Daikin EWLQ014KBW1N, EWLQ025KBW1N, EWLQ033KBW1N, EWLQ049KBW1N, EWLQ064KBW1N Operation manuals

OPERATION MANUAL
EWLQ014KBW1N EWLQ025KBW1N EWLQ033KBW1N EWLQ049KBW1N EWLQ064KBW1N
Operation manual
Condenserless water-cooled water chillers
Bedienungsanleitung
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
Manuel d'utilisation
sans condenseur
Gebruiksaanwijzing
Watergekoelde ijswaterkoelgroepen zonder condensor
Manual de funcionamiento
Enfriadores de agua sin condensador refrigerados por agua
Manuale d'uso
Refrigeratori d'acqua con raffreddamento ad acqua senza
condensatore
∂Б¯ВИЪ›‰ИФ ПВИЩФ˘ЪБ›·˜
À‰Úfi„˘ÎÙÔÈ „‡ÎÙ˜ ÓÂÚÔ‡ ¯ˆÚ›˜ Û˘Ì˘ÎÓˆÙ‹
Manual de operação
Refrigeradores de água arrefecidos a água, sem condensadores
Инструкция по эксплуатации
Бесконденсаторные чиллеры с водяным охлаждением
English
Deutsch
Français
Nederlands
Español
Italiano
EППЛУИО¿
Portugues
русский
EWLQ014KBW1N EWLQ064KBW1N EWLQ025KBW1N EWLQ033KBW1N EWLQ049KBW1N
Condenserless water-cooled water chillers
Operation manual
CONTENTS Page
Introduction ....................................................................................... 1
Technical specifications ............................................................................. 2
Electrical specifications ............................................................................. 2
Description ........................................................................................3
Function of the main components.............................................................. 4
Safety devices............................................................................................ 4
Internal wiring - Parts table........................................................................5
Before operation................................................................................ 6
Checks before initial start-up ..................................................................... 6
Water supply.............................................................................................. 6
Power supply connection and crankcase heating ...................................... 6
General recommendations ........................................................................ 6
Operation .......................................................................................... 6
Digital controller.........................................................................................6
Working with the units................................................................................ 7
Advanced features of the digital controller............................................... 10
BMS connection modbus ................................................................13
General description of Modbus................................................................ 13
Implemented error code........................................................................... 14
Defining the BMS setting ......................................................................... 14
Var iables database.................................................................................. 14
Troubleshooting............................................................................... 15
Maintenance.................................................................................... 16
Important information regarding the refrigerant used .............................. 16
Maintenance activities ............................................................................. 16
Disposal requirements............................................................................. 16
Annex I............................................................................................ 17
Saturated temperature............................................................................. 17
Menu overview ................................................................................ 18
INTRODUCTION
This operation manual concerns condensorless water-cooled water chillers of the Daikin EWLQ-KB series. These units are provided for indoor installation and used for cooling applications. The EWLQ units can be combined with Daikin fan coil units or air handling units for air conditioning purposes. They can also be used for supplying water for process cooling.
This manual has been prepared to ensure adequate operation and maintenance of the unit. It will tell you how to use the unit properly and will provide help if problems occur. The unit is equipped with safety devices, but they will not necessarily prevent all problems caused by improper operation or inadequate maintenance.
In case of persisting problems contact your local Daikin dealer.
Before starting up the unit for the first time, make sure that it has been properly installed. It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in "Before starting".
READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT. DO NOT THROW THIS MANUAL AWAY. KEEP IT IN YOUR FILES FOR FUTURE REFERENCE. Read the chapter "Operation" on page 6 before changing the parameters.
The English text is the original instruction. Other languages are translations of the original instructions.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
Operation manual
1
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Technical specifications
General EWLQ 014 033
(1)
025
Dimensions HxWxD (mm) 600x600x600 Machine weight
(kg)
104 138 149
Connections
• condenser discharge connection (copper)
• condenser liquid connection (copper)
General EWLQ 049 064
5/8" 3/4" 3/4"
5/8" 5/8" 5/8"
Dimensions HxWxD (mm) 600x600x1200 Machine weight
(kg)
252 274
Connections
• condenser discharge connection (copper)
• condenser liquid connection (copper)
Compressor EWLQ 014 033
Model Speed
3/4" 3/4"
5/8" 5/8"
JT140LP8Y1 JT236DJY1 JT315DJY1
025
(rpm)
2900 Oil type FVC68D Oil charge volume
(l)
1,5 3,0 3,0
Refrigerant type R410A
Evaporator
Type brased plate heat exchanger Min. water volume Water flow range
Condenser
(l) 62 103 155
(l/min) 31~75 53~123 76~186
refer to engeneering specifications as published by the supplier of your remote condenser
Compressor EWLQ 049 064
Model 2xJT236DJY1 2xJT315DJY1 Speed
(rpm)
2900 Oil type FVC68D Oil charge volume Refrigerant type
Evaporator
(l) 2 x 3,0 2 x 3,0
R410A
Type brased plate heat exchanger Min. water volume Water flow range
Condenser
(l)
(l/min) 101~247 152~373
205 311
refer to engeneering specifications as published by the supplier of your remote condenser
Electrical specifications
Model EWLQ 014 033
(2)
025
Power supply
• Phase
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM) 16gG 25gG 25gG
(Hz)
(V)
(%)
3N~
50 400 ±10
Compressor
• Phase
•Frequency
•Voltage
• Nominal running current (A) 6.5 10.5 15.0
(Hz)
(V)
3~
50 400
Control
• Phase
•Frequency
•Voltage
• Recommended fuses (aM)
Model EWLQ 049 064
(Hz)
(V)
1~
50 230
factory installed
Power supply
• Phase
•Frequency
•Voltage
•Voltage tolerance
• Recommended fuses (aM) 40gG 50gG
(Hz)
(V)
(%)
3N~
50 400 ±10
Compressor
• Phase
•Frequency
•Voltage
• Nominal running current (A) 10,5 15,0
(Hz)
(V)
3~
50 400
Control
• Phase
•Frequency
•Voltage
• Recommended fuses (aM)
(Hz)
(V)
1~
50 230
factory installed
(1) Refer to the engineering data book for the complete list of specifications.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
(2) Refer to the engineering data book for the complete list of specifications.
Operation manual
2
DESCRIPTION
The EWLQ condenserless water-cooled water chillers are available in 5 standard sizes.
EWLQ049~064KBW1N
17
2
13 14 15 16
EWLQ 014~033KBW1N
2
3
14
9
11
7 8
12 12
Figure: Main components
1 Compressor 2 Evaporator 3 Accumulator 4 Switchbox 5 Chilled water in 6 Chilled water out 7 Discharge stop valve 8 Liquid stop valve
9 Evaporator entering water temperature sensor 10 Freeze up sensor 11 Digital display controller 12 Power supply intake 13 Ball valve (field installed) 14 Water filter (field installed) 15 Air purge valve (field installed) 16 T-joint for air purge (field installed) 17 Flow switch (with T-joint) (field installed) 18 Main switch
500
500
500
3
1
1
3
4
500
5
11
10
500
500
500
500
759
866 1818
10
Required space around the unit for service
Operation manual
3
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Function of the main components
EWLQ014~033KBW1N
EWLQ049~064KBW1N
64
13
5
12
14
R3T
R4T
R3T
R4T
S4LP
S5LP
S4LP
1
M1C
LP
HP
3 7
M2C
LP
HP
M1C
LP
HP
S1HP
Q1D
2
8 9
S2HP
Q2D
S1HP
Q1D
10111513
Figure: Functional diagram
1 Compressor 9 Liquid stop valve 2 Filter 10 Discharge stop valve 3 Expansion valve 11 Accumulator 4 Evaporator 12 Flow switch (delivered with the unit, installed in the field) 5 Evaporator water outlet 13 Ball valve (delivered with the unit, installed in the field) 6 Evaporator water inlet 14 Water filter (delivered with the unit, installed in the field) 7 Sight glass 15 Air purge valve (delivered with the unit, installed in the field) 8 Liquid solenoid valve Field piping
As the refrigerant circulates through the unit, changes in its state or
Safety devices
condition occur. These changes are caused by the following main components:
Compressor The compressor (M*C) acts as a pump and circulates the
refrigerant in the refrigeration circuit. It compresses the refrigerant vapour coming from the evaporator to a pressure at which it can easily be liquified in the condenser.
Filter The filter installed behind the condenser removes small particles
from the refrigerant to prevent blockage of the tubes.
Expansion valve The liquid refrigerant coming from the condenser enters the
evaporator via an expansion valve. The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator.
Evaporator The main function of the evaporator is to take heat from the
water that flows through it. This is done by turning the liquid refrigerant, coming from the condenser, into gaseous refrigerant.
Water in/outlet connections
The unit is equipped with General safety devices: shut down all circuits and stop the whole unit.
I/O PCB (A2P) (input/output) The I/O PCB (A2P) contains a reverse phase protector.
The reverse phase protector detects if the 3 phases of the power supply are connected correctly. If a phase is not connected or if 2 phases are inverted, the unit can not start up.
Overcurrent relay The overcurrent relay (K*S) is located in the switch box of the
unit and protects the compressor motor in case of overload, phase failure or too low voltage. The relay is factory-set and may not be adjusted. When activated, the overcurrent relay has to be reset in the switch box and the controller needs to be reset manually.
High-pressure switch The high-pressure switch (S*HP) is installed on the discharge
pipe of the unit and measures the condenser pressure (pressure at the outlet of the compressor). When the pressure is too high, the pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs to be reset manually.
The water inlet and outlet connection allow an easy connection of the unit to the water circuit of the air handling unit or industrial equipment.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
4
Low pressure switch The low-pressure switch (S*LP) is installed on the suction pipe
of the unit and measures the evaporator pressure (pressure at the intlet of the compressor). When the pressure is too low, the pressure switch is activated and the circuit stops.
When activated, it resets automatically, but the controller needs to be reset manually.
Discharge thermal protector The discharge thermal protector (Q*D) is activated when the
temperature of the refrigerant leaving the compressor becomes too high. When the temperature returns to normal, the protector resets automatically, but the controller needs to be reset manually.
Freeze up sensor The outlet water temperature sensor (R4T) measures the
temperature of the water at the water heat exchanger outlet. The protection device shuts down the circuit when the temperature of the chilled water becomes too low in order to prevent freezing of the water during operation.
When the outlet water temperature returns to normal, the protector resets automatically, but the controller needs to be reset manually.
Fuse for control circuit (F1U) The fuse for control circuit protects cables of control circuit and controller components in case of short circuit.
Fuse for control circuit (F4) The fuse for control circuit protects cables of control circuit in case of short circuit.
Fuse for digital controller (F3U) The fuse protects cables of digital controller and digital controller in case of short circuit.
Flow switch (delivered with the unit, installed in the field) The flow switch measures the flow in the water circuit. In case the flow does not reach the minimum allowed water flow, the unit will be shut down.
Ball valve (delivered with the unit, installed in the field) A ball valve is installed in front of and behind the water filter to allow filter cleaning without having to drain the water circuit.
Water filter (delivered with the unit, installed in the field) The filter installed in front of the unit removes dirt from the water to prevent damage to the unit or blockage of the evaporator or condenser. The water filter should be cleaned on a regular base.
Air purge valve (delivered with the unit, installed in the field) Remaining air in the chiller water system will be automatically removed via the air purge valve.
