Your local independently operated Culligan dealer employs trained
service and maintenance personnel who are experienced in the
installation, function and repair of Culligan equipment. This
publication is written specifically for these individuals and is intended
for their use.
We encourage Culligan users to learn about Culligan products, but
we believe that product knowledge is best obtained by consulting
with your Culligan dealer. Untrained individuals who use this manual
assume the risk of any resulting property damage or personal
injury.
WARNING - Prior to servicing equipment, disconnect
power supply to prevent electrical shock.
This system is not intended to be used for treating water that is
microbiologically unsafe or of unknown quality without
adequate disinfection before or after the system.
Parts List .................................................................20
Introduction
The Culligan® Mark 89 and 812 water softeners are tested and validated by WQA to ANSI/NSF
Standard 44 for the effective reduction of calcium and magnesium (hardness) along with barium
and Radium 226/228*.
SAFE PRACTICES
Throughout this manual there are paragraphs set off by special headings.
NOTICE: Notice is used to emphasize installation, operation or maintenance information which is important, but
does not present any hazard.
Example: NOTICE: The nipple must extend no more than 1 inch above the cover plate.
CAUTION: Caution is used when failure to follow directions could result in damage to equipment or
property. Example:
CAUTION: Disassembly while under water pressure can result in flooding.
WARNING: Warning is used to indicate a hazard which could cause injury or death if ignored. Example:
WARNING! ELECTRICAL SHOCK HAZARD! UNPLUG THE UNIT BEFORE
REMOVING THE TIMER MECHANISM OR COVER PLATES!
SERIAL NUMBERS
The control valve serial number, is on the back of the timer case.
The media tank serial number is on the top edge of the tank side wall.
NOTICE: Do not remove or destroy the serial number. It must be referenced on request for warranty repair or
replacement.
This publication is based on information available when approved for printing. Continuing design refinement
could cause changes that may not be included in this publication.
* Verified utilizing hardness surrogate per ANSI/NSF Standard 44.
2 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Specifications
Culligan® Mark 89 and 812 Water Conditioners with Automatic Time Clock or Soft-Minder® Meter
