Carrier 50DQ User Manual

Carrier
installation, Start-Up
and Service Instructiôns*
Single-Package Heat Pump Units
50DQ
Ô16

INSTALLATION

General — Unit components are mounted to
located at bottom of the unit. Regardless of the
type of mounting configuration, allow a minimum of 12 in. under the outdoor coil for condensate drainage. Increase to 18 in. where prolonged sub-
freezing temperatures exist. Refer to paragraph on
Roof Adapter Curb and Duct Adapter Fabrication.
Roof Mount — Check building codes for weight
distribution requirements. Mount unit on a level platform or frame adequate to support unit weight and size.
Slab Mount — Provide a level concrete slab that
extends beyond unit cabinet at least 6 in. Make
slab 8 in. thick and 4 in. above grade. Refer to Table 1 for proper clearance under outdoor coils. Provide a gravel apron in front of outdoor air openings to prevent grass and foliage from ob
structing air flow.
Rigging and Unit Placement — Inspect unit for
transportation damage. File claim with trans
portation agency. Do not remove shipping skid until unit is ready to be placed. Do not drop unit.
GRAVirv
Fig. 1 - Rigging
Keep unit upright. Use spreader bars to prevent sling or cable damage to unit (Fig. 1). Level unit using unit frame as reference.
Locate unit as close as possible to duct open ings. Outdoor air inlet is not affected by wind. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. Provide clear ance around and above unit for air flow, safety and service access area as shown in Fig. 2.
Although unit is weatherproof, guard against water from higher grade runoff and overhangs. •

Table 1 — Physical Data

UNIT 50DQ OPERATING WEIGHT (lb) REFRIGERANT; R-22 (lb) COMPRESSOR
Oil PP 33-2 (pf)
OUTDOOR AIR FANS
Motor Hp ... Rpm
1-ph
3-ph
Motor Frame (NEMA)
INDOOR AIR FAN SECTION
Motor Hp ... Rpm Motor Frame (NEMA) Motor Pulley Range (in.) Fan Pulley (in.)
Belt; No. ... Type ... Length (in.)
Fan Speed Range Fan Factory Setting (Rpm) Max Allowable Fan Speed (Rpm) Speed change per ^2 turn of motor
movable pulley flange (Rpm)
Movable pulley factory setting
turns open
Max Allowab le full turns from
closed position
PRESSUrIsTAT SETTINGS (psig)
High cutout
cut-in
Low cutout
cut-in _
DEFROST THERMO CONTACTS -
EMERGENCY HEAT THERMO
CONJACTS_ _ _
FILTERS (factory-supplied)
No. ... Size
ANTICIPATOR SETTINGS
First Stage Heating Thermostat
Second Stage Heating Thermostat
1 relay 2 relays 3 relays
C L E A R ^ Q li IR E D U N D E R
OUTDOOR COILS
____
_____
Open Close
. Open . Close
016
1853
34
06DB537
10
2
% .. 1075 % 1140
48
3 .. 1725
56
4.0 - 5.0
8.2
A48 ... 49.3
860-1060
980
1200
20
2
5
390 ± 5 290 + 15
29 i 5 64 + 5
43 F
105 F
______
6 5 ± 6 F ^ 80 ± 6 F
C leanable
2 .. 20 X 20 X 1
2 ... 20 X 25 X 1
4
.8
1.2
12 to 18 in.
(S) © Carrier Corporation 1971
275
Form 50DQ-1SI
5 DIAM MOUNTING HOLES (6)
© Outdoor coil air flow
indoor coil a;r flow
SPACE FOR SERVICE AND AIR FLOW'
\FiLTER ACCESS PANEL
(SOTH ENOS)
\ ACCESSORY ELECTRIC
HEATER ACCESS
'For eiectric heater and indoor air fan section
rerriovai.
NOTES:
1 Provide 6 ft above unit for fan deck service
clearance and outdoor coii air flow.
2. Provide 3 ft in front of unit to accorrs.-nodate rooftop adapter (if used).
3 fi/iain power connections for accessory eiectric
¡'.eaters (if used) must be at compressor end
of unit
Certified dimension drawings are available on recuest.
Fig. 2 — Physical Data and Dimensions; 50DQ016 Unit
■-}
.-'i?
5 MPT
CONDENSATE DRAIN
4
Loading...
+ 4 hidden pages