1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s
Information Manual provided with this unit for more
details.
2. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other
appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone
in your building.
3. IMMEDIATELY call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire
department.
Disconnect gas piping from unit when pressure testing
at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in haz-
ardous condition. If gas valve is subjected to pressure
greater than 0.5 psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
0.5 psig or less, a unit connected to such piping must be
isolated by closing the manual gas valve(s).
INSTALLATION
Step 1 — Provide Unit Support
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical components. Only trained andqualifiedservice personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters.
All other operations should be performed by trained service
personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached
to the unit, and other safety precautions that may apply.
Follow all safety codes. Wearsafety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1
Tab 1a
PC 111Catalog No. 564-962Printed in U.S.A.Form 48E-5SIPg 18-97Replaces: 48E-3SI
1. All panels must be in place when rigging.
2. Unit is not designed for handling by fork truck.
ROOF CURB — Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory.See
Fig. 1 and 2. Install insulation, cant strips, roofing, and counter
flashing as shown. Ductwork can be installed to roof curb
before unit is set in place. Curb should be level. This is necessary to permit unit drain to function properly. Unit leveling tolerance is shown in Fig. 1 and 2. Refer to Accessory
Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may
be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof
curb is critical for a watertight seal. Install gasket with
the roof curb as shown in Fig. 1 and 2. Improperly
applied gasket can also result in air leaks and poor unit
performance.
ALTERNATE UNIT SUPPORT— When the preferred curb
or slab mount cannot be used, support unit with sleepers on
perimeter, using unit curb support area. If sleepers cannot be
used, support long sides of unit (refer to Fig. 3-6) with a
minimum number of 4-in. x 4-in. pads spaced as follows:
48EJ,EK,EW,EY024-034 units require 3 pads on each side;
48EJ,EK,EW,EY038-048 units require 4 pads on each side.
Unit may sag if supported by corners only.
Step 2 — Rig and Place Unit — Inspect unit for trans-
portation damage. File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over
unit to prevent sling or cable damage. Level by using unit
frame as a reference; leveling tolerance is shown in Fig. 1
and 2. See Fig. 7 for additional information. Unit operating
weight is shown in Table 1.
NOTE: On retrofit jobs, ductwork may be attached to old
unit instead of roof curb. Be careful not to damage ductwork
when removing old unit. Attach existing ductwork to roof
curb instead of unit.
Four lifting lugs are provided on the unit base rails as shown
in Fig. 7. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 3-6, around
and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate
unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and ventilation air must be provided in accordance with
Section 5.3 (Air for Combustion and Ventilation) of the
National Fuel Gas Code, ANSI Z223.1 (American National
Standards Institute).
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least
4 ft from any opening through which combustion products
could enter the building, and at least 4 ft from any adjacent
building. When unit is located adjacent to public walkways,
flue assembly must be at least 7 ft above grade.
ROOF MOUNT — Check building codes for weight distribution requirements. Unit weight is shown in Table 1.
Step 3 — Field Fabricate Ductwork
48EJ,EK UNITS — Field-fabricated ductwork should be attached to the roof curb. Supply and return duct dimensions
are shown in Fig. 3 and 4. Air distribution is shown in
Fig. 8.
To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to
14-gage roof curb material with sheet metal screws driven
from inside the duct.
Secure all ducts to the building structure, using flexible
duct connectors between roof curb and ducts as required. Ducts
passing through an unoccupied space must be insulated and
covered with a vapor barrier. Outlet grilles must not lie
directly below unit discharge. The return duct must have a
90-degree elbow before opening into the building space if
the unit is equipped with power exhaust.
For vertical supply and return units, tools or parts could
drop into ductwork and cause an injury. Install 90 degree elbow turns in the supply and return ductwork between the unit and the conditioned space. If a 90 degree
elbow cannot be installed, then grilles of sufficientstrength
and density should be installed to prevent objects from
falling into the conditioned space.
48EW,EY UNITS — Remove shipping covers from supply
and return air openings. Attach field-supplied ductwork to
unit. Use a single duct over both return openings and a single
duct over both supply openings. See Fig. 5 and 6 for duct
opening dimensions. Secure all ducts to the building structure. See Fig. 9. Use flexible duct connectors between unit
and ducts as required. Insulate and weatherproof all external
ductwork, joints, and building openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be
insulated and covered with a vapor barrier.
