Carrier 48DH User Manual

Number One AirConditioniiX) Maker
e
Division of Cairier Corporation Syracuse New York
r
Combination Heating/Cooling Units
The 48DH, DL and DM combination heating/ cooling units are complete systems designed for outdoor installation on slab or rooftop.
Installation consists of: rigging and mounting the unit; attaching ductwork; making single gas, electrical and condensate connections; and attach ing thermostat leads. A field-furnished filter rack is required in the return air stream.

RECEIVING THE UNIT

Examine the unit carefully for any damage incurred in shipment. If found, file claim with
transportation company immediately.
Check unit nameplate to ensure that unit electrical requirements match available power
supply, and that unit is designed for use with the
proper gas type (natural or liquefied petroleum).
Leave unit on shipping skids until ready for
mounting.

INSTALLATION

Check national and local gas and electrical
codes and local building codes for any special installation requirements.
Unit Location — Install unit outdoors and as close
to building duct openings as possible. Unit may face in any direction since neither the condenser
air inlet nor the flue outlet (Fig. 1) are affected by
wind. Do not locate unit near sources of con
taminated air.
Although the unit is weatherproof, position
unit so that water and ice from roofs or eaves
cannot fall directly on the unit. SPACE LIMITATIONS - Provide sufficient space
for unimpeded air flow and for wiring and servicing unit (Fig. 1).
, CONO UNIT
2-0 OVERHEAD SPACE SECTION REQ FOR SERVICE AND ACCESS PANEL
AIR FLOW ;
002
'only .
SERVICE ^ OPENINGS ^0'
ACCESS SIDE
*This dimension is not applicable to 002 units because there are no
mounting rails
ta-'iiEiEJ ance space of 1 in. on duct connection side, and 12 in on
BOTH side:
FLUE OUTLET
—,—X::...
Space required for service Design certified by A G.A. for in­stallation on combustible type floor with a minimum ciear-
remaining sides
Indoor (Evaporator) Air
O'
____WIND CAP ASSEMBLY (CONDENSER AIR OUTLET
îLÎÎÎ 002 UNIT ONLY)
• DIAM*
(SmTG HOLES)
COMBUSTION AIR
.JSSiiSOc 045 8005
n DIAM HOLE
® FOR LINE
POWER WIRING
HEATING SECTION
i ACCESS PANEL
) Condenser Air
Fig. 1 — Physical Data
Table 1 — Base Unit Dimensions (ft-in.)
UNIT
A 3-10 В C D E F G H 0-11У 0-11У J
*Refer to Table 2 for differences of these series
48DL 48 DH 48DL 48DL 48 DM
002* 003
0-10V3
0-11 Уз
1- 0
2- 2У
0- 4 0- 4
3-10
0-1 оу 0-юу 0-1 оу
0-11 у
1- 0 1- 0 1- 0
2- 2%
4- 7 4- 7 4- 7% 4- 7%
1- 2
2- 2У
2- 2У 0-11У 0-11У 0- 4
1- 8 2- 2У
2- 2У 0- 4
48 DH 48DL
004
3_2
5-2У 5- 2% 5- 2%
1-ЗУ 1-8 1- 8 1-0
2-2У
2-4У 2- 2Ув 2- 4У
1-4У 0-7У
5- 2 5- 2 1- 5У 1- 0
2- 2У 1- 4У 1- 4У
0-11
Q45
1- ЗУ
1-11 1-11
1- 0
2- 2%
0- 7У
48DL
5- 2
5- 2У 1- ЗУ
1- 0
2- 2% 2- 2У
2- 4У 1- 4У 0- 7У
48DH
005
5- 7\
5- 8У
1 9
1-11
1- оу
2- 4У 1- 4У 1- 2У
Form 48DH-6
Table 2 — Physical Data
UNIT OPERATING WT (lb) REFRIG (22) CHG (Ib-oz) COMPRESSOR
Cyl inders 2 Rpm (60-Hz)
CONDENSER FAN
Air Quantity (Cfm)
Motor Hp
EVAPORATOR FAN
CAPACITY (1000 Btuh)
Cool in g Input Heotlng/Bonnet*
MAX EXTERNAL
STATIC PRESSURE Heating (in. W.C.)
FILTERSt (1-in. thick)
Disposable — No. .. 1 15x20 1 15x20
