Daikin CTXM15R2V1B, CTXM15R5V1B, FTXM20R2V1B, FTXM20R5V1B, FTXM25R2V1B Installer reference guide

...
Installer reference guide
Daikin room air conditioner
CTXM15R2V1B CTXM15R5V1B
FTXM20R2V1B FTXM20R5V1B FTXM25R2V1B FTXM25R5V1B FTXM35R2V1B FTXM35R5V1B FTXM42R2V1B FTXM42R5V1B
FTXM50R2V1B FTXM60R2V1B FTXM71R2V1B
ATXM20R2V1B ATXM20R5V1B ATXM25R2V1B ATXM25R5V1B ATXM35R2V1B ATXM35R5V1B ATXM50R2V1B
Table of contents
Table of contents
1 About the documentation 4
1.1 About this document ...................................................................................................................................................... 4
2 General safety precautions 5
2.1 About the documentation .............................................................................................................................................. 5
2.1.1 Meaning of warnings and symbols ................................................................................................................ 5
2.2 For the installer............................................................................................................................................................... 6
2.2.1 General ........................................................................................................................................................... 6
2.2.2 Installation site ............................................................................................................................................... 7
2.2.3 Refrigerant — in case of R410A or R32.......................................................................................................... 11
2.2.4 Brine................................................................................................................................................................ 12
2.2.5 Water .............................................................................................................................................................. 13
2.2.6 Electrical ......................................................................................................................................................... 13
3 Specific installer safety instructions 16
4 About the box 18
4.1 Overview: About the box ................................................................................................................................................ 18
4.2 Indoor unit ...................................................................................................................................................................... 18
4.2.1 To unpack the indoor unit .............................................................................................................................. 18
4.2.2 To remove the accessories from the indoor unit .......................................................................................... 18
5 About the unit 20
5.1 System layout.................................................................................................................................................................. 20
5.2 Operation range.............................................................................................................................................................. 20
5.3 About the wireless LAN................................................................................................................................................... 21
5.3.1 Precautions when using the wireless LAN ..................................................................................................... 21
5.3.2 Basic parameters ............................................................................................................................................ 21
5.3.3 Setting the wireless LAN................................................................................................................................. 22
6 Unit installation 23
6.1 Preparing the installation site......................................................................................................................................... 23
6.1.1 Installation site requirements of the indoor unit .......................................................................................... 23
6.2 Opening the indoor unit ................................................................................................................................................. 24
6.2.1 To remove the front panel ............................................................................................................................. 24
6.2.2 To open the service cover .............................................................................................................................. 25
6.2.3 To remove the front grille .............................................................................................................................. 25
6.3 Mounting the indoor unit ............................................................................................................................................... 26
6.3.1 To install the mounting plate ......................................................................................................................... 26
6.3.2 To drill a wall hole........................................................................................................................................... 27
6.3.3 To remove the pipe port cover ...................................................................................................................... 28
6.4 Connecting the drain piping ........................................................................................................................................... 28
6.4.1 General guidelines .......................................................................................................................................... 28
6.4.2 To connect the piping on right side, right-back, or right-bottom ................................................................. 29
6.4.3 To connect the piping on left side, left-back, or left-bottom ........................................................................ 30
6.4.4 To check for water leaks................................................................................................................................. 31
7 Piping installation 32
7.1 Preparing refrigerant piping ........................................................................................................................................... 32
7.1.1 Refrigerant piping requirements.................................................................................................................... 32
7.1.2 Refrigerant piping insulation .......................................................................................................................... 33
7.2 Connecting the refrigerant piping .................................................................................................................................. 33
7.2.1 About connecting the refrigerant piping ....................................................................................................... 33
7.2.2 Precautions when connecting the refrigerant piping .................................................................................... 34
7.2.3 Guidelines when connecting the refrigerant piping ...................................................................................... 35
7.2.4 Pipe bending guidelines ................................................................................................................................. 35
7.2.5 To flare the pipe end ...................................................................................................................................... 35
7.2.6 To connect the refrigerant piping to the indoor unit .................................................................................... 36
Installer reference guide
2
8 Electrical installation 37
8.1 About connecting the electrical wiring .......................................................................................................................... 37
8.1.1 Precautions when connecting the electrical wiring....................................................................................... 37
8.1.2 Guidelines when connecting the electrical wiring......................................................................................... 38
8.1.3 Specifications of standard wiring components.............................................................................................. 39
8.2 To connect the electrical wiring to the indoor unit ....................................................................................................... 39
9 Finishing the indoor unit installation 42
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
Table of contents
9.1 To insulate the drain piping, refrigerant piping and interconnection cable.................................................................. 42
9.2 To pass the pipes through the wall hole ........................................................................................................................ 42
9.3 To fix the unit on the mounting plate ............................................................................................................................ 43
9.4 To close the indoor unit.................................................................................................................................................. 43
9.4.1 To re-install the front grille ............................................................................................................................ 43
9.4.2 To close the service cover .............................................................................................................................. 43
9.4.3 To re-install the front panel ........................................................................................................................... 43
10 Configuration 45
10.1 To set a different address ............................................................................................................................................... 45
11 Commissioning 47
11.1 Overview: Commissioning .............................................................................................................................................. 47
11.2 Checklist before commissioning ..................................................................................................................................... 47
11.3 To perform a test run...................................................................................................................................................... 48
11.3.1 To perform a test run using the user interface ............................................................................................. 48
12 Hand-over to the user 49
13 Disposal 50
14 Technical data 51
14.1 Wiring diagram................................................................................................................................................................ 51
14.1.1 Unified wiring diagram legend....................................................................................................................... 51
15 Glossary 54
Installer reference guide
3
1 | About the documentation

1 About the documentation

1.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
INFORMATION
Make sure that the user has the printed documentation and ask him/her to keep it for future reference.
INFORMATION
This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.
General safety precautions:
- Safety instructions that you MUST read before installing
- Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.
Technical engineering data
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Installer reference guide
4
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

2 General safety precautions

2.1 About the documentation

The original documentation is written in English. All other languages are
translations.
The precautions described in this document cover very important topics, follow
them carefully.
The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised installer.