89 Model812 Model
Control Valve
Overall Conditioner Height51 in51 in
Media Tank Dimensions (Dia x Ht)9 x 45 in12 x 45 in
Salt Storage Tank Dimensions (Dia x Ht)16 x 43 in16 x 43 in
Exchange Media, Type and QuantityCullex
Underbedding, Type and QuantityCullsan® Underbed, 20 lbCullsan Underbed, 30 lb
Exchange Capacity15,400 gr @ 4.0 lb25,000 gr @ 6.0 lb
@ Salt Dosage Per Recharge
Freeboard to Media
2
Freeboard to Underbedding
1
3
Salt Storage Capacity250 lb or 375 lb375 lb
Rated Service Flow @ Pressure Drop7.8 gpm @ 15 psi8.25 gpm @ 15 psi
Total Hardness, Maximum50 gpg75 gpg
Total Iron, Maximum5 ppm5 ppm
Hardness to Iron Ratio, Minimum
4
Operating Pressure20-125 psi20-125 psi
Operating Temperature33-120°F33-120°F
Electrical Requirements120V/60 Hz120V/60 Hz
Electrical Power Consumption, Min/Max3 Watts/35 Watts3 Watts/35 Watts
Drain Flow, Maximum
Recharge Time, Average
5
6
Recharge Water Consumption, Average45 gal/4 lb75 gal/6 lb
998 gr @ 1.8 kg1 620 gr @ 2.7 kg
21,200 gr @ 7.7 lb35,900 gr @ 12.0 lb
1 374 gr @ 3.5 kg2 326 gr @ 5.4 kg
24,200 gr @ 12 lb42,400 gr @ 18.0 lb
1 568 gr @ 5.4 kg2 748 gr @ 8.2 kg
18.9-19.9 in17.5-18.5 in
48-51 cm44-47 cm
39.2 in38.5 in
99.6 cm98 cm
114 kg or 170 kg170 kg
1 300 mg/L1 700 mg/L
5 mg/L5 mg/L
8 gpg to 1 ppm8 gpg to 1 ppm
140 mg/L to 1 mg/L140 mg/L to 1 mg/L
140-860 kPa140-860 kPa
1-50°C1-50°C
2.0 gpm3.5 gpm
7.6 L/pm13.5 L/pm
80 min85 min
170 L/1.8 kg284 L/2.7 kg
1 Capacities and corresponding salt dosages pertain to low hardness waters. Capacities given are per recharge
2 Measured from top of media to top of inlet fitting (backwashed and drained).
3 Measured from top of underbedding to top of inlet fitting.
4 Hardness to iron ratio does not apply and total hardness and iron specifications change as follows when
Sofner-Gard® accessory is used: 89 Model - 50 gpg (855 mg/L) total hardness, 10 ppm (mg/L) iron;
812 Model - 75 gpg (1 200 mg/L) hardness, 20 ppm (20 mg/L) iron.
5 Backwash at 120 psi (830 kPa).
6 10 minute backwash, 7 lb (3.2 kg) 89 model or 13 lb (5.9 kg) 812 model salt dosage.
SPECIFICATIONS 3
Preparation
COMPONENT DESCRIPTION
The water conditioner is shipped from the factory in three cartons. Remove all components from their cartons and
inspect them before starting installation.
Control Valve Assembly - Includes the 5-cycle regeneration control valve and timer assembly. A small parts
package contains installation hardware and consumer literature, including an Owner’s Guide and warranty policy.
Media Tank - Includes Tripl-Hull
media tank complete with Cullex® ion exchange resin, underbedding and
™
outlet manifold.
Salt Storage Tank Assembly - Includes salt storage container with support plate and Dubl-Safe™ brine refill
valve and chamber.
Bypass Valves - The system installation includes a manually operated bypass valve which enables the softener to
be isolated from the water service lines for maintenance and service and also maintain the continuity of the water
supply when the softener is disconnected.
TOOLS AND MATERIALS
The following tools and supplies will be needed, depending on installation method. Observe all applicable codes.
All Installations
• Safety glasses
• Phillips screwdrivers, small and medium tip
• Gauge assembly (PN 00-3044-50 or equivalent)
• Silicone lubricant (PN 00-4715-07 or equivalent) - DO NOT USE PETROLEUM-BASED LUBRICANTS
• A bucket, preferably light-colored
• Towels
Special Tools
• Torch, solder and flux for sweat copper connections
• Threading tools, pipe wrenches and thread sealer for threaded connections.
• Saw, solvent and cement for plastic pipe connections.
Materials
• Brine line, 5/16” (PN 00-3031-28 or equivalent)
• Drain line, 1/2” (PN 00-3030-82, gray, semi-flexible; or PN 00-3319-46, black, semi-rigid; or equivalent)
• Pipe and fittings suited to the type of installation
• Water softener salt (rock, solar or pellet salt formulated specifically for water softeners)
APPLICATION
Water quality - Verify that raw water hardness and iron are within limits. Note the hardness for setting the salt
dosage and recharge frequency.
Pressure - If pressure exceeds 125 psi (860 kPa), install a pressure reducing valve (see materials checklist). On
private water systems, make sure the minimum pressure (the pressure at which the pump starts) is greater than 20
psi (140 kPa). Adjust the pressure switch if necessary.
4 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
CAUTION: The use of a pressure reducing valve may limit the flow of water
in the household.
Temperature - Do not install the unit where it might freeze, or next to a water heater or furnace or in direct
sunlight.
LOCATION
Space requirements - Allow 6-12 inches (15-30 cm) behind the unit for plumbing and drain lines and 4 feet (1.3
metres) above for service access and filling the salt container.
