Daikin EKHVMRD50AAV1, EKHVMRD80AAV1, EKHVMYD50AAV1, EKHVMYD80AAV1 Installation manual

Page 1
INSTALLATION MANUAL
Daikin Altherma indoor unit
EKHVMRD50AAV1 EKHVMRD80AAV1
EKHVMYD50AAV1 EKHVMYD80AAV1
Page 2
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
deklaruje na własną wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
m
o
x
r
19
17
18
20
CE - IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE - DEKLARACJA-ZGODNOŚCI
CE - DECLARAŢIE-DE-CONFORMITATE
19 Direktive z vsemi spremembami.
10 Direktiver, med senere ændringer.
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
декларира на своя отговорност, че оборудването, за което се отнася тази декларация:
b
21
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu donanımının aşağıdaki gibi olduğunu beyan eder:
t
v
k
w
22
23
24
25
instrukcjami:
conformitate cu instrucţiunile noastre
инструкции:
16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
s našim návodom:
22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
01 Directives, as amended.
20 Direktiivid koos muudatustega.
21 Директиви, с техните изменения.
22 Direktyvose su papildymais.
23 Direktīvās un to papildinājumos.
24 Smernice, v platnom znení.
25 Değiştirilmiş halleriyle Yönetmelikler.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
11 Direktiv, med företagna ändringar.
02 Direktiven, gemäß Änderung.
irányelv(ek) és módosításaik rendelkezéseit.
12 Direktiver, med foretatte endringer.
13
14 v platném znění.
15 Smjernice, kako je izmijenjeno.
16
17 z późniejszymi poprawkami.
18 Directivelor, cu amendamentele respective.
03 Directives, telles que modifiées.
04 Richtlijnen, zoals geamendeerd.
05 Directivas, según lo enmendado.
06 Direttive, come da modifica.
07 √‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
08 Directivas, conforme alteração em.
09 Директив со всеми поправками.
<B>
положително от <B> съгласно
Cертификата <C>.
pagal Sertifikatą <C>.
vērtējumam saskaņā ar sertifikātu <C>.
21 Забележка * както е изложено в <A> и оценено
22 Pastaba * kaip nustatyta <A> ir kaip teigiamai nuspręsta
23 Piezīmes * kā norādīts <A> un atbilstoši <B> pozitīvajam
a(z) <C> tanúsítvány szerint.
<B> i Świadectwem <C>.
de <B> în conformitate cu Certificatul <C>.
<A> DAIKIN.TCF.025D3/04-2010
<B> KEMA (NB0344)
<C> 2082543.0551-QUA/EMC
súlade s osvedčením <C>.
<A>‘da belirtildiği gibi ve <C> Sertifikasına
göre <B> tarafından olumlu olarak
değerlendirildiği gibi.
*
Not
24 Poznámka * ako bolo uvedené v <A> a pozitívne zistené <B> v
25
skladu s certifikatom <C>.
kiidetud <B> järgi vastavalt sertifikaadile <C>.
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLÁŠENÍ-O-SHODĚ
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
erklærer som eneansvarlig, at udstyret, som er omfattet af denne erklæring:
u
q
09
10
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - DECLARAÇÃO-DE-CONFORMIDADE
СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ¢H§ø™H ™YMMOPºø™H™
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon, innebærer at:
s
n
11
12
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
c
y
h
j
15
16
13
14
la declaración:
referencia
acordo com as nossas instruções:
инструкциям:
instrukser:
förutsättning att användning sker i överensstämmelse med våra instruktioner:
disse brukes i henhold til våre instrukser:
08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
mukaisesti:
12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC *
19 ob upoštevanju določb:
20 vastavalt nõuetele:
21 следвайки клаузите на:
22 laikantis nuostatų, pateikiamų:
23 ievērojot prasības, kas noteiktas:
24 održiavajúc ustanovenia:
25 bunun koşullarına uygun olarak:
19 Opomba * kot je določeno v <A> in odobreno s strani <B> v
17 Uwaga * zgodnie z dokumentacją <A>, pozytywną opinią
18 Notă * aşa cum este stabilit în <A> şi apreciat pozitiv
16 Megjegyzés * a(z) <A> alapján, a(z) <B> igazolta a megfelelést,
och godkänts av <B> enligt
Certifikatet <C>.
bedømmelse av <B> ifølge Sertifikat <C>.
hyväksynyt Sertifikaatin <C> mukaisesti.
souladu s osvědčením <C>.
12 Merk * som det fremkommer i <A> og gjennom positiv
14 Poznámka * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v
13 Huom * jotka on esitetty asiakirjassa <A> ja jotka <B> on
11 Information * enligt <A>
da <B> secondo il Certificato <C>.
06 Nota * delineato nel <A> e giudicato positivamente
07 ™ËÌ›ˆÛË * fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ <A> Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
положительным решением <B> согласно
positivo de <B> de acordo com o Certificado <C>.
·fi ÙÔ <B> Û‡Ìʈӷ Ì ÙÔ ¶ИЫЩФФИЛЩИОfi <C>.
09 Примечание * как указано в <A> и в соответствии с
08 Nota * tal como estabelecido em <A> e com o parecer
20 Märkus * nagu on näidatud dokumendis <A> ja heaks
strane <B> prema Certifikatu <C>.
15 Napomena * kako je izloženo u <A> i pozitivno ocijenjeno od
Свидетельству <C>.
henhold til Certifikat <C>.
10 Bemærk * som anført i <A> og positivt vurderet af <B> i
Jean-Pierre Beuselinck
General Manager
Ostend, 1st of June 2010
declares under its sole responsibility that the equipment to which this declaration relates:
erklärt auf seine alleinige Verantwortung, dass die Ausrüstung für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que l’équipement visé par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
declara bajo su única responsabilidad que el equipo al que hace
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
a
d
f
l
e
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
01
02
i
06
04
03
05
10 under iagttagelse af bestemmelserne i:
11 enligt villkoren i:
12 gitt i henhold til bestemmelsene i:
13 noudattaen määräyksiä:
14 za dodržení ustanovení předpisu:
15 prema odredbama:
16 követi a(z):
17 zgodnie z postanowieniami Dyrektyw:
18 în urma prevederilor:
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Ф ВНФПИЫМfi˜ ЫЩФУ ФФ›Ф ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
p
g
07
08
EKHVMYD50AAV1, EKHVMYD80AAV1,
EKHVMRD50AAV1, EKHVMRD80AAV1,
instructions:
daß sie gemäß unseren Anweisungen eingesetzt werden:
onze instructies:
nuestras instrucciones:
nostre istruzioni:
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
07 В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
01 following the provisions of:
EN60335-2-40,
02 gemäß den Vorschriften der:
03 conformément aux stipulations des:
04 overeenkomstig de bepalingen van:
05 siguiendo las disposiciones de:
06 secondo le prescrizioni per:
07 Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
08 de acordo com o previsto em:
09 в соответствии с положениями:
according to the Certificate <C>.
beurteilt gemäß Zertifikat <C>.
<B> conformément au Certificat <C>.
<B> overeenkomstig Certificaat <C>.
positivamente por <B> de acuerdo con el
Certificado <C>.
01 Note * as set out in <A> and judged positively by <B>
02 Hinweis * wie in der <A> aufgeführt und von <B> positiv
03 Remarque * tel que défini dans <A> et évalué positivement par
04 Bemerk * zoals vermeld in <A> en positief beoordeeld door
05 Nota * como se establece en <A> y es valorado
3PW60973-2
Page 3
EKHVMRD50+80AAV1 EKHVMYD50+80AAV1
Daikin Altherma indoor unit
Installation manual
CONTENTS Page
1. Definitions .................................................................................. 2
2. General safety precautions........................................................2
3. Introduction ................................................................................ 3
3.1. General information ........................................................................3
3.2. Combination and options ............................................................... 3
3.3. Scope of the manual ...................................................................... 4
3.4. Model identification......................................................................... 4
4. Accessories ............................................................................... 4
4.1. Accessories supplied with this unit.................................................4
5. Overview of unit ......................................................................... 4
5.1. Opening the unit .............................................................................4
5.2. Main components in the unit .......................................................... 5
Reversible unit (EKHVMYD)...........................................................5
Heating only unit (EKHVMRD) ....................................................... 8
5.3. Switch box main components.......................................................11
6. Design of the water circuit........................................................ 11
6.1. Selection of the type of heat emitters ...........................................11
For heating mode ......................................................................... 11
For cooling mode.......................................................................... 11
6.2. General precautions concerning water circuit.............................. 12
6.3. Application examples for heating only units ................................. 13
Floor heating without tank ............................................................ 13
Radiator with tank......................................................................... 13
Fan coils without tank................................................................... 14
Application examples with several heat emitters.......................... 14
6.4. Application examples for reversible units .....................................15
6.5. Selection of meters for billing purpose ......................................... 15
Billing application examples ......................................................... 16
7. Installation of the unit...............................................................18
7.1. Selecting an installation location .................................................. 18
General precautions on installation location................................. 18
7.2. Dimensions and service space ....................................................19
Dimensions of unit........................................................................ 19
Service space of the unit..............................................................21
7.3. Inspecting, handling and unpacking the unit ................................21
7.4. Installing the unit .......................................................................... 21
Preparation before installation on final installation place .............21
Installation on final installation position ........................................23
Connecting the water circuit.........................................................23
Fix the indoor unit refrigerant connections ................................... 24
Close the unit ...............................................................................24
7.5. Leak test and vacuuming drying R410A circuit............................ 25
7.6. Water piping ................................................................................. 25
Checking the water volume and expansion
vessel pre-pressure...................................................................... 25
Setting the pre-pressure of the expansion vessel ........................26
Charging water.............................................................................27
8. Electrical wiring work ...............................................................27
8.1. Precautions on electrical wiring work........................................... 27
8.2. Internal wiring – Parts table..........................................................28
8.3. System overview of field wiring .................................................... 29
8.4. Requirements ...............................................................................29
8.5. Routing .........................................................................................30
8.6. Connection ................................................................................... 30
Installation and connection of the remote controller..................... 31
Connection to a benefit kWh rate power supply........................... 32
9. Start-up and configuration ....................................................... 33
9.1. Pre-operation checks ................................................................... 33
9.2. Final air purging............................................................................ 34
9.3. Field settings ................................................................................ 34
9.4. Procedure .....................................................................................34
9.5. Detailed description......................................................................35
9.6. Simultaneous demand of space heating and domestic water
heating.......................................................................................... 42
9.7. Simultaneous demand of space cooling and domestic water
heating.......................................................................................... 46
9.8. Multiple set point control............................................................... 46
9.9. Field setting table ......................................................................... 49
10. Final check and test run...........................................................52
10.1. Final check...................................................................................52
Multi tenant power supply check .................................................. 52
10.2. System test run ............................................................................52
10.3. Indoor unit individual test run .......................................................52
Temperature read-out mode......................................................... 52
Procedure for space heating/cooling............................................ 52
Procedure for domestic water heating.......................................... 53
11. Maintenance and service .........................................................53
11.1. Maintenance activities.................................................................. 53
Checks .........................................................................................54
11.2. Important information regarding the refrigerant used................... 54
11.3. Vacuuming/recovery and maintenance on refrigerant side .......... 55
System overview .......................................................................... 56
Recovery/vacuuming overview for 1 indoor unit maintenance
(R410A circuit connections) .........................................................56
12. Troubleshooting........................................................................ 56
12.1. General guidelines .......................................................................56
12.2. Opening the unit........................................................................... 56
12.3. Draining the system......................................................................57
12.4. General symptoms.......................................................................57
12.5. Error codes................................................................................... 58
13. Unit specifications ....................................................................59
Technical specifications................................................................ 59
Electrical specifications: power supply.........................................59
Electrical specifications: multi tenant power supply......................59
Thank you for purchasing this product.
The original instructions are written in English. All other languages are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL AND HOW TO CONFIGURE THE UNIT PROPERLY. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
1
Page 4

1. DEFINITIONS

2. GENERAL SAFETY PRECAUTIONS

Installation manual:
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Danger:
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Caution:
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
Note:
Indicates situations that may result in equipment or property-damage accidents only.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the subject of this manual.
Service agent:
Qualified person who can perform or coordinate the required service to the unit.
Legislation:
All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation.
Optional equipment:
Equipment which can optionally be combined to the products as per the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in this manual, but which are not supplied by Daikin.
All activities described in this manual shall be carried out by an installer.
Be sure to wear adequate personal protection equipment (protection gloves, safety glasses, …) when performing installation, maintenance or service to the unit.
If not sure of installation procedures or operation of the unit, always contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories and optional equipment made by Daikin which are specially designed for use with the products as of subject in this manual and have them installed by an installer.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switchbox service panel or before making any connections or touching electrical parts.
To avoid electric shock, be sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, be sure that those voltages are 50 V DC or less.
When service panels are removed, live parts can easily be touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
Do not touch the refrigerant piping, water piping or internal parts during and immediately after operation. The piping and internal parts may be hot or cold depending on the working condition of the unit.
Your hand may suffer burns or frostbite if you touch the piping or internal parts. To avoid injury, give the piping and internal parts time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
Installation manual
2
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 5

3. INTRODUCTION

3.1. General information

This installation manual concerns Daikin Altherma air to water inverter heat pump units of the Daikin EKHVMRD and EKHVMYD series.
These units are intended for indoor installation and aimed for apartment or other multi user buildings.
The unit is designed for floor standing heating operation. The EKHVMYD units can also perform cooling operation. The heat taken from the indoors' during cooling operation can be stored in the domestic hot water tank (=heat recovery operation).
EKHVMRD units can only perform heating operation.
EKHVMRD units have heating capacity ranges of 5.6 kW and 9 kW.
EKHVMYD units have heating capacity ranges of 5.6 kW and 9 kW and cooling capacities of 5 kW and 8 kW.
The indoor units are designed to work in heating and cooling mode at indoor ambient temperatures from 5°C to 30°C.
During heating operation, the unit can heat up the water to temperatures of 25°C to 80°C.
During cooling operation (only for EKHVMYD) the unit can cool down the water to temperatures of 5°C to 20°C.

3.2. Combination and options

The EKHVMRD and EKHVMYD units can only be combined with an outdoor EMRQ unit.
During heating operation, the unit can be combined with space heating radiators (field supply), fan coil units (option or field supply) or floor heating (field supply).
During cooling operation, the unit can be combined with fan coils (option or field supply).
The remote controller with room thermostat functionality is standard supplied with this unit to control your installation.
Domestic hot water tank (option)
An optional EKHTS200AB or EKHTS260AB domestic hot water tank can be connected to the indoor unit. The domestic hot water tank has a water volume of 200 l or 260 l.
Refer to the domestic hot water tank installation manual for further details.
Heat pump convector (option)
An optional FWXV convector for cooling or heating operation can be connected to this indoor unit.
Refer to the heat pump convector installation manual for further details.
Remote controller (option)
An optional secondary EKRUAHT remote controller (with room thermostat functionality) can be connected to the indoor unit. Purpose is to provide the possibility to install the standard remote controller near the unit (for service reasons), and install another remote controller in another place (e.g. living room) to operate your installation.
Refer to "Installation and connection of the remote controller" on
page 31 for further details.
Room thermostat (option)
An optional room thermostat EKRTR or EKRTW can be connected to the indoor unit.
Refer to the room thermostat installation manual for further details.
Heater kit (option)
An optional EKBUH heater kit can be combined with the indoor unit. Purpose is to provide an additional heating capacity during cold outdoor temperatures. The heater kit has a heating capacity of 6 kW, and available for both 1-phase and 3-phase power supply specifications. When using this heater kit, installation of the optional demand PCB is required as well.
Refer to the heater kit installation manual for further details.
P
H
2
3
1
T
A
1 Heat pump capacity 2 Required heating capacity (site dependent) 3 Additional heating capacity provided by the heater kit
T
Ambient (outdoor) temperature
A
P
Heating capacity
H
Digital I/O PCB (option)
An optional EKRP1HBAA digital I/O PCB can be connected to the indoor unit and be used to remotely monitor your system. This address card offers 2 voltage free outputs and 1 high voltage (230 V AC) output.
Refer to the operation manual of the indoor unit and to the digital I/O PCB installation manual for more information.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Demand PCB (option)
An optional EKRP1AHTA demand PCB can be connected to the indoor unit. This PCB is needed when the optional heater kit EKBUH or Daikin room thermostat EKRTR or EKRTW is installed or when multiple set point control is used, and provides the communication with the indoor unit.
Refer to the demand PCB installation manual for further details.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
Individual billing system (field supply).
The Daikin Altherma system uses a common outdoor unit for the different indoor units. Depending of local regulations, the customer is free to choose the allocation method of the common electrical power consumption costs of the outdoor unit.
Daikin advises an allocation method based on the measurements of consumed heat of each indoor unit. In other words, the outdoor unit energy input is allocated according the indoor unit energy output. An individual billing system calculation tool is available on demand. Contact your local dealer.
Refer to "6. Design of the water circuit" on page 11 for further details.
Cooling output (field supply)(only for EKHVMYD)
This is a 230 V AC output (maximum 0.3 A) which is on during cooling operation. This can be used to connect a valve which shuts off radiators to avoid sweat during cooling operation. Refer to
"6.4. Application examples for reversible units" on page 15.
If this option is installed it is not possible to use the remote controller thermostat function.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
3
Page 6

