Carrier TB-NHP User Manual

Page 1
T B --- N A C T B --- N H P Base Series Non---Programmable Thermostat
Installation Instructions
Designed and Assembled
in the USA.
US patents: US20060165149 A1, USD578026 SI, US6205041 B1
Base Non ---Programmable Thermostat
NOTE: Read the entire instruction manual before starting the installation.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
INSTALLATION CONSIDERATIONS 1...................
INSTALLATION 2....................................
Step 1 — Thermostat Location 2........................
Step 2— Install Thermostat 2...........................
Step 3 — Set Thermostat Configuration 2.................
Step 4 — Thermostat Operation 3........................
Step 5 — Check Thermostat Operation 3..................
WIRING DIAGRAMS 4................................
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury, or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency muse use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety--alert symbol When you see this symbol on the unit and in the instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING,and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
.
INTRODUCTION
The Base Series thermostat is an electronic 24VAC, non--programmable, manual changeover wall mount thermostat. This thermostat uses a single setpoint to maintain and control room temperature in both the heating and air conditioning modes. The thermostat is designed to maintain +/-- 2_F accuracy. No batteries are required; temperature, fan, mode, and installer configuration settings are preserved with power off.
INSTALLATION CONSIDERATIONS
Air Conditioner Model
TB--NAC, Base Series Model air conditioner thermostat, may be wired with or without connecting a common wire between the indoor equipment and the thermostat. However, it is recommended to use a common wire whenever possible. Without a common wire this thermostat becomes “power stealing.” This means it will need to steal a small amount of power from the equipment to which it is connected.
NOTE: Not all HVAC equipment is compatible with power stealing type thermostats. All Carrier equipment is directly compatible with this thermostat except the Thermostat Conversion Kit, Part #TSTATXXCNV10. For all non--Carrier equipment, consult the system equipment Installation Instructions before applying this thermostat in a power stealing manner.
Heat Pump Model
TB--NHP, Base Series Model heat pump thermostat, is compatible with all Carrier heat pump systems. It is NOT power stealing and
Page 2
MUST have both the R and C terminals connected to operate properly. This thermostat uses a green LED to indicate auxiliary heat and emergency heat operation.
INSTALLATION
Step 1 — Thermostat Location
Thermostat should be mounted:
S Approximately 5 ft (1.5m) from floor. S Close to or in a frequently used room, preferably on an inside
partitioning wall.
S On a section of wall without pipes or duct work.
Thermostat should NOT be mounted:
S Close to a window, on an outside wall, or next to a door leading
to the outside.
S Exposed to direct light and heat from the sun, a lamp, fireplace,
or other heat--radiating object which may cause a false reading.
S Close to or in direct airflow from supply registers and return--air
grilles.
S In areas with poor air circulation, such as behind a door or in an
alcove.
Step 2 — Install Thermostat
TB--NAC / TB --NHP
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing thermostat, turn off all power to unit. There may be more than 1 disconnect.
1. Turn OFF all power to unit.
2. If an existing thermostat is being replaced:
ENVIRONMENTAL HAZARD
Failure to follow this caution may result in environmental damage.
Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.
3. Separate front and back (mounting base) assembly of ther-
4. Route thermostat wires through hole in mounting base.
5. Drill two 3/16--in. mounting holes in wall where marked.
6. Secure mounting base to wall with 2 anchors and screws
7. Strip 1/4 in. insulation from thermostat wire and adjust
!
WARNING
a. Remove existing thermostat from wall.
b. Disconnect wires from existing thermostat, one at a
time. Be careful not to allow wires to fall back into wall.
c. As each wire is disconnected, record wire color and
terminal marking.
d. Discard or recycle old thermostat.
!
CAUTION
mostat.
Level mounting base against wall (for aesthetic value only, thermostat need not be level for proper operation) and mark wall through 2 mounting holes.
provided making sure all wires extend through hole in plastic.
length to reach terminal block connector on mounting base.
Match and connect proper wiring in accordance with wiring diagrams.
