1.1About the documentation .............................................................................................................................................. 6
1.1.1Meaning of warnings and symbols ................................................................................................................6
1.2For the installer............................................................................................................................................................... 7
1.2.2Installation site ............................................................................................................................................... 8
2.1About this document ...................................................................................................................................................... 13
2.2Installer reference guide at a glance .............................................................................................................................. 14
3 About the box16
3.1Overview: About the box ................................................................................................................................................ 16
3.2Outdoor unit ................................................................................................................................................................... 16
3.2.1To unpack the outdoor unit ........................................................................................................................... 16
3.2.2To handle the outdoor unit ............................................................................................................................ 17
3.2.3To remove the accessories from the outdoor unit........................................................................................ 17
3.2.4To remove the transportation stay ................................................................................................................ 18
3.3Indoor unit ...................................................................................................................................................................... 19
3.3.1To unpack the indoor unit .............................................................................................................................. 19
3.3.2To remove the accessories from the indoor unit .......................................................................................... 19
3.3.3To handle the indoor unit............................................................................................................................... 20
3.4Domestic hot water tank kit ........................................................................................................................................... 20
3.4.1To remove the accessories from the domestic hot water tank kit ............................................................... 20
3.5Checklist for the required DHW accessories.................................................................................................................. 21
4 About the units and options22
4.1Overview: About the units and options.......................................................................................................................... 22
4.2.1Identification label: Outdoor unit .................................................................................................................. 22
4.2.2Identification label: Indoor unit ..................................................................................................................... 23
4.3Combining units and options.......................................................................................................................................... 23
4.3.1Possible options for the outdoor unit ............................................................................................................ 23
4.3.2Possible options for the indoor unit............................................................................................................... 23
4.3.3Possible combinations of indoor unit and outdoor unit................................................................................ 25
5.2Setting up the space heating/cooling system ................................................................................................................ 26
5.3Setting up an auxiliary heat source for space heating ................................................................................................... 37
5.4Setting up the domestic hot water tank......................................................................................................................... 40
5.4.2Selecting the volume and desired temperature for the DHW tank .............................................................. 40
5.4.3Setup and configuration – DHW tank ............................................................................................................ 42
5.4.4DHW pump for instant hot water .................................................................................................................. 42
5.4.5DHW pump for disinfection ........................................................................................................................... 43
5.5Setting up the energy metering...................................................................................................................................... 43
5.5.3Normal kWh rate power supply ..................................................................................................................... 44
5.5.4Preferential kWh rate power supply .............................................................................................................. 46
5.6Setting up the power consumption control ................................................................................................................... 47
5.6.1Permanent power limitation .......................................................................................................................... 47
5.6.2Power limitation activated by digital inputs .................................................................................................. 48
5.7Setting up an external temperature sensor ................................................................................................................... 49
6.2Preparing the installation site......................................................................................................................................... 51
6.2.1Installation site requirements of the outdoor unit........................................................................................ 51
6.2.2Additional installation site requirements of the outdoor unit in cold climates............................................ 53
6.2.3Installation site requirements of the indoor unit .......................................................................................... 54
6.3Preparing water piping ................................................................................................................................................... 55
7.2Opening the units ........................................................................................................................................................... 66
7.2.1About opening the units................................................................................................................................. 66
7.2.2To open the outdoor unit ............................................................................................................................... 66
7.2.3To open the indoor unit ................................................................................................................................. 67
7.2.4To lower the switch box on the indoor unit .................................................................................................. 69
7.3Mounting the outdoor unit............................................................................................................................................. 70
7.3.1About mounting the outdoor unit ................................................................................................................. 70
7.3.2Precautions when mounting the outdoor unit .............................................................................................. 70
7.3.3To provide the installation structure ............................................................................................................. 70
7.3.4To install the outdoor unit ............................................................................................................................. 71
7.3.5To provide drainage........................................................................................................................................ 71
7.3.6To fix the fluorinated greenhouse gases label ............................................................................................... 72
7.3.7To prevent the outdoor unit from falling over .............................................................................................. 72