2.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
2 | General safety precautions
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING/SCALDING
Indicates a situation that could result in burning/scalding because of extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
Symbols used on the unit:
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
Installer reference guide
5
2 | General safety precautions
Symbols used in the documentation:
Symbol Explanation
Before installation, read the installation and operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the service manual.
For more information, see the installer and user reference guide.
The unit contains rotating parts. Be careful when servicing or inspecting the unit.
Symbol Explanation
Indicates a figure title or a reference to it.
Example: " 1–3 Figure title" means "Figure 3 in chapter 1".
Indicates a table title or a reference to it.
Example: " 1–3 Table title" means "Table 3 in chapter 1".

2.2 For the installer

2.2.1 General

If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Installer reference guide
6
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
2 | General safety precautions
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
Do NOT place any objects or equipment on top of the unit.Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…

2.2.2 Installation site

Also, at least, following information MUST be provided at an accessible place at the product:
Instructions for shutting down the system in case of an emergency
Name and address of fire department, police and hospital
Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
Provide sufficient space around the unit for servicing and air circulation.
Make sure the installation site withstands the weight and vibration of the unit.
Make sure the area is well ventilated. Do NOT block any ventilation openings.
Make sure the unit is level.
Do NOT install the unit in the following places:
In potentially explosive atmospheres.
In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
In bathrooms.
Instructions for equipment using R32 refrigerant
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Installer reference guide
7
2 | General safety precautions
WARNING
Do NOT pierce or burn.Do NOT use means to accelerate the defrosting process or to clean the
equipment, other than those recommended by the manufacturer.
Be aware that R32 refrigerant does NOT contain an odour.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well­ventilated room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater) and have a room size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.
NOTICE
Precautions shall be taken to avoid excessive vibration or pulsation to
refrigeration piping.
Protection devices, piping and fittings shall be protected as far as possible against
adverse environmental effects.
Provision shall be made for expansion and contraction of long runs of piping.Piping in refrigerating systems shall be designed and installed such as to minimise
the likelihood of hydraulic shock damaging the system.
The indoor equipment and pipes shall be securely mounted and guarded such
that accidental rupture of equipment or pipes cannot occur from events such as moving furniture or reconstruction activities.
CAUTION
Do NOT use potential sources of ignition in searching for or detection of refrigerant leaks.
Installer reference guide
8
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
NOTICE
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO2eq
1000
GWP × kg
=
=
+
kg
=
kg
=
GWP: xxx
R32
Do NOT re-use joints which have been used already.Joints made in installation between parts of refrigerant system shall be accessible
for maintenance purposes.
Installation space requirements
WARNING
If appliances contain R32 refrigerant, the floor area of the room in which the appliances are installed, operated and stored MUST be larger than the minimum floor area defined in table below A (m2). This applies to:
Indoor units without a refrigerant leakage sensor; in case of indoor units with
refrigerant leakage sensor, consult the installation manual
Outdoor units installed or stored indoors (e.g. winter garden, garage, machinery
room)
Pipework in unventilated spaces
NOTICE
Pipework shall be protected from physical damage.Installation of pipework shall be kept to a minimum.
2 | General safety precautions
To determine the minimum floor area
1 Determine the total refrigerant charge in the system (= factory refrigerant
charge + additional refrigerant amount charged).
2 Determine which graph or table to use.
For indoor units: Is the unit ceiling-mounted, wall-mounted or floor-
standing?
For outdoor units installed or stored indoors, and field piping in unventilated
spaces, this depends on the installation height:
If the installation height is… Then use the graph or table for…
<1.8m Floor-standing units
1.8≤x<2.2m Wall-mounted units
≥2.2m Ceiling-mounted units
3 Use the graph or table to determine the minimum floor area.
Installer reference guide
9
2 | General safety precautions
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190
200
210
220
230
240
250
260
270
280
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
1.822.2
2.4
2.6
2.833.2
3.4
3.6
3.844.2
4.4
4.6
4.855.2
5.4
5.6
5.866.2
6.4
6.6
6.877.2
7.4
7.6
7.8
1.843 7.956
8.0
A
min
(m2)
Floor-standing unit
(c)
Wall-mounted unit
(b)
Ceiling-mounted unit
(a)
m (kg)
Ceiling-mounted
unit
(a)
4.6 13.4
4.6 180
4.8 14.6
4.8 196
5.0 15.8
5.0 213
≤1.842
5.2 17.1
≤1.842
5.2 230
1.843 3.64
5.4 18.5
1.843 28.9
5.4 248
2.0 3.95
5.6 19.9
2.0 34.0
5.6 267
2.2 4.34
5.8 21.3
2.2 41.2
5.8 286
2.4 4.74
6.0 22.8
2.4 49.0
6.0 306
2.6 5.13
6.2 24.3
2.6 57.5
6.2 327
2.8 5.53
6.4 25.9
2.8 66.7
6.4 349
3.0 5.92
6.6 27.6
3.0 76.6
6.6 371
3.2 6.48
6.8 29.3
3.2 87.2
6.8 394
3.4 7.32
7.0 31.0
3.4 98.4
7.0 417
3.6 8.20
7.2 32.8
3.6 110
7.2 441
3.8 9.14
7.4 34.7
3.8 123
7.4 466
4.0 10.1
7.6 36.6
4.0 136
7.6 492
4.2 11.2
7.8 38.5
4.2 150
7.8 518
4.4 12.3
7.956 40.1
4.4 165
7.956 539
m (kg)
A
min
(m2)
4.6 20.0
4.8 21.8
5.0 23.6
≤1.842
5.2 25.6
1.843 4.45
5.4 27.6
2.0 4.83
5.6 29.7
2.2 5.31
5.8 31.8
2.4 5.79
6.0 34.0
2.6 6.39
6.2 36.4
2.8 7.41
6.4 38.7
3.0 8.51
6.6 41.2
3.2 9.68
6.8 43.7
3.4 10.9
7.0 46.3
3.6 12.3
7.2 49.0
3.8 13.7
7.4 51.8
4.0 15.1
7.6 54.6
4.2 16.7
7.8 57.5
4.4 18.3
7.956 59.9
Wall-mounted
unit
(b)
m (kg)
A
min
(m2)
Floor-standing
unit
(c)
m (kg)
A
min
(m2)
Installer reference guide
10
m Total refrigerant charge in the system
A
Minimum floor area
min
(a) Ceiling-mounted unit (= Ceiling-mounted unit)
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
(b) Wall-mounted unit (= Wall-mounted unit)
(c) Floor-standing unit (= Floor-standing unit)

2.2.3 Refrigerant — in case of R410A or R32

If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
2 | General safety precautions
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self­combustion and explosion of the compressor because of air going into the operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Installer reference guide
11
2 | General safety precautions
In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the system.
Charge the liquid refrigerant as follows:
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of oxygen going into the operating compressor.
If Then
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid filling siphon attached")
A siphon tube is NOT present Charge with the cylinder upside down.
Open refrigerant cylinders slowly.
Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount.

