The original instructions are written in English. All other languages
are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE
INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL
AND HOW TO CONFIGURE THE UNIT PROPERLY.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE
REFERENCE.
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
FOR INDOOR INSTALLATION ONLY AND FOR AMBIENT
TEMPERATURES RANGING 4°C~35°C.
Installation manual
1
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
1. DEFINITIONS
1.1. Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and
probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also
be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or
property-damage accidents only.
INFORMATION
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Optional equipment:
Equipment which can optionally be combined to the products as per
the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in
this manual, but which are not supplied by Daikin.
2.GENERALSAFETYPRECAUTIONS
The precautions here, all cover very important topics, so be sure to
follow them carefully.
All activities described in this manual shall be carried out by an
installer and in accordance with the applicable legislation.
Be sure to wear adequate personal protection equipment (protection
gloves, safety glasses, …) when performing installation, maintenance
or service to the unit.
If not sure of installation procedures or operation of the unit, always
contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories
could result in electric shock, short-circuit, leaks, fire or other damage
to the equipment. Be sure only to use accessories and optional
equipment made by Daikin which are specially designed for use with
the products as of subject in this manual and have them installed by
an installer.
Electric current.
Danger of burning and scalding.
1.2. Meaning of used terms
Installation manual:
Instruction manual specified for a certain product or application,
explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application,
explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application,
which explains (if relevant) how to install, configure, operate and/or
maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the
subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required
service to the unit.
Applicable legislation:
All international, European, national and local directives, laws,
regulations and/or codes which are relevant and applicable for a
certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be
installed according to instructions in the documentation.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switch box
service panel or before making any connections or
touching electrical parts.
Do not touch any switch with wet fingers. Touching a switch
with wet fingers can cause electrical shock. Before
touching electrical parts, turn off all applicable power
supply.
To avoid electric shock, be sure to disconnect the power
supply 1 minute or more before servicing the electrical
parts. Even after 1 minute, always measure the voltage at
the terminals of main circuit capacitors or electrical parts
and, before touching, be sure that those voltages are
50 V DC or less.
When service panels are removed, live parts can easily be
touched by accident. Never leave the unit unattended
during installation or servicing when the service panel is
removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
Do not touch the refrigerant piping, water piping or internal
parts during and immediately after operation. The piping
and internal parts may be hot or cold depending on the
working condition of the unit.
Your hand may suffer burns or frostbite if you touch the
piping or internal parts. To avoid injury, give the piping and
internal parts time to return to normal temperature or, if
you must touch them, be sure to wear protective gloves.
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
2
WARNING
■Never directly touch any accidental leaking
refrigerant. This could result in severe wounds caused
by frostbite.
■Do not touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
CAUTION
Do not rinse the unit. This may cause electric shocks or
fire.
3.INTRODUCTION
3.1. General information
Thank you for purchasing this indoor unit.
The unit is the indoor part of the air to water ERHQ or ERLQ heat
pumps. This unit is designed for wall mounted indoor installation. See
"6.1. Selecting an installation location" on page 12. The unit can be
combined with Daikin fan coil units, floor heating applications, low
temperature radiators, Daikin domestic water heating applications
and Daikin solar kit for domestic hot water applications.
Heating/cooling units and heating only units
The unit range consists of two main versions: a heating/cooling
(EKHBX) version and a heating only (EKHBH) version.
Both versions are delivered with an integrated backup heater for
additional heating capacity during low outdoor temperatures. The
backup heater also serves as a backup in case of malfunctioning of
the outdoor unit. The backup heater models are available for a
heating capacity of 3, 6 and 9 kW, and – depending on the heating
capacity – for three different power supply specifications.
Backup heater
Indoor unit modelBackup heater capacity
EKHB*016BB3V33 kW1x 230 V
EKHB*016BB6V36 kW1x 230 V
EKHB*016BB6WN6 kW3x 400 V
EKHB*016BB9WN9 kW3x 400 V
EKHB*016BB6T16 kW3x 230 V
EKHB*016BB9T19 kW3x 230 V
nominal voltage
P
H
43
1
2
T
1 Heat pump capacity
2 Required heating capacity (site dependent)
3 Additional heating capacity provided by the backup heater
4 Equilibriumtemperature (can be set through the user
interface, refer to "8.9. Field settings" on page 26)
Ambient (outdoor) temperature
T
A
Heating capacity
P
H
A
Domestic hot water tank (option)
An optional domestic hot water tank can be connected to the indoor
unit. The domestic hot water tank is available in 2 types:
■tank with built-in electrical booster heater (EKHW*) in 3 different
sizes: 150, 200 and 300 litre,
■tank without electrical booster heater (EKHTS) in 2 different
sizes: 200 and 260 litre.
