Carrier 48EJ, EY024-048 User Manual

Installation, Start-Up and
Service Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ...................1
INSTALLATION .............................1-31
Step 1 — Provide Unit Support ...............1
• ROOF CURB
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit ..................2
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork ............2
Step 4 — Install Flue Hood ..................12
Step5—TrapCondensate Drain ............13
Step 6 — Install Gas Piping ..................13
Step 7 — Controls Options ..................13
• CONSTANT VOLUME APPLICATIONS
• VARIABLE AIR VOLUME (VAV) APPLICATIONS
Step 8 — Make Electrical Connections .......16
• POWER WIRING
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 9 — Make Outdoor-Air Inlet
Adjustments ...............................24
• ECONOMIZER
• ECONOMIZER SETTINGS
Step 10 — Position Power Exhaust/Barometric
Relief Hood ...............................29
Step 11 — Install All Accessories ............30
START-UP ................................31-44
SERVICE ..................................44-55
TROUBLESHOOTING ......................56-61
START-UP CHECKLIST ................CL-1,CL-2
48EJ,EK,EW,EY024-048
Single Package Rooftop Units
Electric Cooling/Gas Heating
1. Improper installation, adjustment, alteration, serv­ice, or maintenance can cause property damage, per­sonal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in haz-
ardous condition. If gas valve is subjected to pressure greater than 0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be
isolated by closing the manual gas valve(s).
INSTALLATION
Step 1 — Provide Unit Support
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ponents. Only trained andqualifiedservice personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, ob­serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wearsafety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire ex­tinguishers available for all brazing operations.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 Tab 1a
PC 111 Catalog No. 564-962 Printed in U.S.A. Form 48E-5SI Pg 1 8-97 Replaces: 48E-3SI
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
ROOF CURB — Assemble or install accessory roof curb in accordance with instructions shipped with this accessory.See Fig. 1 and 2. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb should be level. This is nec­essary to permit unit drain to function properly. Unit level­ing tolerance is shown in Fig. 1 and 2. Refer to Accessory Roof Curb Installation Instructions for additional informa­tion as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1 and 2. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT— When the preferred curb or slab mount cannot be used, support unit with sleepers on perimeter, using unit curb support area. If sleepers cannot be used, support long sides of unit (refer to Fig. 3-6) with a minimum number of 4-in. x 4-in. pads spaced as follows: 48EJ,EK,EW,EY024-034 units require 3 pads on each side; 48EJ,EK,EW,EY038-048 units require 4 pads on each side. Unit may sag if supported by corners only.
Step 2 — Rig and Place Unit — Inspect unit for trans-
portation damage. File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1 and 2. See Fig. 7 for additional information. Unit operating weight is shown in Table 1.
NOTE: On retrofit jobs, ductwork may be attached to old unit instead of roof curb. Be careful not to damage ductwork when removing old unit. Attach existing ductwork to roof curb instead of unit.
Four lifting lugs are provided on the unit base rails as shown in Fig. 7. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 3-6, around and above unit to provide minimum distance from combus­tible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of con­taminated air. For proper unit operation, adequate combus­tion and ventilation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
ROOF MOUNT — Check building codes for weight distri­bution requirements. Unit weight is shown in Table 1.
Step 3 — Field Fabricate Ductwork
48EJ,EK UNITS — Field-fabricated ductwork should be at­tached to the roof curb. Supply and return duct dimensions are shown in Fig. 3 and 4. Air distribution is shown in Fig. 8.
To attach ductwork to roof curb, insert duct approxi­mately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside the duct.
Secure all ducts to the building structure, using flexible duct connectors between roof curb and ducts as required. Ducts passing through an unoccupied space must be insulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if the unit is equipped with power exhaust.
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install 90 de­gree elbow turns in the supply and return ductwork be­tween the unit and the conditioned space. If a 90 degree elbow cannot be installed, then grilles of sufficientstrength and density should be installed to prevent objects from falling into the conditioned space.
48EW,EY UNITS — Remove shipping covers from supply and return air openings. Attach field-supplied ductwork to unit. Use a single duct over both return openings and a single duct over both supply openings. See Fig. 5 and 6 for duct opening dimensions. Secure all ducts to the building struc­ture. See Fig. 9. Use flexible duct connectors between unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and building openings with counter flash­ing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
Install accesssory barometric relief or power exhaust in the field-fabricated return ductwork. Refer to Position Power Exhaust/Barometric Relief Damper Hood section on page 26 for more information.
Instructions continued on page 12.
2
NOTES:
1. All roof curb parts are to be 16 ga galvanized steel.
2. Dimensions are in inches.
3. Toprevent standing water in the drain pan of the indoor sectionandtheheatexchangers,unit can only be pitched as shown.
Fig. 1 — Roof Curb (Sizes 024-034)
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg. in. Deg. in.
1.0 2.9 .50 .75
3
NOTES:
1. All roof curb parts are to be 16 ga galvanized steel.
2. Dimensions are in inches.
3. Toprevent standing water in the drain pan of the indoor sectionandtheheatexchangers,unit can only be pitched as shown.
Fig. 2 — Roof Curb (Sizes 038-048)
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg. in. Deg. in.
1.0 2.9 .50 .75
4
VFD — Variable Frequency Drive NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue dis­chargefacingeconomizerinlet.Minimum clear­ances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Gas Heat Side: 48-09 Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clear­ances, contact Carrier Application Engineer­ing department.
5. Bottom ducts designed to be attached to ac­cessory roof curb. If unit is mounted on dun­nage, it is recommended the ducts be supported by cross braces as done on ac­cessory roof curb.
6. Dimensions are in inches.
UNIT SIZE
OPERATING
WEIGHT
lb ft-in. ft-in. 1 2 3 4
48EJ,EKD024 4176 6- 0
48EJE024 4256 6- 1
48EJ,EKD028 4262 5- 9
48EJE028 4342 5-10
48EJ,EKD030 4262 5- 9
48EJE030 4342 5-10
48EJ,EKD034 4262 5- 9
48EJE034 4342 5-10
A B CORNER WEIGHT (lb)
3
⁄83-63⁄8879 954 1220 1124
5
⁄163-611⁄16917 973 1218 1148
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
Fig. 3 — Base Unit Dimensions, 48EJ,EK024-034
5
VFD — Variable Frequency Drive NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue discharge facing econo­mizer inlet. Minimum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Gas Heat Side: 48-09 Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier Application Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be supported by cross braces as done on accessory roof curb.
