Comtech EF Data PCB-4000A Installation And Operation Manual

Page 1
PCB-4000A
Part Number MN-PCB-4000A
IMPORTANT NOTE: The information contained in this document supersedes all previously published information regarding this product. Product specifications are subject to change without prior notice.
1+1 Phase Combiner
Installation and Operation Manual
Page 2
PCB-4000A 1+1 Phase Combiner
Revision 2
Copyright © 2018 Comtech EF Data. All rights reserved. Printed in the USA. Comtech EF Data, 2114 West 7th Street, Tempe, Arizona 85281 USA, 480.333.2200, FAX: 480.333.2161
Revision History
Rev
Date
Description
- 5-2017
Initial Release.
1 2-2018 Added remote commands STB, STA, STV, TPE, TPS, and RFD to Chapter 5.
Updated Table 6.1, Management Information Base Files, in Chapter 6. Updated Appendix A to add Mounting Bracket Kit, part number KT-0021261 and update cable assembly
in Table A -2 and A-5. Updated Preface Product Support and Comtech EF Data Headquarters information.
2 2-2018
Added default line for IPA, IPG, and SPA commands.
MN-PCB-4000A
Page 3
PCB-4000A 1+1 Phase Combiner Revision 2
TABLE OF CONTENTS
PREFACE ...................................................................................................................................................... I
About this Manual ........................................................................................................................................ i
Conventions and References...................................................................................................................... i
Patents and Trademarks ............................................................................................................................ i
Warnings, Cautions, and Notes ................................................................................................................. ii
Recommended Standard Designations ..................................................................................................... ii
Metric Conversion ...................................................................................................................................... ii
Safety and Compliance .............................................................................................................................. iii
Electrical Safety Notice ............................................................................................................................. iii
Product Support ........................................................................................................................................ iv
Comtech EF Data Headquarters ............................................................................................................... iv
Warranty Policy ......................................................................................................................................... v
Limitations of Warranty .............................................................................................................................. v
Exclusive Remedies .................................................................................................................................. vi
CHAPTER 1. INTRODUCTION ......................................................................................................... 1–1
1.1 Overview ...................................................................................................................................... 1–1
1.2 Functional Description ............................................................................................................... 1–2
1.3 Theory of Operation .................................................................................................................... 1–4
1.3.1 Phase and Gain Equalization ................................................................................................... 1–4
1.3.2 System Gain ............................................................................................................................. 1–5
1.3.3 System Attenuation ................................................................................................................... 1–5
1.3.4 Soft Fail Protection .................................................................................................................... 1–5
1.4 Dimensional Envelope ................................................................................................................ 1–6
CHAPTER 2. EXTERNAL CONNECTORS ...................................................................................... 2–1
2.1 Overview ...................................................................................................................................... 2–1
2.2 Monitor and Control (M&C) Interface Connectors ................................................................... 2–2
2.2.1 SYSTEM COM | J1 Connector ................................................................................................. 2–2
2.2.2 SSPA COM 1 | J2 and SSPA COM 2 | J3 Connectors .............................................................. 2–3
2.3 SSPA SW OUT | J5 Connector ................................................................................................... 2–4
2.3.1 RF INPUT SWITCH | J6 Connector .......................................................................................... 2–5
2.4 RF Interface Connectors ............................................................................................................ 2–6
2.4.1 RF IN 1 | J7 and RF IN 2 | J8 Connectors ................................................................................ 2–6
2.4.2 SSPA OUT 1 | J9 Connector ..................................................................................................... 2–6
2.4.3 SSPA OUT 2 | J10 Connector ................................................................................................... 2–6
2.5 Power and Ground Interfaces .................................................................................................... 2–7
2.5.1 AC Power .................................................................................................................................. 2–7
2.5.2 Ground Connector .................................................................................................................... 2–7
CHAPTER 3. OPERATION AND ADJUSTMENT PROCEDURES .................................................. 3–1
3.1 Overview ...................................................................................................................................... 3–1
3.2 System Assembly, Cabling Connections, and Installation ..................................................... 3–2
3.2.1 1+1 Phase Combiner System Assembly .................................................................................. 3–2
3.2.2 PCCB Cabling Connections ...................................................................................................... 3–3
Table of Contents TOC-1 MN-PCB-4000A
Page 4
PCB-4000A 1+1 Phase Combiner Revision 2
3.2.3 System Component Installation and Interconnection ............................................................... 3–4
3.2.4 LED Status Operation ............................................................................................................... 3–6
3.3 Initial System Setup and Verification ........................................................................................ 3–8
3.4 Gain or Amplitude Balance Ver ification and Alignment .......................................................... 3–9
3.5 Amplitude Alignme nt (as necessary) ...................................................................................... 3–10
3.6 Phase Alignment ....................................................................................................................... 3–11
3.7 System Online and Transmitting ............................................................................................. 3–12
CHAPTER 4. UPDATING FIRMWARE ............................................................................................. 4–1
4.1 Update Firmware via the Internet .............................................................................................. 4–1
4.2 Ethernet FTP Upload Procedure ................................................................................................ 4–2
4.2.1 Setup for the Firmware Download ............................................................................................ 4–2
4.3 Download and Extract the Firmware Update ............................................................................ 4–6
4.4 Firmware Upgrade ....................................................................................................................... 4–8
CHAPTER 5. SERIAL REMOTE CONTROL .................................................................................... 5–1
5.1 Overview ...................................................................................................................................... 5–1
5.1.1 EIA-232 ..................................................................................................................................... 5–1
5.2 Remote Commands and Queries Ovierview ............................................................................ 5–2
5.2.1 Basic Protocol ........................................................................................................................... 5–2
5.2.2 Packet Structure........................................................................................................................ 5–3
5.2.2.1 Start of Packet ............................................................................................................... 5–3
5.2.2.2 T arget (Base) Address ................................................................................................... 5–4
5.2.2.3 Virtual Address .............................................................................................................. 5–4
5.2.2.4 Address Delimiter .......................................................................................................... 5–5
5.2.2.5 Instruction Code ............................................................................................................ 5–5
5.2.3 Instruction Code Qualifier ......................................................................................................... 5–5
5.2.4 Optional Message Arguments ................................................................................................... 5–6
5.2.5 End of Packet ............................................................................................................................ 5–6
5.3 Remote Commands / Queries .................................................................................................... 5–7
CHAPTER 6. ETHERNET-BASED REMOTE PRODUCT MANAGEMENT ..................................... 6–1
6.1 Overview ...................................................................................................................................... 6–1
6.2 Ethernet Management Interface Protocols ............................................................................... 6–1
6.3 SNMP Interface ............................................................................................................................ 6–1
6.3.1 Management Information Base (MIB) Files .............................................................................. 6–2
6.3.2 SNMP Community Strings ........................................................................................................ 6–2
APPENDIX A. ASSEMBLY KITS ......................................................................................................A–1
A.1 Overview ..................................................................................................................................... A–1
A.1.1 Summary of Available Assemblies ............................................................................................ A–3
A.2 C-Band Unit Assemblies............................................................................................................ A–5
A.2.1 C-Band 1+1 Phase Combined HPOD Top Assembly Kit (KT-0000055) ................................... A–5
A.2.2 Phase Combiner Box and Bracket Kit (KT-0021171) ............................................................... A–7
A.2.3 C-Band 1:1 Phase Combined Waveguide and Switches, HPOD (KT-0000054) ...................... A–9
A.2.4 Vertical Mounting Frame Kit (KT-0021179) ............................................................................. A–11
A.3 Common Kit Subassemblies ................................................................................................... A–13
Table of Contents TOC-2 MN-PCB-4000A
Page 5
PCB-4000A 1+1 Phase Combiner Revision 2
A.3.1 HPOD 1:1 Redundancy Pole Mount Kit (PL/12319-1)............................................................ A–13
A.3.2 1:2 Redundant HPOD Mounting Kit (KT-0000017) ................................................................. A–15
A.3.3 Uni-Strut Mount HPOD Mounting Bracket Kit (KT/12300-1) ................................................... A–17
A.3.4 Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261) ......................... A–19
Table of Contents TOC-3 MN-PCB-4000A
Page 6
PCB-4000A 1+1 Phase Combiner Revision 2
LIST OF FIGURES
Figure 1-1. PCB-4000A 1+1 Phase Combined System ............................................................................ 1–1
Figure 1-2. Combined System Block Diagrams ........................................................................................ 1–2
Figure 1-3. Combining Loss vs. Phase Imbalance Summary of Specifications........................................ 1–4
Figure 1-4. PCB-4000A Dimensional Envelope ........................................................................................ 1–6
Figure 3-1. PCB-4000A 1+1 Phase Combiner System Assembly Example ............................................. 3–2
Figure 3-2. PCB-4000A External Connectors - Front ............................................................................... 3–3
Figure 3-3. PCB-4000A External Connectors – Right Side ...................................................................... 3–3
Figure 3-4. PCB-4000A – Left Side ........................................................................................................... 3–4
Figure 3-5. LED Indicators ........................................................................................................................ 3–6
Figure 4-1. Typical Unit to PC Connection ................................................................................................ 4–2
Figure 4-2. Temporary Folder Setup using Windows Desktop ................................................................. 4–3
Figure 4-3. Temporary Folder Setup using Windows Explorer ................................................................. 4–4
Figure 4-4. Temporary Folder Setup using ‘Run’ and ‘Browse’................................................................. 4–4
Figure 4-5. Temporary Folder Setup using Windows Command Line ...................................................... 4–5
Figure 4-6. Download Firmware Archive File ............................................................................................ 4–7
Figure A-1. PCB-4000A 1+1 Phase Combined System ............................................................................ A–2
Figure A-2. C-Band 1+1 Phase Combined HPOD Top Assembly Kit (KT-0000055) ................................ A–5
Figure A-3. Phase Combiner Box and Bracket Kit (KT-0021171) ............................................................. A–7
Figure A-4. C-Band 1:1 Phase Combined Waveguide and Switches, HPOD (KT-0000054) ................... A–9
Figure A-5. Vertical Mounting Frame Kit (KT-0021179) .......................................................................... A–11
Figure A-6. HPOD 1:1 Redundancy Pole Mount Kit (PL/12319-1) .........................................................A–13
Figure A-7. 1:2 Redundant HPOD Mounting Kit (KT-0000017) ..............................................................A–15
Figure A-8. Uni-Strut Mount HPOD Mounting Bracket Kit (KT/12300-1) ................................................A–17
Figure A-9. Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261) .......................A–19
Table of Contents TOC-4 MN-PCB-4000A
Page 7
PCB-4000A 1+1 Phase Combiner Revision 2
LIST OF TABLES
Table 2-1. External Connectors ................................................................................................................. 2–1
Table 2-2. Connector J1 Pinouts ............................................................................................................... 2–2
Table 2-3. Connectors J2 and J3 Pinouts ................................................................................................. 2–3
Table 2-4. Connector J5 Pinouts ............................................................................................................... 2–4
Table 2-5. Connector J6 Pinouts ............................................................................................................... 2–5
Table 3-1. LED Descriptions...................................................................................................................... 3–7
Table 6-1. Management Information Base Files ....................................................................................... 6–2
T able A-1. Appendix Figure Quick Reference ........................................................................................... A–3
T able A-2. C-Band 1+1 Phase Combined HPOD Top Assembly Kit - BOM (KT-0000055) ...................... A–6
T able A-3. Phase Combiner Box and Bracket Kit – BOM (KT-0021171) .................................................. A–8
T able A-4. C-Band 1:1 Phase Combined Waveguide and Switches, HPOD - BOM (KT-0000054) .......A–10
T able A-5. Vertical Mounting Frame Kit – BOM (KT-0021179) ................................................................A–12
T able A-6. HPOD 1:1 Redundancy Pole Mount Kit - BOM (PL/12319-1) ...............................................A–14
Table A-7. Hardware Kit (KT-0020905) ...................................................................................................A–14
T able A-8. 1:2 Redundant HPOD Mounting Kit - BOM (KT-0000017) ....................................................A–16
T able A-9. Uni-Strut Mount HPOD Mounting Bracket Kit - BOM (KT/12300-1) ......................................A–18
T able A-10. Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261) .......................A–20
Table of Contents TOC-5 MN-PCB-4000A
Page 8
PCB-4000A 1+1 Phase Combiner Revision 2
Acronym List
Acronym Description
AOF Amplitude Offset
EIA Electronic Industries Association
GND Ground
HPOD High Powered Outdoor Amplifier
LED Light Emitting Diode M&C Monitor and Control NMS Network Management System
OID Object Identifiers
PCB Printed Circuit Board
PCCB Phase Combiner Control Box
RMA Ret urn Marerial Authorization
RS Recommended Standard
SNMP Simple Network Management System
SSPA Solid State Power Amplifier
VSWR Voltage Standing Wave Ratio
WG Waveguide
Table of Contents TOC-6 MN-PCB-4000A
Page 9
PCB-4000A 1+1 Phase Combiner Revision 2
PREFACE
About this Manual
This manual provides installation and operation information for the Comtech EF Data PCB-4000A 1+1 Phase Combiner. This is an informational document intended for the persons responsible for the operation and maintenance of the PCB-4000A.
Comtech EF Data has reviewed this manual thoroughly in order to provide an easy-to-use guide to your equipment. All statements, technical information, and recommendations in this manual and in any guides or related documents are believed reliable, but the accuracy and completeness thereof are not guaranteed or warranted, and they are not intended to be, nor should they be understood to be, representations or warranties concerning the products described. Further, Comtech EF Data reserves the right to make changes in the specifications of the products described in this manual at any time without notice and without obligation to notify any person of such changes.
