CAT LEHE4651-04 User Manual

AUTOMATIC TRANSFER SWITCH
CTS SERIES AUTOMATIC TRANSFER SWITCH
The Cat® CTS Series Automatic Transfer Switch (ATS) is configurable for applications requiring the dependability and ease of operation found in a full featured power contactor type transfer switch.
The CTS Series is equipped with the MX250 controller that is designed for the most demanding transfer or bypass switch applications.
DESIGN AND CONSTRUCTION FEATURES
Double throw, interlocked operation
Electrically operated, mechanically held
by a simple, over-center mechanism
Silver alloy contacts with separate arcing contacts on 600 amp and above
Arc quenching grids, enclosed arc chambers, and wide contact air gap for superior source to­ source isolation on all units
Control circuit disconnect plug and drive inhibit switch for safe maintenance
Components accessible for inspection and maintenance without removal of the switch or the power conductors
Mechanical indicator and contact chamber cover designed for inspection, safety and position designation
FEATURES
Ratings 40 to 4000 amperes
2, 3 or 4 Poles
NEMA 1, 3R, 4, 4X and 12
Available to 600 VAC, 50 or 60 Hz
Suitable for emergency and standby
applications on all classes of load, 100% tungsten rated through 400 amps
UL 1008 listed at 480 VAC
CSA C22.2 No. 178 certified at 600 VAC
IEC 947-6-1 listed through 480 VAC
PERFORMANCE FEATURES
Contact transfer speed less than 100 milliseconds
High close-in and withstand capability
Temperature rise test per UL 1008 conducted
after overload and endurance tests in unventilated enclosure – exceeds UL requirements
Equipped with the MX250 Control Package
LEHE4651-04
AUTOMATIC TRANSFER SWITCH
THE CAT CTS SERIES OF AUTOMATIC TRANSFER SWITCHES
transfer switch duty with dependability, versatility The Cat CTS Series power contactor and user friendliness of prime concern. Type transfer switch makes use of a fully programmable/configurable microprocessor-based controller to allow the utmost in application flexibility. Further, the CTS Series is offered in a wide array of configurations enabling it to meet the needs of even the most highly critical load. the door for ease of maintenance and separation Available configurations include: from the power section. They are connected
40-4000 Amps:
CTS Automatic Transfer Switches a disconnect plug that allows isolation of the
CTSD Delayed Transition Transfer Switches control panel for maintenance.
CTSM Manual Transfer Switches
100-4000 Amps: CTS SERIES METHOD OF OPERATION
CTSCT Closed Transition Transfer Switches When the normal source fails or the voltage
CBTS Automatic Transfer/Bypass Switches drops to a predetermined point (usually 80% of
CBTSD Delayed Transition Bypass Switches nominal), if required, a circuit is closed to start
CBTSCT Closed Transition Bypass Switches the engine generator set. When the emergency
source reaches 90% of rated voltage and 95% of All CTS products meet or exceed industry rated frequency, the drive solenoid is energized requirements to allow specification and through the emergency coil control relay, causing installation with confidence. the main contacts to disconnect the load from
UL 1008 listed through 480 VAC the normal source and connect it to the
CSA C22.2 No. 178 listed through 600 VAC
IEC 947-6-1 listed through 480 VAC
Codes and Standards
NFPA 70, 99, 101, 110 NEC 517, 700, 701, 702 IEEE 446, 241 NEMA ICS2-447
Controls tested in accordance with: IEEE 472 (ANSI C37.90A) EN55022 Class B (CISPR 22) (Exceeds EN55011 & MILSTD 461 Class 3) EN61000-4-2 Class B (Level 4) EN61000-4-3 (ENV50140) 10v/m EN61000-4-4 EN61000-4-5, IEEE C62.41 All CTS switches employ the simple “over-center” EN61000-4-6 (ENV50141) EN61000-4-11
Equipment (Controls and Power Section) Seismic Test Qualified to: IBC-2003 IEEE-693-2005
Enclosures meet the requirements of: UL 508, UL 50, ICS 6, ANSI C33.76 and NEMA 250
Quality System: ISO 9001 Registered
LEHE4651-04
This ruggedly built family of power contactor switches has been specifically designed for
The CTS power panel components, consisting of power switching contacts, drive mechanism and terminal lugs, are mounted on a specially formed backplane. Logic devices including microprocessor control auxiliary time delays and special accessory equipment are assembled on
with a numbered wiring harness equipped with
emergency source. After the drive solenoid has completed its electrical stroke and is seated, the emergency coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the emergency position. When normal voltage is restored to a predetermined point (usually 90% of nominal), the control voltage sensing energizes. The normal side coil relay closes, and after the drive solenoid has completed its electrical stroke and is seated, the coil control relay opens to disconnect it. The transfer switch is now mechanically locked in the normal position.