Install accesssory barometric relief or power exhaust in
the field-fabricated return ductwork. Refer to Position Power
Exhaust/Barometric Relief Damper Hood section on
page 26 for more information.
Instructions continued on page 12.
2
NOTES:
1. All roof curb parts are to be 16 ga galvanized steel.
2. Dimensions are in inches.
3. Toprevent standing water in the drain pan of the indoor
sectionandtheheatexchangers,unit can only be pitched
as shown.
Fig. 1 — Roof Curb (Sizes 024-034)
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg.in.Deg.in.
1.02.9.50.75
3
NOTES:
1. All roof curb parts are to be 16 ga galvanized steel.
2. Dimensions are in inches.
3. Toprevent standing water in the drain pan of the indoor
sectionandtheheatexchangers,unit can only be pitched
as shown.
Fig. 2 — Roof Curb (Sizes 038-048)
UNIT LEVELING TOLERANCES DIMENSIONS*
*From edge of unit to horizontal.
(Degrees and Inches)
AB
Deg.in.Deg.in.
1.02.9.50.75
4
VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.Center of gravity.
3. Do not locate adjacent units with flue dischargefacingeconomizerinlet.Minimum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Gas Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of
Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier Application Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb. If unit is mounted on dunnage, it is recommended the ducts be
supported by cross braces as done on accessory roof curb.
6. Dimensions are in inches.
UNIT
SIZE
OPERATING
WEIGHT
lbft-in.ft-in.1234
48EJ,EKD02441766- 0
48EJE02442566- 1
48EJ,EKD02842625- 9
48EJE02843425-10
48EJ,EKD03042625- 9
48EJE03043425-10
48EJ,EKD03442625- 9
48EJE03443425-10
ABCORNER WEIGHT (lb)
3
⁄83-63⁄8879 954 1220 1124
5
⁄163-611⁄16917 973 1218 1148
5
⁄83-8899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
5
⁄83-8899 899 1232 1232
1
⁄83-85⁄16929 916 1240 1257
Fig. 3 — Base Unit Dimensions, 48EJ,EK024-034
5
VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet. Minimum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Gas Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact
Carrier Application Engineering department.
5. Bottom ducts designed to be attached to accessory roof curb.
If unit is mounted on dunnage, it is recommended the ducts be
supported by cross braces as done on accessory roof curb.
6. Dimensions are in inches.
Fig. 4 — Base Unit Dimensions, 48EJ,EK038-048
UNIT
SIZE
OPERATING
WEIGHT
lbft-in.ft-in.1234
48EJ,EKD03844427- 8
48EJE03846027-10
48EJ,EKD04446687- 5
48EJE04448287- 6
48EJ,EKD04849557- 3
48EJE04851157- 5
6
ABCORNER WEIGHT (lb)
11
⁄163-107⁄81021 894 1180 1347
1
⁄83-113⁄161080 934 1200 1388
5
⁄163-107⁄81033 906 1275 1455
13
⁄163-113⁄161094 945 1293 1496
11
⁄163-101⁄21068 953 1384 1550
3
⁄163-1013⁄161129 994 1401 1592
VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer inlet.
Minimum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Gas Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier
Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply ductwork
connection is recommended for covering both return and both supply
openings.
Fig. 5 — Base Unit Dimensions, 48EW,EY024-034
UNIT
SIZE
OPERATING
WEIGHT
lbft-in.ft-in.1234
48EW,EYD02441766- 0
48EWE02442566- 1
48EW,EYD02842625- 9
48EWE02843425-10
48EW,EYD03042625- 9
48EWE03043425-10
48EW,EYD03442625- 9
48EWE03443425-10
7
ABCORNER WEIGHT (lb)
3
⁄83-63⁄887995412201124
5
⁄163-611⁄1691797312181148
5
⁄83-889989912321232
1
⁄83-85⁄1692991612401257
5
⁄83-889989912321232
1
⁄83-85⁄1692991612401257
5
⁄83-889989912321232
1
⁄83-85⁄1692991612401257
VFD — Variable Frequency Drive
NOTES:
1. Weights include economizer (STD).
2.Center of gravity.