Size (in.) 1 .20x25 1 20x25 2 15x20 1 20x20
Permanenti — No. ..
Size (in.)
HEAT TEMP RISE (F)
* Ratings shown for elevations up to 2000 ft above sea level. For ele
vations above 2000 ft deduct 4% capacity for each 1000 ft above
sea level
48DL002
331
3.2
M27 (1-ph) M27 (1-ph)
AHbbz^/h(J-ph) AH5527h(3-ph)
1700 1700
Vs
24 24 30 36
56/42
1 15x20 1 15x20 1 20x20
35-65 45-75
48DH002 48DL003
343 385
3 2 3.6 5 1
2 2 2
Propel ler-Type — Direct Drive; Vertical Disc
Vs Vs
Centrifugal —
80/60
80/60
48DL004
M34 M40
2000 2500
Direct Drive; Horizontal Discharge
80/60
1 20x20 1 20x20 1 .20x20
35-65 35-65
i Recommended field-supplied filter
ifBased on 0.082 in. wg pressure drop or less thru filter at 520 ft/min
48 DM004
411
3500
Vs
110/82 5 125/93 75
40
1 20x20 1 .20x20 2 20x20
face velocity.
48DH004
430
5 1
M40
2
2500 2500 2700
Vs
36
35-65 45-75
438
M40 P46
2 2
Vs
36
1 15x20
48DL045 48DL005 48DH005
450 476
5 2 5 1 5 1
large
Vs
Г
42 48
100/75
1 20x25
35-65
P53
2
2700
V,
110/82 5
1 20x25 1 25x25
2 15x20
35 65
512
P53
2
2700
Vs
48
150/112 5
1 20x25 1 .25x25
2 15x20
45-75
OUTSIDE AIR LIMITATIONS - Although there
are no restrictions on either the percentage or the temperature of the outside air circulated thru the
unit, the rate of moisture condensation from the
combustion process increases significantly when return air temperature drops below 50 F. Protect
the drain holes in the bottom pan against ice buildup if outside air of below freezing tempera ture is used
VIBRATION ISOLATION -- The unit compressor, evaporator fan and condenser fan are mounted on isolators to minimize vibration. Additional isola
tion is not required for slab mounting. With some types of roof construction, however, the use of field-furnished mbber pad type isolators may be advisable.
Unit Rigging
1. Sling the unit perpendicularly to shipping skid mnners. Use spreader bars to prevent damage from sling or cable.
2. Raise unit to desired location and remove shipping skid.
3. Mount and level the unit as indicated in Unit Support and Mounting section.
Unit Support and Mounting
LEVELING THE UNIT — Level the unit from end to end but pitch the unit slightly (3/8 to 1/2 in ) towards the condensate drain on the service access face of the unit (Fig. 1). Use the unit frame as a leveling reference.
SLAB MOUNTING — Mount the unit on a concrete pad, cement blocks, bricks or creosoted wood of sufficient area and strength to support the unit weight (Table 2) without distortion or damage and maintain the drainage pitch recommended above.
A gravel apron will prevent grass and foliage
from obstructing the condenser air inlet (Fig. 1). FLAT OR RECESSED ROOF MOUNTING should
be as close as possible to the roof duct opening
Place the unit on at least 2 wooden 2x4 in. or
2x6 in. sleepers.
Sleepers may be perpendicular to or parallel to the unit mounting rails, but must span at least 2 roof joists or purlins to distribute unit weight. Set the sleepers in roof cement or mastic. Do not plug drain holes in the compressor or furnace compartment.
Do not support the unit by the ends of the base rails, nor use vibration isolators at these points. Unit will not be properly supported and could sag in the middle.
PITCHED ROOF MOUNTING -- Constmct a
