Thank you for purchasing this product.
The original instructions are written in English. All other languages
are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE
INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL
AND HOW TO CONFIGURE THE UNIT PROPERLY.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE
REFERENCE.
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Installation manual
1
1. DEFINITIONS
1.1. Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and
probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also
be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or
property-damage accidents only.
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Electric current.
Danger of burning and scalding.
1.2. Meaning of used terms
Installation manual:
Instruction manual specified for a certain product or application,
explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application,
explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application,
which explains (if relevant) how to install, configure, operate and/or
maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the
subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required
service to the unit.
Applicable legislation:
All international, European, national and local directives, laws,
regulations and/or codes which are relevant and applicable for a
certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be
installed according to instructions in the documentation.
Optional equipment:
Equipment which can optionally be combined to the products as per
the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in
this manual, but which are not supplied by Daikin.
2.GENERAL SAFETYPRECAUTIONS
All activities described in this manual shall be carried out by an
installer.
Be sure to wear adequate personal protection equipment (protection
gloves, safety glasses, …) when performing installation, maintenance
or service to the unit.
If not sure of installation procedures or operation of the unit, always
contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories
could result in electric shock, short-circuit, leaks, fire or other damage
to the equipment. Be sure only to use accessories and optional
equipment made by Daikin which are specially designed for use with
the products as of subject in this manual and have them installed by
an installer.
The precautions listed here are divided into the following four types.
They all cover very important topics, so be sure to follow them
carefully.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switchbox
service panel or before making any connections or
touching electrical parts.
Do not touch any switch with wet fingers. Touching a switch
with wet fingers can cause electrical shock. Before
touching electrical parts, turn off all applicable power
supply.
To avoid electric shock, be sure to disconnect the power
supply 1 minute or more before servicing the electrical
parts. Even after 1 minute, always measure the voltage at
the terminals of main circuit capacitors or electrical parts
and, before touching, be sure that those voltages are
50 V DC or less.
When service panels are removed, live parts can easily be
touched by accident. Never leave the unit unattended
during installation or servicing when the service panel is
removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
Do not touch the refrigerant piping, water piping or internal
parts during and immediately after operation. The piping
and internal parts may be hot or cold depending on the
working condition of the unit.
Your hand may suffer burns or frostbite if you touch the
piping or internal parts. To avoid injury, give the piping and
internal parts time to return to normal temperature or, if
you must touch them, be sure to wear protective gloves.
WARNING
■ Tear apart and throw away plastic packaging bags so
that children will not play with them.
Children playing with plastic bags face danger of death
by suffocation.
■ Safely dispose of packing materials. Packing materials,
such as nails and other metal or wooden parts, may
cause stabs or other injuries.
Installation manual
2
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
■ Ask your dealer or qualified personnel to carry out
installation work.
Do not install the machine by yourself.
Improper installation may result in water leakage, electric
shocks or fire.
■ Perform installation work in accordance with this
installation manual.
Improper installation may lead to water leakage, electric
shocks or fire.
■ Be sure to use only the specified accessories and parts
for installation work.
Failure to use the specified parts may result in water
leakage, electric shocks, fire, or the unit falling.
■ Install the unit on a foundation that can withstand its
weight.
■ Insufficient strength may result in the fall of equipment
and causing injury.
■ Carry out the specified installation work in consideration
of strong winds, hurricanes, or earthquakes.
Improper installation work may result in accidents due to
fall of equipment.
■ Make certain that all electrical work is carried out by
qualified personnel according to the local laws and
regulations and this installation manual, using a separate
circuit.
Insufficient capacity of the power supply circuit or
improper electrical construction may lead to electric
shocks or fire.
■ Be sure to install an earth leakage circuit breaker in
accordance with relevant local and national regulations.
Failure to do so may cause electrical shock and fire.
■ Make sure that all wiring is secure, using the specified
wires and ensuring that external forces do not act on the
terminal connections or wires.
Incomplete connection or fixing may cause a fire.
■ When wiring between the indoor and the outdoor units
and wiring the power supply, form the wires so that the
panels can be securely fastened.
If the panels are not in place, overheat of the terminals,
electric shocks or a fire may be caused.
■ After completing the installation work, check to make
sure that there is no leakage of refrigerant gas.
■ Never directly touch any accidental leaking refrigerant.
This could result in severe wounds caused by frostbite.
■ Electrical work must be carried out in accordance with
the installation manual and the national electrical wiring
rules or code of practice.
Insufficient capacity or incomplete electrical work may
cause electrical shock or fire.