Floor surface - Choose an area with solid, level floor free of bumps or irregularities. Bumps, cracks, stones and
other irregularities can cause the salt storage tank bottom to crack when filled with salt and water.
Drain facilities - Choose a nearby drain that can handle the rated drain flow (floor drain, sink or stand pipe). Refer
to the Drain Line Chart, Table 1 (page 10), for maximum drain line length.
NOTICE: Most codes require an anti-siphon device or airgap. Observe all local plumbing codes and drain
restrictions. The system and installation must comply with all state and local laws and regulations.
Electrical facilities - A 6-foot grounded cord is provided. The customer should provide a 3-prong grounded
receptacle, preferably one not controlled by a switch that can be turned off accidentally. Observe local electrical
codes.
WARNING: ELECTRICAL SHOCK HAZARD! DO NOT REMOVE THE
GROUNDING PRONG! IF THE RECEPTACLE IS DESIGNED ONLY FOR
2-PRONG PLUGS, OBTAIN A 3-PRONG ADAPTER AND GROUND IT
SECURELY TO THE RECEPTACLE. DO NOT USE EXTENSION CORDS.
PREPARATION 5
Installation
PLACEMENT
Refer to Fig. 1.
• Set the media tank on a solid, level surface near water, drain and electrical facilities. Place the outlet (black
coupling) of the tank on the left.
• Set the brine system on a flat, smooth, solid surface as near the media tank as possible.
MOUNT THE CONTROL VALVE
See Fig. 2.
• Remove and discard the protective covers on the tankcouplings.
• Lubricate the o-rings on the tank couplings with silicon lubricant.
• Place the control on the tank couplings and press down firmly.
• Install the u-clamps on both sides of the control and secure with the screws.
PLUMBING CONNECTIONS
Two methods of connecting the water softener to the plumbing system are available. Shipped with each softener
is a Culligan® Cul-Flo-Valv® bypass valve. If local conditions warrant, you may use the sweat adaptor kits,
PN 00-3314-44 or 00-3314-45.
NOTICE: The Soft-Minder® meter cannot be used with the sweat adaptors.
CAUTION: Close the inlet supply line and relieve system pressure before
cutting into the plumbing! Flooding could result!
6 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
FIG. 1
FIG. 3
FIG. 2
CAUTION: When making sweat connections, remove all plastic and rubber
components which contact brass or copper. Damage to these components may
result otherwise.
BYPASS VALVE INSTALLATION - TIME CLOCK UNITS ONLY
The bypass valve connects directly to the backplate of the valve with a pair of screws (Fig. 3). To facilitate this
connection, remove the plate by pulling up on the u-clip on the back of the valve. Lubricate all o-rings with silicon
lubricant.
BYPASS VALVE INSTALLATION - SOFT-MINDER® METER ONLY
The Soft-Minder meter is placed between the bypass valve and the control (Fig. 4). Make sure the meter is on the
outlet port of the control. A pair of elongated bolts are packaged with the meter to hold the bypass valve to the
back plate of the control. Lubricate all o-rings with silicon lubricant.
SWEAT ADAPTOR INSTALLATION
The sweat adaptors use a snap ring to hold them to the backplate of the control valve. The back plate will need to
be removed from the valve for this connection. A pair of snap ring pliers, PN 00-5916-09, are needed for this
connection.
FIG. 4
FIG. 5
INSTALLATION 7
CAUTION: When reinstalling back plate to control valve, make sure the u-clip
fully engages the two bottom holes of the bracket (Fig. 5). Secure bracket from
the top with the two mounting screws provided.
CONNECT THE BRINE LINE
Refer to Fig. 7.
• Measure a length of brine line sufficient to reach from the brine tank to the brine fitting and then add four feet
(1.3 meters). Cut both ends squarely and cleanly.
• Remove the brine valve from the brine tank and remove the white nut and insert. Return float rod to its original
position.
