Daikin CTXM15R2V1B, CTXM15R5V1B, FTXM20R2V1B, FTXM20R5V1B, FTXM25R2V1B Installer reference guide

...
Installer reference guide
Daikin room air conditioner
CTXM15R2V1B CTXM15R5V1B
FTXM20R2V1B FTXM20R5V1B FTXM25R2V1B FTXM25R5V1B FTXM35R2V1B FTXM35R5V1B FTXM42R2V1B FTXM42R5V1B
FTXM50R2V1B FTXM60R2V1B FTXM71R2V1B
ATXM20R2V1B ATXM20R5V1B ATXM25R2V1B ATXM25R5V1B ATXM35R2V1B ATXM35R5V1B ATXM50R2V1B
Table of contents
Table of contents
1 About the documentation 4
1.1 About this document ...................................................................................................................................................... 4
2 General safety precautions 5
2.1 About the documentation .............................................................................................................................................. 5
2.1.1 Meaning of warnings and symbols ................................................................................................................ 5
2.2 For the installer............................................................................................................................................................... 6
2.2.1 General ........................................................................................................................................................... 6
2.2.2 Installation site ............................................................................................................................................... 7
2.2.3 Refrigerant — in case of R410A or R32.......................................................................................................... 11
2.2.4 Brine................................................................................................................................................................ 12
2.2.5 Water .............................................................................................................................................................. 13
2.2.6 Electrical ......................................................................................................................................................... 13
3 Specific installer safety instructions 16
4 About the box 18
4.1 Overview: About the box ................................................................................................................................................ 18
4.2 Indoor unit ...................................................................................................................................................................... 18
4.2.1 To unpack the indoor unit .............................................................................................................................. 18
4.2.2 To remove the accessories from the indoor unit .......................................................................................... 18
5 About the unit 20
5.1 System layout.................................................................................................................................................................. 20
5.2 Operation range.............................................................................................................................................................. 20
5.3 About the wireless LAN................................................................................................................................................... 21
5.3.1 Precautions when using the wireless LAN ..................................................................................................... 21
5.3.2 Basic parameters ............................................................................................................................................ 21
5.3.3 Setting the wireless LAN................................................................................................................................. 22
6 Unit installation 23
6.1 Preparing the installation site......................................................................................................................................... 23
6.1.1 Installation site requirements of the indoor unit .......................................................................................... 23
6.2 Opening the indoor unit ................................................................................................................................................. 24
6.2.1 To remove the front panel ............................................................................................................................. 24
6.2.2 To open the service cover .............................................................................................................................. 25
6.2.3 To remove the front grille .............................................................................................................................. 25
6.3 Mounting the indoor unit ............................................................................................................................................... 26
6.3.1 To install the mounting plate ......................................................................................................................... 26
6.3.2 To drill a wall hole........................................................................................................................................... 27
6.3.3 To remove the pipe port cover ...................................................................................................................... 28
6.4 Connecting the drain piping ........................................................................................................................................... 28
6.4.1 General guidelines .......................................................................................................................................... 28
6.4.2 To connect the piping on right side, right-back, or right-bottom ................................................................. 29
6.4.3 To connect the piping on left side, left-back, or left-bottom ........................................................................ 30
6.4.4 To check for water leaks................................................................................................................................. 31
7 Piping installation 32
7.1 Preparing refrigerant piping ........................................................................................................................................... 32
7.1.1 Refrigerant piping requirements.................................................................................................................... 32
7.1.2 Refrigerant piping insulation .......................................................................................................................... 33
7.2 Connecting the refrigerant piping .................................................................................................................................. 33
7.2.1 About connecting the refrigerant piping ....................................................................................................... 33
7.2.2 Precautions when connecting the refrigerant piping .................................................................................... 34
7.2.3 Guidelines when connecting the refrigerant piping ...................................................................................... 35
7.2.4 Pipe bending guidelines ................................................................................................................................. 35
7.2.5 To flare the pipe end ...................................................................................................................................... 35
7.2.6 To connect the refrigerant piping to the indoor unit .................................................................................... 36
Installer reference guide
2
8 Electrical installation 37
8.1 About connecting the electrical wiring .......................................................................................................................... 37
8.1.1 Precautions when connecting the electrical wiring....................................................................................... 37
8.1.2 Guidelines when connecting the electrical wiring......................................................................................... 38
8.1.3 Specifications of standard wiring components.............................................................................................. 39
8.2 To connect the electrical wiring to the indoor unit ....................................................................................................... 39
9 Finishing the indoor unit installation 42
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
Table of contents
9.1 To insulate the drain piping, refrigerant piping and interconnection cable.................................................................. 42
9.2 To pass the pipes through the wall hole ........................................................................................................................ 42
9.3 To fix the unit on the mounting plate ............................................................................................................................ 43
9.4 To close the indoor unit.................................................................................................................................................. 43
9.4.1 To re-install the front grille ............................................................................................................................ 43
9.4.2 To close the service cover .............................................................................................................................. 43
9.4.3 To re-install the front panel ........................................................................................................................... 43
10 Configuration 45
10.1 To set a different address ............................................................................................................................................... 45
11 Commissioning 47
11.1 Overview: Commissioning .............................................................................................................................................. 47
11.2 Checklist before commissioning ..................................................................................................................................... 47
11.3 To perform a test run...................................................................................................................................................... 48
11.3.1 To perform a test run using the user interface ............................................................................................. 48
12 Hand-over to the user 49
13 Disposal 50
14 Technical data 51
14.1 Wiring diagram................................................................................................................................................................ 51
14.1.1 Unified wiring diagram legend....................................................................................................................... 51
15 Glossary 54
Installer reference guide
3
1 | About the documentation

1 About the documentation

1.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
General safety precautions:
- Safety instructions that you MUST read before installing
- Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Installer reference guide
4
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

2 General safety precautions

2.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

2.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
2 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Symbols used on the unit:
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Installer reference guide
5
2 | General safety precautions
Symbols used in the documentation:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".

2.2 For the installer

2.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer reference guide
6
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
2 | General safety precautions
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…

2.2.2 Installation site

Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
In bathrooms.
Instructions for equipment using R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Installer reference guide
7
2 | General safety precautions
WARNING
Do NOT pierce or burn.Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well­ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
Provision shall be made for expansion and contraction of long runs of piping.Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as moving furniture or reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant leaks.
Installer reference guide
8
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
NOTICE
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
Do NOT re-use joints which have been used already.Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
Installation space requirements
WARNING
If appliances contain R32 refrigerant, the floor area of the room in which the appliances are installed, operated and stored MUST be larger than the minimum floor area defined in table below A (m2). This applies to:
Indoor units without a refrigerant leakage sensor; in case of indoor units with
refrigerant leakage sensor, consult the installation manual
Outdoor units installed or stored indoors (e.g. winter garden, garage, machinery
room)
Pipework in unventilated spaces
NOTICE
Pipework shall be protected from physical damage.Installation of pipework shall be kept to a minimum.
2 | General safety precautions
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory refrigerant
charge + additional refrigerant amount charged).
2 Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
For outdoor units installed or stored indoors, and field piping in unventilated
spaces, this depends on the installation height:
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3 Use the graph or table to determine the minimum floor area.
Installer reference guide
9
2 | General safety precautions
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
Installer reference guide
10
m Total refrigerant charge in the system
A
Minimum floor area
min
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)

2.2.3 Refrigerant — in case of R410A or R32

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
2 | General safety precautions
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer reference guide
11
2 | General safety precautions
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Charge the liquid refrigerant as follows:
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

2.2.4 Brine

Installer reference guide
12
If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

2.2.5 Water

2.2.6 Electrical

2 | General safety precautions
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.
If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
Installer reference guide
13
2 | General safety precautions
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Installer reference guide
14
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
2 | General safety precautions
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installer reference guide
15
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
Unit installation (see "6Unit installation"[423])
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
Piping installation (see "7Piping installation"[432])
DANGER: RISK OF BURNING/SCALDING
CAUTION
Use the flare nut fixed to the unit.To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use
refrigeration oil for R32.
Do NOT reuse joints.
CAUTION
Do NOT use mineral oil on flared part.NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
CAUTION
Incomplete flaring may cause refrigerant gas leakage.Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
Installer reference guide
16
Electrical installation (see "8Electrical installation"[437])
DANGER: RISK OF ELECTROCUTION
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
3 | Specific installer safety instructions
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING
Do NOT use locally purchased electrical parts inside the product.Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
Installer reference guide
17
Loading...
+ 39 hidden pages