Daikin EKRTCTRL1, EKRTCTRL2, EKWHCTRL0, EKWHCTRL1, EKPCBO Installation manuals

INSTALLATION MANUAL
Daikin Altherma
heat pump convector options
EKRTCTRL1 EKRTCTRL2 EKWHCTRL0 EKWHCTRL1 EKPCBO
U
I
S
We are sure you will be happy with it because it represents the state of the art in the technology of home air conditioning.
By following the suggestions contained in this manual, the product you have purchased will operate without problems, giving you optimum room temperatures with minimum energy costs.
DAIKIN EUROPE N.V.
Symbols
The pictograms in the next chapter provide the necessary information for correct, safe use of the appliance in a rapid,
Editorial pictograms
User Refers to pages containing instructions or information for the user.
Installer Refers to pages containing instructions or information for the installer.
Safety pictograms
Warning The operation described may cause physical harm if not carried out in accordance with safety regulations.
Dangerous electrical current Make personnel aware that the operation described may lead to electrical shocks if not carried out in accordance with safety regulations.
unmistakable way.
Service Refers to pages containing instructions or information for the CUSTOMER TECHNICAL ASSISTANCE SERVICE installer.
High temperature danger Of safety regulations, the risk of burns caused by contact with components with high temperatures.
Prohibition
Refers to prohibited actions.
2
1 GENERAL
1.1 General warnings ............................................................................4
2 EKRTCTRL1
2.1 Assembly, set-up and connection of on-board control panels ...........................................5
2.2 Assembly ..................................................................................5
2.3 Set-up of auxiliary dip-switch functions B and C ......................................................6
2.4 CP presence contact input connection (only for EKRTCTRL1) ............................................6
2.5 Air temperature probe assembly (only for model EKRTCTRL1) ............................................7
2.6 EKRTCTRL1 connections ......................................................................8
3 EKWHCTRL0
3.1 Continuous modulation circuit board for connecting remote thermostat .....................................9
3.2 LED Indications (Ref. A) ........................................................................9
3.3 EKWHCTRL0 connections ....................................................................10
4 EKWHCTRL1
4.1 Wall-mounted remote control panel assembly EKWHCTRL1 ............................................11
4.2 Spring-loaded terminal connections -AB+ and CP ...................................................12
4.3 CP occupancy contact input connection ..........................................................12
4.4 EKWHCTRL1 Connections ....................................................................13
5 EKRTCTRL2
5.1 Assembly and connections for on-board control panel EKRTCTRL2 ......................................14
5.2 Assembly .................................................................................14
5.3 Air temperature probe assembly ................................................................15
5.4 EKRTCTRL2 Connections .....................................................................15
6 SETUP MENU FOR EKRTCTRL1 - EKWHCTRL1 - EKRTCTRL2
6.1 Setup menu ...............................................................................16
7 EKPCBO
7.1 Assembly and connections for on-board control panel EKPCBO .........................................19
7.2 Assembly .................................................................................19
7.3 EKPCBO Connections .......................................................................20
7.4 Warnings table .............................................................................20
8 VERSIONS WITH CONNECTIONS ON THE RIGH
8.1 Motor connection in versions with hydraulic connections on the right EKREPLH ..............................21
EN
3
SIU
GENERAL
1.1
General warnings
- This instruction is an integral part of the booklet of the appliance on which the kit is installed. Please consult this booklet for general warnings and fundamental safety rules.
- This manual is designed only for the qualified and authorised installation technician, who must be sufficiently trained and in possession of all psycho­physical requirements as per the law.
- All operations must be carried out with care and according to best practices, and in compliance with workplace safety regulations.
- After unpacking, check that the contents are intact and that all parts are included. If not, contact the agent who sold the appliance to you.
- It is forbidden to modify the safety or adjustment devices without authorisation from and indications of the manufacturer.
- It is forbidden to dispose of, or leave in the reach of children, the packaging materials which could become a source of danger.
- Repairs or maintenance must be performed by the Technical Assistance Service or by qualified personnel in accordance with this manual. Do not modify or tamper with the appliance as this could create dangerous situations and the manufacturer will not be liable for any damage caused.