• Slip the white nut over one end of the tubing and press the plastic insert into the end of the tubing. Connect to the
brine valve and tighten nut. (Figure 6)
• Remove white nut and insert from wire tie around drain elbow.
• Slip the white nut over one end of the tubing and press the plastic insert into the end of the tubing. Connect to the
brine connection on the valve and tighten nut.
DRAIN LINE CONNECTION
Refer to Table 1, page 11 under the applicable tank size for drain line length and height limitations, and to Fig. 7.
• Remove 1/2” pipe clamp from end of drain elbow.
• Route a length of 1/2” drain line from the drain elbow to the drain.
• Fasten the drain line to the elbow with the clamp.
• Secure the drain line to the drain to prevent its movement during regeneration. A loop in the end of the tube will
keep it filled with water and will reduce splashing at the beginning of each regeneration.
NOTICE: Observe all plumbing codes. Most codes require an anti-siphon device or air gap at the discharge
point!
FILL THE SALT STORAGE CONTAINER
Fill the salt storage container with water until the level reaches about 1 inch above the salt support plate. Pour salt
into the container. Fill to within a few inches of the top.
FIG. 6
FIG. 7
8 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
SOFT-MINDER® METER CONNECTION
To connect the meter leads, refer to the instructions listed below and the wiring schematic.
• Remove the timer face plate & set it aside.
• Remove the two screws holding the timer cover. Set the timer cover aside.
• Locate the 1/2" hole in the timer plate at the center rear. Remove the plastic plug.
• Slip the meter cable through the hole and toward the circuit board.
• Connect the red wire from the flow meter cable to the common terminal of the lockout switch. Connect the red
wire from the flow meter connection to the normally closed terminal of the lockout switch.
• Connect the flow meter harness to the circuit board. The meter terminal is labeled "METER".
• Locate the strain relief bushing in the parts pack. Place it on the cable at the point of entry to the rear of the
timer plate and push it into the hole.
The Mark 89 and 812 Water Conditioners are designed to perform efficiently on a wide range of water supplies.
Before the unit can be recharged and put into service, several settings must be made.
BACKWASH
Backwash, the first step in the recharge cycle, expands and loosens the resin bed, and flushes away accumulated
turbidity. The backwash interval is preset at the factory for 10 minutes, which is adequate for most water supplies.
It is adjustable, however, from 5 to 30 minutes. It is recommended that backwash last long enough so that the
effluent from the drain line is clear. Backwash too long and water is wasted, not long enough and the tank becomes
fouled with sediment.
If backwash time adjustment is needed, refer to Fig. 8.
• Grasp the front cover by the slots and carefully pull forward to
remove cover. Lay the cover aside in a safe place.
• Loosen screw (A) about 1½ turns. DO NOT loosen screw (B).
• Holding the cam gear (located beneath the backwash dial),
rotate the backwash dial (C) until the desired backwash time
lines up with indicator mark (D).
• Tighten screw (A).
NOTICE: Adjusting the backwash time may cause the salt dosage
setting to change. If the salt dosage needs to be
reset, do not tighten screw (A), and refer to the Salt Dosage
section.
TIME OF RECHARGE
Although the need to recharge is determined by the Soft-Minder
control, time of day the conditioner will actually
recharge can be set on the timer mechanism.
The timer is factory set to recharge about 2:00 a.m., a time when
water usage is at a minimum for most families. If water is drawn
during recharge, hard water will automatically be bypassed to service. If it would be more convenient to have the
water conditioner recharge at a different time of day, the setting may be changed as follows,
referring to Fig. 8.
• Remove the timer cover.
• The position of the peg (H) in relation to the time-of-day dial (J) determines the time when the unit will begin to
recharge.
• Loosen the screw and lift the white time-of-day dial and rotate it until the desired time of recharge is opposite
the peg (H). Please note that whenever the time of recharge is changed, the time-of-day setting may be changed
also.
NOTICE: Whenever the time of recharge is changed the time of day must be reset also.
