The 48DH, DL and DM combination heating/
cooling units are complete systems designed for
outdoor installation on slab or rooftop.
Installation consists of: rigging and mounting
the unit; attaching ductwork; making single gas,
electrical and condensate connections; and attach
ing thermostat leads. A field-furnished filter rack is
required in the return air stream.
RECEIVING THE UNIT
Examine the unit carefully for any damage
incurred in shipment. If found, file claim with
transportation company immediately.
Check unit nameplate to ensure that unit
electrical requirements match available power
supply, and that unit is designed for use with the
proper gas type (natural or liquefied petroleum).
Leave unit on shipping skids until ready for
mounting.
INSTALLATION
Check national and local gas and electrical
codes and local building codes for any special
installation requirements.
Unit Location — Install unit outdoors and as close
to building duct openings as possible. Unit may
face in any direction since neither the condenser
air inlet nor the flue outlet (Fig. 1) are affected by
wind. Do not locate unit near sources of con
taminated air.
Although the unit is weatherproof, position
unit so that water and ice from roofs or eaves
cannot fall directly on the unit.
SPACE LIMITATIONS - Provide sufficient space
for unimpeded air flow and for wiring and servicing
unit (Fig. 1).
, CONO UNIT
2-0 OVERHEAD SPACE SECTION
REQ FOR SERVICE AND ACCESS PANEL
AIR FLOW ;
002
'only.
SERVICE ^
OPENINGS ^0'
ACCESS SIDE
*This dimension is not applicable to 002 units because there are no
mounting rails
ta-'iiEiEJ ance space of 1 in. on duct connection side, and 12 in on
BOTH side:
FLUE OUTLET
—,—X::...
Space required for service Design certified by A G.A. for installation on combustible type floor with a minimum ciear-
remaining sides
Indoor (Evaporator) Air
O'
____WIND CAP ASSEMBLY (CONDENSER AIR OUTLET
îLÎÎÎ 002 UNIT ONLY)
• DIAM*
(SmTG HOLES)
COMBUSTION AIR
.JSSiiSOc 045 8005
n DIAM HOLE
® FOR LINE
POWER WIRING
HEATING
SECTION
i ACCESS PANEL
) Condenser Air
Fig. 1 — Physical Data
Table 1 — Base Unit Dimensions (ft-in.)
UNIT
A3-10
В
C
D
E
F
G
H0-11У0-11У
J
*Refer to Table 2 for differences of these series
48DL48 DH48DL48DL48 DM
002*003
——
0-10V3
0-11 Уз
1- 0
2- 2У
——
0- 40- 4
3-10
0-1 оу0-юу0-1 оу
0-11 у
1- 01- 01- 0
2- 2%
4- 74- 7
4- 7%4- 7%
1- 2
2- 2У
2- 2У
0-11У0-11У
0- 4
1- 8
2- 2У
2- 2У
0- 4
48 DH48DL
004
3_2
5-2У5- 2%5- 2%
1-ЗУ
1-81- 8
1-0
2-2У
2-4У2- 2Ув2- 4У
1-4У
0-7У
5- 25- 2
1- 5У
1- 0
2- 2У
1- 4У1- 4У
0-11
Q45
1- ЗУ
1-111-11
1- 0
2- 2%
0- 7У
48DL
5- 2
5- 2У
1- ЗУ
1- 0
2- 2%2- 2У
2- 4У
1- 4У
0- 7У
48DH
005
5- 7\
5- 8У
1 9
1-11
1- оу
2- 4У
1- 4У
1- 2У
Form 48DH-6
Table 2 — Physical Data
UNIT
OPERATING WT (lb)
REFRIG (22) CHG (Ib-oz)
COMPRESSOR
Cyl inders2
Rpm (60-Hz)
CONDENSER FAN
Air Quantity (Cfm)
Motor Hp
EVAPORATOR FAN
CAPACITY (1000 Btuh)
Cool in g
Input Heotlng/Bonnet*
MAX EXTERNAL
STATIC PRESSURE
Heating (in. W.C.)
FILTERSt (1-in. thick)
Disposable — No. ..1 15x201 15x20
Size (in.)1 .20x251 20x252 15x201 20x20
Permanenti — No. ..
Size (in.)