2.2.4 Brine

Installer reference guide
12
If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

2.2.5 Water

2.2.6 Electrical

2 | General safety precautions
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.
If applicable. See the installation manual or installer reference guide of your application for more information.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
DANGER: RISK OF ELECTROCUTION
Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
Disconnect the power supply for more than 10minutes, and measure the voltage
at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50VDC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
Do NOT touch electrical components with wet hands.Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage categoryIII condition, MUST be installed in the fixed wiring.
Installer reference guide
13
2 | General safety precautions
WARNING
ONLY use copper wires.Make sure the field wiring complies with the applicable legislation.All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
Make sure to install the required fuses or circuit breakers.Make sure to install an earth leakage protector. Failure to do so may cause
electrical shock or fire.
When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
CAUTION
When connecting the power supply: connect the earth cable first, before making
the current-carrying connections.
When disconnecting the power supply: disconnect the current-carrying cables
first, before separating the earth connection.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened before the earth wire is in case the power supply is pulled loose from the stress relief.
NOTICE
Precautions when laying power wiring:
Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
When connecting wiring which is the same thickness, do as shown in the figure
above.
For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
Over-tightening the terminal screws may break them.
Installer reference guide
14
WARNING
After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
Make sure all covers are closed before starting up the unit.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
2 | General safety precautions
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/ OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
Installer reference guide
15
3 | Specific installer safety instructions

3 Specific installer safety instructions

Always observe the following safety instructions and regulations.
Unit installation (see "6Unit installation"[423])
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
Piping installation (see "7Piping installation"[432])
DANGER: RISK OF BURNING/SCALDING
CAUTION
Use the flare nut fixed to the unit.To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use
refrigeration oil for R32.
Do NOT reuse joints.
CAUTION
Do NOT use mineral oil on flared part.NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
CAUTION
Incomplete flaring may cause refrigerant gas leakage.Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
Installer reference guide
16
Electrical installation (see "8Electrical installation"[437])
DANGER: RISK OF ELECTROCUTION
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
3 | Specific installer safety instructions
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING
Do NOT use locally purchased electrical parts inside the product.Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.
Installer reference guide
17
4 | About the box
fe1d e2ba c g h i j

4 About the box

4.1 Overview: About the box

This chapter describes what you have to do after the box with the indoor unit is delivered on-site.
It contains information about:
Unpacking and handling the unit
Removing the accessories from the unit
Keep the following in mind:
At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
When handling the unit, take into account the following:
Fragile, handle the unit with care.
Keep the unit upright in order to avoid damage.
Prepare the path along which you want to bring the unit inside in advance.

4.2 Indoor unit

4.2.1 To unpack the indoor unit

4.2.2 To remove the accessories from the indoor unit

Installer reference guide
18
1 Remove:
the accessory bag located at the bottom of the package,
the mounting plate attached to the back of the indoor unit,
the spare SSID sticker located on the front grille.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
4 | About the box
a Installation manual b Operation manual c General safety precautions
d Spare SSID sticker e1 Class 15~42: Silver allergen removal air purifying filter (without frame) e2 Class 50~71: Titanium apatite deodorising filter and silver allergen removal air purifying filter (with frame)
f Indoor unit fixing screw (M4×12L). Refer to "9.3To fix the unit on the mounting plate"[443]. g Dry battery AAA.LR03 (alkaline) for user interface h User interface holder
i User interface
j Mounting plate
Spare SSID sticker. Do NOT throw away the spare sticker. Keep it in a safe place
in case it is needed in future (e.g. in case the front grille was replaced attach it to the new front grille).
Installer reference guide
19
5 | About the unit
d
c
f
h1 h2
g
e
b
a

5 About the unit

5.1 System layout

WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
a Front cover b Service cover c Caulk pipe hole gap with putty d Refrigerant piping, drain hose and interconnection cable e Intelligent eye sensor
f Insulation tape
g Air filters h1 Class 15~42: Silver allergen removal air purifying filter (without frame) h2 Class 50~71: Titanium apatite deodorising filter and silver allergen removal air purifying filter (with frame)

5.2 Operation range

Use the system in the following temperature and humidity ranges for safe and effective operation.
Outdoor temperature –20~52°CDB –20~24°CDB
Indoor temperature 17~38°C DB
Indoor humidity ≤80%
(a)
(b)
In combination with outdoor units: RXM71R, 2MXM, 2AMXM, 3MXM, 3AMXM,
Outdoor temperature –10~46°CDB –15~24°CDB
In combination with outdoor unit RZAG
Cooling and drying
(a)(b)
Heating
(a)
–21~18°CWB
10~27°CDB
12~28°CWB
(b)
A safety device might stop the operation of the system if the unit runs outside its operation range. Condensation and water dripping might occur if the unit runs outside its operation range.
4MXM, 5MXM
Cooling and drying
(a)(b)
Heating
(a)
–15~18°CWB
Installer reference guide
20
Indoor temperature 18~37°C DB
Indoor humidity ≤80%
10~30°CDB
14~28°CWB
(a)
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
5 | About the unit
(a)
A safety device might stop the operation of the system if the unit runs outside its operation range.
(b)
Condensation and water dripping might occur if the unit runs outside its operation range.
In combination with other outdoor units
Cooling and drying
(a)(b)
Heating
Outdoor temperature –10~50°CDB –20~24°CDB
–21~18°CWB
(a)
Indoor temperature 18~37°C DB
Indoor humidity ≤80%
(a)
A safety device might stop the operation of the system if the unit runs outside its operation range.
(b)
Condensation and water dripping might occur if the unit runs outside its operation range.