FIG. 8
TIME OF DAY
Upon completing the installation, the timer must be set to the correct time of day. Time of day must also be reset
after any kind of power interruption, such as that caused by an electrical storm. See Fig. 8.
• Determine the correct time of day.
• Grasp the gear (K) and lift straight up (the white time-of-day dial will lift with it). Rotate the gear until the
correct time of day lines up with the pointer (P). The dial is spring-loaded and will return its position when
released. Make sure the teeth mesh.
10 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Note that the silver half of the time-of-day dial designates the daytime hours, while the black half designates the
night-time hours.
GUEST CYCLE
An extra recharge can be initiated any time extra soft water is required by pushing the Manual Recharge lever (M)
in the direction of the arrow, then releasing. The unit will still recharge at its regular frequency as determined by
the meter device. On models with meter control, the red button (X) must also be pushed briefly before the recharge
cycle can begin.
SERVICE POSITION
The timer assembly is in the service position when the toothless notch in the cam gear is over the teeth on the idler
gear (L). The timer will return to this position after each recharge (Fig. 8).
TIME CLOCK SETTINGS
To set the Mark 89 and 812 water conditioner for optimal performance, determine the hardness of the water along
with the number of people in the household. Refer to Table 2. Locate the row corresponding to the number of
people in the home and move across to the appropriate hardness column. The number in the shaded region is the
salt dosage. The other number is the frequency of regeneration.
SALT DOSAGE
To set the salt dosage, refer to Fig. 8. Loosen screw (A) and rotate outer dial until the salt dosage dial line up with
the indicator mark (D). Tighten screw (A).
TABLE 2A — CULLIGAN MARK 89 WATER CONDITIONER SALT DOSAGE — FREQUENCY
Household(0-120)(121-240)(241-360)(361-480)(481-600)(601-720)(721-840)(841-960)(961-1080) (1081-1280) per day
12 3 33 3 66
2150(570)
9768111299
Water
3225(850)
679137101114
4300(1135)
686811121720
5375(1420)
75710141820
13 36666 6
6450(1705)
85979131820
23 66666
7525(1990)
5658121620
23 6666
8600(2270)
56681320
23 666
9675(2555)
6861116
23 666
10750(2840)
7971220
*In household application, not recommended for over 10 people because of pressure drop limitations.
23 3 36 6 66
33 6 66 6 66
36 6 66 6 6
REGENERATION FREQUENCY
To set the regeneration frequency, push the number of pins in which corresponds to the number located in Table
2 (refer to Fig. 9 and Table 3).
SOFT-MINDER METERING DEVICE
The Mark 89 and 812 Soft-Minder water conditioners are equipped with water meter which regenerates based
upon the water consumption patterns of the household.
TABLE 3 — RECHARGE FREQUENCY
No. Down onPin No. In onRecharge
Salt ChartFrequency DialFrequency
11Every six days
21 & 4Every three days
31, 3 & 5Every other day
6All PinsEvery day
FIG. 9
12 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
GALLONS SETTING
Determine the daily use for the household. Usually 75-100 gallons per day per person is adequate. Using Table 4,
locate the hardness range for your water supply. Move down the column and locate the gallons setting and salt
dosage which best suits the application. Usually two to three days between regenerations yields the best results.
Allow for one half to one days water usage as reserve capacity. Set the salt dosage per the instructions on page 9.
Set the gallons setting on the circuit board. This is done by removing the two screws of the front cover. The circuit
board is located on the upper left hand corner of the back plate. A set of six dip switches on the circuit board
determine the gallons capacity. Refer to Table 5, Figs. 10 and 11 when setting the dip switches. Make sure all
recharge frequency pins are pushed on.
There are two pilot lights located on the circuit board.
•The green pilot light flickers when water is flowing through the water meter.
•The amber pilot light is a latching indicator, when the preset gallons count has passed, the amber light will
illuminate indicating that the unit will regenerate that night.