Internal wiring - Parts table
Refer to the internal wiring diagram supplied with the unit. The abbreviations used are listed below:
A1P.................... PCB: controller PCB
A2P.................... PCB: I/O PCB (input/output)
A3P............. ** ... PCB: Address card for BMS
A5P,A6P......** ... PCB: Softstarter for circuit 1, circuit 2
A7P............. ** ... PCB: Remote user interface
A71P.................. PCB: power supply card
A72P.................. PCB: remote user interface
E1H,E2H............ Crankcase heater circuit 1, circuit 2
F1,F2,F3.....# .... Main fuses for the unit
F4 ...............*..... Fuse I/O PCB
F5 ...............## .. Surge proof fuse
F6 ...............# .... Fuse for pumpcontactor
F1U.................... Fuse I/O PCB
F3U.................... Fuse for controller PCB
H3P.............*..... Indication lamp alarm
H4P.............*..... Indication lamp operation compressor 1
H5P.............*..... Indication lamp operation compressor 2
H6P.............*..... Indication lamp general operation
K1F,K2F ......# .... Auxiliary contactor for fan motors
K1M,K2M........... Compressor contactor circuit 1, circuit 2
K4S,K5S............ Overcurrent relay circuit 1, circuit 2
K6S............. * ..... Overcurrent relay pump
K1P............. * ..... Pumpcontactor
M1C,M2C .......... Compressor motor circuit 1, circuit 2
PE...................... Main earth terminal
Q1D,Q2D........... Discharge thermal protector circuit 1, circuit 2
R3T.................... Evaporator inlet water temperature sensor
R4T.................... Evaporator outlet water temperature sensor
R5T.................... Condenser inlet temperature sensor
S1HP,S2HP ....... High pressure switch circuit 1, circuit 2
S4LP,S5LP......... Low pressure switch circuit 1, circuit 2
S7S............. * ..... Switch for remote cooling/heating selection
dual setpoint
S9S............. * ..... Switch for remote start/stop
S10L .................. Flow switch
S12M ................. Main isolator switch
TR1.................... Transfo 230 V ➞ 24 V for supply of controller PCB
TR2.................... Transfo 230 V ➞ 24 V for supply of I/O PCB (A2P)
Y3R.................... Reversingvalve
Y1S, Y2S ........... Liquid solenoid valve
X1~3,X1~82A .... Connectors
Not included with standard unit
Not possible as option Possible as option
Obligatory # ##
Not obligatory * **
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
or
(2)
or dual setpoint
Operation manual
5
(1) optional (2) field supply
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
BEFORE OPERATION
Checks before initial start-up
Make sure that the circuit breaker on the power supply panel of the unit is switched off.
After the installation of the unit, check the following before switching on the circuit breaker:
1 Field wiring
Make sure that the field wiring between the local supply panel and the unit has been carried out according to the instructions described in the installation manual, according to the wiring diagrams and according to European and national regulations.
2 Fuses or protection devices
Check that the fuses or the locally installed protection devices are of the size and type specified in the installation manual. Make sure that neither a fuse nor a protection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box on loose connections or damaged electrical components.
5 Fixation
Check that the unit is properly fixed, to avoid abnormal noises and vibrations when starting up the unit.
6 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak, call your local dealer.
8 Oil leak
Check the compressor on oil leakage. If there is an oil leak, call your local dealer.
9 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage on the identification label of the unit.
Power supply connection and crankcase heating
In order to avoid compressor damage, it is necessary to switch on the crankcase heater for at least six hours before starting the compressor after a long period of standstill.
To switch on the crankcase heater proceed as follows:
1 Switch on the circuit breaker on the unit. Make sure that the unit
is “OFF” on the controller.
2 The crankcase heater is switched on automatically. 3 Check the supply voltage on the supply terminals L1, L2, L3, (N)
by means of a voltmeter. The voltage should correspond to the voltage indicated on the identification label of the unit. If the volt­meter reads values which are not within the ranges specified in the technical data, check the field wiring and replace the supply cables if necessary.
4 Check the LED on the reverse phase protector. If it lights up, the
phase order is correct. If not, switch off the circuit breaker and call a licensed electrician to connect the wires of the power sup­ply cable in the correct phase order.
After six hours, the unit is ready for operation.
General recommendations
Before switching on the unit, read following recommendations:
1 When the complete installation and all necessary settings have
been carried out, close all front panels of the unit.
2 The service panel of the switch box may only be opened by a
licensed electrician for maintenance purposes.
OPERATION
The EWLQ units are equipped with a digital controller offering a user­friendly way to set up, use and maintain the unit.
This part of the manual has a task-oriented, modular structure. Apart from the first section, which gives a brief description of the controller itself, each section or subsection deals with a specific task you can perform with the unit.
Digital controller
User interface
The digital controller consists of a numeric display, four labelled keys which you can press and LEDs providing extra user information.
Water supply
Fill the water piping, taking into account the minimum water volume required by the unit. Refer to the chapter "Water charge, flow and quality" in the installation manual.
Make sure that the water is of the quality as mentioned in the installation manual.
Purge the air at the high points of the system and check the operation of the circulation pump and the flow switch.
Use a good thread sealant for the sealing of the connections. The sealing must be able to withstand the pressures and temperatures of the system, it must also be resistant to the used glycol in the water.
The exterior of the water pipes must be adequately protected against corrosion.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Figure - Digital controller
Figure - Remote user interface (optional kit)
Operation manual
6
Keys provided on the controller:
The function carried out when the user presses one or a combination of these keys depends on the status of the controller and the unit at that specific moment.
Keys digital
controller
AT
BU
A + BS
CC
DD
C + DR
Keys remote
interface
Main display Sensor readout menu Parameter selection menu Parameter setting menu
Press once:
Press for 5 seconds:
To be able to access DIRECT parameters
Press for 5 seconds: A + B OR Press once:
S
To be able to access USER parameters (after entering USER password)
Press for 5 seconds: Switch unit on/off in heating mode Press once: Direct access to readout menu sensor (b01/b02/b03)
Press for 5 seconds: Switch unit on/off in cooling mode Press once: Direct access to readout menu sensor (b01/b02/b03)
Press for 5 seconds: Manually alarm reset in the event of alarm
Select previous sensor
Return
Press once:
parameter
Press once:
Select next sensor
parameter
Press once:
Return
Press once:
Select parameter group or
parameter
Press once:
Select previous parameter
group or parameter
Press once:
Select next parameter group
or parameter
Press once:
Cancel and return
Press once:
Confirm and return
Press once:
Increase value
Press once:
Decrease value
LEDs provided on the controller and remote interface:
Function during main display (not inside menu)
Remote
Leds digital controller
P
Led (green) Z Inlet water temperature.
Led (amber)
F
G Led (amber) G
H
Led (red) Y
L Led (amber) L
M Led (amber) M
& Led (amber) &
é Led (amber) é
interface
F
Main display
Indicates that heating mode is active.
Indicates that cooling mode is active.
Indicates that the alarm is active.
Indicates the status of the pump
LED, indicates that at least one compressor is active.
LED is on, indicates that compressor 1 is active. LED is flashing, indicates compressor 1 startup request.
LED is on, indicates that compressor 2 is active. LED is flashing, indicates compressor 2 startup request.
When selecting a parameter group or parameter, different LEDs related to the parameter group or parameter are displayed.
Example: The LEDs F and G are displayed when accessing a parameter group or when accessing parameters directly.
Direct and user parameters
The digital controller provides direct and user parameters. The direct parameters are important for the everyday usage of the unit, e.g. to adjust the temperature setpoint or to consult actual operational information. The user parameters on the contrary provide advanced features such as adjusting time delays.
Each parameter is defined by a code and a value. For example: the parameter used to select local or remote on/off control has code h07 and value 1 or 0.
For an overview of the parameters, refer to "Overview of the direct and user parameters" on page 10.
Working with the units
This chapter deals with the everyday usage of the EWLQ units. Here, you will learn how to perform routine tasks, such as:
"Switching the unit on" on page 8 and "Switching the unit off" on page 8,
"Adjusting the cooling temperature setpoint" on page 8,
"Consulting actual operational information" on page 9,
"Resetting alarms" on page 9,
"Resetting warnings" on page 9.
NOTE
Operation manual
7
Temperature readout tolerance: ±1°C. Legibility of the numeric display may decrease in direct
sunlight.
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Switching the unit on
Switching the unit off
To switch the unit on in cooling mode, proceed as follows:
1 Press the D key for approximately 5 seconds, the G LED will
be displayed.
To switch the unit on in heating mode, proceed as follows:
1 Press the C key for approximately 5 seconds, the F LED will
be displayed.
In both cases an initialization cycle is started, the L LED, the M LED, the & LED and the é LED will light up depending on the programmed thermostat function.
In case the & LED or the é LED is flashing, it indicates that there is a compressor 1 or 2 startup request. The compressor will start after the timer has reached zero.
NOTE
If remote on/off control is enabled, refer to "Selecting local or remote on/off control" on page 12.
2 When the unit is started up for the first time, or when the unit has
been out of operation for a longer period, it is recommended to go through the following checklist.
Abnormal noise and vibrations
Make sure the unit does not produce any abnormal noises or vibrations: check the fixations and piping. If the compressor makes any abnormal noises, this may also be caused by an overcharge of refrigerant.
Working pressure
It is important to check the high and low pressure of the refrigerant circuit to ensure the proper operation of the unit and to guarantee that the rated output will be obtained.
For reference, the average saturated temperature of R410A in relation to the pressure readout can be found in "Annex I" on page 17.
The pressures measured will vary between a maximum and minimum value, depending on the water and outdoor temperatures (at the moment of measurement).
3 If the unit does not start after a few minutes, consult the actual
operational information available in the list of direct parameters. Also refer to the chapter "Troubleshooting" on page 15.
To switch the unit off and cooling mode is active, proceed as follows:
1 Press the D key for approximately 5 seconds, the G LED will
be extinguished.
To switch the unit off and heating mode is active, proceed as follows:
1 Press the C key for approximately 5 seconds, the F LED will
be extinguished.
NOTE
If remote on/off control is enabled, refer to "Selecting local or remote on/off control" on page 12.
How to consult and modify the direct parameters
For an overview of the menu structure, refer to "Menu overview" on page 18.
1 Press B for 5 seconds in the main display.
The -/- parameter group is displayed.
2 Press the C or D key to select the required parameter
group.
3 Press the B key to enter the selected parameter group.
4 Press the C or D key to select the required parameter.
5 Press the B key to consult the selected parameter.
6 Press the C or D key to raise, respectively lower the
setting of the selected parameter. (Only valid for read/write parameters.)
7 Press the B key to confirm the modified setting.
OR Press the A key to cancel the modified setting.
8 Press the A key to return to the parameter group.
9 Press 2 times the A key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display without saving any modified parameter.
How to consult the "sensor readout menu" parameters
NOTE
In case of remote on/off control (h07=1), it is recom­mended to install an on/off switch near the unit in series with the remote switch. The unit can then be switched off from either place.
The selection of cooling mode or heating mode can only be carried out at startup. Selecting an opposite mode without switching the unit off is impossible.
For an overview of the menu structure, refer to "Menu overview" on page 18.
The b01/b02/b03 parameters are part of the "sensor readout menu".
1 Press the C or D key in the main display.
The b01 parameter is displayed. In case no buttons are pressed, the value of the b01 sensor will be displayed until C or D is pressed again to select another parameter (b02 or b03).
2 Press the A key to return to the main display. If during the procedure no buttons are pressed for 30 seconds, the
displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display.
Adjusting the cooling temperature setpoint
1 Modify the r1 cooling setpoint parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 8.
NOTE
When dual setpoint is enabled (refer to "Selecting dual setpoint control" on page 12).
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
8
Consulting actual operational information
The actual operational information that can be consulted in the list of direct parameters consists of:
b01:Evaporator inlet water temperature,
b02:Evaporator outlet water temperature,
b03: When cooling mode is active: inlet water temperature of
the condenser. When heating mode is active: inlet water temperature of the evaporator.
c10:Total running hours of the compressor 1,
c11:Total running hours of the compressor 2,
c15:Total running hours of the pump.
NOTE
These are direct parameters, refer to "How to consult and modify the direct parameters" on page 8.
The parameters b01, b02 and b03 can also be consulted by the "sensor readout menu". Refer to "How to consult the "sensor readout menu" parameters" on page 8.
To reset the timers of parameters c10, c11 and c15 refer to "Resetting warnings" on page 9.
Resetting alarms
When an alarm is detected, the following happens:
the alarm relay is energized,
the H LED is displayed
the display starts flashing, alternately showing the alarm code
and the inlet water temperature.
The following alarm codes may appear on the screen:
a1: indicates an anti-freeze alarm.
e1: indicates that the NTC probe used to measure the
e2: indicates that the NTC probe used to measure the
e3: indicates that the fuse for the evaporator heatertape (F4)
ehs: indicates that the supply voltage is exceedingly high. In
el1: indicates that there is a power supply error (example:
el2: indicates that there is a power supply error (example:
els: indicates that the supply voltage is exceedingly low. In this
epb: indicates that the EEPROM on the controller PCB inside
epr: indicates that the EEPROM on the controller PCB inside
fl: indicates that there was no sufficient water flow either
hp1: indicates that a high pressure switch, the discharge
evaporator inlet water temperature is defective.
evaporator outlet water temperature is defective.
is blown or that there is a reverse phase error or that there is a problem with the I/O PCB (A2P).
