NOTICE
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo equipment, personal computers, etc.

4.5.2 Possible combinations of indoor unit and outdoor unit

Indoor unit Outdoor unit
RZAG71 RZAG100 RZAG125 RZAG140
FCAHG71 O
FCAHG100 O
FCAHG125 O
FCAHG140 O
5 Preparation
In places with weak reception, keep distances of 3 m or more to avoid electromagnetic disturbance of other equipment and use conduit tubes for power and transmission lines.

5.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
Installer and user reference guide
8
Fluorescent lights. When installing a wireless user interface in a
room with fluorescent lights, mind the following to avoid interference:
▪ Install the wireless user interface as close as possible to the
▪ Install the indoor unit as far as possible from the fluorescent
a Earth leakage protector b Fuse c Outdoor unit d Indoor unit e User interface
f Personal computer or radio
indoor unit.
lights.
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12
5 Preparation
1
2
3
4
1
2
3
4
1
2
3
a b c
(mm)
≥1500
2000
4000
≥1500
A
B
C
ba dac
≥1500 ≥500 ≥200
a
A A A
b c
t
Ø
▪ Take care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings.
▪ Choose a location where the hot/cold air discharged from the unit
or the operation noise, will NOT disturb anyone.
Air flow. Make sure nothing blocks the air flow.
Drainage. Make sure condensation water can be evacuated
properly.
Paper pattern for installation (upper part of packing)
(accessory). When selecting the installation location, use the paper pattern. It contains the dimensions of the unit and the required ceiling opening.
Air flow directions. You can select different air flow directions.
Choose the one best suited for the room. Also make sure the "Air flow direction" field setting corresponds with the actual situation (see "7.1Field settings"on page16).
Example:
a All-round air flow b 4-way air flow (with closed corners) (optional blocking pad
kit required)
c 3-way air flow (optional blocking pad kit required)
Ceiling insulation. When conditions in the ceiling exceed 30°C
and a relative humidity of 80%, or when fresh air is inducted into the ceiling, then additional insulation is required (minimum 10mm thickness, polyethylene foam).
Spacing. Mind the following requirements:
B: Minimum and maximum distance to the floor:
▪ Minimum: 2.5m to avoid accidental touching.
▪ Maximum: Depends on the air flow directions and the capacity
class. Also make sure the "Ceiling height" field setting corresponds with the actual situation. See "7.1 Field
settings"on page16.
If air flow direction… Then B
FCAHG71 FCAHG100~140
All-round ≤3.5m ≤4.2m
(a)
4-way
3-way
(a)
(a) Optional blocking kit required
≤4.0m ≤4.5m
≤3.5m ≤4.2m
Do NOT install the unit in the following places:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
▪ Where the voltage fluctuates a lot
▪ In vehicles or vessels
▪ Where acidic or alkaline vapour is present

5.3 Preparing refrigerant piping

5.3.1 Refrigerant piping requirements

A Minimum distance to the wall (see below) B Minimum and maximum distance to the floor (see below) C ≥298mm: In case of installation with standard decoration
panel
≥348mm: In case of installation with fresh air intake kit ≥378mm: In case of installation with self-cleaning
decoration panel
a Indoor unit b Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)
c Air fan d Static volume (example: table)
A: Minimum distance to the wall. Depends on the air flow
directions towards the wall.
a Air outlet and corners open b Air outlet closed, corners open (optional blocking pad kit
required)
c Air outlet and corners closed (optional blocking pad kit
required)
INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Refrigerant piping material
Piping material: Phosphoric acid deoxidised seamless copper.
Piping temper grade and thickness:
Outer diameter
Temper grade Thickness (t)
(a)
(Ø)
9.5mm (3/8") Annealed (O) ≥0.8mm
15.9mm (5/8") Annealed (O) ≥1.0mm
(a) Depending on the applicable legislation and the unit's
maximum working pressure (see "PS High" on the unit name plate), larger piping thickness might be required.
Flare connections: Only use annealed material.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
L1 liquid piping Ø9.5mm
L1 gas piping Ø15.9mm

5.3.2 Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:
▪ with a heat transfer rate between 0.041 and 0.052W/mK (0.035
and 0.045kcal/mh°C)
▪ with a heat resistance of at least 120°C
▪ Insulation thickness
FCAHG71~140FVEB Split system air conditioners 4P429475-1 – 2015.12
Installer and user reference guide
9

6 Installation

A
c
b
d e
a
Ambient
temperature
≤30°C 75% to 80% RH 15mm
>30°C ≥80% RH 20mm
Humidity Minimum thickness

5.4 Preparing electrical wiring

5.4.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
6 Installation
INFORMATION
This chapter only describes installation instructions specific to the indoor unit. For the other instructions, see:
▪ The installation manual of the outdoor unit
▪ The installation manual of the user interface
▪ The installation manual of the decoration panel
NOTICE
After installing the decoration panel:
▪ Make sure there is no gap between the unit body and
the decoration panel. Possible consequence: Air might leak and cause dew drop.
▪ Make sure no oil remains on the plastic parts of the
decoration panel. Possible consequence: Degradation and damage of plastic parts.