This is an informational document intended for the persons responsible for the operation and maintenance of the modem.
Conventions and References
Patents and Trademarks
See all of Comtech EF Data's Patents and Patents Pending at http://patents.comtechefdata.com. Comtech EF Data acknowledges that all trademarks are the property of the trademark owners.
Preface i MN-PCB-4000A
Page 10
PCB-4000A 1+1 Phase Combiner
A CAUTION indicates a hazardous situation that, if not avoided, may result in practices or risks of property damage.
A REFERENCE directs you to important operational information or details publications.
Revision 2
Warnings, Cautions, and Notes
A WARNING indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
minor or moderate injury. CAUTION may also be used to indicate other unsafe
A NOTE: gives you important information about a task or the equipment.
furnished elsewhere, either in the manual or in adjunct Comtech EF Data
Examples of Multi-Hazard Notices
Recommended Standard Designations
Electronic Industries Association (EIA) designations supersede Recommended Standard (RS) designations. Reference to the old RS designations (e.g., RS-232) may appear where it might concern actual text displayed on the unit’s rear panel, Serial Interface, or Web Server Interface pages. All other references in the manual use the EIA designations.
Metric Conversion
Metric conversion information is provided on the inside back cover of this manual. Comtech EF Data provides this information to assist the user in cross-referencing non-Metric to Metric conversions.
Preface ii MN-PCB-4000A
Page 11
PCB-4000A 1+1 Phase Combiner Revision 2
Safety and Compliance
Electrical Safety Notice
Double pole / neutral fusing is used on the prime power supply input.
This equipment is designed to minimize exposure of personnel to hazards. For further information, contact the Comtech EF Data Customer Support Department. The persons responsible for the operation and maintenance of the PCB-4000A must:
Know how to work around, with, and on high voltage equipment.
Exercise every precaution to ensure personnel safety.
Exercise extreme care when working near high voltages.
Be familiar with the warnings presented in this manual.
Preface iii MN-PCB-4000A
Page 12
PCB-4000A 1+1 Phase Combiner Revision 2
Product Support
For all product support, please call:
+1.240.243.1880 +1.866.472.3963 (toll free USA)
By email:
techsupport@comtechefdata.com
Comtech EF Data Headquarters
http://www.comtechefdata.com Comtech EF Data Corp. 2114 West 7th Street Tempe, Arizona USA 85281 +1.480.333.2200
Preface iv MN-PCB-4000A
Page 13
PCB-4000A 1+1 Phase Combiner Revision 2
Warranty Policy
Comtech EF Data products are warranted against defects in material and workmanship for a specific period from the date of shipment, and this period varies by product. In most cases, the warranty period is two years. During the warranty period, Comtech EF Data will, at its opt ion, repair or replace products that prove to be defective. Repairs are warranted for the remainder of the original warranty or a 90 day extended war ranty, whichever is longer. Contact Comtech EF Data for the warranty period specific to the product purchased.
For equipment under warranty, the owner is responsible for freight to Comtech EF Data and all related customs, taxes, tariffs, insurance, etc. Comtech EF Data is responsible for the freight charges only for return of the equipment from the factory to the owner. Comtech EF Data will return the equipment by the same method (i.e., Air, Express, Surface) as the equipment was sent to Comtech EF Data.
All equipment returned for warranty repair must have a valid RMA number issued prior to return and be marked clearly on the return packaging. Comtech EF Data strongly recommends all equipment be returned in its original packaging. Comtech EF Data Corporation’s obligations under this warranty are limited to repair or replacement of failed parts, and the return shipment to the buyer of the repaired or replaced parts.
Limitations of Warranty
The warranty does not apply to any part of a product that has been installed, altered, repaired, or misused in any way that, in the opinion of Comtech EF Data Corporation, would affect the reliability or detracts from the performance of any part of the product, or is damaged as the result of use in a way or with equipment that had not been previously approved by Comtech EF Data Corporation.
The warranty does not apply to any product or parts thereof where the serial number or the serial number of any of its parts has been altered, defaced, or removed.
The warranty does not cover damage or loss incurred in transportation of the product. The warranty does not cover replacement or repair necessitated by loss or damage from any cause beyond the control of Comtech EF Data Corporation, such as lightning or other natural and weather-related events or wartime environments.
The warranty does not cover any labor involved in the removal and or reinstallation of warranted equipment or parts on site, or any labor required to diagnose the necessity for repair or replacement.
The warranty excludes any responsibility by Comtech EF Data Corporation for incidental or consequential damages arising from the use of the equipment or products, or for any inability to use them either separate from or in combination with any other equipment or products.
A fixed charge established for each product will be imposed for all equipment returned for warranty repair where Comtech EF Data Corporation cannot identify the cause of the reported failure.
Preface v MN-PCB-4000A
Page 14
PCB-4000A 1+1 Phase Combiner Revision 2
Exclusive Remedies
Comtech EF Data Corporation’s warranty, as stated is in lieu of all other warranties, expressed, implied, or statutory, including those of merchantability and fitness for a particular purpose. The buyer shall pass on to any purchaser, lessee, or other user of Comtech EF Data Corporation’s products, the aforementioned warranty, and shall indemnify and hold harmless Comtech EF Data Corporation from any claims or liability of such purchaser, lessee, or user based upon allegations that the buyer, its agents, or employees have made additional warranties or representations as to product preference or use.
The remedies provided herein are the buyer’s sole and exclusive remedies. Comtech EF Data shall not be liable for any direct, indirect, special, incidental, or consequential damages, whether based on contract, tort, or any other legal theory.
Preface vi MN-PCB-4000A
Page 15
PCB-4000A 1+1 Phase Combiner Revision 2
Chapter 1. INTRODUCTION
1.1 Overview
Phase combining is a traditional technique that cost effectively increases the available output power of an amplifier system. The PCB-4000A 1+1 Phase Combiner (Figure 1-1), together with two Solid State Power Amplifiers (SSPAs), form a complete 1+1 phase combined system that doubles the available output power. The PCB-4000A also features a “soft fail” configuration; i.e., if one SSPA experiences a failure, the total output power will be reduced by only 3 dB, rather than 6 dB.
Figure 1-1. PCB-4000A 1+1 Phase Combined System
Introduction 1–1 MN-PCB-4000A
Page 16
PCB-4000A 1+1 Phase Combiner Revision 2
1.2 Functional Description
The PCB-4000A is available in a C-Band version. Contact Comtech EF Data for X-band and Ku­band versions. The box may be included in a top-level system assembly or as a subassembly kit. For application examples, see Appendix A. ASSEMBLY KITS.
Monitor & Control (M&C) System Interconnect
RF System Interconnect
Introduction 1–2 MN-PCB-4000A
Figure 1-2. Combined System Block Diagrams
Page 17
PCB-4000A 1+1 Phase Combiner Revision 2
The block diagrams shown in Figure 1-2 depict the major components of the 1:1 phase combined system. (These diagrams employ High Powered Outdoor Amplifiers (HPODs) as the designated SSPAs.)
The Phase Combiner Control Box (PCCB) contains a microprocessor-based Monitor and Control (M&C) circuit board to control the system. Interconnection is as follows:
The PCCB communicates with each SSPA via control cables that are attached from the PCCB “SSPA COM 1 | J2” and “SSPA COM 2 | J3” co nnec tor s to each S SP A.
Through this connection, the PCCB receives its prime power to operate. A +24V signal from each SSPA is diode OR’ed to provide redundant operating power for the PCCB.
A “Y” cable connects to the “SSPA SW OUT | J5” connector for control of the waveguide switches. M&C communication with the PCCB is accomplished via the “SYSTEM COM | J1” connector.
To avoid ambiguities, all communication to each SSPA is also accomplished via the PCCB M&C.
The PCCB provides a weatherized housing for the necessary input RF components. System interconnection is as follows:
An input RF redundancy switch, controlled via the “RF INPUT SWITCH | J6” connector, selects which RF path is directed to the output.
The output RF signal is fed into an in-phase divider, which equally splits the signal in phase and amplitude to the “SSPA OUT 1 | J9” and “SSPA OUT 2 | J10” output connectors.
o The RF path to the “SSPA OUT 1 | J9” output connector contains a manually
adjustable phase shifter. This phase shifter is used to equalize the phase difference of each SSPA signal path to achieve maximum system output power. It is accessible via a small cover panel. This critical component is factory set and should only be adjusted, if needs arise, by carefully following an appropriate alignment procedure.
See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES for operational and alignment information.
o The RF path to the “SSPA OUT 2 | J10” output connector contains a length of
coaxial cable that is factory manufactured to provide equal phase length paths from the RF input to each PCCB output when the adjustable phase shifter is set to its midpoint. This provides a maximum adjustable phase range.
There are also several isolators inside the PCCB that maintain good system Voltage Standing Wave Ratio (VSWR). Do not alter any RF cable inside (or outside) of the box that is part of the RF signal path.
The RF signals from the PCCB are fed to the RF input of the respective SSPA via a set of phase-matched cables. Again, the phase length (and matching) of these cables is essential to system operation and no substitutes should be used. The routing should not be such to cause extreme bends.
The output waveguide combining system consists of balanced waveguide lengths, two waveguide transfer switches, a “Magic-Tee” combiner with termination, and couplers for test and alignment.
Introduction 1–3 MN-PCB-4000A
Page 18
PCB-4000A 1+1 Phase Combiner
Phase and gain equalization are performed at the factory, and no user such as the phase combiner box, needs to be replaced.
Revision 2
1.3 Theory of Operation
As mentioned previously, phase combining is a common technique to increase the available output power of an amplifier system. Referring back to Figure 1-2, when two signals of equal phase and amplitude are fed into the “Magic-Tee” combiner, the individual power of each SSPA is summed at the output port and cancelled in the termination port.
In real systems, the phase and amplitude of the two signals are never exactly equal, so there is a small amount of power that is absorbed by the load termination. This terminated port is sometimes referred to as the “wasted” power port. In practice, however, it is possible to keep phase and amplitude imbalances at low enough levels such that overall combining losses are only in the 0.2 to 0.5 dB range.
Figure 1-3 shows the effects of phase imbalance on the power combining efficiency.
Figure 1-3. Combining Loss vs. Phase Imbalance Summary of Specifications
1.3.1 Phase and Gain Equalization
intervention is required unless an amplifier or other critical system component,
The following paragraphs are provided for informational purposes only.
See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES for operational and alignment information.
Naturally, two separate amplifiers are likely to have different phase and gain characteristics. The PCB-4000A 1+1 system is designed such that the phase difference between the two amplifier paths is compensated by adjusting the phase shifter in the PCCB. This is done at the factory for the full amplifier bandwidth, and should not normally require further adjustment in the field unless an amplifier has been replaced.
Introduction 1–4 MN-PCB-4000A
Page 19
PCB-4000A 1+1 Phase Combiner Revision 2
1.3.2 System Gain
The gains of the amplifiers are calibrated at the factory to provide optimum system performance. The amplifier gain difference is automatically compensated for by the PCCB M&C System. Upon power up, the M&C reads the gain of each individual amplifier as calibrated at the factory, and automatically attenuates the amplifier with the most gain so as to be equal with the lower gain unit.
For example, if SSPA #1 had a factory-calibrated gain setting of 76 dB, and SSPA #2 had a factory-calibrated gain setting of 73 dB, the M&C system would automatically set the attenuation setting of SSPA#1 to 3 dB to equalize the system gain. Although not gen er ally needed or recommended, a user input gain offset setting is also provided for system fine-tuning.
See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES for operational and alignment information.
Due to the power divider and cable losses, the overall gain of the system will be less than the individual gain of each amplifier. Please refer to the system test data sheet for actual system gain.
1.3.3 System Attenuation
The PCB-4000A makes it easy to adjust the overall system gain. Upon input of the requested attenuation setting, the PCB-4000A automatically adjusts the gain of each SSPA accordingly, resulting in the desired attenuation value while maintaining optimum power combining conditions.
The SSPAs included in the system are calibrated over a range 10 dB beyond specification (30 dB vs. 20 dB). As explained above, a portion of the 30 dB range is required for gain equalization. Therefore, the maximum allowable attenuation in a 1+1 system is software limited to 24 dB, but still exceeds system specifications.
1.3.4 Soft Fail Protection
In the event of a failure of one of the SSPAs, the PCB-4000A controls the waveguide switches such that the good unit’s power is routed around the “Magic-Tee” combiner directly to the output port. This results in only a 3 dB power loss, or “soft failure”. Without the waveguide switches, a failure in one unit would result in a 6 dB power loss.
Introduction 1–5 MN-PCB-4000A
Page 20
PCB-4000A 1+1 Phase Combiner Revision 2
1.4 Dimensional Envelope
All dimensions are in English units; metric units are shown in parentheses. This figure is typical for the C-Band versions o f the PCB-4000A.
Introduction 1–6 MN-PCB-4000A
Figure 1-4. PCB-4000A Dimensional Envelope
Page 21
PCB-4000A 1+1 Phase Combiner
Connector Group
(Chapter Sect.)