Refer to the domestic hot water tank installation manual for further
details.
Drain pan kit (option)
For heating/cooling versions (EKHBX), it is necessary to install the
EKHBDP drain pan kit.
For more information concerning the drain pan kit, refer to
"6.5. Installation of the EKHBDP drain pan kit (only for EKHBX
models)" on page 14.
Solar kit for domestic hot water tank (option)
For information concerning the EKSOLHW solar kit, refer to the
installation manual of that kit.
INFORMATION
Use the EKSOLHW solar kit only in combination with the
EKHW* domestic hot water tank.
Connection between EKSOLHW and EKHTS domestic hot
water tank is NOT possible.
Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the
indoor unit and allows:
■remote alarm output,
■heating/cooling ON/OFF output,
■bivalent operation (permission signal for the auxiliary boiler) or
Refer to the operation manual of the indoor unit and to the installation
manual of the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for connecting this
PCB to the unit.
Room thermostat kit (option)
An optional room thermostat EKRTW, EKRTWA, or EKRTR can be
connected to the indoor unit. Refer to the installation manual of the
room thermostat for more information.
Bottom plate heater (option)
Connectable heaters
EKBPHT16Y*EKBPHTH16A
EKHBH/X016BBPossiblePossible
(a) Recommended.
(a)
Installation manual
3
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
Possible combinations
EKHBH/X_BB
ERHQ_BAPossible
ERLQ_BAPossible
ERLQ_CA
(b)
(a) If a bottom plate heater is required, see "Bottom plate heater (option)" on page 3.
(b) Bottom plate heater at outdoor unit is controlled by the outdoor unit pcb.
(a)
Possible
Connection to a benefit kWh rate power supply
This equipment allows for connection to benefit kWh rate power
supply delivery systems. Full control of the unit will remain possible
even in case the benefit kWh rate power supply is of the type that
power supply is interrupted. Refer to "Connection to a benefit kWh
rate power supply" on page 21 for more details.
3.2. Scope of this manual
This manual does NOT include the selection procedure and the water
system design procedure. Only some precautions and tips and tricks
about the design of the water circuit are given in a separate chapter
of this manual.
Once the selection is done and the water system is designed, this
manual describes the procedures for handling, installing and
connecting the EKHBH/X units. This manual has been prepared to
ensure adequate maintenance of the unit, and it will provide help if
problems occur.
INFORMATION
Refer to the installation manual of the outdoor unit for
items not described in this manual.
The operation of the indoor unit is described in the indoor
unit operation manual.
3.3. Model identification
Indoor unit
EKHBX016BB3V3
Backup heater nominal
voltage:
V3 = 1P, 230 V
WN = 3P, 400 V
T1 = 3P, 230 V
Backup heater capacity (kW)
Series
Indication of heating/cooling capacity (kW)
X = heating and cooling,
H = heating only
Hydro box
European kit
(a) For exact values, refer to "12. Technical specifications" on page 50.
(a)
3.4. Typical application examples
The application examples given below are for illustration purposes
only.
Application 1
Space heating only application with the room thermostat connected
to the indoor unit.
When the room thermostat (T) is connected to the indoor unit, the
pump (5) will operate when there is a heating request from the room
thermostat, and the outdoor unit will start operating to achieve the
target leaving water temperature as set on the user interface.
When the room temperature is above the thermostat set point, the
outdoor unit and pump will stop operating.
NOTICE
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 20) and to configure the DIP switch toggle switches
correctly (see "8.2. Room thermostat installation
configuration" on page 23).
Drain pan kit (optional)
EKHBDP150
Drain pan
Hydro box
European kit
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
4
Application 2
Space heating only application without room thermostat connected to
the indoor unit. The temperature in each room is controlled by a valve
on each water circuit. Domestic hot water is provided through the
domestic hot water tank which is connected to the indoor unit.
