Please read these “SAFETY CONSIDERATIONS” carefully before installing air conditioning equipment and
be sure to install it correctly. After completing the installation, make sure that the unit operates properly during
the start-up operation. Please instruct the customer on how to operate the unit and keep it maintained.
Also, inform customers that they should store this installation manual along with the operation manual for
future reference.
This air conditioner comes under the term “appliances not accessible to the general public”.
Meaning of warning and caution symbols.
WARNING .........Failure to observe a warning may result in death.
CAUTION ..........Failure to observe a caution may result in injury or damage to the equipment.
WARNING
• Ask your dealer or qualified personnel to carry out installation work. Do not try to install the air conditioner
yourself.
Improper installation may result in water leakage, electric shocks or fire.
• Perform installation work in accordance with this installation manual.
Improper installation may result in water leakage, electric shocks or fire.
• Be sure to use only the specified accessories and parts for installation work.
Failure to use the specified parts may result in water leakage, electric shocks, fire or the unit falling.
• Install the air conditioner on a foundation strong enough to withstand the weight of the unit.
A foundation of insufficient strength may result in the equipment falling and causing injuries.
• Carry out the specified installation work after considering strong winds, typhoons or earthquakes.
Improper installation work may result in the equipment falling and causing accidents.
• Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried
out by qualified personnel according to local laws and regulations and this installation manual.
An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire.
1English
• Make sure that all wiring is secured, the specified wires and used, and no external forces act on the terminal
connections or wires.
Improper connections or installation may result in fire.
• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the
wires so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric shocks, fire or the terminals overheating.
• If the refrigerant gas leaks during installation, ventilate the area immediately.
Toxic gas may be produced if the refrigerant gas comes into contact with fire.
• After completing the installation work, check that the refrigerant gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source
of fire, such as a fan heater, stove or cooker.
• Before touching electrical parts, turn off the unit.
CAUTION
• Ground the air conditioner.
Do not connect the ground wire to gas or water pipes, lightning conductor or a telephone ground wire.
Incomplete grounding may result in electric shocks.
• Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks.
• While following the instructions in this installation manual, install drain piping in order to ensure proper
drainage and insulate piping in order to prevent condensate.
Improper drain piping may result in water leakage and property damage.
• Install the indoor and outdoor units, power supply wiring and connecting wiring at least 1 meter away from
televisions or radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not be sufficient enough to eliminate the noise.)
• Remote controller (wireless kit) transmitting distance can result shorter than expected in rooms with electronic fluorescent lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as possible.
• Do not install the air conditioner in the following locations:
(a)where a mineral oil mist or an oil spray or vapor is produced, for example in a kitchen
Plastic parts may deteriorate and fall off or result in water leakage.
(b)where corrosive gas, such as sulfurous acid gas, is produced
Corroding copper pipes or soldered parts may result in refrigerant leakage.
(c) near machinery emitting electromagnetic waves
Electromagnetic waves may disturb the operation of the control system and result in a malfunction of the
equipment.
(d)where flammable gases may leak, where there are carbon fiber or ignitable dust suspensions in the air,
or where volatile flammables such as thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.
2.BEFORE INSTALLATION
• Do not exert pressure on the resin parts when opening the unit or when moving it after opening.
• Be sure to check the type of refrigerant to be used before installing the unit. (Using an incorrect refrigerant
will prevent normal operation of the unit.)
• The accessories needed for installation must be retained in your custody until the installation work is completed. Do not discard them!
• Decide upon a line of transport.
• Leave the unit inside its packaging while moving, until reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective plates together with a rope when lifting, to avoid damage or scratches to the unit.
• When selecting installation site, refer to the paper pattern.
English2
• For the installation of an outdoor unit, refer to the installation manual attached to the outdoor unit.
• Do not use the unit in locations with high salt content in the air such as beachfront property, locations where
the voltage fluctuates such as factories, or in automobiles or marine vessels.
1. Precautions
• Be sure to read this manual before installing the indoor unit.
• When selecting installation site, refer to the paper pattern.
• This unit is suitable for installation in a household, commercial and light industrial environment.
• Do not install or operate the unit in rooms mentioned below.
•
Laden with mineral oil, or filled with oil vapor or spray like in kitchens. (Plastic parts may deteriorate.)
• Where corrosive gas like sulfurous gas exists. (Copper tubing and brazed spots may corrode.)
• Where volatile flammable gas like thinner or gasoline is used.
• Where machines can generate electromagnetic waves. (Control system may malfunction.)
• Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates
greatly such as that in factories. Also in vehicles or vessels.
2. Accessories
Check if the following accessories are included with your unit.
(2) Paper pat-
Name(1) Metal clamp
Quantity1 pc.1 pc.1 pc.1 each1 each
Shape
Name
Quantity8 pcs.6 pcs.3 pcs.6 pcs.12 pcs.
Shape
(8) Washer for
hanger bracket
tern for
installation
(9) Large
Clamp
(10) Small
(3) Drain hose
(11) Screws for fixing
Insulation for
fitting
(4) For gas pipe
(5) For liquid pipe
the paper pattern
for installation
Sealing pad
(6) Large
(7) Middle
(12) Duct companion
flange connection screw
Name
Quantity2 pcs.
Shape
• Screws for fixing panels are attached to decoration panel.