8. Push any excess wire back into wall. Seal hole in wall to prevent air leaks. Leaks can affect thermostat operation. Any excess wire left inside thermostat casing may also af­fect thermostat operation by interfering with airflow across the temperature sensor.
9. Snap thermostat together making sure terminal block con­nector aligns, and assembly is secure.
10. Turn on power to unit.
On power up, depending on the thermostat model being used, the LCD readout will display either, AC or PC for air conditioner model (1--stage heat/1--stage cool), or HP or PH for heat pump model (2--stage heat/1--stage cool).
Step 3 — Set Thermostat Configuration
Configuration options allow the installer to configure the thermostat for a particular installation. These selections are intended to be made at installation and normally are not modified by the homeowner. Below is a list of available options followed by a description of each one.
Option 01 -- Equipment Type Option 03 -- Fahrenheit or Centigrade operation Option 04 -- Enable fan (G) ON with heat (W) Option 10 -- O (reversing valve) On with Heat or Cool (present
on Heat Pump model only) Option 13 -- Room temperature offset adjustment Note that not all configuration option numbers are used in this
product.
To Enter The Configuration Mode:
Press and hold FAN button for approximately 10 sec until room temperature disappears and the display reads “01”. You are now in configuration mode.
NOTE: If FAN button is pressed again, or if no button is pressed for 3 minutes, the thermostat will exit configuration mode and return to normal operation. To re--enter configuration mode, the FAN button must be pressed and held for 10 sec again.
While in the configuration mode, the temperature display is used to show both the option number and the selected choice within each option. Each press of the H/C button alternates between the option number and the selection within that option. When the configuration mode is first entered, option 01 is displayed. The up and down buttons now move between the available option numbers. Once an option number is selected, press the H/C button once to display the currently selected choice within that option. The up and down buttons now move between the available choices within that option. After the new choice is made, press the H/C button again to return to the option number display. When finished with option selections, press FAN button once to exit the configuration mode.
Option 01 — Equipment Type
Selections: with HP thermostat: HP, AC, PH, or PC
with AC thermostat: AC or PC
Meanings:
PH or PC selects PTAC units (Packaged Terminal Air Conditioners) which are used in motel rooms and other rented spaces. When this option is selected, the display shows only the setpoint, not the room temperature. Also the compressor timeguard is disabled, allowing the compressortoturnonimmediatelywhenademandis
established. HP or PH controls 1 speed heat pump with 1 stage of aux heat. AC or PC controls 1 speed air conditioner with one stage of heat. Note that this option allows a HP thermostat to be converted to
control an AC system.
2
Page 3
Option 03 — Fahrenheit/Centigrade Selection
This selection operates the thermostat in either Fahrenheit or Centigrade. Factory default is F.
Available Selection:
Use UP and DOWN buttons to change between F and C.
Option 04 — G (fan) ON with W (Heat) Selection
This selection determines whether G (fan) output is to be ON or OFF when W (furnace or strip heat) output is ON. Most furnaces and fan coils manage their own blowers and do not require a separate G signal. For these applications, select OFF. Some auxiliary heaters require a separate G signal from the thermostat to turn on the blower. In this case, select ON. Factory default is OF (off).
Available Selection:
Use UP and DOWN buttons to change between ON and OFF.
Option 10 — O (reversing valve) On with Heat or Cool Selection
This selection is only available on heat pump model thermostats. This selection determines whether the reversing valve is energized in the heating or cooling mode. Factory default is C.
Available Selection:
Use UP and DOWN buttons to change between H and C.
Option 13 — Room Temperature Offset Adjust­ment
This option allows calibration (or deliberate miscalibration) of the room temperature sensor. There are various reasons why homeowners may want to have displayed temperature adjusted to a higher or lower value. The selected number is the number of degrees, plus or minus, which will be added to actual temperature.
The numbers can range between --5 and +5. Factory default is 0.
Available Selection:
Use UP and DOWN buttons to now move between --5 and +5 in increments of 1.