■ Be sure to use a dedicated power circuit. Never use a
power circuit shared by another appliance.
■ For wiring, use a cable long enough to cover the entire
distance with no connection. Do not use an extension
cord. Do not put other loads on the power supply, use a
dedicated power circuit.
Failure to do so may cause abnormal heat, electric
shock, or fire.
■ Do not touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes may
be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor and other refrigerant cycle parts. Your hands
may suffer burns or frostbite if you touch the refrigerant
pipes. To avoid injury, give the pipes time to return to
normal temperature or, if you must touch them, be sure
to wear proper gloves.
CAUTION
■For use of units in applications with temperature
alarm settings it is advised to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for
several minutes during normal operation for
"defrosting of the unit" or when in "thermostat-stop"
operation.
■ Earth the unit.
Earth resistance should be according to local laws and
regulations.
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire.
Incomplete earthing may cause electric shocks.
-Gas pipe.
Ignition or explosion may occur if the gas leaks.
-Water pipe.
Hard vinyl tubes are not effective earths.
-Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a
lightning bolt.
■ Install the indoor and outdoor units, power wire and
connecting wire at least 1 meter away from televisions or
radios to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter
may not be sufficient to eliminate the noise.)
■ Do not rinse the unit. This may cause electric shocks or
fire.
■ Do not install the unit in places such as the following:
-Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall
out or water to leak.
-Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.
-Where there is machinery which emits
electromagnetic waves.
Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.
-Where flammable gases may leak, where carbon
fibre or ignitable dust is suspended in the air or
where volatile flammables, such as thinner or
gasoline, are handled. Such gases may cause a fire.
-Where the air contains high levels of salt such as that
near the ocean.
-Where voltage fluctuates a lot, such as that in
factories.
-In vehicles or vessels.
-Where acidic or alkaline vapour is present.
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Installation manual
3
3.INTRODUCTION
3.1. General information
This installation manual concerns Monoblock units of the GBS
Altherma series.
The Monoblock units exist out of an outdoor installed unit (EBHQ)
and an indoor installed (wall mounted) unit (EKCB).
These units are used for both heating and cooling applications. The
units can be combined with Daikin fan coil units, floor heating
applications, low temperature radiators, domestic hot water tank
(option) and solar kit (option).
A user interface is standard supplied with the unit to control your
installation.
Heating/cooling units and heating only units
The monoblock unit range consists of two main versions: a
heating/cooling version (uses EKCBX indoor unit) and a heating only
version (uses EKCBH indoor unit), both available in 2 capacity sizes:
6 kW (EBHQ006) or 8 kW (EBHQ008).
Both versions (heating only and heating/cooling) are standard
delivered with a backup heater kit (EKMBUH) for additional heating
capacity during cold outdoor temperatures. The backup heater also
serves as a backup in case of malfunctioning of the unit and for
freeze protection of the outside water piping during winter time. The
backup heater factory set capacity is 6 kW, however, depending on
the installation, the installer can limit the backup heater capacity to
3 kW. The backup heater capacity decision is a mode based on the
equilibrium temperature, see scheme below.
P
H
3
EKCBX008BAV3EKCBH008BAV3
1
2
■Domestic hot water tank (option)
An optional EKHW* domestic hot water tank with integrated
3 kW electrical booster heater can be connected to the indoor
unit. The domestic hot water tank is available in three sizes: 150,
200 and 300 litre. Refer to the domestic hot water tank
installation manual for further details.
■Solar kit for domestic hot water tank (option)
For information concerning the EKSOLHW solar kit, refer to the
installation manual of that kit.
■Digital I/O PCB kit (option)
An optional EKRP1HB digital I/O PCB can be connected to the
indoor unit and allows:
■ remote alarm output
■ heating/cooling ON/OFF output
■ bivalent operation (permission signal for the auxiliary boiler)
Refer to the operation manual and to the installation manual of
the digital I/O PCB for more information.
Refer to the wiring diagram or connection diagram for
connecting this PCB to the unit.
■Bottom plate heater EKBPHT08BA (option)
■Remote thermostat kit (option)
An optional room thermostat EKRTWA, EKRTR or EKRTETS
can be connected to the indoor unit. Refer to the installation
manual of the room thermostat for more information.
To obtain more information concerning these option kits, please
refer to dedicated installation manuals of the kits.
Connection to a benefit kWh rate power supply
NOTICE
This equipment allows for connection to benefit kWh rate
power supply delivery systems. Full control of the unit will
remain possible only in case the benefit kWh rate power
supply is of the type that power supply is not interrupted.