6.2 Mounting the indoor unit

6.2.1 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

6.2.2 Guidelines when installing the indoor unit

INFORMATION
Optional equipment. When installing optional equipment,
also read the installation manual of the optional equipment. Depending on the field conditions, it might be easier to install the optional equipment first.
In case of installation with a fresh air intake kit. Install the
fresh air intake kit always before installing the unit.
Decoration panel. Install the decoration panel always after
installing the unit.
Ceiling strength. Check whether the ceiling is strong enough to
support the weight of the unit. If there is a risk, reinforce the ceiling before installing the unit.
▪ For existing ceilings, use anchors.
▪ For new ceilings, use sunken inserts, sunken anchors or other
field supplied parts.

6.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
▪ Mounting the outdoor unit.
▪ Mounting the indoor unit (+ decoration panel).
▪ Connecting the refrigerant piping.
▪ Checking the refrigerant piping.
▪ Charging refrigerant.
▪ Connecting the electrical wiring.
▪ Finishing the outdoor installation.
▪ Finishing the indoor installation.
Installer and user reference guide
10
A 50~100mm: In case of installation with standard panel
100~150mm: In case of installation with fresh air intake kit 130~180mm: In case of installation with self-cleaning
decoration panel
a Ceiling slab b Anchor c Long nut or turnbuckle d Suspension bolt e Suspended ceiling
FCAHG71~140FVEB
Split system air conditioners
4P429475-1 – 2015.12
6 Installation
(mm)
780
710
a1 b
b a2
c
a cb d
(mm)
710 840 860~910
950
c d
e f
780
840
860~910
950
cde
f
a
b
A
C
B
A B C
a
b c
c
bba
Suspension bolts. Use M8~M10 suspension bolts for installation.
Attach the hanger bracket to the suspension bolt. Fix it securely by using a nut and washer from the upper and lower sides of the hanger bracket.
a1 Nut (field supply) a2 Double nut (field supply)
b Washer (accessories) c Hanger bracket (attached to the unit)
Paper pattern for installation (upper part of the packing). Use
the paper pattern to determine the correct horizontal positioning. It contains the necessary dimensions and centres. You can attach the paper pattern to the unit.
If A Then
B C
860mm
20mm 35mm
(= min.)
910mm
35mm 20mm
(= max.)
A Ceiling opening B Distance between the unit and the ceiling opening C Overlapping between the decoration panel and the
suspended ceiling
Installation guide. Use the installation guide to determine the
correct vertical position.
A In case of installation with standard decoration panel B In case of installation with fresh air intake kit C In case of installation with self-cleaning decoration panel
a Suspended ceiling
b Installation guide (accessory)
c Unit
Level. Make sure the unit is level at all four corners using a level
or a water-filled vinyl tube.
a Centre of the unit b Centre of the ceiling opening c Paper pattern for installation (upper part of the packing) d Screws (accessories)
Ceiling opening and unit:
▪ Make sure the ceiling opening is within its limits:
Minimum: 860mm to be able to fit the unit.
Maximum: 910mm to ensure enough overlapping between the
decoration panel and the suspended ceiling. If the ceiling opening is bigger, add extra ceiling material.
▪ Make sure the unit and its hanger brackets (suspension) are
centred within the ceiling opening.
a Level
b Vinyl tube
c Water level
NOTICE
Do NOT install the unit tilted. Possible consequence: If the unit is tilted against the direction of the condensate flow (the drain piping side is raised), the float switch might malfunction and cause water to drip.

6.2.3 Guidelines when installing the drain piping

Make sure condensation water can be evacuated properly. This involves:
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
FCAHG71~140FVEB Split system air conditioners 4P429475-1 – 2015.12
a Drain piping b Refrigerant piping c Hanger bracket pitch (suspension) d Unit e Ceiling opening
f Decoration panel
General guidelines
Pipe length. Keep drain piping as short as possible.
Pipe size. Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 25 mm nominal diameter and 32mm outer diameter).
Installer and user reference guide
11
Loading...
+ 25 hidden pages