3.3. Scope of the manual

This manual does NOT include the selection procedure and the water system design procedure. Only some precautions and tips and tricks about the design of the water circuit are given in a separate chapter of this manual. Also included in this separate chapter are the guidelines for installation of the meters for billing purposes.
Once the selection is done and the water system is designed, this manual describes the procedures for handling, installing and connecting the EKHVMYD and EKHVMRD units. This manual has been prepared to ensure adequate maintenance of the unit, and it will provide help if problems occur.
11 Kit for lifting the unit 12 Flexible water outlet piping 13 Flexible water inlet piping (with manometer) 14 Support plate 15 Piping 16 Stop valves

5. OVERVIEW OF UNIT

NOTE
Refer to the installation manual of the outdoor unit for items not described in this manual.
The operation of the indoor unit is described in the indoor unit operation manual.
3.4. Model identification
EK HV M R/YD 50 AA V1
1N~, 220-240 V, 50 Hz
Series
Identification of the unit capacity
RD = Heating only unit YD = Reversible unit
Multi
Hydrobox
European kit

4. ACCESSORIES

4.1. Accessories supplied with this unit

Following accessories can be found in the unit.
12 31x46
1x 6x1x 1x 1x1x
9101x11
1x2x
1x121x
+
85
8x74x
13

5.1. Opening the unit

To gain access to the unit, top plate, the drip plates and the front plate need to be opened.
1
2
2
5
Once the unit is opened, access is possible to the main components.
To gain access to the electrical components, switch box needs to be opened:
4
3
1 Top plate 2 Drip plate 3 Front plate 4 Sound plate 5 Side plate
4
5
14
1x
1 Installation manual 2 Operation manual 3 Addendum installation manual 4 Wiring diagram 5 User interface kit (remote controller, 4 fixing screws, 2 plugs) 6 Top plate fixing screws + sound bottom plate fixing screws +
lifting fixing screws (8 screws)
7 Stop valve fixing screws (6 screws) 8 Grommet (small) 9 Grommet (large)
10 Top plate insulation
Installation manual
15
6x
16
3x
4
4x
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
See "2. General safety precautions" on page 2.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 7

5.2. Main components in the unit

Reversible unit (EKHVMYD)

10
14
4
6
3
1
12 12
11 8
15
13
26 25
20
9 7
24
16
2
65
4
19 23 22
21
17
18
1 R134a accumulator 14 Flow switch 2 R134a compressor 15 Expansion vessel (cooling/heating) 3 R134a discharge muffler 16 Expansion vessel (heating/domestic hot water heating) 4 R134a low pressure sensor 17 Heating plate heat exchanger 5 R134a high pressure switch 18 Cascade plate heat exchanger 6 R134a high pressure sensor 19 Cooling plate heat exchanger 7 R134a expansion valve 20 Cooling pump 8 R410A cooling expansion valve 21 R410A suction connection
9 R410A heating expansion valve 22 R410A discharge gas connection 10 Heating pump 23 R410A liquid connection 11 Cooling/heating 3-way valve 24 Switchbox 12 Air purge 25 Service port R134a high 13 Safety valve 26 Service port R134a low
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
5
Page 8
R11T
R4T
R10T
Sensor information:
• R3T = R410A liquid temperature
• R4T = Water return temperature
• R5T = Heating leaving water temperature
• R6T = R134a discharge temperature
• R7T = R134a liquid temperature
• R9T = Cooling leaving water temperature
• R10T = R410A liquid temperature (cooling)
• R11T = R410A suction temperature
R6T
R9T
R5T
R3T
R7T
Installation manual
6
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 9
24
1
2
18
19
A/B
9
8
3
18
20
6
K3S SV
14
R5T
Q2L
15
M1P
21
K2S
M
16
17
R4T
17
6
S1PH
10
B1PH
R6T
4
B1PL
7
5
6
11
R3T
12
13 13
K1E
K2E
6
R11T
R7T
6
25
M2P
R9T
15
R10T
K3E
22
16
K1S
M
23
21
22
AB
1 Refrigerant side 22 Safety valve
2 Outdoor unit (EMRQ) 23 Pressure gauge
3 Option domestic hot water tank 24 Flowswitch
4 Muffler 25 Cooling heat exchanger
5 Check valve A Install the 3-way valve in case of domestic hot water tank
6 Filter B Standard
7 Field piping Ø12.7 S1PH High pressure switch
8 Field piping Ø9.52 B1PL Low pressure sensor
9 Field piping Ø15.9 B1PH High pressure sensor 10 Compressor K1E Electronic expansion valve (R410A; heating) 11 Accumulator K2E Electronic expansion valve (R134a) 12 Cascade heat exchanger K3E Electronic expansion valve (R410A; cooling) 13 Service port Q2L Thermistor protector water piping 14 Heating heat exchanger K1S 3-way valve 15 Drain port K2S 3-way valve (cooling/heating) 16 Expansion vessel K3S Solenoid valve 17 Air purge M1P Pump (heating) 18 Shut-off valve M2P Pump (cooling) 19 Water outlet Heating 20 Water inlet Cooling 21 Blow off
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
7
Page 10

Heating only unit (EKHVMRD)

16
15 10
4
6
5
3
1
2
9
8 7
16
11
18
41365
15
14
12
1 R134a accumulator 11 Expansion vessel 2 R134a compressor 12 Heating plate heat exchanger 3 R134a discharge muffler 13 Cascade plate heat exchanger 4 R134a low pressure sensor 14 R410A discharge gas connection 5 R134a high pressure switch 15 R410A liquid connection 6 R134a high pressure sensor 16 Switchbox 7 R134a expansion valve 17 Service port R134a high 8 R410A heating expansion valve 18 Service port R134a low 9 Heating pump
10 Air purge
17
Installation manual
8
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 11
R6T
Sensor information:
• R3T = R410A liquid temperature
• R4T = Water return temperature
• R5T = Heating leaving water temperature
• R6T = R134a discharge temperature
• R7T = R134a liquid temperature
R4T
R7T
R5T
R3T
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
9
Page 12
1
2
17
18
A/B
7
8
S1PH
B1PH
R6T
R5T
5
Q2L
3
4
13
M1P
R4T
B1PL
6
9
16
17
6
19
14
11
6
15
22
20
21
10
R3T
12 12
K1E
K2E
R7T
6
K1S
M
AB
1 Refrigerant side 17 Shut-off valve 2 Outdoor unit (EMRQ) 18 Water outlet 3 Option domestic hot water tank 19 Water inlet 4 Muffler 20 Blow off 5 Check valve 21 Safety valve 6 Filter 22 Pressure gauge 7 Field piping Ø12.7 A Install the 3-way valve in case of domestic hot water tank 8 Field piping Ø9.52 B Standard
9 Compressor S1PH High pressure switch 10 Accumulator B1PL Low pressure sensor 11 Cascade heat exchanger B1PH High pressure sensor 12 Service port K1E Electronic expansion valve (R410A) 13 Heating heat exchanger K2E Electronic expansion valve (R134a) 14 Drain port K1S 3-way valve 15 Expansion vessel Q2L Thermistor protector water piping 16 Air purge M1P Pump
Installation manual
10
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 13

5.3. Switch box main components

6. DESIGN OF THE WATER CIRCUIT

62 161718 21 15 10
8
15
22 11
12
7
13
1
19 20
14
4
1. Main PCB
2. Control PCB
3. Inverter PCB
4. QA PCB
5. Filter PCB
6. Multi tenant PCB
7. Digital I/O PCB (optional)
8. Demand PCB (optional)
9. Terminal block X1M
Main terminal block which allows easy connection of field wiring for power supply.
10. Terminal block X2M
Field wiring terminal block for high voltage connections.
11. Terminal block X3M
Field wiring terminal block for low voltage connections.
12. DC connector X1Y/X4Y
13. AC connector X3Y
14. Pump connector X2Y
15. Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable ties to the switch box to ensure strain relief.
16. Power wiring entry
17. High voltage field wiring entry
18. Low voltage field wiring entry
19. Compressor cable entry
20. Interface relay K1A
21. Interface relay K2A
22. Interface relay K3A
23. Wiring bridges
15
9 23
5
3
The purpose of this chapter is to give guidelines for the design of the water circuit.
Precautions and guidelines that have impact to the unit prescribed in this manual are included into this chapter.
Actions needed during the installation of the unit prescribed in this manual are described in the chapter "7.6. Water piping" on page 25.
WARNING
It is strongly recommended to install an additional filter on the heating water circuit. Especially to remove metallic particles from the field heating piping, it is advised to use a magnetic or cyclone filter which can remove small particles. Small particles can damage the unit and will not be removed by the standard filter of the heat pump unit.

6.1. Selection of the type of heat emitters

The selection of the heat emitter is the choice of the end customer. The choice of the heat emitter will define the needed water temperature from the unit.

For heating mode

Based on the needed water temperature for the heat emitters, following range can be defined:
1. Low temperature (Leaving water temperature range from 25°C
to 40°C). Typical example: floor heating.
2. Medium temperature (Leaving water temperature range from
40°C to 55°C). Typical example: low temperature radiators or convectors.
3. High temperature (Leaving water temperature range from 55°C
to 75°C). Typical example: radiators.

For cooling mode

Fan coil units are advised as heat emitters.
NOTE
In a house a combination of the above mentioned heat emitters is possible.
Once the heat emitters are chosen, the capacity of these heat emitters should be defined and from this the dimensioning and position of the heat emitters in the different rooms should be decided.
An important parameter of the heat emitters is the temperature difference between entering water and leaving water.
This will define the water flow in the system.
Finally, the piping layout from the heat source to the different heat emitters needs to be drawn.
This will finally define following important parameters:
Minimal water volume in the system.
Maximal water volume in the system.
Minimal and maximal water flow in system.
Maximal pressure drop in the system.
If floor cooling is used, it is the responsibility of the
installer to take the needed precautions to avoid floor sweating.
The draining of the fancoil units are the responsibility of the installers.
When radiators are used, a shut-off valve must be installed to avoid sweating of the radiators. (Refer to "6.3. Application examples for heating only
units" on page 13).
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
11
Page 14
NOTE
1 Air to water pump system 2 Balancing bottle 3 High external static pressure pump 4 High external static pressure system
In refurbishment applications, the water system will already be fixed. It is utmost important for these kind of installations to know the parameters mentioned above.

6.2. General precautions concerning water circuit

Before continuing the installation of the unit, check the following points:
The maximum water pressure is 4 bar.
The maximum water temperature is 80°C.
Provide adequate safeguards in the water circuit to be sure that
the water pressure will never exceed the maximum allowable working pressure (4 bar).
Shut-off valves from flexible hoses delivered with the unit should be installed so that normal servicing can be accomplished without draining the system.
Drain taps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance or service to the unit. A drain valve is provided in the unit to drain the water from the unit water system.
Be sure to provide a proper drain for the pressure relief valve to avoid any water coming into contact with electrical parts.
Air vents must be provided at all high points of the system. The vents shall be located at points which are easily accessible for servicing. An automatic air purge is provided inside the indoor unit. Check that this air purge valve is not tightened too much so that automatic release of air in the water circuit remains possible.
Take care that the components installed in the field piping can withstand the water pressure and temperature.
Always use materials which are compatible with the water used in the system and with the materials used on the unit.
Select piping diameter in relation to required water flow and available ESP of the pump.
When designing the hydraulic system always consider the available static pressure of the indoor unit.
100
90 80
50
70 60 50 40
ESP [kPa]
30 20 10
0
5 7 9 11131517192123252729
ESP (kPa) External static pressure (kPa)
flow (l/min) Flow (l/min)
Without 3-way valve
Including 3-way valve
Maximum external static pressure if
Maximum external static pressure if
Maximum external static pressure if ΔT=5°C (cooling)
50/80 Identification of the unit capacity
80
50
50
Flow [l/min]
80
ΔT=5°C
80
ΔT=10°C
ΔT=10°C (heating)
ΔT=5°C (heating)
NOTE
The ESP curves are the maximum ESP curves for different ΔT types (pump rpm=4000 for ΔT=5°C; pump rpm=3600 for ΔT=10°C). The pump of the indoor module is inverter controlled and controls to have a fixed ΔT between return and leaving water temperature.
In case of installing a domestic hot water tank there is an additional pressure drop over the 3-way valve (delivered as accessory with the tank).
NOTE
When replacing an old gas or oil boiler by an air to water pump system:
please always check the specifications of the pump of the old unit;
if the external static pressure of that pump is higher than the external static pressure of the air to water pump system, please install an additional pump with higher external static pressure in combination with a balancing bottle.
3 421
Check that the total water volume in the installation, excluding the internal water volume of the unit, is 20 l minimum.
WARNING
In most applications this miminum water volume will have a satisfying result.
In critical processes or in rooms with a high heat load though, extra water volume might be required
Installation manual
12
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 15
When circulation in each space heating/radiator loop is controlled by remotely controlled valves, it is important that this minimum water volume is kept even if all the valves are closed.
Example (See "6.3. Application examples for heating only
units" on page 13.)
A B
1112
1 Outdoor unit 10 Radiator (field supply)
2 Indoor unit 11 Electronic expansion
3 Refrigerant heat
exchanger 12 Indoor unit refrigerant
4 Water heat exchanger C1 Remote controller
5 Compressor M1...M3 Individual motorized valve
6 Pump
7 Shut-off valve T1...T3 Individual room
8 Collector (field supply)
9 By-pass valve
(field supply)
C1
11
512
A Installation space
B Living room
7 8432 91610
M3
M2
M1
valve
stop valve
to control loop radiators (field supply)
thermostat (field supply)
T3
T2
T1

6.3. Application examples for heating only units

Floor heating without tank

A B
1112
1 Outdoor unit 11 Electronic expansion valve 2 Indoor unit 12 Indoor unit refrigerant stop 3 Refrigerant heat
exchanger
4 Water heat exchanger C1 Remote controller 5 Compressor M1...M3 Individual motorized valve 6 Pump
7 Shut-off valve T1...T3 Individual room thermostat 8 Collector (field supply) 9 By-pass valve (field
supply)
10 FHL: Floor heating loop
(field supply)

Radiator with tank

C1
11
512
A Installation place
B Living room
C2
778432 916
M3
M2
M1
valve
to control loop radiators (field supply)
(field supply)
A B
10
FHL3
T3
10
FHL2
T2
10
FHL1
T1
C1
10 13
743 121214 21
6
M
514
8
1 Outdoor unit 11 Radiator (field supply) 2 Indoor unit 12 Electronic expansion 3 Refrigerant heat exchanger 4 Water heat exchanger 13 By-pass valve (field 5 Compressor 6 Pump 14 Indoor unit refrigerant 7 Shut-off valve 8 Motorized 3-way valve
(optional)
9 Domestic hot water tank
(optional)
10 Collector (field supply) B Living room
valve
supply)
stop valve
C1 Remote controller
(master)
C2 Remote controller (slave)
A Installation place
9
11
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
13
Page 16

Fan coils without tank Application examples with several heat emitters

A B
1112
1 Outdoor unit 11 Electronic expansion valve 2 Indoor unit 12 Indoor unit refrigerant stop 3 Refrigerant heat exchanger 4 Water heat exchanger C1 Remote controller 5 Compressor A Installation place 6 Pump B Living room 7 Shut-off valve M1...M3 Individual motorized valve 8 Collector (field supply) 9 By-pass valve (field supply
10 FCU: Fan coil unit (field
supply)
C1
11
512
7 8432 916
M3
M2
M1
valve
to control loop fan coils (field supply)
T1...T3 Individual room thermostat
(field supply)
10
FCU3
10
FCU2
10
FCU1
T3
T2
T1
Using different heat emitters means using different water set points for the system.
Such installations must be done using a balancing bottle and each kind of heat emitter should have a specific pump.
C1
1
3 34 5 6 8221
7
M
9
21
19 18 11
10 10
1512 14 141613
FHL
35°C
TRD1 TRD2
45°C
FCU
18 20 20
17
65°C
1919
1 Outdoor unit 13 Shut-off valve (field supply) 2 Indoor unit 14 By-pass valve (field supply) 3 Electronic expansion valve 15 FCU: Fan coil unit (field
4 Refrigerant heat exchanger 16 Shut-off valve (field supply) 5 Water heat exchanger 17 Radiator (field supply) 6 Pump 18 Mixing valve (field supply) 7 Motorized 3-way valve
(optional)
8 Domestic hot water tank
(optional)
9 Compressor C1 Remote controller 10 Shut-off valve TRD1 Temperature reducing 11 Balancing bottle (field supply) 12 FHL: Floor heating loop (field
supply)
supply)
19 Pump (field supply)
20 Non-return valve (field
supply)
device 1 (field supply)
TRD2 Temperature reducing
device 2 (field supply)
Refer to chapter "9.8. Multiple set point control" on page 46 for more information about the configuration of your system.
Installation manual
14
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 17