DRIVE MECHANISM
principle to achieve a mechanically locked position in either normal or emergency and a high speed drive assures contact transfer in 100 ms or less. High contact pressure and positive mechanical lock allow for high withstand and closing ratings, far exceeding UL requirements.
2
AUTOMATIC TRANSFER SWITCH
NEUTRAL SWITCHING
The CTS Series is available in true four pole designs for multi-source power systems that require switching the neutral. The neutral contact is on the same shaft as the associated main contacts. This design ensures positive operation, and prevents any possibility that the neutral contact will fail to open or close, as is possible when the neutral pole is an add-on accessory. The neutral contacts are identical to the main contacts, having the same current carrying and high withstand /closing ratings as the mains. They are
designed to break last and make first to negate the
possibility of transients while switching the neutral.
SAFE MANUAL OPERATION
The CTS manual operator consists of a large, easy-to-use handle that fits securely for manual operation during installation and maintenance or in an emergency. Every CTS is provided with an operator inhibit switch to disconnect the electrical drive prior to maintenance. Fully enclosed wrap-around arc covers shield the main contacts and mechanical components, preventing operator exposure during manual operation
TRANSFERRING LARGE MOTOR OR HIGHLY INDUCTIVE LOADS
Some loads, especially large motors receive severe mechanical stress if power is transferred out of phase while the motor is still rotating. Also, back EMF generated by a motor can result in over currents that can blow fuses or trip circuit breakers. The CTS Series offers four solutions to these problems:
1. Optional Universal Motor Disconnect Contact:
This load control disconnects a large motor via its control circuit for an adjustable period of time prior to transfer in either direction. For switching multiple motors, the motor disconnect contact with staged restart disconnects the motors prior to transfer and brings them back on line sequentially.
2. Accessory R50 Phase Monitor: This feature
compares the phase angle between both sources of power and prevents transfer until the two are approximately in phase (within a self adjusting range). The CTS’s high speed transfer action coupled with the MX series microprocessor control logic ensure closures at or near zero degree phase difference
LEHE4651-04
3. Series CTSD: The CTSD offers a delayed
4. Series CTSCT: Cat closed transition
3
CTS SERIES ATS
400 amp, 2 pole
transition on transfer switches 40A and above. This programmed center-off position allows for the full decay of rotating motors or transformer fields. It can also be used for load shedding of selected circuits or other applications which require a means to disconnect the load from either source. Many UPS system manufacturers recommend delayed transition switches to support sequencing of their systems. Reference the CTSD supplement for further details.
switches combine CTSD operation during a source failure with a highly engineered control system that allows momentary paralleling (100 ms) of two acceptable sources, thereby limiting the impact of transfer on the load. Reference the CTSCT supplement for further details.
AUTOMATIC TRANSFER SWITCH
STANDARD FEATURES (MSTD PACKAGE) Feature Function
6/P Momentary Test Switch J2E/J2N Adj. over/under freq (S1 and S2) A3 Aux Contact (S2 position) L1/L2 Source Position LEDs A4 Aux Contact (S1 position) L3/L4 Source Available LEDs Calibrate Volt. and Freq. calibration LN/P Center-Off Position LCD* CDT Load/No-Load Exerciser P1 Source 2 Start Time Delay DS Auto/Inhibit Switch (> 600A) R50 In-Phase Monitor DT Time Delay – Neutral to S1* S13/P Transfer Commit DW Time Delay – Neutral to S2* T Source 1 Stable Time Delay E Engine Start Contact U Source 2 Stop Time Delay EL/P Log of last 16 events and System Data VI Voltage Imbalance K/P S1 and S2 Freq. Indication W S2 Stable Time Delay YEN Bypass T and W Time Delays
*Available with Delayed Transition switches only.