Refer to "[D] Benefit kWh rate power supply/Local shift
value weather dependent" on page 38 for more details.
3.3. Scope of the manual
This manual describes the procedures for handling, installing and
connecting the EBHQ and EKCB units. This manual has been
prepared to ensure adequate maintenance of the unit, and it will
provide help if problems occur.
3.4. Model identification
Outdoor unit
EBHQ008BAV3
4
1Heat pump capacity
2Required heating capacity (site dependent)
3Additional heating capacity provided by the backup heater
4Equilibrium temperature (can be set through the user interface.
refer to "Equilibrium temperature and space heating priority
temperature" on page 33
Ambient (outdoor) temperature
T
A
P
Heating capacity
H
T
A
NOTICE
The EKCB* and EBHQ*006/008 units can not be operated
without the EKMBUH heater kit.
Installation manual
4
Voltage: 1P, 230 V
Series
Indication of heating/cooling capacity (kW)
Refrigerant R410a
Low water temperature, ambient zone 3
Monoblock oudoor heat pump
(a) For exact values, refer to "Technical specifications" on page 47.
Indoor unit
EKCBX008BAV3
Voltage: 1P, 230 V
Series
Can be combined with 6 or 8 kW outdoor unit
X = heating and cooling,
H = heating only
Control box
European kit
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
(a)
4PW64602-1 – 08.2010
4.ACCESSORIES
5.OVERVIEWOFUNIT
4.1. Location of the accessories
4.2. Accessories supplied with the outdoor unit
123546
5.1. Opening of the outdoor and indoor unit
■Opening of the outdoor unit
To gain access to the unit, the service panels need to be opened
as shown in the figure below
6x
1
2
1Installation manual
2Operation manual
3Shut-off valve (2x)
4Wiring diagram sticker (inside top unit cover)
5Cable Ties (15x)
6Thermistor connection cable
4.3. Accessories supplied with the indoor unit
12 43
1user interface kit
(user interface, 4 fixing screws and 2 plugs)
2Accessory bag
(2 mounting bolts and 2 nuts for user interface)
3Wiring diagram sticker (inside unit cover)
4Booster heater extension cable
4x
3
5x
For access to the terminals, following panels have to be
removed as shown in the figure below
1
6x
2
2x
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Installation manual
5
■Opening of the indoor unit
To gain access to the unit, the front cover needs to be opened as
shown in the figure below
5.2. Main components of the outdoor unit and the
indoor unit
Outdoor unit watersystem
1x
WARNING
■Switch off all power supply – i.e. outdoor unit power
supply and backup heater and domestic hot water
tank power supply (if applicable) – before removing
the switch box service panel (outdoor unit and indoor
unit).
■Do not touch the refrigerant pipes during and
immediately after operation as the refrigerant pipes
may be hot or cold, depending on the condition of the
refrigerant flowing through the refrigerant piping,
compressor, and other refrigerant cycle parts. Your
hands may suffer burns or frostbite if you touch the
refrigerant pipes. To avoid injury, give the pipes time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
■Do not touch the internal parts (pump, backup heater,
etc.) during and immediately after operation.
Your hands may suffer burns if you touch the internal
parts. To avoid injury, give the internal parts time to
return to normal temperature or, if you must touch
them, be sure to wear proper gloves.
DANGER
■Do not touch water pipes during and immediately after
operation as the pipes may be hot. Your hand may
suffer burns. To avoid injury, give the piping time to
return to normal temperature or be sure to wear
proper gloves.
■When service panels are removed, live parts can be
easily touched by accident.
Never leave the unit unattended during installation or
servicing when the service panel is removed.
DANGER: ELECTRICAL SHOCK
See "2. General Safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
See "2. General Safety precautions" on page 2.
1
2
6
12a
5
11
1.Switchbox
The switchbox contains connection terminals for the power
supply and a connection point for the thermistor interconnection
cable.
2.Heat exchanger
3.Water inlet connection (1" MBSP)
4.Water outlet connection (1" MBSP)
5.Pump
The pump circulates the water in the water circuit.
6.Manometer
The manometer allows readout of the water pressure in the
system.
7.Expansion vessel (6 litre)
The water in the water circuit expands with rising temperatures.
The expansion vessel stabilises the pressure changes with
changing water temperatures by giving free space to the
changing water volume.
8.Expansion vessel service point
The service point allows connection of a dry nitrogen cylinder to
adjust the expansion vessel pre-pressure if necessary.