In case the unit is equipped with freeze protection, it is highly recommended to install the remote indicator lamp alarm (H3P) (see wiring diagram supplied with the unit). By doing so, breakdown of the fuse for the evaporator heatertape (F4) will be detected sooner and freezing of the circuit will be avoided during cold weather.
this case contact a licensed electrician.
noise). In this case contact a licensed electrician.
noise). In this case contact a licensed electrician.
case contact a licensed electrician.
the unit is defective.
the unit is defective.
during the period of 15 seconds after the pump was started or for 5 seconds while the compressor is active or that the overcurrent protection of the pump is activated.
thermal protection or the overcurrent protection of the compressor motor is activated or that the NTC probe used to measure the ambient temperature is defective.
fl + hp1
: indicates that there is most likely an RPP error or that the
F4 fuse is blown.
lp1: indicates that the low pressure switch is activated.
ter: indicates that there is a remote user interface
communication error.
F]]c`e\:
To reset an alarm, proceed as follows:
1 Find the cause of shutdown and correct.
2 If the alarm codes a1, fl, hp1 or lp1 appear on the display,
communication failure between the digital controller of the unit and the remote user interface. Confirm the correct selection of parameter code h23. This should be default setting 0 and confirm the correction installation according to the installation manual of the remote user interface EKRUMCA.
NOTE
If the alarm codes fl and h1 are flashing alternately, the alarm is most probably caused by the reverse phase protector or by the fuse for evaporator heater­tape (F4) that was blown.
Refer to the chapter "Troubleshooting" on page 15.
reset the alarm manually by pressing the E combination keys C and D simultaneously for approximately 5 seconds.
In all other cases the alarm is reset automatically. Once the alarm is reset, the error code and the H LED no longer
appears on the display. The controller continues its normal operation, displaying the inlet water temperature.
Resetting warnings
During normal operation, the display of the controller may start flashing, alternately showing the inlet water temperature and the following warning code:
hc1: indicates that the compressor 1 requires maintenance: the total running hours of the compressor 1 (direct parameter c10) has exceeded the setting of the timer threshold for maintenance warning (user parameter c14).
hc2: indicates that the compressor 2 requires maintenance: the total running hours of the compressor 2 (direct parameter c11) has exceeded the setting of the timer threshold for maintenance warning (user parameter c14).
To reset the maintenance warning hc1 or hc2, proceed as follows:
1 Consult c10 running hours of compressor 1 or c11 running
hours of compressor 2. These are direct parameters, refer to "How to consult and modify the direct parameters" on page 8.
2 When c10 or c11 parameter value is displayed, press the
C and D key simultaneously for 5 seconds. The value of the timer becomes 0 and the warning is reset.
NOTE
Do not forget to carry out the required maintenance activities after resetting the timers.
Besides resetting timer c10 and c11, it is also possible to reset timer c15 (running hours of pump) in the same way.
Operation manual
9
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Advanced features of the digital controller
This chapter gives an overview of the direct parameters and user parameters provided by the controller. In the following chapter, you will learn how you can set up and configure the unit using these parameters.
Overview of the direct and user parameters
The list of direct parameters is accessible by pressing the B key for approximately 5 seconds. Refer also to "How to consult and modify the direct parameters" on page 8.
Parameter
group
-/- /23
Parameter
code
Description
Measurement unit
0=°C 1=°F
Default
value
Min Max Units
Read/
Write
User/
Direct
Modbus Address
001 R/W U 5 D
-a- No user or direct parameters accessible b01 Evaporator inlet water temperature 0.1°C R D 102 A b02 Evaporator outlet water temperature 0.1°C R D 103 A
-b­b03
When cooling mode is active: inlet water temperature of the condenser. When heating mode is active: inlet
0.1°C R D 104 A
water temperature of the evaporator. Time delay between pump startup and
compressor startup Time threshold between the unit
shutdown and the pump shutdown
15 0 999 1 sec R/W U 238 I
00150 1 min R/W U 239 I
-c-
c07
c08
c10 Total running hours of compressor 1 x100 hours R D 122 A c11 Total running hours of compressor 2 x100 hours R D 123 A
c14
Maintenance threshold for maintenance warning (c10 and c11)
00100 x100 hours R/W U 241 I
c15 Total running hours of pump x100 hours R D 126 A
-d- No user or direct parameters accessible
-f- No user or direct parameters accessible
To activate remote cool/heat control
h06
0=not active 1=active
001 R/W U 14 D
(only in case p09=9) To activate remote on/off control
h07
-h-
0=not active 1=active
(only in case p34=23)
001 R/W U 15 D
To lock the controller keyboard
h09
0=lock
101 R/W U 16 D
1=unlock
h10 Serial address for BMS connection 1 1 200 R/W U 256 I
To select address card connection
h23
0=remote user interface connection
001 R/W U 11 D
1=MODBUS connection Changeable digital input selection
S7S
p09
0=no function 9=remote cool/heat (only active in
combination with h06)
9027 R/W U 277 I
13=remote dual setpoint
-p-
DO NOT SELECT OTHER VALUES
Changeable digital input selection S9S
p34
0=no function 13=remote dual setpoint 23=remote on/off (only active in
23 0 27 R/W U 329 I
combination with h07)
DO NOT SELECT OTHER VALUES
r01
Cooling setpoint
12.0
8.0
(†)
25.0 0.1°C R/W D 41 A
r02 Cooling difference 3.0 0.3 19.9 0.1°C R/W D 42 A
-r-
r03 Heating setpoint 30.0 15.0 50.0 0.1°C R/W D 43 A r04 Heating difference 3.0 0.3 19.9 0.1°C R/W D 44 A
r21
r22
Cooling setpoint 2 Heating setpoint 2
(‡)
(‡)
12.0
30.0 15.0 50.0 0.1°C R/W D 56 A
8.0
(†)
25.0 0.1°C R/W D 55 A
-t- No user or direct parameters accessible
f-r h99 Software release version R D 208 I
(*) D=digital, A=analog, I=integer. (†) –2.0 and –7.0 only applicable for units with glycol applications. (‡) Used in case dual setpoint is enabled in p09 or p34 and dual setpoint digital input is closed.
Parameter
(*)
type
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
10
How to consult and modify the user parameters
Defining the cooling temperature differential
NOTE
When user parameters are consulted, the direct parameters are displayed as well.
For an overview of the menu structure, refer "Menu overview" on page 18.
1 In case of digital controller, press the A and B keys for
approximately 5 seconds until O is displayed. In case of remote user interface, push S once.
2 Enter the correct password by using the C and D keys.
The password’s value is 22.
3 Press the B key to confirm the password and to enter the
menu, s-p is displayed.
4 Press the B key to consult the parameter settings (=s-p).
(l-p means consulting the parameter level, but this function is not used). The -/- parameter group is displayed.
5 Press the C or D key to select the required parameter
group.
6 Press the B key to enter the selected parameter group.
7 Press the C or D key to select the required parameter.
8 Press the B key to consult the selected parameter.
9 Press the C or D key to increase, respectively decrease
the setting. (Only valid for read/write parameters.)
10 Press the B key to confirm the modified setting.
OR Press the A key to cancel the modified setting.
11 Press the A key to return to the parameter group.
12 Press 2 times the A key to return to the main display.
If during the procedure no buttons are pressed for 30 seconds, the displayed parameter code or value will start flashing. After another 30 seconds without pressing any buttons, the controller automatically returns to the main display without saving any modified parameter.
Modify the r02 cooling differential parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 8.
for 1 compressor
compressor
ON
OFF
12 15
r02
r01/
temperature of
°C
inlet water
evaporator
r21
for 2 compressors
compressor
ON
OFF
ON
OFF
12 13.5 15
r02
temperature of
°C
inlet water
evaporator
r01/
r21
Defining the heating temperature differential
Modify the r04 heating differential parameter. This is a direct parameter, refer to "How to consult and modify the
direct parameters" on page 8.
for 1 compressor
compressor
ON
OFF
compressor
ON
OFF
ON
OFF
27 30
r04
for 2 compressors
27 28.5 30
r04
r03/
r22
r03/
r22
°C
inlet water
temperature of
condensor
°C
inlet water
temperature of
condensor
Operation manual
1
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Tasks carried out using user parameters
Defining the measurement unit
Depending on the setting of user parameter /23 (measurement unit), all temperature values are displayed in °C (=0) or in °F (=1).
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
Defining the time delay between pump and compressor startup
User parameter c07 allows you to define the time delay between the pump startup and the compressor startup.
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
Defining the time delay between unit and pump shutdown
User parameter c08 allows you to define the time delay between the unit shutdown and the pump shutdown, more specifically the period during which the pump will still be active after the unit has been shut down.
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
Selecting local or remote on/off control
User parameter h07 in combination with the remote on/off switch (installed by the customer) allows the user to switch the unit on without using the D or C key on the controller.
When user parameter h07 is set to 0 (=not active), the unit can only be switched on by means of the D and C key on the controller.
When user parameter h07 is set to 1 (=active), the unit can be switched on or off as follows:
When remote on/off switch is opened, then the unit is
switched off and it is not possible to switch the unit on/off while pressing the D or C key on the controller (5 sec).
When remote on/off switch is closed, then the unit is
switched on and it is possible to switch the unit on/off while pressing the D or C key on the controller (5 sec).
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
NOTE
This is only in case p34 (changeable digital input selection S9S) has value 23 (default value).
In case dual setpoint function is selected for this function (p34=13) then the remote on/off control is not activated.
Defining the timer threshold for maintenance warning
User parameter c14 allows you to define a timer threshold (running hours of the compressor) after which the controller will generate a maintenance warning or request.
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
Selecting local or remote cool/heat control
User parameter h06 in combination with the remote cool/heat selection switch (installed by the customer) allows the user to select cooling or heating mode without using the D or C key on the controller.
When user parameter h06 is set to 0 (=not active), cooling or heating mode is determined by means of the controller.
When user parameter h06 is set to 1 (=active), cooling or heating mode is determined by means of the remote switch.
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
NOTE
This is only in case p09 (changeable digital input selection S7S) has value 9 (default value).
In case dual setpoint function is selected for this function (p09=13) then the remote cool/heat control is not activated. Meaning the D or C keys on the controller are still active.
Selecting dual setpoint control
User parameters p09 (changeable digital selection S7S) and p34 (changeable digital selection S9S) can be used to assign the dual setpoint control to S7S or S9S.
There are 3 different controls available for 2 different change digital inputs (S7S and S9S):
p09: changeable digital input selection S7S
0=no function
9=remote cool/heat
13=remote dual setpoint
p34: changeable digital input selection S9S
0=no function
13=remote dual setpoint
23=remote on/off
When dual setpoint switch is open, the first setpoint is activated (r01 cooling setpoint or r03 heating setpoint, depending on cooling or heating operation).
When dual setpoint switch is closed, the second setpoint is activated (r21 cooling setpoint 2 or r22 heating setpoint 2, depending on cooling or heating operation).
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
12
Locking the controller keyboard
General information about the Modbus protocol
Once user parameter h09 is set to 0, the following advanced features can no longer be carried out by means of the controller:
modifying direct and user parameters (parameters can be displayed but not modified),
resetting the timers.
switching the unit on/off in cooling or heating
When user parameter h09 is set to 1, the above-described advanced features can be carried out using the controller.
To modify user parameter h09 value from 1 to 0, the standard user parameter modification procedure can be used with the standard password "22". Refer to "How to consult and modify the user parameters" on page 11.
To modify user parameter h09 value from 0 to 1, the user parameter modification procedure can be used with dedicated password "11". Refer to "How to consult and modify the user parameters" on page 11.
BMS CONNECTION MODBUS
By installing the optional kit address card EKAC10C, you will be able to communicate with your chiller through a Building Management System or supervisory system via the Modbus protocol.
General description of Modbus
The address card communicates using the Modbus protocol.
Different parts of the communication network
The communication network consists of two major players:
The Building Management System (BMS) or supervisory
system.
The chiller or multiple chillers.
The BMS or other supervisory system is able to communicate
with the chillers through the address card. The management of the communication occurs in accordance with a master-slave structure in polling, where the supervising BMS is the master and the address cards are the slaves.