6. Dimensions are in inches.
Fig. 4 — Base Unit Dimensions, 48EJ,EK038-048
UNIT SIZE
OPERATING
WEIGHT
lb ft-in. ft-in. 1 2 3 4
48EJ,EKD038 4442 7- 8
48EJE038 4602 7-10
48EJ,EKD044 4668 7- 5
48EJE044 4828 7- 6
48EJ,EKD048 4955 7- 3
48EJE048 5115 7- 5
6
A B CORNER WEIGHT (lb)
11
⁄163-107⁄81021 894 1180 1347
1
⁄83-113⁄161080 934 1200 1388
5
⁄163-107⁄81033 906 1275 1455
13
⁄163-113⁄161094 945 1293 1496
11
⁄163-101⁄21068 953 1384 1550
3
⁄163-1013⁄161129 994 1401 1592
VFD — Variable Frequency Drive NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet. Minimum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Gas Heat Side: 48-09 Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply ductwork connection is recommended for covering both return and both supply openings.
Fig. 5 — Base Unit Dimensions, 48EW,EY024-034
UNIT SIZE
OPERATING
WEIGHT
lb ft-in. ft-in. 1 2 3 4
48EW,EYD024 4176 6- 0
48EWE024 4256 6- 1
48EW,EYD028 4262 5- 9
48EWE028 4342 5-10
48EW,EYD030 4262 5- 9
48EWE030 4342 5-10
48EW,EYD034 4262 5- 9
48EWE034 4342 5-10
7
A B CORNER WEIGHT (lb)
3
⁄83-63⁄8879 954 1220 1124
5
⁄163-611⁄16917 973 1218 1148
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8 899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
VFD — Variable Frequency Drive NOTES:
1. Weights include economizer (STD).
2. Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet. Minimum clearances to be:
Adjacent Units: 158-09 Top of Units: No overhang Condenser Coil: 48-09 Economizer Side: 68-09 Gas Heat Side: 48-09 Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply duct­work connection is recommended for covering both return and both supply openings.
Fig. 6 — Base Unit Dimensions, 48EW,EY038-048
UNIT SIZE
OPERATING
WEIGHT
lb ft-in. ft-in. 1 2 3 4
48EW,EYD038 4442 7- 8
48EWE038 4602 7-10
48EW,EYD044 4668 7- 5
48EWE044 4828 7- 6
48EW,EYD048 4955 7- 3
48EWE048 5115 7- 5
8
A B CORNER WEIGHT (lb)
11
⁄163-107⁄81021 894 1180 1347
1
⁄83-113⁄
5
⁄163-107⁄81033 906 1275 1455
13
⁄163-113⁄
11
⁄163-101⁄21068 953 1384 1550
3
⁄163-1013⁄161129 994 1401 1592
16
1080 934 1200 1388
16
1094 945 1293 1496
UNIT
48EJ,EK,EW,EYD024 4176 1894
48EJ,EWE024 4256 1930 73.3 1862 42.7 1085
48EJ,EK,EW,EYD028
48EJ,EK,EW,EYD034
48EJ,EWE028
48EJ,EWE034
48EJ,EK,EW,EYD038 4442 2015
48EJ,EWE038 4602 2087 94.1 2390 47.2 1199
48EJ,EK,EW,EYD044 4668 2117 89.3 2268 46.9 1191
48EJ,EWE044 4828 2190 90.8 2306 47.2 1199
48EJ,EK,EW,EYD048 4955 2248 87.7 2228 46.5 1181
48EJ,EWE048 5115 2320 89.2 2266 46.8 1189
WEIGHT A B C
lb kg in. mm in. mm in. mm
72.4 1839 42.4 1072
4262 1933 69.6 1768 44.0 111848EJ,EK,EW,EYD030
4342 1969 70.1 1781 44.3 112548EJ,EWE030
87.68 2227
92.7 2355 46.9 1191
150 3810
NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE
WHEN RIGGING.
NOTE: Rig with four cables and spread with two 92 in. (2337 mm) spreader bars. Maintain a dis­tance of 74 in. (1880 mm) from top of unit to eyehook.
NOTE: Add 32 lb (14.5 kg) for domestic crating. Add 312 lb (142 kg) for export crating (024-034 units). Add 346 lb (157 kg) for export crating (038-048 units). Add 250 lb (113 kg) for power exhaust. Add 220 lb (100 kg) for copper condenser coil (024-034 units). Add 285 lb (129 kg) for copper condenser coil (038,044 units). Add 380 lb (172 kg) for copper condenser coil (048 unit).
Fig. 7 — Rigging Label
9
Table 1 — Physical Data
UNIT 48EJ,EK,EW,EY 024D/E 028D/E 030D/E 034D/E NOMINAL CAPACITY (tons) 20 25 27 30 OPERATING WEIGHT (lb)*
Unit
Al/Al† (Lo Heat/Hi Heat) 4176/4256 4262/4342 4262/4342 4262/4342 Al/Cu† (Lo Heat/Hi Heat) 4396/4476 4482/4562 4482/4562 4482/4562 Roof Curb (14-in. curb) 365 365 365 365
COMPRESSOR
Type Ckt 1 06D328 06D328 06D537 06D537
Ckt 2 06D818 06D328 06D328 06D537
Number of Refrigerant Circuits 22 2 2
Oil (oz) (Ckt 1, Ckt 2) 115, 88 115 ea. 115 ea. 115 ea.