Step 4 — Thermostat Operation
Temperature Display
Thermostat will display room temperature until UP or DOWN button is pressed. The word SET appears when these buttons are pressed and the current setpoint is displayed. If no buttons are pressed for 5 sec, the display will change back to show room temperature.
Timeguard Timer
A 5--minute timeguard is built into the thermostat immediately upon power up, and any time the compressor turns off. The compressor will not turn on until the timeguard has expired. The timeguard affects only compressor operation. Pressing UP and FAN buttons simultaneously will override the timeguard for 1 cycle. With PH or PC selected under Option 01, this timer is defeated.
Cycle Timer
In normal heating and cooling operation the thermostat will not allow more than 4 equipment cycles per hour (or 1 cycle every 15
minutes). Both the Y and W outputs have a 15--minute timer that starts counting down when the output is turned on, (e.g., if Y output is turned on for 9 minutes and then satisfies, it cannot turn back on for another 6 minutes regardless of demand). However, pressing UP and FAN buttons simultaneously or changing the setpoint will override the timer for 1 cycle.
Minimum on Timer
Once the equipment has turned on, it will remain on for a minimum of 3 minutes regardless of demand. However, the equipment can turn off in less than 3 minutes if a change in setpoint or a change in mode occurs.
Staging Timer
If the thermostat is a heat pump model, it has 2--stage heat capability. With HP operation, there is a 15--minute delay between the first and second stages of heat. The Y output will energize first, then 15 minutes later, W is allowed to come on if the thermostat determines it is not satisfying the demand.
However, if the heating demand is greater than 5_F, there will be only a 30 second delay before bringing on W.
Auxiliary Heat Indicator
A green LED indicates the use of auxiliary heat or emergency heat.
ErrorMessages
“----” (two dashes) will be displayed if the thermostat cannot properly read room temperature. If “----” appears, replace thermostat.
E4 will be displayed if the thermostat has an internal memory failure. If E4 appears, replace thermostat.
Step 5 — Check Thermostat Operation
Fan Operation
1. Press FAN button. This will start continuous fan operation. FAN annunciator will turn on.
2. Press FAN button again. This will stop continuous fan oper­ation. FAN annunciator will turn off.
Heating Operation
1. Press H/C button until HEAT is displayed.
2. Press UP button until LCD readout reads 3_F above room temperature. Press UP and FAN buttons simultaneously to defeat timers. Heating system should begin to operate im­mediately.
3. For HP thermostats only, press H/C button until EMHT (emergency heat) appears. Press UP and FAN buttons sim­ultaneously to defeat timers. Emergency heating (W is ON, Y is OFF) should begin immediately.
Cooling Operation
1. Press H/C button until COOL is displayed.
2. Press DOWN button until LCD readout reads 3_Fbelow room temperature. Press UP and FAN buttons simultan­eously to defeat timers. Cooling system should begin to op­erate immediately.
Table 1 shows the thermostat outputs for each available stage of heating or cooling. It may be useful in checkout or troubleshooting.
TB--NAC / TB --NHP
Table 1 – Outputs
EQUIPMENT
CONFIGURATION
OPTION #1
AC, PC AC, HP Y, G W --- --- --- ---
HP, PH
RVS = C
HP, PH
RVS = H
THERMOSTAT
FACTORY
CONFIGURATION
HP Y, G , O / B Y, G Y, G , W W
HP Y, G Y, G , O / B Y, G , W, O / B W
COOL
STAGE 1
HEAT
STAGE 1
HEAT
STAGE 2
3
EM HEAT
Page 4
WIRING DIAGRAMS
Fig. 1 -- A/C Thermostat Typical Installation
Fig. 2 -- HP Thermostat Typical Installation
TB--NAC / TB --NHP
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 02/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
C a t a l o g N o : T B --- N A C --- 0 4 S I
R e p l a c e s : TB --- N A C --- 3 S I
Page 5
T B --- N A C T B --- N H P Base Series Non---Programmable Thermostat
Homeowner’s Guide
Designed and Assembled
in the USA.