M&C
Customer EIA-232 and discrete interface
SSPA COM 1 | J2
SSPA COM 2 | J3
Connects to both waveguide switches
Drive input, selects either RF IN 1 or RF IN 2
RF
RF IN 1 | J7
RF IN 2 | J8
SSPA OUT 1 | J9
SSPA OUT 2 | J10
Power/Ground
Pin ‘R’ on SSPA COM 1 J1, SSPA COM 2 J3
See Sect. 2.4.1 for AC power provision note
Ground
#10-32 stud
Common Chassis Ground
Revision 2
Chapter 2. EXTERNAL
CONNECTORS
2.1 Overview
See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES and Appendix A. ASSEMBLY KITS for basic installation and operational examples.
See Chapter 5. SERIAL REMOTE CONTROL for information about the remote M&C.
This chapter summarizes the connectors provided for all necessary external connections between the PCB-4000A and other equipment. Table 2-1 lists the external connectors grouped according to service function. Refer to Figure 3-2 for External Connectors illustration.
(Sect. 2.2)
(Sect. 2.4)
(Sect 2.5)
Table 2-1. External Connectors
Name / Ref Des Connector Type Function
SYSTEM COM | J1 19-pin Circular Connector
19-pin Circular Connector Connects to SSPAs
SSPA SW OUT | J5 19-pin Circular Connector
RF INPUT SWITCH | J6 6-pin Circular Connector
Type ’N’ RF Inputs to PCCB
Type ’N’ RF Outputs to SSPAs
AC
To maintain compl ian ce with the Eu rope an E MC Dir ective (EN55022, EN50082-1), properly shielded cables are required for data I/O.
External Connectors 2–1 MN-PCB-4000A
Page 22
PCB-4000A 1+1 Phase Combiner
When there is a summary fault in the PCB-4000, this pin (NO) will be tied to the Fault
Common pin.
When there is not a summary fault in the PCB-4000, this pin (NC) wil l be tie d t o the Fau lt
Common pin.
Revision 2
2.2 Monitor and Control (M&C) Interface Connectors
All M&C connectors are found on the front panel of the PCCB box.
2.2.1 SYSTEM COM | J1 Connector
The 19-pin circular SYSTEM COM | J1 connector, type MS3112E14-19S, serves as the primary input between the user and the PCCB for controlling and monitoring both SSPAs. Its pinout specification is provided in Table 2-2.
Mating connector: ITT Cannon MS3116J14-19P
(CEFD P/N CN/MS3116J14-19P)
Table 2-2. Connector J1 Pinouts
Pin # Signal Function Signal Name / Description
A ETH_+TX Customer communications interface
B ETH_-TX Customer communications interface C ETH_+RX Customer communications interface D ETH_-RX Customer communications interface E RS232_RD Customer communications interface F Spare Reser4ved for future use G RS232_TD Customer communications interface
H System Fault NO
J System Fault NC K Fault Common
L SSPA 1 Fault NO When there is a fault with SSPA 1, this pin (NO) will be tied to the Fault Common pin. M SSPA 1 Fault NC When there is not a fault with SSPA 1, this pin (NC) will be tied to the Fault Common pin. N Spare Reserved for future use P SSPA 2 Fault NO When there is a fault with SSPA 2, this pin (NO) will be tied to the Fault Common pin. R SSPA 2 Fault N C When there is not a fault with SSPA 2, this pin (NC) will be tied to the Fault Common pin. S System Mute SSPA will be muted if this pin is grounded T SS PA 3 Fault NO (NOTE: This pin is reserved for use with 1:2 systems only.) U SSPA 3 Fault N C (NOTE: This pin is reserved for use with 1:2 systems only.) V Ground GND
External Connectors 2–2 MN-PCB-4000A
Page 23
PCB-4000A 1+1 Phase Combiner
Allow for customer inhibit. Tied to Pin S of System Comm (J1) connector
Revision 2
2.2.2 SSPA COM 1 | J2 and SSPA COM 2 | J3 Connectors
The 19-pin circular SSPA COM 1 | J2 and SSPA COM 2 | J3 connectors, type MS3112E14-19S, serve as the primary input/output interfaces between the PCCB and its specified SSPA. The typical pinout specification is provided in Table 2-3.
Mating connector: ITT Cannon MS3116J14-19P
(P/N CN/MS3116J14-19P)
Table 2-3. Connectors J2 and J3 Pinouts
Pin # Signal Function Signal Name / Description Direction
A NC B NC C NC D NC E RS232_RD Provides for Comm between PCB and SSPA Input F NC G RS232_TD Provides for Comm between PCB and SSPA Output H Switch Inhibit Output Provides a hardware mute input to SSPA with switch fault Output
J NC
K Ground GND
L SUMFLT_NO Monitors SSPA summary fault relay Input M NC N Ground GND P ONLINE_STATUS Used by PCB for online status indication Input R +24V Bias voltage from SSPA Input
S Mute Control T NC
U NC V NC
External Connectors 2–3 MN-PCB-4000A
Page 24
PCB-4000A 1+1 Phase Combiner Revision 2
2.3 SSPA SW OUT | J5 Connector
The 19-pin circular SSPA SW OUT | J5 connector, type MS3112E14-19S, connects via a “Y” cable to the SSPA #1 and SSPA #2 waveguide switches. The typical pinout specification is provided in Table 2-4.
Mating connector: ITT Cannon MS3116J14-19P (P/N CN/MS3116J14-19P)
Table 2-4. Connector J5 Pinouts
Pin # Signal Function Signal Name / Description Direction
A Pos1, SW1 Drive Output B Ground GND C POS2 , SW 1, Dr ive Output D POS1, SW1, Indicator Input E Ground GND F POS2, SW1, Indicator Input
G NC
H POS1 , SW 2, Dr ive Output
J Ground GND K POS2, SW2, Drive Output L POS1, SW2, Indicator Input
M Ground GND
N POS2, SW2, Indicator Input P NC R NC S NC T NC U NC V NC
External Connectors 2–4 MN-PCB-4000A
Page 25
PCB-4000A 1+1 Phase Combiner Revision 2
2.3.1 RF INPUT SWITCH | J6 Connector
The PCCB contains a built-in selector switch – a latching 28 VDC coaxial unit. The switch position is selected by the 6-pin circular RF INPUT SWITCH | J6 connector (P/N CN/MS-PT07M6PC). Its pinout specification is provided in Table 2-5.
Mating connector: ITT Cannon MS3116J10-6S (P/N CN/MS3116J10-6S)
Table 2-5. Connector J6 Pinouts
Pin # Signal Function Signal Name / Description Direction
A
POS1, Drive Input
B
Ground GND
C
POS2, Drive Input
D
POS1, Indicator Output
E
Ground GND
F
POS2, Indicator Output
External Connectors 2–5 MN-PCB-4000A
Page 26
PCB-4000A 1+1 Phase Combiner Revision 2
2.4 RF Interface Connectors
2.4.1 RF IN 1 | J7 and RF IN 2 | J8 Connectors
The Type ‘N’ RF IN 1 | J7 and RF IN 2 | J8 connectors serve as RF signal input interfaces to the PCCB. Note that:
The PCCB selects the RF IN 1 | J7 input when the RF INPUT SWITCH | J6 POS1 Signal Function is activated.
The PCCB selects the RF IN 2 | J8 input when the RF INPUT SWITCH | J6 POS2 Signal Function is activated.
2.4.2 SSPA OUT 1 | J9 Connector
The T ype ‘N’ SS P A OU T | J9 connector, loc ated on the left side pane l of the PCCB, provides the RF signal output from the PCCB to SSPA #1.
2.4.3 SSPA OUT 2 | J10 Connector
The Type ‘N’ S SPA OUT 2 | J10 connector, located on the r ight s i de panel of the PCCB, provides the RF signal output from the PCCB to SSPA #2.
External Connectors 2–6 MN-PCB-4000A
Page 27
PCB-4000A 1+1 Phase Combiner Revision 2
2.5 Power and Ground Interfaces
2.5.1 AC Pow er
The PCB-4000A derives its power from the SSPAs. Each SSPA provides a +24V signal line via cables interconnecting the SSPAs to the SSPA COM 1 | J2 and SSPA COM 2 | J3 connectors (Pin ‘R’ – see Table 2-3). These two signals are “diode OR’ed” to provide redundancy.
Although the PCCB will turn on and function with only one SSPA is powered on, the system does not provide optimum output power unless both SSPAs are powered on.
2.5.2 Ground Connector
A #10-32 stud is provided on the front panel of the PCCB for connecting a common chassis ground among equipment.
External Connectors 2–7 MN-PCB-4000A
Page 28
PCB-4000A 1+1 Phase Combiner Revision 2
Notes:
External Connectors 2–8 MN-PCB-4000A
Page 29
PCB-4000A 1+1 Phase Combiner
remote control commands and queries.
Revision 2
Chapter 3. OPERATION AND
ADJUSTMENT PROCEDURES
Comtech EF Data recommends that only qualified personnel familiar with high-power amplifiers, test equipment, and phase-combined systems attempt the procedures provided in this chapter. Furthermore, before attempting any of these procedures, it is strongly advised to:
Read Chapter 1. INTRO DUCTIO N to becom e famili ar with s ystem ter minolo gy and
Theory of Operation.
Read Chapter 2. EXTERNAL CONNECT ORS to become familiar with the external
connectors and their functionality.
Read Chapter 5. SERIAL REMOTE CONTROL to become familiar with the serial
3.1 Overview
Chapter 1. INTRODUCTION
As indicated in Chapter 1. INTRODUCTION, the PCB-4000A 1+1 Phase Combiner system is aligned at the factory using a network analyzer. The in-factory adjustments are based on the specific arrangement of the SSPAs within the system. To ensure proper system operation and performance, it is mandatory that the components are installed in the same positions as was done in the factory. See Figure 3-1 for an assembly example.
Although the techniques featured in this chapter afford easy adjustment and setting of the phase shifter for optimum output power combining over the full amplifier bandwidth, alignment in the
field is generally not required and it is strongly cautioned against making unneeded adjustments.
However, if an amplifier or other critical system component is replaced (e.g., the PCB-4000A unit), the procedures provided in this chapter explain the steps necessary to restore proper system operation. This chapter also provides a verification procedure in the event that proper system operation confirmation is required.
It is recommended that only qualified personnel familiar with high-power amplifiers, test equipment, and phase combined systems attempt these procedures.
Operation and Adjustment Procedures 3–1 MN-PCB-4000A
Page 30
PCB-4000A 1+1 Phase Combiner Revision 2
3.2 System Assembly, Cabling Connections, and Installation
3.2.1 1+1 Phase Combiner System Assembly
Figure 3-1 shows an exam ple of the PCB-4000A deplo yed in a typical 1+1 phase combined system (see Appendix A. ASSEMBLY KITS for details on band-specific system applications).
Figure 3-1. PCB-4000A 1+1 Phase Combiner S yst e m Asse mb l y Examp le
Operation and Adjustment Procedures 3–2 MN-PCB-4000A
Page 31
PCB-4000A 1+1 Phase Combiner Revision 2
3.2.2 PCCB Cabling Connections
Figure 3-2. PCB-4000A External Connectors - Front
Figure 3-3. PCB-4000A External Connectors – Right Side
Operation and Adjustment Procedures 3–3 MN-PCB-4000A
Page 32
PCB-4000A 1+1 Phase Combiner
Install the SSPAs in their respective positions as detailed in the factory datasheet and in accordance with
fully tightened until the entire system is installed.
Attach the Waveguide (WG) combining network to th e mounting structure and to each SSPA. For a ssembly
gaskets at each SSPA
Tighten all hardware when proper alignment is achieved.
Install the Type ‘N’ RF Phase M atched Coaxial Cables (CEFD P/N CA/RF11872-1). Each cable is labeled
”, connecting it between the PCCB Type ‘N’ port
labeled “SSPA OUT 1 | J10” and the RF Input port on SSPA #2.
Revision 2
Figure 3-4. PCB-4000A – Left Side
3.2.3 System Component Installation and Interconnection
Refer to Figure 3-1 through Figure 3-3 to perform the follow these steps:
Step Procedure
Figure 3-1. The specific serial numbered SSPA that w as aligned in Posit ion 1 at t he factor y must als o now be
1
installed in Positi on 1; the same applies to the SSPA in P osition 2. Refer to cable and component l abeling to assure correct installation. It is suggested that any mounting hardware used in the in stallation process not be
details, see Appendix A. ASSEMBLY KITS. Take care to install the provided WG
2
output. It may be necessary to slightly adjust each SSPA to prevent undue s tress on the wa veguide structure .
3 Assemble the PCB-4000A PCCB to the mounting structure.
according to its destination SSPA:
Connect the cable labeled “SSPA1” from the PCCB Type ‘N’ port labeled “SSPA O UT 1 | J9 ” to the RF Input port on SSPA #1.
4
Repeat this task for the cable labeled “SSPA2
Make sure to correctly install all RF c abling, as an y “cross” connect ions will cause system malfunction.
Operation and Adjustment Procedures 3–4 MN-PCB-4000A
Page 33
PCB-4000A 1+1 Phase Combiner
Install the “COM” Cable (CEFD P/N CA/WR11966-2) between each of the following PCCB connectors and their
(PCCB) “SSPA COM 2 | J3” to SSPA #2
Install a WG Switch Control “Y” Cable (CEFD P/N CA/WR12013-1) between the PCCB connector labeled the ends labeled “SW1” and “SW2” are connected, respectively, to WG Switch #1 and #2.