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1** 25-0 25-0 25-0 25-0 Circuit 2 31-0 25-0 25-0 25-0
CONDENSER COIL Cross-Hatched
Quantity 11 1 1 Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 33.3 33.3 33.3 33.3
CONDENSER FAN Propeller Type
Nominal Cfm 13,420 13,420 13,420 13,420 Quantity...Diameter (in.) 2...30 2...30 2...30 2...30 Motor Hp (1075 Rpm) 11 1 1
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 4...15 4...15 4...15 4...15 Total Face Area (sq ft) 31.7 31.7 31.7 31.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...20x15 2...20x15 2...20x15 2...20x15 Type Drive Belt Belt Belt Belt Nominal Cfm 8,000 10,000 11,000 12,000 Motor Hp 5 10†† 15 7.5 10†† 15 10 15†† 20 10 15†† 20 Motor Frame Size (Standard) S184T S215T D254T S213T S215T D254T S215T D254T S256T S215T D254T S256T
Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter 4.8 4.4 5.7 5.4 6.1 5.5 4.4 4.9 5.9 4.4 5.7 5.9 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7 9.4 8.1 8.7 9.0 9.1 8.7 Nominal Fan Shaft Diameter (in.) 1 Belt, Quantity...Type Belt, Length (in.) Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 Factory Speed Setting (rpm) 717 924 1096 773 962 1106 848 1059 1187 884 1096 1187
FURNACE SECTION
Rollout Switch Cutout Temp (F)| 225 225 225 225 Burner Orifice Diameter
(in. ...drill size)
Thermostat Heat Anticipator
Setting (amps)
Gas Input (Btuh) Stage 1 Low 262,500 262,500 262,500 262,500
Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 15-45/35-65 15-45/35-65 15-45/35-65 15-45/35-65 Manifold Pressure (in. wg)
Gas Valve Quantity 22 2 2 Field Gas Connection Size
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 77 7 7 Reset (Auto.) 22 22 22 22
OUTDOOR-AIR FILTERS 8...16 × 25
Quantity...Size (in.) 4...20 × 25
RETURN-AIR FILTERS
Quantity...Size (in.) 10...20x24x2 10...20x24x2 10...20x24x2 10...20x24x2
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase Motor (Factory-Wired for High Speed) and Forward-Curved Fan
Motor, Quantity...Hp 4...1 4...1 4...1 4...1 Fan, Diameter... Width (in.) 11...10 11...10 11...10 11...10
(High Efficiency) S184T S215T S254T S213T S215T S254T S215T S254T S256T S215T S254T S256T
1
8
13⁄
8
15⁄
15
1...BX59622...BX51542...5VX530531...BX59621...5VX590592...5VX530532...BX52552...5VX500502...5VX530532...BX51542...5VX530532...5VX530
Natural Gas Std .111...34 .111...34 .111...34 .111...34 Liquid Propane Alt .089...43 .089...43 .089...43 .089...43
Stage 1 0.1 0.1 0.1 0.1 Stage 2 0.1 0.1 0.1 0.1
High 394,000 394,000 394,000 394,000
Stage 2 Low 350,000 350,000 350,000 350,000
High 525,000 525,000 525,000 525,000
Natural Gas Std 3.5 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5 3.5
(in.-FPT)
16
1.5 1.5 1.5 1.5
LEGEND
Al — Aluminum Cu — Copper
*Weightof unit does not include variable frequency drive(VFD) barometric relief, or power
exhaust. If a VFD is installed, add the VFD weight in the table at right.
†Evaporator coil fin material/condenser coil fin material.
**Sizes 024-034: Circuit 1 uses the lowerportion of condensercoil, Circuit 2uses the upper
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. See
Table 2 for more information. \Rollout switch is manual reset.
3
⁄89 Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
3
⁄89 Copper Tubes, Aluminum Plate Fins, Intertwined Circuits
8
13⁄
8
13⁄
8
15⁄
8
13⁄
8
15⁄
8
15⁄
8
13⁄
8
15⁄
8
15⁄
8
115⁄
16
115⁄
16
115⁄
16
53
NOTE: High heat is for 48EJ,EW only.
VFD (Hp)
208/230 v 460 v 575 v
VFD WEIGHTS (lb)
5 20 22 60
7.5 51 37 64 10 51 61 64 15 61 63 109 20 63 111 109 25 105 112 174 30 172 118 180
10
Table 1 — Physical Data (cont)
UNIT 48EJ,EK,EW,EY 038D/E 044D/E 048D/E NOMINAL CAPACITY (tons) 35 40 45 OPERATING WEIGHT (lb)*
Unit
Al/Al† (Lo Heat/Hi Heat) 4442/4602 4668/4828 4955/5115 Al/Cu† (Lo Heat/Hi Heat) 4727/4887 4953/5113 5335/5495 Roof Curb (14-in. curb) 410 410 410
COMPRESSOR
Type Ckt 1 06D537 06EA250 06EA265
Ckt 2 06D537 06EA250 06EA250
Number of Refrigerant Circuits 222
Oil (oz) (Ckt 1, Ckt 2) 115 ea. 224 ea. 304, 224
REFRIGERANT TYPE R-22
Operating Charge (lb-oz)
Circuit 1** 34-0 35-0 41-0 Circuit 2 34-0 35-0 41-0
CONDENSER COIL Cross-Hatched
Quantity 2211 Rows...Fins/in. 3...15 3...15 4...15 3...15 Total Face Area (sq ft) 58.3 58.3 66.7
CONDENSER FAN Propeller Type
Nominal Cfm 27,064 27,064 27,064 Quantity...Diameter (in.) 4...30 4...30 4...30 Motor Hp (1075 Rpm) 111
EVAPORATOR COIL Cross-Hatched
Rows...Fins/in. 3...15 3...15 4...15 Total Face Area (sq ft) 34.7 34.7 34.7
EVAPORATOR FAN Centrifugal Type
Quantity...Size (in.) 2...20x15 2...20x15 2...20x15 Type Drive Belt Belt Belt Nominal Cfm 14,000 16,000 18,000 Motor Hp 10 15†† 20 15 20†† 25 20 25†† 30 Motor Frame Size (Standard) S215T D254T S256T D254T S256T S284T S256T S284T S286T
Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 Motor Pulley Pitch Diameter 6.1 5.3 5.7 5.3 5.7 7.5 6.3 5.9 7.5 Nominal Motor Shaft Diameter (in.) 1 Fan Pulley Pitch Diameter (in.) 13.7 9.5 9.5 9.5 9.5 11.1 11.1 12.5 11.1 Nominal Fan Shaft Diameter (in.) 1 Belt, Quantity...Type Belt, Length (in.) Pulley Center Line Distance (in.) 15.6-18.4 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 14.6-17.6 Factory Speed Setting (rpm) 779 976 1050 976 1050 1182 993 1134 1182
FURNACE SECTION
Rollout Switch Cutout Temp (F)| 225 225 225 Burner Orifice Diameter
(in. ...drill size)
Thermostat Heat Anticipator
Setting (amps)
Gas Input (Btuh) Stage 1 Low 300,000 300,000 300,000
Efficiency (Steady State) (%) 82 82 82 Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60 Manifold Pressure (in. wg)
Gas Valve Quantity 222 Field Gas Connection Size (in.-FPT) 1.5 1.5 1.5
HIGH-PRESSURE SWITCH (psig)
Cutout 426 426 426 Reset (Auto.) 320 320 320
LOW-PRESSURE SWITCH (psig)
Cutout 777 Reset (Auto.) 22 22 22
OUTDOOR-AIR FILTERS 8...16 × 25
Quantity...Size (in.) 4...20 × 25
RETURN-AIR FILTERS
Quantity...Size (in.) 10...20x24x2 10...20x24x2 10...20x24x2
POWER EXHAUST Direct Drive, 3-Speed, Single-Phase motor (Factory-Wired for High Speed) and Forward Curved Fan
Motor, Quantity...Hp 4...1 4...1 4...1 Fan, Diameter... Width (in.) 11...10 11...10 11...10
(High Efficiency) S215T S254T S256T S254T S256T S284T S256T S284T S286T
3
8
1...5VX650652...5VX530532...5VX550552...5VX530532...5VX550552...5VX590592...5VX570572...5VX630632...5VX610
Natural Gas Std .120...31 .120...31 .120...31 Liquid Propane Alt .096...41 .096...41 .096...41
Stage 1 0.1 0.1 0.1 Stage 2 0.1 0.1 0.1
High 600,000 600,000 600,000
Stage 2 Low 400,000 400,000 400,000
High 800,000 800,000 800,000
Natural Gas Std 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5
15⁄
8
15
16
LEGEND
Al — Aluminum Cu — Copper
*Weightof unit does not include variable frequency drive(VFD) barometric relief, or power
exhaust. If a VFD is installed, add the VFD weight in the table at right.
