Carrier 48AJ User Manual

Page 1
48AJ,AK,AW,AY020-060
Single Package Rooftop Units
Electric Cooling/Gas Heating
with Scroll Compressor and
COMFORTLINK™ Controls
Installation Instructions
WEATHERMAKER
®
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36
Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1
• ALTERNATE UNIT SUPPORT
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2
• POSITIONING
• ROOF MOUNT
Step 3 — Field Fabricate Ductwork . . . . . . . . . . . . . . . 2
Step 4 — Make Unit Duct Connections . . . . . . . . . . . 2
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . 19
Step 6 — Trap Condensate Drain. . . . . . . . . . . . . . . . 19
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . 19
Step 8 — Make Electrical Connections . . . . . . . . . . 20
•POWER WIRING
• FIELD POWER SUPPLY
• FIELD CONTROL WIRING
Step 9 — Make Outdoor-Air Inlet
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
• ECONOMIZER AND FIXED OUTDOOR AIR DAMPER
Step 10 — Position Power Exhaust/Barometric
Relief Damper Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Step 11 — Route VAV Static Pressure Sensor . . . 34
Step 12 — Install All Accessories . . . . . . . . . . . . . . . 35
Step 13 — Field Modifications. . . . . . . . . . . . . . . . . . . 35
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical compo­nents. Only trained and qualified service personnel should in­stall, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­sonnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
WARNING
WARNING
1. Improper installation, adjustment, alteration, service, or maintenance can cause property damage, personal injury, or loss of life. Refer to the User’s Information Manual provided with this unit for more details.
2. Do not store or use gasoline or other flammable va­pors and liquids in the vicinity of this or any other appliance.
What to do if you smell gas:
1. DO NOT try to light any appliance.
2. DO NOT touch any electrical switch, or use any phone in your building.
3. IMMEDIATELY call your gas supplier from a neigh­bor’s phone. Follow the gas supplier’s instructions.
4. If you cannot reach your gas supplier, call the fire department.
WARNING
Disconnect gas piping from unit when pressure testing at pressure greater than 0.5 psig. Pressures greater than
0.5 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than
0.5 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 0.5 psig or less, a unit connected to such piping must be isolated by closing the manual gas valve(s).
INSTALLATION
Step 1 — Provide Unit Support
CAUTION
1. All panels must be in place when rigging or damage to unit may occur.
2. Unit is not designed for handling by fork truck.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480067-01 Printed in U.S.A. Form 48A-7SI Pg 1 8-09 Replaces: 48A-5SI
Page 2
ROOF CURB — For vertical discharge units, assemble or in­stall accessory roof curb in accordance with instructions shipped with this accessory. See Fig. 1-3. Install insulation, cant strips, roofing, and counter flashing as shown. Ductwork can be installed to roof curb before unit is set in place. Curb should be level. This is necessary to permit unit drain to func­tion properly. Unit leveling tolerance is shown in Fig. 1-3. Refer to Accessory Roof Curb Installation Instructions for additional information as required. When accessory roof curb is used, unit may be installed on class A, B, or C roof covering material.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket with the roof curb as shown in Fig. 1-3. Improperly applied gasket can also result in air leaks and poor unit performance.
ALTERNATE UNIT SUPPORT — When the preferred curb or slab mount cannot be used, support unit with sleepers on pe­rimeter, using unit curb support area. If sleepers cannot be used, support long sides of unit (refer to Fig. 4-10) with a mini­mum number of 4-in. x 4-in. pads spaced as follows: 48AJ,AK,AW,AY020-035 units require 3 pads on each side; 48AJ,AK,AW,AY036-050 units require 4 pads on each side; 48AJ,AK,AW,AY051 and 060 units require 6 pads on each side. Unit may sag if supported by corners only.
Step 2 — Rig and Place Unit — Inspect unit for
transportation damage. See Tables 1-6 for physical data and specifications. File any claim with transportation agency.
Do not drop unit; keep upright. Use spreader bars over unit to prevent sling or cable damage. This unit must be handled with a crane and can not be handled by a fork truck. Level by using unit frame as a reference; leveling tolerance is shown in Fig. 1-3. See Fig. 10 for additional information. Unit operating weight is shown in Table 2.
NOTE: On retrofit jobs, ductwork may be attached to the old unit instead of a roof curb. Be careful not to damage ductwork when removing old unit. Attach existing ductwork to roof curb instead of unit.
Four lifting lugs are provided on the unit base rails as shown in Fig. 4-10. Refer to rigging instructions on unit.
POSITIONING — Maintain clearance, per Fig. 4-10, around and above unit to provide minimum distance from combustible materials, proper airflow, and service access.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air. For proper unit operation, adequate combustion and venti­lation air must be provided in accordance with Section 5.3 (Air for Combustion and Ventilation) of the National Fuel Gas Code, ANSI Z223.1 (American National Standards Institute).
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 4 ft from any opening through which combustion products could enter the building, and at least 4 ft from any adjacent building. When unit is located adjacent to public walkways, flue assem­bly must be at least 7 ft above grade.
ROOF MOUNT — Check building codes for weight distribu­tion requirements. See Fig. 11. Unit operating weight is shown in Table 2.
Step 3 — Field Fabricate Ductwork — Secure all
ducts to building structure. Use flexible duct connectors be­tween unit and ducts as required. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
NOTE: Due to width of the horizontal supply and return duct­work, provisions should be made for servicing of the outdoor air filters (i.e., catwalk over ductwork).
Ducts passing through an unconditioned space must be in­sulated and covered with a vapor barrier. Outlet grilles must not lie directly below unit discharge. The return duct must have a 90-degree elbow before opening into the building space if the unit is equipped with power exhaust.