3. Do not locate adjacent units with flue discharge facing economizer
inlet. Minimum clearances to be:
Adjacent Units: 158-09
Top of Units: No overhang
Condenser Coil: 48-09
Economizer Side: 68-09
Gas Heat Side: 48-09
Filter Access Side: 108-09 (For Removal of Evaporator Coil)
4. For smaller service and operational clearances, contact Carrier
Application Engineering department.
5. Dimensions are in inches.
6. For side-supply/return applications, a single return and supply ductwork connection is recommended for covering both return and both
supply openings.
Fig. 6 — Base Unit Dimensions, 48EW,EY038-048
UNIT
SIZE
OPERATING
WEIGHT
lbft-in.ft-in.1234
48EW,EYD03844427- 8
48EWE03846027-10
48EW,EYD04446687- 5
48EWE04448287- 6
48EW,EYD04849557- 3
48EWE04851157- 5
8
ABCORNER WEIGHT (lb)
11
⁄163-107⁄8102189411801347
1
⁄83-113⁄
5
⁄163-107⁄8103390612751455
13
⁄163-113⁄
11
⁄163-101⁄2106895313841550
3
⁄163-1013⁄16112999414011592
16
108093412001388
16
109494512931496
UNIT
48EJ,EK,EW,EYD024 4176 1894
48EJ,EWE0244256 193073.3 186242.7 1085
48EJ,EK,EW,EYD028
48EJ,EK,EW,EYD034
48EJ,EWE028
48EJ,EWE034
48EJ,EK,EW,EYD038 4442 2015
48EJ,EWE0384602 208794.1 239047.2 1199
48EJ,EK,EW,EYD044 4668 211789.32268 46.91191
48EJ,EWE0444828 219090.8 230647.2 1199
48EJ,EK,EW,EYD048 4955 224887.72228 46.51181
48EJ,EWE0485115 232089.2 226646.8 1189
WEIGHTABC
lbkgin.mmin.mmin.mm
72.4 183942.4 1072
4262 193369.61768 44.0111848EJ,EK,EW,EYD030
4342 196970.11781 44.3112548EJ,EWE030
87.68 2227
92.7 235546.9 1191
1503810
NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE
WHEN RIGGING.
NOTE: Rig with four cables and spread with two
92 in. (2337 mm) spreader bars. Maintain a distance of 74 in. (1880 mm) from top of unit to
eyehook.
NOTE:
Add 32 lb (14.5 kg) for domestic crating.
Add 312 lb (142 kg) for export crating (024-034 units).
Add 346 lb (157 kg) for export crating (038-048 units).
Add 250 lb (113 kg) for power exhaust.
Add 220 lb (100 kg) for copper condenser coil (024-034 units).
Add 285 lb (129 kg) for copper condenser coil (038,044 units).
Add 380 lb (172 kg) for copper condenser coil (048 unit).
Fig. 7 — Rigging Label
9
Table 1 — Physical Data
UNIT 48EJ,EK,EW,EY024D/E028D/E030D/E034D/E
NOMINAL CAPACITY (tons)20252730
OPERATING WEIGHT (lb)*
Unit
Al/Al† (Lo Heat/Hi Heat)4176/42564262/43424262/43424262/4342
Al/Cu† (Lo Heat/Hi Heat)4396/44764482/45624482/45624482/4562
Roof Curb (14-in. curb)365365365365
Quantity11 1 1
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)33.333.333.333.3
CONDENSER FANPropeller Type
Nominal Cfm13,42013,42013,42013,420
Quantity...Diameter (in.)2...302...302...302...30
Motor Hp (1075 Rpm)11 1 1
EVAPORATOR COILCross-Hatched
Rows...Fins/in.4...154...154...154...15
Total Face Area (sq ft)31.731.731.731.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20x152...20x152...20x152...20x15
Type DriveBeltBeltBeltBelt
Nominal Cfm8,00010,00011,00012,000
Motor Hp510††157.510††151015††201015††20
Motor Frame Size (Standard)S184TS215TD254TS213TS215TD254TS215TD254TS256TS215TD254TS256T
Motor Bearing TypeBallBallBallBall
Maximum Allowable Rpm1200120012001200
Motor Pulley Pitch Diameter4.84.45.75.46.15.54.44.95.94.45.75.9
Nominal Motor Shaft Diameter (in.)1
Fan Pulley Pitch Diameter (in.)12.48.69.112.411.18.79.48.18.79.09.18.7
Nominal Fan Shaft Diameter (in.)1
Belt, Quantity...Type
Belt, Length (in.)
