• Daikin Altherma low temperature split • EHBX-C
1
2
• Heating • Daikin Altherma low temperature split
4
2 Specifications
Notes
(1) With option kit *KHBDP installed: Height = XXX mm
(2) DB/WB 7ºC/6ºC - LWC 35ºC (DT=5ºC)
(3) The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and acoustic environment.
(4) The sound pressure level mentioned is maximum possible value inside operation range of unit
(5) 15ºC-25ºC: BUH only, no heat pump operation = during commisioning
(6) Including piping + PHE + back-up heater; excluding expansion vessel
(7) Value mentioned is connection after ball valves, Connection at unit is G1-1/4 FEMALE
(8) See separate drawing for operation range
(9) \> 50ºC BSH only, no heatpump operation
(10) BUH 3V/9W can only operate at flow \> 12/15 l/min
(11) Refer to operation range for detail for differences between *RHQ* and *RLQ* models
(12) PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
2-2 Electrical Specifications EHBX04C3V EHBX08C3V EHBX08C9W EHBX16C3V EHBX16C9W
Power supply Voltage range Min. % 10
Max. % 10
Wiring connectionsCommunication cable
Quantity 3
Remark 2.5 mm²
Wiring connectionsElectric meter
Quantity 2
Wiring connectionsPreferential kWh rate
power supply
Quantity Power: 2
Wiring connectionsDomestic hot water
pump
Quantity 2
Remark Minimum 0.75 mm² (2A inrush, 1A continuous)
Wiring connectionsFor power supply
connection to optional
*KHW*
Quantity 3G
Remark 13A (Select diameter and type according to national and local regulations)
Wiring connectionsFor connection to
optional *KHW* model
+ Q2L
Quantity 5G
Remark Select diameter and type according to national and local regulations / For more details of the voltage
range and current, refer to installation manual
Wiring connectionsFor connection with
R5T
Quantity Wire included in option *KHW*
Remark Wire included in option *KHW*
Wiring connectionsFor connection with
R6T
Quantity 2
Remark Minimum 0.75 mm²
Wiring connectionsFor connection with
A3P
Remark Select diameter & type according to national & local regulations / Voltage: 230V / Max.current: 100mA
/ Min. 0.75mm²
Wiring connectionsFor connection with
M2S
Quantity 2
Remark Voltage: 230V / Max.current: 100mA / Min. 0.75mm² / Select diameter & type according to national &
local regulations
Wiring connectionsFor connection with
M3S
Quantity 3
Remark Select diameter & type according to national & local regulations / Voltage: 230V / Max.current: 100mA
/ Min. 0.75mm²
Wiring connectionsFor connection with
bottom plate heater
Quantity 2
Remark Select diameter and type according to national and local regulations
Wiring connectionsFor connection with
user interface
Quantity 2
Remark 0,75 mm² till 1,25 mm² (max length 500m)
Wiring connectionsFor connection with
optional FWXV*
(demand input and
output)
Quantity 4
Remark 100 mA, minimum 0.75 mm²
Notes PED unit category: Art3§3: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC