Daewoo DSA-099L, DSA-189L, DSA-129L Service Manual

Manual de servicio
Split Acondicionador de Aire
Modelo :
CONTENTS
PP
11
Service and Maintenance ..........................................................2
Exploded views and part list .....................................................17
Disassembly and reassembly ....................................................9
Block diagram ..........................................................................27
Controls specification ........................................................ ........4
Troubleshooting ........................................................................15
Wiring diagram .........................................................................26
1
1
3
3
2
2
1
1
3
3
2
2
Air Conditioner no use for a long time.
Start fan only for 3-4 hours to comple­tely dry the inside of the indoor unit. Set COOL mode or HEAT mode, and select the highest setting tempera­ture, then fan turns.
Turn off air conditioner, unplug the power plug. Otherwise, the accumul­ated dirt may cause fire.
FAN OPERA
TION
Take the batteries out of the remote controller.
Want to use the Air Conditioner
Clean filters and replace them to origi­nal position.Clean indoor unit with soft
cloth. Do not use gasoline, benzene, thinner, grinding powder, detergent,insecticide etc. to clean units as they can hurt the units.
Inlets and outlets of indoor and outdo­or units shall not be covered/blocked.
Ground wire shall not be loose. Put in batteries, and plug the power plug.
SERVICE AND MAINTENANCE
22
33
11
1
4
4
3
3
2
2
1
1
4
4
3
3
2
2
Filters should be cleaned once every two weeks.
Take out filters.
Clean filters with a vacuum cleaner or by typing them gently. ( If they are very dirty, wash them in warm water below 45 dissolved with neutral scouring agent.)
Clean filters with clean water, then dry them in cool air.
Insert them at original position, then push down and close front panel.
Clean deodorization filters and air cleaner.
Take out filters first, then take out deodorization filter and air cleaner.
Clean deodorization filter, air clean­er with warm water below 45 dissolved with neutral scouring agent.
Clean filters with clean water, then dry them in cool air.
Insert them at original position, then push down and close front panel.
Deodorization filter, Air cleaner, Filters must be cleaned termly. Open front panel only after air conditioner stops completely.
C
C
SERVICE AND MAINTENANCE
CONTROLS SPECIFICATION
1
1
2
2
ABBREVIATION
Ts: Setting Temperature Tr: Room Temperature Ti: Indoor defrost sensor temperature To: Outdoor defrost sensor temperature
OPERATION OF MAIN BOARD
COOL MODE
If Tr > Ts, cool operation is activated. Compressor and outdoor fan are turned on. Indoor fan runs at the set speed.
If Tr Ts-1 cool operation is terminated. Compressor and outdoor fan are
turned off.
The range of Ts is 16-31
Indoor fan speed can be adjusted for low, medium, high and auto.Compressor will be delayed for 3 minutes before it is turned on or off.
C
C
Indoor de-ice
This process is checked by the indoor defrost sensor (Ti). If Ti =2 , indoor fan increase to high speed, when Ti -1 for 1 minute continuously, compressor and outdoor fan are turn off , indoor fan increases to high speed . When Ti 8 for 5 minutes continuously, compressor and outdoor are turn on. de-ice operation is on for more than 8 minutes, system will return to normal operation.
C
C
AUTO CHANGEOVER MODE
Per Room
Temperature (RT)
Cooling only type
Mode
PRE-SET Temperature PRE-SET Temperature
Mode
24
26
RT-2
RT-2
Cool Cool
Dry RT-2
RT-2
Dry
Heat
Heat pump type
above 26
25-26
23-25
below 23
C
24
C C
C
C
C
C
FAN MODE
Indoor fan runs at the set speed while compressor and outdoor fan are turned off.
Indoor fan speed can be adjusted for low, medium and high.
When this mode is selected, the system will change from AUTO COOL to AUTO DRY to AUTO HEAT mode according to the room temperature and will run according to the programmed temperature set points as in the following table. If the unit is restarted after it is stopped for less than 2 hours, it will resume at the previously established mode before it was stopped. (i.e. AUTO COOL or AUTO DRY or AUTO HEAT) If the unit is restarted after it is stopped for more than 2 hours, it will run in a new mode according to the room temperature when it is restarted. During this mode the temperature set point can only be set + or - 2 Deg. C of the room temperature.
C
44
C C
Outdoor de-ice
After 40 minutes of continuous heating operation, if To -4 , the outdoor de-ice operation is activated. Compressor is turned off. Indoor fan speed reduces to low speed. After 30 seconds delay, 4 way value and outdoor fan will be turned off, indoor fan reduces to low speed, 15 seconds later, the compressor is turned on and indoor fan turn off for the de-ice operation, if To 15 or 10 minutes has elapsed, the de-ice operation will be terminated. Then, the compressor is turned off. After 30 seconds delay, 4 way valve and outdoor fan are turned on, 15 seconds later, compressor and outdoor fan are turned on for return to normal operation, indoor fan is turned on for return to normal operation also.
C
C
4WV
COMPRESSOR
30S
15S
MAX 10 MINS
HEAT MODE
If Tr < Ts, heat operation is activated. Compressor and outdoor fan are turned on.
If Tr Ts + 1 , heat operation is terminated. Compressor and outdoor fan are turned off.
The range of Ts is 16 - 31 .
Indoor fan speed can be adjusted for low, medium, high and auto.