To attach ductwork to roof curb, insert duct approximately 10 to 11 in. up into roof curb. Connect ductwork to 14-gage roof curb material with sheet metal screws driven from inside the duct.
Follow AMCA (Air Movement and Control Association) guidelines relating to ductwork connections to the unit. These guidelines recommend a minimum 2 ters of straight duct connected to supply air inlet and outlet openings before any transitions, fittings, dampers, etc. Failure to adhere to these guidelines may result in system effects which can impact the unit’s ability to achieve published performance.
1
/2 equivalent duct diame-
WARNING
For vertical supply and return units, tools or parts could drop into ductwork and cause an injury. Install a 90-degree elbow turn in the supply and return ductwork between the unit and the conditioned space. If a 90-degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space.
Step 4 — Make Unit Duct Connections
48AJ AND AK UNITS — Unit is shipped for thru-the­bottom duct connections. Field-fabricated ductwork should be attached to the roof curb. Supply and return duct dimensions are shown in Fig. 4-6. Air distribution is shown in Fig. 12. Refer to installation instructions shipped with roof curb for more information.
48AW AND AY UNITS — Remove shipping covers from supply and return air openings. Attach field-supplied ductwork to unit. Connect to the unit with a single duct for all supply openings and with a single duct for all return openings. Splitting of the airflow into branch ducts should not be done at the unit. Sufficient duct length should be used prior to branch­ing to ensure the air temperatures are well mixed within the ductwork. See Fig. 7-9 for duct opening dimensions. Secure all ducts to building structure. Air distribution is shown in Fig. 7-9 and Fig. 13.
Install accessory barometric relief or power exhaust in the field-fabricated return ductwork. Refer to Step 10 — Position Power Exhaust/Barometric Relief Damper Hood section on page 33 for more information.
Instructions continued on page 19.
2
Page 3
NOTES:
Fig. 1 — Roof Curb — 48AJ,AK020-035 Units
DUCT PRIOR TO ANY SUPPLY TAKE OFFS OR BRANCHES.
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO OUTSIDE OF PART.
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DISASSEMBLED.
3. ALL ROOF CURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. UNITS WITH ELECTRIC HEAT MUST BE INSTALLED WITH A 90° ELBOW ON THE SUPPLY
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMENSIONS ARE IN INCHES.
a48-6715
3
Page 4
NOTES:
Fig. 2 — Roof Curb — 48AJ,AK036-050 Units
DUCT PRIOR TO ANY SUPPLY TAKE OFFS OR BRANCHES.
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO OUTSIDE OF PART.
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DISASSEMBLED.
3. ALL ROOF CURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. UNITS WITH ELECTRIC HEAT MUST BE INSTALLED WITH A 90° ELBOW ON THE SUPPLY
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMENSIONS ARE IN INCHES.
a48-6716
4
Page 5
NOTES:
Fig. 3 — Roof Curb — 48AJ,AK051 and 060 Units
OUTSIDE OF PART.
ASSEMBLED.
SIONS ARE IN INCHES.
1. UNLESS OTHERWISE SPECIFIED, ALL DIMENSIONS ARE TO
2. ROOF CURB ACCESSORY CRRFCURB005A00 IS SHIPPED DIS-
3. ALL ROOFCURB PARTS ARE TO BE 14 GA. GALVANIZED STEEL.
4. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
a48-6717
5
Page 6
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 4 — Base Unit Dimensions — 48AJ,AK020-035
1. WEIGHTS INCLUDE ECONOMIZER (STD).
NOTES:
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR
REMOVAL OF EVAPORATOR COIL)
CLEARANCES, CONTACT CARRIER APPLICA-
TION ENGINEERING DEPARTMENT.
TACHED TO ACCESSORY ROOF CURB. IF UNIT
IS MOUNTED ON DUNNAGE, IT IS RECOM-
MENDED THAT THE DUCTS BE SUPPORTED
BY CROSS BRACES AS DONE ON ACCESSO-
RY ROOF CURB.
OTHER DIMENSIONS ARE IN INCHES.
4. FOR SMALLER SERVICE AND OPERATIONAL
5. BOTTOM DUCTS ARE DESIGNED TO BE AT-
6. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL
a48-8235
6
Page 7
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 5 — Base Unit Dimensions — 48AJ,AK036-050
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
OTES:
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR
REMOVAL OF EVAPORATOR COIL)
CLEARANCES, CONTACT CARRIER APPLICA-
TION ENGINEERING DEPARTMENT.
TACHED TO ACCESSORY ROOF CURB. IF UNIT
IS MOUNTED ON DUNNAGE, IT IS RECOM-
MENDED THAT THE DUCTS BE SUPPORTED BY
CROSS BRACES AS DONE ON ACCESSORY
ROOF CURB.
OTHER DIMENSIONS ARE IN INCHES.
4. FOR SMALLER SERVICE AND OPERATIONAL
5. BOTTOM DUCTS ARE DESIGNED TO BE AT-
6. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL
a48-8236
7
Page 8
Fig. 6 — Base Unit Dimensions — 48AJ,AK051 and 060
8
Page 9
NOTES:
Fig. 7 — Base Unit Dimensions — 48AW,AY020-035
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR REMOVAL OF
EVAPORATOR COIL)
CONTACT CARRIER APPLICATION ENGINEERING
DEPARTMENT.
SIONS ARE IN INCHES.
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES,
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
A48-8380
9
Page 10
* OPERATING WEIGHT INCLUDES LARGEST INDOOR FAN MOTOR, CU/AL COILS,
MODULATING POWER EXHAUST (VARIABLE AIR VOLUME), AND VARIABLE
FREQUENCY DRIVE (VARIABLE AIR VOLUME).
Fig. 8 — Base Unit Dimensions — 48AW,AY036-050
TOP OF UNITS: NO OVERHANG
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
1. WEIGHTS INCLUDE ECONOMIZER (STD).
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
NOTES:
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 10’ - 0” [3048] (FOR REMOVAL
OF EVAPORATOR COIL)
ANCES, CONTACT CARRIER APPLICATION ENGINEER-
ING DEPARTMENT.
MENSIONS ARE IN INCHES.
4. FOR SMALLER SERVICE AND OPERATIONAL CLEAR-
5. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DI-
a48-8239
10
Page 11
Fig. 9 — Base Unit Dimensions — 48AW,AY051 and 060
FOR CENTERS OF
GRAVITY, OPERATING
AND CORNER WEIGHTS,
SEE FIGURE 10
a48-8240
11
Page 12
48AJ/AK051 LOW HEAT
48AJ/AK060 LOW HEAT
48AJ/AK051 HIGH HEAT
48AW/AY051 HIGH HEAT
48AW/AY051 LOW HEAT
48AW/AY060 LOW HEAT
LEGEND
48AJ/AK060 HIGH HEAT
48AW/AY060 HIGH HEAT
CV Constant Volume
FIOP — Factory-Installed Option
IFM — Indoor Fan Motor
VAV — Volume Air volume
VFD — Variable Frequency Drive
NOTES:
DAMP ER.
1. WEIGHTS INCLUDE ECONOMIZER OR OUTDOOR AIR
TOP OF UNITS: NO OVERHANG
2. CENTER OF GRAVITY.
3. UNIT CLEARANCES:
48AJ/AK LOW HEAT
48AJ/AK HIGH HEAT
48AW/AY LOW HEAT
48AJ/AK LOW HEAT
48AJ/AK HIGH HEAT
48AW/AY HIGH HEAT
48AW/AY LOW HEAT
48AW/AY HIGH HEAT
Fig. 10 — Center of Gravity and Weights — 48AJ,AK,AW,AY051,060
CONDENSER COIL: 4’ - 0“ [1219]
ECONOMIZER SIDE: 6’ - 0” [1829]
HEAT SIDE: 4’’ - 0” [1219]
FILTER ACCESS SIDE: 15’ - 0” [4572] (FOR REMOVAL
OF EVAPORATOR COIL)
CONTACT CARRIER APPLICATION ENGINEERING DEPART-
MENT.
CESSORY ROOF CURB. IF UNIT IS MOUNTED ON DUNNAGE,
IT IS RECOMMENDED THAT THE DUCTS BE SUPPORTED BY
CROSS BRACES AS DONE ON ACCESSORY ROOF CURB.
FILTERS (INDOOR FAN MOTOR IS NOT INCLUDED). ADD IN-
DOOR FAN MOTOR, FIOPS, AND ACCESSORIES FOR TOTAL
OPERATING WEIGHT.
TRANSDUCER, AND ASSOCIATED WIRING.
SIONS ARE IN INCHES.
TURN AND SUPPLY DUCTWORK CONNECTION IS RECOM-
MENDED FOR COVERING ALL THREE RETURN AND ALL
THREE SUPPLY OPENINGS. THE ENTIRE AREA AROUND
THE DUCT OPENINGS IS AVAILABLE FOR A 1.5” DUCT
FLANGE ATTACHMENT.
4. FOR SMALLER SERVICE AND OPERATIONAL CLEARANCES,
5. BOTTOM DUCTS ARE DESIGNED TO BE ATTACHED TO AC-
6. BASE UNIT WEIGHTS INCLUDE OUTDOOR AIR HOODS AND
7. VAV MOTOR WEIGHTS INCLUDE INDOOR MOTOR, VFD, VFD
8. DIMENSIONS IN [ ] ARE IN MILLIMETERS. ALL OTHER DIMEN-
9. FOR SIDE-SUPPLY/RETURN APPLICATIONS, A SINGLE RE-
a50-8102
12
Page 13
Table 1 — Physical Data — 48AJ,AK,AW,AY Units
UNIT 48AJ,AK,AW,AY 020 025 027 030
NOMINAL CAPACITY (tons) 20 25 27 30
BASE UNIT See Operating Weights Table OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2) 2…SR*782AT/1…SR*782AE
Number of Refrigerant Circuits 22 22 Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged Precharged
REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 26-8 33-8 35-8 29-0 Circuit 2 14-0 17-8 20-0 30-8
CONDENSER COIL* Internally Enhanced, Quantity 11 11 Rows ... Fins/in. 2 ... 15 3 ... 15 3 ... 15 4 ... 15 Total Face Area (sq ft) 33.3 33.3 33.3 33.3
CONDENSER FAN Propeller Type Nominal Cfm 17,200 15,850 15,850 14,500 Quantity... Diameter (in.) 2 ... 30 2 ... 30 2 ... 30 2 ... 30 Motor Hp 11 11
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits Tube Size (in.) Rows ... Fins/in. 3 ... 15 3 ... 15 4 ... 15 4 ... 15 Total Face Area (sq ft) 31.7 31.7 31.7 31.7
EVAPORATOR FAN Centrifugal Type Quantity ... Size (in.) 2 ... 20 X 15 2 ... 20 X 15 2 ... 20 X 15 2 ... 20 X 15 Type Drive Belt Belt Belt Belt Nominal Cfm 8,000 10,000 11,000 12,000 Motor Hp 5 10 15 5 10 15 10 15 20 10 15 20 Motor Frame Size 184T 215T 254T 184T 215T 254T 215T 254T 256T 215T 254T 256T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1200 1200 1200 1200 Motor Pulley Pitch Diameter (in.) 4.8 4.4 5.7 4.8 6.1 5.5 4.4 4.9 5.9 4.4 5.7 5.9 Nominal Motor Shaft Diameter (in.) 11/ Fan Pulley Pitch Diameter (in.) 12.4 8.6 9.1 12.4 11.1 8.7 9.4 8.1 8.7 9.5 9.1 8.7 Nominal Fan Shaft Diameter (in.) 115/ Belt Quantity 112 1 1 2 2 222 22 Belt Type BX56 BX50 5VX530 BX56 5VX570 5VX530 BX50 5VX530 5VX530 BX50 5VX530 5VX530 Belt Length (in.) 56 63 53 56 57 53 50 50 53 50 53 53 Pulley Center Line Distance (in.) 16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4 15.6-18.4 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9 Factory Speed Setting (rpm) 677 895 1096 677 962 1106 819 1096 1187 884 1096 1187
FURNACE SECTION Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max. Rollout Switch Cutout Temp (F)† 225 225 225 225
Burner Orifice Diameter (in. ...drill size)
Natural Gas Std .111 ... 34 .111 ... 34 .111 ... 34 .111 ... 34 Liquid Propane Alt .089 ... 43 .089 ... 43 .089 ... 43 .089 ... 43 Thermostat Heat Anticipator Setting Stage 1 (amps) 0.24 0.24 0.24 0.24 Stage 2 (amps) 0.13 0.13 0.13 0.13 Gas Input (Btuh) Stage 1 (Low Heat/High Heat) Stage 2 (Low Heat/High Heat) Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 15-45/35-65 15-45/35-65 15-45/35-65 15-45/35-65 Manifold Pressure (in. wg) Natural Gas Std 3.5 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 22 22
HIGH-PRESSURE SWITCH (psig) Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
MIXED-AIR FILTERS Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2 10 ... 20 x 24 x 2 Pleated 5 ... 20 x 20 x 4
3
/
8
13/
8
15/
8
16
8
262,500/394,000 262,500/394,000 262,500/394,000 262,500/394,000
350,000/525,000 350,000/525,000 350,000/525,000 350,000/525,000
5 ... 20 x 24 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST
Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11 x 10
Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan
LEGEND *Sizes 020-040: Circuit 1 uses the lower por tion of condenser coil, Circuit 2 uses the upper
Al — Aluminum Cu — Copper
1…SR*812AT, 1…SR*942AT/
1…SR*942AE
3
/8″ Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins
3
/
8
11/
8
13/
8
115/
16
5 ... 20 x 20 x 4 5 ... 20 x 24 x 4
15/
8...16 x 25 x 2
4...20 x 25 x 2
2 ... SR*942AT/1…SR*942AE 2…SR*782AT/2…SR*812AT
3
/
8
13/
8
8
115/
5 ... 20 x 20 x 4 5 ... 20 x 24 x 4
15/
15/
8
16
8
Housing
portion. Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Rollout switch is manual reset.
13/
8
3
/
8
15/
8
115/
16
5 ... 20 x 20 x 4 5 ... 20 x 24 x 4
15/
8
13
Page 14
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)
UNIT 48AJ,AK,AW,AY 035 036 040 041
NOMINAL CAPACITY (tons) 35 35 40
BASE UNIT See Operating Weights Table OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2)
Number of Refrigerant Circuits 2222 Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged Precharged
REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 33-0 36-0 36-0 47-0 Circuit 2 38-0 58-0 47-0 47-0
CONDENSER COIL* Internally Enhanced, 3/8″ Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins Quantity 1222 Rows ... Fins/in. 4 ... 15 2...15/4…15 2 ... 15 / 4 … 15 4...15/4…15 Total Face Area (sq ft) 33.3 66.7 66.7 66.7
CONDENSER FAN Propeller Type Nominal Cfm 14,500 30,000 30,000 30,000 Quantity... Diameter (in.) 2 ... 30 4...30 4 ... 30 4...30 Motor Hp 1111
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits Tube Size (in.) Rows ... Fins/in. 6 ... 16 4...17 4 ... 16 4...17 Total Face Area (sq ft) 31.3 31.3 31.3 31.3
EVAPORATOR FAN Centrifugal Type Quantity ... Size (in.) 2 ... 20 X 15 2...20 X 15 2 ... 20 X 15 2...20 X 15 Type Drive Belt Belt Belt Belt Nominal Cfm 14,000 14,000 16,000 16,000 Motor Hp 15 20 25 15 20 25 15 20 25 15 20 25 Motor Frame Size 254T 256T 284T 254T 256T 284T 254T 256T 284T 254T 256T 284T Motor Bearing Type Ball Ball Ball Ball Maximum Allowable Rpm 1300 1300 1300 1300 Motor Pulley Pitch Diameter (in.) 5.15.76.25.35.77.55.35.77.55.35.77.5 Nominal Motor Shaft Diameter (in.) 15/ Fan Pulley Pitch Diameter (in.) 8.7 8.7 8.7 9.5 9.5 11.1 9.5 9.5 11.1 9.5 9.5 11.1
Nominal Fan Shaft Diameter (in.) 115/ Belt Quantity 222222222222 Belt Type 5VX500 5VX530 5VX550 5VX530 5VX550 5VX590 5VX530 5VX550 5VX590 5VX530 5VX550 5VX590 Belt Length (in.) 50 53 55 53 55 5 9 53 55 59 53 55 59 Pulley Center Line Distance (in.) 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6 Factory Speed Setting (rpm) 1005 1147 1247 976 1050 1182 976 1050 1182 976 1050 1182