sturdy welded or bolted frame of
1-1/2 X 1-1/2 X 1/4 in. or larger angle iron, with frame members at right angles to unit rails. Make provisions for securing unit to frame. Use roof cement or mastic where frame is in contact with roof.
%
r
Ductwork Installation — For air duct system design
information, refer to Carrier System Design Man ual, Part 2. System air flow must be within the range of temperature rise and external static pressure shown on the unit A.G.A. rating plate.
Bolt or screw ductwork to unit supply and return air duct flanges and seal joints with sheet metal flashing. Flange location and dimensions are given in Fig. 1 and Table 1. Use flexible connectors between ductwork and unit to dampen vibration. If a single split duct is connected to the unit, use a gasket to prevent air bypass between supply and return sides.
Insulate and weatherproof all external duct work. Secure ducts to building structure and
weatherproof all duct openings in wall or roof. Ducts passing thru unconditioned spaces must be insulated and provided with a vapor barrier.
Filter Installation (Field-Supplied)
1. Locate filter in return air system. Convenient location for filter is inside building behind
return air grille. Size and number of required filters is given in Table 2.
2. Attach filter manufacturer’s instructions to filter rack.
retaining clip on the unit top cover. Fasten the inlet box with sheet metal screws provided.
2. Place end of heat-shield collar (item 2) over top cover extrusion.
3. Slide flue pipe into heat-shield collar and secure wind cap assembly (item 1) with 3 sheet metal screws thru wire cage eyelets.
WIND CAP ASSEMBLY
FLUE PIPE
(PART OF WIND CAP
ASSEMSLY)
£Y£LETS(3)
■JXHEAT-SHIELC
^COLLAR
COMBUSTION
AIR INLET BOX
RETAINJNO
CLIP
TOP COVER OF UNIT
ASSEMBLE WIND CAP AND
COMBUSTION-AIR INLET BOX
Locate — The wind cap assembly, heat-shield collar
and combustion-air inlet box (items 1, 2 and 3 of Fig. 2) are shipped within the condenser section of all size 003 thru 005 units except 460 volt unit.
On 460 volt, size 003 thru 005 units, only the
combustion-air inlet box is shipped within the
condenser section. The heat-shield collar and wind cap assembly are shipped in a separate package.
On size 002 units of any voltage, the combustion-air inlet box is inside the unit behind the heating section access panel (Fig. 1). The
heat-shield collar and wind cap assembly are
shipped in a separate package.
Remove — On size 002 units, remove the heating
section access panel (Fig. 1) and obtain the combustion-air inlet box.
On size 003 thru 005 units, remove 6 sheet
metal screws and lift condenser fan, grille and
orifice from the top of the condenser section (Fig.
3). Remove and discard metal banding securing the wind cap and/or inlet box and remove the item(s) from the condenser section.
Before replacing the condenser fan, grille and orifice, remove any shipping tape from the con denser fan.
Assemble (Fig. 2)
1. Mount the combustion-air inlet box (item 3) by sliding the horizontal box flange under the
TOP COVER EXTRUSION
FLUE BOX EXTRUSION
HEATING SECTION
ACCESS PANEL
Fig. 2 — Wind Cap and Air Inlet Box Assembly
Fig. 3 — Removing Condenser Fan
and Orifice Assembly