Pulley Center Line Distance (in.)16.0-18.7 15.6-18.4 15.0-17.915.6-18.415.0-17.9 15.6-18.415.0-17.915.6-18.415.0-17.9
Factory Speed Setting (rpm)717924109677396211068481059118788410961187
UNIT 48EJ,EK,EW,EY038D/E044D/E048D/E
NOMINAL CAPACITY (tons)354045
OPERATING WEIGHT (lb)*
Unit
Al/Al† (Lo Heat/Hi Heat)4442/46024668/48284955/5115
Al/Cu† (Lo Heat/Hi Heat)4727/48874953/51135335/5495
Roof Curb (14-in. curb)410410410
COMPRESSOR
Type Ckt 106D53706EA25006EA265
Ckt 206D53706EA25006EA250
Number of Refrigerant Circuits222
Oil (oz) (Ckt 1, Ckt 2)115 ea.224 ea.304, 224
REFRIGERANT TYPER-22
Operating Charge (lb-oz)
Circuit 1**34-035-041-0
Circuit 234-035-041-0
CONDENSER COILCross-Hatched
Quantity2211
Rows...Fins/in.3...153...154...153...15
Total Face Area (sq ft)58.358.366.7
CONDENSER FANPropeller Type
Nominal Cfm27,06427,06427,064
Quantity...Diameter (in.)4...304...304...30
Motor Hp (1075 Rpm)111
EVAPORATOR COILCross-Hatched
Rows...Fins/in.3...153...154...15
Total Face Area (sq ft)34.734.734.7
EVAPORATOR FANCentrifugal Type
Quantity...Size (in.)2...20x152...20x152...20x15
Type DriveBeltBeltBelt
Nominal Cfm14,00016,00018,000
Motor Hp1015††201520††252025††30
Motor Frame Size (Standard)S215TD254TS256TD254TS256TS284TS256TS284TS286T
Motor Bearing TypeBallBallBall
Maximum Allowable Rpm120012001200
Motor Pulley Pitch Diameter6.15.35.75.35.77.56.35.97.5
Nominal Motor Shaft Diameter (in.)1
Fan Pulley Pitch Diameter (in.)13.79.59.59.59.511.111.112.511.1
Nominal Fan Shaft Diameter (in.)1
Belt, Quantity...Type
Belt, Length (in.)
Pulley Center Line Distance (in.)15.6-18.415.0-17.915.0-17.914.6-17.615.0-17.914.6-17.6
Factory Speed Setting (rpm)77997610509761050118299311341182
inside gas section of unit. To install, secure flue hood to access panel. See Fig. 10.
NOTE: When properly installed, flue hood will line up with
combustion fan housing. See Fig. 11.
BELT
(Lb at
.24 in.)
Fig. 8 — Air Distribution — Thru-the-Bottom
Fig. 9 — Air Distribution — Thru-the-Side
Fig. 10 — Flue Hood Location
12
Step5—TrapCondensate Drain — See Fig. 3-6
for drain location. Condensate drain is open to atmosphere
and must be trapped. Install a trapped drain at the drain location. A trap at least 4-in. deep must be used. See Fig. 12.
Trap must be installed to prevent freeze-up.
Condensate pans are sloped so that water will completely
drain from the condensate pan to comply with indoor air quality guidelines. The condensate drain pan is fitted with a 1-in.
FPT coupling.
Step 6 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local
building codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a
sure tap for test gage connection at unit. Field gas piping
must include sediment trap and union. See Fig. 13. An
1
⁄8-in. NPT is also located on the gas manifold adjacent to
the gas valve.
Do not pressure test gas supply while connected to unit.
Always disconnect union before servicing.
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than
13.5 in. wg.
1
⁄8-in. NPT pres-
Fig. 11 — Combustion Fan Housing Location
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas
connection.
Step 7 — Controls Options — The control options
that the units can provide are based on the following parameters: CV (constant volume) or VAV (variable air volume)
operation; stand-alone unit with field-supplied sensors installed (CV or VAV); as a system via Carrier Comfort System (TEMP or VVTt); optional electronic expansion board
installed (CV or VAV); linked to the Carrier Comfort
Network; and availability of a computer and software
(ComfortWorks™ Building Supervisor, and Service Tool) or
LID-2B accessory installed to access the base control board.