Properly terminate the WG system output port, review all cables for proper connections, and ensure that all
Revision 2
Step Procedure
corresponding SSPA “COM” ports:
5
6
(PCCB) “SSPA COM 1 | J2” to SSPA #1
SSPA SW OUT | J5 ” and the two WG switches as sh own in Figure 3-1. Pay particular attention to en s ure that
7 Install the user-provided RF Input Switch control cable (if applicable) to the PCCB “RF INPUT SWITCH | J6”.
8
mounting hardware is tightened.
Operation and Adjustment Procedures 3–5 MN-PCB-4000A
Page 34
PCB-4000A 1+1 Phase Combiner Revision 2
3.2.4 LED Status Operation
The PCB-4000A features four Light-Emitting Diode (LED) indicators – three are operational, with the fourth reserved for future applications. Each LED provides visual cues to the operational, online, and offline status of the system.
Figure 3-5 illustrates the location of the LED indicators. Located on the top of the PCB-4000A enclosure under a pivoting protective plate, view the LEDs by first loosening the captive screw that keeps the plate in place, and then swiveling the plate to reveal the LED display window.
Operation and Adjustment Procedures 3–6 MN-PCB-4000A
Figure 3-5. LED Indicators
Page 35
PCB-4000A 1+1 Phase Combiner
LED *
Color / Behavior
Description
SUM
Green
Phase Combiner has no summary fault.
Red
A Summary Fault has occurred.
SSPA 1
(LED 3)
Green
SSPA is unfaulted, unmated.
Orange
SSPA is unfaulted but muted.
Red
SSPA is faulted.
Revision 2
The behavior of the LEDs, as they appear under varying operational conditions, is as follows:
Table 3-1. LED Descriptions
(LED 1)
(LED 2)
-or­SSPA 2
(LED 4) Inoperable (always dark), reserved for future use
* If LED light is blinking, this indicates there is a switch fault.
Operation and Adjustment Procedures 3–7 MN-PCB-4000A
Page 36
PCB-4000A 1+1 Phase Combiner
In the normal 1+1 phase combiner mode, the RED=X remote command setting should be set to “1”. Verify the setting is accurate by querying the system (see Chapter 5. SERIAL REMOTE CONTROL).
B. Apply a low-level signal at center frequency; ma king sur e the output signa l (a t t he s ystem ou tpu t p ort –not
the coupled port) will be at least 10 dB below Prated.
C. Measure the output power and include the coupler correction factor.
B. Measure the power and include coupler correction factor.
B. Again, verify the appropriate ratio of the transmitted to dissipated power.
Revision 2
3.3 Initial System Setup and Verification
Verify that the system has been assembled, that all cables have been connected, and that the output port is terminated in a broadband high power load as depicted in Figure 1-2 block diagram in Chapter 1. INTRODUCTION. If the system is “live” and you desire only to verify operation, see Section 3.5.
Verify the overall system performance by measuring the ratio of the transmitted power to that of the power being dissipated by the “dummy” load. Adjust the gain and amplitude balance if necessary.
Follow these steps:
Step Procedure
1
A. Attach a power meter to the Combined Output Power Test Coupler (Figure 3-1).
2
A. Attach a p ower met er t o the Was ted (“Load”) Power Test Coupler (Figure 3-1).
3
If the Wasted (“Load”) po wer level is 15-20 dB below the t ransmitt ed power, the sy stem
4
is operating correctly.
If the ratio is below 10 dB, proceed to the gain and phase alignment procedures that follow in this chapter.
A. Slowly increase the input power until the desired operating output power is achieved.
5
6 If desired, repeat Steps 1 through 5 at different frequencies to verify proper full bandwidth operation.
Operation and Adjustment Procedures 3–8 MN-PCB-4000A
Page 37
PCB-4000A 1+1 Phase Combiner
B. Apply a low-level signal at center frequency, making sure the output signal will be at least 10 dB below
To measure only the individual gain of SSPA#1, SSPA#2 must by bypassed by changing the state of th e
5. SERIAL REMOTE CONTROL):
The output of SSPA#1 will be sent to the system output, while SSPA#2 will be muted and directed to the “wasted” port.
Execute remote command BYP=1 to measure the individual gain of SSPA#2. This time, the output of SSPA#2 will be sent to the system output, while SSPA#1 will be muted and directed to the “wasted” port.
Compare the levels of the two paths. Typically, the gains of each SSPA will be within ± 1 dB at center frequency. If the above test is performed at other frequencies, it is reasonable to assume that the gain
Revision 2
3.4 Gain or Amplitude Balance Verification and Alignment
This procedure is generally not necessary if all parameters of Section 3.3 have been met.
As a result of the configuration of the waveguide switches in a 1+1 system, it is possible to measure the individual gain of each SSPA path by switching each SSPA individually to the output load.
This procedure assumes that the output port is terminated and that data will be taken using the Combined Output Power and Wasted Power Test Couplers (Figure 3-1).
Follow these steps:
Step Task
A. Attach a power meter to the Combined Output Test Coupler (Figure 3-1).
1
Prated.
waveguide switches via remote control (for detailed remote command and query information, see Chapter
2
A. Execute remote command RED=0; B. Execute remote command BYP=2.
3 Record the amplitude or gain level of SSPA#1.
4
5 Record the amplitude or gain level of SSPA#2.
6
difference may be greater.
Operation and Adjustment Procedures 3–9 MN-PCB-4000A
Page 38
PCB-4000A 1+1 Phase Combiner
Again, insure the input signal is at center frequency and that the output power level is approximately Prated
-10 dB.
Alternately toggle between remote commands BYP=1 and BYP=2 to measure the gains of each SSPA path. Note which path has the greater amount of gain.
Use the Amplitude Offset (AOF) remote command/query to equalize the gain between the 2 pa ths. For example, if SSPA 1 has 2 dB excess gain:
A. Query the offset of SSPA 1 using remote query AOF?1.
add 2 dB. For this example, assume SSPA 1 responded with 1 dB. Adding 2 dB of required additional offset to the existing 1 dB of offset results in 3 dB of required offset.
B. Now send remote command AOF=1,3.00.
Proceed to the Phase Alignment procedure (Section 3.6) if anything has been changed or altered that may
3.2.4.
Revision 2
3.5 A mplitude Alignment (as necessary)
Even if the difference of each individual SSPA path is greater than ±1 dB, amplitude adjustment may not be necessary to meet all parameters of Section 0. However, if these parameters have not been met, then fine tuning adjustment is advisable.
If the system is to be used in a narrow frequency range, you may also wish to optimize the gain balance over this narr ow range.
Follow these steps:
Step Task
1 If Steps 1 through 6 in Section 3.4 have not been completed, perform them now.
2
3
4
5
affect the phase alignment. Otherwise, verify proper operation via the LED Indicators as detailed in Section
The unit should respond with a gain offset ranging between 0 and 6. Record this value, and then
Operation and Adjustment Procedures 3–10 MN-PCB-4000A
Page 39
PCB-4000A 1+1 Phase Combiner
Ensure the system is set to 1+1 phase combined mode by issuing remote command RED=1 (see Chapter 5. SERIAL REMOTE CONTROL).
B. Apply a low-level signal at center frequency, making sure the output signal (at the system output port –
not the coupled port) will be at least 10 dB below Prated.
If the Wasted (“Load”) power level is 15-20 dB below the transmitted power, the system is operating correctly. However, if the ratio is below 10-15 dB, proceed to the align the phase shifter:
the transmitted and “wasted” power simultaneously, it is recommended to minimize the “wasted”
Verify that the system works over the full bandwidth by injecting a signal at the start and stop frequencies as
performance at any one particular frequency must be sacrificed slightly to achieve full bandwidth operation.
Make sure the lock nut on the phase shifter is tightly secured by using the supplied socket, and then replace the cover panel.
Revision 2
3.6 Phase A lignment
As the system is aligned at the factory, this step is typically not required unless it is necessary to replace one of the SSPAs or other critical path components. Make sure to meet all parameters of Section 0 before performing this adjustment.
This procedure assumes that the system installation is complete and that the output port terminates in a broadband high power load.
Verify the overall s ystem performance b y measuring the ratio of the transmitted po wer to that of the power being dissipated by the “dummy” load. If necessary, adjust the phase balance by trimming the phase sh ifter, which is located ins ide the PCCB box and acc essible via a secured cover labeled P HASE AD J on the left side of the box.
Follow these steps:
Step Task
1
A. Attach a power meter to the Combined Output Test Coupler (Figure 3-1).
2
C. Measure the output power and include the coupler correction factor. A. Attach a power meter to the Wasted (“Load”) Power Test Coupler (Figure 3-1).
3
B. Measure the power and include coupler correction factor.
A. Remove the PHASE ADJ cover panel (Figure 3-4) located on the left side of the PCCB box.
4
B. Utilizing the supplied socket and screwdriver, first loosen the phase shifter lock nut. C. Slowly adjust the phase shifter by turning the screwdriver. The system is aligned at the operating
frequency when the transmitted to “wasted” power ratio is maximized. If it is not possible to view power. Generally, the “wasted” power reading will be more sensitive to phase shifter adjustments.
A. Achieve the desired operating output power by slowly increasing the input power.
5
B. Verify the appropriate ratio of the transmitted to dissipated power once more.
well. The ratio of the transmitted to “wasted” power should be 15-20 dB, but is not likely to be as good as it
6
was at the adjustment (center) frequency. If acceptable full bandwidth performance is not measured, it may be necessary to repeat Steps 2 through 5 for the start, stop, and center frequencies – realizing that optimum
7
Operation and Adjustment Procedures 3–11 MN-PCB-4000A
Page 40
PCB-4000A 1+1 Phase Combiner
A. Attach a power meter to the Combined Output Test Coupler (Figure 3-1).
B. Measure the output power and include the coupler correction factor.
A. Attach a power meter to the Wasted (“Loa d” ) Power Test Coupler (Figure 3-1).
B. Measure the power and include the coupler correction factor.
Revision 2
3.7 System Online and Transmitting
This procedure assumes that the system installation is complete and that access to the system output port is unavailable due to current system traffic.
To check for proper operation, measure and compare the difference in power transmitted versus the power dissipated in the load termination.
Follow these steps:
Step Task
1
2
3 The Wasted (“Load”) power level should be 15-20 dB below the power being transmitted to the antenna.
Operation and Adjustment Procedures 3–12 MN-PCB-4000A
Page 41
PCB-4000A 1+1 Phase Combiner Revision 2
Chapter 4. UPDATING FIRMWARE
4.1 Update Firmware via the Internet
To ensure optimal performance, it is importa n t to op erate the PCB-4000A with its latest available firmware.
The PCB-4000A 1+1 Phase Combiner is factory-shipped with the latest version of operating firmware. If a fir mware update is needed, it can be acquired by d ownload from t he Comtech EF Data Web site (www.comtechefdata.com normal business hours, via e-mail or on CD by standard mail delivery.
The PCB-4000A Firmware Update process is as follows:
Ethernet FTP Upload
Download and Extract the Firmward Update
Firmware Upgrade
) or from Comtech EF Data Cus tomer Support, during
Updating Firmware 4–1 MN-PCB-4000A
Page 42
PCB-4000A 1+1 Phase Combiner
9600 or 19200 bps (Baud
Rate)
Revision 2
4.2 Ethernet FTP Upload Procedu re
4.2.1 Setup for the Firmware Download
Do these steps:
1. Locate and identify the exterior connectors on the Phase Combiner Control Box (PCCB).
2. Connect the PCB-4000A to a user-supplied PC.
User-supplied items needed:
A Microsoft Windows-based PC, equipped with an available serial port, and running a terminal emulator program (e.g., Tera Term or HyperTerminal).
A serial adapter cable for connecting the PC to the PCB-4000A. If needed, the CA/WR12243-1 System Programming Cable is available from Comtech EF Data. Contact CEFD Customer Support for ordering information.
Figure 4-1. Typical Unit to PC Connection
a. Connect the user PC serial port to the PCB-4000A “SYSTEM COM | J1” port. b. On the PC: Open the terminal emulator program.
Refer to your terminal emulator program HELP feature or user guide for operating and configuration instructions.
Configure the utility program serial port communication and terminal display operation:
8 Data Bits 1 Stop Bit
• Parity = NO • Port Flow Control = NONE • Display New line Rx/Tx: CR
• Local Echo = ON
c. Energize the PCB-4000A (the PCB-4000A derives its power from the SSPAs).
Updating Firmware 4–2 MN-PCB-4000A
Page 43
PCB-4000A 1+1 Phase Combiner Revision 2
3. Obtain the firmware number for the PCB-4000A.
On the PC: Via serial remote control, obtain the firmware number by using the
<1/FRW? query.
See Chapter 5. SERIAL REMOTE CONTROL for information and instructions on using remote commands and queries via the PCB-4000A Serial Interface.
4. Create a temporary folder (subdirectory) on the user PC for the firmware archive download.
Drive letter “c:” is used in these examples. Any valid, writable drive
letter can be used.
Typical for all tasks: Type the command withou t qu otes, and then press
Enter to execute.
There are several ways you may use create a temporary folder on a Windows-based PC: a. Use the Windows Desktop to create and rename the temporary folder.
Right-click anywhere on the desktop to open the popup submenu, and then select
New > Folder to create the temporary folder. The new folder will be created on the desktop.
Right-click on the new folder and then select “Rename” from the popup submenu.
Rename this folder to "temp" or some other convenient, unused name.
Figure 4-2. Temporary Folder Setup using Windows Desktop
Updating Firmware 4–3 MN-PCB-4000A
Page 44
PCB-4000A 1+1 Phase Combiner Revision 2
b. Use Windows Explorer to create and rename the temporary folder.