†Evaporator coil fin material/condenser coil fin material.
**Sizes 024-034: Circuit 1 uses the lowerportion of condensercoil, Circuit 2uses the upper
portion. Sizes 038-048: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
††Motor and drive shown will deliver approximately 2.5 in. wg net external static. See
Table 2 for more information. \Rollout switch is manual reset.
3
⁄89 Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
3
⁄89 Copper Tubes, Aluminum Plate Fins, Intertwined Circuits
15⁄
8
15⁄
8
115⁄
15⁄
8
16
17⁄
8
15⁄
8
NOTE: High heat is for 48EJ,EW only.
VFD (Hp)
208/230 v 460 v 575 v
VFD WEIGHTS (lb)
5 20 22 60
7.5 51 37 64 10 51 61 64 15 61 63 109 20 63 111 109 25 105 112 174 30 172 118 180
115⁄
17⁄
8
16
17⁄
8
59
11
Table 2 — Evaporator Fan Motor Data (Units with Starting Serial Numbers 4197 and Later)
UNIT
MOTOR
SIZE
48E
024
028
030
034
038
044
048
NOTE: Motor shaft speed is 1750 rpm. The fan shaft diameter is 1
MOTOR
SHAFT
HP
10 1.38 924 2BK50 4.4 None-1.375 2B5V86 8.6 B-1.9375 (2) BX51 54 5.21 15 1.62 1096 2B5V56 5.7 B-1.625 2B5V90 9.1 B-1.9375 (2) 5VX530 53 6.00
7.5 1.38 773 BK60H 5.4 H-1.375 1B5V124 12.4 B-1.9375 BX59 62 6.48 10 1.38 962 1B5V60 6.1 H-1.375 1B5V110 11.1 B-1.9375 5VX590 59 7.37 15 1.62 1106 2B5V54 5.5 B-1.625 2B5V86 8.7 B-1.9375 (2) 5VX530 53 6.12
10 1.38 848 2BK50 4.4 None-1.375 2B5V94 9.4 B-1.9375 (2) BX52 55 5.27 15 1.62 1059 2B5V48 4.9 B-1.625 2B5V80 8.1 B-1.9375 (2) 5VX500 50 6.63 20 1.62 1187 2B5V58 5.9 B-1.625 2B5V86 8.7 B-1.9375 (2) 5VX530 53 7.31
10 1.38 884 2BK50 4.4 H-1.375 2B5V90 9.0 B-1.9375 (2) BX51 54 5.24 15 1.62 1096 2B5V56 5.7 B-1.625 2B5V90 9.1 B-1.9375 (2) 5VX530 53 6.00 20 1.62 1187 2B5V58 5.9 B-1.625 2B5V86 8.7 B-1.9375 (2) 5VX530 53 7.31
10 1.38 779 1B5V60 6.1 None-1.375 1B5V136 13.7 B-1.9375 5VX650 65 7.62 15 1.62 976 2B5V52 5.3 B-1.625 2B5V94 9.5 B-1.9375 (2) 5VX530 53 6.37 20 1.62 1050 2B5V56 5.7 B-1.625 2B5V94 9.5 B-1.9375 (2) 5VX550 55 7.60
15 1.62 976 2B5V52 5.3 B-1.625 2B5V94 9.5 B-1.9375 (2) 5VX530 53 6.37 20 1.62 1050 2B5V56 5.7 B-1.625 2B5V94 9.5 B-1.9375 (2) 5VX550 55 7.60 25 1.88 1182 2B5V74 7.5 B-1.875 2B5V110 11.1 B-1.9375 (2) 5VX590 59 7.60
20 1.62 993 2B5V62 6.3 B-1.625 2B5V110 11.1 B-1.9375 (2) 5VX570 57 7.22 25 1.88 1134 2B5V80 5.9 B-1.875 2B5V124 12.5 B-1.9375 (2) 5VX630 63 7.36 30 1.88 1182 2B5V74 7.5 B-1.875 2B5V110 11.1 B-1.9375 (2) 5VX590 59 9.07
DIA. (in.)
5 1.12 717 BK55 4.8 None-1.125 1B5V124 12.4 B-1.9375 BX59 62 5.10
FAN SHAFT SPEED
(rpm)
MOTOR
SHEAVE
MOTOR
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
15
⁄16inches.
FAN
FAN
SHEAVE
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
(QUANTITY)
OUTSIDE
BELT
LENGTH
TENSION
Step 4 — Install Flue Hood — Flue hood is shipped
inside gas section of unit. To install, secure flue hood to ac­cess panel. See Fig. 10.
NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 11.
BELT
(Lb at
.24 in.)
Fig. 8 — Air Distribution — Thru-the-Bottom
Fig. 9 — Air Distribution — Thru-the-Side
Fig. 10 — Flue Hood Location
12
Step5—TrapCondensate Drain — See Fig. 3-6
for drain location. Condensate drain is open to atmosphere and must be trapped. Install a trapped drain at the drain lo­cation. A trap at least 4-in. deep must be used. See Fig. 12. Trap must be installed to prevent freeze-up.
Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air qual­ity guidelines. The condensate drain pan is fitted with a 1-in. FPT coupling.
Step 6 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a sure tap for test gage connection at unit. Field gas piping must include sediment trap and union. See Fig. 13. An
1
⁄8-in. NPT is also located on the gas manifold adjacent to
the gas valve.