The chiller unit can be identified by the supervisor through the assignment of an address within the Modbus network. The address of the chiller unit can be programmed during the configuration of the BMS settings.
The variables database of every chiller with installed address card is the point of reference for the supplier of the supervisory system in Modbus to assign a suitable meaning to the variables. The variables can be read and/or written by the supervisory system. Whether the variables are read-only or read/write depends on the connected chiller and/or the application program being used.
- If the supervisory system assigns a value to a variable with
read-only status, the command will not be executed at all.
-Variables requested by the supervisory system that are not
available in a chiller with an address card are sent from the address card to the supervisory system with zero value. The supervisory system will have to manage these properly.
- In case the supervisory system tries to write a value of a
parameter that is out of range, the writing will be ignored.
The Modicon Modbus protocol implemented in the address card complies with the content of the following document:
Modicon Modbus Protocol
Reference Guide
June 1996, PI-MBUS-300 Rev. J
The Modbus protocol implemented is of the RTU (Remote Terminal Unit) type based on character tranmission times. The configuration uses the multi-drop feature of RS485. The address sent within the Modbus packet addresses the chiller unit.
Implemented RS485 communication settings for the Modbus protocol
The RS485 communication settings are implemented as follows:
Baud-rate: 9600
Stop bit: 2
Parity: none
Implemented commands for the Modbus protocol
The implemented commands in the program are as listed:
Modbus command Meaning Notes
01 read coil status Read digital
02 read input
status
03 read holding
registers
04 read input
registers
05 force single coil Write individual
06 preset single
register
15 force multiple
coils
16 preset multiple
registers
variable(s)
Read digital variable(s)
Read analogue variable(s)
Read analogue variable(s)
digital variable(s) Write individual
analogue variable(s) Write series of
digital variables
Write series of analogue variables
Note that:
Due to the variety of chillers with installed address cards, no distinction is made between input variables (with read-only status) and output variables (with read/write status) so that the knowledge of the database and its management depends on the part present on the supervisory system.
Due to the general nature of the system, the address card answers in the same way to various Modbus commands.
obtains current status (ON/ OFF) of a group of logic coils or discrete input
obtains current status (ON/ OFF) of a group of logic coils or discrete input
obtains current binary value in one or more holding registers
obtains current binary value in one or more holding registers
forces single coil to ON or OFF status
places a specific binary value into a holding register
forces a series of consecutive logic coils to be defined to ON or OFF status
places specific binary values into a series of consecutive holding registers
Operation manual
13
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Data representation of the Modbus protocol
Digital All digital data is coded by a single bit:
"0" for OFF
"1" for ON.
All digital variables are assigned to bits of consecutive registers, each one having:
the lower-address variable assigned to the less significant bit
the higher-address variable assigned to the most significant
bit.
Analogue and integer data An analogue and integer value is represented by a 16-bit WORD register in binary notation. For each register, the first byte contains the high order bits and the second byte contains the low order bits.
The analogue variables are represented in tenths:
for example, the value 10.0 is transmitted as 0064h=100d for example, the value –10.0 is transmitted as FF9Ch=–100d
The integer variables are transferred using the effective
value: for example, the value 100 is transmitted as 0064h=100d
The address card operates on registers where one register must be considered at 16-bit.
In case the BMS or supervisory system tries to write a value of a parameter that is out of range, the writing will be ignored.
Implemented error code
Code Modbus interpretation Condition
1 Illegal function Message is not supported or the
number of variables required is greater than the allowed limit (length 20)
Defining the BMS setting
Activating the Modbus protocol
The Modbus protocol is activated by setting the h23 parameter to 1. This is a user parameter, refer to "How to consult and modify the user
parameters" on page 11.
Defining the unit’s serial address
To define each unit’s unique serial address required for communication with the supervisionary system, set parameter h10.
This is a user parameter, refer to "How to consult and modify the user parameters" on page 11.
Variables database
The BMS or supervisory system and the chiller unit communicate through a fixed set of variables, also called address numbers. Hereafter, you will find the information you need about the digital, integer and analogue variables that the BMS or supervisory system can read from or write to the address card of the chiller.
For addresses of all the direct and user parameters refer to "Overview of the direct and user parameters" on page 10.
Overview of all variables which are not direct or user parameters
Description
Circuit alarm
General alarm
NTC Probe alarm
Input of flowswitch
alarm
Input of
changeable digital
S7S input
Input of high
pressure or
discharge protector
or overcurrent
alarm
Input of low
pressure switch
alarm
Input of
changeable digital
S9S input
Output of
compressor 1
Output of
compressor 2
Output of pump
Output of reversing
valve
Output of alarm
On or off
Cooling or heating
(*) D=digital.
1=A1, HP1, or LP1 alarm codes active
0=no alarm code active
1=FL alarm code
0=no alarm code active
1=E1, E2, or E3 alarm
codes
0=no alarm code active
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=closed
0=open
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=on 0=off
1=cooling
0=heating
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read/
write
Read/
write
Modbus address
Parameter
type
41 D
45 D
46 D
53 D
54 D
55 D
56 D
57 D
59 D
60 D
61 D
62 D
63 D
64 D
65 D
(*)
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
14
TROUBLESHOOTING
This section provides useful information for diagnosing and correct­ing certain troubles which may occur in the unit.
Before starting the trouble shooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
Before contacting your local dealer, read this chapter carefully, it will save you time and money.
When carrying out an inspection on the supply panel or on the switch box of the unit, always make sure that the circuit breaker of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circum­stances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem cannot be found, call your local dealer.
Symptom 1: The unit does not start, but the L LED lights up
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
Power supply failure. Check the voltage on the supply
Blown fuse or interrupted protection device.
Loose connections. Inspect connections of the field
Shorted or broken wires. Test circuits using a tester and repair
Symptom 2: The unit does not start, but the
POSSIBLE CAUSES CORRECTIVE ACTION
The flowstart timer is still running. The unit will start after approx.
The anti-recycling timer is still active. The circuit can only start up after
The guard timer is still active. The circuit can only start up after
Symptom 3: The unit does not start and the
POSSIBLE CAUSES CORRECTIVE ACTION
One of the following safety devices is activated:
•Reverse phase protector
•Overcurrent relay (K*S)
• Discharge thermal protector (Q*D)
•Evaporating temperature thermostat (S*T)
• Flow switch (S10L)
• High pressure switch (S*HP)
The unit is in anti-freeze alarm. Check on the controller and refer to
The remote ON/OFF input is enabled and the remote switch is off.
The keyboard is locked. The user parameter h09 is set to 0.
Check the controller setpoint.
panel. Inspect fuses and protection devices.
Replace by fuses of the same size and type (refer to chapter "Electrical specifications" on page 2).
wiring and the internal wiring of the unit. Tighten all loose connections.
if necessary.
L LED is flashing
15 seconds. Make sure that water is flowing through the evaporator.
approximately 6 minutes.
approximately 1 minute.
L LED does not light up
Check on the controller and refer to symptom "4. One of the following safety devices is activated". Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 9.
symptom "4. One of the following safety devices is activated". Refer to the explanation of the digital controller in the chapter "Resetting alarms" on page 9
Put the remote switch on or disable the remote ON/OFF input.
Unlock the controller keyboard.
Symptom 4: One of the following safety devices is activated
Symptom 4.1: Overcurrent relay of compressor
POSSIBLE CAUSES CORRECTIVE ACTION
Failure of one of the phases. Check fuses on the supply panel or
Voltage too low. Measure the supply voltage. Overload of motor. Reset. If the failure persists, call your
RESET Push the red button on the over-
Symptom 4.2: Low pressure switch or anti-freeze alarm
POSSIBLE CAUSES CORRECTIVE ACTION
Water flow to water heat exchanger too low.
Shortage of refrigerant. Check for leaks and refill refrigerant,
Unit is working out of its operation range.
Inlet temperature to the water heat exchanger is too low.
Flow switch is not working or no water flow.
RESET After pressure rise, the low pressure
Symptom 4.3: High-pressure switch
POSSIBLE CAUSES CORRECTIVE ACTION
Condenser fan does not operate properly.
Dirty or partially blocked condenser. Remove any obstacle and clean
Inlet air temperature of the condenser is too high.
RESET After pressure decrease, the high
Symptom 4.4: Reverse phase protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Tw o phases of the power supply are connected in the wrong phase position.
One phase is not connected properly.
RESET After inverting two phases or fixing
Symptom 4.5: Discharge thermal protector is activated
POSSIBLE CAUSES CORRECTIVE ACTION
Unit is working outside the operation range.
RESET After temperature decrease, the
Symptom 4.6: Flow switch is activated
POSSIBLE CAUSES CORRECTIVE ACTION
No water flow. Check the water pump.
RESET After finding the cause, the flow
measure the supply voltage.
local dealer.
current relay inside the switch box. The controller still needs to be reset.
Increase the water flow.
if necessary. Check the operation conditions of
the unit. Increase the inlet water temperature.
Check the flow switch and the water pump.
switch resets automatically, but the controller still needs to be reset.
Check that the fans turn freely. Clean if necessary.
condenser coil using brush and blower.
The air temperature measured at the inlet of the condenser should not exceed 43°C.
pressure switch resets automatically, but the controller still needs to be reset.
Invert two phases of the power supply (by licensed electrician).
Check the connection of all phases.
the power supply cables properly, the protector is reset automatically, but the unit still needs to be reset.
Check the operation condition of the unit.
thermal protector resets automatically but the controller still needs to be reset.
switch is reset automatically, but the controller still needs to be reset.
Operation manual
15
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
Symptom 5: Unit stops soon after operation
POSSIBLE CAUSES CORRECTIVE ACTION
One of the safety devices is activated.
Voltage is too low. Test the voltage in the supply panel
Symptom 6: Unit runs continuously and the water temperature remains higher than the temperature set on the controller
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting on the controller is too low.
The heat production in the water circuit is too high.
Water flow is too high. Recalculate the water flow.
Symptom 7: Excessive noises and vibrations of the unit
POSSIBLE CAUSES CORRECTIVE ACTION
Unit has not been fixed properly. Fix the unit as described in the
Check safety devices (refer to symptom "4. One of the following safety devices is activated").
and, if necessary, in the electrical compartment of the unit (voltage drop due to supply cables is too high).
Check and adjust the temperature setting.
The cooling capacity of the unit is too low. Call your local dealer.
installation manual.
MAINTENANCE
In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
If the unit is used for air conditioning application, the described checks should be executed at least once a year. In case the unit is used for other applications, the checks should be executed every 4 months.
Maintenance activities
The wiring and power supply must be checked by a licensed electrician.
Field wiring and power supply
• Check the power supply voltage on the local supply panel. The voltage should correspond to the voltage marked on the identifi­cation label of the unit.
• Check the connections and make sure they are properly fixed.
• Check the proper operation of the circuit breaker and the earth leak detector provided on the local supply panel.
Internal wiring of the unit Visually check the switch box on loose connections (terminals
and components). Make sure that the electrical components are not damaged or loose.
Earth connection Make sure that the earth wires are still connected properly and
that the earth terminals are tightened.
Refrigerant circuit
• Check for leaks inside the unit. In case a leak is detected, call
your local dealer.
• Check the working pressure of the unit. Refer to paragraph
"Switching the unit on" on page 8.
Compressor
• Check on oil leaks. If there is an oil leak, call your local dealer.
• Check for abnormal noises and vibrations. If the compressor is
damaged, call your local dealer.
Water supply
• Check if the water connection is still well fixed.
• Check the water quality (refer to the installation manual of the unit
for specifications of the water quality).
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Do never clean the unit with water under pressure.
Important information regarding the refrigerant used
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.
Refrigerant type: R410A
(1)
GWP
value: 2090
(1)
GWP = global warming potential
Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Operation manual
16
ANNEX I
Saturated temperature
The figures below represent the average saturated temperature of R410A in relation to the pressure readout.
High pressure side
NOTES
Low pressure side
conditions:
- high pressure = 20 bar
- subcool = 3°C
Operation manual
17
Condenserless water-cooled water chillers
EWLQ014~064KBW1N
DEOMHP0110817EU
MENU OVERVIEW
DC
2"
DC
2"
2"
C
B
A
A
C/
D
B
C D
C
D
C
DC D
C
D
C
D
C
D
C
D
C
D
C D
C
D
C D
C
D
C
D
C
D
C
D
B
A
B
B
=
A
=
A
D
C
D
B
5"
A+B
/
S
5"
CD
Select and read parameter
Sensor readout menu
(
b01
/b02/b03)
confirm
cancel
Main display
(*) l-p function is not used.