1. To Select the Mode: Use the H/C button to move between the choices. OFF, HEAT, COOL, or EMHT will appear on the display. EMHT will only appear on heat pump models.
2. To Select the Fan Operation: Use the FAN button to move between continuous fan (in­dicated by the FAN ON icon) and auto fan operation.
3. To Read the Room Temperature: The large display reads room temperature until a button is pressed.
4. To Adjust the Setpoint: In normal operation, the large display shows room temper­ature. At the first press of the UP or DOWN button, the large display shows the current setpoint and the SET TEMP icon is turned on. Further presses of the UP or DOWN but­ton adjust the setpoint upward or downward. Five seconds after the last button press, the display returns to the room temperature and the SET TEMP icon turns off.
Base Non ---Programmable Thermostat
TROUBLESHOOTING
What if there is a green light on in the upper corner of the display area?
This thermostat uses a green LED to indicate auxiliary heat and emergency heat operation on the Heat Pump model. This green light means one of two things.
1. Auxiliary Heat is on: This light turns on automatically when the system determ­ines that it’s too cold outside for your heat pump to heat the house without help. So, it’s getting help from the electric heaters.
NOTE: This indicator does not reflect a problem with your system.
2. Emergency Heat is on: If the heat pump is not working properly, you can manually select the emergency heat for extra help in heating. You’ll know there’s a problem if the house can’t seem to get warm when it’s cold outside. You want to avoid using emergency heat, though, because it’s the most expensive option. And, of course, if you suspect a problem with your heat pump, call your heating and cooling dealer immediately.
Page 6
TB--NAC / TB --NHP
2
Page 7
CARRIER CORPORATION
Limited Warranty for Thermostats
FOR WARRANTY SERVICE OR REPAIR:
Contact the installer or a Carrier dealer. You may find the installer’s name on the equipment or in your Owner’s Packet. You c an also find a Carrier dealer online at www.carrier.com
For help, contact: Carrier Corporation, Consumer Relations, P.O. Box 4808, Syracuse, New York 13221, Phone 1-800-227-7437
PRODUCT REGISTRATION: You can register your product online at www.carrier.c om
Model Number______________________________________________ Serial Number _____________________________________________
Date of Installation ___________________________________________ Installed by ________________________________________________
Name of Owner ______________________________________________ Address of Installation _______________________________________ Carrier Corporation (hereinafter “Company”) warrants this product against failure due to defect in materials or workmanship under normal use and maintenance as follows. All warranty periods begin on the date of original installation. If a part fails due to defect during the applicable warranty period Company will provide a new or remanufactured part, at Company’s option, to replace the failed defective part at no charge for the part. Alternatively, and at its option, the Company will allow a credit in the amount of the then factory selling price for a new equivalent part to ward the retail purchase price of a new Company product. Except as otherwise stated herein, those are Company’s exclusive obligations under this warranty for a product failure. This limited warranty is subject to all provisions, conditions, limitations and exclusions listed below and on the reverse (if any) of this document.
OWNER-OCCUPIED, RESIDENTIAL APPLICATIONS This warranty is to the original purchasing owner and is transferable only to the extent and as stated in the Warranty Conditio ns and below. The warranty period in years, depending on the part and the claimant, is as shown in the chart below.
* If properly registered within 90 days, otherwise 5 years (except in California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration, registration is not required to obtain longer warranty periods). See Warranty Conditions below. ** If properly transferred within 90 days, otherwise 5 years. See Warranty Conditions below. In California and Quebec and other jurisdictions that prohibit warranty benefits conditioned on registration, registration is not required for a transfer and all warranty periods for subsequent owners are five years from original installation. *** Applies only to Thermostats. Active electronic finished good accessories, such as the optional ExP module, have different warranty terms. See product for details.
OTHER RESIDENTIAL APPLICATIONS (Apartments, Rental Properties, etc.) The warranty period is five (5) years and is not transferable.
