9. Operation of the central control and menu structure ............... 10
The original instructions are written in English. All other languages
are translations of the original instructions.
1.Supplied accessories and intended
use
1 Power supply 24 V AC for Microtech III controller
(Siemens)
2 POL687.70 Microtech III central control
(Siemens/McQuay)
3 Connectors for Microtech III controller
4 Sensor holder
5 Sensor for common leaving water
6 Basic installation instructions
Intended use
The central control is used to control following Daikin units in
cascade.
EKHBRD* series
EKHVM* series
HXHD125*
EWAQ16..64
EWYQ16..64
Every unit or group of units is connected through an RTD-W ModBus
gateway (to be bought separately from Daikin) to the central control.
Moreover, the central control can control other components of the
installation as explained in "2. General layout and setup of a system"
on page 2.
Installation and operation manual
1
Central control for hydroboxes
4P341705-1 – 2013.02
EKCC7-W
2.General layout and setup of a system
The central control can control the following in a system:
Leaving water temperature to the secondary circuit (circuit to the
heat emitters)
The setpoint for the leaving water temperature to the secondary
circuit can be set. The central control will change the setpoint of
the units and switch more or less units ON/OFF in order to reach
this setpoint.
Pump of the secondary circuit
Backup heater for room heating
Domestic hot water temperature in a centralized domestic hot
water tank
In case of a system with domestic hot water, the system can be set
up in 2 ways:
1. System with integrated hot water tank(s)
In this case, the units for domestic hot water have their own
tank, 3-way valve and 3-way valve control. The parameters for
heating domestic hot water (setpoint, schedule, etc.) must be set
on the control of the unit itself. Refer to the operation/installation
manual of the unit.
On the central control, you can define whether a unit has
domestic hot water function or not. (This can be defined in the
installer settings. Refer to "Configuration" on page 4.)
If the unit is defined as a unit for domestic hot water, it will
always get the lowest priority to start up during room heating, in
order to reserve it as much as possible for DHW heating. During
room cooling, it will always get the highest priority in order to
recover the heat to the DHW tank.
Refer to Figure 3: System with integrated hot water tanks on
page 9 for a setup example.
1A~B Hydroboxes with integrated tank
3~5 Hydroboxes/inverter chillers
A Domestic hot water tanks (EKHTS200/260)
B Non-return valve (field supply)
C Backup heater (field supply)
D Leaving water temperature to secondary circuit sensor
(supplied with EKCC7-W)
E Secondary circuit pump (field supply)
F Central control (supplied with EKCC7-W)
When the system is set to heating or cooling (on the central
control or by external contact connected to the central control),
the central control will switch on the pump of the secondary
circuit and change the setpoint of the hydroboxes in order to
reach the setpoint for the leaving water temperature to the
secondary circuit. In this example, units 1A and 1B are
controlled together, since they are connected to the same
RTD-W.
If the hydroboxes cannot reach the set temperature to the
secondary circuit and depending on other parameters set on the
central control, the central control will also switch on the backup
heater.
2. System with centralized domestic hot water tank
In this case, a tank sensor in the centralized tank is connected to
the central control. The central control will increase the setpoint
of the units and switch the 3-way valve when the temperature in
the tank becomes too low.
INFORMATION
This means that the units are put in heating mode to
heat the DHW tank. For this reason, this setup is only
applicable to EKHBRD*AC units set to configuration C
(refer to ‘Application guide Altherma Flex for
commercial applications’).
This setup is not advised for EKHVM units, since
heating mode is only possible up to an outdoor
temperature of 25°C.
For EWYQ units, post-heating of domestic hot water
might be required, since the maximum leaving water
temperature of these units is limited to 55°C.
Refer to Figure 2: System with centralized domestic hot water
tank on page 8 for a setup example.
1A~5 Hydroboxes/inverter chillers
A Centralized domestic hot water tank (field supply)
B Domestic hot water sensor (Daikin option: EKCLWS)
C Non-return valve (field supply)
D 3-way valve for DHW (field supply)
E Backup heater with integrated pump (field supply)
F Leaving water temperature to secondary circuit sensor
(supplied with EKCC7-W)
G Secondary circuit pump (field supply)
H Central control (supplied with EKCC7-W)
When the system is set to heating or cooling (on the central
control or by external contact connected to the central control),
the central control will switch on the pump of the secondary
circuit, switch the hydroboxes ON/OFF and change the setpoint
in order to reach the setpoint for the leaving water temperature
to the secondary circuit. In this example, units 1A and 1B are
controlled together, since they are connected to the same
RTD-W.