FURNACE SECTION Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max. Rollout Switch Cutout Temp (F)† 225 225 225 225 Burner Orifice Diameter (in ...drill size) Natural Gas Std .111 ... 34 .120...31 .120 ... 31 .120...31 Liquid Propane Alt .089 ... 43 .096...41 .096 ... 41 .096...41 Thermostat Heat Anticipator Setting Stage 1 (amps) 0.24 0.1 0.24 0.1 Stage 2 (amps) 0.13 0.1 0.13 0.1 Gas Input (Btuh) Stage 1 (Low Heat/High Heat) Stage 2 (Low Heat/High Heat) Efficiency (Steady State) (%) 82 82 82 82 Temperature Rise Range 15-45/35-65 10-40/30-60 10-40/3 -60 10-40/30-60 Manifold Pressure (in. wg) Natural Gas Std 3.5 3.5 3.5 3.5 Liquid Propane Alt 3.5 3.5 3.5 3.5 Gas Valve Quantity 2222
HIGH-PRESSURE SWITCH (psig) Cutout 426 426 426 426 Reset (Auto.) 320 320 320 320
MIXED-AIR FILTERS Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 10...20 x 24 x 2 Pleated 5 ... 20 x 20 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing Motor, Quantity...Hp 4...1 Fan, Diameter...Width (in.) 11 x 10
LEGEND *Sizes 020-040: Circuit 1 uses the lower por tion of condenser coil, Circuit 2 uses the upper
Al — Aluminum Cu — Copper
1…SR*812AT,
1…SR*942AT/2…SR*942AT
1
/
2
15/
8
17/
8
16
8
1…SR*812AT,
1…SR*942AT/2…SR*942AT
1
/
2
15/
15/
8
115/
17/
8
16
2…SR*942AT/2…SM125 2…SR*942AT/2…SM125
1
/
2
15/
8
15/
8
115/
17/
8
16
15/
8
262,500/394,000 300,000/600,000 300,000/600,000 300,000/600,000
350,000/525,000 400,000/800,000 400,000/800,000 400,000/800,000
10 ... 20 x 24 x 2 10...20 x 24 x 2
5 ... 20 x 20 x 4 5 ... 20 x 24 x 4
5 ... 20 x 24 x 4
5...20 x 20 x 4
5...20 x 20 x 4
8...16 x 25 x 2
4...20 x 25 x 2
portion. Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Rollout switch is manual reset.
8
5...20 x 20 x 4
5...20 x 20 x 4
115/
40
1
/
2
15/
17/
8
16
8
14
Page 15
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)
UNIT 48AJ,AK,AW,AY 050 051 060
NOMINAL CAPACITY (tons) 50 50 60
BASE U NIT See Operating Weights Table OPERATING WEIGHT (lb)
COMPRESSOR
Quantity ... Type (Ckt 1/Ckt 2)
Number of Refrigerant Circuits 22 2 Oil (oz) (Ckt 1, Ckt 2) Precharged Precharged Precharged
REFRIGERANT TYPE R-22 Operating Charge (lb-oz) Circuit 1 64-4 98-0 81-0 Circuit 2 58-8 98-0 81-0
CONDENSER COIL* Internally Enhanced, 3/8″ Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins Quantity 22 2 Rows ... Fins/in. 4 ... 15 4…15 4…15 Total Face Area (sq ft) 66.7 100 100
CONDENSER FAN Propeller Type Nominal Cfm 25,600 38,400 38,400 Quantity... Diameter (in.) 4 ... 30 6...30 6 ... 30 Motor Hp 11 1
EVAPORATOR COIL Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits Tube Size (in.) Rows ... Fins/in. 6 ... 16 4...17 4 ... 17 Total Face Area (sq ft) 31.3 48.1 48.1
EVAPORATOR FAN Centrifugal Type Quantity ... Size (in.) 2 ... 20 X 15 3...20 X 15 3 ... 20 X 15 Type Drive Belt Belt Belt Nominal Cfm 20,000 20,000 24,000
Motor Hp 20 25 30 20 25 30
Motor Frame Size 256T 284T 286T 256T 284T 286T 324T 324T 284T 286T 324T 324T Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1300 1200 1200 Motor Pulley Pitch Diameter (in.) 5.7 6.2 6.7 5.9 5.3 5.9 6.5 9.5 5.3 5.9 6.5 9.5 Nominal Motor Shaft Diameter (in.) 15/ Fan Pulley Pitch Diameter (in.) 9.5 9.5 9.5 11.1 9.1 9.5 9.5 13.7 9.1 9.5 9.5 13.7
Nominal Fan Shaft Diameter (in.) 115/ Belt Quantity 2222333 2 333 2 Belt Type 5VX550 5VX570 5VX570 5VX560 5VX530 5VX550 5VX570 5VX650 5VX530 5VX550 5VX570 5VX650 Belt Length (in.) 55 57 57 56 53 55 57 65 53 55 57 65 Pulley Center Line Distance (in.) 15.0-17.9 14.6-17.6 14.6-17.6 15.0-17.9 15.2-17.5 14.7-17.2 14.2-17.0 14.2-17.0 15.2-17.5 14.7-17.2 14.2-17.0 14.2-17.0 Factory Speed Setting (rpm) 1061 1154 1249 930 1019 1086 1197 1214 1019 1086 1197 1214
FURNACE SECTION Supply Line Pressure Range 5.0-in. wg min/13.5-in. wg max. Rollout Switch Cutout Temp (F)† 225 225 225 Burner Orifice Diameter (in ...drill size) Natural Gas Std .120 ... 31 .120...31 .120 ... 31 Liquid Propane Alt .096 ... 41 .096...41 .096 ... 41 Thermostat Heat Anticipator Setting Stage 1 (amps) 0.24 0.1 0.36 Stage 2 (amps) 0.13 0.1 0.13 Gas Input (Btuh) Stage 1 (Low Heat/High Heat) Stage 2 (Low Heat/High Heat) Efficiency (Steady State) (%) 82 82 82 Temperature Rise Range 10-40/30-60 10-40/30-60 10-40/30-60 Manifold Pressure (in. wg) Natural Gas Std 3.5 3.3 3.3 Liquid Propane Alt 3.5 3.3 3.3 Gas Valve Quantity 23 3
HIGH-PRESSURE SWITCH (psig) Cutout 426 426 426 Reset (Auto.) 320 32 0 320
MIXED-AIR FILTERS Quantity ... Size (in.) Standard 10 ... 20 x 24 x 2 16...20 x 24 x 2 Pleated 5 ... 20 x 20 x 4
OUTDOOR-AIR FILTERS
Quantity...Size (in.)