OTHER APPLICATIONS This warranty is non-transferable. The warranty period is one (1) year on all such applications.
LEGAL REMEDIES: The owner must 4808, Syracuse, New York 13221, of any defect or complaint with the product, stating the defect or complaint and a specific req uest for repair, replacement, or other correction of the product under warranty, mailed at least thirty (30) days before pursuing any legal rights or remedies.
49004DP122 01/10
Product Original Owner Subsequent Owner
notify the Company in writing, by certified or registered letter to Carrier Corporation, Warranty Claims, P.O. Box
.
Limited Warranty (Years)
)5 ro( **01 )5 ro( *01 ***statsomrehT BT,CT ,PT
TB--NAC / TB --NHP
3
Page 8
CARRIER CORPORATION
WARRANTY CONDITIONS:
1. To obtain the longer warranty periods as shown in the table under original owner, for the original purchaser, the product must registered at www.carrier.com registration are prohibited by law, registration is not required and the longer warranty period shown will be apply.
2. Where a product is installed in a newly constructed home, the date of installation is the date the homeowner purchased the home from the builder.
3. If the date of original installation cannot be verified, then the warranty period begins ninety (90) days from the date of product manufacture (as indicated by the model and serial number). Proof of purchase may be required at time of service.
4. The remainder of the first five years of warranty is freely transferable without registration. To obtain a transfer of the longer warranty periods as shown in the table under subsequent owner, a subsequent owner must register the transfer at www.carrier.com of the change in ownership and payment of a transfer fee. Not applicable in all jurisdictions. See website for details.
5. Product must be installed properly and by a licensed HVAC technician.
6. The warranty applies only to products remaining in their original installation location.
7. Installation, use, care, and maintenance must be normal and in accordance with instructions contained in the Installation Instructions, Owner’s Manual and Company’s service information.
8. Defective parts must be returned to the distributor through a registered servicing dealer for credit.
LIMITATIONS OF WARRANTIES: ALL IMPLIED WARRANTIES AND/OR CONDITIONS (INCLUDING IMPLIED WARRANTIES OR CONDITIONS OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE OR PURPOSE) ARE LIMITED TO THE DURATION OF THIS LIMITED WARRANTY. SOME STATES OR PROVINCES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY OR CONDITION LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE EXPRESS WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED, ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON, WHATSOEVER.
THIS WARRANTY DOES NOT COVER:
TB--NAC / TB --NHP
1. Labor or other costs incurred for diagnosing, repairing, removing, installing, shipping, servicing or handling of either defective parts, or replacement parts, or new units.
2. Any product purchased over the Internet.
3. Normal maintenance as outlined in the installation and servicing instructions or Owner’s Manual, including filter cleaning and/or replacement and lubrication.
4. Failure, damage or repairs due to faulty installation, misapplication, abuse, improper servicing, unauthorized alteration or improper operation.
5. Failure to start due to voltage conditions, blown fuses, open circuit breakers, or damages due to the inadequacy or interruption of electrical service.
6. Failure or damage due to floods, winds, fires, lightning, accidents, corrosive environments (rust, etc) or other conditions beyond the control of Company.
7. Parts not supplied or designated by Company, or damages resulting from their use.
8. Products installed outside the U.S.A. or its territories and Canada.
9. Electricity or fuel costs, or increases in electricity or fuel costs from any reason whatsoever, including additional or unusual use of supplemental electric heat.
10. Any cost to replace, refill or dispose of refrigerant, including the cost of refrigerant.
11. ANY SPECIAL, INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE WHATSOEVER. Some states or provinces do not allow the exclusion of incidental or consequential damages, so the above limitation may not apply to you.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state or province to province.
within ninety (90) days of original installation. In jurisdictions where warranty terms conditioned on
be properly
within 90 days
49004DP122 01/10
Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 02/10
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
C a t a l o g N o : T B --- N A C --- 0 4 S I
R e p l a c e s : TB --- N A C --- 3 S I
Loading...