HEAT TEMP RISE (F)
* Ratings shown for elevations up to 2000 ft above sea level. For ele
vations above 2000 ft deduct 4% capacity for each 1000 ft above
sea level
48DL002
331
3.2
M27 (1-ph)M27 (1-ph)
AHbbz^/h(J-ph)AH5527h(3-ph)
17001700
Vs
24243036
56/42
1 15x201 15x201 20x20
35-6545-75
48DH00248DL003
343385
3 23.65 1
222
Propel ler-Type — Direct Drive; Vertical Disc
VsVs
Centrifugal —
80/60
80/60
48DL004
M34M40
20002500
Direct Drive; Horizontal Discharge
80/60
1 20x201 20x201 .20x20
35-6535-65
i Recommended field-supplied filter
ifBased on 0.082 in. wg pressure drop or less thru filter at 520 ft/min
48 DM004
411
3500
Vs
110/82 5125/93 75
40
1 20x201 .20x202 20x20
face velocity.
48DH004
430
5 1
M40
2
250025002700
Vs
36
35-6545-75
438
M40P46
22
Vs
36
1 15x20
48DL04548DL00548DH005
450476
5 25 15 1
large
Vs
Г
4248
100/75
1 20x25
35-65
P53
2
2700
V,
110/82 5
1 20x25
1 25x25
2 15x20
35 65
512
P53
2
2700
Vs
48
150/112 5
1 20x25
1 .25x25
2 15x20
45-75
OUTSIDE AIR LIMITATIONS - Although there
are no restrictions on either the percentage or the
temperature of the outside air circulated thru the
unit, the rate of moisture condensation from the
combustion process increases significantly when
return air temperature drops below 50 F. Protect
the drain holes in the bottom pan against ice
buildup if outside air of below freezing tempera
ture is used
VIBRATION ISOLATION -- The unit compressor,
evaporator fan and condenser fan are mounted on
isolators to minimize vibration. Additional isola
tion is not required for slab mounting. With some
types of roof construction, however, the use of
field-furnished mbber pad type isolators may be
advisable.
Unit Rigging
1. Sling the unit perpendicularly to shipping skid
mnners. Use spreader bars to prevent damage
from sling or cable.
2. Raise unit to desired location and remove
shipping skid.
3. Mount and level the unit as indicated in Unit
Support and Mounting section.
Unit Support and Mounting
LEVELING THE UNIT — Level the unit from end
to end but pitch the unit slightly (3/8 to 1/2 in )
towards the condensate drain on the service access
face of the unit (Fig. 1). Use the unit frame as a
leveling reference.
SLAB MOUNTING — Mount the unit on a
concrete pad, cement blocks, bricks or creosoted
wood of sufficient area and strength to support the
unit weight (Table 2) without distortion or damage
and maintain the drainage pitch recommended
above.
A gravel apron will prevent grass and foliage
from obstructing the condenser air inlet (Fig. 1).
FLAT OR RECESSED ROOF MOUNTING should
be as close as possible to the roof duct opening
Place the unit on at least 2 wooden 2x4 in. or
2x6 in. sleepers.
Sleepers may be perpendicular to or parallel to
the unit mounting rails, but must span at least 2
roof joists or purlins to distribute unit weight. Set
the sleepers in roof cement or mastic. Do not plug
drain holes in the compressor or furnace
compartment.
Do not support the unit by the ends of the base
rails, nor use vibration isolators at these points.
Unit will not be properly supported and could sag
in the middle.
PITCHED ROOF MOUNTING -- Constmct a
sturdy welded or bolted frame of
1-1/2 X 1-1/2 X 1/4 in. or larger angle iron, with
frame members at right angles to unit rails. Make
provisions for securing unit to frame. Use roof
cement or mastic where frame is in contact with
roof.
%
r
Ductwork Installation — For air duct system design
information, refer to Carrier System Design Man
ual, Part 2. System air flow must be within the
range of temperature rise and external static
pressure shown on the unit A.G.A. rating plate.
Bolt or screw ductwork to unit supply and
return air duct flanges and seal joints with sheet
metal flashing. Flange location and dimensions are
given in Fig. 1 and Table 1. Use flexible connectors
between ductwork and unit to dampen vibration.
If a single split duct is connected to the unit, use a
gasket to prevent air bypass between supply and
return sides.
Insulate and weatherproof all external duct
work. Secure ducts to building structure and
weatherproof all duct openings in wall or roof.
Ducts passing thru unconditioned spaces must be
insulated and provided with a vapor barrier.
Filter Installation (Field-Supplied)
1. Locate filter in return air system. Convenient
location for filter is inside building behind
return air grille. Size and number of required
filters is given in Table 2.
2. Attach filter manufacturer’s instructions to
filter rack.
retaining clip on the unit top cover. Fasten the
inlet box with sheet metal screws provided.
2. Place end of heat-shield collar (item 2) over top
cover extrusion.