9.Drain and fill valve (2x)
10. Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
11. Water filter
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the heat exchanger. The water filter
should be cleaned on a regular base. See "16. Maintenance and
service" on page 43.
12. Temperature sensors (thermistors)
Tw o temperature sensors determine the water inlet temperature
(12a) and water outlet temperature (12b). A third thermistor
(12c) measures the refrigerant temperature.
13. Power supply intake
14. Thermistor interconnection cable intake
15. Shut-off valves (accessory)
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the outdoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter replacement of the outdoor unit.
16. Flow switch
The flow switch checks the flow in the water circuit and protects
the heat exchanger against freezing and the pump against
damage. In case the minimum required flow is not achieved, the
unit will be shut down.
17. Pressure relief valve
The pressure relief valve prevents excessive water pressure in
the water circuit (≥3 bar).
10
12b
12b12c
17
7
8
16
3994
1415
13
Installation manual
6
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Indoor unit
Indoor unit switch box
12
12
3
3
1Indoor unit
2User interface mounted on the indoor front panel
3Field wiring intake
1.The user interface must be mounted on the EKCB front panel
and allows the installer and user to set up, use and maintain the
unit.
2.Field wiring intake is foreseen to allow mounting and connecting
the field wiring to the terminals inside the EKCB.
5.3. Main components of the outdoor unit switch box
and indoor unit switch box
Outdoor unit switch box
2
1
1
1Ter minal blocks
The terminal blocks allow easy connection of field
wiring.
2Thermistor interconnection cable connector
The electric wiring diagram can be found on the inside of
the outdoor unit top panel.
411413910 11
A4P
F1B
5
7
7
K3M
X3M
X4M
FU1
8
2
TR1
SS2
X9A
X13A
FU2
X15M
X2MX14M
66 26612626
1.Main PCB
The main PCB (Printed Circuit Board) controls the functioning of
the unit.
2.Te r minal blocks X2M, X14M, X15M
The terminal blocks allow easy connection of field wiring.
3.Thermistor interconnection cable connector
4.Booster heater contactor K3M (only for installations with a
domestic hot water tank installed)
5.Booster heater circuit breaker F1B (only for installations with a
domestic hot water tank installed)
The circuit breaker protects the booster heater in the domestic
hot water tank against overload or short circuit.
6.Cable tie mountings
The cable tie mountings allow to fix the field wiring with cable
ties to the switch box to ensure strain relief.
7.Te r minal blocks X3M, X4M (only for installations with a domestic
hot water tank installed)
8.PCB fuse FU1
9.DIP switch SS2
The DIP switch SS2 provides 4 toggle switches to configure
certain installation parameters. See "13.1. DIP switch settings
overview" on page 28.
10. X13A socket
The X13A socket receives the K3M connector (only for
installations with a domestic hot water tank installed).
11. X9A socket
The X9A socket receives the thermistor connector (only for
installations with a domestic hot water tank installed).
12. Fuse FU2 (in line fuse)
13. Transformer TR1
14. A4P
Digital I/O PCB (only for installations with a solar kit or a digital
I/O PCB kit installed).
The electric wiring diagram can be found on the inside of
the indoor unit front panel
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Installation manual
7
5.4. Functional diagram of outdoor hydraulic
compartment
6.SELECTINGANINSTALLATIONLOCATION
12345
R12T
t >
6
1Outdoor unit EBHQ*BAV3
2Backup heater EKMBUH*6V3
3Heat exchanger
4Heat exchanger refrigerant side
5Water outlet
6Water inlet
7Refrigerant outlet
8Refrigerant intlet
R11TWater outlet temperature sensor
R12TBackup heater temperature sensor
R13TRefrigerant temperature thermistor
R14TWater inlet temperature sensor
Waterflow direction
Refrigerant flow direction in cooling mode
Refrigerant flow direction in heating mode
1213
1117
14 15
16
R11T
7
9101011
8
WARNING
Be sure to provide for adequate measures in order to
prevent that the EBHQ outdoor unit be used as a shelter by
small animals.
Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
t >
R14T
R13T
t >t >
customer to keep the area around the EBHQ outdoor unit
clean and clear.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
7
8
This unit, both indoor and outdoor, is suitable for
installation in a commercial and light industrial
environment.
General precautions on outdoor installation location
Select an installation site that meets the following requirements and
that meets with your customer's approval.
■The unit is designed to be installed in an outdoor location.
■The space around the unit is adequate for maintenance and
servicing (refer to "7.3. Service space" on page 10).
■The space around the unit allows for sufficient air circulation.