See Table 3.
NOTE: Access to the base control board allows unit occupancy schedules, unit timeclock, and various set points to be
changed from their factory-defined default settings.
All units are equipped with a supply air thermistor (SAT)
located in the supply fan discharge and an outdoor air thermistor (OAT) located in the outdoor air hood. Variable air
volume units are supplied with a return air thermistor (RAT)
located on the return air damper support.
CONSTANT VOLUME APPLICATIONS — The units, as
shipped, are operable as stand-alone units, using either a standard (mechanical or electronic) 2-stage heat, 2-stage cool thermostat, or with an electronic room sensor and a timeclock to
establish unit start and stop times.
With a standard thermostat (programmable is optional),
heating and cooling operation is set by space temperature.
With a space sensor and timeclock, the machine will operate at default values unless they are changed using appropriate input devices. The space sensor senses space temperature and may be equipped with a timed override feature, which
allows unit operation during unoccupied periods.
Fig. 12 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
Fig. 13 — Field Gas Piping
The space sensors may be used in multiples of 4 or 9 to
achieve space temperature averaging. The use of a space sensor also allows the unit to be turned on and off from a remote signal.
Features with Thermostat Control of Unit
• two-stage heating
• two-stage cooling
• control of unit using Y1, Y2, W1, W2, and G thermostat
inputs
• control of the indoor fan
• outdoor-air temperature/supply-air temperature
monitoring
• control of an outdoor air condenser fan based on outdoor-
air temperature
13
Table 3 — Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATIONDEFAULT COOLINGDEFAULT HEATING
CV or VAV Unit with SPT Sensor
CV Unit with SPT Sensor and Remote
Start/Stop Switch
VAV Unit Remote Start/Stop Switch Only
VAV Unit with SPT Sensor and Remote
Start/Stop Switch
LEGEND
CV— Constant Volume
NA — Not Available
RAT — Return-Air Temperature
SAT — Supply-Air Temperature
SPT — Space Temperature
VAV — VariableAir Volume
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling— NA
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling— 78 F (SPT)
Unoccupied Cooling — 90 F (RAT)
Occupied Cooling— 55 F (SAT)
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling— 55 F (SAT)
*With DIP Switch No. 5 configured to OPEN (Occupied Heat
Enabled).
NOTE: Space temperature sensor and remote start/stop switch are
field-supplied.
Unoccupied Heating — 55 F (SPT)
Occupied Heating— NA
Unoccupied Heating — 55 F (SPT)
Occupied Heating— 68 F (SPT)
Unoccupied Heating — 55 F (RAT)
Occupied Heating— 68 F (RAT)*
Unoccupied Heating — 55 F (SPT)
Occupied Heating— 68 F (RAT)*
• control of modulating economizer damper to provide free
cooling when outdoor conditions are suitable, using
supply-air temperature as a control point
• control of the economizer damper and indoor fan to obtain
unoccupied free cooling
• provide power exhaust output to an external power exhaust controller
• support a field test for field checkout
• control of 2 stages of CV power exhaust
• compressor Time Guardt (power up, minimum off and on
times)
• compressor lockout during low supply-air temperature
Additional features are provided by accessing the standard unit control board via software with a computer. These
features are:
• electronic expansion board features (if installed)
• control board diagnostics
• ability to change supply air set point (economizer control)
• ability to change high outdoor temperature lockout set point
(economizer control)
• ability to change power exhaust set points
NOTE: A CV unit without a thermostat requires a field-
supplied sensor for operation.
Features with Sensor Control of Unit (Stand-Alone Appli-
cations — Unit control is limited to CV unoccupied default
set points, 90 F for cooling, 55 F for heating. There are
2 sensor options available:
• T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
• T-56 sensor will monitor room temperature, provide un-
occupied override capability (1 hour), and provide a temperature offset of 5° F.
Standard features are:
• support of remote occupied/unoccupied input to start and
stop the unit
• cooling capacity control of 3 stages using economizer and
2 compressors to maintain space temperature to an occupied or unoccupied set point
• enable heating or cooling during unoccupied periods as
required to maintain space temperature within the unoccupied set points
• adjustment of space temperature set points of ±5° F when
using a T-56 sensor
Additional features with sensor control of unit (with computer access) are:
• 365 day timeclock with backup (supports minute, hour,day
of week, date, month, and year)
• daylight savings time function
• occupancy control with 8 periods for unit operation
• holiday table containing up to 18 holiday schedules
• ability to initiate timed override from T-55or T-56 sensors
for a timed period of 1 to 4 hours
• ability to use multiple space temperature sensors to average the space temperature
• temperature compensated start to calculate early start times
before occupancy
• access to the Display, Maintenance, Configuration,
Service, and Set Point data tables through network
software
When the unit is equipped with a field-supplied space
temperature sensor and a remote contact closure (remote start/
stop) on the base control board, the occupied default set points
will monitor unit operation. The occupied default set points
are 78 F cooling and 68 F heating. See Fig. 14 for remote
start/stop wiring.
NOTE: For units with a field-supplied space temperature sesor which have not had the base unit control board accessed
via software to set an occupancy schedule, the remote start/
stop closure will allow the unit to operate in the preconfigured occupied default set points (based on return-air
temperature) of 78 F cooling and 68 F heating. Without this
feature, the unit will control to the unoccupied default set
points of 90 F cooling and 55 F heating.
An electronic expansion board may be field-installed to
provide the following features:
• control of modulating economizer damper to maintain in-
door air quality (IAQ) when outdoor conditions are
suitable
NOTE: The IAQ sensor must be set for current output
(4 to 20 mA), not voltage output. Ensure the jumper on
the sensor is in the upper position. See Fig. 15.
• provide discrete inputs for fan status, filter status, field-
applied status, and demand limit
• provide an output for the external alarm light indicator
• provide power exhaust fire outputs for direct control of
modulated power exhaust stages during fire or smoke modes
• control of smoke control modes including evacuation, smoke
purge, pressurization, and fire shutdown (modulating power
exhaust required)
When the unit is connected to the CCN (Carrier Comfort
Network), the following expansion board features can be
utilized:
• perform Demand Limit functions based on CCN loadshed
commands or the state of the discrete input
• alarm monitoring of all key parameters
• CCN protocol
• provides CCN IAQ participation
See Carrier TEMP or VVTt (Variable Volume and Temperature) literature for complete TEMP (single zone) or VVT
(multi-zone) application information.
14
REMOTE
START/STOP
SWITCH
(FIELD-SUPPLIED)
R
Y1
Y2
W1
W2
G
C
X
CONTROL
BOX
LEGEND
Field Supplied Wiring
Fig. 14 — Field Control Remote Start/Stop
JUMPER CONNECTION
FOR VOLTAGE OUTPUT
JUMPER CONNECTION
FOR CURRENT OUTPUT
Fig. 15 — Indoor Air Quality Sensor Configuration
Features with Sensor Control of Unit (Network Applications) — The base control board provides, as standard, a connection for use with a Carrier VVT system and can also be
integrated into a Carrier Comfort Network.
When the unit is accessed via a PC equipped with ComfortWorks™, Building Supervisor, or Service Tool software,
or accessory LID-2B, the following features can be
accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored
This access is available on the base control board via a
RJ-11 phone jack or a 3-wire connection to the communication bus. See Fig. 16. The timeclock has a 10-hour minimum back-up time to provide for unit power off for servicing unit or during unexpected power outages. For complete
Carrier Comfort System (CCS) or Carrier Comfort Network
(CCN) features and benefits, refer to the product literature.
VARIABLE AIR VOLUME (VAV) APPLICATIONS
Features with Stand-Alone Applications — The units, as
shipped, are operable as stand-alone units with the addition
of a timeclock to establish unit start and stop times.
Heating and cooling in both on and off modes is controlled to default values by the base unit control. Set points
may be changed with appropriate input devices.
The control has an on-board occupancy schedule which
can be set using an input device and eliminates the need for
an external timeclock.
During both the on and off periods, cooling operation is
controlled to the supply air setting and heating is controlled
to the return air setting (or to the optional space temperature
sensor). During the on period, the supply fan runs continuously.During the off period, the supply fan will be activated
if the return air sensor is outside of the set points and will
run log enough to accurately sample the space temperature.
The supply fan will then continue to run until any heating or
cooling load is satisfied, at which point it will turn off.
The use of a space sensor will allow for supply air reset
to conserve energy and maintain comfort. If equipped with
an override feature, the sensor will allow operation during
the off period for a fixed length of time.