POWER EXHAUST Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing Motor, Quantity...Hp 4...1
LEGEND *Sizes 020-040: Circuit 1 uses the lower por tion of condenser coil, Circuit 2 uses the upper
Al — Aluminum Cu — Copper
2…SM125/1…SM125,
1…SM175
1
/
2
17/
8
8
16
2…SM125/2…SM125
1
/
2
40
(High Eff.)
17/
15/
8
17/
8
17/
8
115/
21/
8
8
16
40
(Prem. Eff.)
21/
8
25 30
17/
8
1..SM160,1..SM175/
1..SM160,1..SM175
1
/
2
(High Eff.)
17/
8
115/
16
300,000/600,000 582,000/873,000 582,000/873,000
400,000/800,000 776,000/1,164,000 776,000/1,164,000
16 ... 20 x 24 x 2
8 ... 20 x 20 x 4 8 ... 20 x 24 x 4
5 ... 20 x 24 x 4
8...16 x 25 x 2
4...20 x 25 x 2
11 x 10
8...20 x 20 x 4
8...20 x 24 x 4
12...16 x 25 x 2
6...20 x 25 x 2
6...1
11 x 10 Fan, Diameter...Width (in.)
portion. Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have intertwined evaporator coils.
†Rollout switch is manual reset.
40
21/
8
40
(Prem. Eff.)
21/
8
15
Page 16
MM
INCHES
MM
8
1755 44.3 1125
1768 44.6 1133
69.6
69.1
173546.5 1181
MM INCHES
87.7 2227 69.1 1755 44.3 1125
INCHES
KG
2782 87.7 2227 93.8 2383 47.2 1199
WEIGHT BAC
LB
6134
36 6014 272887.7 2227 96.3 2446 46.1 1172
UNIT
48AJ/AKE040
50AW/AY040 5962 2704 87.7 2227 90.8 2306 46.5 1181
50AJ/AK020 4607 2090 87.7 2227 70.9 1801 42.0 1067
48AJ/AKD020 4697 2131 87.7 2227 71.9 1826 42.5 1080
50AW/AY020 4685 2125 87.7 2227 70.9 1801 42.0 1067
48AW/AYD020 4737 2149 87.7 2227 71.9 1826 42.5 1080
48AJ/AKE020 4777 2167 87.7 2227 72.8 1849 41.0 1041
48AW/AYE020 4817 2185 87.7 2227 72.8 1849 41.0 1041
50AJ/AK025 4680 212387.7 2227 68.0 1727 43.9 1115
48AJ/AKE025 4850 2200 87.7 2227
48AJ/AKD025 4770 2164 87.7 2227 69.1 1755 44.3 1125
50AW/AY025 4758 215887.7 2227 68.0 1727 4 3.9 1115
48AW/AYE025 4890 221887.7 2227 69.6 1768 44.6 1133
50AJ/AK027 4873 2210 87.7 2227 68.0 1727 43.9 1115
48AW/AYD025 4810 2182
48AJ/AKD027 4963 2251 87.7 2227
48AJ/AKE027 5043 2287 87.7 2227 69.6 1768 44.6 1133
50AW/AY027 4951 2246 87.7 2227 68.0 1727 43.9 1115
48AW/AYD027 5003 2269 87.7 2227 69.1 1755 44.3 1125
48AW/AYE027 5083 2306 87.7 2227 69.6 1768 44.6 1133
50AJ/AK030 5023 227887.7 2227 68.0 1727 43.6 1107
48AJ/AKD030 5113 2319 87.7 2227 69.1 1755 44.0 111
48AJ/AKE030 5193 2356 87.7 2227 69.6 1768 44.3 11 25
48AW/AYD030 5153 2337 87.7 2227 69.1 1755 44.0 1118
50AW/AY030 5101 2314 87.7 2227 68.0 1727 43.6 1107
48AW/AYE030 5233 2374 87.7 2227 69.6 1768 44.3 112 5
50AJ/AK035 5229 2372 87.7 2227 68.3 173546.5 1181
48AJ/AKD035 5434 2465 87.7 2227 69.4 1763 46.9 1191
48AJ/AKE035 5594 2537 87.7 2227 70.0 1778 47.2 1199
50AW/AY035 5422 2459 87.7 2227 68.3
48AW/AYD035 5474 2483 87.7 2227 69.4 1763 46.9 1191
48AW/AYE0355634 2556 87.7 2227 70.0 1778 47.2 1199
50AJ/AK036 5609 2544 87.7 2227 93.4 2372 45.3 1152
48AJ/AKD036 5814 2637 87.7 2227 94.8 2409 45.8 116 3
48AJ/AKE036 5974 2710 87.7 2227 96.3 2446 46.1 1172
50AW/AY0365802 2632 87.7 2227 93.3 2370 45.4 1153
48AW/AYD036 5854 2655 87.7 2227 94.8 2408 45.8 11 63
48AW/AYE0
48AW/AYD040 6014 2728 87.7 2227 92.3 2344 46.9 1191
50AJ/AK040 5769 2617 87.7 2227 90.8 2306 46.5 1181
48AJ/AKD040 5974 2710 87.7 2227 92.3 2344 46.9 1191
C
76 161.7 4106 126.0 3200 44.6 1133
4118 161.7 4106 137.7 3498 48.6 1234
48AJ/AKD060 8838 4009 161.7 4106 130.7 3320 46.6 1184
48AJ/AKE060 9078
48AW/AYE051 8964 4066 161.7 4106 140.2 3562 48.7 1237
50AJ/AK060 8708 3950 161.7 4106 123.6 3139 44.6 1133
50AW/AY051 8759 3973 161.7 4106 125.9 3198 44.6 1133
48AW/AYE040 6174 2801 87.7 2227 93.8 2383 47.2 1199
50AJ/AK041 5885 2669 87.7 2227 89.0 2261 45.6 1158
50AW/AY041 6078 2757 87.7 2227 89.1 2262 45.6 1159
48AJ/AKD041 6090 2762 87.7 2227 90.5 2300 46.0 1169