There must be sufficient space for air passage and no
obstructions around the air intake and the air exhaust (see
"Installing near a wall or obstacle" on page 9).
■There must be sufficient space for carrying the unit into and out
of the site.
■There is no danger of fire due to leakage of inflammable gas.
The site must be free from the possibility of flammable gas
leakage in a nearby place.
■The equipment is not intended for use in a potentially explosive
atmosphere.
■Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.
■All piping lengths and distances have been taken into
consideration.
Requirement Value
Maximum allowable distance between the
domestic hot water tank and the outdoor unit
(only for installations with a domestic hot
water tank installed). The thermistor cable
supplied with the domestic hot water tank is
12 m in length (to be connected to the
indoor unit EKCB).
Maximum allowable distance between the
3-way valve and the outdoor unit (only for
installations with a domestic hot water tank
installed)
10 m
10 m
(try to keep as close to
the outdoor unit as
possible)
Installation manual
8
■Since drain flows out of the unit, do not place anything under the
unit which must be kept away from moisture.
■Ta ke care that in the event of a water leak, water cannot cause
any damage to the installation space and surroundings (e.g. in
case of a blocked drain pipe).
■Install the unit and power cords at least 3 m away from television
and radio sets. This is to prevent interference to images and
sounds.
Depending on radio wave conditions, electromagnetic
interference may still occur even if installed more than 3 m away.
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
■Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone, and the location
is selected according the applicable legislation.
Although the noise produced by the unit during operation is low,
avoid installation near to places where even low noise levels can
be disturbing (e.g., bedroom windows, terraces, next-door
neighbours).
■Do not install the unit in places often used as workplace.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
■Be sure that sufficient precautions are taken, in accordance with
relevant local laws and regulations, in case of refrigerant
leakage.
Wheater dependent precautions
■Select a place where the rain can be avoided as much as
possible.
■In heavy snowfall areas, it is very important to select an
installation site where the snow will not affect the unit. If lateral
snowfall is possible, Be sure that the heat exchanger coil is not
affected by the snow (if necessary construct a lateral canopy).
■Ensure that water cannot cause any damage to the location by
adding water drains to the foundation and prevent water traps in
the construction.
■Do not install the unit in areas where the air contains high levels
of salt such as that near the ocean, corrosion may shorten the
life of the unit.
■Prevent direct exposure to winds coming from the sea.
■Be sure that the air inlet and outlet of the unit are not positioned
towards the main wind direction. frontal wind will disturb the
operation of the unit. If necessary, use a screen to block the wind.
■When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the unit's air
outlet cause short circuit (suction of discharge air), and this may
have the following consequences:
- deterioration of the operational capacity,
- frequent frost acceleration in heating operation,
- disruption of operation due to rise of high pressure,
- when a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
-Turn the air outlet side toward the building's wall, fence or
screen.
Selecting an outdoor location in cold climates
NOTICE
When operating the unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.
■To prevent exposure to wind, install the unit with its suction side
facing the wall.
■Never install the unit at a site where the suction side may be
exposed directly to wind.
■To prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.
■When installing the unit in a place frequently exposed to snow,
pay special attention to the following:
- Elevate the foundation as high as possible.
- Select an installation site where the snow will not affect the
unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is not affected by the snow (if necessary
construct a lateral canopy).
Construct a large canopy.
Construct a pedestal.
Install the unit high enough off the ground
to prevent burying in snow.
Place of installation
■Prepare a water drainage channel around the outdoor unit, to
drain waste water from around the unit.
■If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).
■If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.
■If you install the unit on a building frame,
please install a waterproof plate (field
supply)(within 150 mm of the underside of
the unit) in order to avoid the drainwater
dripping. (See figure).
Make sure there is enough room to do the installation
■ Set the outlet side at a right angle to the direction of the wind.
Strong wind
Blown air
Strong wind
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
NOTICE
Units cannot be installed hanging from the ceiling or
stacked.
■Installing near a wall or obstacle
- Where a wall or other obstacle is in the path of the unit’s air
intake or exhaust airflow, the distances as indicated on the
figures below need to be respected.
- The wall height on the exhaust side should be 1200 mm or
less.
■Do not sit or stand on top of the unit.
■Do not place any objects or equipment on top of the unit.
Installation manual
9
General precautions on indoor installation location
The EKCB unit is to be wall mounted in an indoor location that meets
the following requirements:
■The space around the unit is adequate for servicing. Refer to
"7.3. Service space" on page 10.
■The space around the unit allows for sufficient air circulation.
■The installation surface is a flat and vertical non-combustible
wall, capable of supporting the operation weight of the unit (refer
to the "Technical specifications" on page 47).