5.3 About the wireless LAN

For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit http://
www.onlinecontroller.daikineurope.com.
INFORMATION
Daikin Industries Czech Republic s.r.o. declares that the radio equipment type
inside of this unit is in compliance with Directive 2014/53/EU.
This unit is considered as combined equipment according to the definition of
Directive 2014/53/EU.
14~28°CWB
(b)
10~30°CDB

5.3.1 Precautions when using the wireless LAN

Do NOT use near:
Medical equipment. E.g. persons using cardiac pacemakers or defibrillators. This
product may cause electromagnetic interference.
Auto-control equipment. E.g. automatic doors or fire alarm equipment. This
product may cause faulty behaviour of the equipment.
Microwave oven. It may affect wireless LAN communications.

5.3.2 Basic parameters

What Value
Frequency range 2400MHz~2483.5MHz
Radio protocol IEEE 802.11b/g/n
Radio frequency channel 1~13
Output power 13dBm
Effective radiated power 15dBm (11b) / 14dBm (11g) / 14dBm
Power supply DC 14 V / 100 mA
(11n)
Installer reference guide
21
5 | About the unit

5.3.3 Setting the wireless LAN

To install the Daikin Residential Controller application
The customer is responsible for providing:
Smartphone or tablet with minimum supported version of Android or iOS,
specified on http://www.onlinecontroller.daikineurope.com
Internet line and communicating device, such as modem, router, etc.
Wireless LAN access point.
Installed free Daikin Residential Controller application.
1 Open:
Google Play for appliances using Android.App Store for appliances using iOS.
2 Search for Daikin Residential Controller.
3 Follow the directions on the screen to install.
Installer reference guide
22
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

6 Unit installation

In this chapter
6.1 Preparing the installation site ................................................................................................................................................ 23
6.1.1 Installation site requirements of the indoor unit .................................................................................................. 23
6.2 Opening the indoor unit ......................................................................................................................................................... 24
6.2.1 To remove the front panel ..................................................................................................................................... 24
6.2.2 To open the service cover ...................................................................................................................................... 25
6.2.3 To remove the front grille ...................................................................................................................................... 25
6.3 Mounting the indoor unit....................................................................................................................................................... 26
6.3.1 To install the mounting plate ................................................................................................................................. 26
6.3.2 To drill a wall hole .................................................................................................................................................. 27
6.3.3 To remove the pipe port cover .............................................................................................................................. 28
6.4 Connecting the drain piping ................................................................................................................................................... 28
6.4.1 General guidelines.................................................................................................................................................. 28
6.4.2 To connect the piping on right side, right-back, or right-bottom ......................................................................... 29
6.4.3 To connect the piping on left side, left-back, or left-bottom................................................................................ 30
6.4.4 To check for water leaks ........................................................................................................................................ 31

6.1 Preparing the installation site

6 | Unit installation
Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit MUST be covered.
Choose an installation location with sufficient space for carrying the unit in and out of the site.
WARNING
The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

6.1.1 Installation site requirements of the indoor unit

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
INFORMATION
The sound pressure level is less than 70dBA.
Air flow. Make sure nothing blocks the air flow.
Drainage. Make sure condensation water can be evacuated properly.
Wall insulation. When conditions in the wall exceed 30°C and a relative humidity
of 80%, or when fresh air is inducted into the wall, then additional insulation is required (minimum 10mm thickness, polyethylene foam).
Wall strength. Check whether the wall or the floor is strong enough to support
the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit.
Installer reference guide
23
6 | Unit installation
≥50
≥50
≥30
(mm)
Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 3 metres may NOT be sufficient.
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
Fluorescent lights. When installing a wireless user interface in a room with
fluorescent lights, mind the following to avoid interference:
- Install the wireless user interface as close as possible to the indoor unit.
- Install the indoor unit as far as possible from the fluorescent lights.
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:
Where the voltage fluctuates a lot
In vehicles or vessels
Where acidic or alkaline vapour is present
In places where a mineral oil mist, spray or vapour may be present in the
atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
In places where the unit would be in the path of direct sunlight.
In bathrooms.
Sound sensitive areas (e.g. near a bedroom), so that the operation noise will
cause no trouble.
WARNING
Do NOT place objects below the indoor and/or outdoor unit that may get wet. Otherwise condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, and objects under the unit may get dirty or damaged.
Spacing. Install the unit at least 1.8 m from the floor and keep the following
requirements in mind for distances from the walls and the ceiling:

6.2 Opening the indoor unit

6.2.1 To remove the front panel

Installer reference guide
24
1 Hold the front panel by the panel tabs on both sides and open it.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
2 Remove the front panel by sliding it to the left or the right and pulling it
a
a b
1
2
3 4
toward you.
Result: The front panel shaft on 1 side will be disconnected.
3 Disconnect the front panel shaft on the other side in the same manner.

6.2.2 To open the service cover

1 Remove 1 screw from the service cover.
2 Pull out the service cover horizontally away from the unit.
6 | Unit installation
a Front panel shaft

6.2.3 To remove the front grille

1 Remove the front panel to remove the air filter.
2 For class 50~71 remove the flap (horizontal blade). Push the blade on its left
side to the centre and unhook it. Push blade on its right side to centre to unhook it from shaft. Disconnect the 2 centre connection points.
a Service cover screw b Service cover
NOTICE
When closing the service cover, make sure that the tightening torque does NOT exceed 1.4(±0.2)N•m.
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
3 Remove 2 screws (class 15~42) or 3 screws (class 50~71) from the front grille.
4 Push down the 3 upper hooks marked with a symbol with 3 circles.
Installer reference guide
25
6 | Unit installation
b
a
a
1
2
a Upper hook
b Symbol with 3 circles
5 We recommend opening the flap before removing the front grille.
6 Place both hands under the centre of the front grille, push it up and then
toward you.