645321
78
M
M1T1M2T2M3
6
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Collector (field supply)
9 By-pass valve (field supply)
10 Domestic hot water tank (optional)
11 Booster heater
12 Heat exchanger coil
FHL1...3 Floor heating loop
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control the floor heating loop
(field supply)
11 12
(1)
(2)
FHL1
FHL2
10
Pump operation
With no thermostat connected to the indoor unit (2), the pump (5) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
INFORMATION
Details on pump configuration can be found under
"8.3. Pump operation configuration" on page 24.
9
T3
FHL3
Domestic water heating
When domestic water heating mode is enabled (either manually by
the user, or automatically through a schedule timer) the target
domestic hot water temperature will be achieved by a combination of
the heat exchanger coil and the electrical booster heater
(4)
heater
.
(3)
or backup
When the domestic hot water temperature is below the user
configured set point, the 3-way valve will be activated to heat the
domestic hot water by means of the heat pump. In case of large
domestic hot water demand or a high domestic hot water
temperature setting, the booster heater (11)
(5)
or backup heater (4)
can provide auxiliary heating.
INFORMATION
Only for EKHW*:
■At low outdoor temperatures when space heating
demand is higher, the indoor unit can be configured to
have the domestic hot water heated by the booster
heater exclusively. This assures that the full capacity
of the heat pump is available for space heating.
■Details on domestic hot water tank configuration for
low outdoor temperatures can be found under
"8.9. Field settings" on page 26, field settings [5-02]
to [5-04].
Only for EKHTS:
■At low outdoor temperatures when space heating
demand is higher, the indoor unit can be configured to
have the domestic hot water heated the heat pump
and backup heater at the same time. This assures
that the interruption of space heating is limited to a
minimum.
■Details on domestic hot water tank configuration for
low outdoor temperatures can be found under
"8.9. Field settings" on page 26, field settings [5-02]
to [5-04].
NOTICE
Be sure that the correct field settings are active or selected
according to the applicable tank type. See field settings in
"[4] Backup/booster heater operation and space heating
off temperature" on page 28 for more details.
(6)
Space heating
The outdoor unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.
NOTICE
When circulation in each space heating loop (FHL1...3) is
controlled by remotely controlled valves (M1...3), it is
important to provide a by-pass valve (9) to avoid the flow
switch safety device from being activated.
The by-pass valve should be selected as such that at all
time the minimum water flow as mentioned under
"6.7. Water pipework" on page 14 is guaranteed.
It is recommended to select a pressure difference
controlled by-pass valve.
(1) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(2) Only applicable for tank with built-in electrical booster heater (EKHW*).
Installation manual
5
(3) Only applicable for tank with built-in electrical booster heater (EKHW*).
(4) Only applicable for tank without electrical booster heater (EKHTS).
(5) Only applicable for tank with built-in electrical booster heater (EKHW*).
(6) Only applicable for tank without electrical booster heater (EKHTS).
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
Application 3
Space heating and cooling application with the room thermostat set
for heating/cooling connected to the indoor unit. Heating is provided
through floor heating loops and fan coil units. Cooling is provided
through the fan coil units only.
Domestic hot water is provided through the domestic hot water tank
which is connected to the indoor unit.
9
T
645321
7
M
6
M
11 12
FCU1
8
FHL1
FCU2
FHL2
FCU3
FHL3
NOTICE
■Make sure to connect the thermostat wires to the
correct terminals (see "Connection of the thermostat
cable" on page 20) and to configure the DIP switch
toggle switches correctly (see "8.2. Room thermostat
installation configuration" on page 23).
■Wiring of the 2-way valve (8) is different for a NC
(normal closed) valve and a NO (normal open) valve!
Make sure to connect to the correct terminal numbers
as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the
room thermostat and cannot be done by the user interface on the
indoor unit.
Domestic water heating
Domestic water heating is as described under "Application 2" on
page 5.
Application 4
Space heating and cooling application without the room thermostat
connected to the indoor unit, but with the heating only room
thermostat (set heating only) controlling the floor heating and the
heating/cooling thermostat (set heating/cooling) controlling the fan
coil units. Heating is provided through floor heating loops and fan coil
units. Cooling is provided through the fan coil units only.
9
10
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Motorised 3-way valve (delivered with domestic hot water
tank)
8 Motorised 2-way valve (field supply)
9 Collector (field supply)
10 Domestic hot water tank (optional)
11 Booster heater
12 Heat exchanger coil
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T Room thermostat (optional)
(1)
(2)
Pump operation and space heating and cooling
According to the season, the customer will select heating or cooling
on the room thermostat (T). This selection is not possible by
operating the user interface.