OPTIONAL PACKAGES
Exerciser (MEXE) Package, includes:
STDS Functions
A1/A1E – S1/S2 Failure aux contact
A3/A4 – One additional contact each
CDP – Programmable exerciser
Q2 – Remote Peak Shave/Load Test
R16 – Phase Rotation Sensing
Controls (MCON) Package, includes:
EXES Functions
Q3 – Remote Inhibit transfer to Emergency
Q7 – Inhibit Transfer to Normal
T3/W3 – Elevator Pre-Signal Aux Contacts
UMD – Universal Motor Load Disconnect
LEHE4651-04
Sensing (MSEN) Package, includes:
EXES Functions
Normal Source Over voltage sensing (3 phase)
Q7 – Inhibit Transfer to Normal
S12P – Auto/Manual Selector Switch
Special (MSPE) Package, includes:
CONS Functions
SENS Functions
S5P – Manual transfer to Normal Switch
(Replaces S12P)
Switchgear (MPSG) Package, includes:
SPES Functions
Additional set of A3/A4 Contacts
R15 – Load Shed to “Dead Normal” or
R15D – Load Shed to Neutral Position*
S12/P – Auto-Manual Selector Switch
Screenshot of ATS operating parameters on Cat Switchgear HMI.
Combined with the optional Modbus Communication Card, the PSGS package allows for integration with Cat Switchgear. This feature allows ATS operating parameters to be displayed on the PowerLynx optional Remote Monitoring Software. Supply of this feature set affords real-time monitoring of the ATS as well as direct control over the following parameters from the Switchgear HMI:
Timer Settings
Pickup/Dropout settings
Testing Functions
Alarm functions
Manual operation
4
®
3000 HMI as well as on the
AUTOMATIC TRANSFER SWITCH
CTS SERIES ACCESSORY DEFINITIONS
6P
Microprocessor activated test switch (Momentary)
6A
Hardwired test switch (Maintained)
6AP
Microprocessor activated test switch (Maintained)
6BK
Hardwired test switch (Maintained Auto – Momentary Test) Key operated
6CK
Hardwired test switch (Maintained Auto – Maintained Test) Key operated
A1
Auxiliary Contact S.P.D.T. – Normal (Source 1) Failure
A1E
Auxiliary Contact S.P.D.T. – Emergency (Source 2) Failure
A3
Auxiliary Contact – closed in emergency (Source 2) Additional available (10 max.) on CTS Series and need to be specified
A4
Auxiliary Contact – closed in normal (Source 1) Additional available (10 max.) on CTS Series and need to be specified
A62
Motor disconnect and staged restart (1 contact)
AB3
Auxiliary contact – closed in bypass emergency (Source 2) (S.P.D.T.) (Standard up to 400A) Additional available (10 max.) on CBTS Series and need to be specified
AB4
Auxiliary contact – closed in bypass emergency (Source 1) (S.P.D.T.) (Standard up to 400A) Additional available (10 max.) on CBTS Series and need to be specified
CALIBRATE
Microprocessor activated calibration feature
CDP
Programmable exerciser daily, 7/14/28/365 days user-selectable, with or without load
CDT
Exerciser no load timer
CTAP
Chicago transfer alarm panel mounted in door of enclosure. Includes 3 aux. contacts and fuse.
DS
Disconnect Switch. Disconnects source voltage to transfer power panel.
DT (DELAYED TRANSITION ONLY)
Time Delay from Neutral Switch position to Source 2 on retransfer
DW (DELAYED TRANSITION ONLY)
Time Delay from Neutral Switch position to Source 2
on retransfer
E
Engine Start Relay
EL/P
Event log of last 16 events
ETHERNET
Ethernet Communication Adapter. Requires Modbus Communication Module.
F
Fan contact, closed when engine runs.