6.3 Mounting the indoor unit

In this chapter
6.3.1 To install the mounting plate ................................................................................................................................. 26
6.3.2 To drill a wall hole .................................................................................................................................................. 27
6.3.3 To remove the pipe port cover .............................................................................................................................. 28

6.3.1 To install the mounting plate

1 Install the mounting plate temporarily.
2 Level the mounting plate.
3 Mark the centres of the drilling points on the wall using a tape measure.
Position the end of tape measure at symbol " ".
4 Finish the installation by securing the mounting plate on the wall using
M4×25L screws (field supply).
Class 15~42 Class 50~71
Installer reference guide
26
INFORMATION
The removed pipe port cover can be kept in the mounting plate pocket.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
6 | Unit installation
169
279
377.5
778
A
295
44.5
160
53
53
44.5
120
120
293.5
50
170
A
d
e
(mm)
a
a
f
h g
a
a
bac
a
c
a
d
e
A
A
998
299
170
60
170
52
52
120.5
130
53
65
469
475
PIPING HOLE CENTER:170mm TO THE LEFT
PIPING HOLE CENTER:170mm TO THE LEFT
(mm)
A
PIPING HOLE CENTER:170mm TO THE LEFT
PIPING HOLE CENTER:170mm TO THE LEFT
e
d
e
d
b
a
c
a
c
a
a
gh
f
a
B
A For class: 15~42
B For class: 50~71 a Recommended mounting plate fixing spots f Position for the tape measure at symbol " " b Pocket for the pipe port cover g Gas pipe end
c Tabs for placing a spirit level h Liquid pipe end
d Through-the-wall hole: e Drain hose position
Class 15~42 Ø65 mm Class 50~71 Ø80 mm

6.3.2 To drill a wall hole

CAUTION
For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
1 Bore a 65mm (class 15~42) or 80mm (class 50~71) large feed-through hole in
2 Insert a wall embedded pipe into the hole.
3 Insert a wall cover into the wall pipe.
NOTICE
Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.
the wall with a downward slope towards the outside.
Installer reference guide
27
6 | Unit installation
Ø65/80
a
b
c

6.3.3 To remove the pipe port cover

a Wall embedded pipe
b Putty
c Wall hole cover
4 After completing wiring, refrigerant piping and drain piping, do NOT forget to
seal the gap with putty.
To connect the piping on right-side, right-bottom, left-side or left-bottom, the pipe port cover MUST be removed.
1 Cut off the pipe port cover from inside the front grille using a coping saw.
2 Remove any burrs along the cut section using a half round needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this would damage the front grille.

6.4 Connecting the drain piping

In this chapter
6.4.1 General guidelines.................................................................................................................................................. 28
6.4.2 To connect the piping on right side, right-back, or right-bottom ......................................................................... 29
6.4.3 To connect the piping on left side, left-back, or left-bottom................................................................................ 30
6.4.4 To check for water leaks ........................................................................................................................................ 31

6.4.1 General guidelines

Pipe length. Keep drain piping as short as possible.
Pipe size. If drain hose extension or embedded drain piping is required, use
appropriate parts that match the hose front end.
Installer reference guide
28
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
6 | Unit installation
Ø16
Ø18
a
a
b c
Ø16
Ø16
a b c
Ø18
≥50
mm
NOTICE
Install the drain hose with a downward slope.Traps are NOT permitted.Do NOT put the end of the hose in water.
Drain hose extension. To extend the drain hose, use a field supplied hose with
inner Ø16mm. Do NOT forget to use a heat insulation tube on the indoor section of the extension hose.
a Drain hose supplied with the indoor unit b Heat insulation tube (field supply) c Extension drain hose
Rigid polyvinyl chloride pipe. When connecting a rigid polyvinyl chloride pipe
(nominal Ø13mm) directly to the drain hose as with embedded piping work, use a field supplied drain socket (nominal Ø13mm).
a Drain hose supplied with the indoor unit b Drain socket with nominal Ø13mm (field supply) c Rigid polyvinyl chloride pipe (field supply)
Condensation. Take measures against condensation. Insulate the complete drain
piping in the building.
1 Insert the drain hose in the drain pipe as shown in the following figure, so it
will NOT be pulled out of the drain pipe.

6.4.2 To connect the piping on right side, right-back, or right-bottom

INFORMATION
The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
Installer reference guide
29
6 | Unit installation
A
B
C
a
b
a
a
b
a
b

6.4.3 To connect the piping on left side, left-back, or left-bottom

1 Attach the drain hose with adhesive vinyl tape to the bottom of the
refrigerant pipes.
2 Wrap the drain hose and the refrigerant pipes together using insulation tape.
A Right-side piping B Right-bottom piping
C Right-back piping
a Remove the pipe port cover here for right side piping
b Remove the pipe port cover here for right-bottom piping
INFORMATION
The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.
1 Remove the insulation fixing screw on the right side and remove the drain
hose.
2 Remove the drain plug on the left side and attach it to the right side.
NOTICE
Do NOT apply lubricating oil (refrigerant oil) to the drain plug when inserting it. The drain plug may deteriorate and cause drain leakage from the plug.
a 4mm hexagonal wrench
3 Insert the drain hose on the left side and do not forget to tighten it with the
fixing screw; otherwise water leakage may occur.
a Insulation fixing screw
b Drain hose
4 Attach the drain hose to the refrigerant piping bottom side using adhesive
vinyl tape.
Installer reference guide
30
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
A
B
C
b
a

6.4.4 To check for water leaks

1 Remove the air filters.
2 Gradually pour approximately 1 l of water in the drain pan, and check for
water leaks.
6 | Unit installation
A Left-side piping B Left-back piping C Left-bottom piping
a Remove the pipe port cover here for left-side piping
b Remove the pipe port cover here for left-bottom piping
Installer reference guide
31
7 | Piping installation
t
Ø

7 Piping installation

In this chapter

7.1 Preparing refrigerant piping

7.1.1 Refrigerant piping requirements

7.1 Preparing refrigerant piping................................................................................................................................................... 32
7.1.1 Refrigerant piping requirements ........................................................................................................................... 32
7.1.2 Refrigerant piping insulation.................................................................................................................................. 33
7.2 Connecting the refrigerant piping.......................................................................................................................................... 33
7.2.1 About connecting the refrigerant piping ............................................................................................................... 33
7.2.2 Precautions when connecting the refrigerant piping............................................................................................ 34
7.2.3 Guidelines when connecting the refrigerant piping.............................................................................................. 35
7.2.4 Pipe bending guidelines ......................................................................................................................................... 35
7.2.5 To flare the pipe end .............................................................................................................................................. 35
7.2.6 To connect the refrigerant piping to the indoor unit ............................................................................................ 36
INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Foreign materials inside pipes (including oils for fabrication) must be
≤30mg/10m.
Refrigerant piping diameter
Use the same diameters as the connections on the outdoor units:
15~42 Ø6.4 Ø9.5
50~60 Ø6.4 Ø12.7
Refrigerant piping material
Piping material: Phosphoric acid deoxidised seamless copper.
Flare connections: Only use annealed material.
Piping temper grade and thickness:
Outer diameter (Ø) Temper grade Thickness (t)
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.
Class Pipe outer diameter (mm)
Liquid pipe Gas pipe
71 Ø6.4 Ø15.9
(a)
6.4mm (1/4") Annealed (O) ≥0.8mm
9.5mm (3/8")
12.7mm (1/2")
15.9mm (5/8")
Installer reference guide
32
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
(a)
ØiØ
i
t
ØpØ
p
Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.