EWLQ014~064KBW1N
Condenserless water-cooled water chillers
DEPMHP0110817EU
Enter
password
Select
parameter
setting
values s-p
or levels
l-p
(*)
Select
parameter
group
Select
parameter
Read and
modify
parameter
Operation manual
18
EWLQ014KBW1N EWLQ064KBW1N EWLQ025KBW1N EWLQ033KBW1N EWLQ049KBW1N
Wassergekühlte Kaltwassererzeuger ohne
Verflüssiger
Bedienungsanleitung
INHALTSVERZEICHNIS Seite
Einleitung .......................................................................................... 1
Technische Daten ...................................................................................... 2
Technische Daten zur Elektrik ................................................................... 2
Beschreibung ....................................................................................3
Funktion der Hauptkomponenten .............................................................. 4
Schutzvorrichtungen.................................................................................. 4
Innenverkabelung – Teileübersicht ............................................................ 5
Vor der Inbetriebnahme..................................................................... 6
Kontrollen vor der erstmaligen Inbetriebnahme......................................... 6
Wasserzufuhr............................................................................................. 6
Netzanschluss und Kurbelwannenheizung................................................ 6
Allgemeine Empfehlungen......................................................................... 6
Betrieb............................................................................................... 6
Digitalregler................................................................................................ 7
Arbeiten mit den Einheiten......................................................................... 8
Erweiterte Funktionen des Digitalreglers................................................. 11
Modbus für BMS-Verbindung .......................................................... 14
Allgemeine Beschreibung des Modbus-Protokolls................................... 14
Implementierter Fehlercode..................................................................... 15
Festlegen der Einstellung des Gebäudeverwaltungssystems ................. 15
Var iablendatenbank................................................................................. 15
Fehlerbeseitigung............................................................................ 16
Wartung........................................................................................... 17
Wichtige Informationen hinsichtlich des verwendeten Kältemittels ......... 17
Wartungsarbeiten .................................................................................... 17
Vorschriften zur Entsorgung .................................................................... 17
Anhang I.......................................................................................... 18
Sättigungstemperatur .............................................................................. 18
Menüüberblick................................................................................. 19
EINLEITUNG
Diese Bedienungsanleitung bezieht sich auf die kompakten wasser­gekühlten Kaltwassererzeuger (ohne Verflüssiger) der Baureihen Daikin EWLQKB. Diese Einheiten sind für die Anwendung in geschlossenen Räumen vorgesehen und werden zum Kühlen verwendet. Die Einheiten der Baureihe EWLQ lassen sich mit Verdampfereinheiten oder Luftbehandlungsgeräten von Daikin zur Klimatisierung kombinieren. Sie können zudem zur Versorgung mit Kühlwasser zur Verfahrenskühlung eingesetzt werden.
Diese Anleitung wurde erarbeitet, um eine ordnungsgemäße Funktion und Wartung der Einheit zu gewährleisten. Sie beschreibt die sachgemäße Bedienung der Einheit und gibt bei etwaigen Problemen Hilfestellung. Die Einheit ist zwar mit Schutzvorrichtungen ausgestattet; diese verhindern jedoch nicht automatisch alle Probleme, die auf unsachgemäße Bedienung oder Wartung zurück­zuführen sind.
Wenden Sie sich bei hartnäckigen Störungen an Ihren Daikin-Händler.
Achten Sie vor dem ersten Einschalten der Einheit darauf, dass sie korrekt installiert wurde. Lesen Sie sich hierzu die mit der Einheit ausgelieferte Installationsanleitung und die Empfehlungen unter "Kontrollen vor der Erstinbetrieb­nahme" sorgfältig durch.
LESEN SIE SICH DIESE ANLEITUNG SORGFÄLTIG DURCH, BEVOR SIE DIE EINHEIT IN BETRIEB NEHMEN. WERFEN SIE SIE NICHT WEG. BEWAHREN SIE SIE AUF, SO DASS SIE AUCH SPÄTER NOCH DARIN NACHSCHLAGEN KÖNNEN. Lesen sie sich unbedingt das Kapitel "Betrieb" auf Seite 6 durch, bevor sie diese Parameter ändern.
Bei der englischen Fassung der Anleitung handelt es sich um das Original. Bei den Anleitungen in anderen Sprachen handelt es sich um Übersetzungen des Originals.
Das Gerät ist nicht konzipiert, um von folgenden Personengruppen einschließlich Kindern benutzt zu werden: Personen mit eingeschränkten körperlichen, sensorischen oder geistigen Fähigkeiten oder Personen mit mangelhafter Erfahrung oder Wissen, es sei denn, sie sind von einer Person, die für ihre Sicherheit verantwortlich ist, darin unterwiesen worden, wie das Gerät ordnungsgemäß zu verwenden und zu bedienen ist. Kinder sollten so beaufsichtigt werden, dass gewährleistet ist, dass sie nicht mit dem Gerät spielen.
Bedienungsanleitung
1
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU
Technische Daten
Allgemeines EWLQ 014 033
(1)
025
Abmessungen HxBxT (mm) 600x600x600 Maschinengewicht
(kg)
104 138 149
Anschlüsse
• Gasleitungsanschlus s am Verflüssiger (Kupfer)
• Flüssigkeitsleitungs­anschluss am Verflüssiger (Kupfer)
Allgemeines EWLQ 049 064
5/8" 3/4" 3/4"
5/8" 5/8" 5/8"
Abmessungen HxBxT (mm) 600x600x1200 Maschinengewicht
(kg)
252 274
Anschlüsse
• Gasleitungsanschlus s am Verflüssiger (Kupfer)
• Flüssigkeitsleitungs­anschluss am Verflüssiger (Kupfer)
Verdichter EWLQ 014 033
Modell Drehzahl
3/4" 3/4"
5/8" 5/8"
025
JT140LP8Y1 JT236DJY1 JT315DJY1
(rpm)
2900
Öltyp FVC68D
(l)
Ölfüllmenge Kältemitteltyp
Verdampfer
1,5 3,0 3,0
R410A
Ty p messingverlöteter Platten-Wärmetauscher Mindestwasser-
menge Wasserdurchfluss-
bereich
Verflüssiger
(l) 62 103 155
(l/min) 31~75 53~123 76~186
weitere Informationen finden Sie in den vom Hersteller Ihres separaten Verflüssigers bereit gestellten technischen Daten
Verdichter EWLQ 049 064
Modell Drehzahl
2xJT236DJY1 2xJT315DJY1
(rpm)
2900 Öltyp FVC68D Ölfüllmenge Kältemitteltyp
Verdampfer
(l) 2 x 3,0 2 x 3,0
R410A
Ty p messingverlöteter Platten-Wärmetauscher Mindestwasser-
menge Wasserdurchfluss-
bereich
Verflüssiger
(l)
205 311
(l/min) 101~247 152~373
weitere Informationen finden Sie in den vom Hersteller Ihres separaten Verflüssigers bereit gestellten technischen Daten
014
(2)
025
Technische Daten zur Elektrik
Modell EWLQ
Netzanschluss
• Phase
•Frequenz
• Spannung
• Spannungstoleranz
• Empfohlene Sicherungen (aM) 16gG 25gG 25gG
(Hz)
(V)
(%)
3N~
50 400 ±10
Verdichter
• Phase
•Frequenz
• Spannung
• Nennbetriebsstrom (A) 6,5 10,5 15,0
(Hz)
(V)
3~
50 400
Steuerung
• Phase
•Frequenz
• Spannung
• Empfohlene Sicherungen (aM)
Modell EWLQ
(Hz)
(V)
049 064
1~
50 230
werkseitig installiert
Netzanschluss
• Phase
•Frequenz
• Spannung
• Spannungstoleranz
• Empfohlene Sicherungen (aM) 40gG 50gG
(Hz)
(V)
(%)
3N~
50 400 ±10
Verdichter
• Phase
•Frequenz
• Spannung
• Nennbetriebsstrom (A) 10,5 15,0
(Hz)
(V)
3~
50 400
Steuerung
• Phase
•Frequenz
• Spannung
• Empfohlene Sicherungen (aM)
(Hz)
(V)
1~
50 230
werkseitig installiert
033
(1) Die vollständigen technischen Daten sind dem technischen Datenbuch zu
entnehmen.
EWLQ014~064KBW1N
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
DEOMHP0110817EU
(2) Die vollständigen technischen Daten sind dem technischen Datenbuch zu
entnehmen.
Bedienungsanleitung
2
BESCHREIBUNG
Die wassergekühlten Kaltwassersätze der Baureihe EWLQ sind in 5 Standardgrößen erhältlich.
EWLQ049~064KBW1N
17
2
13 14 15 16
EWLQ014~033KBW1N
500
2
3
500
14
9
11
7 8
12 12
Abbildung: Hauptkomponenten
1 Verdichter 2 Verdampfer 3 Akkumulator 4 Schaltkasten 5 Kaltwasser ein 6 Kaltwasser aus 7 Absperrventil der Gasleitung 8 Absperrventil der Flüssigkeitsleitung
9 Wassertemperaturfühler am Verdampfereingang 10 Frostschutzsensor 11 Steuerung mit digitaler Anzeige 12 Netzanschluss 13 Kugelventil (bauseitig) 14 Wasserfilter (bauseitig) 15 Entlüftungsventil (bauseitig) 16 T-Anschluss für Luftaustritt (bauseitig) 17 Strömungsschalter (mit T-Anschluss) (bauseitig) 18 Hauptschalter
500
3
1
1
3
4
500
5
11
10
500
500
500
500
759
866 1818
10
Für Wartung erforderlicher Abstand um die Einheit
Bedienungsanleitung
3
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU
Funktion der Hauptkomponenten
EWLQ014~033KBW1N
EWLQ049~064KBW1N
64
13
5
12
14
R3T
R4T
R3T
R4T
S4LP
S5LP
S4LP
1
M1C
LP
HP
3 7
M2C
LP
HP
M1C
LP
HP
S1HP
Q1D
2
8 9
S2HP
Q2D
S1HP
Q1D
10111513
Abbildung: Funktionsplan
1 Verdichter 9 Absperrventil der Flüssigkeitsleitung 2 Filter 10 Absperrventil der Gasleitung 3 Expansionsventil 11 Akkumulator 4 Verdampfer 12 Strömungsschalter (im Lieferumfang der Einheit, am Montageort installiert) 5 Wasserauslass Verdampfer 13 Kugelventil (im Lieferumfang der Einheit, am Montageort installiert) 6 Wassereinlass Verdampfer 14 Wasserfilter (im Lieferumfang der Einheit, am Montageort installiert) 7 Schauglas 15 Entlüftungsventil (im Lieferumfang der Einheit, am Montageort installiert) 8 Magnetventil der Flüssigkeitsleitung Bauseitige Rohrleitung
Beim Durchlauf durch die Einheit ändert sich die Beschaffenheit des
Schutzvorrichtungen
Kältemittels. Diese Änderungen werden durch die folgenden Hauptkomponenten verursacht:
Verdichter Der Verdichter (M*C) arbeitet wie eine Pumpe und lässt das
Kältemittel im Kältemittelkreislauf zirkulieren. Er verdichtet den Kältemitteldampf aus dem Verdampfer, und zwar mit einem Druck, mit dem er am leichtesten im Verflüssiger verflüssigt werden kann.
Filter Der hinter dem Verflüssiger installierte Filter filtert kleine Partikel
aus dem Kältemittel heraus, so dass ein Verstopfen der Rohre verhindert wird.
Expansionsventil Das flüssige Kältemittel, das aus dem Verflüssiger kommt,
gelangt über ein Expansionsventil in den Verdampfer. Das Expansionsventil bringt das flüssige Kältemittel auf einen Druck, bei dem es im Verdampfer leicht verdampft werden kann.
Verdampfer Die wichtigste Funktion des Verdampfers ist es, die Wärme aus
dem Wasser, das durch ihn fließt, abzuziehen. Dies geschieht durch Umwandlung des flüssigen Kältemittels aus dem Verflüssiger in gasförmiges Kältemittel.