When space heating/cooling is requested by the room thermostat
(T), the pump will start operating and the indoor unit (2) will switch to
"heating mode"/"cooling mode". The outdoor unit (1) will start
operating to achieve the target leaving hot/cold water temperature.
In case of cooling mode, the 2-way valve (8) will close as to prevent
cold water running through the floor heating loops (FHL).
(1) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(2) Only applicable for tank with built-in electrical booster heater (EKHW*).
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
10
T4
T5
FCU2
FHL2
T6
FCU3
FHL3
T
7
645321
M
6
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Motorised 2-way valve to shut off the floor heating loops
during cooling operation (field supply)
8 Motorised 2-way valve for activation of the room thermostat
(field supply)
9 Collector (field supply)
10 By-pass valve (field supply)
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T Heating only room thermostat (optional)
T4...6 Individual room thermostat for fan coil heated/cooled room
(optional)
FCU1
8
M
FHL1
Pump operation
With no thermostat connected to the indoor unit (2), the pump (5) can
be configured to operate either as long as the indoor unit is on, or
until the required water temperature is reached.
INFORMATION
Details on pump configuration can be found under
"8.3. Pump operation configuration" on page 24.
Installation manual
6
Space heating and cooling
According to the season, the customer will select heating or cooling
through the user interface on the indoor unit.
The outdoor unit (1) will operate in heating mode or cooling mode to
achieve the target leaving water temperature.
With the unit in heating mode, the 2-way valve (7) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the 2-way valve (7) is closed to prevent
cold water running through the floor heating loops (FHL).
4532
1
67
8
M
8
9
10
NOTICE
■When closing several loops in the system by remotely
controlled valves, it might be required to install a bypass valve (10) to avoid the flow switch safety device
from being activated. See also "Application 2" on
page 5.
■Wiring of the 2-way valve (7) is different for a NC
(normal closed) valve and a NO (normal open) valve!
Make sure to connect to the correct terminal numbers
as detailed on the wiring diagram.
The ON/OFF setting of the heating/cooling operation is done by the
user interface on the indoor unit.
Application 5
Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin indoor unit or by an
auxiliary boiler connected in the system. The decision whether either
the EKHB* indoor unit or the boiler will operate can be achieved by
an auxiliary contact or an EKHB* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat,
an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 7.
The EKHB* indoor unit controlled contact (also called 'permission
signal for the auxiliary boiler') is determined by the outdoor
temperature (thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 8.
Bivalent operation is only possible for space heating operation, not
for the domestic water heating operation. Domestic hot water in such
an application is always provided by the domestic hot water tank
which is connected to the Daikin indoor unit.
The auxiliary boiler must be integrated in the piping work and in the
field wiring according to the illustrations below.
CAUTION
■Be sure that the boiler and the integration of the boiler
in the system is in accordance with the applicable
legislation.
■Daikin can not be put responsible for incorrect or
unsafe situations in the boiler system.
6
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Motorised 3-way valve (delivered with domestic hot water
H Heating demand room thermostat (optional)
K1A Auxiliary relay for activation of EKHB* unit (field supply)
K2A Auxiliary relay for activation of boiler (field supply)
K2A
11
15
K1A
9
13
EKHB*
X2M
123 4
FHL1
K2A
FHL2
B
TI
X
FHL3
Y
12
14
(1)
(2)
Installation manual
7
(1) For tank without electrical booster heater (EKHTS), the backup heater will
be used in domestic water heating mode.
(2) Only applicable for tank with built-in electrical booster heater (EKHW*).
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
Field wiring configuration B
EKHB*
X2M
123 4
K1A
Com
HC
EKRTR*
Com Common room thermostat (optional)
K1A Auxiliary relay for activation of boiler unit (field supply)
KCR Permission signal for the auxiliary boiler
EKHB*
X2M
3 4
12
K1A
Com
H
C
EKRTW*
BTIBoiler thermostat input
C Cooling demand room thermostat (optional)
H Heating demand room thermostat (optional)
EKRP1HB*
KCR
X1 X2
K1A
X
Y
B
TI
Operation
■Configuration A
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the position of
the auxiliary contact (A).
■Configuration B
When the room thermostat requests heating, either the EKHB*
unit or the boiler starts operating, depending on the outdoor
temperature (status of "permission signal for the auxiliary
boiler").
When the permission is given towards the boiler, the space
heating operation by the EKHB* unit will be automatically
switched off.