6.4. Application examples for reversible units 6.5. Selection of meters for billing purpose

Daikin advises an allocation method based on the measurements of consumed heat of each indoor unit. Following measurements are
C1
1
2
3
4912
14
13
3
6
10
8
7
required:
the outdoor unit power consumption: by means of an electrical power meter
the indoor unit energy consumption:
EKHVMYD by means of a heat and cooling meter
EKHVMRD by means of a heat meter
the indoor unit energy consumption during domestic hot water
operation (if installed): by means of a heat meter.
The selection of the meters for billing purpose is the choice of the end customer.
Refer to databook for specifications to be used for meter selection.
3
11
5
WARNING
Selection and installation of the meters should be done in accordance with applicable legislation.
20
Check the meter supplier documentation for detailed installation instructions. Before installation of the meters, check the following
17
points:
install separate watt-hour meter for each outdoor unit
all heat meters in the apartment are to be supplied by the same
supplier
to facilitate readout and service work, heat meters should be easily accessible. Choose a mounting location with sufficient clearance for data read-out.
avoid installation of meters inside the indoor unit service space
15
16 20
M2
M1
18
T2
18
T1
in order to guarantee indoor unit servicing.
all heat meters and heating and cooling meters in the apartment
17
M2
M1
19
FCU2
T2
19
FCU1
T1
building are to be installed at identical piping distance from the indoor unit.
21 16
1 Outdoor unit 14 Domestic hot water tank
2 Indoor unit 15 Balancing bottle (field
3 Indoor unit refrigerant stop
valves
4 Cascade heat exchanger 17 By-pass valve (field supply) 5 Cooling heat exchanger 18 Radiator (field supply) 6 Heating expansion valve 19 FCU: Fan coil unit (field 7 Cooling expansion valve 8 R134a compressor 20 Shut-off valve (field supply)
9 Heating heat exchanger 21 Temperature reducing valve 10 Heating pump 11 Cooling pump C1 Remote controller 12 Heating - domestic hot water
3-way valve (optional)
13 Cool/heat 3-way valve T1...T2 Individual room thermostat
NOTE
In order to avoid radiator sweating during cooling
M1...M2 Individual motorized valve
(optional)
supply)
16 Pump (field supply)
supply)
(field supply)
to control loop (field supply)
(field supply)
operation, shut-off valve (20) should be installed. This shut-off valve can be controled from the indoor unit by connecting to X2M position 17 and 18 (refer to wiring diagram for further details).
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
15
Page 18

Billing application examples

EKHVMYD – Tank heat meter between tank and indoor unit EKHVMYD – Tank heat meter on tapping side
4 4
1
5 6 723
8
91320 19
1
4 4
5 6 723
8
9 131312
M
3
7
10
4
17
20 1913 12
M
18
15
16
1 Outdoor unit 14 Flow measuring unit of space 2 Indoor unit
3 Indoor unit refrigerant
stop valves
4 Electronic expansion
valve
5 Refrigerant heat
exchanger
6 Heating heat
exchanger
7 Pump 20 Tank billing kit (optional) in 8 Motorized 3-way valve
(optional)
9 Domestic hot water
tank (optional)
10 Compressor 11 Shut-off valve 12 Flow measuring unit of
heat meter (field supply)
13 Temperature sensors
heat meter (field supply)
11 11
14
heat and cooling meter (field supply)
15 Temperature sensor space
heat and cooling meter (field supply)
16 Space heating and cooling
applications
17 Cooling heat exchanger 18 Cool/heat 3-way valve 19 Field piping
case the domestic hot water tank is mounted on top of the indoor unit OR Floor mounted tank kit (optional) in case the domestic hot water tank is installed on the floor next to the indoor unit
M
3
10
4
17
7
M
18
15
16
1 Outdoor unit 13 Temperature sensors heat 2 Indoor unit 3 Indoor unit refrigerant
stop valves
4 Electronic expansion
valve
5 Refrigerant heat
exchanger
6 Heating heat
exchanger
7 Pump 16 Space heating and cooling 8 Motorized 3-way valve
(optional) 17 Cooling heat exchanger
9 Domestic hot water
tank (optional)
10 Compressor 11 Shut-off valve 12 Flow measuring unit of
heat meter (field supply)
11 11
14
meter (field supply)
14 Flow measuring unit of space
heat and cooling meter (field supply)
15 Temperature sensor space
heat and cooling meter (field supply)
applications
18 Cool/heat 3-way valve
Installation manual
16
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 19
EKHVMRD – Tank heat meter between tank and indoor unit EKHVMRD – Tank heat meter on tapping side
4 45 6 7 91318 17
1
23
8
M
3
10
15
11 11
16
1 Outdoor unit 14 Flow measuring unit of space
2 Indoor unit
3 Indoor unit refrigerant
stop valves
4 Electronic expansion
valve
5 Refrigerant heat
exchanger
6 Heating heat
exchanger
7 Pump
8 Motorized 3-way valve
(optional)
9 Domestic hot water
tank (optional)
10 Compressor 11 Shut-off valve 12 Flow measuring unit of
heat meter (field supply)
13 Temperature sensors
heat meter (field supply)
15 Temperature sensor space
16 Space heating applications
17 Field piping 18 Tank billing kit (optional) in
18 17
13 12
14
heat meter (field supply)
heat meter (field supply)
case the domestic hot water tank is mounted on top of the indoor unit OR Floor mounted tank kit (optional) in case the domestic hot water tank is installed on the floor next to the indoor unit
1
4 45 6 7 9 13131223
8
M
3
10
15
16
1 Outdoor unit 11 Shut-off valve 2 Indoor unit 12 Flow measuring unit of heat 3 Indoor unit refrigerant
stop valves
4 Electronic expansion
valve
5 Refrigerant heat
exchanger
6 Heating heat
exchanger
7 Pump 16 Space heating applications 8 Motorized 3-way valve
(optional)
9 Domestic hot water
tank (optional)
10 Compressor
11 11
14
meter (field supply)
13 Temperature sensors heat
meter (field supply)
14 Flow measuring unit of space
heat meter (field supply)
15 Temperature sensor space
heat meter (field supply)
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
17
Page 20

7. INSTALLATION OF THE UNIT

7.1. Selecting an installation location

WARNING
Be sure to provide for adequate measures in order to prevent that the unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean and clear.

General precautions on installation location

Select an installation site that meets the following requirements:
The foundation must be strong enough to support the weight of the unit. The floor is flat to prevent vibrations and noise generation and to have sufficient stability. This is especially of importance when the optional domestic hot water tank is installed on top of the unit.
The space around the unit is adequate for maintenance and servicing (refer to "Service space of the unit" on page 21).
The space around the unit allows for sufficient air circulation.
There is no danger of fire due to leakage of inflammable gas.
The equipment is not intended for use in a potentially explosive
atmosphere.
Select the location of the unit in such a way that the sound generated by the unit does not disturb anyone, and the location is selected according the applicable legislation. If the sound is measured under actual installation conditions, the measured value will be higher than the sound pressure level mentioned in "13. Unit specifications" on page 59 due to environmental noise and sound reflections. Choose the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, …)
All piping lengths and distances have been taken into consideration (For requirements of piping length for the refrigerant piping, refer to the outdoor unit installation manual).
Requirement Value
Maximum allowable distance between the domestic hot water tank and the indoor unit (only for installations with domestic hot water tank).
10 m
NOTE
If the installation is equipped with a domestic hot water tank (optional), please refer to the domestic hot water tank installation manual.
Take care that in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
The installation location is frost-free.
Be sure that sufficient precautions are taken, in accordance with
the applicable legislation, in case of refrigerant leakage.
When installing the unit in a small room, take measures in order to keep the refrigerant concentration from exceeding allowable safety limits in the event of a refrigerant leak.
Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.
Do not climb, sit or stand on top of the unit.
Do not place any objects or equipment on top of the unit (top
plate).
Do not install the unit in places often used as workplace. In case of construction works, where a lot of dust is created, the unit must be covered.
Do not install the unit in places with high humidity (e.g. bathroom) (max humidity (RH)=85%).
Installation manual
18
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 21

7.2. Dimensions and service space

Dimensions of unit

EKHVMYD
18
19
20
694
74
40
79 241
2x 60
38
14
15
81
3 2 1
9
7
4 5
611
120
62
708
60
465
381
251
120
16 17 17
7 79 976
10 10
12 12
11 11
10 10
13 13
1
2 3
6
7 8
8 4
5
8
4 5
8
600
17
1 Suction pipe connection Ø15.9 solder (R410A) 11 Water filter 2 Discharge pipe connection Ø12.7 solder (R410A) 12 Water in connection G1" (female) 3 Liquid pipe connection Ø9.52 solder (R410A) 13 Water out connection G1" (female) 4 R134a service ports 5/16" flare (low) 14 Control wiring intake (knock-out hole Ø37) 5 R134a service ports 5/16" flare (high) 15 Power supply wiring intake (knock-out hole Ø37) 6 Pressure gauge 16 Knock-out hole for refrigerant piping and water piping 7 Blow off valve 17 Levelling feet 8 Drain valve water circuit 18 Liquid stop valve Ø9.52 solder (R410A) 9 Air purge 19 Discharge stop valve Ø12.7 solder (R410A)
10 Shut-off valves 20 Suction stop valve Ø15.9 solder (R410A)
17
16
26.5
607
622
637
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
19
Page 22
EKHVMRD
79 242
81
2x 60
38
74
13
694
14
2 1
8
3 4
17
18
6 68 8 2 15
9 9
11 11
5
611
120
62
708
60
465
381
251
120
15 16 16
10
9 9
12 12
10
3 4
7
3 4
7
600
16
1 Discharge pipe connection Ø12.7 solder (R410A) 10 Water filter 2 Liquid pipe connection Ø9.52 solder (R410A) 11 Water in connection G1" (female) 3 R134a service ports 5/16" flare (low) 12 Water out connection G1" (female) 4 R134a service ports 5/16" flare (high) 13 Control wiring intake (knock-out hole Ø37) 5 Pressure gauge 14 Power supply wiring intake (knock-out hole Ø37) 6 Blow off valve 15 Knock-out hole for refrigerant piping and water piping 7 Drain valve water circuit 16 Levelling feet 8 Air purge 17 Liquid stop valve Ø9.52 solder (R410A) 9 Shut-off valves 18 Discharge stop valve Ø12.7 solder (R410A)
16
15
26.5
622
637
Installation manual
20
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 23

Service space of the unit

7.4. Installing the unit

30
A
>600
D
B
>250
>500
A Space required for switch box removal B Left installation (top view) C Right installation (top view) D Space required for wiring (in case of right installation)
C
>250
NOTE
Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe the EN378 is the applicable standard that shall be used.
Preparation before installation on final installation place
After unpacking the unit and before installing the unit on its final installation position, following preparations need to be done:
Open the unit Refer to the "5.1. Opening the unit" on page 4.
Knock out the needed knockout holes. This installation instruction consists of installation of
refrigerant piping,
water piping and
electrical wiring.
For each of these a dedicated knock out hole is foreseen at the backside of the unit:
1
2
3
1
3

7.3. Inspecting, handling and unpacking the unit

At delivery, the unit must be checked and any damage must be reported immediately to the carrier’s claims agent.
Bring the unit as close as possible to its final installation position in its original package to prevent damage during transport.
Unpack the indoor unit completely according to the instructions mentioned on the unpacking instructions sheet.
Check if all indoor unit accessories (see "4. Accessories" on
page 4) are enclosed.
WARNING
Tear apart and throw away plastic packaging bags so that children will not play with them. Children playing with plastic bags face danger of death by suffocation.
AB
1 Knock out hole for refrigerant piping 2 Knock out hole for electrical wiring
3 Knock out hole for water piping A Left installation B Right installation
Knockout holes are foreseen at both sides of the unit. Pay attention to knock out the correct holes depending on your installation location.
Refrigerant piping and water piping must go through different knockout holes.
The electrical wiring must always enter the unit at the upper knockout holes at the left side of the unit (see the figure above).
Do NOT use the lower knockout holes.
To punch a knockout hole, punch it with a hammer, remove all burrs and install the supplied grommets (see "4. Accessories" on
page 4).
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
12 3 4
1 Knockout hole 2 Burr 3 Grommet 4 Putty or insulation materials (field supply)
Before installation of the unit to its final position, it is advised to connect the water flexible pipes and refrigerant pipes to the unit (delivered as accessory).
Installation manual
21
Page 24
Take out all accessories from the indoor unit.
Connect the flexible pipes to the indoor unit connection.
Installation of accessory pipes for refrigerant piping.
Depending on left or right connection, different accessory pipes are delivered with the unit (refer to "4. Accessories" on page 4). The refrigerant piping needs to be brazed.
Fixation of piping in case of left connection
3x
Caution for brazing.
Make sure to blow through with nitrogen when brazing. Blowing through with nitrogen prevents the creation of large quantities of oxidized film on the inside of the piping. An oxidized film adversely affects valves and compressors in the refrigerating system and prevents proper operation.
The nitrogen pressure should be set to 0.02 MPa (i.e., just enough so it can be felt on the skin) with a pressure-reducing valve.
12 345
6
1 Refrigerant piping 2 Part to be brazed 3 Taping 4 Hands valve 5 Pressure-reducing valve 6 Nitrogen
6
Do not use anti-oxidants when brazing the pipe joints. Residue can clog pipes and break equipment.
Do not use flux when brazing copper-to-copper refrigerant piping. Use phosphor copper brazing filler alloy (BCuP) which does not require flux.
Flux has an extremely harmful influence on refrigerant piping systems. For instance, if chlorine based flux is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will deteriorate the refrigerant oil.
Fixation of piping in case of right connection
3x
NOTE
The back plate is not shown on the illustration, but it is not needed to take out the back plate for the installation.
Installation manual
22
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 25
Installation on final installation position
Place the unit in the appropriate installation location.
The weight of the unit is approximately 116 kg. At least two persons are required to lift the unit.
Use the plates delivered with the unit to lift the unit.
Push the sound strips against the ground and fix the side plates with the appropriate screws.
1
3
3
1
116 kg
Level the unit to a stable position using the levelling feet.
Only for EKHVMYD:
Unscrew and remove the 2 beams (1) that protect the drain pan during transport.
Standard installation location of the optional domestic hot water tank is on top of the indoor unit.
If available service space to left and/or right side is limited, carefully consider all tank module installation steps first.
2
2
0 mm
2x
Close the sound panel(s) and decoration panel(s) which will be on the wall side and for which fixation is not possible anymore after the unit is put on its final location.

Connecting the water circuit

Water connections must be made. The connected flexible pipes need to be connected to the piping that leads to the heat emitters as follows:
1122
1 Field piping 2 To heat emitters
1 1
Be careful not to deform the unit piping by using excessive force when connecting the piping. Deformation of the piping can cause the unit to malfunction.
If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit:
Use clean pipes only.
Hold the pipe end downwards when removing burrs.
Cover the pipe end when inserting it through a wall so that no
dust and dirt enter.
Use a good thread sealant for the sealing of the connections.
When using non-brass metallic piping, make sure to insulate
both materials from each other to prevent galvanic corrosion.
Because brass is a soft material, use appropriate tooling for
2x2x
connecting the water circuit. Inappropriate tooling will cause damage to the pipes.
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Never use Zn-coated parts in the water circuit. Excessive corrosion of these parts may occur as copper piping is used in the unit's internal water circuit.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
23
Page 26
NOTE
When using a 3-way valve or a 2-way valve in the water circuit, the maximum changeover time of the valve shall be less than 60 seconds.
Precautions when connecting field piping and regarding insulation
The complete water circuit, inclusive all piping, must be insulated to prevent reduction of the heating capacity.
If the indoor ambient temperature is higher than 30°C and the humidity is higher than RH 80% then the thickness of the insulation materials should be at least 20 mm in order to avoid condensation on the surface of the insulation.

Fix the indoor unit refrigerant connections

NOTE
For servicing purposes, it is needed to be able to evacuate the refrigerant circuit. Therefore, stop valves are foreseen as accessories.
These stop valves must be installed near to the unit, and on an accessible place (when service is needed the stop valves need to be closed and equipment for recovery/vacuuming has to be connected).
Decide where to install the stop valves and position the stop valves on the wall by using the support plate.
NOTE
Consider carefully the installation location of the flexible water inlet pipe.
According to the direction of the water flow, the water filter must be positioned as shown in the figure.
Provide sufficient space allowing easy access to clean the water filter and regular operation check of the safety valve.
Provide a flexible hose for pressure relief valve blow-off (field supply).
Consider to support the water inlet pipe and water outlet pipe so not to stress the field piping.
It is very important to keep good visibility of the manometer. The position of the manometer can be changed as shown in the figure below. Make sure that the capillary tube does not come in contact with sharp edges and prevent bending of the capillary tube as much as possible.
Change the position of the manometer when piping is on the left side of the unit
1
2
3 3 3
1 Support plate 2 Stop valve 3 To outdoor unit
Finalise the refrigerant piping work (connect the prepared refrigerant piping to the piping coming from the outdoor unit). Refer to the above cautions for brazing and to the outdoor unit installation manual.
1
2
3
Mounting of the manometer against a wall (the 2 screws are field supply).
1
2x
2
2x
3
NOTE
Above instruction is for an EKHVMYD unit.
For the heating only unit EKHVMRD only 2 pipes (liquid and discharge pipe) need to be connected.

Close the unit

1 Put the sound bottom plate at the bottom of the unit and fix it
with the appropriate screws.
2x
1 2
NOTE
Only for EKHVMYD:
If the 2 beams that protect the drain pan during transport were not removed before attempting to put the sound bottom plate in place, the sound bottom plate cannot be mounted. Refer to
"Installation on final installation position" on page 23.
Installation manual
24
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 27
2 Fix the top panel on the unit with the appropriate screws.
4x

7.5. Leak test and vacuuming drying R410A circuit

When the indoor unit was powered on before all brazing and refrigerant piping work was finished on R410A side, a special setting needs to be applied to open all valves before vacuuming can start. See also the installation manual of the outdoor unit for furter details and "11.3. Vacuuming/recovery and maintenance on refrigerant side"
on page 55.

