Cornelius COR6519UBCSD Service Manual

®
BOTTLE COOLERS
COR6519UBCSD
Service Manual
Release Date: May, 2004 Publication Number: 630460278SER Revision Date: NA Revision: A Visit the IMI Cornelius web site at www.cornelius.com
SERVICE MANUAL
The products, technical information, and instructions contained in this manual are subject to change without notice. These instructions are not intended to cover all details or varia­tions of the equipment, nor to provide for every possible contingency in the installation, operation or maintenance of this equipment. This manual assumes that the person(s) working on the equipment have been trained and are skilled in working with electrical, plumbing, pneumatic, and mechanical equipment. It is assumed that appropriate safety precautions are taken and that all local safety and construction requirements are being met, in addition to the information contained in this manual.
To inquire about current revisions of this and other documentation or for assistance with any Cornelius product contact:
www.cornelius.com
800-238-3600
Trademarks and copyrights: Aurora, Cornelius, Decade, Hydro Boost, Sitco, Spirit, UF-1, Vanguard, Venture, Olympus,
and Vista are registered trademarks of IMI Cornelius Inc. Optifill trademark is pending.
This document contains proprietary information and it may not be
reproduced in any way without permission from Cornelius.
Printed in U.S.A.
Copyright © 2004, All Rights Reserved, IMI Cornelius, Inc.
COR6519UBCSD Service Manual
TABLE OF CONTENTS
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i
English . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Features of the Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Description of its components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
The Refrigeration Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Cleaning and Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Condensate Disposal System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Possible causes and solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Español . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Caracteristicas del equipo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Sistema de Refrigeracion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Explicación de los componentes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
El Ciclo de Refrigeracion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Diagrama eléctrico . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Limpieza y Mantenimiento Preventivo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Sistema de Recolección de Condensado . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Principales Problemas del Refrigerador . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Posibles causas y soluciones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
© 2004, IMI Cornelius Inc. - i - Publication Number: 630460278SER
COR6519UBCSD Service Manual
Publication Number: 630460278SER - ii - © 2004, IMI Cornelius Inc.
FEATURES OF THE UNIT
Sturdy, stainless steel top
Strong body with thick walls, injected with CFC-free polyurethane foam
Exterior cabinet and lining made of galvanized, pre­painted steel, with baked polyester paint
Reinforced, heavy-duty, adjustable dividers
Interior lining made of acrylic-coated galvanized steel for extra corrosion resistance
Heavy-duty R-134a condensing unit with easy access for maintenance
COR6519UBCSD Service Manual
ENGLISH
Rubber pull handle for easy sliding of lids
Forced-air evaporator for quick temperature pull­down
Reinforced, 16 gauge galvanized steel base
Forced-air condenser made of copper and aluminum, resistant to rust and saline environments
FIGURE 1
R
EFRIGERATION SYSTEM
Description of its components
Compressor:
The compressor is a factory-sealed unit located underneath (outside) the cooling cabinet. This pump is activated by a motor which draws low-pressure vapor (refrigerant) from the evaporator. It then compresses the gas and forces it into the condenser at a high pressure.
Starter relay:
The starter relay is attached on one side of the compressor box. The compressor motor has two windings: one for starting and another for running. In order to provide for necessary additional torque when the motor is first ignited, the starter relay connects the additional start-up windings. After the motor reaches its correct operating speed, the relay opens the ignition windings and the motor carries on with the operation windings.
Thermal protector:
This protector is a thermo-sensible device attached to one side of the compressor’s box. In any given situation, if the compressor overheats or the voltage source varies drastically, the thermal protector opens, turning off the compressor. After the compressor cools down to a normal and safe working temperature, the thermal protector turns on the compressor.
Condenser:
The condenser is located underneath (outside) the cooling cabinet in front of the compressor. It receives hot, high-pressure refrigerant gas from the compressor and cools it down until it returns to liquid state.