7.4Mounting the indoor unit ............................................................................................................................................... 73
7.4.1About mounting the indoor unit .................................................................................................................... 73
7.4.2Precautions when mounting the indoor unit................................................................................................. 73
7.4.3To install the indoor unit ................................................................................................................................ 73
7.4.4To connect the drain hose to the drain ......................................................................................................... 74
7.5Connecting water piping................................................................................................................................................. 75
7.5.1About connecting the water piping ............................................................................................................... 75
7.5.2Precautions when connecting the water piping ............................................................................................ 75
7.5.3To connect the water piping .......................................................................................................................... 75
7.5.4To connect the water piping for domestic hot water.................................................................................... 78
7.5.5To connect the recirculation piping ............................................................................................................... 81
7.5.6To fill the water circuit ................................................................................................................................... 81
7.5.7To protect the water circuit against freezing ................................................................................................ 81
7.5.8To fill the domestic hot water tank ................................................................................................................ 85
7.5.9To insulate the water piping .......................................................................................................................... 85
7.6Connecting the electrical wiring..................................................................................................................................... 86
7.6.1About connecting the electrical wiring .......................................................................................................... 86
7.6.3Precautions when connecting the electrical wiring....................................................................................... 86
7.6.4Guidelines when connecting the electrical wiring......................................................................................... 87
7.6.5Specifications of standard wiring components.............................................................................................. 87
7.6.6To connect the electrical wiring to the outdoor unit .................................................................................... 88
7.6.7To connect the electrical wiring to the indoor unit ....................................................................................... 89
7.6.8To connect the main power supply................................................................................................................ 91
7.6.9To connect the backup heater power supply ................................................................................................ 92
7.6.10To connect the shut-off valve ........................................................................................................................ 94
7.6.11To connect the electricity meters .................................................................................................................. 95
7.6.12To connect the domestic hot water pump .................................................................................................... 95
7.6.13To connect the alarm output ......................................................................................................................... 95
7.6.14To connect the space cooling/heating ON/OFF output................................................................................. 96
7.6.15To connect the changeover to external heat source..................................................................................... 96
7.6.16To connect the power consumption digital inputs........................................................................................ 97
7.6.17To connect the safety thermostat (normally closed contact)....................................................................... 97
7.7Finishing the outdoor unit installation ........................................................................................................................... 98
7.7.1To finish the outdoor unit installation ........................................................................................................... 98
7.8Finishing the indoor unit installation.............................................................................................................................. 98
7.8.1To close the indoor unit ................................................................................................................................. 98
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
8.1.1To access the most used commands ............................................................................................................. 101
8.3.3Main menu screen.......................................................................................................................................... 106
8.4Settings menu ................................................................................................................................................................. 114
8.4.3Main zone ....................................................................................................................................................... 117
8.4.4Additional zone ............................................................................................................................................... 127
9.2Precautions when commissioning.................................................................................................................................. 168
9.3Checklist before commissioning..................................................................................................................................... 169
9.4Checklist during commissioning ..................................................................................................................................... 169
9.4.1To check the minimum flow rate ................................................................................................................... 170
9.4.3To perform an operation test run .................................................................................................................. 172
9.4.4To perform an actuator test run .................................................................................................................... 172
11.1 Overview: Maintenance and service .............................................................................................................................. 178
11.3 Checklist for yearly maintenance of the outdoor unit ................................................................................................... 178
11.4 Checklist for yearly maintenance of the indoor unit ..................................................................................................... 178
11.5 To drain the domestic hot water tank............................................................................................................................ 182
11.6 To inspect the inside of the domestic hot water tank ................................................................................................... 183
11.7 About cleaning the water filter in case of trouble ......................................................................................................... 184
11.7.1To remove the water filter ............................................................................................................................. 184
11.7.2To clean the water filter in case of trouble.................................................................................................... 185
11.7.3To install the water filter................................................................................................................................ 186
12.2 Precautions when troubleshooting ................................................................................................................................ 187
12.3 Solving problems based on symptoms ........................................................................................................................... 188
12.3.1Symptom: The unit is NOT heating or cooling as expected........................................................................... 188
12.3.2Symptom: Hot water does NOT reach the desired temperature.................................................................. 188