7.6. Water piping

The unit is equipped with a water inlet and water outlet for connection to a water circuit. This circuit must be provided by an installer and must comply with the applicable legislation.
3 Stick the top plate insulation (accessory) at the inside of the top
decoration panel according to the figure below.
1 2
5 mm
3 4
4 Fix the top decoration panel on top
of the unit using the appropriate screws. In case a domestic hot water tank (optional) is installed, refer to the domestic hot water tank installation manual.
2x
NOTE
The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
For precautions about the design of the water circuit, refer to "6. Design of the water circuit" on page 11.
Checking the water volume and expansion vessel pre-pressure
The expansion vessel in the unit avoids that the pressure in the system increases due to temperature differences.
The unit is equipped with a 7 l expansion vessel for which the pre-pressure can be changed (default pre-pressure is 1 bar).
Changing the pre-pressure of the expansion vessel might be needed if the water volume of the system is too big in relation with the needed leaving water temperature.
Refer to the graph below.
2.50
2.25
2.00
1.75
1.50
1.25
A
1.00
5 Fix the front and remaining side decoration panel(s) back to the
unit using the appropriate screws.
2x
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
0.75
0.50
0.25
0.00 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400
20
B
80°C water temperature
65°C water temperature
35°C water temperature
Never change the pre-pressure of the system to a value lower than 0.3 bar
A Pre-pressure (bar) B System water volume (l)
Installation manual
25
Page 28
How to check if the pre-pressure of the system needs to be changed:
0
Step 1: define the needed leaving water temperature in the system: e.g. 65°C
Step 2: define the maximal water volume in the system with the default pre-pressure of 1 bar
2.50
Setting the pre-pressure of the expansion vessel
When it is required to change the default pre-pressure of the expansion vessel (1 bar), keep in mind the following guidelines:
Use only dry nitrogen to set the expansion vessel pre-pressure.
Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure should only be adjusted by a licensed installer.
2.00
1.50
A
1.00
0.50
0.00 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 27
B
65°C water temperature
A Pre-pressure (bar) B System water volume (l)
If the total water volume of the system is <150 l: no change of pre-pressure needed.
If the total water volume of the system is >150 l: change of pre-pressure needed.
NOTE
Never change the pre-pressure of the system to a value lower than 0.3 bar.
In this example (when the needed water temperature is 65°C) the maximal water volume is 215 l.
NOTE
To set the pre-pressure, the expansion vessel needs to be accessed from the front or the right.
Accessing the expansion valve from the front:
Remove the front decoration panel.
Remove the switch box.
Remove the small expansion valve (2 l) only in case of
EKHVMYD.
6
1 2 3 4 5
1 Front decoration panel 2 Switch box 3 Small expansion vessel (2 l) 4 Sound panel 5 Right decoration panel 6 Pre-charge valve
Installation manual
26
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 29

Charging water

8. ELECTRICAL WIRING WORK

1 Connect the water supply to a fill valve (field supply).
2 For EKHVMRD unit, make sure to open the automatic air purge.
3 For EKHVMYD unit, the unit has 2 automatic air purge valves.
Make sure to open both of them for these units.
4 When a tank is used, a 3-way valve needs to be installed (refer
to the manual of the domestic hot water tank for details).
5 Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as possible using the air purge
valves. Air present in the water circuit might cause malfunctioning of the heater kit (if installed).
6 For units with optional heater kit: remove air in the heater vessel
using the heater kit air purge valve.
NOTE
For final purging of the unit, operation of the pump is needed. Therefore, the unit needs to be finally installed.
During filling, it might not be possible to remove all air in the system. Remaining air will be removed through the automatic air purge valves during first operating hours of the system. Additional filling with water afterwards might be required. Pump only operation in order to purge the air of the system is possible through field settings. Refer to field settings "[E-04] Pump only operation" on
page 41 for further details.
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature). However, at all times water pressure shall remain above 1 bar to avoid air entering the circuit.
The unit might dispose some excessive water through the pressure relief valve.
Water quality must be according to EU directive 98/83 EC.

8.1. Precautions on electrical wiring work

WARNING: Electrical installation
All field wiring and components must be installed by an installer and must comply with the applicable legislation
NOTE
Electrical wiring work recommendations.
To persons in charge of electrical wiring work: Do not operate the unit until the refrigerant piping is complete. Running the unit before the piping is ready will break the compressor.
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
WARNING
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with the applicable legislation.
Use only copper wires.
All field wiring must be carried out in accordance with
the wiring diagram supplied with the unit and the instructions given below.
Never squeeze bundled cables and be sure that it does not come in contact with the non-insulated piping and sharp edges. Be sure no external pressure is applied to the terminal connections.
Power supply wires must be attached securely.
If the power supply has a missing or wrong N-phase,
equipment will break down.
Be sure to establish an earth. Do not earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
Be sure to install an earth leakage protector in accordance with the applicable legislation. Failure to do so may cause electric shock or fire.
Be sure to use a dedicated power circuit, never use a power supply shared by another appliance.
When installing the earth leakage protector be sure that it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause a capacitor abnormal heating accident due to high­frequency waves. Therefore, never install a phase advancing capacitor.
Be sure to install the required fuses or circuit breakers.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
27
Page 30
ATTENTION
The equipment described in this manual may cause electronic noise generated from radio-frequency energy. The equipment complies to specifications that are designed to provide reasonable protection against such interference. However, there is no guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping proper distances away from stereo
equipment, personal computers, etc....
In extreme circumstances you shall keep distances of 3m or more and use conduit tubes for power and transmission lines.
WARNING
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Point of attention regarding quality of the public electric power supply.
This equipment complies with respectively:
EN/IEC 61000-3-11 is less then or equal to Z
EN/IEC 61000-3-12
(1)
provided that the system impedance Z
.
max
(2)
provided that the short-circuit power S
sys
is greater than or equal to the minimum Ssc value
at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with respectively:
Z
less than or equal to Z
sys
max
Ssc greater than or equal to the minimum Ssc value.
Z
(Ω) Minimum Ssc value
max
EKHVMYD50A 0.46 1459 kVA
EKHVMYD80A 0.46 1459 kVA
EKHVMRD50A 0.46 1459 kVA
EKHVMRD80A 0.46 1459 kVA
(1) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current 75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase.
Installation manual
28
8.2. Internal wiring – Parts table
Refer to the wiring diagram sticker on the unit. The abbreviations used are listed below:
A1P............................ Main PCB
A2P............................ User interface PCB
A3P............................ Control PCB
A4P............................ Inverter PCB
A5P............................ QA PCB
A6P............................ Filter PCB
A7P......................*.... Digital I/O PCB
A8P......................*.... Demand PCB
A9P............................ Multi tenant PCB
A10P....................*.... Thermostat PCB
A11P....................*.... Receiver PCB
B1PH......................... High pressure sensor
B1PL.......................... Low pressure sensor
C1~C3 ....................... Filter capacitor
C1~C3 (A4P)............. PCB capacitor
DS1 (A*P).................. Dip switch
F1U............................ Fuse (T, 3.2 A, 250 V)
F1U (A1P,A3P,A9P) ... Fuse (T, 3.15 A, 250 V)
sc
F1U (A6P) ................. Fuse (T, 6.3 A, 250 V)
F1U,F2U (A7P)....*.... Fuse (5 A, 250 V)
F3U,F4U.............. *.... Fuse (T, 6.3 A, 250 V)
HAP (A*P) ................. PCB LED
IPM1.......................... Integrated power module
K1A~K3A................... Interface relay
K1E~K3E................... Electronic expansion valve
K*R (A*P) .................. PCB relay
K1S~K3S................... 3-way valve
K4S..................... #.... 2-way valve
M1C........................... Compressor
M1F ........................... Switch box cooling fan
M1P,M2P ................... DC inverter pump
PC (A11P) ...........*.... Power circuit
PHC1................... *.... Optocoupler input circuit
PS (A*P).................... Switching power supply
Q1DI,Q2DI.......... #.... Earth leakage protector
Q2L............................ Thermal protector water piping
R1,R2 (A4P).............. Resistance
R1L............................ Reactor
R1H (A10P).........*.... Humidity sensor
R1T (R10P) .........*.... Ambient sensor
R2T......................*.... Domestic hot water tank thermistor
R2T......................*.... External sensor (floor or ambient)
R3T............................ Liquid thermistor R410A
R4T............................ Returning water thermistor
R5T............................ Leaving water thermistor (heating)
R6T............................ Discharge thermistor
R7T............................ Liquid thermistor R134a
R8T............................ Fin thermistor
R9T............................ Leaving water thermistor (cooling)
R10T.......................... Liquid thermistor (cooling)
R11T.......................... Suction thermistor (cooling)
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 31
RC (A*P).................... Receiver circuit
S1PH ......................... High pressure switch
S1S..................... #.... Benefit kWh rate power supply contact
S3S..................... #.... Input multiple setpoint 1
S4S..................... #.... Input multiple setpoint 2
SS1 (A1P).................. Selector switch (emergency)
SS1 (A2P).................. Selector switch (master/slave)
SS1 (A7P)............* .... Selector switch
TC (A*P) .................... Transmitter circuit
T1R,T2R (A*P) .......... Diode bridge
T3R............................ Power module
V1C~V8C .................. Ferrite core noise filter
X1M~X3M.................. Terminal strip
X1Y~X4Y...................Connector
X*M (A*P) ............* .... PCB terminal strip
Z1F~Z5F (A*P) .......... Noise filter
*.... Included in option kit
#.... field supplied
NOTE
The wiring diagram on the indoor unit is only for the indoor unit.
For the outdoor unit refer to the wiring diagram of the outdoor unit.
8.3. System overview of field wiring
Field wiring consists out of power supply, multi tenant power supply, indoor-outdoor communication (=transmission) wiring, wiring of the user interface, wiring for connection of options and field supply accessories.
NOTE
Carefully install multi tenant power supply. This power supply will guarantee correct outdoor unit operation if one tenant shuts of power supply. If the multi tenant power supply is not installed, the outdoor unit will stop operating if one tenant shuts off the main power supply.
If during service the main power supply is cut off for safety of electric shock, make sure that also the multi tenant power supply is cut off.

8.4. Requirements

A power supply (see table below) must be provided for connection of the unit. The power supply must be protected with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage protector in accordance with applicable legislation.
Selection and sizing of the wiring should be done in accordance with the applicable legislation based on the information mentioned in the table below:
Maximum
Cable
bundle
Item
In case of normal kWh rate power supply installation
1 HV Multi tenant power supply 2 1 2 PS Normal kWh rate power supply 2+GND
In case of benefit kWh rate power supply installation
1 HV Multi tenant power supply 2 1 2 PS Normal kWh rate power supply 2+GND 1.25 3 PS Benefit kWh rate power supply 2+GND
4 LV Transmission wiring (F1/F2) 2
5 LV Standard remote controller (P1/
6 LV Secondary remote controller
7 LV Domestic hot water tank
8 LV External room thermostat
9 LV Benefit kWh rate power supply
10 LV
11 LV
12 LV Heater kit signal
13 HV
14 HV
15 HV Cooling on/off output 2
16 HV Heater kit control
PS = Power supply LV = Low voltage HV = High voltage
(a) Optional (b) Refer to the nameplate on the indoor unit.
(c) Minimum cable section 0.75 mm2. (d) This device and connection cable is delivered with the domestic hot water tank. (e) Only for EKHVMYD models.
P2)
(P1/P2)
thermistor (R2T)
signal ON/OFF
switch (S1S)
Multiple set point signal 1
Multiple set point signal 2
3-way valve (K1S)
Digital I/O PCB outputs
Description
(a)
(a)
(a)
(a)
(a)
(a)
(a)
(a)
Required number
of conductors
(a)
(a)
Refer to the installation manual of the heater kit
Refer to the installation manual of the heater kit
2
2
2
2
2
2
2
3
2
running
current
(b)
(b)
–1.25
(c)
(c)
(c)
(d)
100 mA
100 mA
100 mA
100 mA
(d)
300 mA
300 mA
(e)
(c)
(c)
(c)
(c)
(c)
(c)
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
29
Page 32

8.5. Routing

8.6. Connection

Take out the switchbox and put it in front of the unit and open the switchbox cover. Refer to "7.1. Selecting an installation location" on
page 18.
NOTE
When installing field supply or option cables, always make sure that the switchbox is placed before the unit. This will make it possible to remove the switchbox easily during service.
Route the wires into the unit as follows:
PS
HV
LV
LV HV
PS
LV
HV
PS
PS
HV
LV
Use the appropriate cables, connect the power supply, multi tenant power supply, and communication cable(s) to the appropriate terminals as shown below.
5 5
1
5
3
2
4
1 Power supply 2 Multi tenant power supply 3 Transmission wiring 4 User interface wiring 5 Stress relief
PS
LV H V
LV HV+PS
To avoid electric noise problems, be sure that cables are put in the correct bundle as mentioned on the figure.
Be sure to fix the cable with cable ties to the cable tie mountings to ensure strain relief and to make sure that it does not come in contact with the piping and sharp edges.
CAUTION
Do not push or place redundant cable length in the unit.
Refer also to the wiring diagram for further details.
For the connections of optional PCB's please refer to the respective installation manual.
WARNING
The length of the conductors between the power supply stress relief and the terminal block itself must be such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
Installation manual
30
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 33

Installation and connection of the remote controller

The unit is equipped with a remote controller offering user-friendly way to set up, use and maintain the unit. Before operating the remote controller, follow this installation procedure.
X3M
6
P2
P1
X3M
P2
1
P1
NOTE
The wiring for connection is not included.
The remote controller, delivered in a kit, has to be mounted indoors.
When the remote controller thermostat function is used, select the installation location considering it should be a place:
where the average temperature in the room can be
detected,
that is not exposed to direct sunlight,
that is not near a heat source,
that is not affected by outside air or air draught due
to e.g. door opening/closing,
where the display is kept clean,
where the temperature is between 0°C and 50°C,
where the relative humidity is maximum 80%.
1 Remove the front part of the remote controller.
Insert a slotted screwdriver into the slots (1) in the rear part of the remote controller, and remove the front part of the remote controller.
2 Fasten the remote controller on a flat
surface.
2
P1P2
P1P2
3
4 5
1 Unit 2 Rear part of the remote controller 3 Front part of the remote controller 4 Wired from the rear 5 Wired from the top 6 Notch the part for the wiring to pass through with nippers,
etc.
Connect the terminals on top of the front part of the remote controller and the terminals inside the unit (P1 to X3M: P1, P2 to X3M: P2).
NOTE
Peel the shield for the part that has to pass through the inside of the remote controller case ( l ).
1
4 Reattach the upper part of the remote controller.
Be careful not to pinch the wiring when attaching.
NOTE
3 Wire the unit.
NOTE
Be careful not to distort the shape of the lower part of the remote controller by over tightening the mounting screws.
If next to the standard remote controller the optional remote controller is installed as well:
Connect the electrical wires of both remote controllers in the same way like described below.
Select a master and a slave remote controller by switching the SS1 selector switch.
PCB
SS
M
SS1
S Slave
M Master
Only the remote controller set as master can work as room thermostat.
First begin fitting from the clips at the bottom.
1
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
31
Page 34
Connection to a benefit kWh rate power supply
WARNING
A benefit kWh rate power supply is only possible for the indoor unit. For compressor reliability reasons it is not allowed to connect the outdoor unit to such a power supply.
Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such benefit rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the benefit kWh rate power supply delivery systems available, if any.
When the equipment is connected to such benefit kWh rate power supply, the electricity company is allowed to:
interrupt power supply to the equipment for certain periods of time;
demand that the equipment only consumes a limited amount of electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the unit compressors will not operate.
Possible types of benefit kWh rate power supply
Possible connections and requirements to connect the equipment to such power supply are illustrated in the figures below:
1
2
1
2
1
2
3
1
2
3
[6-04]=1
LN
LN
LN
S1S
S1S
S1S
1
2
43
1
2
43
1
2
3
4 4
[6-04]=2
LN
1
S1S
43
LN
2
S1S
43
L N
3
S1S
WARNING
For a benefit kWh rate power supply like illustrated below as type 1
During the period that the benefit kWh rate is active and power supply is continuous, then stand-by power consumption of the inverter PCB is possible.
LN
6
4
X3M7 8 X2M8 9X1ML N
1 Benefit kWh rate power supply box 2 Receiver controlling the signal of the electricity company 3 Benefit kWh rate power supply 4 Voltage free contact to indoor unit 5 Normal kWh rate power supply 6 Fuse (field supply)
In case of benefit kWh rate power supply installation, remove the wiring bridges on X2M before installing the normal kWh rate power supply.
5
X2M10 118 9
Installation manual
32
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 35
Type 1
The benefit kWh rate power supply is of the type that power supply is not interrupted.
Type 2
The benefit kWh rate power supply is of the type that power supply will be interrupted after elapse of time.
Type 3
The benefit kWh rate power supply is of the type that power supply is interrupted immediately.
When parameter [6-04]=1 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will open and
the unit will go in forced off mode
(1)
.
When parameter [6-04]=2 at the moment that the benefit kWh rate signal is sent by the electricity company, that contact will close and
the unit will go in forced off mode
(1) When the signal is released again, the voltage free contact will close and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to field setting "[8] Option setup, "[8-01]" on
page 39 in the chapter "9.3. Field settings" on page 34.
(2) When the signal is released again, the voltage free contact will open and
the unit will restart operation. It is therefore important to leave the auto restart function enabled. Refer to field setting "[8] Option setup, "[8-01]" on
page 39 in the chapter "9.3. Field settings" on page 34.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
(2)
.