7.1.2 Refrigerant piping insulation

Use polyethylene foam as insulation material:
- with a heat transfer rate between 0.041 and 0.052 W/mK (0.035 and
0.045kcal/mh°C)
- with a heat resistance of at least 120°C
Insulation thickness
7 | Piping installation
Pipe outer diameter (Øp) Insulation inner diameter
6.4mm (1/4") 8~10mm ≥10mm
9.5mm (3/8") 10~14mm ≥13mm
12.7mm (1/2") 14~16mm ≥13mm
15.9mm (5/8") 16~20mm ≥13mm
If the temperature is higher than 30°C and the humidity is higher than RH80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.

7.2 Connecting the refrigerant piping

7.2.1 About connecting the refrigerant piping

Before connecting the refrigerant piping
Insulation thickness (t)
(Øi)
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the indoor unit
Connecting the refrigerant piping to the outdoor unit
Insulating the refrigerant piping
Keeping in mind the guidelines for:
- Pipe bending
- Flaring pipe ends
- Using the stop valves
Installer reference guide
33
7 | Piping installation

7.2.2 Precautions when connecting the refrigerant piping

INFORMATION
Also read the precautions and requirements in the following chapters:
General safety precautionsPreparation
DANGER: RISK OF BURNING/SCALDING
CAUTION
Use the flare nut fixed to the unit.To prevent gas leakage, apply refrigeration oil only to the inside of the flare. Use
refrigeration oil for R32.
Do NOT reuse joints.
CAUTION
Do NOT use mineral oil on flared part.NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material
may dissolve and damage the system.
NOTICE
Take the following precautions on refrigerant piping into account:
Avoid anything but the designated refrigerant to get mixed into the refrigerant
cycle (e.g. air).
Only use R32 when adding refrigerant.Only use installation tools (e.g. manifold gauge set) that are exclusively used for
R32 installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
Install the piping so that the flare is NOT subjected to mechanical stress.Protect the piping as described in the following table to prevent dirt, liquid or
dust from entering the piping.
Use caution when passing copper tubes through walls (see figure below).
Unit Installation period Protection method
Outdoor unit >1month Pinch the pipe
<1month Pinch or tape the pipe
Installer reference guide
34
Indoor unit Regardless of the period
INFORMATION
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

7.2.3 Guidelines when connecting the refrigerant piping

a
b
c
d
R=
0.4~0.8
±2
45°
90°
±2
ØA
a b
Take the following guidelines into account when connecting pipes:
Coat the flare inner surface with ether oil or ester oil when connecting a flare
nut. Tighten 3 or 4 turns by hand, before tightening firmly.
ALWAYS use 2 wrenches together when loosening a flare nut.
ALWAYS use a spanner and torque wrench together to tighten the flare nut when
connecting the piping. This to prevent nut cracking and leaks.
a Torque wrench
b Spanner
c Piping union
d Flare nut
Piping size (mm) Tightening torque
(N•m)
7 | Piping installation
Flare dimensions
(A) (mm)
Flare shape (mm)
Ø6.4 15~17 8.7~9.1
Ø9.5 33~39 12.8~13.2
Ø12.7 50~60 16.2~16.6
Ø15.9 62~75 19.3~19.7

7.2.4 Pipe bending guidelines

Use a pipe bender for bending. All pipe bends should be as gentle as possible (bending radius should be 30~40 mm or larger).

7.2.5 To flare the pipe end

1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing down so that the chips do NOT enter
the pipe.
CAUTION
Incomplete flaring may cause refrigerant gas leakage.Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.Use flare nuts that are included with the unit. Using different flare nuts may
cause refrigerant gas leakage.
a Cut exactly at right angles.
b Remove burrs.
3 Remove the flare nut from the stop valve and put the flare nut on the pipe.
Installer reference guide
35
7 | Piping installation
A
a b
c
c
a
b
f
d
g
e
4 Flare the pipe. Set exactly at the position as shown in the following figure.
Flare tool for R32
(clutch type)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
5 Check that the flaring is properly made.
a Flare’s inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.

7.2.6 To connect the refrigerant piping to the indoor unit

WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
Pipe length. Keep refrigerant piping as short as possible.
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
1 Connect refrigerant piping to the unit using flare connections.
2 Insulate the refrigerant piping, interconnection cable and drain hose on the
indoor unit as follows:
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Liquid pipe
e Liquid pipe insulation
f Finishing tape
g Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause condensation.
Installer reference guide
36
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

8 Electrical installation

In this chapter
8.1 About connecting the electrical wiring .................................................................................................................................. 37
8.1.1 Precautions when connecting the electrical wiring .............................................................................................. 37
8.1.2 Guidelines when connecting the electrical wiring ................................................................................................ 38
8.1.3 Specifications of standard wiring components ..................................................................................................... 39
8.2 To connect the electrical wiring to the indoor unit ............................................................................................................... 39

8.1 About connecting the electrical wiring

Before connecting the electrical wiring
Make sure:
The refrigerant piping is connected and checked
The water piping is connected
Typical workflow
8 | Electrical installation
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the electrical
specifications of the units.
2 Connecting the electrical wiring to the outdoor unit. 3 Connecting the electrical wiring to the indoor unit. 4 Connecting the main power supply.