Do not pressure test gas supply while connected to unit. Always disconnect union before servicing.
IMPORTANT: Natural gas pressure at unit gas con­nection must not be less than 5 in. wg or greater than
13.5 in. wg.
1
⁄8-in. NPT pres-
Fig. 11 — Combustion Fan Housing Location
Size gas-supply piping for 0.5-in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
Step 7 — Controls Options — The control options
that the units can provide are based on the following param­eters: CV (constant volume) or VAV (variable air volume) operation; stand-alone unit with field-supplied sensors in­stalled (CV or VAV); as a system via Carrier Comfort Sys­tem (TEMP or VVTt); optional electronic expansion board installed (CV or VAV); linked to the Carrier Comfort Network; and availability of a computer and software (ComfortWorks™ Building Supervisor, and Service Tool) or LID-2B accessory installed to access the base control board. See Table 3.
NOTE: Access to the base control board allows unit occu­pancy schedules, unit timeclock, and various set points to be changed from their factory-defined default settings.
All units are equipped with a supply air thermistor (SAT) located in the supply fan discharge and an outdoor air ther­mistor (OAT) located in the outdoor air hood. Variable air volume units are supplied with a return air thermistor (RAT) located on the return air damper support.
CONSTANT VOLUME APPLICATIONS — The units, as shipped, are operable as stand-alone units, using either a stand­ard (mechanical or electronic) 2-stage heat, 2-stage cool ther­mostat, or with an electronic room sensor and a timeclock to establish unit start and stop times.
With a standard thermostat (programmable is optional), heating and cooling operation is set by space temperature.
With a space sensor and timeclock, the machine will op­erate at default values unless they are changed using appro­priate input devices. The space sensor senses space tempera­ture and may be equipped with a timed override feature, which allows unit operation during unoccupied periods.
Fig. 12 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
Fig. 13 — Field Gas Piping
The space sensors may be used in multiples of 4 or 9 to achieve space temperature averaging. The use of a space sen­sor also allows the unit to be turned on and off from a re­mote signal.
Features with Thermostat Control of Unit
• two-stage heating
• two-stage cooling
• control of unit using Y1, Y2, W1, W2, and G thermostat
inputs
• control of the indoor fan
• outdoor-air temperature/supply-air temperature
monitoring
• control of an outdoor air condenser fan based on outdoor-
air temperature
13
Table 3 — Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATION DEFAULT COOLING DEFAULT HEATING CV or VAV Unit with SPT Sensor CV Unit with SPT Sensor and Remote
Start/Stop Switch VAV Unit Remote Start/Stop Switch Only VAV Unit with SPT Sensor and Remote
Start/Stop Switch
LEGEND
CV Constant Volume NA — Not Available RAT — Return-Air Temperature SAT — Supply-Air Temperature SPT — Space Temperature VAV — VariableAir Volume
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — NA
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 78 F (SPT)
Unoccupied Cooling — 90 F (RAT) Occupied Cooling — 55 F (SAT)
Unoccupied Cooling — 90 F (SPT) Occupied Cooling — 55 F (SAT)
*With DIP Switch No. 5 configured to OPEN (Occupied Heat
Enabled).
NOTE: Space temperature sensor and remote start/stop switch are field-supplied.
Unoccupied Heating — 55 F (SPT) Occupied Heating — NA
Unoccupied Heating — 55 F (SPT) Occupied Heating — 68 F (SPT)
Unoccupied Heating — 55 F (RAT) Occupied Heating — 68 F (RAT)*
Unoccupied Heating — 55 F (SPT) Occupied Heating — 68 F (RAT)*
• control of modulating economizer damper to provide free cooling when outdoor conditions are suitable, using supply-air temperature as a control point
• control of the economizer damper and indoor fan to obtain unoccupied free cooling
• provide power exhaust output to an external power ex­haust controller
• support a field test for field checkout
• control of 2 stages of CV power exhaust
• compressor Time Guardt (power up, minimum off and on times)
• compressor lockout during low supply-air temperature
Additional features are provided by accessing the stand­ard unit control board via software with a computer. These features are:
• electronic expansion board features (if installed)
• control board diagnostics
• ability to change supply air set point (economizer control)
• ability to change high outdoor temperature lockout set point
(economizer control)
• ability to change power exhaust set points NOTE: A CV unit without a thermostat requires a field-
supplied sensor for operation. Features with Sensor Control of Unit (Stand-Alone Appli-
cations — Unit control is limited to CV unoccupied default set points, 90 F for cooling, 55 F for heating. There are 2 sensor options available:
• T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
• T-56 sensor will monitor room temperature, provide un-
occupied override capability (1 hour), and provide a tem­perature offset of 5° F.
Standard features are:
• support of remote occupied/unoccupied input to start and
stop the unit
• cooling capacity control of 3 stages using economizer and
2 compressors to maintain space temperature to an occu­pied or unoccupied set point
• enable heating or cooling during unoccupied periods as
required to maintain space temperature within the unoc­cupied set points
• adjustment of space temperature set points of ±5° F when
using a T-56 sensor
Additional features with sensor control of unit (with com­puter access) are:
• 365 day timeclock with backup (supports minute, hour,day
of week, date, month, and year)
• daylight savings time function
• occupancy control with 8 periods for unit operation
• holiday table containing up to 18 holiday schedules
• ability to initiate timed override from T-55or T-56 sensors for a timed period of 1 to 4 hours
• ability to use multiple space temperature sensors to aver­age the space temperature
• temperature compensated start to calculate early start times before occupancy
• access to the Display, Maintenance, Configuration, Service, and Set Point data tables through network software
When the unit is equipped with a field-supplied space temperature sensor and a remote contact closure (remote start/ stop) on the base control board, the occupied default set points will monitor unit operation. The occupied default set points are 78 F cooling and 68 F heating. See Fig. 14 for remote start/stop wiring.
NOTE: For units with a field-supplied space temperature se­sor which have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/ stop closure will allow the unit to operate in the pre­configured occupied default set points (based on return-air temperature) of 78 F cooling and 68 F heating. Without this feature, the unit will control to the unoccupied default set points of 90 F cooling and 55 F heating.
An electronic expansion board may be field-installed to provide the following features:
• control of modulating economizer damper to maintain in-
door air quality (IAQ) when outdoor conditions are suitable
NOTE: The IAQ sensor must be set for current output (4 to 20 mA), not voltage output. Ensure the jumper on the sensor is in the upper position. See Fig. 15.