9. START-UP AND CONFIGURATION

The indoor unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user expertise.
ATTENTION
It is important that all information in this chapter is read sequentially by the installer and that the system is configured as applicable.

9.1. Pre-operation checks

Switch off the power supply before making any connections.
After the installation of the unit, check the following:
1 Field wiring
Make sure that the field wiring has been carried out according to the instructions described in the chapter "8. Electrical wiring
work" on page 27, according to the wiring diagrams and
according to European and national regulations.
2 Fuses and protection devices
Check that the fuses and other locally installed protection devices are of the size and type specified in the chapter
"Electrical specifications: power supply" on page 59. Make sure
that neither a fuse nor a protection device has been bypassed.
3 Earth wiring
Make sure that the earth wires have been connected properly and that the earth terminals are tightened.
4 Internal wiring
Visually check the switch box and the inside of the unit on loose connections or damaged electrical components.
5 Installation
Check that the unit is properly installed, to avoid abnormal noises and vibrations when starting up the unit.
6 Damaged equipment
Check the inside of the unit on damaged components or squeezed pipes.
7 Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a refrigerant leak try to repair the leak (recovery, repair, and vacuuming needed). If it is impossible to repair by yourself, perform a recovery operation as mentioned in chapter
"11.3. Vacuuming/recovery and maintenance on refrigerant side" on page 55 and call your local dealer.
Do not touch any refrigerant which has leaked out of refrigerant piping connections. This may result in frostbite.
8 Vacuuming and refrigerant charging
Refer to the outdoor unit manual for more details.
9 Water leak
Check the inside of the unit on water leakage. In case there is a water leakage try to repair the leak. If it is impossible to repair by yourself, close the water inlet and water outlet shut-off valves and call your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The voltage must correspond to the voltage on the identification label of the unit.
Installation manual
33
Page 36
11 Air purge valve
Make sure the air purge valve of the heat pump is open (at least 2 turns).
Make sure the air purge valve of the heater kit is open (at least 2 turns). See installation manual of the heater kit.
12 Shut-off valves
Make sure that the shut-off valves are correctly installed and fully open.
Operating the system with closed valves will damage the pump!
Once all checks are fulfilled, the unit must be closed, only then can the unit be powered up. When the power supply to the indoor unit is turned on, "88" is displayed on the remote controller during its initialization, which might take up to 30 seconds. During this process the remote controller can not be operated.

9.2. Final air purging

To get rid of all the air in the system, the pump should be operated.
Therefore, change the field setting [E-04] as explained in the chapter
"9.3. Field settings" on page 34. More details about setting "[E-04] Pump only operation" can be found on page 41.
In case of an optional tank installed with the EKHVMYD units the system includes two 3-way valves (cool/heat and heat/domestic hot water). If no tank is installed, only 1 3-way valve is included.
In case of an optional tank installed with the EKHVMRD units the system includes one 3-way valves (heat/domestic hot water).

9.3. Field settings

The indoor unit should be configured by the installer to match the installation environment (outdoor climate, installed options, etc.) and user demand. Therefore, a number of so called field settings are available. These field settings are accessible and programmable through the user interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example [5-03], which is indicated on the user interface display. The first digit [5] indicates the 'first code' or field setting group. The second and third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given in the "9.9. Field
setting table" on page 49. In this list we provided for 2 columns to
register the date and value of altered field settings at variance with the default value.
A detailed description of each field setting is given under
"9.5. Detailed description" on page 35.

9.4. Procedure

To change one or more field settings, proceed as follows.
3
2
1 Press the z button for a minimum of 5 seconds to enter FIELD
SET MODE. The $ icon (3) will be displayed. The current selected field setting code is indicated ; (2), with the set value displayed to the right - (1).
2 Press the ébi button to select the appropriate field setting
first code.
3 Press the ébj button to select the appropriate field setting
second code.
4 Press the pfi button and pfj button to change
the set value of the select field setting.
5 Save the new value by pressing the pr button.
6 Repeat step 2 through 4 to change other field settings as
required.
7 When finished, press the z button to exit FIELD SET MODE
NOTE
Changes made to a specific field setting are only stored when the pr button is pressed. Navigating to a new field setting code or pressing the z button will discard the change made.
The field settings are grouped by their field setting first code. For example, field settings [0-00]; [0-01]; [0-02]; [0-03] are defined as "Group 0". When different values are changed within the same group, pressing the pr button will save all the values changed within this group. Be aware of this when changing field settings within the same group and pressing on the pr button.
1
.
Installation manual
34
NOTE
NOTE
Before shipping, the set values have been set as shown under "9.9. Field setting table" on page 49.
When exiting FIELD SET MODE, "88" may be displayed on the remote controller LCD while the unit initializes itself.
When running through the field settings you may notice that there are some more field settings as there are mentioned in the "9.9. Field setting table" on page 49.
These field settings are not applicable and may not be changed!
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 37