© 2004, IMI Cornelius Inc. - 1 - Publication Number: 630460278SER
COR6519UBCSD Service Manual
Condenser fan motor:
The condenser fan motor is located underneath the cooling cabinet. It is a ventilation device which forces the ambient air to flow over the condenser in order to cool down the refrigerant flowing inside it. The fan motor works only if the compressor is on.
Evaporator:
The evaporator is located inside the cooling cabinet. As the gas flows at a low pressure through the evaporator, it absorbs heat through the copper coil from inside the cabinet.
Evaporator fan motor:
This device provides the required circulation of air through the cooling cabinet as well as over the surface of the evaporators serpentine thermal exchange area. This fan motor runs continuously.
The evaporator and condenser serpentines have aluminum fins that help increase the surfaces for the thermal exchange in an efficient way.
Capillary tube:
It consists of several feet of tubing having a small inside diameter. It is a device used to control the amount of refrigerant that flows into the evaporator.
Drier:
The drier is located in between the condenser and the evaporator. It traps and removes moisture in the refrigeration system while allowing oil and refrigerant to flow freely.
Accumulator:
The accumulator is located in between the evaporator and the compressor. It is a storage tank which receives refrigerant liquid from the evaporator and prevents it from flowing into the compressor.
Temperature control:
The adjustable temperature control is responsible for detecting temperature changes inside the cooling cabinet. It also starts the compressor motor whenever the cabinet rises above the desired temperature.
The temperature control consists of a switch which is mechanically activated by a diaphragm. This diaphragm is connected to a thermo-sensible bulb (located inside the cabinet) through a small diameter tube. All three components (the diaphragm, the thermo-sensible bulb, and the small diameter tube) are filled with refrigerant gas which reacts to temperature changes.
When the cabinet temperature rises, the refrigerant in the bulb heats up and expands, expanding the diaphragm. The diaphragms expanding closes the temperature controls interrupting device and then starts the compressor and condenser motors.
The drop in temperature inside the cooling compartment is caused by the refrigerant’s continuous circulation through the system. When the temperature drops, the refrigerant inside the temperature controls bulb contracts, allowing the diaphragm to open the interrupting device, which consequently shuts down the compressor and condenser motors.
Cooling cabinet:
This is the area where the goods are stored. It has been designed to allow for constant cold air circulation to flow through the goods.
THE REFRIGERATION CYCLE
1. Depending on the increase in temperature inside the cooling compartment, the refrigerant gas inside the temperature control's bulb heats up and expands, expanding the diaphragm. The diaphragm's expansion closes the temperature control's interrupting device.
2. The temperature control's interrupting device turns on the compressor and condenser motors.
3. The compressor recirculates the refrigerant throughout the system by drawing the refrigerant gas as low vapor pressure from the evaporator. Then it compresses the refrigerant and forces it into the condenser.
Publication Number: 630460278SER - 2 - © 2004, IMI Cornelius Inc.
COR6519UBCSD Service Manual
4. The condenser, with the help of its fan motor, removes the refrigerant's heat as it flows through the condenser. The heat is then released to the outside environment. Consequently, the decrease in temperature will change the refrigerant from a gaseous to a liquid state.
5. The capillary tube regulates the amount of refrigerant that is discharged into the evaporator.
6. The evaporator's serpentine allows the refrigerant to absorb and remove heat from the cooling compartment.
7. The drop in temperature inside the cooling compartment is caused by the refrigerant's continuous circulation through the system. This gas continuously absorbs the heat that exists inside the cooling compartment and expels it to the outside environment. When the temperature drops, the refrigerant inside the temperature control's bulb contracts, allowing the diaphragm to open the interrupting device, which consequently shuts down the compressor and condenser motors.
FIGURE 2
© 2004, IMI Cornelius Inc. - 3 - Publication Number: 630460278SER
Loading...
+ 15 hidden pages