• provide discrete inputs for fan status, filter status, field-
applied status, and demand limit
• provide an output for the external alarm light indicator
• provide power exhaust fire outputs for direct control of
modulated power exhaust stages during fire or smoke modes
• control of smoke control modes including evacuation, smoke
purge, pressurization, and fire shutdown (modulating power exhaust required)
When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized:
• perform Demand Limit functions based on CCN loadshed
commands or the state of the discrete input
• alarm monitoring of all key parameters
• CCN protocol
• provides CCN IAQ participation
See Carrier TEMP or VVTt (Variable Volume and Tem­perature) literature for complete TEMP (single zone) or VVT (multi-zone) application information.
14
REMOTE START/STOP SWITCH (FIELD-SUPPLIED)
R
Y1 Y2 W1
W2
G C
X
CONTROL BOX
LEGEND
Field Supplied Wiring
Fig. 14 — Field Control Remote Start/Stop
JUMPER CONNECTION FOR VOLTAGE OUTPUT
JUMPER CONNECTION FOR CURRENT OUTPUT
Fig. 15 — Indoor Air Quality Sensor Configuration
Features with Sensor Control of Unit (Network Applica­tions) — The base control board provides, as standard, a con­nection for use with a Carrier VVT system and can also be integrated into a Carrier Comfort Network.
When the unit is accessed via a PC equipped with Com­fortWorks™, Building Supervisor, or Service Tool software, or accessory LID-2B, the following features can be accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored
This access is available on the base control board via a RJ-11 phone jack or a 3-wire connection to the communi­cation bus. See Fig. 16. The timeclock has a 10-hour mini­mum back-up time to provide for unit power off for servic­ing unit or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature.
VARIABLE AIR VOLUME (VAV) APPLICATIONS Features with Stand-Alone Applications — The units, as
shipped, are operable as stand-alone units with the addition of a timeclock to establish unit start and stop times.
Heating and cooling in both on and off modes is con­trolled to default values by the base unit control. Set points may be changed with appropriate input devices.
The control has an on-board occupancy schedule which can be set using an input device and eliminates the need for an external timeclock.
During both the on and off periods, cooling operation is controlled to the supply air setting and heating is controlled to the return air setting (or to the optional space temperature sensor). During the on period, the supply fan runs continu­ously.During the off period, the supply fan will be activated if the return air sensor is outside of the set points and will run log enough to accurately sample the space temperature. The supply fan will then continue to run until any heating or cooling load is satisfied, at which point it will turn off.
The use of a space sensor will allow for supply air reset to conserve energy and maintain comfort. If equipped with an override feature, the sensor will allow operation during the off period for a fixed length of time.
Base unit control supports a Heat Interlock Relay (field supplied) to fully open the VAV terminal devices during heat­ing operation.
Standard features of a VAV unit with a remote start/stop switch are:
• control board diagnostics
• control of an outdoor condenser fan based upon outdoor
air temperature
• control of modulating economizer to provide free cooling
when outdoor conditions are suitable, using supply-air tem­perature as a set point
• support of remote occupied/unoccupied input to start or
stop the unit
• provide power exhaust output to an external power ex-
haust controller
• support supply-air temperature reset to offset supply air
set point
• support a field test for field check out
• support linkage to DAV systems
• cooling capacity control of up to 6 stages plus economizer
with compressors and unloaders to maintain supply air tem­perature set point during occupied periods
• control of one stage of heat to maintain return-air tem-
perature at heating set point during occupied periods
• provide a variable frequency drive high voltage relay out-
put to enable VFD
• control of heat interlock relay
• compressor Time Guard override (power up, minimum off
and on times)
With the addition of a remote start/stop switch heating or cooling is enabled during unoccupied periods as required to maintain space temperature to within unoccupied set points.
Additional features may be provided with Electronic Access to Unit Control Board. These features are:
• additional control board diagnostics
• electronic expansion board features (if installed)
• control of the economizer damper and indoor fan to obtain
unoccupied free cooling
• 365-day timeclock with backup (supports minute, hour, day,
month, and year)
• holiday table containing up to 18 holiday schedules
• occupancy control with 8 periods for unit operation
• support a set of display, maintenance, configuration, serv-
ice, and set point data tables for interface with Building Supervisor, ComfortWorks, or Service Tool software soft­ware or accessory LID-2B
15
When a VAV unit with a space temperature sensor is ac­cessed via a computer, the following additional features are available:
• ability to initiate timed override from T-55 sensors
• temperature compensated start to calculate early start time
before occupancy
• provide space temperature reset to reset the supply air set
point upward when the temperature falls below the occu­pied cooling set point
An electronic expansion board may be field-installed to provide the following features:
• fan status
• filter status
• field-applied status
• demand limiting
• IAQ Sensor
• OAQ Sensor
• alarm light
• fire unit shutdown
• fire pressurization
• fire evacuation
• fire smoke purge
When the unit is connected to the CCN (Carrier Comfort Network), the following expansion board features can be utilized:
• CCN IAQ (indoor air quality) participation
• CCN OAQ (outdoor air quality) participation
• CCN demand limit participation
• modulated power exhaust override
• ability to use multiple space temperature sensors (mul-
tiples of 4 and 9 only) to average space temperature (DAV only)
Afield-supplied T -55space temperature sensor can be added to monitor room temperature and provide unoccupied over­ride capability (1 hour).
When the unit is equipped with a field-supplied space tem­perature sensor and a remote contact closure (remote start/ stop) the occupied default set points will monitor unit op­eration. The occupied default set points are 55 F (supply air) cooling and 68 F (return air temperature) heating. See Fig. 14 for remote start/stop wiring.
NOTE: For units without a space temperature sensor and which have not had the base unit control board accessed via soft­ware to set an occupancy schedule, the remote start/stop clo­sure will allow the unit to operate in the pre-configured oc­cupied default set points of 55 F (supply-air temperature) cooling and 68 F (return-air temperature) heating. Without an occupancy schedule, the unit will control to the unoccu­pied default set points of 90 F (return air) cooling and 55 F (return air) heating.
Features with NetworkApplications —The base control board provides, as standard, a connection for use with a Carrier Comfort System and can also be integrated into a Carrier Comfort Network. When the unit is accessed via a PC equipped with ComfortWorks™, Building Supervisor, or Service Tool software or LID-2B accessory,the following features can be accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored
This access is available on the base control board via a RJ-11 phone jack or a 3-wire connection to the communi­cation bus. See Fig. 16. The internal timeclock has a 10-hour minimum back-up time to provide for unit power off for ser­vicing unit or during unexpected power outages. For com­plete Carrier Comfort System (CCS) or Carrier Comfort Network (CCN) features and benefits, refer to the product literature.