If the hydroboxes cannot reach the set temperature to the
secondary circuit and depending on other parameters set on the
central control, the central control will also switch on the backup
heater.
When domestic hot water heating is required, the central control
will switch the 3-way valve for DHW and increase the setpoint of
units 1A and 1B until the required domestic hot water
temperature is reached.
3.Installation
3.1.Mounting place
When the central control is ON, the units will be controlled (setpoint
setting, ON/OFF control, etc.) by the central control. This will overrule
the ON/OFF setting on the individual remote controllers. For ON/OFF
control using the remote controllers of the units, the central control
must be set to OFF. In order to allow local control of the units at all
times, the central control must be installed in the vicinity of the
individual remote controllers.
3.2.Wiring the central control
Also refer to Figure 1: Electrical wiring diagram on page 8.
WARNING
All electrical wiring must be installed by a licensed
electrician and must comply with local regulations.
Modbus wiring
The control uses Modbus to communicate with the hydroboxes.
Make sure to wire the RS485 wiring (2-wire twisted pair + shield)
from the central control to the RTD-Ws.
Also make sure to configure the addresses on the RTD-W
correctly (refer to RTD-W manual).
Digital inputs
In order to start the system in heating/cooling by an external
voltage free contact, wire the following digital inputs:
- DI1-M (T10): Heating ON
- DI2-M (T10): Cooling ON
INFORMATION
The central control can also be configured to start
heating/cooling using the central control. In that case,
it is not necessary to wire these contacts.
- X1-M(T8): This voltage free input changes the value of the
outdoor temperature at which the backup heater is allowed to
operate. Also refer to "4.5. Backup heater?" on page 4.
- X2-M(T8): This voltage free input detects alarms of the
backup heater.
EKCC7-W
Central control for hydroboxes
4P341705-1 – 2013.02
Installation and operation manual
2
Analog inputs
4
3
2
1
- AI1-M(T7): Common leaving water sensor. This sensor
measures the leaving water temperature to the secondary
circuit. (Supplied with EKCC7-W).
- AI2-M(T7): Domestic hot water temperature. (Daikin option
EKCLWS). Only if you have a centralized tank and DHW
must be controlled by the central control.
Digital outputs
- C3-DO3(T3): Contact to start the secondary pump. This
contact closes whenever heating or cooling is ON.
- C4-DO4(T3): Contact to energize the 3-way valve for DHW.
This contact closes when DHW heating is requested.
- C5-DO5(T4): Contact to start the backup heater. This contact
closes when backup heater operation is requested.
- C8-DO8(T4): This contact closes when there is an alarm in
the system (e.g. one of the heatpump units is in alarm, faulty
common leaving water sensor, etc.).
- C9-DO9(T5): Heating operation. This contact closes when
the system is in room heating mode.
- C10-D010(T5): Cooling operation. This contact closes when
the system is in room cooling mode.
INFORMATION
Contact rating:
Switching voltage AC 24 V…230 V (–20%, +10%)
Rated current (res./ind.) Max. AC 3 A / 2 A (cos φ0.6)
Switching current at AC 19 V Min. AC 30 mA
Max. external supply line fusing 6.3 A slow wire fuse or
circuit breaker.
WARNING
Do not mix SELV/PELV and line voltage on the same
terminal.
Use external protection for inductive load.
4.Installer settings
Refer to "9. Operation of the central control and menu structure" on
page 10 for basic operation of the central control.
All items in the ‘Installer settings’ menu are explained below in detail.
To make the installer settings available, scroll to ‘Installer password’
in the main menu and enter the installer password (default: ‘6000’)
and then go to the ‘Installer settings’ menu.
4.1.Confirmation of the installer settings
Some settings require a restart of the central control in order to
become effective. This is indicated in the first line of the ‘Installer
settings’ menu. When this line shows ‘Restart now?’, changes were
made in the installer settings that require a restart to become
effective. Enter the line and select to restart the central control.
When the line shows ‘No need to restart’, all changes are already
effective.
4.2.Language
Select the desired language.
4.3.Operating modes?
Define the possible operating modes of the system.
Heating only/Cooling only/Heating and cooling
This will make sure the user can only select the appropriate modes.
Restart the central control after changing these settings in order to
make them effective.
4.4.Centralized DHW tank?
Define if the system has a centralized DHW tank.