The softener also has a ten gallon setting to assist the service personnel in trouble shooting the equipment. To
trouble shoot the meter, set the dip switches to the OFF position. Run water into a measured pail. The green light
will flicker. When ten gallons has passed, the amber light will light up. This will help determine if the meter is
properly measuring the gallons count.
TABLE 4A — MARK 89 (0.7FT3) GALLON CAPACITIES TO SIGNAL (RESERVE)
The brine valve contains a float-actuated safety shut-off device to prevent overflow of the brine tank in the un
likely case of an electrical or mechanical failure during the brine tank refill cycle.
It is recommended that the brine valve float be used as intended, that is, as a secondary, safety shutoff. Remember, the timer mechanism provides the primary refill shut-off. To use the float as a safety shut-off, refer to Table 6
for the salt dosage and brine tank size being used. The "A" dimension is the distance between the filter screen and
the bottom of the float (Fig. 12) when the float stem is in its fully raised position; adjust the float and rubber
grommets accordingly.
RAPID RINSE
The rapid rinse time, which is established when setting the salt dosage, is usually adequate for most installations.
It may be increased, if necessary, but it MUST NEVER be reduced from the salt dosage which is required for
adequate regeneration.
To adjust rapid rinse refer to the section on Salt Dosage. Each one-pound increase in salt dosage will increase
rapid rinse time, the brine valve float will become the primary brine refill shutoff. In this case refer to the correct
Table 7 column for the salt dosage and brine tank size being used, and adjust the "A" dimension accordingly.
RUNTEST
SW-1OFFON
FIG. 10
14 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
FIG. 11
TABLE 5 — REGENERATION SCHEDULE
CAPACITYSWITCH POSITION
(GALS.)SW2SW3SW4SW5SW6
10OFFOFFOFFOFFOFF
100ONOFFOFFOFFOFF
200OFFONOFFOFFOFF
300ONONOFFOFFOFF
400OFFOFFONOFFOFF
500ONOFFONOFFOFF
600OFFONONOFFOFF
700ONONONOFFOFF
800OFFOFFOFFONOFF
900ONOFFOFFONOFF
1000OFFONOFFONOFF
1100ONONOFFONOFF
1200OFFOFFONONOFF
1300ONOFFONONOFF
1400OFFONONONOFF
1500ONONONONOFF
1600OFFOFFOFFOFFON
1700ONOFFOFFOFFON
1800OFFONOFFOFFON
1900ONONOFFOFFON
2000OFFOFFONOFFON
2100ONOFFONOFFON
2200OFFONONOFFON
2300ONONONOFFON
2400OFFOFFOFFONON
2500ONOFFOFFONON
2600OFFONOFFONON
2700ONONOFFONON
2800OFFOFFONONON
2900ONOFFONONON
3000OFFONONONON
3100ONONONONON
FIG. 12
TABLE 6 - "A" DIMENSION CHART
160 lb. Brine Tank250 lb. Brine Tank375 lb. Brine Tank
WARNING: FOR PROTECTION, A SANITIZING AGENT HAS BEEN ADDED
TO THE SOFTENER TANK AT THE FACTORY. THIS SANITIZING AGENT
MUST BE FLUSHED OUT BEFORE THE UNIT IS PLACED INTO SERVICE
BY RUNNING AT LEAST 50 GALLONS OF WATER THROUGH THE UNIT
DRAIN.
• Close the main supply valve.
• Set the bypass valve(s) to bypass.
• All faucets in the installation site should be closed.
• Direct the drain line discharge into a bucket where flow can be observed.
• Plug the unit into a 120 Volt, 60 Hertz, single phase grounded, 3-wire receptacle (or 2-wire receptacle with
grounded 3-prong adapter).
• Set the timer to the correct time of day.
• Open the main supply valve.
• On the timer, push the Manual Recharge lever to the left until it stops.
• Slowly shift the Cul-Flo-Valv® bypass toward the "Soft Water" position until water flows. On three-valve
bypass installations, close the bypass valve and open the outlet and inlet valves.
