Combination Heating/Cooling Units
MODEL
48DL,DM006300
48DL,DM006310
48DL,DM006400
48DL,DM006410
48DL,DM0Ò65Ò0
48DL,DM006510
48DL,DM006600
48DL,DM006610
o
O
□
INDEX
VOLTS/PH
230/1
208/3
230/3
460/3
LABEL DIAGRAM
F
48DL504344
48DL504334
48DL504364
LEGEND
Contactoi
Cooling Compensator
Com|)i essoi
Gas Valve
Heal ArUicipalor
Ignition Commi
Indooi Fan Moloi
Indoor Fari Motor Capaoiloi
Indooi Fan Relay
Limit Switch
Outdoor Fan Motor
Outdoor Fan Motot Capacitor
Ouad Ter minai
Run Capacitor
Roll-Out Swilcii
Star t Capacitor
Start Relay
Thermostat Cooling
Time Delay Relay
Thermostat Healing
r I atisiormcr
To indicate common potential only,
not to represent wire
Field F-^ower Wires
Fiiild Control Wires
Field Ground Wites
Field Splice
Junction
Component Conriections (marked)
Comporront Connections (uninai ked)
Tliermostat Conriectiotis
Dwg No.
NOTES
1. Fan motors are thermally protected.
2 Terminations in low-voltage connection box
suitable for connection of NFC Class 2 control
circuit wiring at 24 volts.
3. Wire units in accordance with local codes
4 When original factory wiring must be replaced,
use the same type of wire or equivalent
5 Use copper or copper-clad conductors only
CONTROL CENTERS
No. 1 No. 2 No. 3
HH07AT074 HH01AD042
Thermostat 1 hermostnt Thermostat
and and and
HH93AZ076t
S u b b a s e
*Contml Centers shown on Label Diagrams
¡Automatic Changeover Subbase
HH93AZ080 is suitable for use if manual changcovei is
desired
HH93AZ042
Subbase Subbase
INITIAL START-UP SEQUENCE
Start-Up Sequence, Natural and LP Gas Units With
Intermittent Spark Ignition of Pilot, indoor (evap
*
HH01AD040
1IH93AZ040
orator) fan motor time delay relay and Essex
SX242 gas valve. (See Caution above )
MANUAL SEQUENCE
1 With power off turn manual gas valve knob to
ON position
2 Set thermostat selector switch at HEAT posi
tion and set thermostat dial a few degrees above
room temperature.
3 Turn power on.
AUTOMATIC SEQUENCE
1 Pilot valve opens, spark ignition and indoor fan
time delay relay energize.
2 Gas flows to pilot and ignites Pilot flame
sensing probe permits energizing of the main
gas valve Gas flows to main burner and ignites
3 Time delay relay starts indoor fan motor in 30
— 45 seconds.
4. When thermostat setting is satisfied, main gas
valve and pilot gas valve close and flames are
extinguished
5 Indoor fan motor stops in 1- to 1-1/2 minutes
© Cairiei Corporation 1977
Forni 48DL 1W
CaBXIO??-. Do iiot »so màfcii»s to'
piìot oa ioimriiiient pOotumit^aS' fó'pos&ifcìe
elect ncsJ sitot.^ ha/:,arii.
GENERAL OPERATING SEQUENCES
These sequences apply to both natural and LP
gas units in normal operation after initial start-up
Operating Sequence-Heating
NATURAL GAS AND LP UNITS WITH INTER
MITTENT PILOT
1 Thermostat selector switch at HEAT or AUTO.
Thermostat dial set above room temperature,
2. Pilot gas valve opens Gas flows to pilot and
ignites Pilot flame setting probe causes main
gas valve to open Gas flows to main burner and
ignites.
3. TDR starts indoor fan motor in 30 — 45
seconds
4 When thermostat is satisfied both pilot gas and
main gas valves close. Pilot and main burner
flames arc extinguished.
5 TDR stops indoor fan motor in 1- to 1-1/2
minutes.
6 Pilot is on only when thermostat calls for
heating
Operating Sequence — Cooling
1 Unit energized. Thermostat selector switch at
COOL or AUTO Thermostat dial set below
room temperature
2 Indoor and outdoor fans and compressor start
3. When thermostat setting is satisfied, fans and
compressor stop.
Automatic Operation — Power and gas on. Room
thermostat (control center) set at AUTO. Fan
switch (on control center) set at AUTO.
Unit performs as described in the operating
sequences above on call for heating or cooling.
Automatic changeover type thermostat is required
Continuous Fan Operation — With power supplied
to unit and fan switch at ON position, indoor fan
remains on at all times.
Fig. 1 — Label Diagram, 48DL,DM006; 230-1-60
2