9.5. Detailed description

19°C
19°C
19°C
22°C
21°C
62°C
62°C
62°C
65°C
64°C
18°C
57°C
5:00
23:00
19°C
18°C
19°C
22°C
21°C
62°C
60°C
62°C
65°C
64°C
19°C
62°C
19°C
62°C
19°C
62°C
57°C
60°C
For a summary of all field settings refer to "9.9. Field setting table" on
page 49.
[0] Remote control setup
[0-00] User permission level
The remote controller can be programmed to make certain buttons and functions unavailable for the user. There are 2 permission levels defined. Both levels (level 2 and level 3) are basically the same, the only difference is that for level 3 no water temperature settings are possible (see table below).
level 2 level 3
Operation ON/OFF Operable Operable
Domestic water heating operation ON/ OFF
Setting the leaving water temperature Operable
Setting the room temperature Operable Operable
Quiet mode ON/OFF
Weather dependent set point operation ON/OFF
Setting the clock
Programming the schedule timer
Schedule timer operation ON/OFF Operable Operable
Field settings
Error code display Operable Operable
Test operation
By default no level is defined so all buttons and functions are operable. The actual permission level is determined by field setting. For permission level 2, set field setting [0-00] to 2, for permission level 3, set field setting [0-00] to 3. Once the field setting is set, the chosen permission level is not yet active. Enabling the selected permission level is done by simultaneously pressing buttons pi and pj immediately followed by simultaneously pressing buttons s and ba, and keeping all 4 buttons pressed for at least 5 seconds. Note that no indication on the remote controller is given. After the procedure the blocked buttons will not be available anymore. Deactivating the selected permission level is done in the same way.
[0-01] Room temperature compensation value
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be used as countermeasure for thermistor tolerances or capacity shortage. The compensated temperature (= measured temperature plus compensation value) is then used for controlling the system and will be displayed in the temperature read-out mode. See also
"[9] Automatic temperature compensation" on page 39 for
compensation values for leaving water temperature and domestic hot water temperature.
[0-02] Setting not available
[0-03] Status: defines whether the ON/OFF instruction can be
used in the schedule timer for space heating. Refer to the operation manual for details how to program the schedule timer. The schedule timer for space heating can be programmed in 2 different ways: based on the temperature set point (both leaving water temperature and room temperature) and based on the ON/OFF instruction.
NOTE
By default space heating based on temperature set point (method 1) is enabled, so only temperature shifts are possible (no ON/OFF instruction).
Advantage of this method is that you can simply switch off the space heating operation by pushing the y button without disabling the automatic domestic hot
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
water storage operation (e.g. during summertime when no space heating is required).
Operable Operable
Operable
Permission
In the following tables both methods on how to interpret the schedule timer are shown.
Method 1 Space heating based on temperature set point
During operation During schedule timer operation the operation LED is lit
When pushing the y button
When pushing the r/p button
(a) For leaving water temperature and/or room temperature
continuously.
The schedule timer for space heating will stop and will not start again. The controller will be switched off (operation LED will stop working). However, the schedule timer icon will stay displayed
which means that the domestic water heating stays enabled.
The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again. The schedule timer icon will not be displayed anymore.
(a)
Operation example: Schedule timer based on temperature set
points.
When setback function is enabled, the setback operation will have priority over the scheduled action in the schedule timer.
T
22
22°C
65
1
19
19°C19°C19°C
62
62°C62°C
65°C
19
62
62°C
21°C
21
64°C
64
19
62
t
16:00
0:30
6:30 9:00
T
2
18
18°C
60
60°C
57
23:00
A
57°C
5:00
5:0023:00
t
T
22°C
22
65
3
19
19°C
62
62°C62°C
1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are enabled A Setback function
t Time
T Temperature set point
65°C
60
60°C
23:00
16:00
Room temperature
Leaving water temperature
0:30
18°C
18
57
57°C
21°C
21
64
64°C
19
19°C
19
19°C
62
62
62°C
62°C
5:00 9:00
6:30
19°C
19
19
19°C
62
62
62°C
t
Installation manual
35
Page 38
Method 2 Space heating based on ON/OFF instruction
18°C
60°C
5:00
23:00
19°C
19°C
22°C
21°C
62°C
62°C
65°C
64°C
19°C
19°C
22°C
21°C
62°C
62°C
65°C
64°C 18°C
60°C
During operation When the schedule timer switches space heating OFF,
When pushing the y button
When pushing the r/p button
the controller will be switched off (operation LED will stop working). Note that this has no influence on the domestic water heating.
The schedule timer for space heating will stop (when active at that moment) and will start again at the next scheduled ON function. The "last" programmed command overrules the "preceding" programmed command and will remain active until the "next" programmed command occurs. Example: imagine the actual time is 17:30 and actions
are programmed at 13:00, 16:00 and 19:00. The "last" programmed command (16:00) overruled the "previous" programmed command (13:00) and will remain active until the "next" programmed command (19:00) occurs. So in order to know the actual setting, one should consult the last programmed command. It is clear that the "last" programmed command may date from the day before. Refer to the operation manual. The controller will be switched off (operation LED will stop working). However the schedule timer icon will stay displayed which means that the domestic heating stays enabled.
The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again. The schedule timer icon will not be displayed anymore.
Operation example: Schedule timer based on ON/OFF instruction.
When setback function is enabled, the setback operation will have priority over the scheduled action in the schedule timer if ON instruction is active. If OFF instruction is active this will have priority over the setback function. At any time the OFF instruction will have the highest priority.
B
22
22°C
65
1
19°C19°C
19
62
62°C62°C
65°C
OFF ONON
21°C
21
64°C
64
19
62
t
9:00
16:00
6:300:30
[1] Automatic storage timing for domestic water heating
In this mode, the indoor unit will deliver hot water to the domestic hot water tank based on the daily fixed pattern. This mode will continue until storage temperature is reached.
Automatic storage is the advised domestic hot water mode. In this mode water heats up during the night (when space heating requirements are lower) until the storage set point. The heated water is stored in the domestic hot water tank at a higher temperature so it can fulfil the domestic hot water requirements throughout the day.
The storage temperature set point and timing are field settings.
[1-00] Status: defines whether the domestic water heating
(storage mode) during night is enabled (1) or not (0).
[1-01] Start time: time of the night at which the domestic water
should be heated.
[1-02] Status: defines whether the domestic water heating
(storage mode) during daytime is enabled (1) or not (0).
[1-03] Start time: time of the day at which the domestic water
should be heated.
NOTE
Make sure the domestic hot water is only heated up to the domestic hot water temperature you require. Start with a low domestic hot water storage temperature set point, and only increase if you feel that the domestic hot water supply temperature is not sufficient for your needs (this depends on your water using pattern).
Make sure the domestic hot water is not heated unnecessary. Start with activating automatic storage during night (default setting). If it seems that the domestic hot water night storage operation is not sufficient for your needs, an additional storage during daytime can be set.
For energy-saving purposes, it is advised to enable the weather dependent domestic water heating. Refer to setting "[b-02]" on page 40.
Refer to "[b] Domestic hot water set points" on page 40 for temperature set points.
18
23:00
23:00
18°C
18
60
60°C
18°C
60
60°C
A
OFF ONON
5:00
5:0023:00
21
21°C
64
64°C
6:30 9:00
t
19
62
t
2
B
22
22°C
65
65°C
19
19°C19°C
62
62°C62°C
3
16:00
1 Schedule timer 2 Setback function 3 When both setback function and schedule timer are enabled A Setback function B ON/OFF instruction
t Time
T Temperature set point
Room temperature
Leaving water temperature
[0-04] Status: defines whether the ON/OFF instruction can be
used in the schedule timer for cooling. Same as for [0-03] but for cooling schedule timer.
For cooling, no setback function is available.
Installation manual
36
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 39
[2] Automatic setback function
Setback function provides the possibility to lower the room temperature. The setback function can for instance be activated during the night because the temperature demands during night and day are not the same.
NOTE
By default the setback function is enabled.
The setback function can be combined with the
automatic weather dependent set point operation.
Setback function is an automatic daily scheduled function.
[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)
[2-01] Start time: time at which setback is started
[2-02] Stop time: time at which setback is stopped
Setback can be configured for both room temperature control and leaving water temperature control.
T
A
21°C
[5-03] 18°C
t
[2-01] [2-02]
A Normal room temperature set point
t Time
T Temperature
T
65°C
A
5°C [5-02]
60°C
B
t
[2-01] [2-02]
A Normal leaving water temperature set point B Leaving water setback temperature
t Time
T Temperature
It is advised to set the start time of automatic storage during night [1-01] on the moment that the setback function starts [2-01].
Refer to "[5] Automatic setback and disinfection set point" on page 38 for temperature set points.
NOTE
Setback function for cooling does not exist.
[3] Weather dependent set point
When weather dependent operation is active, the leaving water temperature is determined automatically depending on the outdoor temperature: colder outdoor temperatures will result in warmer water and vice versa. The unit has a floating set point. Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point.
During weather dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C. This "Shift value" is the temperature difference between the temperature set point calculated by the controller and the real set point. E.g. a positive shift value means that the real temperature set point will be higher than the calculated set point.
It is advised to use the weather dependent set point because it adjusts the water temperature to the actual needs for space heating. It will prevent the unit from switching too much between thermo ON operation and thermo OFF operation when using the remote controller room thermostat or external room thermostat.
T
t
Lo_Ti
+ 05
Shift value
Hi_Ti
Lo_A Hi_A T
T
t
T
A
Shift value = Shift value
Target water temperature
Ambient (outdoor) temperature
00
– 05
A
[3-00] Low ambient temperature (Lo_A): low outdoor
temperature.
[3-01] High ambient temperature (Hi_A): high outdoor
temperature.
[3-02] Set point at low ambient temperature (Lo_Ti): the target
outgoing water temperature when the outdoor temperature equals or drops below the low ambient temperature (Lo_A). Note that the Lo_Ti value should be higher than Hi_Ti, as for colder outdoor temperatures (i.e. Lo_A) warmer water is required.
[3-03] Set point at high ambient temperature (Hi_Ti): the target
outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature (Hi_A). Note that the Hi_Ti value should be lower than Lo_Ti, as for warmer outdoor temperatures (i.e. Hi_A) less warm water suffices.
NOTE
If by mistake the value of [3-03] is set higher than the value of [3-02], the value of [3-03] will always be used.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
37
Page 40
[4] Disinfection function
This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a specific temperature.
NOTE
If a domestic hot water tank is installed, the disinfection function is enabled by default.
[4-00] Status: defines whether the disinfection function is turned
ON (1) or OFF (0).
[4-01] Operation interval: day of the week at which the domestic
water should be heated.
[4-02] Start time: time at which the disinfection operation is
started
Even if all schedule timers are de-activated and there is no reheat function active, the disinfection function will operate if a domestic hot water tank is installed and field setting [4-00] is set to ON.
The disinfection function field settings must be configured by the installer according to national and local regulations.
Refer to "[5] Automatic setback and disinfection set point" for temperature set points.
[5] Automatic setback and disinfection set point
See also "[4] Disinfection function" on page 38 for more information about the disinfection operation.
[5-00] Set point: disinfection water temperature to be reached
[5-01] Interval: time period defining how long the disinfection
temperature set point should be maintained
T
ABC
D
E
F
G
t
A Storage operation (if activated) B Reheat operation (if activated) C Disinfection operation (if activated)
Field settings
D Disinfection operation temperature [5-00] (e.g. 70°C) E Hot water storage temperature [b-03] (e.g. 60°C) F Reheat maximum water temperature [b-01] (e.g. 45°C)
G Reheat minimum water temperature [b-00] (e.g. 35°C)
t Time
T Domestic hot water tank temperature
See also "[2] Automatic setback function" on page 37 for more information about setback operation.
[5-02] Leaving water setback temperature.
[5-03] Room setback temperature.
[5-04] Setting not available
[6] Option setup
[6-00] Domestic hot water tank option
If the domestic hot water tank is installed, its operation must be enabled by field setting. Default [6-00]=0 which means no tank is installed. Set [6-00] to 1 if the optional domestic hot water tank is installed.
NOTE
When enabling the domestic hot water tank option be aware that the advised default settings become active:
[1-00]=1=automatic night storage
[4-00]=1=disinfection function
[6-01] External room thermostat option
If the optional external room thermostat is installed, its operation must be enabled by field setting. Default [6-01]=0, which means no external room thermostat is installed. Set [6-01] to 1 if the optional external room thermostat is installed. The external room thermostat only gives an ON/OFF signal to the heat pump based on the room temperature. Because it does not give continuous feedback information to the heat pump, it is supplementary to the remote controller room thermostat function. To have a good control of the system and avoiding frequent ON/OFF it is advised to use the automatic weather dependent set point operation.
[6-02] Heater kit
Once installed, you can activate the heater kit by changing field setting [6-02]=1.
From that moment on, the heat pump system will take the heater kit into account whilst deciding operation. When the heater is actually operating, the heater symbol ( is shown on the remote controller. There is no step 1-2 indication.
For more information, see installation manual of the heater kit, especially concerning the test run for the heater kit.
[6-03] Setting not available
[6-04] Benefit kWh rate power supply mode
If benefit kWh rate power supply is used, the mode must be selected. Default [6-04]=0 which means no benefit kWh rate power supply is used. Set [6-04] to 1 to use benefit kWh rate power supply mode 1 (normally closed contact which will open when the power supply is interrupted), or set [6-04] to 2 to use benefit kWh rate power supply mode 2 (normally opened contact which will close when the power supply is interrupted).
See "Connection to a benefit kWh rate power supply" on page 32 for more information.
[7] Option setup
[7-00] Setting not available.
[7-01] Setting not available.
[7-02] See chapter "9.8. Multiple set point control" on page 46.
[7-03] See chapter "9.8. Multiple set point control" on page 46.
[7-04] See chapter "9.8. Multiple set point control" on page 46.
Installation manual
38
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 41
[8] Option setup
C
[8-00] Remote controller temperature control
When using the remote control delivered with the unit, 2 types of temperature control are possible. Default [8-00]=1 which means that the remote controller is used as room thermostat, so the remote controller can be placed in the living room to control the room temperature. Set [8-00] to 0 to use the unit in leaving water temperature control.
[8-01] Backup heater optional setting
This setting applies to installations with a backup heater installed (refer to "[6-02] Heater kit" on page 38).
[8-01]=0 (default)
During benefit kWh rate power supply mode the backup heater will not operate. No automatic heat pump operation stop is performed at lower ambient temperatures.
[8-01]=1
During benefit kWh rate power supply mode the backup heater will operate automatically in emergency mode. If the ambient temperature is lower than –25°C, the heat pump operation will stop and the unit will automatically change to emergency operation.
For more information about connections to the backup heater, refer to the backup heater installation manual.
[8-02] Emergency operation
During emergency mode, heating is only done by the heater kit, not by the heat pump.
Activation of emergency mode is done by changing field setting [8-02]=1.
Activating the emergency mode will stop the heat pump operation. The pump of the indoor unit will be started, but heating itself is done by the heater kit. If there are no error conditions in leaving or returning water thermistors, the heater kit can start to follow emergency operation.
NOTE
Before activating emergency operation, be sure to activate the heater kit. The heater will stay in emergency mode until the field setting is set back to default [8-02]=0.
[8-03] Quiet mode
The unit has a quiet mode functionality for which 3 levels can be selected:
[8-03]=1 low noise level 1 (default)
[8-03]=2 low noise level 2
[8-03]=3 low noise level 3
Activating this quiet mode is done by pushing the QUIET MODE button on the remote controller or through the schedule timer.
[8-04] Freeze-up prevention
The unit has a freeze-up prevention functionality for which 3 levels can be selected:
[8-04]=0 prevention level 0 (default: no prevention)
[8-04]=1 prevention level 1
[8-04]=2 prevention level 2
The freeze-up prevention is only active when the unit is in thermo OFF condition. If prevention level 1 is enabled, the freeze-up prevention will start if the outdoor ambient temperature <4°C and if leaving or return water temperature <7°C. For prevention level 2, the freeze-up prevention will start as soon as the ambient temperature <4°C. For both cases the pump will operate and if leaving or return water <5°C for 5 minutes the unit will start up to prevent too low temperatures. It is advised to enable freeze-up prevention if the indoor unit is located in a colder ambient room (e.g. garage, ...) to prevent water freeze-up.
[9] Automatic temperature compensation
If needed, it is possible to adjust some thermistor value of the unit by a correction value. This can be used as countermeasure for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus compensation value) is then used for controlling the system and will be displayed in the temperature read-out mode.
[9-00] Leaving water temperature compensation value for
heating operation.
[9-01] Domestic hot water tank compensation value.
[9-02] Thermo ON/OFF admission
By changing this value the operation range for space heating operation can be modified. If the ambient temperature becomes higher than (24°C + the value of [9-02]) no space heating is possible. Space heating can be requested as long as the ambient temperature is lower than (20°C + the value of [9-02]).
Example:
[9-02]=–2°C
T
A
24°C–2°C = 22°C
C
B
20°C–2°C = 18°C
A No space heating operation possible B Request for space heating possible C Hysteresis area T Ambient temperature
[9-03] Leaving water temperature compensation value for
cooling operation. Not available for heating only model.
[9-04] Setting not available.
[A] Option setup
[A-00] Current limitation.
This setting provides the possibility to limit the power consumption of the indoor unit as follows:
[A-00]=0 16.5 A (default)
[A-00]=1 13.2 A (±80%)
[A-00]=2 10.7 A (±65%)
The indoor unit current is limited, the outdoor unit is slave and will also reduce its power consumption consequently (if other indoor units loads correspond). However, transient conditions with higher power consumption are possible.
[A-01] Change setting for allowable height difference between
the highest and lowest installed indoor units. Difference in height between outdoor and indoor units H140 m Difference in height between lowest and heighest indoor unit H215 m. If setting [A-01] is changed, maximum H2 difference can be increased to 25 m. Depending on H2 level, use the settings in the table for designated indoor units.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
39
Page 42
Example 1:
H1
Example 2:
H2
[b] Domestic hot water set points
The reheat mode will prevent the domestic hot water from cooling
[A-01] setting
0x15 m 0
15<x20 m 1
20<x25 m 2
A
[A-01]= 2 (level 2)
down lower than a certain temperature. When enabled the indoor unit will deliver hot water to the domestic hot water tank if the reheat minimum value is reached. The domestic water heating will continue until the reheat maximum temperature is reached. In this way always a minimum of domestic hot water is available.
[b-00] Set point: reheat minimum temperature (see figure
below).
[b-01] Set point: reheat maximum temperature (see figure
D
T
below).
ABC
B
[A-01]= 1 (level 1)
C
x=23 m
[A-01]=0 (default)
x=19 m
E
F
G
X
x=15 m
X
[A-01]=0 (default)
[A-01] setting
0x15 m 0
15<x20 m 1
20<x25 m 2
[A-01]= 2 (level 2)
A Storage operation (if activated) B Reheat operation (if activated) C Disinfection operation (if activated)
Field settings
D Disinfection operation temperature [5-00] (e.g. 70°C) E Hot water storage temperature [b-03] (e.g. 60°C) F Reheat maximum water temperature [b-01] (e.g. 45°C)
G Reheat minimum water temperature [b-00] (e.g. 35°C)
t Time
T Domestic hot water tank temperature
t
C
[A-01]= 1 (level 1)
H1
H2
B
x=23 m
[A-01]=0 (default)
x=19 m
A
x=15 m
[A-01]=0 (default)
[A-02] Temperature difference for leaving and returning water in
heating mode. The unit is designed to support radiator operation. The advised leaving water temperature (set by the remote controller) for radiators is 65°C. In such a case the unit will be controlled to realize a temperature difference (ΔT) of 10°C, which means that the returning water to the unit is around 55°C. Depending on the installed application (radiators, fan coil units, ...) or situation, it can be required to change the ΔT. This can be done by changing field setting [A-02].
[A-03] See chapter "9.8. Multiple set point control" on page 46.
[A-04] See chapter "9.8. Multiple set point control" on page 46.
[b-02] Status: defines whether the weather dependent domestic
water heating is turned ON (1) or OFF (0). If enabled, the storage set point will be set weather dependent. In case of a higher ambient temperature (e.g. during summer­time), the cold supply water to the mixing tap (e.g. shower, bath) will also have a higher temperature. This makes that the temperature of the hot water from the domestic hot water tank may be lower to reach the same water mixing temperature from the shower or bath mixing tap. In this way, with a lower domestic hot water tank temperature setting the comfort level can be kept the same but with a lower energy consumption.
T
[b-04]
55°C
A
15°C25°C
A Ambient temperature T Domestic hot water storage temperature
NOTE
The maximum setting temperature for domestic hot water can be changed with field setting [b-04]. Other settings are fixed
Installation manual
40
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 43
[b-03] Set point: storage temperature (see figure above)
NOTE
If weather dependent domestic water heating is enabled [b-02], the storage temperature will be set automatically and the field setting [b-03] will be of no importance.
[b-04] Maximal domestic hot water setting during weather
depending domestic hot water setpoint. Refer to the figure above.
[C] Leaving water temperature limits
To prevent misuse concerning leaving water temperatures, it is possible to limit the set points.
[C-00] Maximum leaving water setpoint in heating operation.
[C-01] Minimum leaving water setpoint in heating operation.
[C-02] Maximum leaving water setpoint in cooling operation.
[C-03] Minimum leaving water setpoint in cooling operation.
[C-04] Field setting not available.
[d] Domestic water heating retention times
The heat pump can only work in either space heating operation or domestic water heating operation. No simultaneous operation is possible, except when using multiple set point control (see chapter
"9.8. Multiple set point control" on page 46 for more information).
[d-00] Set point: minimum operation time for domestic water
heating
[d-01] Set point: maximum operation time for domestic water
heating
[d-02] Set point: interval minimum stop time of domestic water
heating
Changing the timer values can have an impact on space heating and domestic water heating heat up timers. The default values are proposed but can be changed depending on the complete system installation.
For a detailed explanation about simultaneous request of space heating and domestic water heating, see chapter "9.6. Simultaneous
demand of space heating and domestic water heating" on page 42.
[d-03] Setting not available.
[d-04] Setting not available.
[E] Service mode
[E-00] Vacuum mode
When recovering/vacuuming of the indoor unit is needed, field setting [E-00] can be activated. It will force the unit into thermo OFF and will open the expansion valve of the indoor unit R134a circuit so full vacuuming is possible. By default [E-00]=0, set to 1 to enable the vacuum mode.
NOTE
Do not forget to restore the field setting [E-00] to the default value when vacuuming is finished! See also "11.3. Vacuuming/recovery and maintenance
on refrigerant side" on page 55.
[E-01] Setting not available.
[E-02] Setting not available.
[E-03] Setting not available.
[E-04] Pump only operation
When commissioning and installing the unit it is very important to get all air out of the water circuit.
Through this field setting the pump can be operated without actual operation of the unit. By doing so this will enhance the air removal from the circuit. The pump can operate at different speed:
[E-04]=0 normal operation of the unit (default)
[E-04]=1 low pump speed operation
[E-04]=2 high pump speed operation
If you select [E-04]=1 or 2 and [6-00]=1, the unit will activate the domestic hot water 3-way valve and heat/cool 3-way valve. This function is a helpful feature to get all air removed out of the system (as well in space heating/cooling as in domestic hot water heating).
For EKHVMRD:
[E-04]=1 or 2
Pump operation for 20 minutes
space 3-way valve in space heating mode
if [6-00]=1
Pump operation for 10 minutes
3-way valve in domestic hot water heating mode
For EKHVMYD:
[E-04]=1 or 2
Pump operation for 20 minutes
space 3-way valve in space heating mode
if [6-00]=1
Pump operation for 10 minutes
3-way valve in domestic hot water heating mode
3-way valve in domestic hot water heating mode and
Pump operation for 10 minutes
space 3-way valve in cooling mode
See chapter "10. Final check and test run" on page 52 for more information.
[F] Option setup
[F-00] Temperature difference for leaving and returning water in
cooling mode. Depending on the type of heat emitter in cooling mode (fan coil, floor heating, etc) the difference in temperature between entering and leaving water in cooling mode can be modified by changing setting [F-00] This setting is only applicable for EKHVMYD-units.
[F-01]: Setting not available
[F-02]: Heat recovery setting.
Unit heat recovery = heat recovery within 1 indoor unit (the energy recovered in cooling mode will be used to warm-up the domestic hot water)
[F-02]=1 unit heat recovery is allowed for this unit (default)
[F-02]=2 no heat recovery is allowed for this unit
NOTE
Cooling to heating heat recovery is judged by the outdoor unit logic.
[F-03]: Setting not available
[F-04]: Setting not available
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
41
Page 44

9.6. Simultaneous demand of space heating and domestic water heating

Remote controller leaving water temperature control
When the reheat temperature is reached, the further heat up till storage temperature of the domestic hot water tank will be decided by the running timers which are programmed by the installer.
1 Reheat operation
When requesting space heating and domestic water heating (reheat) at the same time, the domestic water will be heated till maximum reheat temperature, then space heating will start again.
D
ON OFF
G
75°C
J
C
H
B
F
ON OFF
35°C
A
A Operation
Space heating
Domestic water heating
B Domestic hot water reheat thermo-on request C Domestic hot water tank temperature D Leaving water thermo-on request
F Domestic hot water lower limit temperature
G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00]
J Domestic hot water reheat maximum temperature [b-01]
ON ON
OFF OFF
2 Storage operation
When requesting space heating and domestic water heating (storage) at the same time, domestic water will be heated according to running timer, then space heating will start again according to running timer, then domestic water heating will start again according to running timer, this will continue till storage set point is reached.
D
ON OFF
G
75°C
C
J
H
B
F
ON OFF
35°C
A
3
2
1
A Operation
Space heating
Domestic water heating
B Domestic hot water storage thermo-on request C Domestic hot water tank temperature D Leaving water thermo-on request
F Domestic hot water lower limit temperature
G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00]
J Domestic hot water reheat maximum temperature [b-01]
ON ON
OFF OFF
1 Maximum operation time for domestic water heating
(initial 30 minutes [d-01])
2 Interval minimum stop time for domestic water heating
(initial 15 minutes [d-02])
3 Maximum operation time for domestic water heating
(initial 30 minutes [d-01])
Installation manual
42
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 45
External room thermostat
K
K
When the reheat temperature is reached, the further heat up of the domestic hot water tank will be decided by the external room thermostat thermo conditions and running timers which are programmed by the installer.
1 Reheat operation
When requesting space heating and domestic water heating (reheat) at the same time, the domestic water will be heated till maximum reheat temperature, then space heating will start again.
2 Storage operation
When requesting space heating and domestic water heating (storage) at the same time, domestic water will be heated according to running timer, then space heating will start again according to running timer, then domestic water heating will start again according to running timer, this will continue till storage set point is reached.
E
K
+X°C
–X°C
L
E
K
D
+X°C
–X°C
ON OFF
G
J
C
H
B
F
ON OFF
A
A Operation
Space heating
Domestic water heating
B Domestic hot water reheat thermo-on request C Domestic hot water tank temperature D Room temperature thermo-on request
E Remote controller room temperature F Domestic hot water lower limit temperature
G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00]
J Domestic hot water reheat maximum temperature [b-01]
K External room thermostat set point
L External room thermostat ON/OFF hysteresis
ON ON
OFF OFF
75°C
35°C
L
D
ON OFF
G
75°C
C
J
H
B
F
ON OFF
35°C
A
3
2
1
A Operation
Space heating
Domestic water heating
B Domestic hot water storage thermo-on request C Domestic hot water tank temperature D Room temperature thermo-on request E Remote controller room temperature F Domestic hot water lower limit temperature G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00] J Domestic hot water reheat maximum temperature [b-01] K External room thermostat set point L External room thermostat ON/OFF hysteresis
ON ON
OFF OFF
1 Maximum operation time for domestic water heating
(initial 30 minutes [d-01])
2 Interval minimum stop time for domestic water heating
(initial 15 minutes [d-02])
3 Maximum operation time for domestic water heating
(initial 30 minutes [d-01])
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
43
Page 46
Remote controller room temperature control
When the reheat temperature is reached, the further heat up till storage temperature of the domestic hot water tank will be decided by the remote controller room thermostat in order to prevent the room temperature to drop too much.
1 Reheat operation
When requesting space heating and domestic water heating (reheat) at the same time, the domestic water will be heated till maximum reheat temperature, then space heating will start again.
K
+0.5°C
–0.5°C
E
–3.0°C
D
ON OFF
G
75°C
J
C
H
B
F
ON OFF
35°C
A
A Operation
Space heating
Domestic water heating
B Domestic hot water reheat thermo-on request C Domestic hot water tank temperature D Room temperature thermo-on request
E Remote controller room temperature F Domestic hot water lower limit temperature
G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00]
J Domestic hot water reheat maximum temperature [b-01]
K Remote controller thermostat set point
ON ON
OFF OFF
2 Storage operation
When requesting space heating and domestic water heating (storage) at the same time, domestic water will be heated, but as soon as the room temperature drops 3°C from set point, space heating will start till 0.5°C above set point, then domestic water will be heated again till storage set point.
K
+0.5°C
–0.5°C
E
–3.0°C
D
ON OFF
G
75°C
C
J
H
B
F
ON OFF
35°C
A
4
1 3
5
A Operation
Space heating
Domestic water heating
B Domestic hot water storage thermo-on request C Domestic hot water tank temperature D Room temperature thermo-on request
E Remote controller room temperature F Domestic hot water lower limit temperature
G Domestic hot water upper limit temperature
(maximum possible storage temperature) [b-03]
H Domestic hot water reheat minimum temperature [b-00]
J Domestic hot water reheat maximum temperature [b-01]
K Remote controller thermostat set point
ON ON
OFF OFF
1 Minimum operation time for domestic water heating
(initial 10 minutes [d-00])
2 Maximum operation time for domestic water heating
(initial 30 minutes [d-01])
3 Interval minimum stop time for domestic water heating
(initial 15 minutes [d-02])
4 No simultaneous operation 5 Timers for domestic water heating start 6 Timer for space heating start
(a) The minimum operation time is only valid when room temperature is more
than 3°C lower as set point and set point J is reached.
(b) The maximum operation time is only valid when room temperature is more
than 0.5°C lower as set point and set point J is reached.
6
2
(a)
(b)
Installation manual
44
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 47
Simultaneous
request space
heating and
domestic water
heating?
Yes (1)
Domestic hot water production will start
No
Normal operation
space heating or
domestic water
heating
Domestic hot water
temperature reached
A=minimum ([b-01];
55°C)?
Ye s
Leaving water
control?
No
External room
thermostat contol?
No
Remote controller room
thermostat control.
(1) are in relation with each other (2) are in relation with each other (*) Storage set point can be automatic value if [b-02]=1
No Domestic hot water
Ye s
Ye s
production will
continue without time
limit till A is reached.
Storage setpoint [b-03]
reached? (*)
Yes Yes (2)
Operation will switch to
space heating
Storage setpoint [b-03]
reached? (*)
Yes Yes No
Operation will switch to
space heating
No Timer [d-01] (30
minutes) passed
since? (1)
Operation will
switch to space
heating
Timer [d-02] (15
minutes) passed
sicne? (2)
Ye s
No Room
temperature
–3°C?
<T
set
No Operation will
No Space heating
No
continue in
domestic hot water
operation will
continue till timer
finished
Timer [d-01] (30
minutes) passed
since? (1)
Operation will
continue in
domestic hot water
No
Timer [d-00] (10
minutes) passed
since? (1)
Yes (2)
Ye s
Operation will
switch to space
heating
Yes (2) Space heating
Timer [d-02] (15
minutes) passed
since? (2)
No
operation will
continue timer till
finished
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
45
Page 48