• Allow the unit to fill slowly until water flows from the drain line.
• When flow to drain is established, open the bypass fully. Watch the drain line discharge for signs of resin. If
resin particles appear, reduce the flow. Increase the flow again when resin no longer appears in the discharge.
• When the unit is filled with water, return the timer to the service position.
WARNING: ALTHOUGH NOT NORMALLY NECESSARY, SHOULD YOU NEED
TO DISASSEMBLE ANY PART OF THE CONTROL VALVE OR REMOVE THE
CONTROL FROM THE TANK ASSEMBLY OR ASSOCIATED PLUMBING,
DEPRESSURIZE THE UNIT FIRST CLOSING THE MAIN SUPPLY VALVE,
THEN OPEN A CONVENIENT FAUCET DOWN STREAM FROM THE WATER
CONDITIONER.
During the recharge cycle, hard water will be available to all the lines in the household. Immediately following
recharge, the water to service will be soft.
Because of the volume of water contained in the water heater, the hot water may not be soft for several days. Soft
hot water can be made available almost immediately, however, if the water heater is drained immediately after
recharge and allowed to refill with soft water.
BEFORE LEAVING THE INSTALLATION SITE
Make sure the brine tank is filled with water to the level of the float. Fill the tank with a hose or put the unit into
a full recharge so that the brine refill cycle will fill the tank.
Explain the operation of the softener to the customer. Give the customer a copy of the Owner's Guide and
warranty policy. Make sure the customer knows that there will be new sounds associated with the recharging of
the unit. Advise the customer to periodically check and replenish the salt supply.
Clean up the unit and the installation site, removing any soldering or pipe threading residues from the equipment
with a damp towel.
16 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Appendix A - Sanitizing Instructions
A water softener in daily use on a potable water supply generally requires no special attention other than keeping
the salt tank filled. Occasionally, however, a unit may require sanitation under one of the following conditions:
•The unit has stood idle for a week or more (the premises vacant or the residents on vacation).
•On private supplies, the appearance of off-tastes and odors, particularly if musty or "rotten egg" (caused by
harmless sulfate-reducing bacteria).
For occasional occurrences, the softener can be sanitized with household bleach as follows.
NOTICE: If the water supply contains iron, regenerate the softener before sanitizing to remove accumulated iron
from the Cullex® resin.
WARNING: HAZARD FROM TOXIC FUMES! CHLORINE BLEACH AND
COMMON IRON CONTROL CHEMICALS MAY GENERATE TOXIC FUMES
WHEN MIXED.
•IF THE UNIT USES CULLIGAN® SOFNER-GARD™ CHEMICAL OR OTHER COMPOUNDS
CONTAINING SODIUM HYDROSULFITE OR SODIUM BISULFITE, OR ANY OTHER
REDUCING AGENT, DISCONNECT THE DEVICE AND MANUALLY REGENERATE THE UNIT
BEFORE SANITIZING.
•DO NOT USE THIS PROCEDURE IF THE SOFTENER SALT CONTAINS IRON CONTROL
ADDITIVES.
1.Remove the brine tank cover and the small cover on the brine valve chamber.
2.Pour directly into the brine chamber 1 cup (9-inch units) or 2 cups (12-inch units) of common household
bleach (5-1/4% sodium hypochlorite).
3.Manually start a recharge cycle. Allow the unit to complete the recharge cycle automatically.
If tastes and odors return frequently, even after sanitization, a continuous chlorination system may be needed.
Contact Household Application Engineering for assistance. Also, have the consumer send a sample to a qualified
laboratory for bacterial analysis.
