INSTALLATION MANUAL
Multi-zoning base unit 230 V
1 Scope of supply
1x 2x
T4AH
2 About these instructions
These instructions must be read completely and thoroughly before commencing any work with the base. These instructions must be kept and are to be handed over to future users.
https://qr.daikin.eu?N=EKWUFHTA1V3
The following symbols show
a warning with respect to electrical voltage
important information.
3 Safety
3.1 Intended use
The base serves
• the arrangement of a room-by-room temperature control system with a maximum of 10 zones for heating and cooling systems,
• the connection of a maximum of 18 actuators and 10 room control units,
• the connection of actuators with the direction of control action NC (normally closed) or NO (normally open), depending on the thermostat used,
• the connection of an external timer,
• depending on the type used, the connection of a pump or a boiler, a CO signal generator, a temperature limiter or dew point sensor,
a xed installation.
Every other use, modication and conversion is expressly forbidden and leads to
dangers the manufacturer cannot be held liable for.
3.2 Safety notes
All safety notes in these instructions must be observed in order to avoid acci­dents involving personal harm and/or property damage.
WARNING Danger to life due to the electrical voltage at the base station!
• Always disconnect from the mains network and secure against unintended activation before opening.
• Only an authorised electrician may open the device.
• Disconnect external voltages and secure against activation.
• Only use the product if it is in perfect state.
• Do not operate the device without the device cover.
• This unit is not intended to be used by persons (including children) with restrict­ed physical, sensory or mental skills or those who lack experience or knowl­edge. If necessary, these persons must be supervised by a person responsible for their safety or receive instructions from this person on how to use this unit.
• Ensure that children do not play with this device. Children must be super­vised if necessary.
• In case of emergency, disconnect the complete room-by-room temperature control system.
3.3 Personnel-related preconditions
The electrical installation must be performed according to the current national regulations as well as according to the regulations of your local electric power utility company. These instructions presume specialist knowledge corresponding
to an o󰀩cially recognised degree in one of the following professions:
• Systems Mechanic for sanitary, heating and air condition technology
• Electrical Equipment Installer or
• Electronics Engineer
according to the profession designations o󰀩cially announced in the Federal Re­public of Germany, and to comparable professions within the European Com­munity Law.
EKWUFHTA1V3
4 Device overview
4.1 Connections and indications
The following instructions show the full equipment. Individual positions may be omitted depending on the present base.
1
1 Boiler connection 2 Pump connection 3 Protective conductor connection
(only for 230 V) 4 Voltage supply 5 Fuse 6 Temperature limiter or dew point
sensor 7 Reduction channel, external timer
4.2 Technical data
Operating voltage: 230 V ±10 %, 50 Hz Power input 230 V: max. 50 VA Fuse 230 V: T4AH Number of heating zones: 10 Connectable actuators Type EKWCVATR1V3 10 heating zones: max. 18
The following applies to other actuators than those mentioned above Inrush current per actuator: max. 500 mA (for 230 V) Pump/boiler control
Switching power: 2 A, 200 VA inductive Turn-on delay: 2 min Follow-up time fixed/adjustable: Pump protection function: 14 days for 1 minute Control direction: NC or NO Ambient temperature: 0 to +50 °C Storage temperature: -20 to +70 °C Ambient humidity: 80%, not condensing Temperature for ball pressure test: Plastic enclosures: 75 °C Pollution degree: 2 Rated impulse voltage: 1500 V ERP class acc. to EU 811/2013: 1=1 % Protection class 230 V: II Protection type: IP 20 Type action: Type 1 / Type 1.C Dimensions (H x L x D): 90 x 326.5 x 50 mm
4.3 Conformity
This product is labelled with the CE Marking and thus is in compliance with
following regulations:
• 2014/30/EU with amendments “Council Directive on the approximation of the
laws of the Member States relating to Electromagnetic Compatibility”
2014/35/EU with amendments “Council for Coordination of the Regulations
of EU Member Countries regarding the electrical equipment for use within
certain voltage limits”
2011/65/EU “Restriction of the Use of Certain Hazardous Substances in
Electrical and Electronic Equipment” Increased protection requirements may exist for the overall installation, the com­pliance of which is the responsibility of the installer.