Only if the system has a centralized domestic hot water tank and field
supplied 3-way valve, select:
Centralized tank
And enter the desired value for:
DT LWT-SP tank
This value determines the temperature difference between the
setpoint of the leaving water temperature of the unit(s) and the
setpoint of the tank. The higher the value, the faster the tank can
be heated. The lower the value, the more efficiently the tank will
be heated.
DHW differential
Differential for tank heating.
Installation and operation manual
3
1 DHW differential
2 SP tank (set by user)
3 Start tank heating
4 Stop tank heating
Central control for hydroboxes
4P341705-1 – 2013.02
EKCC7-W
4.5.Backup heater?
1
2
345
AB
BC
C
A
1°C
4.6.System layout?
Define here if the system has a backup heater or not. If so, select
‘Backup heating’ and define the backup heater method.
3 methods for the backup heating can be defined:
Method 1: Outd Temp
The backup heater will be allowed to operate, depending on the
outdoor temperature.
- BUH allowed: Below this temperature, BUH is allowed to
operate, but BUH has the lowest priority.
Above this temperature, only heatpump units will run (even if
target leaving water temperature cannot be reached, unless
a heatpump is in alarm, then also BUH will run.)
- BUH only: Below this outdoor temperature, all heatpump
units will be stopped for room heating, and only BUH will
operate for room heating.
1 At increasing outdoor temperature
2 At decreasing outdoor temperature
3 BUH only
4 BUH allowed
5 Outdoor temperature
A BUH-only zone
B BUH allowed
C No BUH allowed
Method 2: Outd. Temp. + ext. contacts
Define the following settings:
- With open contact
BUH allowed: Define the outdoor temperature for ‘BUH
allowed’ with OPEN contact.
BUH only: Define the outdoor temperature for ‘BUH only’ with
OPEN contact.
- With closed contact
BUH allowed: Define the outdoor temperature for ‘BUH
allowed’ with CLOSED contact.
BUH only: Define the outdoor temperature for ‘BUH only’ with
CLOSED contact.
Method 3: Outd. Temp. + time
- Time Zone 1
Define the outdoor temperature for ‘BUH allowed’ and ‘BUH
only’ from Time Zone 1 onwards.
- Time Zone 2
Define the outdoor temperature for ‘BUH allowed’ and ‘BUH
only’ from Time Zone 2 onwards.
- Select time zones
Select for every day of the week the time and zone (Time
Zone 1=Z1/Time Zone 2=Z2)
INFORMATION
General note on schedule settings:
Settings with time 00:00 are neglected.
ON/OFF method
Define here if the system has to be set to off, heating or cooling on
the central control (refer to the ‘User settings’ menu > Set room
mode) or by external contacts.
Configuration
Enter
No of units installed: The number of units installed.
Configure unit type auto
When ‘YES’ is selected, the system will detect and configure the
unit type (cooling only/heating only/reversible) automatically.
INFORMATION
The central control will show the maximum number of
units that can be controlled. Only the unit numbers
entered above have to be configured. After restarting
the central control, the list of units will be restricted to
the number of units installed.
Unit configuration:
For every unit, enter the following items (the number in the ‘Unit’
column corresponds to the address on the RTD-W).
• Group (GRP)
Enter which group the indoor unit belongs to. Units belonging
to the same group are usually connected to the same
outdoor unit, because the program will start up units
belonging to the same group first, before starting up units
belonging to another group. This is done in order to avoid
several outdoor units running at the same time at low load.
•Type (TYP)
It is recommended to configure the unit type automatically
(see above). However, the type can be changed manually if
desired. In this case, enter if the unit has cooling only,
heating only or cooling and heating function.
• Domestic hot water (DHW)
What happens when you enter yes (Y) depends on whether
the domestic hot water is controlled by the central control or
not. (Refer to "2. General layout and setup of a system" on
page 2).
If the domestic hot water function is controlled by the unit(s)
itself (integrated tank) and DHW=Y for this unit, then this unit
will always get the lowest priority to start up in heating mode,
in order to preserve it for domestic hot water heating. In
cooling mode, it will get the highest priority in order to be able
to do heat recovery. Domestic hot water heating itself will be
done as configured on the remote controller of the unit.
If the domestic hot water function is controlled by the central
control (refer to Installer settings – Centralized DHW tank?),
the units for domestic hot water must be configured to
DHW=Y. When domestic hot water heating is requested, the
central control will increase the setpoint for those units only.
EKCC7-W
Central control for hydroboxes
4P341705-1 – 2013.02
Installation and operation manual
4
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.