■During normal operation the control box may produce sound
which could be observed as noise. The sound origin can be
contactor activation. Therefore it is advisable to install the
control box on a firm wall and not in nor close to a sound
sensitive environment (e.g. bedroom).
■Do not install the unit in places with high humidity (e.g.
bathroom).
■The equipment is not intended for use in a potentially explosive
atmosphere.
■Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of
dust is created, the unit must be covered.
■Do not place any objects or equipment on top of the unit.
CAUTION
If the installation is equipped with a domestic hot water
tank (optional), please refer to the domestic hot water tank
installation manual.
7.DIMENSIONSANDSERVICESPACE
7.1. Dimensions of outdoor unit
7.3. Service space
The space around the unit is adequate for servicing and the minimum
space for air inlet and air outlet is available. (Refer to the figure
below).
>150>50
>350>150
Unit of measurement: mm
NOTICE
The wall height on the air outlet side (marked with grey
arrow in the figure above) must be less than 1200 mm.
The installation space required on this drawing is for full load heating
operation without considering possible ice accumulation.
If the location of the installation is in a cold climate, then all
dimensions above should be >500 mm to avoid accumulation of ice
in between the outdoor unit and the nearest walls.
■The connection piping outlet direction in the installation shown in
the figure is frontward or downward.
■When routing the piping backward, secure space of ≥250 mm on
the right side of the unit.
(>300)
*
360
22
122
10784
20
Unit of measurement: mm
7.2. Dimensions of indoor unit
390
412
100
1189
1170
806
NOTICE
(*) If shut off valves are directly installed on the water inlet
and outlet, increase installation space at the rear of the
unit to a minimum of 300 mm.
7.4. Service space of indoor unit
50
50
10050
600
Unit of measurement: mm
Unit of measurement: mm
Installation manual
10
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
8.TYPICALAPPLICATIONEXAMPLES
The application examples given below are for illustration purposes
only.
8.1. Application 1
8.2. Application 2
Space heating only application without room thermostat connected to
the unit. The temperature in each room is controlled by a valve on
each water circuit. Domestic hot water is provided through the
domestic hot water tank which is connected to the unit.
Space heating only application with a room thermostat connected to
the unit.
When a room thermostat (T) is connected to the unit and when there
is a heating request from the room thermostat, the unit will start
operating to achieve the target leaving water temperature as set on
the user interface.
When the room temperature is above the thermostat set point, the
unit will stop operating.
CAUTION
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 27) and to configure the DIP switch toggle switches
correctly (see "13.2. Room thermostat installation
configuration" on page 28).
9Booster heater
10Heat exchanger coil
11Domestic hot water tank (optional)
FHL1...3Floor heating loop (field supply)
T1...3Individual room thermostat (field supply)
M1..3Individual motorised valve to control loop FHL1...3
(field supply)
CControl box
IUser interface
7
6
T1
M
M1
109 11
FHL1
T3
M2T2M3
FHL2
8
FHL3
Pump operation
With no thermostat connected to the unit (1), the pump (3) can be
configured to operate either as long as the unit is on, or until the
required water temperature is reached.
Details on pump configuration can be found under
"13.3. Pump operation configuration" on page 29.
Space heating
The unit (1) will operate to achieve the target leaving water
temperature as set on the user interface.
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
CAUTION
When circulation in each space heating loop (FHL1..3) is
controlled by remotely controlled valves (M1..3), it is
important to provide a by-pass valve (7) to avoid the flow
switch safety device from being activated.
The by-pass valve should be selected as such that at all
time the minimum water flow as mentioned under
"10. Piping connection work" on page 18 is guaranteed.
It is recommended to select a pressure difference
controlled by-pass valve.
Installation manual
11
Domestic water heating
When domestic water heating mode is enabled (either manually by
the user, or automatically through a schedule timer) the target
domestic hot water temperature will be achieved by a combination of
the heat exchanger coil and the electrical booster heater.
When the domestic hot water temperature is below the user
configured set point, the 3-way valve will be activated to heat the
domestic water by means of the heat pump. In case of large domestic
hot water demand or a high domestic hot water temperature setting,
the booster heater (9) can provide auxiliary heating.
CAUTION
It is possible to connect either a 2-wire or a 3-wire 3-way
valve (7). Make sure to fit the 3-way valve correctly. For
more details, refer to "Wiring the 3-way valve" on page 28.
The unit can be configured so that at low outdoor
temperatures the domestic water is exclusively heated by
the booster heater. This assures that the full capacity of the
heat pump is available for space heating.