8.1.1 Precautions when connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION
INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
INFORMATION
Also read "8.1.3Specifications of standard wiring components"[439].
WARNING
All wiring MUST be performed by an authorised electrician and MUST comply
with the applicable legislation.
Make electrical connections to the fixed wiring.All components procured on-site and all electrical construction MUST comply
with the applicable legislation.
Installer reference guide
37
8 | Electrical installation
b a
WARNING
If the power supply has a missing or wrong N-phase, equipment might break
down.
Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber,
or telephone earth. Incomplete earthing may cause electrical shock.
Install the required fuses or circuit breakers.Secure the electrical wiring with cable ties so that the cables do NOT come in
contact with sharp edges or piping, particularly on the high-pressure side.
Do NOT use taped wires, stranded conductor wires, extension cords, or
connections from a star system. They can cause overheating, electrical shock or fire.
Do NOT install a phase advancing capacitor, because this unit is equipped with an
inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps that provide full disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.
WARNING
Do NOT use locally purchased electrical parts inside the product.Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

8.1.2 Guidelines when connecting the electrical wiring

Keep the following in mind:
Installer reference guide
38
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.
a Stranded conductor wire
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
b Round crimp-style terminal
c b
c
aa
A
AA´
c b ba c
a
B
B
1-3
d
c
b
a
Use the following methods for installing wires:
Wire type Installation method
Single-core wire
a Curled single-core wire
b Screw
c Flat washer
Stranded conductor wire with round crimp-style terminal
a Terminal
8 | Electrical installation
b Screw
c Flat washer
O Allowed
X NOT allowed
The earth wire between the wire retainer and the terminal must be longer than
the other wires.

8.1.3 Specifications of standard wiring components

Component
Interconnection cable (indoor↔outdoor) 4-core cable 1.5mm²~2.5mm²
andapplicable for 220~240V

8.2 To connect the electrical wiring to the indoor unit

H05RN-F (60245 IEC 57)
Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.
1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a
guide.
a Mounting plate (accessory)
b Piece of packing material
Installer reference guide
39
8 | Electrical installation
a
b
c
c Interconnection cable d Wire guide
INFORMATION
Support the unit using a piece of packing material.
2 Open the front panel, and then the service cover. Refer to "6.2Opening the
indoor unit"[424].
3 Pass the interconnection cable from the outdoor unit through the feed-
through wall hole, through the back of the indoor unit and through the front side.
Note: In case the interconnection cable was stripped in advance, cover the ends with insulating tape.
4 Bend the end of the cable up.
NOTICE
Be sure to keep the power line and transmission line apart from each other.
Transmission wiring and power supply wiring may cross, but may NOT run parallel.
In order to avoid any electrical interference the distance between both wirings
should ALWAYS be at least 50mm.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
a Terminal block b Electrical component block c Cable clamp
5 Strip the wire ends approximately 15mm.
Installer reference guide
40
6 Match wire colours with terminal numbers on the indoor unit terminal blocks
and firmly screw the wires to the corresponding terminals.
7 Connect the earth wire to the corresponding terminal.
8 Firmly fix the wires with the terminal screws.
9 Pull the wires to make sure that they are securely attached, then retain the
wires with the wire retainer.
10 Shape the wires so that the service cover fits securely, then close the service
cover.
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
8 | Electrical installation
Installer reference guide
41
9 | Finishing the indoor unit installation
d
e
c
bfa
a b
c c d e

9 Finishing the indoor unit installation

9.1 To insulate the drain piping, refrigerant piping and interconnection cable

1 After the drain piping, refrigerant piping and the electrical wiring are finished.
Wrap refrigerant pipes, interconnection cable and drain hose together using insulation tape. Overlap at least half the width of the tape with each turn.
a Drain hose b Interconnection cable c Mounting plate (accessory) d Refrigerant piping e Indoor unit fixing screw M4×12L (accessory)
f Bottom frame

9.2 To pass the pipes through the wall hole

1 Shape the refrigerant pipes along the pipe path marking on the mounting
plate.
a Drain hose b Caulk this hole with putty or caulking material c Adhesive vinyl tape d Insulation tape e Mounting plate (accessory)
NOTICE
Do NOT bend refrigerant pipes.Do NOT push the refrigerant pipes onto the bottom frame or the front grille.
Installer reference guide
42
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
9 | Finishing the indoor unit installation
2 Pass the drain hose and refrigerant pipes through the wall hole.

9.3 To fix the unit on the mounting plate

1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a
guide.
2 Press the bottom frame of the unit with both hands to set it on the bottom
hooks of the mounting plate. Make sure that the wires do NOT get squeezed anywhere.
Note: Take care that the interconnection cable does NOT get caught in the indoor unit.
3 Press the bottom edge of the indoor unit with both hands until it is firmly
caught by the mounting plate hooks.
4 Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws
M4×12L (accessory).

9.4 To close the indoor unit

9.4.1 To re-install the front grille

1 Install the front grille and firmly engage the 3 upper hooks.
2 Install 2 screws (class 15~42) or 3 screws (class 50~71) back on the front grille.
3 For class 50~71 re-install the lower flap (horizontal blade). Connect the 2
centre connection points. Hook the right side of the blade to the shaft. Hook the blade on its left side.
4 Install the air filter, mount the front panel and close it.

9.4.2 To close the service cover

1 Place the service cover to its original place on the unit.
2 Install 1 screw back on the service cover.
NOTICE
When closing the service cover, make sure that the tightening torque does NOT exceed 1.4(±0.2)N•m.

9.4.3 To re-install the front panel

1 Attach the front panel. Align the shafts with the slots and push them all the
way in.
2 Close the front panel slowly; press at both sides and at the centre.
Installer reference guide
43
9 | Finishing the indoor unit installation
Installer reference guide
44
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

10 Configuration

a
ON/ OFF
b
a

10.1 To set a different address

In case 2 indoor units are installed in 1 room, different addresses for 2 user interfaces can be set.
1 Remove the cover and the batteries from the user interface.
2 Cut the address jumper J4.
10 | Configuration
a Address jumper J4
NOTICE
Be careful NOT to damage any of the surrounding parts when cutting the address jumper.
3 Turn the power supply on.
4 Press and simultaneously.
5 Press , select and press .
Result: The operation lamp will start to blink.
a Operation lamp
b Indoor unit ON/OFF switch
6 Press the indoor unit ON/OFF switch while the operation lamp is blinking.
Address jumper Address
Factory setting 1
After cutting with nippers 2
Installer reference guide
45
10 | Configuration
INFORMATION
If the setting could NOT be completed while the operation lamp was blinking, repeat the setting process from the beginning.
7 When the setting is complete, keep pressed for at least 5seconds.
Result: The user interface will return to the previous screen.
Installer reference guide
46
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

11 Commissioning

11.1 Overview: Commissioning

Typical workflow
Commissioning typically consists of the following stages:
1 Checking the "Checklist before commissioning". 2 Performing a test run for the system.