12.3.3Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 189
12.3.4Symptom: The system is making gurgling noises after commissioning ........................................................ 189
12.3.5Symptom: The pump is making noise (cavitation)......................................................................................... 190
12.3.6Symptom: The pressure relief valve opens.................................................................................................... 190
12.3.7Symptom: The water pressure relief valve leaks........................................................................................... 191
12.3.8Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 191
12.3.9Symptom: The pressure at the tapping point is temporarily unusually high................................................ 192
12.3.10 Symptom: Decoration panels are pushed away due to a swollen tank ........................................................ 192
12.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error) ............................................. 192
12.4 Solving problems based on error codes ......................................................................................................................... 193
12.4.1To display the help text in case of a malfunction .......................................................................................... 193
13.2 To pump down ................................................................................................................................................................ 199
13.3 To activate and deactivate the vacuum mode field setting........................................................................................... 200
13.4 To perform vacuum drying ............................................................................................................................................. 200
13.5 Using the stop valve and service port ............................................................................................................................ 201
13.5.1To handle the stop valve ................................................................................................................................ 201
13.5.2To open/close the stop valve ......................................................................................................................... 202
13.5.3To handle the stem cap.................................................................................................................................. 202
13.5.4To handle the service cap............................................................................................................................... 202
14 Technical data204
14.1 Service space: Outdoor unit ........................................................................................................................................... 204
14.2 Piping diagram: Outdoor unit ......................................................................................................................................... 205
14.3 Piping diagram: Indoor unit ............................................................................................................................................ 206
14.4 Wiring diagram: Outdoor unit ........................................................................................................................................ 207
14.5 Wiring diagram: Indoor unit ........................................................................................................................................... 210
14.7 Technical specifications: Domestic hot water tank........................................................................................................ 215
14.7.1Test results in accordance with EN12897 (2016) .......................................................................................... 215
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Installer reference guide
5
1 | General safety precautions
1 General safety precautions
1.1 About the documentation
▪ The original documentation is written in English. All other languages are
translations.
▪ The precautions described in this document cover very important topics, follow
them carefully.
▪ The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised
installer.
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold
temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Installer reference guide
6
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Symbols used on the unit:
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
The unit contains rotating parts. Be careful when servicing or
inspecting the unit.
Symbols used in the documentation:
SymbolExplanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".
1 | General safety precautions
1.2 For the installer
1.2.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
Installer reference guide
7
1 | General safety precautions
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
1.2.2 Installation site
Also, at least, following information MUST be provided at an accessible place at the
product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
▪ Provide sufficient space around the unit for servicing and air circulation.
▪ Make sure the installation site withstands the weight and vibration of the unit.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪ In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
1.2.3 Refrigerant
Installer reference guide
8
▪ In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
If applicable. See the installation manual or installer reference guide of your
application for more information.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
1 | General safety precautions
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ In case of R410A or R32 refrigerant: Toxic gas might be produced if refrigerant
gas comes into contact with fire.
▪ In case of CO
refrigerant: Refrigerant gas is toxic in high concentrations.
2
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
Installer reference guide
9
1 | General safety precautions
▪ In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
1.2.4 Brine
If applicable. See the installation manual or installer reference guide of your
application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area
immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room,
e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply with the safety and
environmental precautions specified in the applicable legislation.
Installer reference guide
10
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
1.2.5 Water
1.2.6 Electrical
1 | General safety precautions
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1minute, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable legislation.
▪ All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
▪ NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
▪ Make sure to install the required fuses or circuit breakers.
▪ Make sure to install an earth leakage protector. Failure to do so may cause
electric shock or fire.
▪ When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Installer reference guide
11
1 | General safety precautions
CAUTION
▪ When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
▪ When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
▪ The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened
before the earth wire is in case the power supply is pulled loose from the stress
relief.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness, do as shown in the figure
above.
▪ For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 m away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 m may not be
sufficient.
WARNING
▪ After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
Installer reference guide
12
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
2 About the documentation
2.1 About this document
INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it
for future reference.
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
2 | About the documentation
▪ Indoor unit installation manual:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
▪ Outdoor unit installation manual:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
▪ Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
▪ Addendum book for optional equipment:
- Additional info about how to install optional equipment
- Format: Paper (in the box of the indoor unit) + Digital files on http://
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Technical engineering data
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
Installer reference guide
13
2 | About the documentation
▪ Heating Solutions Navigator
- Digital toolbox that offers a variety of tools to facilitate the installation and
- To access Heating Solutions Navigator, registration to the Stand By Me
▪ Daikin e-Care
- Mobile app for installers and service technicians that allows you to register,
- The mobile app can be downloaded for iOS and Android devices using the QR
configuration of heating systems.
platform is required. For more information, see https://
professional.standbyme.daikin.eu.
configure and troubleshoot heating systems.
codes below. Registration to the Stand By Me platform is required to access
the app.
