Carrier 58DP User Manual

58DP,DR
HEATING A COOLING
Downflow Gas-Fired Natural-Draft Furnaces

Installation, Start-Up and Service

Instructions

NOTE: Read the entire instructions before starting the
installation.
NOTE: The Energy Guide tag can be removed from the fur

INTRODUCTION

Before installing the furnace, refer to “Procedures for Natural-Draft Gas-Fired Furnaces” (packaged with the
equipment) for information concerning combustion, venting, piping, and other standard installation practices. Further reference is made to the current edition of the National Fuel
Gas Code NFPA No. 54, T1A-54-1984-1/ANSI Z223.1-1984, Z223.1a-1987.
Each furnace is shipped from the factory completely assem bled with multispeed direct-drive blower and wired ready for downflow indoor heating installation only. AU sizes feature a printed-circuit board control center with easy-to-read, low­voltage terminal strip to ensure proper connections.

A CAUTION

Do not install furnace in a damp, corrosive, or contami nated atmosphere. Make sure all combustion and circu lating air requirements listed in “Procedures for Natural-Draft Gas-Fired Furnaces” are adhered to, in addition to all local codes and ordinances.
Do not use this furnace during construction when adhe sives, sealers and/or new carpets are being installèd. If the furnace is required during construction, use clean outside air for combustion and ventilation. Compoxmds of chlorine and fluorine when burned with combustion air form acids which will cause corrosion of the heat
exchangers and metal vent system. Some of these com pounds are paneling and dry wall adhesives, paints, thinners, masonry cleaning materials, and many other solvents commonly used in the construction process.
The design of the downflow gas-flred furnace is A.G.A. cer tified for installation on noncombustible flooring. The fur nace may be installed on combustible flooring when installed with the accessory floor base. This furnace is for installation in alcoves, basements, closets, or utility rooms. This furnace line is not A.G.A. design certified for installa tion in a mobile home, recreation vehicle, or outdoors.
Installation comprises the following:
*1. Inspection
*11. Location, Ventilation, and Air for Combustion
*III. Gas Piping
*IV. Venting

V. Supply-Air Plenum Installation

VI. Electrical
EFFICIENCY RATING CERTIFIED
a
Sizes 050 075 thru 150 Sides—Single-Wall Vent 1 1
Back 0 0 Top of Plenum Vent Connector—Single-Wall 6 6
Front-Combustion Air* * 6 6
*The 6-inch front clearance is needed for combustion-air entry and
drafthood reiief.
ama
Fig. 1—Model 58DP
Table 1—Clearances (In Inches)
Type-BI Double-Wall Vent 0 1
1 1
Type-B1 Double-Wall 1 1
Service 30 30
A78593
VII. Sequence of Operation
VIII. Filter
IX. Startup and Adjustment
X. Care and Maintenance
*To perform these sections (or installation steps), refer to the appropriate sections of “Procedures for Natural-Draft Gas-Fired Furnaces” booklet packaged with this unit.
For accessory installation details, refer to the applicable
installation literature.
V. SUPPLY-AIR PLENUM INSTALLATION A. Installation on a concrete slab
1. See Fig. 2 for dimensions and location of supply-air
opening in furnace bottom.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
'' I ^ PC 101 Cataiog No. 535-871 Printed in U.S.A. Form 58DP,DR-2SI 11/87
Tab I6al8a
Pgl
Repiaces: 58DP,DR-1Si
Table 2—Dimensions (in Inches)
Size Vent 050-BA 075-AA 075-BA 100-AA 17’¿ 100-BA 125-AA 21 125-BA 150-BA
14^16 12^,6
M'h M'k
177^
21
24’¿
15%
157s 15% 15%
19% 19%
22'%s
12-’-’/i6
16 4 16 4 16 5
16 19% 5 19%
23