6 7 8 9 102 3 4 5
11121314
8 Heating/cooling change-over 9 Thermostat connection 10 LEDs 11 Strain relief 12 Connection of actuators 13 DIP switch 14 Contacts for casing cover with
integrated system clock
2 min / 5 - 15 min
Terminals: 100 °C
1
NC
NO
2 32 3
~
5 Installation
N/L2
CO
A
L/L1
N/L2
CO
A
L/L1
%H
N/L2
L/L1
CO
N L
~
PE
N
L
PE
1
2b 2b
1. Take o󰀨 the cover.
2. Install the base. In case of wall mounting, x the base to the wall with 2 Ø 4 mm screws and corresponding dowels based on the quality of the wall. In case of installation on a mounting bracket, use a TS 35/7.5 bracket.
3. Make the electric connection.
4. Install the cover.
5.1 Select and insert the fuse
21
230 V
2a
3
7 LED signalling
Function Colour Explanation
Pump/boiler Green On: Pump/boiler active
O󰀨: Pump/boiler inactive Flashing: Temperature limiter/dew point sensor active
Mains voltage Green On: Device in operation
O󰀨: Device not in operation Flashing: Valve protection function active (Option)
Fuse Red On: Fuse defective Change over Blue On: Cooling mode active
O󰀨: Heating mode active
Heating zones
1 to 10
Green On: Heating zone active
O󰀨: Heating zone o󰀨
8 Maintenance
8.1 Fuse change
WARNING! Electrical voltage! Danger to life!
• Always disconnect the base from the mains network and secure against unintended activation before opening.
• Disconnect external voltages and secure against unintended activation.
1 32
230 V
T4AH
T4AH
The voltage used must be marked on the
identication plate.
5.2 Parametrization
0min 5min
2 32 3
10min 15min
The control direction is set with jumper 1:
NO operation: Jumper 1 = ON NC operation: Jumper 1 = OFF
The xed follow-up time of 2 minutes of the pump or
the boiler can be increased by an additional 5, 10 or
15 minutes using jumper 2 and 3:
Time Jumper 2 Jumper 3
0 min OFF OFF
5 min OFF ON 10 minutes ON OFF 15 minutes ON ON
8.2 Cleaning
Only use a dry and solvent-free, soft cloth for cleaning.
9 Dismantling
WARNING! Electrical voltage! Danger to life!
• Always disconnect the base from the mains network and secure against unintended activation before opening.
• Disconnect external voltages and secure against unintended activation.
• De-energise the complete installation.
Remove the wiring to all externally connected components.
Remove the base and dispose of it properly, if necessary.
6 Electric connection
For the connection of the voltage supply, the cable sections must be 1.5 mm² for 230 V. Depending on the voltage version of the base, it is possible to take L1 or L and L2 or N, as well as the protective conductor, from the base. A temperature limiter/dew point sensor can be connected to the contact TB/%H in NC operation; this contact cannot be used in NO operation. If no temperature limiter is connected, the connection TB/%H must be bridged (provided for at the factory). The bridge
must be removed as soon as a temperature limiter is connected. The temperature limiter must be a normally closed contact.
The wiring of the thermostats depends on the present ba-
sis. For wiring purposes,
please observe the instruc­tions of the thermostat or of the respective component.
Cable bridge in the parametrization NO operation for all unused thermostat connections.
Digital controller
Analogue thermostat
Actuator
Boiler
Pump
Voltage source
Temperature limiter
System clock
CO
Heating/cooling change-over
Cooling
Heating
This symbol means that electrical and electronic products may NOT be mixed with unsorted household waste. Units must be treated at a specialized treatment facility for reuse, recycling and recovery.
These instructions are protected by copyright. All rights reserved. They may not be copied, reproduced, abbreviated or transmitted, neither in whole nor in parts, in any form, neither mechanically nor electronically, without the previous consent of the manufacturer.
2
4P560992-1 2019.01 Copyright 2019 Daikin