For more details see field setting [C-02~C-04].
NOTICE
■Configuration A
Make sure that auxiliary contact (A) has sufficient
differential or time delay so as to avoid frequent
changeover between the EKHB* unit and the boiler. If
the auxiliary contact (A) is an outdoor temperature
thermostat, make sure to install the thermostat in the
shade, so that it is not influenced or turned ON/OFF
by the sun.
Configuration B
Make sure that the bivalent hysteresis [C-04] has
sufficient differential to avoid frequent changeover
between the EKHB* unit and the boiler. As the
outdoor temperature is measured via the outdoor unit,
air thermistor make sure to install the outdoor unit in
the shade, so that it is not influenced by the sun.
Frequent switching may cause corrosion of the boiler
in an early stage. Contact the manufacturer of the
boiler.
■During heating operation of the EKHB* unit, the unit
will operate so as to achieve the target leaving water
temperature as set on the user interface. When
weather dependent operation is active, the water
temperature is determined automatically depending
on the outdoor temperature.
During heating operation of the boiler, the boiler will
operate so as to achieve the target leaving water
temperature as set on the boiler controller.
Never set the target leaving water temperature set
point on the boiler controller above 55°C.
■Make sure to only have 1 expansion vessel in the
water circuit. An expansion vessel is already
premounted in the Daikin indoor unit.
NOTICE
Make sure that return water to the EKHB* heat exchanger
never exceeds 55°C.
For this reason, never put the target leaving water
temperature set point on the boiler controller above 55°C
and install an aquastat
(a)
valve in the return water flow of
the EKHB* unit.
Make sure that the non-return valves (field supply) are
correctly installed in the system.
Make sure that the room thermostat EKRTR or EKRTW
are not frequently turned ON/OFF.
Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the
temperature drops to a lower level, the aquastat valve must operate to open the
return water flow to the EKHB* unit again.
INFORMATION
Manual permission towards the EKHB* unit on the boiler.
In case only the EKHB* unit should operate in space
heating mode, disable the bivalent operation via setting
[C-02].
In case only the boiler should operate in space heating
mode, increase the bivalent ON temperature [C-03] to
25°C.
Domestic water heating
Domestic water heating is as described under "Application 2" on
page 5.
NOTICE
Make sure to configure the DIP switch SS2-3 on the PCB
of the EKHB* switch box correctly. Refer to "8.2. Room
thermostat installation configuration" on page 23.
For configuration B: Make sure to configure the field
settings [C-02, C-03 and C-04] correctly. Refer to "Bivalent
operation" on page 35.
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
8
Application 6
Space heating with room thermostat application through floor heating
loops and fan coil units. The floor heating loops and fan coil units
require different operating water temperatures.
The floor heating loops require a lower water temperature in heating
mode compared to fan coil units. To achive these two set points, a
mixing station is used to adapt the water temperature according to
requirements of the floor heating loops. The fan coil units are directly
connected to the indoor unit water circuit and the floor heating loops
after the mixing station. The control of this mixing station is not done
by the indoor unit.
The operation and configuration of the field water circuit is the
responsibility of the installer.
Daikin only offers a dual set point control function. By this function
two set points can be generated. Depending on the required water
temperature (floor heating loops and/or fan coil units are required)
first set point or second set point can be activated.
B
7
T1
A
FCU1
8
FCU2
FCU3
T2
645321
Pump operation and space heating
When the room thermostat for the floor heating loop (T1) and the fan
coil units (T2) are connected to the indoor unit, the pump (5) will
operate when there is a request for heating from T1 and/or T2. The
outdoor unit will start operating to achieve the target leaving water
temperature. The target leaving water temperature depends on which
room thermostat is requesting heating.
Set pointField settingThermo status
Zone AFirstUIONOFFONOFF
Zone BSecond[7-03]OFFONONOFF
Resulting water temperatureUI[7-03][7-03]—
Result pump operationONONONOFF
When the room temperature of both zones is above the thermostat
set point, the outdoor unit and pump will stop operating.
NOTICE
■Make sure to connect the thermostat wires to the
correct terminals (see "5. Overview of the indoor unit"
on page 10).
■Make sure to configure the field settings [7-02], [7-03]
and [7-04] correctly. Refer to "Dual set point control"
on page 33.
■Make sure to configure the DIP switch SS2-3 on the
PCB of the EKHBH switch box correctly. Refer to
"8.2. Room thermostat installation configuration" on
page 23.