Details on domestic hot water tank configuration for low
outdoor temperatures can be found under "13.9. Field
settings" on page 31, field settings [5-02] to [5-04].
Pump operation and space heating and cooling
According to the season, the customer will select cooling or heating
on the room thermostat (T). This selection is not possible by
operating the user interface.
When space heating/cooling is requested by the room thermostat
(T), the pump will start operating and the unit (1) will switch to
"heating mode"/"cooling mode". The unit (1) will start operating to
achieve the target leaving cold/hot water temperature.
In case of cooling mode, the motorised 2-way valve (12) will close as
to prevent cold water running through the floor heating loops (FHL).
CAUTION
Make sure to connect the thermostat wires to the correct
terminals (see "Connection of the thermostat cable" on
page 27) and to configure the DIP switch toggle switches
correctly (see "13.2. Room thermostat installation
configuration" on page 28).
CAUTION
Wiring of the 2-way valve (12) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
8.3. Application 3
Space cooling and heating application with a room thermostat
suitable for heating/cooling changeover connected to the unit.
Heating is provided through floor heating loops and fan coil units.
Cooling is provided through the fan coil units only.
Domestic hot water is provided through the domestic hot water tank
which is connected to the unit.
6
I
C
T
43251
7
M
12
FCU1
FCU2
6
M
109 11
FHL1
FHL2
FCU3
FHL3
The ON/OFF setting of the heating/cooling operation is done by the
room thermostat and cannot be done by the user interface.
Domestic water heating
Domestic water heating is as described under "8.2. Application 2" on
page 11.
8.4. Application 4
Space cooling and heating application without a room thermostat
connected to the unit, but with a heating only room thermostat
controlling the floor heating and a heating/cooling thermostat controlling
the fan coil units. Heating is provided through floor heating loops and fan
coil units. Cooling is provided through the fan coil units only.
12Motorised 2-way valve to shut off the floor heating loops
during cooling operation (field supply)
13Motorised 2-way valve for activation of the room thermostat
FCU1...3Fan coil unit with thermostat (field supply)
FHL1...3Floor heating loop (field supply)
(field supply)
T4...6Individual room thermostat for fan coil heated/cooled room
(optional)
THeating only room thermostat (optional)
CControl box
IUser interface
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Pump operation
With no thermostat connected to the unit (1), the pump (3) can be
configured to operate either as long as the unit is on, or until the
required water temperature is reached.
Details on pump configuration can be found under
"13.3. Pump operation configuration" on page 29.
Space heating and cooling
According to the season, the customer will select cooling or heating
through the user interface.
The unit (1) will operate in cooling mode or heating mode to achieve
the target leaving water temperature.
With the unit in heating mode, the 2-way valve (12) is open. Hot water
is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the motorised 2-way valve (12) is
closed to prevent cold water running through the floor heating loops
(FHL).
CAUTION
When closing several loops in the system by remotely
controlled valves, it might be required to install a by-pass
valve (8) to avoid the flow switch safety device from being
activated. See also "8.2. Application 2" on page 11.
CAUTION
Wiring of the 2-way valve (12) is different for a NC (normal
closed) valve and a NO (normal open) valve! Make sure to
connect to the correct terminal numbers as detailed on the
wiring diagram.
CAUTION
■Be sure that the boiler and the integration of the boiler
in the system is in accordance with relevant local laws
and regulations.
■Always install a 3-way valve, even if no domestic hot
water tank is installed. This to ensure that the freeze
protection function (see "[4-04] Freeze protection
function" on page 33) can operate when the boiler is
active.
I
C
1
M
2
FHL1 FHL2 FHL3
1Motorised 3-way valve
2Boiler
■Daikin can not be put responsible for incorrect or
unsafe situations in the boiler system.
The ON/OFF setting of the heating/cooling operation is done by the
user interface.
8.5. Application 5
Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin unit or by an auxiliary
boiler connected in the system. The decision whether either the
EBHQ* unit or the boiler will operate can be achieved by an auxiliary
contact or an EKCB* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat,
an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 14.
The EKCB* unit controlled contact (also called 'permission signal for
the auxiliary boiler") is determined by the outdoor temperature
(thermistor located at the outdoor unit). See "Field wiring
configuration B" on page 14.
Bivalent operation is only possible for space heating operation, not
for the domestic water heating operation. Domestic hot water in such
an application is always provided by the domestic hot water tank
which is connected to the Daikin unit.
The auxiliary boiler must be integrated in the piping work and in the
field wiring according to the illustrations below.