Step 8 — Make Electrical Connections
POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate.
When installing units, provide a disconnect per NEC (National Electrical Code) of adequate size (MOCP [maxi­mum overcurrent protection] of unit is on the informative plate). All field wiring must comply with NEC and all local codes. Size wire based on MCA (minimum circuit amps) on the unit informative plate. See Fig. 17 for power wiring con­nections to the unit power terminal block andequipment ground.
The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 17. Units have circuit breakers for compressors, fan motors, and control circuit. If required by local codes, provide an additional disconnectswitch. Whenever external electrical sources are used, unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI C1-latest year.
All field wiring must comply with NEC and local code requirements.
FIELD POWER SUPPLY — Unit is factory wired for volt­age shown on unit nameplate. See Table 4 for electrical data.
Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (cor­ner post next to control box).
1
⁄2-in. NPT coupling for field power wiring and a
A3
3
⁄4-in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 21⁄2-in. (024-034) or 3-in. (038-048) knockouts for the field power wiring. See Fig. 3-6. If control wiring is to be brought in through the side of unit, a7⁄8-in. diameter hole is provided in the con­denser side post next to the control box.
If disconnect box is mounted to corner post, be careful
not to drill any screws into the condenser coil. Routing Through Bottom of Unit — If wiring is brought in
through bottom of unit, use field-supplied watertight conduit to run power wiring from basepan out through bottom 31⁄2-in. hole to the disconnect box and back into unit to the main control box.
Use strain relief going into control box through 2 diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section above).
Low-voltage wiring must be run in watertight conduit from the basepan to control box and through
7
⁄8-in. diameter hole provided in bottom of unit control box. Field-supplied strain relief must be used going into the box. After wiring is in control box, make connections to proper terminals on ter­minal blocks (see Field Control Wiring section on page 21).
Install conduit connector in unit basepan as shown in Fig. 3-6. Route power and ground lines through connector to terminal connections in unit control box as shown on unit wiring diagram and Fig. 17.
Routing Through Side of Unit — Route power wiring in field­supplied watertight conduit into unit through 21⁄2-in. hole. See Fig. 17.
Use field-supplied strain relief going into control box through
1
⁄2-in. diameter hole provided. After wires are in unit con-
2 trol box, connect to power terminal block (see Power Wiring section on this page).
Bring low-voltage control wiring through factory-drilled
7
⁄8-in. diameter hole in condenser side post. Use strain relief
going into7⁄8-in. diameter hole in bottom of unit control box.
After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring sec­tion on page 21).
1
⁄2-in.
16
17
LEGEND
CCN — Carrier Comfort Network COM — Common D—Diode LED — Light-Emitting Diode N.C. — Normally Closed
N.O. — Normally Open R—Relay SIO — Serial Input/Output SW — Switch T—Terminal
Fig. 16 — Control Board Diagram
*Where X is the unit control software version number.
Table 4 — Electrical Data
UNIT
SIZE
48E
024
028
030
NOMNAL
VOLTAGE
(3 Ph 60 Hz)
208/230 187 254 39.1 228 25.6 160 2 1 5.3
460 414 508 19.9 114 11.5 80 2 1 2.7
575 518 632 16.0 91 9.6 64 2 1 2.4
208/230 187 254 39.1 228 39.1 228 2 1 5.3
460 414 508 19.9 114 19.9 114 2 1 2.7
575 518 632 16.0 91 16.0 91 2 1 2.4
208/230 187 254 57.1 266 39.1 228 2 1 5.3
460 414 508 25.6 120 19.9 114 2 1 2.7
575 518 632 20.5 96 16.0 91 2 1 2.4
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
COMPRESSOR
No. 1 No. 2
OFM IFM
POWER
EXHAUST
FLA
Hp FLA FLA LRA FLA MCA MOCP*
(ea)
0.96 101.8/100.3 125/125
16.7/
5
15.2
23.6 41.6 0.96 125.4/123.9 150/150 — 0.96 115.9/113.1 150/150
30.8/
10
28.0
23.6 41.6 0.96 139.5/136.7 175/175 — 0.96 131.3/127.1 150/150
46.2/
15
42.0
23.6 41.6 0.96 154.9/150.7 175/175
5 7.6
10 14.0
15 21.0
5 6.1
10 11.0
15 17.0
7.5
10
15
7.5 11.0
10 14.0
15 21.0
7.5 9.0
10 11.0
15 17.0
10
15
20
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
0.50 49.4 60
12.6 23.6 0.50 62.0 80 — 0.50 55.8 70
12.6 23.6 0.50 68.4 80 — 0.50 62.8 80
12.6 23.6 0.50 75.4 90 — 0.50 40.5 50
12.6 23.6 0.50 53.1 60 — 0.50 45.4 60
12.6 23.6 0.50 58.0 70 — 0.50 51.4 60
12.6 23.6 0.50 64.0 80 — 0.96 122.8/120.6 150/150
24.2/
22.0
23.6 41.6 0.96 146.4/144.2 175/175 — 0.96 129.4/126.6 150/150
30.8/
28.0
23.6 41.6 0.96 153.0/150.2 175/175 — 0.96 144.8/140.6 175/175
46.2/
42.0
23.6 41.6 0.96 168.4/164.2 200/200 — 0.50 61.2 80
12.6 23.6 0.50 73.8 90 — 0.50 64.2 80
12.6 23.6 0.50 76.8 90 — 0.50 71.2 90
12.6 23.6 0.50 83.8 100 — 0.50 49.8 60
12.6 23.6 0.50 62.4 70 — 0.50 51.8 60
12.6 23.6 0.50 64.4 80 — 0.50 57.8 70
12.6 23.6 0.50 70.4 80 — 0.96 151.9/149.1 200/200
30.8/
28.0
23.6 41.6 0.96 175.5/172.7 225/225 — 0.96 167.3/163.1 225/225
46.2/
42.0
23.6 41.6 0.96 190.9/186.7 225/225 — 0.96 180.5/175.1 225/225
59.4/
54.0
23.6 41.6 0.96 204.1/198.7 250/250 — 0.50 71.3 90
12.6 23.6 0.50 83.9 100 — 0.50 78.3 100
12.6 23.6 0.50 90.9 110 — 0.50 84.3 100
12.6 23.6 0.50 96.9 110 — 0.50 57.4 70
12.6 23.6 0.50 70.0 90 — 0.50 63.4 80
12.6 23.6 0.50 76.0 90 — 0.50 68.4 80
12.6 23.6 0.50 81.0 100
COMBUSTION
FAN MOTOR
See Legend and Notes on page 19.