■It is the installers responsibility to make sure no
unwanted situations can occur (e.g. too high water
temperatures towards floor heating loops, etc.)
■Be aware that the actual water temperature through
the floor heating loops depends on the control and
setting of the mixing station.
6
9
1 Outdoor unit
2 Indoor unit
3 Heat exchanger
4 Backup heater
5 Pump
6 Shut-off valve
7 Collector zone B (field supply)
8 Collector zone A (field supply)
9 Mixing station (field supply)
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
T1 Room thermostat for zone A (optional)
T2 Room thermostat for zone B (optional)
FHL1
FHL2
FHL3
INFORMATION
■The advantage of the dual set point control is that the
heat pump will/can operate at the lowest required
leaving water temperature when only floor heating is
required. Higher leaving water temperatures are only
required in case fan coil units are operating.
This results in a better performance of the heat pump.
■The hydraulic balance is very important. (Hydrobox mixing station - FCU1...3)
INFORMATION
■The request signals for space heating can be
implemented in two different ways (installer choice).
- Thermo ON/OFF signal from room thermostat
- Status signal (active/not active) from the mixing
station
■Daikin does not offer any type of mixing station. Dual
set point control only provides the possibility to use
two set points.
■When only zone A request heating, zone B will be fed
with water at a temperature equal to the first set point.
This can lead to unwanted heating of zone B.
■When only zone B request heating, the mixing station
will be fed with water at a temperature equal to the
second set point.
Depending on the control of the mixing station, the
floor heating loop can still receive water at a
temperature equal to set point of the mixing station.
■At this type of application heating/cooling selection
always has to be done on the user interface. Refer to
"Dual set point control" on page 33 for more details.
■The front flap on the indoor unit cover gives access to the
manometer and user interface.
■The indoor unit cover can be removed by removing the 2 bottom
screws and unhitching the cover.
INFORMATION
Make sure to fix the cover with the screws when installing
the cover (screws are delivered as accessory).
11
5.2. Main components
20
19
18
33
3
3
2
1
1
2
■To gain access to the switch box components – e.g. to connect
the field wiring – the switch box service panel can be removed.
Thereto, loosen the front screws and unhitch the switch box
service panel.
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
See "2. General safety precautions" on page 2.
3
4
17
5
6
3
16
14
21
13
10
12
3
7
15
3
8
9
13
10
11
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
10
1.Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2.Backup heater
The backup heater consists of an electrical heating element in
the backup heater vessel that will provide additional heating
capacity to the water circuit if the heating capacity of the outdoor
unit is insufficient due to low outdoor temperatures.
3.Temperature sensors
Four temperature sensors determine the water and refrigerant
temperature at various points in the water circuit.
4.Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
5.Heat exchanger
6.Expansion vessel (10 l)
7.User interface
The user interface allows the installer and user to set up, use
and maintain the unit.
8.Refrigerant liquid connection
9.Refrigerant gas connection
10. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the indoor unit.
11. Water inlet connection
12. Water outlet connection
13. Drain and fill valves
14. Water filter
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the evaporator. The water filter must
be cleaned on a regular base. See "10. Maintenance and
service" on page 45.
15. Manometer
The manometer allows readout of the water pressure in the
water circuit.
16. Flow switch
The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against
damage.
17. Pump
The pump circulates the water in the water circuit.
18. Backup heater thermal protector
The backup heater is equipped with a thermal protector. The
thermal protector is activated when the temperature becomes
too high.
19. Backup heater thermal fuse
The backup heater is equipped with a thermal fuse. The thermal
fuse is blown when the temperature becomes too high (higher
than the backup heater thermal protector temperature).
20. Pressure relief valve
The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some
water.
21. Pressure relief valve hose
The actual outlet of the pressure relief valve. Make sure to
provide a proper drain.
5.3. Switch box main components
15
X9A
12
X13A
11
SS2
10
FU1
9
16
6
6
1.Backup heater contactors K1M, K2M, K5M and K6M.
2.Main PCB
The main PCB (Printed Circuit Board) controls the functioning of
the unit.
3.Booster heater contactor K3M (only for installations with
domestic hot water tank)
4.Booster heater circuit breaker F2B (only for installations with
domestic hot water tank)
The circuit breaker protects the booster heater in the domestic
hot water tank against overload or short circuit.
5.Backup heater circuit breaker F1B, F3B
The circuit breaker protects the backup heater electrical circuit
against overload or short circuit.