App StoreGoogle Play
2.2 Installer reference guide at a glance
ChapterDescription
General safety precautionsSafety instructions that you must read before
installing
About the documentationWhat documentation exists for the installer
About the boxHow to unpack the units and remove their
accessories
About the units and options▪ How to identify the units
▪ Possible combinations of units and options
Application guidelinesVarious installation setups of the system
PreparationWhat to do and know before going on‑site
InstallationWhat to do and know to install the system
ConfigurationWhat to do and know to configure the system
after it is installed
CommissioningWhat to do and know to commission the system
after it is configured
Hand‑over to the userWhat to give and explain to the user
Installer reference guide
14
Maintenance and serviceHow to maintain and service the units
TroubleshootingWhat to do in case of problems
DisposalHow to dispose of the system
Technical dataSpecifications of the system
GlossaryDefinition of terms
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
2 | About the documentation
ChapterDescription
Field settings tableTable to be filled in by the installer, and kept for
future reference
Note: There is also an installer settings table in
the user reference guide. This table has to be
filled in by the installer and handed over to the
user.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Installer reference guide
15
3 | About the box
3 About the box
3.1 Overview: About the box
3.2 Outdoor unit
3.2.1 To unpack the outdoor unit
This chapter describes what you have to do after the boxes with the outdoor and
indoor unit are delivered on-site.
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in advance.
Installer reference guide
16
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
3 | About the box
1
4
5
2
3
4×
143 kg
3.2.2 To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
3.2.3 To remove the accessories from the outdoor unit
1Open the outdoor unit.
2Remove the accessories.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Installer reference guide
17
3 | About the box
1×
2×
2×
1×1×
ENERG
IJAY
IAIE
ENERG
IJAY
IAIE
1×
RXXX
1×1×
ade
bc
a Outdoor unit installation manual
b Fluorinated greenhouse gases label
c Multilingual fluorinated greenhouse gases label
d Shut-off valve (with integrated filter)
e Energy label
3.2.4 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
The compressor transportation stay must be removed. It is installed under the
compressor leg in order to protect the unit during transport. Proceed as shown in
the figure and procedure below.
1Remove the nut (a) of the compressor mounting bolt.
2Remove and discard the transportation stay (b).
3Re-install the nut (a) of the compressor mounting bolt and tighten to
10.1N•m of torque.
Installer reference guide
18
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
(10.1 N·m)
a
1
3
2
b
3.3 Indoor unit
12
8×
1×
4×
8×
1×
1×1×
4×1×
1×1×1×1×
abcde
jklfghi
3 | About the box
INFORMATION
This unit has been tested and approved according to BSEN12897:2016
3.3.1 To unpack the indoor unit
3.3.2 To remove the accessories from the indoor unit
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
a Shut-off valves for water circuit
b Overpressure bypass valve
c Tundish (to mount onto the pressure relief valve discharge pipe)
d Brass compression coupler
e Discharge pipe (for pressure relief valve)
f General safety precautions
Installer reference guide
19
3 | About the box
b
aa
b
d
b
a
c
e
g
f
3.3.3 To handle the indoor unit
g Addendum book for optional equipment
h Indoor unit installation manual
i Operation manual
j Sealing rings for shut-off valves (space heating water circuit)
k Sealing rings for field-supplied shut-off valves (domestic hot water circuit)
l Sealing tape for low voltage wiring intake
Use the handles at the back and at the bottom to carry the unit.
a Handles at the back of the unit
b Handles at the bottom of the unit. Carefully tilt the unit to the back so that the handles become visible.