Base unit control supports a Heat Interlock Relay (field
supplied) to fully open the VAV terminal devices during heating operation.
Standard features of a VAV unit with a remote start/stop
switch are:
• control board diagnostics
• control of an outdoor condenser fan based upon outdoor
air temperature
• control of modulating economizer to provide free cooling
when outdoor conditions are suitable, using supply-air temperature as a set point
• support of remote occupied/unoccupied input to start or
stop the unit
• provide power exhaust output to an external power ex-
haust controller
• support supply-air temperature reset to offset supply air
set point
• support a field test for field check out
• support linkage to DAV systems
• cooling capacity control of up to 6 stages plus economizer
with compressors and unloaders to maintain supply air temperature set point during occupied periods
• control of one stage of heat to maintain return-air tem-
perature at heating set point during occupied periods
• provide a variable frequency drive high voltage relay out-
put to enable VFD
• control of heat interlock relay
• compressor Time Guard override (power up, minimum off
and on times)
With the addition of a remote start/stop switch heating or
cooling is enabled during unoccupied periods as required to
maintain space temperature to within unoccupied set points.
Additional features may be provided with Electronic
Access to Unit Control Board. These features are:
• additional control board diagnostics
• electronic expansion board features (if installed)
• control of the economizer damper and indoor fan to obtain
unoccupied free cooling
• 365-day timeclock with backup (supports minute, hour, day,
month, and year)
• holiday table containing up to 18 holiday schedules
• occupancy control with 8 periods for unit operation
• support a set of display, maintenance, configuration, serv-
ice, and set point data tables for interface with Building
Supervisor, ComfortWorks, or Service Tool software software or accessory LID-2B
15
When a VAV unit with a space temperature sensor is accessed via a computer, the following additional features are
available:
• ability to initiate timed override from T-55 sensors
• temperature compensated start to calculate early start time
before occupancy
• provide space temperature reset to reset the supply air set
point upward when the temperature falls below the occupied cooling set point
An electronic expansion board may be field-installed to
provide the following features:
• fan status
• filter status
• field-applied status
• demand limiting
• IAQ Sensor
• OAQ Sensor
• alarm light
• fire unit shutdown
• fire pressurization
• fire evacuation
• fire smoke purge
When the unit is connected to the CCN (Carrier Comfort
Network), the following expansion board features can be
utilized:
• CCN IAQ (indoor air quality) participation
• CCN OAQ (outdoor air quality) participation
• CCN demand limit participation
• modulated power exhaust override
• ability to use multiple space temperature sensors (mul-
tiples of 4 and 9 only) to average space temperature (DAV
only)
Afield-supplied T -55space temperature sensor can be added
to monitor room temperature and provide unoccupied override capability (1 hour).
When the unit is equipped with a field-supplied space temperature sensor and a remote contact closure (remote start/
stop) the occupied default set points will monitor unit operation. The occupied default set points are 55 F (supply air)
cooling and 68 F (return air temperature) heating. See
Fig. 14 for remote start/stop wiring.
NOTE: For units without a space temperature sensor and which
have not had the base unit control board accessed via software to set an occupancy schedule, the remote start/stop closure will allow the unit to operate in the pre-configured occupied default set points of 55 F (supply-air temperature)
cooling and 68 F (return-air temperature) heating. Without
an occupancy schedule, the unit will control to the unoccupied default set points of 90 F (return air) cooling and 55 F
(return air) heating.
Features with NetworkApplications —The base control board
provides, as standard, a connection for use with a Carrier
Comfort System and can also be integrated into a Carrier
Comfort Network. When the unit is accessed via a PC equipped
with ComfortWorks™, Building Supervisor, or Service Tool
software or LID-2B accessory,the following features can be
accessed:
• on-board timeclock can be programmed
• occupancy schedules can be programmed
• unit set points can be changed
• alarms can be monitored
This access is available on the base control board via a
RJ-11 phone jack or a 3-wire connection to the communication bus. See Fig. 16. The internal timeclock has a 10-hour
minimum back-up time to provide for unit power off for servicing unit or during unexpected power outages. For complete Carrier Comfort System (CCS) or Carrier Comfort
Network (CCN) features and benefits, refer to the product
literature.
Step 8 — Make Electrical Connections
POWER WIRING — Units are factory wired for the voltage
shown on the unit nameplate.