Anschlüsse für Wassereinlass und Wasserauslass Die Anschlüsse für Wassereinlass und Wasserauslass ermöglichen
einen einfachen Anschluss der Einheit an den Wasserkreislauf des
Die Einheit ist mit allgemeinen Schutzvorrichtungen ausgestattet: Diese Vorrichtungen schalten sämtliche Schaltkreise sowie die gesamte Einheit ab.
E/A-Leiterplatte (A2P) (Eingang/Ausgang) Die E/A-Leiterplatte (A2P) ist mit einem Phasenumkehrschutz ausgestattet.
Dieser Phasenumkehrschutz erkennt, wenn die 3 Phasen der Stromversorgung richtig angeschlossen wurden. Wenn eine Phase nicht angeschlossen oder wenn 2 Phasen vertauscht wurden, kann die Einheit nicht eingeschaltet werden.
Überstromrelais Das Überstromrelais (K*S) befindet sich im Schaltkasten der
Einheit und schützt den Verdichtermotor bei Überlastung, Phasenausfall oder bei zu niedriger Spannung. Das Relais wurde werksseitig eingestellt und darf nicht verstellt werden. Ist es aktiviert, muss die Rücksetzung über den Schaltkasten erfolgen. Anschließend muss der Regler manuell zurückgesetzt werden.
Hochdruckschalter Der Hochdruckschalter (S*HP) ist an der Gasleitung der Einheit
eingebaut und misst den Verflüssigerdruck (Druck am Austritt des Verdichters). Steigt der Druck zu sehr an, wird der Druckschalter aktiviert, und der Schaltkreis wird unterbrochen.
Nach Aktivierung wird der Schalter automatisch zurückgesetzt. Der Regler muss jedoch noch manuell zurückgesetzt werden.
Luftbehandlungsgeräts oder an industrielle Anlagen.
EWLQ014~064KBW1N
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
DEOMHP0110817EU
Bedienungsanleitung
4
Niederdruckschalter Der Niederdruckschalter (S*LP) ist am Saugrohr der Einheit
installiert und misst den Verdampferdruck (Druck am Verdichtereingang). Ist der Druck zu niedrig, wird der Druckschalter ausgelöst und der Stromkreis unterbrochen.
Nach Aktivierung wird der Schalter automatisch zurückgesetzt. Der Regler muss jedoch noch manuell zurückgesetzt werden.
Austrittsthermoschutz Der Austrittsthermoschutz (Q*D) spricht bei einem übermäßigen
Anstieg der Kältemitteltemperatur bei Austritt aus dem Verdichter an. Hat die Temperatur wieder den normalen Wert erreicht, setzt sich der Thermoschutz automatisch zurück. Der Regler muß jedoch manuell zurückgesetzt werden.
Frostschutzsensor Der Fühler für die Wassertemperatur bei Austritt (R4T) misst die
Temperatur des Wassers am Ausgang des Wasserwärme­tauschers. Die Schutzvorrichtung unterbricht den Schaltkreis, wenn die Temperatur des gekühlten Wassers zu stark absinkt, um ein Einfrieren des Wassers während des Betriebs zu verhindern.
Hat die Wassertemperatur bei Austritt wieder den normalen Wert erreicht, wird die Schutzvorrichtung automatisch zurückgesetzt. Der Regler muss anschließend noch manuell zurückgesetzt werden.
Sicherung für Regelkreis (F1U) Die Sicherung für den Regelkreis schützt die Kabel des Regelkreises und der Reglerkomponenten bei Kurzschlüssen.
Sicherung für Regelkreis (F4) Die Sicherung für den Regelkreis schützt die Kabel des Regelkreises bei einem Kurzschluss.
Sicherung für Digitalregler (F3U) Diese Sicherung schützt die Kabel des Digitalreglers sowie den Regler selbst bei Kurzschlüssen.
Strömungsschalter (im Lieferumfang der Einheit, am Montageort installiert) Der Strömungsschalter misst den Wasserfluss im Kreislauf. Wenn der Wasserfluss den erforderlichen Wert nicht erreicht, wird die Einheit abgeschaltet.
Kugelventil (im Lieferumfang der Einheit, am Montageort installiert) Vor und hinter dem Wasserfilter ist ein Kugelventil angebracht, so dass ein Reinigen des Filters möglich ist, ohne den Wasserkreislauf entleeren zu müssen.
Wasserfilter (im Lieferumfang der Einheit, am Montageort installiert) Der im vorderen Teil der Pumpe installierte Filter entfernt Schmutzpartikel aus dem Wasser, um eine Beschädigung der Einheit oder eine Verstopfung des Verdampfers oder Verflüssigers zu verhindern. Das Wasserfilter muss in regelmäßigen Abständen gereinigt werden.
Entlüftungsventil (im Lieferumfang der Einheit, am Montageort installiert) Die im Wassersystem des Kaltwassererzeugers verbliebene Luft wird über dieses Ventil automatisch evakuiert.
Innenverkabelung – Teileübersicht
Siehe den der Einheit beiliegenden Innenverdrahtungsplan. Die verwendeten Abkürzungen sind nachfolgend aufgeführt:
A1P.................... PCB: Leiterplatte des Reglers
A2P.................... PCB: E/A-Leiterplatte (Eingang/Ausgang)
A3P............. ** ... PCB: Adresskarte für BMS
A5P,A6P......** ... PCB: Softstarter für Kreislauf 1, Kreislauf 2
A7P............. ** ... PCB: Fernbedienung
A71P.................. PCB: Stromversorgungskarte
A72P.................. PCB: Fernbedienung
E1H,E2H............ Kurbelgehäuseheizung Kreislauf 1, Kreislauf 2
F1,F2,F3.....# .... Hauptsicherungen für die Einheit
F4 ...............*..... Sicherung E/A PCB
F5 ...............## .. Träge Sicherung
F6 ...............# .... Sicherung für Pumpenschütz
F1U.................... Sicherung E/A PCB
F3U.................... Sicherung für Regler PCB
H3P.............*..... Anzeigelampe Alarm
H4P.............*..... Anzeigelampe Betrieb Verdichter 1
H5P.............*..... Anzeigelampe Betrieb Verdichter 2
H6P.............*..... Anzeigelampe, allgemeiner Betrieb
K1F,K2F ......# .... Hilfsschütz für Lüftermotoren
K1M,K2M........... Verdichterschütz Kreislauf 1, Kreislauf 2
K4S,K5S............ Überstromrelais Kreislauf 1, Kreislauf 2
K6S............. * ..... Überstromrelais Pumpe
K1P............. * ..... Pumpenstecker
M1C,M2C .......... Verdichtermotor Kreislauf 1, Kreislauf 2
PE...................... Haupterdungsklemme
Q1D,Q2D........... Austrittsthermoschutz Kreislauf 1, Kreislauf 2
R3T.................... Wassertemperaturfühler Verdampfereingang
R4T.................... Wassertemperaturfühler Verdampferausgang
R5T.................... Temperaturfühler Verflüssigereingang
S1HP,S2HP ....... Hochdruckschalter Kreislauf 1, Kreislauf 2
S4LP,S5LP......... Niederdruckschalter Kreislauf 1, Kreislauf 2
S7S............. * ..... Schalter für Fernwahl Kühlung/Heizung
dualen Sollwert
S9S............. * ..... Schalter für Fern-Start/Stopp
Sollwert
S10L .................. Strömungsschalter
S12M ................. Haupttrennschalter
TR1.................... Trafo 230 V 24 V zur Stromversorgung der
Leiterplatte des Reglers
TR2.................... Trafo 230 V 24 V zur Stromversorgung der E/A-
Leiterplatte (A2P)
Y3R.................... Umkehrventil
Y1S, Y2S ........... Magnetventil der Flüssigkeitsleitung
X1~3,X1~82A .... Anschlüsse
Nicht in der Standardausführung
Nicht als Option lieferbar Als Option lieferbar
Verbindlich # ##
Nicht verbindlich * **
(1)
(1)
(1)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
(2)
oder
(2)
oder dualen
Bedienungsanleitung
5
(1) sonderzubehör (2) bauseitig
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU
VOR DER INBETRIEBNAHME
Kontrollen vor der erstmaligen Inbetriebnahme
Überprüfen Sie, ob der Hauptschalter der Einheit auf der Ver teilertafel ausgeschaltet ist.
Überprüfen Sie nach der Installation der Einheit und vor dem Einschalten des Hauptschalters folgende Punkte:
1 Bauseitige Verkabelung
Überprüfen Sie, ob die bauseitige Verdrahtung gemäß den in der Installationsanleitung enthaltenen Anleitungen, den Elektro­schaltplänen und den europäischen und nationalen Vorschriften durchgeführt wurde.
2 Sicherungen oder Schutzvorrichtungen
Überprüfen Sie, ob Größe und Ausführung der Sicherungen oder der bauseitig installierten Schutzvorrichtungen der Installationsanleitung entsprechen. Achten Sie außerdem darauf, dass keine Sicherung und keine Schutzvorrichtung überbrückt wurde.
3 Erdung
Achten Sie darauf, dass die Erdungsleitungen ordnungsgemäß angeschlossen und die Erdungsklemmen festgezogen sind.
4 Innenverkabelung
Überprüfen Sie den Schaltkasten auf lose Verbindungen oder beschädigte elektrische Bauteile.
5 Ver ankerung
Überprüfen Sie, ob die Einheit ordnungsgemäß verankert wurde, um bei Inbetriebnahme ungewöhnliche Betriebs­geräusche und Vibrationen zu vermeiden.
6 Beschädigte Ausrüstung
Überprüfen Sie die Einheit innen auf beschädigte Teile oder zusammengedrückte Rohrleitungen.
7 Austritt von Kältemittel
Überprüfen Sie das Innere der Einheit auf austretendes Kälte­mittel. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
8 Austritt von Öl
Überprüfen Sie den Verdichter auf austretendes Öl. Ist dies der Fall, verständigen Sie bitte Ihren Händler.
9 Anschlussspannung
Überprüfen Sie die Netzspannung auf der Verteilertafel. Die Spannung muss mit der auf dem Typenschild der Einheit angegebenen Spannung übereinstimmen.
Netzanschluss und Kurbelwannenheizung
Nach einem längeren Stillstand muss die Kurbelwannenheizung mindestens sechs Stunden vor dem Einschalten des Verdichters eingeschaltet werden, um eine Beschädigung des Verdichters zu vermeiden.
Einschalten der Kurbelwannenheizung:
1 Schalten Sie den Leistungsschalter an der Einheit ein. Stellen
Sie sicher, dass die Einheit auf "AUS" steht am Regler.
2 Die Kurbelwannenheizung schaltet sich automatisch ein. 3 Überprüfen Sie die Anschlussspannung an den Netzklemmen
L1, L2, L3 und (N) mit einem Voltmeter. Die Spannung muss der auf dem Typenschild der Einheit angegebenen Spannung entsprechen. Wenn das Voltmeter Werte anzeigt, die nicht den in den technischen Daten aufgeführten Werten entsprechen, müssen die bauseitige Verkabelung überprüft und die Netzkabel bei Bedarf ausgetauscht werden.
4 Überprüfen Sie die LED der Phasenumkehrschutzvorrichtung.
Leuchtet sie, ist die Phasenreihenfolge korrekt. Ist dies nicht der Fall, müssen Sie den Hauptschalter ausschalten und die Adern des Netzkabels von einem zugelasssenen Elektriker in der richtigen Phasenlage anklemmen lassen.
Nach sechs Stunden kann die Einheit in Betrieb genommen werden.
Allgemeine Empfehlungen
Lesen Sie sich vor dem Einschalten der Einheit die folgenden Empfehlungen durch:
1 Schließen Sie alle Frontblenden der Einheit, nachdem sämtliche
Installationsarbeiten und Einstellungen vorgenommen wurden.
2 Die Bedienungstafel des Schaltkastens darf nur von einem
zugelassenen Elektriker zu Wartungszwecken geöffnet werden.
BETRIEB
Die Einheiten der Baureihe EW sind mit einem Digitalregler ausgestattet, der die Inbetriebnahme, die Bedienung und die Wartung der Einheit besonders bedienerfreundlich macht.
Dieser Teil der Anleitung ist funktionsorientiert und modular aufgebaut. Mit Ausnahme des ersten Abschnitts, der einen kurzen Überblick über den Regler selbst vermittelt, behandelt jeder Abschnitt oder Unterabschnitt eine bestimmte Funktion der Einheit.
