Concord
CXA 40 - 120
User’s guide to commercial central heating boilers
GUIDE
Page 2
2
Concord CXA 40-120 - User's Guide
ALL MODELS
THE GAS SAFETY (INSTALLATION & USE) REGULATIONS 1994, AMENDMENTS 1996 OR
RULES IN FORCE impose certain statutory
obligations on gas users. This appliance must be installed by a CORGI registered installer.
Knob setting Approx. flow temp oC Approx. flow temp oF
1 60 140
2 64 147
3 69 156
4 73 163
5 77 171
6 82 180
WARNING.
This appliance MUST be efficiently earthed.
1. It is ESSENTIAL that the instructions in this booklet
are strictly followed, for safe, economical operation of the boiler.
2. Do not obstruct ventilation ducts, grilles or openings in the boiler room, or the passage of combustion and ventilation air to the boiler.
3. Do not store objects around or on the boiler, and keep access clear at all times.
4. Switch off and disconnect the electricity supply before carrying out maintenance work.
5. Do not turn off the boiler if it is to be left unattended in frosty weather.
MAINTENANCE
The appliance should be serviced at least once a year by a CORGI registered installer.
CLEANING
For normal cleaning simply dust with a dry cloth.
To remove stubborn marks and stains use a damp cloth and mild detergent.
DO NOT use abrasive cleaning materials.
CAUTION.
To avoid the possibility of injury during the use or cleaning of this
appliance care should be taken when handling edges of sheet steel components.
CONCORD CXA 40 - 80 models
1
6
5
7
2
2
4
LEGEND
1. Thermostat knob.
2. Mains gas inlet cock.
3. Overheat thermostat
button.
4. Lockout light.
5. Lockout reset button.
6. Burner on light.
7. Overheat light
3
Page 3
3
Concord CXA 40-120 - User's Guide
CONCORD CXA 90 - 120 models
1
6
5
2
2
3
4
TO LIGHT THE BOILER
1. Check that the boiler thermostat knob (1) on the control box
is OFF.
2. Ensure that the mains gas inlet cock (2) is open (groove in the square head in line with the gas pipe).
3. Press in the overheat thermostat button (3).
4. Ensure all system controls (time switch, system controls
etc.) are calling for heat.
5. Turn the boiler thermostat knob (1) to position 6.
6. If the boiler does not light at the end of the ignition period
the Lockout light (4) on the control box will be illuminated. Press in and release the Lockout reset button (5). The controls will reset and after a period of time will attempt to relight.
7. Once the pilot has lit the controls open the main gas valves and the main burners will light and the Burner On light (6) will be illuminated.
8. Set all system controls to the required settings.
9. Set the boiler thermostat knob (1) to the required setting.
7
LEGEND
1. Thermostat knob.
2. Mains gas inlet cock.
3. Overheat thermostat
button.
4. Lockout light.
5. Lockout reset button.
6. Burner on light.
7. Overheat light
CONTROL PANEL LIGHTS
1. The Boiler On light (6) is illuminated while the boiler is firing.
2. If the Overheat light (7) is lit, pull off the casing lower front
panel and press in the overheat reset button (3). Replace the lower front panel and follow the boiler lighting instructions above. If the overheat condition persists consult a CORGI registered installer.
3. If the Lockout light (4) is lit press in the Lockout reset button (5).
If the lockout condition persists consult a CORGI registered installer.
TO SHUT DOWN THE BOILER
For short periods
Turn the boiler off at the time clock or system controls. Wait 6 min. and then turn the boiler control thermostat knob (1) to
OFF. Note the frost warning below.
For long periods
Turn the boiler off at the time clock or system controls. Wait for 6 min. and then turn the boiler control thermostat knob (1) to OFF. Turn off the inlet gas cock (groove in the square head across the line of the gas pipe). Note the frost warning below.
TO RELIGHT THE BOILER
After short periods
Switch on the time switch or system controls and turn boiler thermostat knob (1) to the required setting. The boiler will light providing the external controls are calling for heat.
After long periods
Follow the lighting instructions above. Refill the system if it has been drained.
FROST WARNING
If frost is likely, leave the boiler thermostat at position 6 and do not turn off the gas cock. This will enable the built-in frost thermostat to protect the boiler. Note that this may not protect remote parts of the system, in which case a separate frost thermostat should be fitted or the system drained and the boiler shut down, as for "Long Periods".
Page 4
Caradon Plumbing Limited, P.O. Box 103, National Ave, Kingston upon Hull, HU5 4JN. Telephone: 01482 492 251 Fax: 01482 448 858. Registration No. London 322 137. Registered Office: National Avenue, Kingston upon Hull, HU5 4JN. A subsidiary of Caradon plc
Caradon Plumbing Limited pursues a policy of continuing improvement in the design and performance of its products. The right is therefore reserved to vary specification without notice.
May 2000 154 870 A01
Ideal Consumer Helpline Tel: 01482 498 376