POWER SUPPLY
18
Table 4 — Electrical Data (cont)
UNIT
FLA Full Load Amps HACR — Heating, Air Conditioning and
IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2. Unbalanced 3-Phase Supply Voltage
NOMINAL
SIZE
VOLTAGE
48E
(3 Ph 60 Hz)
208/230 187 254 57.1 266 57.1 266 2 1 5.3
034
038
nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent voltage imbalance. % Voltage Imbalance
= 100 x
460 414 508 25.6 120 25.6 120 2 1 2.7
575 518 632 20.5 96 20.5 96 2 1 2.4
208/230 187 254 57.1 266 57.1 266 4 1 5.3
460 414 508 25.6 120 25.6 120 4 1 2.7
575 518 632 20.5 96 20.5 96 4 1 2.4
Refrigeration
max voltage deviation from average voltage
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
LEGEND
Use the following formula to determine
average voltage
COMPRESSOR
No. 1 No. 2
or
OFM IFM
FLA
Hp FLA FLA LRA FLA MCA MOCP*
(ea)
10
15
20
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
10
15
20
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 − 452=5v (BC) 464 − 457=7v (AC) 457 − 455=2v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER
EXHAUST
0.96 169.9/167.1 225/200
30.8/
28.0
23.6 41.6 0.96 193.5/190.7 250/225 — 0.96 185.3/181.1 225/225
46.2/
42.0
23.6 41.6 0.96 208.9/204.7 250/250 — 0.96 198.5/193.1 250/250
59.4/
54.0
23.6 41.6 0.96 222.1/216.7 275/250 — 0.50 77.0 100
12.6 23.6 0.50 89.6 110 — 0.50 84.0 100
12.6 23.6 0.50 96.6 110 — 0.50 90.0 110
12.6 23.6 0.50 102.6 125 — 0.50 61.9 80
12.6 23.6 0.50 74.5 90 — 0.50 67.9 80
12.6 23.6 0.50 80.5 100 — 0.50 72.9 90
12.6 23.6 0.50 85.5 100 — 0.96 180.5/177.7 225/225
30.8/
28.0
23.6 41.6 0.96 204.1/201.3 250/250 — 0.96 195.9/191.7 250/225
46.2/
42.0
23.6 41.6 0.96 219.5/215.3 275/250 — 0.96 209.1/203.7 250/250
59.4/
54.0
23.6 41.6 0.96 232.7/227.3 275/275 — 0.50 82.4 100
12.6 23.6 0.50 95.0 110 — 0.50 89.4 110
12.6 23.6 0.50 102.0 125 — 0.50 95.4 110
12.6 23.6 0.50 108.0 125 — 0.50 66.7 80
12.6 23.6 0.50 79.3 90 — 0.50 72.7 90
12.6 23.6 0.50 85.3 100 — 0.50 77.7 90
12.6 23.6 0.50 90.3 110
COMBUSTION
FAN MOTOR
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
7
457
= 1.53%
POWER SUPPLY
452 + 464 + 455
3
1371
=
3
= 457
19
Table 4 — Electrical Data (cont)
UNIT
FLA Full Load Amps HACR — Heating, Air Conditioning and
IFM Indoor (Evaporator) Fan Motor LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code OFM Outdoor (Condenser) Fan Motor RLA Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2. Unbalanced 3-Phase Supply Voltage
NOMINAL
SIZE
VOLTAGE
48E
(3 Ph 60 Hz)
208/230 187 254 69.2 345 69.2 345 4 1 5.3
044
048
nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply volt­age is greater than 2%.
the percent voltage imbalance. % Voltage Imbalance
= 100 x
460 414 508 28.8 173 28.8 173 4 1 2.7
575 518 632 26.7 120 26.7 120 4 1 2.4
208/230 187 254 82.1 446 69.2 345 4 1 5.3
460 414 508 42.3 223 28.8 173 4 1 2.7
575 518 632 34.6 164 26.7 120 4 1 2.4
Refrigeration
max voltage deviation from average voltage
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA Qty Hp
LEGEND
Use the following formula to determine
average voltage
COMPRESSOR
No. 1 No. 2
or
OFM IFM
FLA
Hp FLA FLA LRA FLA MCA MOCP*
(ea)
15
20
25
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
20
25
30
20 27.0
25 34.0
30 40.0
20 22.0
25 27.0
30 32.0
EXAMPLE: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 − 452=5v (BC) 464 − 457=7v (AC) 457 − 455=2v
Maximum deviation is 7 v. Determine percent voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT:Ifthesupply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER
EXHAUST
0.96 223.1/218.9 275/275
46.2/
42.0
23.6 41.6 0.96 246.7/242.5 300/300 — 0.96 236.3/230.9 300/300
59.4/
54.0
23.6 41.6 0.96 259.9/254.5 300/300 — 0.96 251.7/244.9 300/300
74.8/
68.0
23.6 41.6 0.96 275.3/268.5 300/300 — 0.50 96.6 125
12.6 23.6 0.50 109.2 125 — 0.50 102.6 125
12.6 23.6 0.50 115.2 125 — 0.50 109.6 125
12.6 23.6 0.50 122.2 150 — 0.50 86.7 110
12.6 23.6 0.50 99.3 125 — 0.50 91.7 110
12.6 23.6 0.50 104.3 125 — 0.50 96.7 110
12.6 23.6 0.50 109.3 125 — 0.96 252.4/247.0 300/300
59.4/
54.0
23.6 41.6 0.96 276.0/270.6 300/300 — 0.96 267.8/261.0 300/300
74.8/
68.0
23.6 41.6 0.96 291.4/284.6 300/300 — 0.96 281.0/273.0 300/300
88.0/
80.0
23.6 41.6 0.96 304.6/296.6 350/300 — 0.50 119.5 150
12.6 23.6 0.50 132.1 150 — 0.50 126.5 150
12.6 23.6 0.50 139.1 175 — 0.50 132.5 150
12.6 23.6 0.50 145.1 175 — 0.50 101.6 125
12.6 23.6 0.50 114.2 125 — 0.50 106.6 125
12.6 23.6 0.50 119.2 150 — 0.50 111.6 125
12.6 23.6 0.50 124.2 150
COMBUSTION
FAN MOTOR
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
7
457
= 1.53%
POWER SUPPLY
452 + 464 + 455
3
1371
=
3
= 457
20
Loading...
+ 44 hidden pages