48AJ/AKE041 6250 2835 87.7 2227 92.1 2338 46.3 1177
48AW/AYD041 61302781 87.7 2227 90.6 2300 46.0 1169
48AW/AYE041 6290 285387.7 2227 92.1 233946.3 117 7
50AJ/AK050 6338 2875 87.7 2227 89.2 2266 46.1 1171
48AJ/AKE050 6703 3040 87.7 2227 92.2 2342 46.8 1189
48AJ/AKD050 6543 296887.7 2227 90.7 2304 46.5 1181
50AW/AY050 6531 2962 87.7 2227 89.2 2266 46.1 1171
48AW/AYD050 6583 2986 87.7 2227 90.7 2304 46.5 1181
A
48AW/AYD051 8714 3953 161.7 4106 133.2 3382 46.6 1185
48AJ/AKD051 8674 3935 161.7 4106 133.2 3383 46.6 1185
48AJ/AKE051 8914 4043 161.7 4106 140.2 3562 48.7 1237
48AW/AYE050 67433059 87.7 2227 92.2 2342 46.8 1189
50AJ/AK051 8544 38
48AW/AYD060 8878 4027 161.7 4106 130.7 3320 46.6 1184
48AW/AYE060 9128 4140 161.7 4106 137.7 3498 48.6 1234
50AW/AY060 8923 4047 161.7 4106 123.6 3139 44.6 1133
Fig. 11 — Rigging Information
B
CAUTION - NOTICE TO RIGGERS:
ALL PANELS MUST BE IN PLACE WHEN RIGGING.
NOTE: Rig with four cables and spread with two 92 inch (2337 MM) spreader bars.
Maintain a distance of 74 inches (1880 MM) from top of unit to eyehook.
OF
CENTER
GRAVITY
16
a48-8246
NOTE:
Add 312 lb (142 kg) for export crating. (020-035 units)
Add 220 lb (100 kg) for copper condenser coil. (020-035 units)
Add 380 lb (172 kg) for copper condenser coil. (036-050 units)
Add 346 lb (157 kg) for export crating. (036-050 units)
Add 651 lb (295 kg) for copper condenser coil. (051 and 060 units)
Add 588 lb (266 kg) for export crating. (051 and 060 units)
Page 17
Table 2 — Unit Operating Weights
UNIT
48AJ/AK Low Heat 3842 3915 4032 4182 4435 4815 4975 5091 5446 7224 7388 48AJ/AK High Heat 3922 3995 4112 4262 4595 4975 5135 5251 5606 7464 7628 48AW/AY Low Heat 3882 3955 4072 4222 4475 4855 5015 5131 5486 7264 7428 48AW/AY High Heat 3962 4035 4152 4302 4635 5015 5175 5291 5646 7514 7678
020 025 027 030 035 036 040 041 050 051 060
BASE UNIT WEIGHTS — lb
Table 3 — Option and Accessory Weights
OPTION/
ACCESSORY
Barometric Relief 300 300 300 300 300 300 300 300 300 450 450 Powe r Exh au st 450 450 450 450 450 450 450 450 450 675 675 Mod. Power Exhaust 500 500 500 500 500 500 500 500 500 725 725 Cu Tubing/Cu Fin Condenser Coil 220 220 220 220 285 380 285 380 380 651 651
Outdoor Air Hood Crate and Packaging (Less Hoods' Weight)
Outdoor Air Hoods/Filters 170 170 170 170 170 170 170 170 170 255 255 Hail Guard 73 73 73 73 73 146 146 146 146 219 219 Roof Curb (14-in.) 365 365 365 365 410 410 410 410 410 540 585
020 025 027 030 035 036 040 041 050 051 060
45 45 45 45 45 45 45 45 45 45 45
(Packaging Only) (Packaging Only)
Table 4 — Constant Volume Fan Motor Weights
CV MOTOR WEIGHTS — lb
MOTOR
HP
5
10
15
20
25
30
40
UNIT
VOLTAGE
230/460 78 94
575 78 92
230/460 118 164
575 118 156
230/460 150 217
575 150 220
230/460 212 250
575 212 258
230/460 240 309
575 240 319
230/460 283 355
575 283 359
230/460 372 415
575 372 410
HIGH
EFFICIENCY
IFM
PREMIUM
EFFICIENCY
IFM
LEGEND AND NOTES FOR TABLES 2-5
OPTION/ACCESSORY WEIGHTS — lb
Table 5 — Variable Volume Fan Motor Weights
VAV MOTOR WEIGHTS — lb
MOTOR
HP
5
10
15
20
25
30
40
UNIT
VOLTAGE
230/460 125 141
575 163 177
230/460 204 250
575 204 242
230/460 238 305
575 240 310
230/460 348 386
575 304 350
230/460 377 446
575 375 454
230/460 480 552
575 418 494
230/460 637 680
575 587 625
HIGH
EFFICIENCY
IFM
PREMIUM
EFFICIENCY
IFM
LEGEND
Cu Copper CV Constant Volume FIOP — Factory-Installed Option HP Horsepower IFM Indoor Fan Motor VAV Variable Air Volume VFD — Variable Frequency Drive
NOTES:
1. Base unit weight includes outdoor-air hoods. Base unit weight does NOT include indoor-fan motor. ADD indoor-fan motor, FIOPs, and accessories for TOTAL operating weight.