Wasserzufuhr
Füllen Sie die Wasserleitungen, und halten Sie sich dabei an die für die Einheit erforderliche Mindestwassermenge. Weitere Informationen finden Sie im Kapitel "Füllmenge, Durchfluss und Qualität des Wassers" in der Installationsanleitung.
Achten Sie darauf, dass das Wasser der in der Installationsanleitung aufgeführten Qualität entspricht.
Entlüften Sie die oben gelegenen Stellen des Systems, und überprüfen Sie den Betrieb der Umwälzpumpe und des Strömungsschalters.
Verwenden Sie für das Abdichten der Anschlüsse ein gutes Gewinde-Dichtungsmittel. Die Abdichtung muss den Drücken und den Temperaturen des Systems standhalten können, es muss ebenfalls beständig sein gegenüber dem verwendeten Glykol im Wasser.
Die Außenfläche der Wasserrohre muss entsprechend vor Korrosion geschützt werden
EWLQ014~064KBW1N
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
DEOMHP0110817EU
Bedienungsanleitung
6
Digitalregler
Benutzerschnittstelle
Der Digitalregler verfügt über ein numerisches Display, vier beschriftete Tasten und LED-Anzeigen, mit denen zusätzliche Benutzerinformationen abgerufen werden können.
Abbildung – Digitalregler
Abbildung – Fernbedienung (Optionssatz)
Tasten auf dem Regler:
Welche Funktion beim Drücken einer oder einer Kombination dieser Tasten ausgeführt wird, hängt davon ab, in welchem Status sich Regler und Einheit zu diesem Zeitpunkt befinden.
Digitalregler-
Tasten
AT
BU
A + BS
CC
DD
C + DR
Fernbedienungs-
tasten
Hauptanzeige Sensorausgabemenü Parameterauswahlmenü Parametereinstellmenü
5 Sekunden lang drücken: Zugriff auf DIREKTE Parameter
5 Sekunden lang drücken: A + B ODER Einmal drücken:
S
Zugriff auf BENUTZER-Parameter (nach Eingabe des BENUTZER­Kennworts)
5 Sekunden lang drücken: Einheit in Betriebsart "Heizen" ein-/ ausschalten Einmal drücken: Direkter Zugriff auf Sensorausgabemenü (b01/b02/b03)
5 Sekunden lang drücken: Einheit in Betriebsart "Kühlen" ein-/ ausschalten Einmal drücken: Direkter Zugriff auf Sensorausgabemenü (b01/b02/b03)
5 Sekunden lang drücken: Manuelle Alarmzurücksetzung im Alarmfall
Einmal drücken:
Zurückkehren
Einmal drücken:
Vorherigen
Sensorparameter
auswählen
Einmal drücken:
Nächsten
Sensorparameter
auswählen
Einmal drücken:
Zurückkehren
Einmal drücken:
Parametergruppe oder
Parameter auswählen
Einmal drücken:
Vorherige Parametergruppe
oder vorherigen Parameter
auswählen
Einmal drücken:
Nächste Parametergruppe
oder nächsten Parameter
auswählen
Einmal drücken:
Abbrechen und
zurückkehren
Einmal drücken:
Bestätigen und
zurückkehren
Einmal drücken:
Wert erhöhen
Einmal drücken:
Wert verringern
Bedienungsanleitung
7
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU
LED-Anzeigen auf dem Regler und der Fernbedienung:
Funktion – Hauptanzeige (nicht im Menü)
Digitalregler-LEDs Fernbedienung Hauptanzeige
P
F
G
H
L
M
&
é
LED (grün)
LED
(bernsteinfarben)
LED
(bernsteinfarben)
LED (rot)
LED
(bernsteinfarben)
LED
(bernsteinfarben)
LED
(bernsteinfarben)
LED
(bernsteinfarben)
Z Wassertemperatur bei Eintritt.
F
G
Y
L
M
&
é
Zeigt an, dass der Heizbetrieb aktiviert ist.
Zeigt an, dass der Kühlbetrieb aktiviert ist.
Zeigt an, dass der Alarm aktiviert ist.
Zeigt den Status der Pumpe an
Zeigt an, dass mindestens ein Verdichter aktiviert ist.
LED leuchtet ständig: Zeigt an, dass Verdichter 1 aktiv ist. LED blinkt: Zeigt eine Startanforderung von Verdichter 1 an.
LED leuchtet ständig: Zeigt an, dass Verdichter 2 aktiv ist. LED blinkt: Zeigt eine Startanforderung von Verdichter 2 an.
Beim Auswählen einer Parametergruppe oder eines Parameters werden verschiedene LEDs in Bezug auf die Parametergruppe oder den Parameter angezeigt.
Beispiel: Die LEDs F und G werden beim Zugriff auf eine Parametergruppe oder beim direkten Zugriff auf Parameter angezeigt.
HINWEIS
Temperaturausgabetoleranz: ±1°C. Durch Einstrahlung von direktem Sonnenlicht kann die
Lesbarkeit des numerischen Displays beeinträchtigt werden.
Direkte Parameter und Benutzerparameter
Der Digitalregler stellt direkte Parameter und Benutzerparameter zur Verfügung. Die direkten Parameter sind für den täglichen Einsatz der Einheit wichtig, beispielsweise zum Einstellen der Temperatur oder zum Abrufen von aktuellen Betriebsinformationen. Die Benutzer­parameter bieten andererseits erweiterte Funktionen wie das Einstellen von Zeitverzögerungen.
Jeder Parameter wird durch einen Code und einen Wert definiert. Der Parameter, mit dem beispielsweise die lokale Regelung oder Fernregelung Ein/Aus ausgewählt wird, hat den Code h07 und den Wert 1 oder 0.
Einen Überblick über die Parameter finden Sie unter "Übersicht über die direkten Parameter und Benutzerparameter" auf Seite 11.
Arbeiten mit den Einheiten
Dieses Kapitel behandelt den alltäglichen Betrieb der Einheiten des Typs EWLQ. Es erläutert Ihnen unter anderem die folgenden Routinefunktionen:
"Einschalten der Einheit" auf Seite 8 und "Ausschalten der Einheit" auf Seite 9,
"Ändern der Temperatureinstellung für den Kühlbetrieb" auf Seite 9,
"Abrufen der aktuellen Betriebsinformationen" auf Seite 9,
"Rücksetzen bei einer Störung" auf Seite 9,
"Zurücksetzen von Warnmeldungen" auf Seite 10.
Einschalten der Einheit
Um die Einheit im Kühlbetrieb einzuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste D, die LED G
wird angezeigt.
Um die Einheit im Heizbetrieb einzuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste C, die LED F
wird angezeigt.
Dann wird in beiden Fällen ein Initialisierungszyklus gestartet, die LED L, die LED M, die LED & und die LED é leuchten je nach der programmierten Thermostatfunktion.
Wenn die LED & oder die LED é blinkt, liegt eine Startanforderung von Verdichter 1 oder 2 vor. Der Verdichter wird gestartet, wenn der Zeitgeber den Wert 0 erreicht hat.
HINWEIS
2 Wenn die Einheit zum ersten Mal in Betrieb genommen wird,
3 Nimmt die Einheit nach einigen Minuten den Betrieb nicht auf,
HINWEIS
Bei Aktivierung der Fernregelung Ein/Aus siehe "Auswählen der lokalen Ein/Aus-Regelung oder Fernregelung Ein/Aus" auf Seite 13.
oder wenn sie über einen längeren Zeitraum nicht in Betrieb war, sollte die folgende Checkliste durchgegangen werden.
Ungewöhnliche Geräusche und Vibrationen
Achten Sie darauf, dass die Einheit keine ungewöhnlichen Geräusche oder Vibrationen verursacht: Überprüfen Sie Ver ankerung und die Leitungen. Erzeugt der Verdichter ungewöhnliche Geräusche, kann dies auch daran liegen, dass zu viel Kältemittel eingefüllt wurde.
Betriebsdruck
Hoch- und Niederdruck des Kältemittelkreislaufs müssen überprüft werden, um den ordnungsgemäßen Betrieb der Einheit zu gewährleisten und um sicherzustellen, dass die Nennleistung erzielt wird.
Die durchschnittliche Sättigungstemperatur des Kältemittels R410A im Verhältnis zum Druckwert kann in "Anhang I" auf Seite 18 nachgeschlagen werden.
Die gemessenen Druckwerte schwanken zwischen einem Höchst- und einem Mindestwert. Dies ist von Wasser- und Außentemperatur abhängig (zum Zeitpunkt der Messung).
lesen Sie sich die Betriebsinformationen durch, die in der Liste der direkten Parameter aufgeführt sind. Siehe auch Kapitel "Fehlerbeseitigung" auf Seite 16.
Bei Fernregelung Ein/Aus (h07=1) wird empfohlen, zusätzlich zum Fernregelungsschalter einen Ein-/Aus­Schalter an der Einheit zu installieren. Die Einheit kann dann von jedem beliebigen Platz aus ausgeschaltet werden.
Die Auswahl des Kühl- oder Heizbetriebs kann nur beim Anfahren des Geräts erfolgen. Die Auswahl der jeweils anderen Betriebsart ist ohne Ausschalten des Geräts nicht möglich.
EWLQ014~064KBW1N
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
DEOMHP0110817EU
Bedienungsanleitung
8
Ausschalten der Einheit
Ändern der Temperatureinstellung für den Kühlbetrieb
Um die Einheit im Kühlbetrieb auszuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste D, die LED G
erlöscht.
Um die Einheit im Heizbetrieb auszuschalten, gehen Sie wie folgt vor:
1 Drücken Sie etwa 5 Sekunden lang die Taste C, die LED F
erlöscht.
HINWEIS
Bei Aktivierung der Fernregelung Ein/Aus siehe "Auswählen der lokalen Ein/Aus-Regelung oder Fernregelung Ein/Aus" auf Seite 13.
Abrufen und Ändern der direkten Parameter
Einen Überblick über die Menüstruktur finden Sie unter "Menüüberblick" auf Seite 19.
1 Drücken Sie 5 Sekunden lang die Taste B in der
Hauptanzeige. Die Parametergruppe -/- wird angezeigt.
2 Drücken Sie die Taste C oder D zum Auswählen der
gewünschten Parametergruppe.
3 Drücken Sie die Taste B zum Eingeben der ausgewählten
Parametergruppe.
4 Drücken Sie die Taste C oder D zum Auswählen des
gewünschten Parameters.
5 Drücken Sie die Taste B zum Abrufen des ausgewählten
Parameters.
6 Drücken Sie zum Erhöhen bzw. Senken des Werts des
ausgewählten Parameters die Taste C oder D. (Nur gültig für Lese-/Schreibparameter.)
7 Drücken Sie die Taste B zum Bestätigen der modifizierten
Einstellung. ODER Drücken Sie die Taste A, um die modifizierte Einstellung nicht zu übernehmen.
8 Drücken Sie die Taste A, um zur Parametergruppe
zurückzukehren.
9 Drücken Sie 2-mal die Taste A, um zur Hauptanzeige
zurückzukehren.
Wenn während einer Maßnahme 30 Sekunden lang keine Taste gedrückt wird, beginnt der angezeigte Parametercode oder Wert zu blinken. Wenn weitere 30 Sekunden lang keine Taste gedrückt wird, wird automatisch wieder die Hauptanzeige eingeblendet, ohne dass modifizierte Parameter gespeichert werden.
Abrufen der Parameter des "Sensorausgabemenüs"
Einen Überblick über die Menüstruktur finden Sie unter "Menüüberblick" auf Seite 19.
Die Parameter b01/b02/b03 sind Teil des "Sensorausgabemenüs".
1 Drücken Sie in der Hauptanzeige die Taste C oder D.
Der Parameter b01 wird angezeigt. Wenn keine Taste gedrückt wird, wird der Wert des Sensors b01 angezeigt, bis C oder D wieder gedrückt wird, um einen anderen Parameter (b02 oder b03) auszuwählen.
2 Drücken Sie die Taste A, um zur Hauptanzeige
zurückzukehren.
Wenn während einer Maßnahme 30 Sekunden lang keine Taste gedrückt wird, beginnt der angezeigte Parametercode oder Wert zu blinken. Wenn weitere 30 Sekunden lang keine Taste gedrückt wird, wird automatisch wieder die Hauptanzeige eingeblendet.