When installing units, provide a disconnect per NEC
(National Electrical Code) of adequate size (MOCP [maximum overcurrent protection] of unit is on the informative
plate). All field wiring must comply with NEC and all local
codes. Size wire based on MCA (minimum circuit amps) on
the unit informative plate. See Fig. 17 for power wiring connections to the unit power terminal block andequipment ground.
The main power terminal block is suitable for use with
aluminum or copper wire. See Fig. 17. Units have circuit
breakers for compressors, fan motors, and control circuit. If
required by local codes, provide an additional disconnectswitch.
Whenever external electrical sources are used, unit must be
electrically grounded in accordance with local codes, or in
absence of local codes, with NEC, ANSI C1-latest year.
All field wiring must comply with NEC and local code
requirements.
FIELD POWER SUPPLY — Unit is factory wired for voltage shown on unit nameplate. See Table 4 for electrical data.
Field wiring can be brought into the unit from bottom
(through basepan and roof curb) or through side of unit (corner post next to control box).
1
⁄2-in. NPT coupling for field power wiring and a
A3
3
⁄4-in. NPT coupling for 24-v control wiring are provided in
basepan. In the side post, there are two 21⁄2-in. (024-034) or
3-in. (038-048) knockouts for the field power wiring. See
Fig. 3-6. If control wiring is to be brought in through the
side of unit, a7⁄8-in. diameter hole is provided in the condenser side post next to the control box.
If disconnect box is mounted to corner post, be careful
not to drill any screws into the condenser coil.
Routing Through Bottom of Unit — If wiring is brought in
through bottom of unit, use field-supplied watertight conduit
to run power wiring from basepan out through bottom
31⁄2-in. hole to the disconnect box and back into unit to the
main control box.
Use strain relief going into control box through 2
diameter hole provided. After wires are in unit control box,
connect to power terminal block (see Power Wiring section
above).
Low-voltage wiring must be run in watertight conduit from
the basepan to control box and through
7
⁄8-in. diameter hole
provided in bottom of unit control box. Field-supplied strain
relief must be used going into the box. After wiring is in
control box, make connections to proper terminals on terminal blocks (see Field Control Wiring section on page 21).
Install conduit connector in unit basepan as shown in
Fig. 3-6. Route power and ground lines through connector to
terminal connections in unit control box as shown on unit
wiring diagram and Fig. 17.
Routing Through Side of Unit — Route power wiring in fieldsupplied watertight conduit into unit through 21⁄2-in. hole.
See Fig. 17.
Use field-supplied strain relief going into control box through
1
⁄2-in. diameter hole provided. After wires are in unit con-
2
trol box, connect to power terminal block (see Power Wiring
section on this page).
Bring low-voltage control wiring through factory-drilled
7
⁄8-in. diameter hole in condenser side post. Use strain relief
going into7⁄8-in. diameter hole in bottom of unit control box.
After wiring is in control box, make connection to proper
terminals on terminal blocks (see Field Control Wiring section on page 21).
1
⁄2-in.
16
17
LEGEND
CCN — Carrier Comfort Network
COM — Common
D—Diode
LED — Light-Emitting Diode
N.C. — Normally Closed
N.O. — Normally Open
R—Relay
SIO — Serial Input/Output
SW — Switch
T—Terminal
Fig. 16 — Control Board Diagram
*Where X is the unit control software version number.
FLA— Full Load Amps
HACR — Heating, Air Conditioning and
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2. Unbalanced 3-Phase Supply Voltage
NOMINAL
SIZE
VOLTAGE
48E
(3 Ph 60 Hz)
208/230187 254 57.1 266 57.1 266215.3
034
038
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percent voltage imbalance.
% Voltage Imbalance
FLA— Full Load Amps
HACR — Heating, Air Conditioning and
IFM— Indoor (Evaporator) Fan Motor
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC— National Electrical Code
OFM— Outdoor (Condenser) Fan Motor
RLA— Rated Load Amps
*Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combi-
2. Unbalanced 3-Phase Supply Voltage
NOMINAL
SIZE
VOLTAGE
48E
(3 Ph 60 Hz)
208/230187 254 69.2 345 69.2 345415.3
044
048
nation load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker. Canadian units may be fuse or circuit breaker.
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
the percent voltage imbalance.
% Voltage Imbalance