Select File > New > Folder to create the temporary folder. The new folder will be
created in the active folder.
Right-click the “New Folder” folder name, and then rename this folder to "temp" or
some other convenient, unused name.
Figure 4-3. Temporary Folder Setup using Windows Explorer
c. Use the ‘Run’ and ‘Browse’ windows to create and rename the temporary folder.
Select [Start] on the Windows task bar, and then click the Run... icon. The ‘Run
window will open.
Click [Browse] in the ‘Run’ window. The ‘Browse’ window will open.
Click the Create New Folder icon in the ‘Browse’ window. The new folder will be
created.
Right-click the “New Folder” folder name, and then rename this folder to “temp” or
some other convenient, unused name.
Figure 4-4. Temporary Folder Setup using ‘Run’ and ‘Browse’
Updating Firmware 4–4 MN-PCB-4000A
Page 45
PCB-4000A 1+1 Phase Combiner Revision 2
d. Use Windows Command-line to create the temporary folder.
First, click [Start] on the Windows taskbar, and then click the ‘Run...’ icon (or,
depending on Windows OS versions prior to Windows 95, click the ‘MS-DOS Prompt’ icon from the Main Menu).
Next, open a Command-line window…
o For Windows 95 or Windows 98 – Type “command”. o For any Windows OS versions later than Windows 98 – Type “cmd” or
command”.
o Alternately, from [Start], select All Programs > Accessories > Command
Prompt.
o Finally, from the Command-lin e ‘c:\>’ prompt, type “mkdir temp” or “md temp
(mkdir and md stand for make directory), and then click [OK].
Figure 4-5. Temporary Folder Setup using Windows Comma n d L ine
There should now be a "temp" folder created and available for placement of the firmware file download.
Updating Firmware 4–5 MN-PCB-4000A
Page 46
PCB-4000A 1+1 Phase Combiner Revision 2
4.3 Download and Extract the Firmware Update
1. First, download the firmware update file from the Comtech EF Data Web site: a. Go online to www.comtechefdata.com
b. On the Main page – under Support Information or the Support tab, select the Software
Downloads hyperlink.
c. On the Software Downloads page – click Download Flash and Software Update
Files.
d. On the Flash Updates Index page – select the (Select a Product Line) Amplifiers
hyperlink.
e. Under the PCB-4X00A heading, select the PCB-4000A (1+1 Phase Combiner) product
hyperlink.
f. Select the appropriate firmware archive EXE or ZIP file download hyperlink.
About Firmware Numbers, File Versions, and Formats: The Comtech EF Data Web site catalogues its firmware update files by product type (e.g., router, modem, etc.), the specific model, and optional hardware configurations.
The download hyperlink for the PCB-4000A base unit firmware appears as FW-0021045x.zip, where ‘x’ denotes the revision letter.
About File Archive Formats: Comtech EF Data provides its downloadable files in two compressed archive formats: *.exe (self­extracting) and *.zip (compressed).
The *.exe file does not require a file archiver and compression utility program such as PKZIP for Windows, WinZip, ZipCentral, etc. (PKZIP for DOS is not supported due to file naming conventions). Comtech EF Data
does not provide this utility program.
Some firewalls do not allow the download of *.exe files. Download the *.zip file instead, and extract the firmware files from the archive download with a user-supplied utility program. For detailed information on handling archived files, refer to the utility program Help documentation.
g. Download the firmware archive file to the temporary folder.
Once the EXE or ZIP hyperlink is selected the ‘File Download’ window opens and prompts selection of [Open] or [Save]:
o Click [Open] to turn over file extraction to the user-supplied utility program . Be
sure to extract the firmware files to the “temp” folder created earlier.
o Click [Save] to open the ‘Save As’ window. Be sure to select and [Save] the
archive *.exe or *.zip file to the “temp” folder created earlier.
o Otherwise, click [Cancel] to quit and exit the file download process.
.
Updating Firmware 4–6 MN-PCB-4000A
Page 47
PCB-4000A 1+1 Phase Combiner Revision 2
Figure 4-6. Download Firmware Archive File
2. Extract the firmware files from the archive file. a. (If not already done with File Download > [Open]) Extract the firmware files from the
downloaded *.exe or *.zip archive file with the user-supplied utility program:
b. Double-click on the archive file name, and then follo w the prom pts provided by the user-
supplied utility program. Extract, at a minimum, four files:
FW-0021045*_Bulk_v*_*_*.zip, where “*_*_*” is the version (bulk image file).
FW10874-2-.mib (Comtech EF Data MIB file)
FW-0021047*.mib (PCB-4X00A MIB file), where “*” is the r evi s io n.
PCB-4X00A_ReleaseNotes_v*_*_*.doc, where “*” is the version (release notes).
3. Confirm availability of the firmware files in the temporary folder. There are several ways you may view the con tents of the temporary folder on a W indows-
based PC. a. From the Windows Desktop:
Double-left-click the “temp” folder saved to the Windows Desktop.
Use Windows Explorer to locate, and then double-left-click the “temp” folder.
Use the ‘Browse’ window ([Start] > ...Run > [Browse]) to locate, and then double-
click the “c:\temp” folder.
b. Using Command-line:
Typ e “cd c:\temp” at th e C omm and-line prompt to cha nge to the tem por ary dir ector y created earlier using Command-line.
Type “dir” to list the files e xtracted to the temporary director y from the downloaded archive file.
The firmware files have been successfully downloaded and are now available for transfer to the PCB-4000A.
Updating Firmware 4–7 MN-PCB-4000A
Page 48
PCB-4000A 1+1 Phase Combiner Revision 2
4.4 Firmware Upgrade
1. With the System Programming cable (CEFD P/N CA/WR12243-1) connected, verify the communication and connection by issuing a “ping” command to the modem.
a. Locate the IP address of the unit remotely by using <1/IPA?. b. Select the “Start” button on the Windows toolbar and select the “Run…” option. c. From WinXP or Windows7, t ype “cmd” or use the “DOS Prompt” or “Command
Prompt” icons in the Start Menu. d. Change the temporary directory created earlier to “cd C:\temp”. e. Use “dir” to show the files previously downloaded.
2. Initiate an FTP session with the unit using a DOS window. a. Using the PC, type “ftp xxx.xxx.xxx.xxx” where “xxx.xxx.xxx.xxx” is the IP
address of the unit, obtained previously in step 1.a.
b. Type “comtech” for the user name and “comtech” for the password to complete
the login. c. Verify the FTP transfer is binary by typing “bin”. d. Type “prompt”, then type “hash” to initiate the file transfers.
3. Type “put FW-0021045*_Bulk_v*_*_*.zip” to begin the file transfers.
4. Type “bye” and close the DOS window to terminate the FTP session.
5. Verify the FTP upgrade using <1/SWR? serial remote command.
6. Change the desired image to boot using the <1/IMG=X serial remote command, where X is 1 or 2, and then reboot the unit.
7. Verify the new software versions are booting by using <1/RET? The serial remote command response:
PCB-4X00A Phase C om b i n er Ver: X.X .X.
8. Disconnect the System Programming cable (CEFD P/N CA/WR12243-1) and reconnect the original System Communications connection cable.
9. The LEDs on the top of the PCCB may illuminate GREEN (unmuted), ORANGE (muted), or RED (faulted) to indicate the current status of the PCCB, SSPA1, and SSPA2 operations.
See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES, Section
3.2.4, for additional information on the LED operation states .
The PCB-4000A Firmware Update Process is now complete.
Updating Firmware 4–8 MN-PCB-4000A
Page 49
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–1 MN-PCB-4000A
Chapter 5. SERIAL REMOTE CONTROL
5.1 Overview
Remote monitor and control of the PCB-4000A 1+1 Phase Combiner is available only through an EIA-232 connection, and data is transmitted in asynchronous serial form using ASCII characters. Control and status information is transmitted in packets of variable length, in accordance with the structure and protocol defined in later sections.
5.1.1 EIA-232
The Controller device connects directly to the Target via a two-wire-plus-ground connection. Controller-to-Target data is carried, via EIA-232 electrical levels, on one conductor, and Target-to-Controller data is carried in the other direction on the other conductor.
Page 50
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–2 MN-PCB-4000A
5.2 Remote Command s a nd Q ue ri es Ovierview
5.2.1 Basic Protocol
All data is transmitted as asynchronous serial characters, suitable for transmission and reception by a UART. The asynchronous character is fixed at 8-N-1 (8 data bits, no parity, one stop bit). Only two baud rates are supported: 9600 baud and 19200 baud.
All data is transmitted in framed packets. The host Controller is assumed to be a user PC running a terminal emulator program or an ASCII dumb terminal that is in charge of the process of monitor and control. The Controller is the only device that is permitted to initiate, at will, the transmission of data. Targets are only permitted to transmit when they have been specifically instructed to do so by the Control ler.
All bytes within a packet are printable ASCII characters, less than ASCII code 127. In this context, the Carriage Return and Line Feed characters are considered printable.
All messages from Controller-to-Target require a response – with one exception: This will be either to return data that has been requested by the Controller, or to acknowledge reception of an instruction to change the configurati on of the Target.
Page 51
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–3 MN-PCB-4000A
5.2.2 Packet Structure
Controller-to-Target
Start of Packet
Target Address
Address Delimiter
Instruction Code
Code Qualifier
Optional Arguments
End of Packet
<
ASCII code 60
(1 character)
(4 characters)
/
ASCII code 47
(1 character)
(3 characters)
= or ?
ASCII codes 61 or 63
(1 character)
(n characters)
Carriage Return
ASCII code 13
(1 character)
Example: <0412/MUT=1{CR}
Target-to-Controller
Start of Packet
Target Address
Address Delimiter
Instruction Code
Code Qualifier
Optional Arguments
End of Packet
>
ASCII code 62
(1 character)
(4 characters)
/
ASCII code 47
(1 character)
(3 characters)
=, ?, !, or *
ASCII codes
61, 63, 33, or 42
(1 character)
(From 0 to n
characters)
Carriage Return, Line
Feed
ASCII codes 13,10
(2 characters)
Example: >0412/MUT={CR}{LF}
5.2.2.1 Start of Packet
Controller-to-Target – This is the character ‘<’ (ASCII code 60).
Target-to-Controller – This is the character ‘>’ (ASCII code 62).
Because this is used to provide a reliable indication of the start of packet, these two characters may not appear anywhere else within the body of the message.
Page 52
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–4 MN-PCB-4000A
5.2.2.2 Target (Base) A ddress
Up to 9,999 devices can be uniquely addressed. In the EIA-232 application, the permissible range of values is 1 to 9999. It is programmed into a Target unit using serial remote control. The factory default target address is 1.
The Controller sends a packet with the address of a Target – the destination of the packet. When the Target responds, the address used is the same address, to indicate to the Controller the source of the packet. The Controller does not have its own address.
5.2.2.3 Virtual Address
Virtual Address is a method th at allows t he user to ac cess the SSPA via the PCC B using any communic ations softwar e. Virtual Address is supported in the EIA-232 application.
The following example depicts use of the virtual addressing scheme:
<123V1/MUT? where:
Base address = 123; ‘V’ = virtual address delimiter; 1 = virtual address of SSPA automatically set by the PCCB.
Notes:
1. Only four virtual commands can be used to program the individual SSPAs when in Phase Combined mode (RED=1):
CAA=
DAT=
TIM=
IAP=
2. All virtual queries can be directed to the individual SS PAs in any mode.
3. The following virtual commands can NEVER be used to program the individual SSPAs:
MUT=
ATT=
Page 53
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–5 MN-PCB-4000A
5.2.2.4 Address Delimiter
This is the “forward slash” character '/' (ASCII code 47).
5.2.2.5 Instruction Code
This three-character alphabetic sequence identifies the subject of the message. Wherever possible, the instruction codes have been chosen to have some significance. This aids in the readability of the message if seen in its raw ASCII form. Upper and lower case alphabetic characters (i.e., A-Z [ASCII codes 65-90], and a-z [ASCII codes 97-122]) may be used.
5.2.3 Instruction Code Qual ifie r
This single character further qualifies the preceding instruction code. Code Qualifiers obey the following rules:
1. From Controller-to-Target, the only permitted values are:
Symbol
Definition
= (ASCII code 61)
‘=’ is used as the assignment operator, and is used to indicate that the parameter defined by the preceding byte should be set to the
value of the argument(s) that follow it. For example: MUT=1 would mean 'enable the Mute function.'
? (ASCII code 63)
‘?’ is used as the query operator, and is used to indicate that the Target should return the current value of the parameter defined by
the preceding byte. For example: MUT? Would mean ‘return the current state of the Mute function.’
2. From Target-to-Controller, the only permitted values are:
Symbol
Definition
=
(ASCII code 61)
The = code is used in two ways: First, if the Controller has sent a query code to a Target (for example: MUT? would mean ‘return the current state of the Mute
function’), the Target would then respond with MUT=x, where ‘x’ represents the state in question (1 being ‘enabled’, 2 being ‘disabled). Second, if the Controller sends an instruction to set a parameter to a particular value, then, providing the value sent in the argument is
valid, the Target will acknowledge the message by replying with MUT= (with no message arguments).
Page 54
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–6 MN-PCB-4000A
Symbol
Definition
?