LEHE4651-04
CT
CTS SERIES ACCESSORY GROUP MATRIX
CTS SERIES ACCESSORY DEFINITIONS (continued)
HT(1)(2)
Heater and Thermostat 208/240V (1) 380/600V (2) mounted and inter-wired in enclosure. (requires larger enclosure for 40-200A)
K
Frequency Meter (Analog) – Door mounted
K/P
Frequency Indication on the controller
LNP
Center-off position LCD-Indicator
L1
LED light indicates Switch in Source 2 position
L2
LED light indicates Switch in Source 1 position
L3
LED light indicates Source 1 available
L4
LED light indicates Source 2 available
5
AUTOMATIC TRANSFER SWITCH
CTS SERIES ACCESSORY DEFINITIONS (continued)
LonWorks
LonWorks Communication Module
M1
Single Phase Amp Meter (Analog)
M2
Three Phase Amp Meter (Analog)
M90
EPM2000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factor and Frequency). 3 Line LED Display. 50/60 Hz Universal Operation. 1 or 3 phase. Standard Modbus RTU RS485 communications capability.
M90A
Includes Modbus communication card and factory wiring between EPM2000 and Modbus communication card.
M90B
Includes Modbus communication card, Ethernet communication adapter and factory wiring between EPM2000 and Modbus communication card.
M91
EPM6000 True RMS Digital Meter with display (Amps, Volts, Power, Energy, Power Factor and Frequency, THD). Certified energy and demand metering. Meets ANSI C12.20 and IEC 687 Accuracy Classes. Front IrDA Port Laptop Connection. Standard Modbus RTU RS485 or DNP 3.0 communications capability.
M91A
Includes Modbus communication card and factory wiring between EPM6000 and Modbus communication card.
M91B
Includes Modbus communication card, Ethernet communication adapter and factory wiring between EPM6000 and Modbus communication card.
Modbus
Modbus RTU Communication Module
N1
Running Time Indicator – Door mounted
N2
Operation Counter – Door Mounted
P1
Engine Start Timer (adjustable to 6 seconds)
P2
Engine Start Timer – Extended time delay (adjustable to 300 seconds)
Q2
Peak shave/remote load test/area protection – Relay (S.P.D.T.) (Need to specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V default standard)
Q3
Inhibit transfer to emergency (Source 2) (load add relay) – Relay (S.P.D.T.) (Need to specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V default standard)
Q7
Inhibit transfer to normal (Source 1) – Relay (S.P.D.T.) (Need to specify voltage – 120 VAC, 24 VAC, 24 VDC – 120V default standard)
R1-1/R1-3
Over Voltage sensing for normal (Source 1) single (R1-1) or three (R1-3) phase
R15/R15D
Load Shed. Should Source 2 become overloaded, a signal can be given to switch to the Neutral position.
R16
Phase rotation sensing of Normal (Source 1) and
Emergency (Source 2)
R26/R26D
Interruptible Power Rate Provisions. Allow transfer out of Source 1 position to Mid position or dead Source 2. Alarm and Pre-Signal circuit included. (Need to specify voltage – 120 VAC, 24 VAC, 24 VDC
R50
In Phase monitor between Normal (Source 1) and Emergency (Source 2) to allow transfer
S5P
Microprocessor activated auto/manual retransfer selector switch for transferring to Normal (Source 1) (includes microprocessor activated YN accessory)
S12P
Microprocessor activated auto/manual retransfer selector switch for transferring to Normal (Source 1) (includes microprocessor activated YN & YE accessory)
S13P
Microprocessor activated commit/no commit on transferring to Emergency (Source 2) (with enable/disable settings)
S14K
Keyed selector switch for retransfer to normal-test-auto
SW1
Auto/Off/Start Engine control selector – Door mounted (keyed or non-keyed operation available)
SW2
Auto/Off Engine control selector – Door mounted (keyed or non-keyed operation available)
SW3
Source Priority Selector Switch – Door mounted. Allows selection of Source 1 or Source 2 to be the Prime Source. Transfer Switch will transfer to selected Prime Source if that Source is available. (keyed or non-keyed operation available)
T
Retransfer to Normal (Source 1) adjustable time delay
T3/W3
Pre-signal contact on transfer to Normal (Source 1) or Emergency (Source 2) during test
U
Engine stop /cool adjustable cool down timer
UMD
Pre and post transfer output adjustable time range. Functions in both directions. Includes 2 circuits. (Additional circuits available).
