Daikin EKWCVATR1V3 Operation manuals

Daikin EKWCVATR1V3 Operation manuals

ACTUATOR 230 V

EKWCVATR1V3

https://qr.daikin.eu?N=EKWCVATR1V3

ASSEMBLY

"Click"

DISASSEMBLY

PRESS

CONNECTION

L

~ 230 V

N

brown

blue

 

 

<![if ! IE]>

<![endif]>+ 7.0 mm

 

<![if ! IE]>

<![endif]>52.2 mm

<![if ! IE]>

<![endif]>50.3 mm

 

48.4 mm

44.3 mm

First-

“First-Open“ function

 

Open

 

≈0.5 mm

NC

 

 

 

Powerer on

Power off

 

>6minin..

 

NC

Adaption check

Normally

0.5 mm

Closed

 

 

 

Operation mode

 

 

 

Power

 

 

 

on

Technical Specifications:

 

 

Operating voltage:

 

230 V, +10 % … -10 %, 50/60 Hz

Operating capacity:

1 W

Max. inrush current:

< 550 mA for max. 100 ms

Actuating force:

 

100 N +10 %

Type of protection:

 

IP 54

Ambient temperature:

0 °C … 60 °C

Storage temperature:

-25 °C … 60 °C

Stroke:

 

4.0 mm

This symbol means that electrical and electronic products may NOT be mixed with unsorted household waste. Units must be treated at a specialized treatment facility for reuse, recycling and recovery.

By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health.