3. Slide flue pipe into heat-shield collar and secure
wind cap assembly (item 1) with 3 sheet metal
screws thru wire cage eyelets.
WIND CAP
ASSEMBLY
FLUE PIPE
(PART OF WIND CAP
ASSEMSLY)
£Y£LETS(3)
■JXHEAT-SHIELC
^COLLAR
COMBUSTION
AIR INLET BOX
RETAINJNO
CLIP
TOP COVER
OF UNIT
ASSEMBLE WIND CAP AND
COMBUSTION-AIR INLET BOX
Locate — The wind cap assembly, heat-shield collar
and combustion-air inlet box (items 1, 2 and 3 of
Fig. 2) are shipped within the condenser section of
all size 003 thru 005 units except 460 volt unit.
On 460 volt, size 003 thru 005 units, only the
combustion-air inlet box is shipped within the
condenser section. The heat-shield collar and wind
cap assembly are shipped in a separate package.
On size 002 units of any voltage, the
combustion-air inlet box is inside the unit behind
the heating section access panel (Fig. 1). The
heat-shield collar and wind cap assembly are
shipped in a separate package.
Remove — On size 002 units, remove the heating
section access panel (Fig. 1) and obtain the
combustion-air inlet box.
On size 003 thru 005 units, remove 6 sheet
metal screws and lift condenser fan, grille and
orifice from the top of the condenser section (Fig.
3). Remove and discard metal banding securing the
wind cap and/or inlet box and remove the item(s)
from the condenser section.
Before replacing the condenser fan, grille and
orifice, remove any shipping tape from the con
denser fan.
Assemble (Fig. 2)
1. Mount the combustion-air inlet box (item 3) by
sliding the horizontal box flange under the
TOP COVER
EXTRUSION
FLUE BOX
EXTRUSION
HEATING SECTION
ACCESS PANEL
Fig. 2 — Wind Cap and Air Inlet Box Assembly
Fig. 3 — Removing Condenser Fan
and Orifice Assembly
PIPING AND WIRING
Gas Piping — Install piping per national and local
codes and ANSI Z223.1 entitled “Installation of
Gas Appliances and Gas Piping,” (published by
American Gas Association, 1515 Wilson Blvd.,
Arlington (Rosslyn), Va. 22209).
1. Furnish the gas line from the main gas supply
to the unit gas valve (Fig. 4).
2. Size the supply pipe for 0.3-in. wg maximum
pressure drop and for the volume of gas
required (Tables 3, 5 and 6). Pipe size must
equal or exceed size of gas connection at unit.
3. Use pipe dope approved for use with liquefied
petroleum (LP) gases.
4. Pitch all horizontal pipe runs towards the unit
1/4 in. per 15 ft to prevent trapping condensed
moisture.
5. Support piping to maintain proper pitch,
prevent strain on unit controls, and prevent
accidental movement of piping.
6. Install a tee for attachment of a dirt and
moisture drip pocket (Fig. 4). Tee should be at
same level or below gas valve connection. Drip
pocket must be protected against freeze-up.
7. Install manual shutoff valve on gas piping per
local codes.
8. Provide a ground joint union in the gas supply
line near the unit gas valve.
9. Protect gas piping from freezing temperatures.
Gas stoppage can result from failure to insulate
pipe against wide or sudden temperature
changes.
10. When piping is completed, check entire gas
assembly and field piping with soap and water
solution.
Never use an open ñame for leak testing.
Fig. 4 — Gas Piping Details
Table 3 — Maximum Pipe Cap. (cfh)^
PIPE
LENGTH (ft)
10
2092
3073152
4063130245
50
60
70
80
90
100
*Cfh — Cu ft/hr based on 0.3 in. wg pressure drop and 0.6 gas
specific gravity.
NOTE;
Correction is not necessary for normal number of fittings nor
for 0.7 gas specific gravity unless specified.
NOMINAL PIPE SIZE
V.
132
56115
—
_
—
-
V
/4
278
190
105
96
90
84160
79
1
520
350
285
215
195
180
170
150
1V4
1050
730
590
500
440
400
370
350
320
305
Table 4 — Electrical Data (60-Hz)
UNIT
Model Serie
48DL,DH
002
200
300
400
200
48DL
003
300
400
500
^00
48DL,DH,
DM004
48DL
045
300
400
500
600
200
300
400
500
600^
200
48DL,DH
005
FLA — Full Load Amps
FU — Dual Element Fuse or Circuit Breaker having high inrush
capability (max allowable amps)
ICF — Max Instantaneous Current Flow during start-up is the sum
of compressor LRA plus the FLA of all other motors in
the unit.