(ASCII code 63)
The ? code is only used as follows: If the Controller sends an instruction to set a parameter to a particular value, then, if the value sent in the argument is not valid, the
Target will acknowledge the message by replying (for example) with MUT? (with no me ssage arguments). This indicates that there was an error in the argument of the message sent by the Controller.
!
(ASCII code 33)
The ! code is only used as follows: If the Controller sends an instruction code that the Target does not recognize, the Target will acknowledge the message by echoing the
invalid instruction, followed by the ! character; for example, XYZ!
*
(ASCII code 42)
The * code is only used as follows: If the Controller sends an instruction to set a parameter to a particular value, but then the value sent in the argument is valid but the
target is in the wrong mode (e.g., Standby mode in Redundancy configuration or the Remote state is Ethernet Remote (LRS=3)), such that it will not permit that particular parameter to be changed at that time, the Target will acknowledge the message by replying ( for example) with MUT* (with no message arguments).
#
ASCI code 35)
The # code is only used as follows: If the controller sends an instruction code that the target cannot currently perform because of hardware resource issues, then the target
will acknowledge the message by echoing the invalid instruction, followed by the # character; for example, MUT# (with no message arguments).
5.2.4 Optional Message Arguments
Arguments are not required for all messages. Arguments are ASCII codes for the characters 0 to 9 (ASCII codes 48 to 57), period (ASCII code 46) and comma (ASCII code 44).
5.2.5 End of Packet
Controller-to-Target – This is the ‘Carriage Return’ character (ASCII code 13).
Target-to-Controller – This is the two-character sequence ‘Carriage Return’, ‘Line Feed’ (ASCII codes 13 and 10).
Both indicate the valid termination of a packet.
Page 55
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–7 MN-PCB-4000A
5.3 Remote Commands / Que rie s
Index Notes: Column ‘ C’ = Comman d; Column ‘Q’ = Qu ery; co lumns mar ked ‘X’ designate instruction code as Command only, Query only, or
Command/Query.
CODE C Q PAGE CODE C Q PAGE CODE C Q PAGE CODE C Q PAGE
AMP X X 5–8 FBR X - 5–15 RAS - X 5–11 SPA X X 5–13 AOF X X 5–8 FRW - X 5–10 RCM X X 5–13 STA X X 5–15
ATT X X 5–8 IAP X - 5–13 RCS - X 5–11 STB X X 5–15
BYP X X 5–8 IMG X X 5–15 RED X X 5–12 STV X X 5–16 CAA X - 5–8 IPA X X 5–14 RET - X 5–12 SWR - X 5–15 CAS - X 5–9 IPG X X 5–14 RFD X - 5–16 TIM X X 5–13 CCS - X 5–9 LNA - X 5–10 RMS - X 5–12 TNA - X 5–13
CID X X 5–9 LRS X X 5–13 RSN - X 5–12 TPE X X 5–16 CMS - X 5–9 MAC - X 5–14 RUS - X 5–12 TPS X X 5–16 CUS - X 5–10 MUT X X 5–10 SBR X X 5–12 TSC - X 5–15
DAT X X 5–10 PNG X X 5–14 SFS - X 5–13 WCM X X 5–14
Unless otherwise noted – In the tables that follow, these codes are used in the ‘Response to Command’ column
= Message ok ? Received ok, but invalid arguments were found * Message ok, but not permitted in current mode
Page 56
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–8 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
RF Power
Amplifier State
AMP=
PCB
1 byte,
value of 0, 1
Command or Query.
Turns ON or OFF the SSPAs in the form AMP=x, where:
0 = Off 1 = On
AMP=
AMP? AMP* AMP#
AMP?
ALL
AMP=x
(see Description of Arguments for details)
Attenuation
Offset
AOF=
PCB
7 bytes,
alphanumeric
Command or Query.;
Sets attenuation offset for specified SSPA Command: AOF=x,yy.yy where:
x=0 or 1 (SSPA number) yy.yy=Attenuation offset
Query: AOF?
Example: AOF=1,01.50
Note: AOF command will not take values greater than 6 dB)
AOF=
AOF? AOF* AOF#
AOF?
PCB
AOF=x,yy.yy
(see Description of Arguments for details)
Attenuation
ATT=
PCB
5 bytes,
numerical
Command or Query.
Valid attenuation level, in dB, at 0.25-dB step size as factory default.
Example: ATT=12.25 Note: The attenuation range is limited to a maximum of 24 dB.
ATT=
ATT? ATT* ATT#
ATT?
ALL
ATT=xx.xx
(see Description of Arguments for details)
Bypass SSPA
BYP=
PCB
1 byte
value of 0, 1 or 2
Command or Query.
Command: BYP=a, where:
a = 0 (No SSPA is bypassed)
1 (SSPA #1 is bypassed) 2 (SSPA #2 is bypassed)
• Command bypasses the SSPA specified by argument.
• Command works only in RED=0 mode.
Query: BYP?
Query returns the number of the SSPA that is currently bypassed or offline.
Query works in any RED mode.
BYP=
BYP? BYP* (received ok but in the wrong RED mode)
BYP?
PCB
BYP=a
(see Description of Arguments for details)
Clear All
Stored Alarms
CAA=
ALL
None
Command only.
Instructs the slave to clear all Stored Events.
This command takes no arguments.
CAA= N/A N/A
N/A
Page 57
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–9 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Concise
Alarm Status
N/A
N/A
11 bytes
numerical with commas
Query only.
Used to Query the Alarm status of the unit, response is comma delimited. Example: CAS=a,b,c,d,e,f,g’cr’’lf’ where:
a thru k = 0 or 1, 0 = OK 1 = FT a = +24V Power Supply b = +5V Power Supply c = SSPA1 d = SSPA2 e = reserved f = SW1 Absent FLT
g = SW2 Absent FLT
N/A
CAS?
ALL
(Check SSPA manual for arguments returned from SSPA)
CAS=x….x
(see Description of Arguments for details)
Concise
Configuration Status
N/A
N/A
24 bytes
numerical
Query only.
Used to query the summarized version of RCS. Example: CCS=aa.aa,b,c,d,e,f,g’cr’’lf’ where:
aa.aa = attenuation in dB b = RF power amplifier state c = mute state d = redundancy/phase combine mode
e,f,g = SSPAs fault status (g is reserved (X))
N/A
CCS?
SSPA
(per MBT manual)
CCS=x….x
(see Description of Arguments for details)
Circuit
Identification
CID=
PCB
24 bytes,
alphanumeric
Command or Query.
Used to identify or name the unit or station. First line is limited to 24 characters. Second line is also limited to 24 characters. No carriage return between first line and second line.
CID=
CID?
CID?
ALL
CID=x…x
(see Description of Arguments for
details)
Concise
Maintenance Status
N/A
N/A
16 bytes
numerical
Query only.
Used to Query the Maintenance status of the unit in concise format. Response is comma delimited. Example: CMS=aa.a,b.b,c.c,d.d’cr’’lf’ where:
aa.a = +24V Power Supply b.b = +5V Power Supply c.c = +3.3V Power Supply
d.d = +1.5V Power Supply
N/A
CMS?
ALL
(Check SSPA manual for arguments returned from SSPA)
CMS=x….x
(see Description of Arguments for details)
Page 58
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–10 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Concise
Utility Status
N/A
N/A
11 bytes
alphanumeric
Query only.
Used to Query the Maintenance status of the unit, response is comma delimited. Example: CUS=aaaa,bbbb’cr’’lf’ where:
aaaa = Remote Unit Address bbbb = Remote Baud Rate
N/A
CUS?
ALL
(Check SSPA manual for arguments returned
from SSPA)
CUS=x….x
(see Description of Arguments for details)
Set
RTC(Real­Time-Clock) Date
DAT=
ALL
6 bytes,
numerical
Command or Query.
A command in the form mmddyy, where; dd = day of the month, between 01 and 31, mm = month of the year, between 01 and 12 and yy = year, between 00 and 99 (2000 to 2099)
Example: DAT=042503 would be April 24, 2003
DAT=
DAT? DAT*
DAT?
ALL
DAT=xx
(see Description of Arguments for details)
Retreive
Firmware Number
N/A
N/A
32 bytes
Query only.
Gets the Firmware Numbers of the unit. Example: FRW=’cr’
BULK=FW-0021045’cr’
MnC =FW-0021046’cr’’lf’
N/A
FRW?
ALL
FRW= x….x
(see Description of Arguments for details)
Retrieve next
5 unread Stored Alarms
N/A
N/A
145 bytes
Query only.
The unit returns the oldest 5 Stored Events which have not yet been read over the remote control. Reply format: Sub-body{CR}Sub-body{CR}Sub-
body{CR}Sub-body{CR}Sub-body, where Sub-body= YYYYYYYYYY ZZ mmddyy hhmmss, where:
YYYYYYYYYY being the fault description. ZZ being the alarm type.
FT = Fault OK = Clear IF = Information
If there are no new events, the unit will reply with LNA*
N/A
LNA?
SSPA
LNA=YY..ss
(see Description of Arguments for details)
Mute State
MUT=
PCB
1 byte,
value of 0,1
Command or Query.
Mute the SSPAs, where:
0 = Disabled, 1 = Enabled 2 = Inhibit asserted (Query only)
Example: MUT=1
MUT=
MUT? MUT*
MUT?
ALL
MUT=x
(see Description of Arguments for details)
Page 59
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–11 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Retrieve
Alarm Status
N/A
N/A
53 bytes
alphanumeric
Query only.
Used to Query the Alarm status of the unit. Example: RAS=’cr’
P24VT=OK’cr’ P5VLT=OK’cr’ SSPA1=OK’cr’ SSPA2=OK’cr’ SSPA3=NA’cr’ SW1FT=OK’cr’
SW2FT=OK’’cr’’lf’
N/A
RAS?
ALL
(Check SSPA manual for arguments returned from SSPA)
RAS=x….x
(see Description of Arguments for details)
Retrieve
Configuration Status
N/A
N/A
33 bytes
alphanumeric
Query only.
Used to Query the configuration status. Example: RCS=’cr’
ATT=12.75’cr’ AMP=1’cr’ MUT=1’cr’ PCM=1,0’cr’ FLT=0,0,X’cr’’lf’ where: ATT= attenuation in dB AMP= RF power amplifier state, 0=OFF, 1=ON MUT=RF mute state, 0=unmuted, 1=muted PCM=Redundancy/Phase Combined mode,
0 = off 1 = 1:1 phase combine 2 = 1:2 phase combine (future) 3 = reserved 4 = reserved
FLT=X,Y,Z -> SSPAs fault state
X = SSPA#1 (1=faulted, 0=unfaulted) Y = SSPA#2 (1=faulted, 0=unfaulted)
Z = reserved (X)
N/A
RCS?
SSPA
(per MBT manual)
RCS=x….x
(see Description of Arguments for details)
Page 60
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–12 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Redundancy
/Phase Combine Mode
RED=
PCB
1 byte,
value of 0, 1,2,3
Command or Query.
Set the redundancy/phase combine mode.
0 = Off 1 = 1:1 Phase combined 2 = reserved 3 = reserved
4 = reserved
RED=
RED?
RED?
PCB
RED=x
(see Description of Arguments for details)
Retrieve
Equipment Type
N/A
N/A
35 bytes,
alphanumeric
Query only.
The unit returns a string indicating the Model Number and the value of internal software revision installed. Example: PCB-4000A Phase Combiner Ver: 1.1.1
N/A
RET?
ALL
RET=x….x
(see Description of Arguments for
details)
Retrieve
Maintenance Status
N/A
N/A
42 bytes,
alphanumeric
Query only.
Used to Query the maintenance status of the unit.
P24VT=23.5’cr’ P05VT=4.8’cr’ P03VT=3.3’cr’ P01VT=1.5’cr’’lf’
N/A
RMS?
ALL
(Check SSPA manual for arguments returned
from SSPA)
RMS=x….x
(see Description of Arguments for details)
Serial
Number
N/A
PCB
9 bytes,
numerical 000000000 to 999999999
Query only.
Used to Query the units 9 digit serial number. Slave returns its S/N, in the form xxxxxxxxx. Example: RSN=000000165
N/A
RSN?
ALL
RSN=xxxxxxxx
x (see Description of Arguments for
details)
Retrieve
Utility Status
N/A
N/A
17 bytes
alphanumeric
Query only.
Used to Query the utility status of the unit Example: RUS=’cr’
ADR=0001’cr’ BDR=9600’cr’’lf’
N/A
RUS?
ALL
(Check SSPA manual for arguments returned
from SSPA)
RUS=x….x
(see Description of Arguments for details)
Remote Baud
Rate
SBR=
PCB
4 bytes
Command or Query.
Set remote baud rate as follows:
9600 = 9600 baud 19K2 = 19200 baud
SBR=
SBR? SBR#
SBR?
PCB
SBR=xx
(see Description of Arguments for
details)
Page 61
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–13 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Summary
Fault Status
N/A
N/A
1 byte,
value of 0,1
Query only.
Used to Query the status of the Summary Fault Relay. Example: SFS=0 where:
0 = OK 1 = FT
N/A
SFS?
SSPA
SFS=x
(see Description of Arguments for details)
Remote
Address
SPA=
PCB
4 bytes,
numerical
Command or Query.
Set Physical Address-between 0001 to 9999. Resolution 0001
Example: SPA=0412
Default: 1
SPA=
SPA?
SPA?
PCB
SPA=x
(see Description of Arguments for details)
Set RTC Time
TIM=
ALL
6 bytes,
numerical
Command or Query.