PIPING AND WIRING

Gas Piping — Install piping per national and local
codes and ANSI Z223.1 entitled “Installation of Gas Appliances and Gas Piping,” (published by American Gas Association, 1515 Wilson Blvd., Arlington (Rosslyn), Va. 22209).
1. Furnish the gas line from the main gas supply to the unit gas valve (Fig. 4).
2. Size the supply pipe for 0.3-in. wg maximum pressure drop and for the volume of gas
required (Tables 3, 5 and 6). Pipe size must equal or exceed size of gas connection at unit.
3. Use pipe dope approved for use with liquefied
petroleum (LP) gases.
4. Pitch all horizontal pipe runs towards the unit
1/4 in. per 15 ft to prevent trapping condensed
moisture.
5. Support piping to maintain proper pitch, prevent strain on unit controls, and prevent accidental movement of piping.
6. Install a tee for attachment of a dirt and moisture drip pocket (Fig. 4). Tee should be at same level or below gas valve connection. Drip
pocket must be protected against freeze-up.
7. Install manual shutoff valve on gas piping per local codes.
8. Provide a ground joint union in the gas supply line near the unit gas valve.
9. Protect gas piping from freezing temperatures.
Gas stoppage can result from failure to insulate
pipe against wide or sudden temperature
changes.
10. When piping is completed, check entire gas assembly and field piping with soap and water solution.
Never use an open ñame for leak testing.
Fig. 4 — Gas Piping Details
Table 3 — Maximum Pipe Cap. (cfh)^
PIPE
LENGTH (ft)
10 20 92 30 73 152
40 63 130 245 50 60 70 80 90
100
*Cfh — Cu ft/hr based on 0.3 in. wg pressure drop and 0.6 gas
specific gravity.
NOTE; Correction is not necessary for normal number of fittings nor for 0.7 gas specific gravity unless specified.
NOMINAL PIPE SIZE
V.
132
56 115
_ —
-
V
/4
278 190
105
96 90 84 160 79
1
520 350
285 215
195 180 170
150
1V4
1050
730 590 500 440 400 370 350 320 305
Table 4 — Electrical Data (60-Hz)
UNIT
Model Serie
48DL,DH
002
200
300
400
200
48DL
003
300 400
500
^00
48DL,DH,
DM004
48DL
045
300 400 500 600
200
300 400 500
600^
200
48DL,DH
005
FLA — Full Load Amps
FU — Dual Element Fuse or Circuit Breaker having high inrush
capability (max allowable amps)
ICF — Max Instantaneous Current Flow during start-up is the sum
of compressor LRA plus the FLA of all other motors in the unit.
300 400 500 600
VOLTAGE Norn V/Ph
230/1 208/3
208/1 230/1 208/3 230/3
___ 460A3__
'^208/l~
230/1 208/3 230/3 460/3
208/1 230/1 208/3 230/3 460/3
'208/1^
230/1 208/3 230/3 460/3
WSA FLA ICF FU
23 5 19 5 21 6 16 8
29 8
27 3
18.8 15 5 17 4
8.8
39 0 35 9
25 0
23 3
11.3 41 0
36 5
27.4 24 5 12 4
46 5 41 5 29 5
25 2
13 3
17 9 14 0
24 3
22.3 14 4
32 4 117 9 29 9 105 9 21 2 19 8 75 9
34 1 30 5
23 2 20 9
38 5 132.6 60 31 9 126 0 3 8 2.8 34 5
24.9
21.5
11.3
UNIT
102.8
7 4 31 9
10.0 115 6 60
100 6 50 23 9 94 0
10 6
112 6
IFM LRA OFM
WSA
COMPR OFM
FLA LRA
83 4 75 4 30 58 4
91 8 73 8
63.8
85 9 30
39.0 15
85.6 35 16 6 79 0 73 6 30 14 3 67 0 3 8 2.8 38 3 15 7 3 35 0 3 8 2 8
93.6 40 18 3 76 6
38 3 20 8 0
35 20
40 20.8
35
25 25 15
50 26 5 45
20
50 27 9 106 0 35
Indoor (Evaporator) Fan Motor Locked Rotor Amps Outdoor (Condenser) Fan Motor
Wire Sizing Amps per NEC equals 1.25 x FLA of the largest
motor plus the sum of all other motors in the unit.
16 1 80 0
14 5 10 6 55 0
18.8 12 0 70 0 10 9
5 5 30 0
24 0 15 3 80 0 13 9 70 0
7 0 35 0
27 5
14 9 70 0
72 0
99 0
88.0
60.0
112,0 100 0
109 0
87 0
35 0
FLA
2 0 1 4 2 0 2 0
2 4 2 4 2 4 2 4
2.4 1 4 3 1 1
3 1 3 1 2 8
3.1 3 1 2.8
3 8 2.8 3 8
3 8 2 8
3 8 2.8 3 8 2 8 3 8 3 8 2.8
1 4
1.4
1 4 1 4 1 4
1.4
2.8
2.8 2 8
2 8
2 8
Loading...
+ 9 hidden pages