6.Te r minal blocks
The terminal blocks allow easy connection of field wiring.
7.Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
8.Te r minal blocks X3M, X4M (only for installations with domestic
hot water tank)
9.PCB fuse FU1
10. DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure
certain installation parameters. See "8.1. DIP switch settings
overview" on page 23.
11. X13A socket
The X13A socket receives the K3M connector (only for
installations with domestic hot water tank).
TR1
K1MK2M
A1P
A4P
X2MX4M
X1M
F2B F3B F1B
K4M
K5M
K3MK6M
X3M
FU2
1
2
3
1
4
5
5
14
13
17
8
8
7
Installation manual
11
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
12. X9A socket
The X9A socket receives the thermistor connector (only for
installations with domestic hot water tank).
13. Pump fuse FU2 (in line fuse)
14. Pump relay K4M
15. Transformer TR1
16. A4P
Digital I/O PCB (only for installations with solar kit or digital I/O
PCB kit).
17. X6YA/X6YB/X6Y
Connectors for connecting to a normal kWh rate power supply.
See also "Connection to a benefit kWh rate power supply" on
page 21.
NOTICE
The electrical wiring diagram can be found on the inside of
the switch box cover.
5.4. Functional diagram
3248
R1T
t >
56 7
R2T
t >
6.INSTALLATIONOFTHEINDOORUNIT
6.1. Selecting an installation location
WARNING
Be sure to provide for adequate measures in order to
prevent that the unit be used as a shelter by small animals.
CAUTION
■Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean and
clear.
■The equipment is not intended for use in a potentially
explosive atmosphere.
■Be sure that sufficient precautions are taken, in
accordance with the applicable legislation, in case of
refrigerant leakage.
■When installing the unit in a small room, take
measures in order to keep the refrigerant
concentration from exceeding allowable safety limits
in the event of a refrigerant leak.
Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
■Where flammable gases may leak, where carbon fibre
9
or ignitable dust is suspended in the air or where
volatile flammables, such as thinner or gasoline, are
handled.
Such gases may cause a fire.
H
O
2
R3T
t >
1 Outdoor unit
2 Indoor unit
3 Expansion vessel
4 Manometer
5 Air purge valve
6 Pressure relief valve
7 Backup heater
8 Pump
9 Flow switch
10 Shut-off valve water outlet with drain valve (field
installation)
11 Shut-off valve water inlet with drain valve (field installation)
12 Filter
13 Heat exchanger
R1T Outlet water heat exchanger thermistor
R2T Outlet water backup heater thermistor
R3T Refrigerant liquid side thermistor
R4T Inlet water thermistor
R4T
t >
12131
The unit is to be wall mounted in an indoor location that meets the
10
following requirements:
■The installation location is frost-free.
■The space around the unit is adequate for servicing. (See
figure 2).
■The space around the unit allows for sufficient air circulation.
■There is a provision for condensate drain (only for EKHBX
models with drain pan kit EKHBDP) and pressure relief valve
blow-off.
■The installation surface is a flat and vertical non-combustible
11
wall, capable of supporting the operation weight of the unit (see
"12. Technical specifications" on page 50).
■All piping lengths and distances have been taken into
consideration.
Requirement Value
Maximum allowable refrigerant piping length between
outdoor unit and indoor unit
Minimum required refrigerant piping length between
outdoor unit and indoor unit
Maximum allowable height difference between
outdoor unit and indoor unit
Maximum allowable distance between the 3-way
valve and the indoor unit (only for installations with
domestic hot water tank).
Maximum allowable distance between the domestic
hot water tank and the indoor unit (only for
installations with domestic hot water tank). The
thermistor cable supplied with the domestic hot water
tank is 12 m in length.
(a) Depending on the connected outdoor unit. Refer to the installation manual
of the outdoor unit.
(b) When <5 m, recharging of the outdoor unit (depending on the connected
outdoor unit) is required. Refer to the installation manual of the outdoor
unit.
75 m / 50 m
3 m
30 m
3 m
10 m
(a)
(b)
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
■During normal operation the hydrobox unit will produce sound
which could be observed as noise. The sound origin can be
water pump operation and/or contactor activation. Therefore it is
advisable to install the hydrobox unit on a firm wall and not in nor
close to a sound sensitive environment (e.g. bedroom).
Installation manual
12
■Do not install the unit in places with high humidity (e.g.
bathroom).
■Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
■Ta ke care that in the event of a water leak, water can not cause
any damage to the installation space and surroundings.
■Do not place any objects or equipment on top of the unit.
■Install the power wire at least 1 meter away from televisions or
radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)
■Do not install the unit in places such as the following:
■ Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or
water to leak.
■ Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.
■ Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.
■ Where the air contains high levels of salt.
■ Where voltage fluctuates a lot, such as that in factories.
■ In vehicles or vessels.
■ Where acidic or alkaline vapour is present.
INFORMATION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.
6.3. Inspecting, handling and unpacking the unit
■The indoor unit is packed in a cardboard box, fixed by straps on
a wooden pallet.
■At delivery, the unit must be checked and any damage must be
reported immediately to the carrier claims agent.
■Check if all indoor unit accessories (see "4. Accessories" on
page 9) are enclosed.
■Bring the unit as close as possible to its final installation position
in its original package in order to prevent damage during
transport.
■The indoor unit weighs approximately 48 kg and should be lifted
by two persons using the two lifting bars provided.
CAUTION
■Do not grasp the switch box or piping to lift the unit!
Tw o lifting bars are provided to lift the unit.
■Safely dispose of packing materials. Packing
materials, such as nails and other metal or wooden
parts, may cause stabs or other injuries.
WARNING
Tear apart and throw away plastic packaging bags so that
children will not play with them. Children playing with
plastic bags face danger of death by suffocation.
6.2. Dimensions and service space
Unit of measurement: mm
Dimensions of the unit, see figure 3.
1 Flexible drain hose
2 Water outlet connection
3 Water inlet connection
4 Refrigerant liquid connection
5 Refrigerant gas connection
FBSP Female British Standard Pipe
MBSP Male British Standard Pipe
Required service space, see figure 2.
Installation manual
13
Indoor unit for air to water heat pump system
EKHBH/X016BB
4PW62572-1A – 01.2011
6.4. Mounting the indoor unit
CAUTION
The weight of the indoor unit is approximately 48 kg. Two
persons are required to mount the unit.
1Put the installation pattern (see packing) on the wall and mark
the fixation positions (2 on top (● T) and 2 at the bottom (● B)).
Make sure that the marks (2 by 2) are completely level and the
dimensions of the marks are corresponding according to
figure 4.
When the unit is not installed level, air might get trapped in the
water circuit resulting in malfunctioning of the unit.
Pay special attention to this when installing an EKHBX model to
prevent overflow of the drain pan.
2Drill 4 holes and install 4 plugs (suitable for M10).
3Put the screws in top plugs and hang the indoor unit on the top
screws.
4Put the screws in bottom plugs and fix the screws firmly.
1
2
3
6.5. Installation of the EKHBDP drain pan kit (only for
EKHBX models)
For heating/cooling models, it is necessary to install the drain pan kit
(see "4. Accessories" on page 9).
During cooling operation, water vapour (humidity) in the air might
condense to liquid and collect on the cold refrigerant and water pipes.
This water is collected in the drain pan, which must be connected to a
drain.
For installation instructions, refer to the instruction sheet delivered
with the drain pan kit.
CAUTION
Make sure to position the pressure relief valve hose end in
the drain pan. Failure to do so might lead to water coming
into contact with electrical parts, resulting in electrical
shocks or short-circuit of the electrical system.
6.6. Refrigerant pipework
For all guidelines, instructions and specifications regarding
refrigerant pipework between the indoor unit and the outdoor unit,
please refer to the outdoor unit installation manual.
The location of the gas pipe and liquid pipe on the indoor unit is
shown under "5.2. Main components" on page 10.
Refrigerant piping
specifications
Gas pipe connection15.9 mm (5/8 inch)15.9 mm (5/8 inch)
Liquid pipe connection9.5 mm (3/8 inch)9.5 mm (3/8 inch)
Indoor unitOutdoor unit
CAUTION
When connecting the refrigerant pipes, always use two
wrenches/spanners for tightening or loosening nuts!
Failure to do so can result in damaged piping connections
and leaks.
6.7. Water pipework
Checking the water circuit
The units are equipped with a water inlet and water outlet for
connection to a water circuit. This circuit must be provided by an
installer and must comply with the applicable legislation.
NOTICE
The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.
1
4
EKHBH/X016BB
Indoor unit for air to water heat pump system
4PW62572-1A – 01.2011
Installation manual
14