3.4 Domestic hot water tank kit
3.4.1 To remove the accessories from the domestic hot water tank kit
a Pressure reducing valve/pressure relief valve combination. Water inlet and water
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Installer reference guide
21
4 | About the units and options
4 About the units and options
4.1 Overview: About the units and options
This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the indoor unit
▪ Combining the outdoor unit with options
▪ Combining the indoor unit with options
4.2 Identification
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
4.2.1 Identification label: Outdoor unit
Location
Model identification
Example: EPGA11DAV3
CodeExplanation
EPEuropean hydro-split outdoor pair heat pump
GMedium water temperature – ambient zone: −10~−20°C
ARefrigerant R32
11Capacity class
Installer reference guide
22
DAModel series
V3Power supply
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
4.2.2 Identification label: Indoor unit
Location
Model identification
Example: EAVH16SU23DA6V
CodeDescription
EEuropean model
AVFloor-standing hydro-split unit with integrated tank
HHeating only
16Capacity class
SIntegrated tank material: Stainless steel
UUK model
4 | About the units and options
23Integrated tank volume
DAModel series
6VBackup heater model
4.3 Combining units and options
INFORMATION
Certain options might not be available in your country.
4.3.1 Possible options for the outdoor unit
Bottom plate heater (EKBPH140L7)
▪ Prevents freeze-up of the bottom plate.
▪ Recommended in areas with low ambient temperature and high humidity.
For installation instructions, see the installation manual of the bottom plate heater.
4.3.2 Possible options for the indoor unit
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
User interface used as room thermostat (BRC1HHDA)
▪ The user interface used as room thermostat can only be used in combination
with the user interface connected to the indoor unit.
▪ The user interface used as room thermostat needs to be installed in the room
that you want to control.
For installation instructions, see the installation and operation manual of the user
interface used as room thermostat.
Installer reference guide
23
4 | About the units and options
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat
can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat
and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination
with the wireless thermostat (EKRTR1).
For installation instructions, see the installation manual of the room thermostat
and addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating/cooling On/OFF output
▪ Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and
addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install
the demand PCB.
For installation instructions, see the installation manual of the demand PCB and
addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature
sensor.
As an option the remote indoor sensor can be installed to measure the room
temperature on another location.
For installation instructions, see the installation manual of the remote indoor
sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the user interface is
configured with room thermostat functionality.
▪ You can only connect either the remote indoor sensor or the remote outdoor
sensor.
Remote outdoor sensor (EKRSCA1)
Installer reference guide
24
By default the sensor inside the outdoor unit will be used to measure the outdoor
temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor
temperature on another location (e.g. to avoid direct sunlight) to have an
improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor
sensor and the addendum book for optional equipment.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
4 | About the units and options
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
PC cable (EKPCCAB4)
The PC cable makes a connection between the switch box of the indoor unit and a
PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable.
Heat pump convector (FWXV)
For providing space heating/cooling, it is possible to use heat pump convectors
(FWXV).
For installation instructions, see the installation manual of the heat pump
convectors, and the addendum book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
For installation instructions, see the installation manual of the LAN adapter.
Universal centralised controller (EKCC8-W)
Controller for cascade control.
Bizone kit (BZKA7V3)
You can install an optional bizone kit.
For installation instructions, see the installation manual of the bizone kit.
Conversion kit (EKHVCONV2)
Use the connection kit to convert a heating only model to a reversible model.
For installation instructions, see the installation manual of the conversion kit.
4.3.3 Possible combinations of indoor unit and outdoor unit
Indoor unitOutdoor unit
EPGA11EPGA14EPGA16
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
The purpose of the application guidelines is to give a glance of the possibilities of
the heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant for reference only, and
are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are the responsibility of the
installer.
▪ For more information about the configuration settings to optimize heat pump
operation, see "8Configuration"[4100].
This chapter contains application guidelines for:
▪ Setting up the space heating/cooling system
▪ Setting up an auxiliary heat source for space heating
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption control
▪ Setting up an external temperature sensor
5.2 Setting up the space heating/cooling system
The heat pump system supplies leaving water to heat emitters in one or more
rooms.
Because the system offers a wide flexibility to control the temperature in each
room, you need to answer the following questions first:
▪ How many rooms are heated or cooled by the heatpump system?
▪ Which heat emitter types are used in each room and what is their design leaving
water temperature?
Once the space heating/cooling requirements are clear, we recommend to follow
the setup guidelines below.
Installer reference guide
26
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if [C.2]
Space heating/cooling=On.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
5.2.1 Single room
A
B
a
Underfloor heating or radiators – Wired room thermostat
5 | Application guidelines
INFORMATION
In case an external room thermostat is used and room frost protection needs to be
guaranteed in all conditions, then you have to set Emergency [9.5] to Automatic.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this
valve might not be shown on the illustrations.