Compressor will delay for 3 minutes before it is turned on or off.
C
C
Compressor will delay for 3 minutes before it is turned on or off.
HEAT MODE
OPT
-4
15
C
C
DE-ICE
INDOOR FAN
OUTDOOR FAN
30S
15S
DRY MODE
If Tr 15 , dry operation is activated. Compressor and outdoor fan are turned on interval.
C
If Tr 23 , Compressor and outdoor fan are operating in sequence as follows: See A of fig1 If Tr<23 Compressor and outdoor fan are operating in sequence as follows: see B of FIG1.
C
C
Tr 23
Tr 23<
C
C
OUTDOOR FAN
INDOOR FAN
COMPRESSOR
8mins
3mins
4mins
1min
2mins 3mins
8mins
1min
2mins
4mins
1min 1min
Fig.1
A
B
CONTROLS SPECIFICATION
55
TIMER
Timer off can only be set when the system is operating.
Timer on can only be set when the system is off.
The maximum set time is 12 hours.
Changing of on/off state will cancel timer mode.
SLEEP MODE
In cool mode, after sleep mode is set, Ts will increase 1 in first hours, will increase 2 in second hours and will operation as the temperature
In heat mode, after sleep mode is set, Ts will decrease 2 in first hours, will increase 2 in second hours and will operation as the temperature
Changing of operation mode will cancel sleep mode.
C
C
C
C
HEAT MODE COOL MODE
Ts
Ts-1
Ts-2
Ts
Ts+1
Ts+2
1 HR
1 HR
1 HR
Time
C
CONTROLS SPECIFICATION
HIGH PRESSURE PROTECTION
If Ti > 50 , the outdoor fan is turned off. After that, if Ti < 47 , the system will start again.( For 07.09 type)
C C
C
C
Compressor ON Outdoor Fan OFF
Compressor ON Outdoor Fan ON Normal Operation zone
Compressor ON Outdoor Fan OFF (High pressure protection)
Compressor OFF Outdoor Fan OFF (High pressure protection)
Compressor ON Outdoor Fan ON Normal Operation zone
Temp Increasing
Temp decreasing
47
C(07.09)
50 (07.09)
C
63
C
If Ti > 63 , the compressor is turned off. After that, if Ti < 50 , the system will start again.( for 07.09 type)
If Ti > 55 , the outdoor fan is turned off. After that, if Ti < 50 , the system will start again.( For 12.18 type)
C C
50
C(12.18)
55 (12.18)
C
If Ti > 63 , the compressor is turned off. After that, if Ti < 55 , the system will start again.( For12.18 type)
C
C
66
MANUAL SWING (STEPPING MOTOR)
If the indoor fan is operating, the louver will swing or can be stopped at a preferred location in any mode. The louver change location follow the order of :
If a command is received, the system will respond with a beep.
BUZZER
In cool mode, if Tr-Ts < 0 , indoor fan is run at low speed. If 0 <Tr-Ts<2 , if indoor fan is running at low speed, there will be no change in speed , if fan is running at medium speed ,there will be no change in speed ,if indoor fan is run at high speed ,it will change to medium speed. If 2 <Tr-Ts<4 indoor fan keep original speed. If Tr-Ts>4 indoor fan is run at high speed.
AUTO FAN SPEED
C
C
C
C
0
Tr-Ts
HIGH SPEED
MEDIUM SPEED
LOW SPEED
C
2
C
4
C
C
C
In heat mode, if Tr-Ts < 1 , indoor fan is run at low speed. If 1 <Tr-Ts<3 , if indoor fan is run at low speed, there will be no change in speed , if fan run at medium speed ,there will be no change in speed , if indoor fan is run at high speed ,will change to medium Speed. If 3 <Tr-Ts<5 indoor fan keep original speed. If Tr-Ts>5 indoor fan is run at high speed.
C
C
C
C
0
Tr-Ts
HIGH SPEED
MEDIUM SPEED
LOW SPEED
C
2
C
4
C
C
C
CONTROLS SPECIFICATION
77
MANUAL OPERATION BUTTON
3
3
OPERATION OF CONTROL PANEL ON INDOOR UNIT
Every press of this button will turn the system on or off.
SYSTEM LED LIGHT
When system is operating, the RUN light is on. When system is off, the light is off.
(Cool only type) Every time the switch is pressed, it changes in sequence of
COOL STOP.
(Heat pump type) Every time the switch is pressed, it changes in sequence of
COOL HEAT STOP.
MANUAL run operation procedure as the following:
In the first 30 minutes operation, the compressor don't stop ,indoor fan hold high speed. After 30 minutes, emergency run operation start.
Mode
Setting temperature
Deflector
Swing
Swing
HEAT
Fan speed
High
High
COOL
24
C
24
C
When sleep mode is operating, the SLEEP light is on. When sleep mode is off, the light is off. When timer is operating, the TIME light is on. When time is over, the light is off.
CONTROLS SPECIFICATION
88
SELF DIAGNOSIS FUNCTION
Our company provides the end-users with thoughtful services by installing various diagnostic systems to indicate the following irregular performances.
Check code
Diagnosis of malfunction
FAULT F7
FAULT F8
FAULT F9
Indoor TEMP sensor faults
Indoor coil pipe TEMP sensor faults
Outdoor coil pipe TEMP sensor faults
FAULT F6
PG motor faults
Loading...