1 Ändern Sie den Kühlungssollwertparameter r1. Dies ist ein direkter Parameter, siehe "Abrufen und Ändern der
direkten Parameter" auf Seite 9.
HINWEIS
Wenn dualer Sollwert aktiviert ist (siehe "Auswählen der dualen Einstellung" auf Seite 13).
Abrufen der aktuellen Betriebsinformationen
Die Liste der direkten Parameter enthält die folgenden Betriebsinformationen:
b01:Wassertemperatur am Verdampfereingang,
b02:Wassertemperatur am Verdampferausgang,
b03: Bei eingeschaltetem Kühlbetrieb: Wassereintritts-
temperatur Verflüssiger. Bei eingeschaltetem Heizbetrieb: Wassereintrittstemperatur des Verdampfers.
c10: Gesamtbetriebsstunden des Verdichters 1,
c11: Gesamtbetriebsstunden des Verdichters 2,
c15: Gesamtbetriebsstunden der Pumpe.
HINWEIS
Dies sind direkte Parameter, siehe "Abrufen und Ändern der direkten Parameter" auf Seite 9.
Die Parameter b01, b02 und b03 können auch über das "Sensorausgabemenü" abgerufen werden. Siehe "Abrufen der Parameter des "Sensorausgabemenüs"" auf Seite 9.
Informationen zum Zurücksetzen der Zeitgeber der Parameter c10, c11 und c15 finden Sie unter "Zurücksetzen von Warnmeldungen" auf Seite 10.
Rücksetzen bei einer Störung
Bei Feststellung einer Störung geschieht Folgendes:
Das Alarmrelais wird aktiviert.
die LED H wird angezeigt
Das Display beginnt zu blinken und zeigt abwechselnd den
Störungs-Code und die Wassertemperatur bei Eintritt an.
Das Display kann die folgenden Störungscodes anzeigen:
a1:zeigt eine Störung der Frostschutzvorrichtung an.
e1:zeigt an, dass der NTC-Fühler zur Messung der
Verdampferwassertemperatur beim Eintritt defekt ist.
e2:zeigt an, dass der NTC-Fühler zur Messung der Verdampferwassertemperatur beim Austritt defekt ist.
e3:zeigt an, dass die Sicherung der Verdampferheizung (F4) durchgebrannt ist, dass ein Phasenumkehrfehler vorliegt oder dass es ein Problem mit der E/A-Leiterplatte (A2P) gibt.
Wenn die Einheit mit einer Frostschutzvorrichtung aus­gestattet ist, ist es empfehlenswert, die Warnlampe für die Ferndiagnose (H3P) zu installieren (siehe den der Einheit beiliegenden Elektroschaltplan). Dadurch kann ein Durchbrennen der Sicherung der Verdampfer­heizung (F4) früher erkannt werden. Außerdem kann so ein Einfrieren des Kreislaufs bei kaltem Wetter vermieden werden.
ehs:zeigt an, dass die Versorgungsspannung zu hoch ist. Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
el1:zeigt einen Fehler bei der Stromversorgung an (Beispiel: Rauschen). Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
Bedienungsanleitung
9
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU
el2:zeigt einen Fehler bei der Stromversorgung an (Beispiel: Rauschen). Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
els:zeigt an, dass die Versorgungsspannung zu niedrig ist. Wenden Sie sich in diesem Fall an einen zugelassenen Elektriker.
epb:zeigt an, dass der EEPROM auf der Leiterplatte des Reglers in der Einheit defekt ist.
epr:zeigt an, dass der EEPROM auf der Leiterplatte des Reglers in der Einheit defekt ist.
fl:zeigt an, dass während der 15 Sekunden, nachdem die Pumpe gestartet wurde, oder während der 5 Sekunden bei aktiviertem Verdichter nur ungenügender Wasser­durchfluss vorhanden war oder dass der Überstromschutz der Pumpe aktiviert wurde.
hp1:zeigt an, dass ein Hochdruckschalter, der Austrittsthermo- schutz oder der Überstromschutz des Verdichtermotors aktiviert oder dass der NTC-Fühler zum Messen der Umgebungstemperatur defekt ist.
fl + hp1:
zeigt an, dass höchstwahrscheinlich ein RPP-Fehler vorliegt oder dass die Sicherung F4 durchgebrannt ist.
lp1:zeigt an, dass der Niederdruckschalter aktiviert ist.
ter:zeigt an, dass ein Datenübertragungsfehler bei der
Fernbedienung vorliegt.
F]]c`e\:
Datenübertragung zwischen dem Digitalregler der Einheit und der Fernbedienung ist gestört. Prüfen Sie die korrekte Auswahl des Parametercodes h23. Dies sollte die Standardeinstellung 0 sein, und prüfen Sie, ob die Installation gemäß der Installationsanleitung der Fernbedienung EKRUMCA korrekt ist.
So setzen Sie die Wartungswarnmeldung hc1 oder hc2 zurück:
1 Rufen Sie c10, Betriebsstunden von Verdichter 1, oder c11,
Betriebsstunden von Verdichter 2, ab. Dies sind direkte Parameter, siehe "Abrufen und Ändern der direkten Parameter" auf Seite 9.
2 Wenn der Parameterwert c10 oder c11 angezeigt wird,
drücken Sie 5 Sekunden lang gleichzeitig die Tasten C und D. Der Wert des Zeitgebers ändert sich auf 0 und der Warnhinweis wird zurückgesetzt.
HINWEIS
Vergessen Sie nicht, nach dem Zurücksetzen der Zeitschaltuhren die erforderlichen Wartungsarbeiten durchzuführen.
Neben den Zeitgebern c10 und c11 kann auch der Zeitgeber c15 (Betriebsstunden der Pumpe) in derselben Weise zurückgesetzt werden.
HINWEIS
Wenn die Störungs-Codes fl und h1 abwechselnd blinken, wird die Störung wahrscheinlich vom Phasenumkehrschutz oder von der durchgebrannten Sicherung für die Verdampferheizung (F4) verursacht.
So setzen Sie einen Alarm zurück:
1 Stellen Sie fest, weshalb die Einheit abgeschaltet wurde, und
beheben Sie die Ursache. Siehe Kapitel "Fehlerbeseitigung" auf Seite 16.
2 Wenn der Störungscode a1, fl, hp1 oder lp1 auf dem
Display angezeigt wird, setzen Sie die Störungsmeldung manuell zurück, indem Sie die E-Kombinationstasten C und D gleichzeitig ca. 5 Sekunden lang drücken.
In allen anderen Fällen wird der Alarm automatisch zurückgesetzt.
Nach Rücksetzen des Alarms werden der Störungscode und die LED H nicht mehr auf dem Display angezeigt. Der Regler setzt seinen normalen Betrieb fort und zeigt die Wassertemperatur bei Eintritt an.
Zurücksetzen von Warnmeldungen
Die Anzeige des Reglers kann im Normalbetrieb zu blinken beginnen und abwechselnd die Wassertemperatur bei Eintritt und folgenden Warncode anzeigen:
hc1:zeigt an, dass Verdichter 1 gewartet werden muss: Die Gesamtbetriebsstunden des Verdichters 1 (direkter Parameter c10) haben die Zeitschaltuhrschwelle für die Wartungswarnmeldung überschritten (Benutzerparameter c14).
hc2:zeigt an, dass Verdichter 2 gewartet werden muss: Die Gesamtbetriebsstunden des Verdichters 2 (direkter Parameter c11) haben die Zeitschaltuhrschwelle für die Wartungswarnmeldung überschritten (Benutzerparameter c14).
EWLQ014~064KBW1N
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
DEOMHP0110817EU
Bedienungsanleitung
10
Erweiterte Funktionen des Digitalreglers
Dieses Kapitel gibt Ihnen einen Überblick über die direkten Parameter und Benutzerparameter, die der Regler bietet. Im folgenden Kapitel erfahren Sie, wie Sie die Einheit über diese Parameter einrichten und konfigurieren können.
Übersicht über die direkten Parameter und Benutzerparameter
Die Liste der direkten Parameter können Sie aufrufen, indem Sie die Taste B ca. 5 Sekunden lang drücken. Siehe auch "Abrufen und Ändern der direkten Parameter" auf Seite 9.
Parameter-
gruppe
Parameter-
code
-/- /23
-a- Kein Benutzerparameter oder direkter Parameter verfügbar
-b-
-c-
-d- Kein Benutzerparameter oder direkter Parameter verfügbar
-f- Kein Benutzerparameter oder direkter Parameter verfügbar
-h-
-p-
-r-
-t- Kein Benutzerparameter oder direkter Parameter verfügbar f-r h99 Softwareversion LD208 G
(*) D=digital, A=analog, G=Ganzzahl. (†) –2,0 und –7,0 nur für Einheiten mit Glykolanwendungen gültig. (‡) Wird verwendet, wenn dualer Sollwert in p09 oder p34 aktiviert ist und der Digitaleingang für dualen Sollwert geschlossen ist.
Maßeinheit
b01 Wassertemperatur am Verdampfereingang 0,1°C L D 102 A b02 Wassertemperatur am Verdampferausgang 0,1°C L D 103 A
Bei eingeschaltetem Kühlbetrieb: Wassereintrittstemperatur des Verflüssigers.
b03
Bei eingeschaltetem Heizbetrieb: Wassereintrittstemperatur des Verdampfers.
Zeitverzögerung zwischen Pumpenstart und
c07
Verdichterstart Zeitspanne zwischen dem Abschalten der
c08
Einheit und dem Abschalten der Pumpe Gesamtbetriebsstunden des Verdichters 1 x100
c10
Gesamtbetriebsstunden des Verdichters 2 x100
c11
Grenzwert für Wartungswarnhinweis
c14
(c10 und c11) Gesamtbetriebsstunden der Pumpe x100
c15
Zum Aktivieren der Fernregelung "Kühlen/ Heizen"
h06
0=nicht aktiv 1=aktiv
(nur wenn p09=9) Zum Aktivieren der Fernregelung Ein/Aus
0=nicht aktiv
h07
1=aktiv
(nur, wenn p34=23) Zum Sperren oder Freigeben der
Reglertastatur
h09
0=sperren 1=freigeben
Serielle Adresse für Verbindung mit
h10
Gebäudeverwaltungssystem Zum Auswählen einer
Adresskartenverbindung
h23
0=Fernbedienungsverbindung 1=MODBUS-Verbindung
Var iable Auswahl der digitalen Eingabe S7S
0=keine Funktion 9=Fernregelung "Kühlen/Heizen"
p09
(nur aktiv in Kombination mit h06) 13=dualer Sollwert – Fernbedienung
KEINE ANDEREN WERTE AUSWÄHLEN Änderbare Auswahl der digitalen
Eingabe S9S
0=Keine Funktion
p34
13=dualer Sollwert aus der Ferne 23=Fernbedienung Ein/Aus (nur aktiv in Kombination mit h07)
KEINE ANDEREN WERTE AUSWÄHLEN
Sollwert für Kühlung
r01 r02 Kühlungsunterschied 3,0 0,3 19,9 0,1°C L/S D 42 A r03 Sollwert für Heizung 30,0 15,0 50,0 0,1°C L/S D 43 A r04 Unterschied beim Heizen 3,0 0,3 19,9 0,1°C L/S D 44 A
r21
Sollwert 2 für Kühlung
r22
Sollwert 2 für Heizung
Beschreibung
0=°C 1=°F
(‡)
(‡)
Standard-
wert
001 L/S B 5 D
15 0 999 1 Sek. L/S B 238 G
00150 1 Min. L/S B 239 G
00100
001 L/S B 14 D
001 L/S B 15 D
101 L/S B 16 D
11200 L/S B 256 G
001 L/S B 11 D
9027 L/S B 277 G
23 0 27 L/S B 329 G
12,0
12,0 30,0 15,0 50,0 0,1°C L/S D 56 A
Min. Max. Einheiten
0,1°C L D 104 A
Stunden
Stunden
x100
Stunden
Stunden
(†)
8,0
8,0
25,0 0,1°C L/S D 41 A
(†)
25,0 0,1°C L/S D 55 A
Lesen/
Schreiben
Benutzerp. /Direkter P.
LD122 A
LD123 A
L/S B 241 G
LD126 A
Modbus­Adresse
Parameter-
(*)
typ
Bedienungsanleitung
11
Wassergekühlte Kaltwassererzeuger ohne Verflüssiger
EWLQ014~064KBW1N
DEOMHP0110817EU