A command in the form hhmmss, indicating the time from midnight, where hh = hours, between 00 and 23; mm = minutes, between 00 and 59, and ss = seconds, between 00 and 59 Example: TIM=231259 would be 23 hours, 12 minutes and 59
seconds past midnight.
TIM =
TIM? TIM *
TIM?
ALL
TIM=xx
(see Description of Arguments for details)
Retrieve
Number of unread Stored Alarms
N/A
N/A
2 bytes,
numerical
Query only.
Returns the number of Stored Events which remain unread, in the form xx. Example reply: TNA=18
N/A
TNA?
SSPA
TNA=xx
(see Description of Arguments for
details)
Initialize
Stored Alarms Pointer
IAP=
ALL
None
Command only.
Resets internal pointer to allow LNA? Query to start at the beginning of the stored alarms log.
IAP=
IAP? IAP*
N/A
N/A
N/A
Remote State
LRS=
PCB
1 byte, value of
1 or 3
Command or Query.
Used set the user’s Remote state in the form x, where:
1=Serial Remote (RS-232) 3=Ethernet Remote
Example: LRS=1 (selects Serial Remote)
LRS
LRS? LRS* LRS#
LRS?
PCB
LRS=x
(see Description of Arguments)
SNMP Read
Community String
RCM=
PCB
Up to 20
characters, no spaces
Command or Query.
Sets or returns the SNMP Read Community string.
Example: RCM=public
Notes: Empty string is not allowed.
RCM=
RCM? RCM#
RCM?
PCB
RCM=x…x
(see Description of Arguments)
Page 62
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–14 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
SNMP Write
Community String
WCM=
PCB
Up to 20
characters, no spaces
Command or Query.
Sets or returns the SNMP Write Community string.
Example: WCM=private
Notes: Empty string is not allowed
WCM=
WCM? WCM#
WCM?
PCB
WCM=x…x
(see Description of Arguments)
IP Address
IPA=
PCB
18 bytes
numerical
Command or Query.
Used to set the IP Address and network prefix for the 10/100 Base T Ethernet management port, in the form aaa.bbb.ccc.ddd.yy, where permitted ranges are:
aaa = 0-223 bbb = 0-255 ccc = 0-255 ddd = 001-255 yy=08-30
Example: IPA=010.006.030.001.24
Default: 192.168.1.4.24
IPA=
IPA? IPA*
IPA?
PCB
IPA=
aaa.bbb.ccc.dd d.yy (see Description of Arguments)
IP Gateway
IPG=
PCB
15 bytes
numerical
Command or Query.
Used to set the IP Gateway Address for the Ethernet management port, in the form aaa.bbb.ccc.ddd, where permitted ranges are:
aaa = 0-223 bbb = 0-255 ccc = 0-255 ddd = 001-255
Example: IPG=010.006.030.001
Default: 192.168.1.5
IPG=
IPG? IPG* IPG#
IPG?
PCB
IPG=
aaa.bbb.ccc.dd d (see Description of Arguments)
MAC Address
N/A
N/A
12 bytes, alpha-
numerical
Query only.
Used to query the unique MAC Address for the modem. Example: MAC=0006B00001C2
N/A
MAC?
PCB
MAC=aabbccd
deeff (see Description of
Arguments)
Ping Reply
Enable
PNG=
PCB
1 byte, value of
0 or 1
Command or Query.
Used to Enable or Disable Ping reply in the form x, where:
0=Disable Ping Reply 1=Enable Ping Reply
PNG=
PNG? PNG*
PNG?
PCB
PNG=x
(see Description of Arguments)
Page 63
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–15 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
Software
Revision
N/A
N/A
32 bytes
Query only.
Unit returns the firmware information for Boot, Image 1 (Bulk1) and Image 2 (Bulk2) installed in the unit.
Example: SWR=Boot:1.1.1Bulk1:1.1.1Bulk2:1.1.1
N/A
SWR?
PCB
SWR=x...x
(see description of arguments)
Software
Image
IMG=
N/A
1 byte, value of
1 or 2
Command or Query.
Used to set the active software image for the next reboot in the form x, where:
1=Boot from Bulk Image #1 for next reboot
2=Boot from Bulk Image #2 for next reboot
IMG=
IMG? IMG* IMG#
IMG?
PCB
IMG=x
(see Description of Arguments)
Force Reboot
FRB=
PCB
None
Command only.
Force a hard reset of the unit in 5 seconds.
FRB=
FRB? FRB*
FRB#
N/A
N/A
N/A
Terminal
Status Change
N/A
N/A
1 byte, value of
0 or 1
Query only.
Unit returns the configuration change state since last time it’s queried in the form x, where:
0=Unit configuration has not been changed since last query.
1=Unit configuration has been changed since last query.
N/A
TSC?
PCB
TSC=x
(see Description of Arguments)
SNMP Trap
Destination IP Address 1
STA=
PCB
15 bytes,
Numerical
Command or Query.
Used to set the IP address of the first SNMP Trap destination IP Address 1 Where traps will be sent in the form:
xxx.xxx.xxx.xxx is the IP addresss
Example:
<1/STA=010.006.030.001
When not configured, returns >0001/STA=0.0.0.0
STA=
STA!
STA=xxx.xxx.x
xx.xxx
(See description of arguments)
PCB
STA=xxx.xxx.x
xx.xxx
(See description of arguments)
SNMP Trap
Destination IP Address 2
STB=
PCB
15 bytes,
Numerical
Command or Query.
Used to set the IP address of the first SNMP Trap destination IP Address 2 Where traps will be sent, in the form:
xxx.xxx.xxx.xxx is the IP addresss
Example:
<1/STB=010.006.030.001
When not configured, returns >0001/STB=0.0.0.0
STB =
STB!
STB?
PCB
STB=xxx.xxx.x
xx.xxx
(See description of arguments)
Page 64
PCB-4000A 1+1 Phase Combiner Revision 2
Serial Remote Control 5–16 MN-PCB-4000A
Parameter
Type
Command
(Instruction
Code and
qualifier)
Command
Valid for
PCB or
SSPA
Arguments for
Command or
Response to
Query
Description of Arguments
(Note that all arguments are ASCII numeric codes – i.e.,
ASCII codes between 48 and 57)
Response to
Command
(Target to
Controller)
Query
(Instruction
Code and
qualifier)
Query Valid
for PCB or
SSPA
Response to
Query
(Target to
Controller)
SNMP
Trap Version
STV=
PCB
1 byte
Command or Query.
SNMP Trap Version that will be used to send traps.
1 = SNMP Trap Version 1 2 = SNMP Trap Version 2
Example: <1/STV=0
STV =
STV!
STV?
PCB
STV =x
(See description of arguments)
Time Protocol
Enable
TPE=
PCB
1 byte,
numerical
Command or Query.
0 = Time protocol disabled 1 = Time protocol enabled
Example: TPE=1 (Time protocol enabled)
Default Value: 255 or 0
TPE=
TPE?
TPE?
PCB
TPE=x
(see description of arguments)
Time Protocol
Server
TPS=
PCB
15 bytes,
alpha-numeric
Command or Query.
Used to set the Time Server IP address for the Unit. Tx Ethernet management port, in the format: xxx.xxx.xxx.xxx, where: xxx.xxx.xxx.xxx is the Time server IP address
Example: TPS=192.168.001.005
Default Value: 255.255.255.255 or 0.0.0.0
TPS=
TPS?
TPS?
PCB
TPS=
xx.xxx.xxx.xxx. yy (see description of arguments)
Restore
Factory Defaults
RFD=
PCB
None
Command only.
Restores factory defaults in the NVRAM
Example: RFD=’cr’
RFD=
RFD?
RFD*
N/A
PCB
N/A
Page 65
PCB-4000A 1+1 Phase Combiner
PROCEED WITH ETHERNET-BASED REMOTE PRODUCT MANAGEMENT ASSUMING
connector.
Revision 2
Chapter 6. ETHERNET-BASED
REMOTE PRODUCT
MANAGEMENT
6.1 Overview
Ethernet-based Remote Product Management is available using the SYSTEM COM | J1 connector.
THAT:
The PCB-4000A is operating with the latest version firmware files.
The PCB-4000A is connected to a user-supplied, Windows-based PC, and:
o The PC Ethernet port is connected to the PCB-4000A SYSTEM COM | J1
6.2 Ethernet Management Interface Protocols
The user PC facilitates access to Ethernet-based remote monitor and control (M&C) of the PCB-4000A through the Simple Network Management Protocol (SNMP). This non-secure interface requires a user-supplied Network Management System (NMS) and a user-supplied Management Information Base (MIB) File Browser.
SNMP user interface is only available when the unit’s Local/Remote state is set to Ethernet Remote through LRS serial remote command (LRS=3).
6.3 SNMP Interface
The SNMP is an Internet-standard protocol for managing devices on IP networks. An SNMP managed network consists of three key components:
The managed device. This includes the PCB-4000A.
The SNMP Agent. The software that runs on the PCB-4000A. The SNMP Agent
supports both SNMPv1 and SNMPv2c.
The user-supplied NMS. The software that runs on the manager.
Ethernet-based Remote Product Management 6–1 MN-PCB-4000A
Page 66
PCB-4000A 1+1 Phase Combiner
MIB File/Name (where ‘x’ is revision letter)
FW-0021074*.mib
ComtechEFData MIB file gives the root tree for ALL Comtech EF Data products
Module: ComtechEFData
FW-0021047*.mib
PCB-4X00A MI B file
FW-0021048*.mib
PCB-4X00A MI B file
CAUTION – In SNMP v1/v2c, the SNMP Community String is sent unencrypted in
security is a concern.
information on the required FW/SW compatib ility.
Revision 2
6.3.1 Management Information Base (MIB) Files
MIB files are used for SNMP remote management of a unique device. A MIB file consists of a tree of nodes called Object Identifiers (OIDs). Each OID provides remote management of a particular function. These MIB files should be compiled in a user-supplied MIB Browser or SNMP Network Monitoring System server. The following MIB files are associated with the PCB-4000A:
Table 6-1. Management Information Base Files
Description
ComtechEFData MIB file
and consists of only the following OID:
Name: comtechEFData Type: MODULE-IDENTITY OID: 1.3.6.1.4.1.6247 Full path:
iso(1).org(3).dod(6).internet(1).private(4).enterprises(1).comtechEFData(6247)
MIB file consists of all of the OIDs for management of the unit functions.
MIB file consists of all of the OIDs for traps of the unit functions.
6.3.2 SNMP Community Strings
the SNMP packets. Caution must be taken by the network administrator to ensure that SNMP packets travel only over a secure and private network if
The PCB-4000A uses Community Strings as a password scheme that provides authentication before gaining access to the Agent MIBs. They are used to authenticate users and determine access privileges to the SNMP Agent.
Type the SNMP Community String into the us er -supplied MIB Browser or Network Node Management software.
Two Comm unit y Strings are defined for SNMP access:
Read Community default = public
Write Community default = private
The Read and Write Community Strings can be conf igured using serial remote comm and RCM and WCM when remote state is at Serial Remote.
For proper SNMP operation, the PCB-4000A MIB files must be used with the associated version of the unit. Refer to the PCB-4000A FW Release Notes for
Ethernet-based Remote Product Management 6–2 MN-PCB-4000A
Page 67
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–1 MN-PCB-4000A
Appendix A. ASSEMBLY KITS
A.1 Overview
This appendix provides a reference to the Comtech EF Data accessory and assembly kits that satisfy installation requirements for a PCB­4000A 1+1 Phase Combined System – an example is shown as Figure A-1.
The PCB-4000A 1+1 Phase Combiner stand alone unit is available in a C-Band version only. Contact Comtech EF Data for X-Band or Ku-Band versions. The PCCB may be available as a top assembly line item or as a kit subassembly item.
Page 68
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–2 MN-PCB-4000A
Figure A-1. PCB-4000A 1+1 Phase Combined System
Page 69
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–3 MN-PCB-4000A
A.1.1 Summary of Av ailable Assemblies
Table A-1 outlines availability of assembly kits for the PCB-4000A. This includes common subassemblies that may be shared amongst the available configurations. Note that since the model of the SSPA pair deployed within a 1+1 Phase Combined System may vary, the illustrations provided herein either show installed SSPAs for reference purposes only, or otherwise intentionally omit the depiction of any installed SSPA.
Table A-1. Appendix Figure Quick Reference
Assembly
Type
Sect. CEFD Part No. Description
C-Band
A.2.1 KT-0000055 C-Band 1+1 Phase Combined HPOD Top Assembly Kit A.2.2 KT-0021171
C-Band 1:1 Phase Combiner Box and Bracket Kit
(Item No. 3 of KT-0000055 Top Assembly Kit)
A.2.3 KT-0000054
C-Band 1:1 Phase Combined Waveguide and Switches, HPOD
(Item No. 4 of KT-0000055 Top Assembly Kit)
A.2.4 KT-0021179 Vertical Mounting Frame Kit
Not Shown
PL-0022667
C-Band 1:1 Combiner Box
(Item No. 9 of KT-0021171)
Common
A.3.1 PL/12319-1
HPOD 1:1 Redundancy Pole Mount Kit.
(Use in connection with KT-0000055 Top Assembly Kit)
A.3.2 KT-0000017
1:2 Redundant HPOD Mounting Kit.
(Item No. 1 of KT-0000055 Top Assembly Kit)
A.3.3 KT/12300-1
Uni-Strut Mount HPOD Mounting Bracket Kit.