9.7. Simultaneous demand of space cooling and domestic water heating

The unit can perform simultaneous operation of cooling and domestic water heating.
During cooling operation, the energy taken from the cooled motor will be transferred into energy to heat up the domestic water. It is a recovery function and is controlled automatically by the system.
This heat recovery is only possible if heat recovery operation is permitted (it is an installation related setting).

9.8. Multiple set point control

If you want to use multiple set point control, a temperature reducing device (TRD) is needed. The temperature reducing device converts the high inlet water temperature to a reduced water outlet temperature which will be delivered to the appliance(s).
When temperature reducing devices are installed, the system can be configured to use multiple water set points.
The water set points can be selected in function of multiple set point operation patterns.
Below the 2 possible patterns are explained in detail.
Multiple set point control according to pattern A
During normal operation, domestic water heating and space heating modes are separated and activated intermittent to fulfil a simultaneous request. Therefor multiple set point pattern A can be configured to allow simultaneous domestic water heating and space heating operation without intermission.
Schematic overview:
Pattern A design Classic design
During domestic water heating operation, the water temperature set point is normally higher than the set point requested during space heating operation. The valve allowing water to enter the domestic hot water tank coil is open. The heat pump will deliver water with a higher temperature which is needed for production of the domestic hot water. At that time, the lower temperature appliances have to be protected against the higher water temperature by a temperature reducing valve.
The configuration of pattern A allows 2 space heating set points and one (same as in the classic design) domestic hot water set point.
The request signals for space heating can be implemented in 2 different ways (installer choice):
thermo ON/OFF signal (from external room thermostat)
Space 1 DHWSpace 2
TRD
TRD
status signal (active/not active) from the corresponding temperature reducing device (TRD)
Space 1
DHWSpace 2
TRD TRD
Space 1 DHW Space 1
M
TRD
1
DHW
Protection is required by means of a temperature reducing device (TRD) (depending on set point)
Indoor unit
1 Domestic hot water shut-off valve (field supply)
DHW Domestic hot water tank
TRD Temperature reducing device
Space 1 Space 1
Balancing bottle
During space heating operation, water is provided based on the selected water temperature set point for space heating. A shut-off valve (field supply) must be installed in the domestic hot water tank coil circuit. The valve must be closed to protect the domestic hot water tank from cooling down by lower temperature water going through the coil during space heating. Connection and control of this shut-off valve is the reponsability of the installer.
Indoor unit
DHW Domestic hot water tank
TRD Temperature reducing device
Space 1 Space 1
Space 2 Space 2
Balancing bottle
The electrical connections on the unit should be done on the optional demand PCB.
The configuration of pattern A is done by field settings:
1 Select the appropriate pattern: [7-02]=0
2 Turn on multiple set point 1: [7-03]=0 [7-03]=1
Turn on multiple set point 2: [7-04]=0 [7-04]=1
3 Enter the temperature multiple set point 1: [A-03] (see below)
Enter the temperature multiple set point 2: [A-04] (see below)
Configuration example:
Set
point
Domestic hot water
Space 1 65°C [A-03] OFF ON/OFF ON ON OFF
Space 2 35°C [A-04] OFF ON/OFF ON OFF ON
Resulting heat pump water OFF >70°C 65°C 65°C 35°C
70°C
(a) The water temperature needed to reach this set point of course is higher
than 70°C.
Field
setting
(a)
[b-03] OFF ON OFF OFF OFF
Thermo status
Installation manual
46
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 49
NOTE
If the system is configured according to pattern A, nor the remote controller room thermostat function (default OFF if multiple set point is selected) nor the external room thermostat (as replacement of the remote controller room thermostat function) may be used.
The remote controller water temperature value is ignored when pattern A is active.
It is the installers responsibility to make sure no unwanted situations can occur (e.g. too high water temperatures towards floor heating loops, etc.).
It is the installers responsibility to make sure the water circuit is well balanced (e.g. when a domestic hot water request occurs, there will be sufficient flow towards other appliances as well, etc.)
Daikin does not offer any temperature reducing device (TRD). This system only provides the possibility to use multiple set points.
It is advised to only use the automatic storage functionality for domestic water heating when applying pattern A (with a high set point temperature).
Multiple set point control according to pattern B
The basic setup of multiple set point pattern B is the same as a normal classic design, so again no domestic water heating and space heating is possible simultaneously.
Multiple set point pattern B is focussed on space heating operation and allows using multiple water set points in combination with the remote controller or external room thermostat.
The configuration of pattern B allows 3 space heating set points and 1 domestic hot water set point.
The request signals for space heating can be implemented in 2 different ways (installer choice):
thermo ON/OFF signal (from external room thermostat)
A
Space 1
TRD
Space 2 Space 0
TRD
M
DHW
status signal (active/not active) from the corresponding temperature reducing device
A
Space 1 Space 2 Space 0
TRD
TRD
M
DHW
Indoor unit
DHW Domestic hot water tank
TRD Temperature reducing device
Space 0 Space 0
Space 1 Space 1
Space 2 Space 2
Balancing bottle
A Classic room thermostat control with remote controller room
thermostat function and external room thermostat
Space 0, not using a temperature reducing device (TRD), always needs to be linked with the highest water temperature set point and can be controlled by the remote controller room thermostat function or by the external room thermostat. Settings for space 0 can be made
on the remote controller (same as during normal operation
(1)
).
The electrical connections on the unit should be done on the optional demand PCB.
The configuration of pattern B is done by field settings:
1 Select the appropriate pattern: [7-02]=1
2 Turn on multiple set point 1: [7-03]=0 [7-03]=1
Turn on multiple set point 2: [7-04]=0 [7-04]=1
3 Enter the temperature multiple set point 1: [A-03] (see below)
Enter the temperature multiple set point 2: [A-04] (see below)
Configuration example:
Set
point
Space 0 65°C Remote
Space 1 45°C [A-03] OFF ON/OFF ON ON OFF
Space 2 35°C [A-04] OFF ON/OFF OFF ON ON
Resulting heat pump water OFF 65°C 45°C 45°C 35°C
Field
setting
controller
Thermo status
OFF ON OFF OFF OFF
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Pattern B can also be used to do some primary multi zoning (if all set point temperatures are selected the same, no temperature reducing device (TRD) is required).
Multiple thermo ON signals for 3 rooms can be generated. Thermo OFF signals are only valid if all requests are OFF.
(1) When using the automatic weather dependent function for setting of
space 0, you have to make sure that the lowest possible temperature of the space 0 floating set point (including the possible negative shift value) is higher than the temperature set point of spaces 1 and 2. This means that field setting [3-03] of space 0 needs to be higher than temperature set point of spaces 1 and 2.
Installation manual
47
Page 50
NOTE
Leaving water control is not allowed for pattern B.
It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high water temperatures towards floor heating loops, etc.).
It is the installers responsibility to make sure the water circuit is well balanced (e.g. when a domestic hot water request occurs, there will be sufficient flow towards other appliances as well, etc.)
Daikin does not offer any temperature reducing device (TRD). This system only provides the possibility to use multiple set points.
When space 0 is in thermo OFF, but space 1 or 2 are active, space 0 will be fed with water at a temperature equal to the highest set point of spaces 1 and 2. This can lead to unwanted heating of space 0.
Installation manual
48
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 51

9.9. Field setting table

First
Second code
code
0 Remote control setup
1 Automatic storage timing for domestic water heating
2 Automatic setback function
3 Weather dependent set point
4 Disinfection function
5 Automatic setback and disinfection set point
6 Option setup
7 Option setup
Setting name
00 User permission level 2 2~3 1
01 Room temperature compensation value 0 –5~5 0.5 °C
02 Not applicable. Do not change the default value. 1
03 Status: space heating schedule timer mode
Method 1=1 / Method 2=0
04 Status: space cooling schedule timer mode
Method 1=1 / Method 2=0
00 Status: night time storage 1 (ON) 0/1
01 Night time storage start time 1:00 0:00~23:00 1:00 hour
02 Status: day time storage 0 (OFF) 0/1
03 Day time storage start time 15:00 0:00~23:00 1:00 hour
00 Status: setback operation 1 (ON) 0/1
01 Setback operation start time 23:00 0:00~23:00 1:00 hour
02 Setback operation stop time 5:00 0:00~23:00 1:00 hour
00 Low ambient temperature (Lo_A) –10 –20~5 1 °C
01 High ambient temperature (Hi_A) 15 10~20 1 °C
02 Set point at low ambient temperature (Lo_Ti) 70 25~80 1 °C
03 Set point at high ambient temperature (Hi_Ti) 45 25~80 1 °C
00 Status: disinfection operation 1 (ON) 0/1
01 Disinfection operation day selection Fri Mon~Sun
02 Disinfection operation start time 23:00 0:00~23:00 1:00 hour
00 Set point: disinfection operation temperature 70 60~75 5 °C
01 Disinfection operation time duration 10 5~60 5 min
02 Leaving water setback temperature 5 0~10 1 °C
03 Room setback temperature 18 17~23 1 °C
04 Not applicable. Do not change the default value. 0
00 Domestic hot water tank installed 0 (OFF) 0/1
01 Optional room thermostat installed 0 (OFF) 0/1
02 Optional backup heater installed 0 (OFF) 0/1
03 Not applicable. Do not change the default value. 0
04 Benefit kWh power supply mode 0 0/2 1
00 Not applicable. Do not change the default value. 0
01 Not applicable. Do not change the default value. 0
02 Multiple set point pattern 0 (A) 0/1
03 Multiple set point 1 0 (OFF) 0/1
04 Multiple set point 2 0 (OFF) 0/1
Installer setting at variance with default value
Default
value
1 (ON) 0/1
1 (ON) 0/1
Range Step UnitDate Value Date Value
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
49
Page 52
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
8 Option setup
00 Remote controller temperature control 1 (ON) 0/1
01 Backup heater kit optional setting 1 (ON) 0/1
02 Emergency mode 0 (OFF) 0/1
03 Status: low noise level 1 1~3 1
04 Status: freeze-up prevention 0 0~2 1
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating)
0 –2~2 0.2 °C
01 Domestic hot water tank compensation value 0 –5~5 0.5 °C
02 Thermo ON/OFF admission 0 –5~5 0.5 °C
03 Leaving water temperature compensation value
(cooling)
0 –2~2 0.2 °C
04 Not applicable. Do not change the default value. 0
A Option setup
00 Current limitation. 0 0~2 1
01 Indoor unit height difference setting 0 0~2 1
02 Set point: heating required temperature difference
for leaving and returning water
03 Set point: multiple set point 1 required temperature
value
04 Set point: multiple set point 2 required temperature
value
10 5~15 1 °C
35 25~80 1 °C
65 25~80 1 °C
b Domestic hot water set points
00 Set point: reheat minimum temperature 35 35~65 1 °C
01 Set point: reheat maximum temperature 45 35~75 1 °C
02 Status: weather dependent domestic water
heating
1 (ON) 0/1
03 Set point: storage temperature 70 45~75 1 °C
04 Automatic maximum domestic hot water storage
temperature
70 55~75 1 °C
C Leaving water temperature limits
00 Set point: heating leaving water maximum
temperature
01 Set point: heating leaving water minimum
temperature
02 Set point: cooling leaving water maximum
temperature
03 Set point: cooling leaving water minimum
temperature
80 37~80 1 °C
25 25~37 1 °C
20 18~22 1 °C
5 5~18 1 °C
04 Not applicable. Do not change the default value. 0
d Domestic water heating retention times
00 Set point: minimum time for domestic water
heating
01 Set point: maximum time for domestic water
heating
02 Set point: interval minimum stop time of domestic
water heating
10 5~20 1
30 10~60 5
15 5~30 5
03 Not applicable. Do not change the default value. 15
04 Not applicable. Do not change the default value. 40
E Service mode
00 Vacuum mode R134a 0 0/1
01 Not applicable. Do not change the default value. 0
02 Not applicable. Do not change the default value. 0
03 Not applicable. Do not change the default value. 1
04 Pump only operation 0 0~2 1
Installation manual
50
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 53
First code
Second code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
F Option setup continued
00 Set point: cooling required temperature difference
for leaving and returning water
5 5~15 1 °C
01 Not applicable. Do not change the default value. 0
02 Heat recovery allowance 1 0~2 1
03 Not applicable. Do not change the default value. 10
04 Not applicable. Do not change the default value. 50
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
51
Page 54

10. FINAL CHECK AND TEST RUN

10.3. Indoor unit individual test run

10.1. Final check

Before switching on the unit, read the following:
When the complete installation and all necessary settings have been carried out, be sure that all panels of the unit are closed. If this is not the case, inserting your hand through the remaining openings can cause serious injury due to electrical and hot parts inside the unit.
The service panel of the switch box may only be opened by a licensed electrician for maintenance purposes.
In order to purge most of the air out of the system perform a pump operation as described below:
1 Change field setting [E-04]
The default value is 0.
When changing the setting to 1, the pump will operate at low
speed (pump only, the unit will not operate).
When changing the field setting to 2, the pump will operate at
high speed.
2 When air purging is finished, change the field setting back to 0.
It is the responsibility of the installer to make sure that the air is purged out of the unit and system.
NOTE
Be sure that all stop valves are open. (Refer to vacuuming
Be sure that all water valves are open.
When using thermostatic radiator valves, make sure to open all valves during air purging operation.
procedure of the outdoor unit)

Multi tenant power supply check

Cut off the power supply to the indoor unit. If the multi tenant power supply is installed, the remote controller will keep operating. Confirm that the remote controller still operates for more than 15 seconds after the power supply was cutt off.

10.2. System test run

Before you can check test operation of each indoor unit separately, you have to do the system test run. System test run is explained in the installation manual of the outdoor unit. This is an automatic test run which can take up to more than 1 hour.
When the system test run is finished, it is possible to do an individual test run as described in "10.3. Indoor unit individual test run" on
page 52. During this test run, the installer should check indicated
items.
NOTE
The installer is obliged to verify correct operation of the indoor and outdoor unit after installation. Therefor a test run must be performed according to the procedures described below. At any time it is possible to check correct operation of space heating and domestic water heating.
NOTE
When the indoor units and outdoor unit are powered on for the first time, an initialisation takes place. This will take maximum 12 minutes.
When using the remote controller during the initialisation, an error code (UH) can be displayed.
During the first start up of the unit (the first 48 hours of compressor running), it might happen that the noise level of the unit is higher than mentioned in the technical specifications. This is not an abnormal event.
Start up of the unit in space heating mode is only possible when the outdoor ambient temperature is lower than 20°C. Refer to "[9-02] Thermo ON/OFF
admission" on page 39 how to increase this
temperature limit.