9Booster heater
10Heat exchanger coil
11Domestic hot water tank (optional)
14Boiler (field supply)
15Aquastat valve (field supply)
16Shut-off valve (field supply)
17Non-return valve (field supply)
FHL1...3Floor heating loop (field supply)
CControl box
IUser interface
17
616
FHL1
FHL2
FHL3
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Installation manual
13
Field wiring configuration A
L
Com
H
EKCB(H/X)*
EKCB(H/X)*/auto
Boiler
thermostat input
AAuxiliary contact (normal closed)
HHeating demand room thermostat (optional)
K1AAuxiliary relay for activation of EBHQ* unit
K2AAuxiliary relay for activation of boiler (field supply)
/Boiler
N
A
K1A
K2A
Boiler thermostat input
(field supply)
X2M
123 4
K1A
Boiler
thermostat input
X
K2A
Field wiring configuration B
EKCB(H/X)*
X2M
3 4
12
K1A
Com
H
C
EKRTW*
Boiler
thermostat input
CCooling demand room thermostat (optional)
HHeating demand room thermostat (optional)
ComCommon room thermostat (optional)
K1AAuxiliary relay for activation of boiler unit
KCRPermission signal for the auxiliary boiler
EKRP1HB
KCR
X1 X2
K1A
X Y
Boiler
thermostat input
Boiler thermostat input
(field supply)
Operation
■Configuration A
When the room thermostat requests heating, either the EBHQ*
unit or the boiler starts operating, depending on the position of
the auxiliary contact (A).
■Configuration B
When the room thermostat requests heating, either the EBHQ*
unit or the boiler starts operating, depending on the outdoor
temperature (status of "permission signal for the auxiliary
boiler").
When the permission is given towards the boiler, the space
heating operation by the EBHQ* unit will be automatically
switched off.
For more details see field setting [C-02~C-04].
NOTICE
■Configuration A
Make sure that auxiliary contact (A) has sufficient
differential or time delay so as to avoid frequent
Y
changeover between the EBHQ* unit and the boiler. If
the auxiliary contact (A) is an outdoor temperature
thermostat, make sure to install the thermostat in the
shade, so that it is not influenced or turned ON/OFF
by the sun.
Configuration B
Make sure that the bivalent hysteresis [C-04] has
sufficient differential to avoid frequent changeover
between the EBHQ* unit and the boiler. As the outdoor
temperature is measured via the outdoor unit’s air
thermistor, make sure to install the outdoor unit in the
shade, so that it is not influenced by the sun.
Frequent switching may cause corrosion of the boiler
in an early stage. Contact the manufacturer of the
boiler.
■During heating operation of the EBHQ* unit, the unit
will operate so as to achieve the target leaving water
temperature as set on the user interface. When
weather dependent operation is active, the water
temperature is determined automatically depending
on the outdoor temperature.
During heating operation of the boiler, the boiler will
operate so as to achieve the target leaving water
temperature as set on the boiler controller.
Never set the target leaving water temperature set
point on the boiler controller above 55°C.
■Make sure to only have 1 expansion vessel in the
water circuit. An expansion vessel is already
premounted in the unit.
NOTICE
Make sure to configure the DIP switch SS2-3 on the PCB
of the EKCB(H/X)* switch box correctly. Refer to
"13.2. Room thermostat installation configuration" on
page 28.
For configuration B: Make sure to configure the field
settings [C-02, C-03 and C-04] correctly. Refer to "Bivalent
operation" on page 37.
CAUTION
Make sure that return water to the EBHQ* heat exchanger
never exceeds 55°C.
For this reason, never put the target leaving water
temperature set point on the boiler controller above 55°C
and install an aquastat
(a)
valve in the return water flow of
the EBHQ* unit.
Make sure that the non-return valves (field supply) are
correctly installed in the system.
Make sure that the room thermostat (th) is not frequently
turned ON/OFF.
Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 55°C and must operate to close the return
water flow to the unit when the measured temperature exceeds 55°C. When the
temperature drops to a lower level, the aquastat valve must operate to open the
return water flow to the EBHQ* unit again.
Installation manual
14
CAUTION
Manual permission towards the EBHQ* unit on the boiler.
In case only the EBHQ* unit should operate in space
heating mode, disable the bivalent operation via setting
[C-02].
In case only the boiler should operate in space heating
mode, increase the bivalent ON temperature [C-03] to
25°C.
EBHQ006+008BAV3 + EKCBX/H008BAV3
Unit for air to water heat pump system
4PW64602-1 – 08.2010
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.