3English
(13) Small sealing pad
(Other)
• Operation manual
• Installation manual
3. Optional accessories
• For this indoor unit, the optional remote controller is necessary. In case of downward air inlet, the dec-
oration panel and the canvas for decoration panel are necessary.
(Refer to “4. PREPARATIONS BEFORE INSTALLATION”)
• Remote controller
Remote controllerBRC1C61
NOTE
• If the customer wishes to use a remote controller that is not listed on the table, select a suitable remote
controller after consulting catalogs and technical materials.
• Use the decoration panel which apply to the below table.
ModelMin. height above ceiling
FBQ60BV1
FBQ71BV1
FBQ60BVL
FBQ71BVL
∗ When using the canvas duct for the decoration panel, the decoration panel needs at least 42.5 cm
of ceiling space.
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER
INSTALLATION IS FINISHED.
a. Items to be checked after completion of work
Items to be checkedIf not properly done, what is likely to occurCheck
Are the indoor unit and outdoor unit fixed
firmly?
Is the gas leak test finished?It may result in insufficient cooling.
Is the unit fully insulated?Condensate water may drip.
Does drainage flow smoothly?Condensate water may drip.
35 cm or moreInstallation not required ∗
∗
The unit may drop, vibrate or make noise.
Decoration panel
ColorWhite
BYBS71DJW1
Canvas duct for
decoration panel
KSAJ25K80
Does the power supply voltage correspond
to that shown on the name plate?
Are wiring and piping correct?
Is the unit safely grounded?It may result in electric shock.
Is wiring size according to specifications?
Is something blocking the air outlet or inlet
of either the indoor or outdoor units?
Are refrigerant piping length and additional
refrigerant charge noted down?
b. Items to be checked at time of delivery
∗Also review the “1. SAFETY CONSIDERATIONS”
Items to be checkedCheck
Did you explain about operations while showing the operation manual to your customer?
Did you hand the operation manual over to your customer?
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
The unit may malfunction or the components burn out.
It may result in insufficient cooling.
The refrigerant charge in the system is not
clear.
English4
c. Points for explanation about operations
The items withWARNING andCAUTION marks in the operation manual are the items pertaining
to possibilities for bodily injury and material damage in addition to the general usage of the product.
Accordingly, it is necessary that you make a full explanation about the described contents and also ask
your customers to read the operation manual.
4. Note to the installer
Be sure to instruct customers how to properly operate the unit (especially cleaning filters, operating different functions, and adjusting the temperature) by having them carry out operations themselves while
looking at the manual.
3.SELECTING INSTALLATION SITE
Please attach additional thermal insulation material to the unit body when it is believed that the relative humidity in the ceiling exceeds 80%. Use glass wool, polyethylene foam, or similar with a thickness of 10 mm or
more as thermal insulation material.
1. Select an installation site where the following conditions are fulfilled and that meets
your customer’s approval.
• In the upper space (including the back of the ceiling) of the indoor unit where there is no possible
dripping of water from the refrigerant pipe, drain pipe, water pipe, etc.
• Where optimum air distribution can be ensured.
• Where nothing blocks air passage.
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit weight.
• Where the false ceiling is not noticeably on an incline.
• Where sufficient clearance for maintenance and service can be ensured.
• Where there is no risk of flammable gas leakage.
• Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the
installation manual for the outdoor unit.)
CAUTION
•
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from
televisions and radios. This is to prevent image interference and noise in those electrical appliances.
(Noise may be generated depending on the conditions under which the electric wave is generated,
even if 1 meter is kept.)
Drain pipe
Liquid pipe
Power supply
wiring port
Transmission
300 or
more
(Service space)
Gas pipe
Maintenance
drain hose
Floor
Required service space
2500 or higher
from the floor
For installation
in high places
wiring port
2. Use suspension bolts for installation. Check whether the ceiling is strong enough to
support the weight of the unit or not. If there is a risk, reinforce the ceiling before
installing the unit.
(Installation pitch is marked on the paper pattern for installation. Refer to it to check for points requiring
reinforcement.)
5English
4.PREPARATIONS BEFORE INSTALLATION
1. Relation of ceiling opening to unit and suspension bolt position. (Refer to Fig. 1)
(Indoor unit)
Indoor unit
1050
1000
(Suspension bolt pitch)
Pipe
800 (Indoor unit)
For standard installation (air inlet on the both side), choose one of the below two means of installation.
NOTE
• For other than standard installation, contact your Daikin dealer for details.
For mounting decoration panel with canvas duct
Canvas duct for
decoration panel
(Optional accessory)
Ceiling
surface
630145
(Suspension
bolt pitch)
Fig. 1
(Ceiling opening)
Suspension bolt (×4)
180
or more
425
120
462
Decoration panel
(Optional accessory)
(120-300)
Indoor unit
(Back side)
1060
(Ceiling opening)
For mounting decoration panel directly
Ceiling
surface
180
462
(Ceiling opening)
350
or more
Decoration panel
Indoor unit
(Back side)
1060
(Ceiling opening)
2. The fan speed for this indoor unit is preset to provide standard external static pressure.
• If higher or lower external static pressure is required, reset the external static pressure by changing
the initial setting from the remote controller. Refer to the section entitled “10. FIELD SETTING”.
English6