Fig. 2—Dimensionai Drawing

Table 3—Ratings and Performance*
Size
050-BA 075-AA 075-BA 100-AA 100-BA 125-AA 125-AA 150-BA
*The above ratings are certified for aititudes to 2000 ft. For elevators above 2000 ft, reduce ratings 4% for each 1000 ft above sea level. Refer to'
National Fuel Gas Code Table F4. fDetermined by U.S. Government tests. ijrDeduct 1000 Btuh for Model 58DR.
Input Btuh
50,000 39,000f 75,000 58,000
100,000 78,000t
125,000 97,000f
150,000
Capacity
Btuht
116,000f
Temp
Rise
Range
45—75 0.50 70—100 0.12 45—75 0.50 895 70—100 0.20 850 60—90 0.50 70—100 0.20 60—90 55—85 0.50 1535
Ext Static
Pressure
0.50
Heating
CFM
Ext Static
600 0.5 800 %-SP 630
960 0.5 1630 %-PSC 1050 1195 0.5 1620 'k-PSC 187
Cooling Motor
Pressure
0.5 1255 %-SP 157
0.5 2075 %-PSC
CFM
HP&
Type
7io-SP
%-SP
'h-SP
2. Construct hole in floor per dimensions in Fig. 3 and
Table 4.
3. Place plenum and furnace as shown in Fig. 4.
B. Installation on a combustible floor
1. Read Installation Instructions packaged with acces sory combustible floor base.
2. Cut and frame hole in floor per dimensions hsted in Installation Instructions packaged with combustible floor base. If this requires cutting of a floor joist, tie ends of cut joist into adjacent joists so that proper floor support win be maintained.
3. Assemble and install combustible floor base per
instructions packaged with base.
4. When completed, combustible floor base, plenum, and furnace (or coü casing when used) should be installed as shown in Fig. 6.
A73382
4
5
5 6
Approx
Shipping
Weight
129 148
163 170 187
227
Fig. 3—Floor Opening for
Concrete Slab
Table 4—Opening Dimensions
Furnace Casing
Width 14%6
17%
21
24%
♦These dimensions apply when a Model 28RC or RD Evaporator Coil
casing is to be installed.
A B
13% 19%
16%6
19% 19%
23%6
Heat-Only Heat/Cool*
19%
19%
19%6 19%s 19%6 19%6
2
Fig. 5—Combustible Floor Base

A WARNING

The cabinet must have an uninterrupted or unbroken ground according to National Electrical Code, ANSI/ NFPA 70-1987, or local codes to minimize personal
injury if an electrical fault should occur. This may con sist of electrical wire or conduit approved for electrical ground when installed in accordance with existing elec trical codes. Do not use gas piping as an electrical ground. A failure to adhere to this warning can result in an electrical shock, fire, or death.
If line-voltage wiring to the unit is encased in a nonmetallic sheath, connect the incoming ground wire to the grounding wire inside the furnace J-box. If metallic conduit is used, it will serve as the ground.
B. Low-Voltage Wiring
Make field low-voltage connections at the low-voltage termi nal strip. See Fig. 9.
NOTE: Use AWG No. 18 “color-coded” copper thermostat
wire for lengths up to 100 ft. Above 100 ft, use AWG No. 16 wire.
Fig. 6—Furnace, Plenum, and
Base Installed on a Combustible Floor
VI. ELECTRICAL CONNECTIONS A. Line-Voltage Wiring
NOTE: Refer to “Procedures for Natural-Draft Gas Fur
naces” (packaged with the equipment) for additional information.

A CAUTION

Do not connect aluminum wire between disconnect switch and furnace.
See Fig. 9 for wiring diagram showing the proper field high-
and low-voltage wiring. Use a separate fused branch electrical circuit containing a
properly sized fuse or HACR-type circuit breaker for this furnace. A disconnecting means must be located within sight from, and readily accessible to, the furnace. In some areas, the unit door switch may qualify as the disconnecting means.
Fig. 7—Amp Draw Check With Ammeter
mSm
A79077

Fig, 8—Printed-Circuit Control Center

3
A78461.
Loading...
+ 7 hidden pages