(Item No. 2 of KT-0000055 Top Assembly Kit)
A.3.4 KT-0021261
Vertical Uni-Strut HPOD Mounting Bracket Kit
(Item No. 2 of KT-0021171 Top Assembly Kit)
Page 70
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–4 MN-PCB-4000A
BLANK PAGE
Page 71
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–5 MN-PCB-4000A
A.2 C-Band Unit Assemblies
A.2.1 C-Band 1+1 Phase Combined HPOD Top Assembly Kit (KT-0000055)
Figure A-2. C-Band 1+1 Phase Combined HPOD Top Assembly Kit (KT-0000055)
Page 72
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–6 MN-PCB-4000A
Table A-2. C-Band 1+1 Phase Combined HPOD Top Assembly Kit - BOM (KT-0000055)
See Figure A-2
Item
No.
QTY CEFD Part No. Description
1 1 KT-0000017 1:2 Unistrut Mounting Kit 2 2 KT/12300-1 HPOD Mounting Bracket Kit 3 1 KT-0021171 C-Band Phase Combiner Box and Bracket Kit
4 1 KT-0000054 C-Band 1:1 HPOD Waveguide and Switch Kit N/A 2 CA/RF11872-1* Cable Assembly, Ku-Band RF IN N/A 2 CA-0021592* Cable Assembly, SSPA to Combiner Box N/A 1 CA/WR12013-1* Cable Assembly, Switches, Combined System N/A A/R HW/TW14.5HDBLK Cable Ties
Notes:
1. A/R = As Required
2. *See Chapter 3. OPERATION and ADJUSTMENT PROCEDURES for information on making cable connections in a 1+1 Phase Combiner System.
Page 73
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–7 MN-PCB-4000A
A.2.2 Phase Combiner Box and Bracket Kit (KT-0021171)
Figure A-3. Phase Combiner Box and Bracket Kit (KT-0021171)
Page 74
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–8 MN-PCB-4000A
Table A-3. Phase Combiner Box and Bracket Kit – BOM (KT-0021171)
See Figure A-3
Item
No.
QTY U/M CEFD Part No. Description
1 1 EA
FP-0022138
Bracket, HPOD Phase Combiner
2 2 EA
HW/1/4-20HEXNUT
1/4-20 HEXNUT,SS
3 4 EA
HW/1/4-20X1SHCS
1/4X20X1 Socket HD Cap Screws
4 6 EA
HW/1/4-FLT
1/4 Flat Washer
5 6 EA
HW/1/4-SPLIT
1/4 Split Washer
6 4 EA
HW/10-32X3/8SH
10-32 x 3/8 Socket Head Cap, SS
7 4 EA
HW/10-FLT
#10 Flat Washer, SS
8 4 EA
HW/10-SPLIT
#10 Split Lock Washers, SS
9 1 EA
PL-0022667
Combiner Box, 1:1 C-Band
Page 75
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–9 MN-PCB-4000A
A.2.3 C-Band 1:1 Phase Combined Waveguide and Switches, HPOD (KT-0000054)
Figure A-4. C-Band 1:1 Phase Combined Waveguide and Switches, HPOD (KT-0000054)
Page 76
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–10 MN-PCB-4000A
Table A-4. C-Band 1:1 Phase Combined Waveguide and Switches, HPOD - BOM (KT-0000054)
See Figure A-4
Item
No.
QTY CEFD Part No. Description
1 1 FP-0000414
MOUNTING BRACKET, DUAL VERTICAL SWITCHES, CPR-137
2 4 HW/3/8SPRINGNUT
SPRINGNUT, 3/8-16, SHORT SPRING, SS (P3300)
3 4 HW/3/8-FLT
3/8 FLAT WASHER, SS
4 4 HW/3/8-SPLIT
3/8 SPLIT LOCK WASHER SS
5 4 HW/3/8-16X1BLT
3/8 - 16 HEX HEAD BOLT, 1.0 LONG, SS
6 1 FP-0000416
SUPPORT BRACKET, CPR-137 TERMINATION
7 2 HW/1/4-FLT
1/4 FLAT WASHER
8 2 HW/1/4-SPLIT
1/4 SPLIT WASHER
9 2 HW/1/4-20X5/8SHCS
SCREW, 1/4-20 X 5/8 SHCS, SCREW, 1/4-20 X 5/8 SHCS, SS
10 2 SW/WGS28V-137S
SW WAVEGUIDE, CPR137, +28V SEALED
11
136
HW/10-FLT
#10 FLAT WASHER SS
12
128
HW/10-SPLIT
#10 SPLIT LOCK WASHER SS
13
64
HW/10-32X1/2SH
#10-32X1/2 SOCKET HEAD CAP SCREW, SS
14 9 GA/CPR-137-R-H-C
GASKET, D SHAPE, CPR-137, HALF THICKNESS, CONDUCTIVE
15 1 HW-0000131
RF MAGIC TEE, COUPLER, 5.85-6.425 GHz, WR-137G, C-BAND, 4 WAY
16
56
HW/10-32X5/8SHC
#10-32 X 5/8 SOCKET HEAD CAP SCREW, SS
17 3 FP-0000410
WAVEGUIDE, CPRG-137, H-BEND ELBOW
18 9 GA/CPR137-R-F-C
GASKET, ROUND, CPR137, FULL THICKNESS, CONDUCTIVE
19 1 RF/CG-137-40-N
RF CROSSGUIDE, WR137, 40DB, N FEMALE, GROOVED
20 8 HW/10-32X3/4SH
#10-32X3/4 SOCKET HEAD CAP SCREW, SS
21 8 HW/10-32HEXNUT
#10-32 HEX NUT, SS
22 1 RF/C-TERM1000W
RF TERMINATION, LOAD, 1000 WATT, CPRG-137
23 1 FP-0000411
WAVEGUIDE, CPRG-137, SWITCH TO MAGIC TEE
24 1 FP-0000408
WAVEGUIDE, CPRG-137, SWITCH TO SWITCH
25 2 FP-0000409
WAVEGUIDE, CPRG-137, E-BEND ELBOW
Page 77
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–11 MN-PCB-4000A
A.2.4 Vertical Mounting Frame Kit (KT-0021179)
Figure A-5. Vertical Mounting Frame Kit (KT-0021179)
Page 78
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–12 MN-PCB-4000A
Table A-5. Vertical Mounting Frame Kit – BOM (KT-0021179)
See Figure A-5
Item
No.
QTY CEFD Part No. Description
1 1 KT-0021175 MOUNTING KIT, 1:2 REDUNDANT HPOD, INDOOR MTG FRAME, VERTICAL WITH POST BASES
2 2 KT-0021261 MOUNTING BRACKET KIT, UNI STRUT MOUNT HPOD
3 1 KT-0021171 KIT, 1:1 PHASE COMBINER BOX AND BRACKET, C-BAND
4 1 KT-0000054 1:1 PHASE COMBINED C-BAND WAVEGUIDE & SWITCHES, HPOD N/A 2 CA/RF11872-1 RF IN, MATCHED SET, 1:2 KU-BAND N/A 2 CA-0021592 SS PA TO C OM BI NER BO X N/A 1 CA/WR-12013-1 CABLE ASSY, SWITCHES, COMBINED SYSTEM N/A A/R LB/CABLE-1RFIN LABEL, CABLE, RF INPUT, SSPA #1 ID LABEL PRINT IN HOUSE, ( ROHS) N/A A/R LB/CABLE-2RFIN LABEL, CABLE, RF INPUT, SSPA #2 ID LABEL PRINT IN HOUSE, ( ROHS)
N/A A/R LB/HPODSSPA-1
LABEL, HPOD, SSPA #1 ID LABEL PRINT IN HOUSE, USE BRADY LABEL LAT-21-773-1 (ROHS)
N/A A/R LB/HPODSSPA-2 LABEL, HPOD, SSPA #2 ID LABEL PRINT IN HOUSE, (ROHS)
Page 79
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–13 MN-PCB-4000A
A.3 Common Kit Subassemblies A.3.1 HPOD 1:1 Redundancy Pole Mount Kit (PL/12319-1)
Figure A-6. HPOD 1:1 Redundancy Pole Mount Kit (PL/12319-1)
*
11
3
4 5 2 * *
Page 80
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–14 MN-PCB-4000A
Table A-6. HPOD 1:1 Redundancy Pole Mount Kit - BOM (PL/12319-1)
See Figure A-6
Item
No.
QTY CEFD Part No. Description
- N/A N/A
Strut (Shown for refere nce only)
2 1 FP/BR0072
Bracket, Strap Tensioner
3 1 FP/BR0070
Strap, Termination, Pole Mounting Kit
4 1 FP/BR0071
Bracket, Modification, 1-1/4 Strap (TRIM TO REQUIRED LENGTH)
5 1 FP/BR0069
Strap, Fixed, Pole Mounting Kit
11 2 HW/PIPEBLOCK
Pipe Block, 2/8 inch, 1 and 5/8 unistrut channel
* 1 KT-0020905
Kit, Commn Purchase Hardware Kit for CSAT PL/12319-1 and AS/0414. See Table A-7.
Table A-7. Hardware Kit (KT-0020905)
* This is part of the HPOD 1:1 Redundancy Pole Mount Kit, Part No. PL/12319-1.
See Figure A-6
Item
No.
QTY CEFD Part No. Description
6 2 HW/M8X1.25X25HEXSS
Bolt, Hex head, M8X1.25X25, SS
7 7 HW/M8FLATSS
Washer, Flat, M8, SS, METRIC
8 7 HW/M8LOCKSS
Washer, Split Lock, M8, SS, METRIC
9 2 HW/M8SPRINGNUT
Spring Nut, M8X1.25
10 5 HW/M8X1.25MMHEXNUTSS
Nut, Hex M8X1.25X16MM, SS
Page 81
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–15 MN-PCB-4000A
A.3.2 1:2 Redundant HPOD Mounting Kit (KT-0000017)
Figure A-7. 1:2 Redundant HPOD Mounting Kit (KT-0000017)
Page 82
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–16 MN-PCB-4000A
Table A-8. 1:2 Redundant HPOD Mounting Kit - BOM (KT-0000017)
See Figure A-7 Item No. QTY CEFD Part No. Description
1 3 FP-0000134 Unistrut, Dual Channel, 74.13” LG
2 4 FP/BR11932-1 Bracket, Unistrut, SS, 26.25” LG
4 12 HW/3/8SPRINGNUT Spring Nut, 3/8-16, Short Spring, SS (P3300)
5 12 HW-0000069 Washer, Flat, Thick, 3/8, SS
6 12 HW/3/8-SPLIT Washer, Lock, Split, 3/8, SS
7 12 HW/3/8-16X1BLT Bolt, Hex Head, 3/8 x 1” LG, SS
Page 83
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–17 MN-PCB-4000A
A.3.3 Uni-Strut Mount HPOD Mounting Bracket Kit (KT/12300-1)
Figure A-8. Uni-Strut Mount HPOD Mounting Bracket Kit (KT/12300-1)
Page 84
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–18 MN-PCB-4000A
Table A-9. Uni-Strut Mount HPOD Mounting Bracket Kit - BOM (KT/12300-1)
See Figure A-8
Item
No.
QTY CEFD Part No. Description
1 2 FP/BR12239-1 Bracket, Unistrut
2 4 HW/3/8SPRINGNUT Spring Nut, 3/8-16, Short Spring, SS (P3300)
3 4 HW/3/8-FLT Washer, Flat, 3/8
4 4 HW/3/8-SPLIT Washer, Lock, Split, 3/8, SS
5 4 HW/3/8-16X1BLT Bolt, Hex Head, 3/8-16 x 1” LG, SS
6 4 HW/5/16-18HEXNT Nut, Hex, 5/16-18, SS
7 8 HW/5/16-Flat Washer, Flat, 5/16, SS
8 4 HW/5/16-SPLIT Washer, Lock, Split, 5/16, SS
9 4 HW/5/16-18X1BLT Bolt, Hex Head, 5/16-18 x 1” LG, SS
Page 85
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–19 MN-PCB-4000A
A.3.4 Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261)
Figure A-9. Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261)
Page 86
PCB-4000A 1+1 Phase Combiner Revision 2
Assembly Kits A–20 MN-PCB-4000A
Table A-10. Vertical Frame Uni-Strut Mount HPOD Mounting Bracket Kit (KT-0021261)
See Figure A-9
Item
No.
QTY CEFD Part No. Description
1 2 FP-0022325 Mounting Bracket, HPOD & LPOD PS-2, with Gussets
2 4 HW/3/8SPRINGNUT Spring Nut, 3/8-16, Short Spring, SS (P3300 Channel)
3 4 HW/3/8-16X1BLT Bolt, Hex Head, 3/8-16 x 1” LG, SS
4 4 HW/5/16-18HEXNT Nut, Hex, 5/16-18, SS
5 8 HW/5/16-FLT Washer, Flat, 5/16, SS
6 4 HW/5/16-SPLIT Washer, Lock, Split, 5/16, SS
7 4 HW/5/16-18X1BLT Bolt, Hex Head, 3/8-16 x 1” LG, SS
8 4 HW/3/8-FLT
Washer, Flat, 3/8, SS Replacerd HW/3/8Flat on 10-25-00
9 4 HW/3/8-SPLIT Washer, Lock, Split, 3/8, SS
Page 87
Page 88
2114 WEST 7TH STREET TEMPE ARIZONA 85281 USA
480 333 2200 PHONE
333 2161 FAX
480
Loading...