Temperature read-out mode

On the remote controller, the actual temperatures can be displayed.
1 Push and hold the ba button for 5 seconds.
The leaving water temperature is displayed (icons l and = and é are blinking).
2 Use the pi and pj buttons to display:
The entering water temperature (icons l and = are blinking and the é icon is flashing slowly).
The indoor temperature (icons l and = are blinking).
The outdoor temperature (icons l and u are blinking).
The hot water supply tank temperature (icons l and w are
blinking).
3 Push the ba button again to leave this mode. If no button is
pressed, the remote controller leaves the display mode after 10 seconds.

Procedure for space heating/cooling

1 Check the leaving water and entering water temperature through
the remote controller read-out mode and write down the displayed values. See "Temperature read-out mode" on
page 52.
2 Select the operation mode: heating or cooling.
3 Push the z button 4 times so the t icon will be displayed.
4 Perform the test as follows (when no action is performed, the
user interface will return to normal mode after 10 seconds or by pressing the z button once):
To test the space heating/cooling operation push the y button to start the test run operation.
5 The test run operation will end automatically after 30 minutes or
when reaching the set temperature. The test run operation can be stopped manually by pressing the z button once. If there are misconnections or malfunctions, an error code will be displayed on the user interface. Otherwise, the user interface will return to normal operation.
6 To resolve the error codes, see "12.5. Error codes" on page 58.
Installation manual
52
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 55
7 Check the leaving water and entering water temperature through
C–
the remote controller read-out mode and compare them with the values noted with step 1. After 20 minutes of operation an increase/decrease of the values should confirm the space heating/cooling operation.

11.1. Maintenance activities

DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
NOTE
NOTE
To display the last resolved error code, push the z button 1 time. Push the z button again 4 times to return to normal mode.
It is not possible to perform a test run if a forced operation from the outdoor unit is in progress. Should forced operation be started during a test run, the test run will be aborted.

Procedure for domestic water heating

1 Check the domestic hot water tank temperature through the
remote controller read-out mode. See "Temperature read-out
mode" on page 52.
2 Push the w button for 5 seconds.
The w icon will start blinking with 1 second intervals.
3 Keep the unit operating for 20 minutes and check the domestic
hot water tank temperature through the remote controller again. An increase of the value with 5°C should confirm the domestic
water heating operation.
4 The operation will stop if the tank storage temperature has been
reached.

11. MAINTENANCE AND SERVICE

WARNING: ELECTRIC SHOCK
Before carrying out any maintenance or repair activity, always switch off the circuit breaker on the supply panel, remove the fuses or open the protection devices of the unit.
Make sure that before starting any maintenance or repair activity, also the power supply to the outdoor unit is switched off.
Before carrying out any maintenance or repair activity, always switch off the multi tenant power supply.
Do not touch live parts for 10 minutes after the power supply is turned off because of high voltage risk.
Additionally, measure the points as shown in the figure below with a tester and confirm that the voltage of the capacitor in the main circuit is no more than 50 V DC.
In order to ensure optimal availability of the unit, a number of checks and inspections on the unit and the field wiring have to be carried out at regular intervals.
This maintenance should be carried out by your local installer.
To execute the maintenance activities as mentioned below, it is only required to remove the front decoration panel.
To take away the front decoration panel, remove the 2 bottom screws and then unhitch the panel.
2x
C+C+C+
C–
C–
Please note that some sections of the electric component box are hot.
Make sure you do not touch a conductive section.
Do not rinse the indoor unit. This may cause electric
shocks or fire.
Play it safe!
Touch a metal part by hand (such as the stop valve) in order to eliminate static electricity and to protect the PCB before performing service.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
53
Page 56

Checks

The described checks must be executed at least once a year by qualified personnel.
1 Pressure relief valve hose
Check that the pressure relief valve hose is positioned appropriately to drain the water.
2 Water pressure relief valve
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter-clockwise:
If you do not hear a clacking sound, contact your local dealer.
In case the water keeps running out of the unit, close both
the water inlet and outlet shut-off valves first and then contact your local dealer.
3 Indoor unit switch box
Carry out a thorough visual inspection of the switch box and look for obvious defects such as loose connections or defective wiring.
4 Water pressure
Check if the water pressure is above 1 bar. If necessary add water.
5 Water filter
Clean the water filter.

11.2. Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R134a
(1)
GWP
value: 1300
(1)
GWP = global warming potential
NOTE
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. Therefore, an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.
Installation manual
54
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 57

11.3. Vacuuming/recovery and maintenance on refrigerant side

This flow chart indicates the main items and actions which have to be considered during vacuuming/recovery operations on the system. When certain settings and operations explained in the flow chart are not followed this can be improper operation of the unit due to bad vacuuming/ recovery. In case of problems, please contact your local dealer.
R134a circuit needs
to be maintenanced?
Yes Indoor unit remocon
setting [E-00]=1 to
open electronic
expansion valve
No
R410A circuit needs
to be maintenanced?
Ye s
First installation
No
Ye s Ye s
Indoor unit was
powered on?
No
Other indoor or
outdoor unit(s) were
powered on?
No Open stop valve
Ye s Ye s Ye s
Start recovery/
vacuuming of R134a circuit
indoor units
(a)
. Field
(2)
piping and indoor unit
R410A
vacuuming can
start
Maintenance
Complete indoor
system R410A
circuit?
No
1 indoor unit?
Close this indoor
unit stop valve
(a)
(2)
Valves on R410A circuit need to be
opened. Apply
outdoor unit field
setting 2-21 (see
installation manual of
outdoor unit)
Open stop valve
(a)
indoor units.
(2)
Field piping and
indoor unit R410A
vacuuming can start
Ye s
Open all
stopvalves (1)
(a)
and (2)
Apply outdoor
unit field setting
2-21 (see
installation
manual of
outdoor unit)
Field piping +
indoor + outdoor
unit(s)?
No
Field piping only +
indoor unit
Close stop valve
outdoor unit (1)
Open stop valve indoor unit (2)
(a)
(a)
Apply outdoor unit
field setting 2-21
(see installation
manual of outdoor
unit)
Apply outdoor
unit field setting
2-21 (see
installation
manual of
outdoor unit)
Recovery start +
measure
recovered
R410A amount
Maintenance
Start vacuuming
Recharge
system with
measured
R410A amount
Cancel outdoor unit field setting
2-21 (see
installation
manual of
outdoor unit)
(a) (1) and (2) refers to the legend of the figure in next chapter "System overview" on page 56.
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Open stop valve(s) (if applicable)
Restart system
Installation manual
55
Page 58

System overview

1 3
2 3
4
1 Stop valve outdoor unit 2 Stop valve indoor unit 3 Brazing point 4 Field piping

Recovery/vacuuming overview for 1 indoor unit maintenance (R410A circuit connections)

1
VACU

12.2. Opening the unit

To facilitate access to the air purge valve, thermal cut-out, 3-way valve, thermistors, field wiring duct, ..., the top decoration panel of the unit can be removed by removing the 2 screws at the rear and then unhitch the panel. Both the drain plates can be removed.
To gain access to the indoor unit at the front side, the total switch box can be removed from the unit.
1 To remove the front decoration
panel, remove the 2 bottom screws and then unhitch the panel.
2x
4x
2x
234
1 Pressure reducing valve 2 Nitrogen 3 Refrigerant R410A tank (siphon system) 4 Measuring instrument 5 Vacuum pump
5

12. TROUBLESHOOTING

This section provides useful information for diagnosing and correcting certain troubles which may occur in the unit.
This troubleshooting and related corrective actions may only be carried out by your local installer.

12.1. General guidelines

Before starting the troubleshooting procedure, carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.
When carrying out an inspection on the switch box of the unit, always make sure that the main switch of the unit is switched off.
When a safety device was activated, stop the unit and find out why the safety device was activated before resetting it. Under no circumstances safety devices may be bridged or changed to a value other than the factory setting. If the cause of the problem can not be found, call your local dealer
If the pressure relief valve is not working correctly and is to be replaced, always reconnect the flexible hose attached to the pressure relief valve, to avoid water dripping out of the unit!
.
2 Loosen the front screws and unhitch the total switch box.
Switch off all power supply – also outdoor unit power supply, etc., ... – before removing the switch box service cover.
The switch box can now be placed just before the indoor unit. The compressor cable located at the backside of the unit can be untied to place the switch box further away from the unit.
1
4x
1
2
2
1
MAX.
15 cm
1
3
5
Make sure to always fix the cover with the screws when removing the switch box.
Parts inside the unit can be hot and burning is possible.
Make sure to switch off all power supplies before removing the switch box from the unit.
4
Installation manual
56
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 59

12.3. Draining the system

12.4. General symptoms

For EKHVMRD
If draining is needed, connect the drain hose (2) to the drain valve (1) as described in the figure below and open the drain valve (1).
1
2
For EKHVMYD
For draining of the system, connect the drain hose (3) to the drain pan (2) as described in the figure below. Open the drain taps (1) and let the water flow into the drain pan (2).
1
1
Symptom 1: The unit is turned on (y LED is lit) but the unit is not heating as expected
POSSIBLE CAUSES CORRECTIVE ACTION
The temperature setting is not correct.
The water flow is too low. • Check that all shut-off valves of
The water volume in the installation is too low.
Capacity shortage • Check if the cooling fan at the rear
Symptom 2: Pump is making noise (cavitation)
POSSIBLE CAUSES CORRECTIVE ACTION
There is air in the system. Purge air.
Water pressure at pump inlet is too low.
Check the controller set point.
the water circuit are completely open.
• Check if the water filter needs cleaning.
• Make sure there is no air in the system (purge air).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Make sure that the expansion vessel is not broken.
Make sure that the water volume in the installation is above the minimum required value (refer to "Checking
the water volume and expansion vessel pre-pressure" on page 25).
of the switch box is working properly.
• Check if the unit is not installed in a too hot location (>30°C).
• Check on the manometer that there is sufficient water pressure. The water pressure must be >0.3 bar (water is cold), >>0.3 bar (water is hot).
• Check that the manometer is not broken.
• Check that the expansion vessel is not broken.
• Check that the setting of the pre-pressure of the expansion vessel is correct (refer to "Setting
the pre-pressure of the expansion vessel" on page 26).
Symptom 3: The water pressure relief valve opens
2
3
The expansion vessel is broken. Replace the expansion vessel.
The water volume in the installation is too high.
Symptom 4: The water pressure relief valve leaks
Dirt is blocking the water pressure relief valve outlet.
Symptom 5: The user interface displays " certain buttons
The current permission level is set to a level that prevents using the pressed button.
POSSIBLE CAUSES CORRECTIVE ACTION
Make sure that the water volume in the installation is under the maximum allowed value (refer to
"Checking the water volume and expansion vessel pre-pressure" on page 25).
POSSIBLE CAUSES CORRECTIVE ACTION
Check for correct operation of the pressure relief valve by turning the red knob on the valve counter clockwise:
• If you do not hear a clacking sound, contact your local dealer.
• In case the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your local dealer.
nn
nn
POSSIBLE CAUSES CORRECTIVE ACTION
Change the "user permission level" field setting [0-00], see "Field settings" in the operation manual.
" when pressing
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
57
Page 60
Symptom 6: Space heating capacity shortage at low outdoor temperatures
POSSIBLE CAUSES CORRECTIVE ACTION
The heater kit is not activated. Check that the "heater kit operation
status" field setting [6-02] is turned on, see "Field settings" in the operation manual of the indoor unit.

12.5. Error codes

When a safety device is activated, the user interface LED will be flashing, and an error code will be displayed.
A list of errors and corrective actions can be found in the table below.
Reset the safety by pushing the y button.
In case this procedure for resetting the safety is not successful, contact your local dealer.
For other error codes which may be displayed during the system test run or operation, see the installation manual of the outdoor unit.
Error
code
A1 Failure of writing memory
(EEPROM error)
A6 Malfunction of pump in water
circuit (M1P+M2P)
A9 R410A expansion valve error
(K1E)
AA Heater kit thermal cut out error
(if the heater kit option installed)
Heater kit connected to the benefit kWh rate power supply
AE Water system warning low flow
is expected by the unit.
AJ Capacity error Contact your local dealer.
C1 Bad ACS communication Contact your local dealer.
C4 R410A liquid thermistor error
(R3T)
C5 Domestic hot water tank
thermistor error (R2T)
C9 Returning water thermistor error
(R4T)
CA Heating leaving water thermistor
error (R5T)
CE Cooling leaving water thermistor
error (R9T)
CJ Remote controller thermostat
thermistor error
E1 Compressor PCB error Contact your local dealer.
E3 High pressure error (S1PH) • Check wiring connections on
E3 Thermal cut-out error (Q2L) • Reset the thermal cut-out.
Failure cause Corrective action
Contact your local dealer.
• Make sure waterflow is possible (open all valves in the circuit).
• Force clean water through the unit.
• Check wiring connections.
• Contact your local dealer.
• Make sure the circuit is filled with water (no air inside).
• Make sure waterflow is possible (open all valves in the circuit).
Make sure the heater kit is connected to a normal power supply.
• Check filter.
• Make sure all valves are open.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Check if the domestic hot water option is turned active (refer to field setting [6-00]).
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
Contact your local dealer.
outdoor unit and indoor unit.
• Make sure the circuit is filled with water (no air inside, e.g. is the air purge open?)
• Make sure the domestic hot water tank is filled with water.
• Make sure water flow is possible (open all valves in the circuit).
• Make sure the water filter is not blocked.
• Make sure all refrigerant stop valves are open.
• Contact your local dealer.
• Contact your local dealer.
Error
code
E4 Low pressure error (B1PL) • Check wiring connections on
E5 Overload activation of
E9 R134a expansion valve error
F3 Discharge temperature error Contact your local dealer.
J3 Discharge thermistor error (R6T) • Check wiring connections.
J5 R134a liquid thermistor error • Check wiring connections.
J6 R410A liquid thermistor error
J7 R410A suction thermistor error
JA R134a high pressure sensor
JC R134a low pressure sensor error
L1 Compressor inverter PCB error Contact your local dealer.
L4 Fin thermistor error • Check wiring connections.
L5 Compressor inverter PCB error Contact your local dealer.
L8 Compressor inverter PCB error Contact your local dealer.
L9 Compressor inverter PCB error Contact your local dealer.
LC Inverter communication problem Contact your local dealer.
LH Converter error Contact your local dealer.
P1 Main compressor PCB error Contact your local dealer.
PJ Bad combination inverter
U2 Power supply error • Check wiring connections.
U4 QA transmission problem Contact your local dealer.
U5 Remote controller error Contact your local dealer.
UA Type connection problem • Wait till initialisation between
UC Address duplication error Contact your local dealer.
UF Transmission problem with
UF QA wiring problem Contact your local dealer.
UH Address error Contact your local dealer.
Failure cause Corrective action
outdoor unit and indoor unit.
• Contact your local dealer.
compressor (M1C)
(K2E) or R410A expansion valve error (K3E)
(R10T)
(R11T)
error (B1PH)
(B1PL)
components
outdoor unit
Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Contact your local dealer.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Check wiring connections.
• Contact your local dealer.
• Contact your local dealer.
Contact your local dealer.
• Contact your local dealer.
outdoor unit and indoor unit is finished (after power ON, wait at least 12 minutes).
• Contact your local dealer.
Contact your local dealer.
Installation manual
58
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Page 61

13. UNIT SPECIFICATIONS

Technical specifications
Nominal capacity (heating) Nominal capacity (cooling)
(kW) (kW)
EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1
5.6 9 5.6 9 —— 5 8
Casing material Pre-coated sheet metal Dimensions HxWxD
(mm)
705x600x695
Weight
• with packaging
• without packaging
(kg) (kg)
110.8 100.8 115.8 115.8 92 92 107 107
Water connections
• water inlet/outlet G 1" (female)
• water inlet/outlet material
• piping diameter
• maximum working pressure
(inch)
(bar)
brass
1
4
Refrigerant connections
• discharge side diameter
• suction side diameter
• liquid side diameter
Heating water system volume
(mm) (mm) (mm)
12.7
15.9
9.52
(l)
20~200
Refrigerant type R134a Pump
• type DC motor
• no. of speed inverter controlled
Sound pressure level Pressure relief valve water
circuit Operation range - water
side (heating) Operation range - water
side (cooling)
(dBa)
(bar)
(°C)
(°C)
40 42 40 42
3
25~80
5~20
(a)
Operation range - outdoor
• space heating
• domestic hot water
(°C) (°C)
–20~20 –20~35
Operation range - indoor
• Ambient temperature
(a) Water conditions: entering water 55°C/leaving water 65°C. For more information, see data book.
(°C)
5~30
Electrical specifications: power supply
Phase 1N~ Frequency
(Hz)
Voltage range
• minimum
• maximum
(V) (V)
Voltage tolerance –10%/+6% Maximum running current Recommended field fuse
(A) (A)
EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1
50
220 240
16.5 20
Electrical specifications: multi tenant power supply
Phase 1N~ Frequency Voltage
(Hz)
(V)
Voltage tolerance –20%/+20% Maximum running current Recommended field fuse
(A) (A)
EKHVMRD50AAV1 EKHVMRD80AAV1 EKHVMYD50AAV1 EKHVMYD80AAV1
50 24
1
3.15
EKHVMRD50+80AAV1 + EKHVMYD50+80AAV1
Daikin Altherma indoor unit
4PW61263-1A – 10.2010
Installation manual
59
Page 62
NOTES
Page 63
NOTES
Page 64
4PW61263-1A 10.2010
Copyright 2010 Daikin
Loading...