VI
Voltage imbalance between phases (3 Phase only)
W
Adjustable time delay on transfer to Emergency (Source 2)
YEN
Bypass transfer timers function (soft key switch in
microprocessor)
LEHE4651-04
6
AUTOMATIC TRANSFER SWITCH
CTS SERIES DIMENSIONAL SPECIFICATIONS
CTS Series Transfer Switches
Ampere Height Width Depth Reference Application
Rating Poles (A) (B) (C) Figure Weight Notes
40,80, 100 & 150 2,3 24 (610) 18 (457) 11 (279) A 57 (26) 1-7
4 24 (610) 18 (457) 11 (279) A 60 (27)
225, 260 & 400 2,3 46 (1168) 24 (610) 14 (356) A 165 (75) 1-7
4 46 (1168) 24 (610) 14 (356) A 170 (68)
600 2,3 74 (1880) 40 (1016) 20 (508) B 380 (172) 1-8
4 74 (1880) 40 (1016) 20 (508) B 430 (195)
800, 1000 & 1200 2,3 74 (1880) 40 (1016) 20 (508) B 455 (206) 1-8
4 74 (1880) 40 (1016) 20 (508) B 540 (245)
1600 & 2000 3 90 (2286) 36 (914) 48 (1219) C 1010 (458) 1-8
4 90 (2286) 36 (914) 48 (1219) C 1160 (526)
3000 3 90 (2286) 36 (914) 48 (1219) C 1130 (513) 1-8
4 90 (2286) 36 (914) 48 (1219) C 1395 (633)
4000 3 90 (2286) 47 (1194) 62 (1575) C 1595 (723) 1-11
4 90 (2286) 47 (1194) 62 (1575) C 1850 (839)
Application Notes :
1. Dimensions are listed in inches (mm) and weights in pounds (kg).
2. Includes 1.25" door projection beyond base depth. Allow a minimum of 3" additional depth for projection of handle, light, switches, pushbuttons, etc.
3. All dimensions and weights are approximate and subject to change without notice and are not for construction use.
4. Special enclosures (NEMA 3R, 4, 12, etc.) may include mounting tabs, etc. Consult the published dimension drawings for details.
5. Normal and emergency may be ordered inverted on any switch. The load may be inverted 500-1200 amps. Consult the factory for details.
6. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact Caterpillar.
7. Packing materials must be added to weights shown. Allow 15% additional weight for cartons, skids, crates, etc.
8. Add 4" in height for removable lifting lugs.
9. 4000 amp depth dimension shown is standard. Depending on your cable/conduit requirements you may desire a deeper enclosure. Consult Caterpillar for further details.
10. Lug adapters for 3000-4000 amp limits may be staggered length for ease of entrance. Consult Caterpillar for details.
11. Ventilation louvers on side/rear of enclosure at 3000 and 4000A. One side or rear must be clear to afford proper airflow.
NEMA 1 Enclosed
LEHE4651-04
7
AUTOMATIC TRANSFER SWITCH
AL-CU UL LISTED SOLDERLESS SCREW-TYPE TERMINALS FOR EXTERNAL POWER CONNECTIONS
Switch Size
Amps
40-80
100-225
260
400
600 2
NOTES: * Line and load terminals are located in rear and arranged for bus bar connection.
1. Special terminal lugs and neutral bars are available at additional cost. Contact factory and advise cable sizes and number of conductors per pole.
2. Fully rated solid neutral (3x standard normal power connector) provided when required by system voltage.
3. Normal and emergency may be ordered inverted on any switch. Load may be inverted 600-1200 amps. Consult the factory for details.
4. Lug adapters for 3000-4000 amp units may be staggered length for ease of entrance. Consult the factory for details.
5. Special lug arrangements may require different enclosure dimensions. For certified drawings, contact Caterpillar
Normal, Emergency
& Load Terminals
Cables
per Pole
1
Range of Switch Size Cables
Wire Sizes Amps per Pole
#8 to 3/0 AWG 800/1000/1200
#6 AWG to 250 MCM
#6 AWG to 350 MCM
#4 AWG to 600 MCM
#2 AWG to 600 MCM
1600
2000
3000
4000
Normal, Emergency
& Load Terminals
4
8 600 MCM
Range of
Wire Sizes
#2 AWG to 600 MCM
Information contained in this publication may be considered confidential. Discretion is recommended when distributing.
CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow,” the “Power Edge” trade dress as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.Cat-Electric
©2012 Caterpillar
Materials and specifications are subject to change without notice.
Power.com
All Rights Reserved.
Printed in U.S.A.
LEHE4651-04 (11/12)
8
Loading...