Setup
A Main leaving water temperature zone
B One single room
a User interface used as room thermostat
▪ The underfloor heating or radiators are directly connected to the indoor unit.
▪ The room temperature of the main room is controlled by the user interface used
as a room thermostat (optional equipment BRC1H).
Configuration
SettingValue
Unit temperature control:
▪ #: [2.9]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the user interface.
▪ Code: [C-07]
Number of water temperature zones:
0 (Single zone): Main
▪ #: [4.4]
▪ Code: [7-02]
Benefits
▪ Highest comfort and efficiency. The smart room thermostat functionality can
decrease or increase the desired leaving water temperature based on the actual
room temperature (modulation). This results in:
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
- Stable room temperature matching the desired temperature (higher comfort)
- Less ON/OFF cycles (more quiet, higher comfort and higher efficiency)
- Lowest possible leaving water temperature (higher efficiency)
Installer reference guide
27
5 | Application guidelines
A
B
b
a
Underfloor heating or radiators – Wireless room thermostat
▪ Easy. You can easily set the desired room temperature via the user interface:
- For your daily needs, you can use preset values and schedules.
- To deviate from your daily needs, you can temporarily overrule the preset
values and schedules, or use the holiday mode.
Setup
A Main leaving water temperature zone
B One single room
a Receiver for wireless external room thermostat
b Wireless external room thermostat
▪ The underfloor heating or radiators are directly connected to the indoor unit.
▪ The room temperature is controlled by the wireless external room thermostat
(optional equipment EKRTR1).
Configuration
SettingValue
Unit temperature control:
▪ #: [2.9]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
▪ Code: [C-07]
Number of water temperature zones:
0 (Single zone): Main
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main
zone:
▪ #: [2.A]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
▪ Code: [C-05]
heating or cooling demand.
Benefits
▪ Wireless. The Daikin external room thermostat is available in a wireless version.
Installer reference guide
28
▪ Efficiency. Although the external room thermostat only sends ON/OFF signals, it
is specifically designed for the heatpump system.
▪ Comfort. In case of underfloor heating, the wireless external room thermostat
prevents condensation on the floor during cooling operation by measuring the
room humidity.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Heatpump convectors
A
B
a
Setup
▪ The heatpump convectors are directly connected to the indoor unit.
▪ The desired room temperature is set via the remote controller of the heat pump
convectors.
▪ The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
5 | Application guidelines
A Main leaving water temperature zone
B One single room
a Remote controller of the heatpump convectors
▪ The space operation mode is sent to the heat pump convectors by one digital
output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat pump convectors, make sure each one receives the
infrared signal from the remote controller of the heatpump convectors.
Configuration
SettingValue
Unit temperature control:
▪ #: [2.9]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
▪ Code: [C-07]
Number of water temperature zones:
0 (Single zone): Main
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main
zone:
▪ #: [2.A]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
▪ Code: [C-05]
heating or cooling demand.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Benefits
▪ Cooling. The heat pump convector offers, besides heating capacity, also excellent
cooling capacity.
▪ Efficiency. Optimal energy efficiency because of the interlink function.
▪ Space cooling is provided by the heat pump convectors only. The underfloor
heating is shut off by the shut-off valve.
Setup
A Main leaving water temperature zone
B One single room
a Remote controller of the heatpump convectors
▪ The heatpump convectors are directly connected to the indoor unit.
▪ A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
▪ The desired room temperature is set via the remote controller of the heat pump
convectors.
▪ The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
▪ The space operation mode is sent by one digital output (X2M/4 and X2M/3) on
the indoor unit to:
- The heatpump convectors
- The shut-off valve
Configuration
SettingValue
Unit temperature control:
▪ #: [2.9]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
▪ Code: [C-07]
Installer reference guide
30
Number of water temperature zones:
0 (Single zone): Main
▪ #: [4.4]
▪ Code: [7-02]
External room thermostat for the main
zone:
▪ #: [2.A]
▪ Code: [C-05]
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
EPGA11~16DAV3 + EAVH16SU18+23DA6V
Daikin Altherma 3 H F
4P606487-1A – 2020.03
Loading...
+ 198 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.