APPENDIX A - SANITIZING INSTRUCTIONS 17
Wiring Schematic
Automatic Clock Timer
18 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Meter
®
Timer with Soft-Minder
WIRING SCHEMATIC 19
Control Valve
20 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Control Valve Parts List
6400-4429-84Power Cord
6500-3318-48Terminal Strip
6600-4442-84Screw
6700-4015-67Clip
6801-0017-84Screw
8000-4429-29Label
8100-4022-01Screw
8301-0128-09Control Cover
8400-4457-80Cover Plate
8501-0046-89Cul-Flo Bracket
8600-3183-83Screw
9900-4452-69Eductor Screen
‡9800-4012-48Eductor w/O-Rings
10200-4432-91Connector Brine Line
‡100 00-3084-38O-Ring
‡101 00-3084-37O-Ring
10300-3031-93Nut, PP, 0.312"
10400-3031-92Insert, PP, 0.312"
‡105 00-4479-87O-Ring
10700-4479-86O-Ring
10800-3084-07O-Ring
‡106 01-0136-06Eductor Sleeve and Eductor Piston Assembly
00-5418-34Float Valve Body with Ball Seat, 150 lb.
Brine Tank
2000-3045-37Brine Valve Chamber, 250 lb. (114 kg) &
375 lb. (170 kg) Salt Storage Tank (US)
00-4413-92Brine Valve Chamber, 160 lb. (Shown)
†Brine Valve Chamber, 350 lb. (159 kg)
(Canadian)
2100-3046-06Cap, Brine Valve Chamber
*00-3184-92Screw, Brine Valve Chamber (Canadian)
#10 - 16 x 1/2-inch TRS HD PHIL
*00-3306-29Connector Spacer, Brine Valve Chamber
(Canadian)
*00-4463-88Screw, St. Steel, Brine Valve Chamber (US)
*00-4463-89Nut, St. Steel, Brine Valve Chamber (US)
* Not Illustrated
† Replace with 00-3045-15 and relocate spacer
‡ Recommended Spare Parts
24 CULLIGAN® MARK 89 AND 812 WATER CONDITIONER
Timer & Parts List
ItemPart No.
00-4429-21Mark 89/812 Timer Replacement
100-4482-57Screw, #4-24 x 0.625" Phil.
200-4031-54Screw, #4-24 x 0.312" Oval Hd.
300-4417-67Adjustment Lever
400-4413-35Dial, Salt Dosage
500-4413-38Dial, Backwash
600-4010-24Cam, Notched
700-4045-02Lever, Manual Regeneration
800-4409-32Spring
900-4413-32Gear, Idler
1000-4409-47Pin, Retainer
1100-4409-28Pin
1200-4409-29Wheel, Interval
1300-4477-96Screw, #4-40 x 0.750" Rd. Hd.
†00-4428-85Screw, #4-40 x 1.625" Lg. Slot
1400-4406-30Washer
1500-4031-39Spring
1600-4409-35O-ring
1700-4414-08Screw, #4-24 x 0.250" Pan Hd.
1800-3354-29Gear, Gray
1900-4409-43Gear, Black
† Used only for Aqua-Sensor
‡ Recommended Spare Parts
* Not Illustrated
Description
®
ItemPart No.Description
2000-4409-40Pointer, Time of day
2101-0013-85Dial, Time of day
2201-0013-84Wheel, Time of Regeneration
2301-0013-86Decal
2400-4409-30Spacer
2500-4409-31Switch, Miniature
2600-4475-72Screw, #4-24 x 0.875" Phil
2700-4421-48Spacer
†28 00-4480-04Spacer
2900-4412-63Spring
3100-4442-99Decal
3200-4010-23Cam, Refill, Backwash
3300-4413-40Cam, Backwash
3401-0017-58Cam, Fast Rinse
†35 00-3183-32Washer
‡†36 00-4416-77Switch, Push Button
3700-4459-38Plate with Inserts
‡38 00-4409-34Motor, Timer
3900-4414-10Screw, #4-40 x 0.250" Pan Hd.
*00-3300-00Kit, Frequency Wheel, 6-Day
*00-3300-01Kit, Frequency Wheel, 7-Day
TIMER PARTS LIST 25
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.