4
SIU
EKRTCTRL1
2.1
Assembly, set-up and connection of on-board control panels
The controllers have two independent clean contacts for controlling a refrigerator unit, a boiler and a presence input. The 2 tube versions have a 230V output to power the summer and winter solenoid valve. The 10 kΩ water temperature probe positioned in the
2.2
Assembly
Slide the control panel into its housing in the upper part of the device and fix it with the two fixing screws (ref. A). To install the connection box:
- open the box (ref. B);
- lock the lower tooth into its hole (ref. C) on the side of the device;
- hook the upper part of the box to the side (ref. D);
- fix it with the two fixing screws (ref. E);
- connect the grounding cable to the fan coil body (ref. M) using the fixing screws (the minimum force that must be applied for tightening screws must be around 2N);
- connect the fast connector of the MOTOR to the other on the board (ref. I) *;
- on the two GRID block terminals (ref. L) there is a bridge that allows the FWXM-series to work without a microswitch.
- For other versions, remove the bridge and connect the two terminals originating on the grill safety microswitch*;
- connect the water probe to the H2 connector on the device.
compartment on the battery regulations the minimum level when heating (30°C) and the maximum level when cooling (20°C). The board also has a function when there is no water probe, in such cases the fan stop thresholds are ignored.
The water temperature probe controls the temperature inside the batteries and determines when the fan starts according to pre-set parameters (minimum operation in winder and maximum in summer).** Check that they are correctly inserted into the compartment on the battery.
- Connect the electrics, tidy cables and fix them with the three clevises supplied (ref. G);
- close the box with the 4 screws (ref. H);
- refit the vanity plate on the side of the unit;
- tighten the upper screws on the control panel;
- place the screw head covers in their housing on the control panel;
* For versions with hydraulic connections on the right,
refer to the relevant paragraph
** The regulation also works without a water probe
connected
EN
A
D
B
C
E
G
H
I
L
M
5
SIU
2.3
Set-up of auxiliary dip-switch functions B and C
There are two dip switches on the controller circuit board for configuring unit operation as per requirements.
- The night-time heating operation logic is modified by using dip switch C:
- in the ON position, the fan is always off, and heats the room using radiation and natural convection, as with traditional radiators; in the off position it operates as a normal fan.
- By positioning dip switch B to ON, when cooling, the fan operates at the minimum speed even after having
2.4
CP presence contact input connection (only for EKRTCTRL1)
On closing the contact connected to the CP input (ref. A) the panel is placed in stand-by mode. If the contact is open the unit is active, if the contact is closed it is deactivated when a key is pressed the symbol flashes.
B
reached the set point, to allow for more uniform operation of the temperature probe and to avoid layering in the air. With the cursor in the OFF position, the functions are cycled (4 minutes ON, 10 minutes OFF).
The input cannot be connected in parallel to that of other electronic boards (use separate contacts).
C
MOTOR
BAOND
LED
LN
C
ASCII
RTU
H4 H2 AIR
N EV1 N EV2
COMM
GRIDGRIDCP
A
CHILLER BOILER
6
SIU
2.5
Air temperature probe assembly (only for EKRTCTRL1)
- To position the temperature probe (ref. A):
- pass the probe through the hole on the shoulder (ref. B)
A
D
- insert the probe into the lower hole (ref. C)
- fix the probe on the relevant hook (ref. D)
C
B
EN
7
SIU
2.6 EKRTCTRL1 connections
H2* water temperature probe (10 kΩ) AIR air temperature probe (10 kΩ) M1 DC inverter fan motor S1 grill safety micro-switch
Y1
Y2
L-N
water solenoid valve (230V/ 50Hz 1A output voltage) mobile flap connection 230V/ 50Hz 1A output voltage. 230V/50Hz electrical power supply
EKRTCTRL1
BO boiler consent output (free contact max 1A)
CH chiller consent output (free contact max 1A)
CP
* If after switching the power on the board
presence input sensor (if closed, the fan coil unit is placed in standby).
detects the H2 probe, start-up occurs in normal conditions with the minimum water temperature when heating (30°C) and maximum when cooling (20°C). The board also has a function when there is no probe, in such cases the fan stop minimum and maximum thresholds are ignored.
8
Loading...
+ 16 hidden pages