Daikin EKMV2C09B7, EKMV3C09B7 Installation manuals

INSTALLATION MANUAL
2-way valve kit/3-way valve kit for fan coil units
EKMV2C09B7 EKMV3C09B7
EKMV2C09B7 EKMV3C09B7
2-way valve kit/3-way valve kit for fan coil units
Installation manual
Read this manual attentively before installation. Do not throw it away. Keep it in your files for future reference.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories made by Daikin that are specifically designed for the use with the equipment and have them installed by a professional.
If unsure of installation procedures or use, always contact your dealer for advice and information.
Danger: electric shock
Switch off all power supply before removing the control box cover or before making any connections or touching electrical parts.
This option kit needs to be used in combination with an EKRP1C11 kit and a FWF or FWC fan coil unit.
The units are equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by a licensed technician and must comply with all relevant European and national regulations.

ACCESSORIES SUPPLIED WITH THE KIT

1 2 3 4
2x
CONNECTION OF THE FAN COIL UNIT TO FIELD
PIPING BY USE OF THE 2-WAY/3-WAY VALVE
Refer to the installation manual of the fan coil unit for details on installing the fan coil unit.
Be careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the piping can cause malfunction of the unit.
If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
Use a good thread sealant for the sealing of the connections. The sealing must be able to withstand the pressures and temperatures of the system.
When using non-brass metallic piping, make sure to insulate both materials from each other to prevent galvanic corrosion.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Never use Zn-coated parts in the water circuit. Excessive corrosion of these parts may occur as copper piping is used in the unit's internal water circuit.
The equipment is not intended for use in a potentially explosive atmosphere.
5 6 7 8
1 Actuator with toothed ring
2 2-way valve (only for EKMV2C09B7)
3 3-way valve (only for EKMV3C09B7)
4 Insulation tape
5 Insulation for valve
6 Installation manual
7 O-ring (1x for EKMV2C09B7) (2x for EKMV3C09B7)
8 Wire (in case 2 valves are connected on same fan coil unit)
KRP1B101 box and EKRP1C11 PCB are needed for combination with the FWF units.
KRP1H98 box and EKRP1C11 PCB are needed for combination with the FWC units.
Installation manual
1
2-way valve kit/3-way valve kit for fan coil units
EKMV2C09B7 + EKMV3C09B7
4PW65144-1 – 10.2010

Water piping connections

2
3
5
4
2
3
4
A
50 mm
5
2 pipe models
FWF
1 2 3
FWC
3
1 2
1 Water out
2 Water in
3 Air purge
1 Mount the actuator on the valve body.
1 Remove the blue and red cap from the valve.
2 Push the toothed ring firmly onto the valve.
3 Mount the actuator on the ring.
4 Rotate the actuator 15° clockwise until you hear a "click". In
order to unfasten the actuator, rotate it 15° counterclockwise.
5 Push the red button inwards.
2-way valve
3-way valve
Modify the inlet side (A) so that the distance between the connection points is equal to 50 mm.
4 pipe models
FWF
1 2
FWC
1 5 6
3 4
5 6
3 4
2
1 Water out heating coil
2 Water in heating coil
3 Water out cooling coil
4 Water in cooling coil
5 Air purge heating coil
6 Air purge cooling coil
EKMV2C09B7 + EKMV3C09B7
2-way valve kit/3-way valve kit for fan coil units
4PW65144-1 – 10.2010
Installation manual
2