11.2 Checklist before commissioning

After the installation of the unit, first check the items listed below. Once all checks are fulfilled, the unit must be closed. Power-up the unit after it is closed.
You read the complete installation instructions, as described in the installer reference guide.
The indoor units are properly mounted.
11 | Commissioning
The outdoor unit is properly mounted.
Air inlet/outlet
Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets, cardboard, or any other material.
There are NO missing phases or reversed phases.
The refrigerant pipes (gas and liquid) are thermally insulated.
Drainage
Make sure drainage flows smoothly.
Possible consequence: Condensate water might drip.
The system is properly earthed and the earth terminals are tightened.
The fuses or locally installed protection devices are installed according to this document, and have NOT been bypassed.
The power supply voltage matches the voltage on the identification label of the unit.
The specified wires are used for the interconnection cable.
The indoor unit receives the signals of the user interface.
There are NO loose connections or damaged electrical components in the switchbox.
The insulation resistance of the compressor is OK.
There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units.
There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are properly insulated.
The stop valves (gas and liquid) on the outdoor unit are fully open.
Installer reference guide
47
11 | Commissioning

11.3 To perform a test run

11.3.1 To perform a test run using the user interface

Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating mode.
Prerequisite: Test run should be performed in accordance with the operation
manual of the indoor unit to make sure that all functions and parts are working properly.
1 In cooling mode, select the lowest programmable temperature. In heating
mode, select the highest programmable temperature. Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal level. In cooling
mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3minutes after the unit is turned OFF.
1 Press to switch the system on.
2 Press and simultaneously.
3 Press , select and press .
Result: Test run operation will stop automatically after about 30minutes.
4 To stop operation sooner, press .
Installer reference guide
48
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

12 Hand-over to the user

Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
Make sure that the user has the printed documentation and ask him/her to keep
it for future reference. Inform the user that he can find the complete documentation at the URL mentioned earlier in this manual.
Explain the user how to properly operate the system and what to do in case of
problems.
Show the user what to do for the maintenance of the unit.
12 | Hand-over to the user
Installer reference guide
49
13 | Disposal

13 Disposal

NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
Installer reference guide
50
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06

14 Technical data

,
A
INDOOR
OUTDOOR
A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
The full set of latest technical data is available on the Daikin Business Portal
(authentication required).

14.1 Wiring diagram

14.1.1 Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*" in the part code.
Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
14 | Technical data
Connection Protective earth (screw)
Connector
Rectifier
Earth Relay connector
Field wiring Short-circuit connector
Fuse Terminal
Indoor unit Terminal strip
Outdoor unit Wire clamp
Residual current device
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
YLW Yellow
Symbol Meaning
A*P Printed circuit board
BS* Pushbutton ON/OFF, operation switch
BZ, H*O Buzzer
C* Capacitor
Installer reference guide
51
14 | Technical data
Symbol Meaning
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*,
Connection, connector MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE
D*, V*D Diode
DB* Diode bridge
DS* DIP switch
E*H Heater
FU*, F*U, (for characteristics, refer to
Fuse PCB inside your unit)
FG* Connector (frame ground)
H* Harness
H*P, LED*, V*L Pilot lamp, light emitting diode
HAP Light emitting diode (service monitor
green)
HIGH VOLTAGE High voltage
IES Intelligent eye sensor
IPM* Intelligent power module
K*R, KCR, KFR, KHuR, K*M Magnetic relay
L Live
L* Coil
L*R Reactor
M* Stepper motor
M*C Compressor motor
M*F Fan motor
M*P Drain pump motor
M*S Swing motor
MR*, MRCW*, MRM*, MRN* Magnetic relay
N Neutral
n=*, N=* Number of passes through ferrite core
PAM Pulse-amplitude modulation
PCB* Printed circuit board
PM* Power module
PS Switching power supply
Installer reference guide
52
PTC* PTC thermistor
Q* Insulated gate bipolar transistor (IGBT )
Q*C Circuit breaker
Q*DI, KLM Earth leak circuit breaker
Q*L Overload protector
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
14 | Technical data
Symbol Meaning
Q*M Thermo switch
Q*R Residual current device
R* Resistor
R*T Thermistor
RC Receiver
S*C Limit switch
S*L Float switch
S*NG Refrigerant leak detector
S*NPH Pressure sensor (high)
S*NPL Pressure sensor (low)
S*PH, HPS* Pressure switch (high)
S*PL Pressure switch (low)
S*T Thermostat
S*RH Humidity sensor
S*W, SW* Operation switch
SA*, F1S Surge arrester
SR*, WLU Signal receiver
SS* Selector switch
SHEET METAL Terminal strip fixed plate
T*R Transformer
TC, TRC Transmitter
V*, R*V Varistor
V*R Diode bridge, Insulated-gate bipolar
transistor (IGBT) power module
WRC Wireless remote controller
X* Terminal
X*M Terminal strip (block)
Y*E Electronic expansion valve coil
Y*R, Y*S Reversing solenoid valve coil
Z*C Ferrite core
ZF, Z*F Noise filter
Installer reference guide
53
15 | Glossary

15 Glossary

Dealer
Sales distributor for the product.
Authorised installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply
Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Installer reference guide
54
Daikin room air conditioner
ATXM50R2V1B
4P518023-8G – 2020.06
DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş.
İSTANBUL / TÜRKİYE Tel: 0216 453 27 00 Faks: 0216 671 06 00 Çağrı Merkezi: 444 999 0 Web: www.daikin.com.tr
G
ülsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe
Copyright 2020 Daikin
Verantwortung für Energie und Umwelt
4P518023-8G 2020.06
Loading...