2. The VAV motor weights include indoor fan motor and the VFD (variable frequency drive), VFD transducers, and associated wiring.
17
Page 18
Table 6 — Evaporator Fan Motor Data
UNIT SIZE
48AJ,AK,
AW,AY
020
025
027
030
035
036
040
041
050
051
060
NOTES:
1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 115/16 inches.
2. All indoor fan motors meet the minimum efficiency requirements as established by the Energy Policy Act of 1992 (EPACT), effective October 24, 1997.
MOTOR
HP
5 1.125 677 BK55 4.8 NONE - 1.125 1B5V124 12.4 B - 1.9375 BX56 8 10 1.375 895 2BK50 4.4 NONE - 1.375 2B5V86 8.6 B - 1.9375 BX50 8 15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 9
5 1.125 677 BK55 4.8 NONE - 1.125 1B5V124 12.4 B - 1.9375 BX56 8 10 1.375 962 1B5V60 6.1 H - 1.375 1B5V110 11.1 B - 1.9375 5VX570 11 15 1.625 1106 2B5V54 5.5 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 9
10 1.375 819 2BK50 4.4 NONE - 1.375 2B5V94 9.4 B - 1.9375 (2) BX50 8 15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 10 20 1.625 1187 2B5V58 5.9 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
10 1.375 884 2BK50 4.4 H - 1.375 2B5V94 9.5 B - 1.9375 (2) BX50 8 15 1.625 1096 2B5V56 5.7 B - 1.625 2B5V90 9.1 B - 1.9375 (2) 5VX530 9 20 1.625 1187 2B5V58 5.9 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
15 1.625 1005 2B5V50 5.1 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX500 9 20 1.625 1147 2B5V56 5.7 B - 1.625 2B5V86 8.7 B - 1.9375 (2) 5VX530 10 25 1.875 1247 2B5V62 6.2 B - 1.875 2B5V86 8.7 B - 1.9375 (2) 5VX530 11
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10 20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11 25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10 20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11 25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
15 1.625 976 2B5V52 5.3 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX530 10 20 1.625 1050 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 11 25 1.875 1182 2B5V74 7.5 B - 1.875 2B5V110 11.1 B - 1.9375 (2) 5VX590 11
20 1.625 1061 2B5V56 5.7 B - 1.625 2B5V94 9.5 B - 1.9375 (2) 5VX550 10 25 1.875 1154 2B5V62 6.2 B - 1.875 2B5V94 9.5 B - 1.9375 (2) 5VX570 11 30 1.875 1247 2B5V66 6.7 B - 1.875 2B5V94 9.5 B - 1.9375 (2) 5VX570 13
20 1.625 930 2B5V58 5.9 B - 1.625 2B5V110 11.1 B - 1.9375 (2) 5VX560 11 25 1.875 1019 3B5V52 5.3 B - 1.875 3B5V90 9.1 B - 1.9375 (3) 5VX530 12 30 1.875 1086 3B5V58 5.9 B - 1.875 3B5V94 9.5 B - 1.9375 (3) 5VX550 12
40 High 2.125 1197 3B5V64 6.5 B - 2.125 3B5V94 9.5 B - 1.9375 (3) 5VX570 14
40 Prem. 2.125 1214 2B5V94 9.5 B - 2.125 2B5V136 13.7 B - 1.9375 (2) 5VX650 15
25 1.875 1019 3B5V52 5.3 B - 1.875 3B5V90 9.1 B - 1.9375 (3) 5VX530 12 30 1.875 1086 3B5V58 5.9 B - 1.875 3B5V94 9.5 B - 1.9375 (3) 5VX550 12
40 High 2.125 1197 3B5V64 6.5 B - 2.125 3B5V94 9.5 B - 1.9375 (3) 5VX570 14
40 Prem. 2.125 1214 2B5V94 9.5 B - 2.125 2B5V136 13.7 B - 1.9375 (2) 5VX650 15
MOTOR
SHAFT DIA.
(in.)
FAN SHAFT SPEED
(rpm)
MOTOR
SHEAVE
(P/N)
MOTOR
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
FAN
SHEAVE
(P/N)
FAN
SHEAVE
PITCH
DIAMETER
(in.)
BUSHING
DIAMETER
(in.)
BELT
(Quantity)
(P/N)
BELT
TENSION
(lb at .25 in.)
a48-8241
Fig. 12 — Air Distribution — Thru-the-Bottom
a48-8242
Fig. 13 — Air Distribution — Thru-the-Side
18
Page 19
Step 5 — Install Flue Hood
48AJ,AK,AW,AY020-050 UNITS — Flue hood is shipped inside gas section of unit. To install, secure flue hood to access panel. See Fig. 14.
48AJ,AK,AW,AY051 AND 060 UNITS — Flue hood and wind baffle are shipped inside gas section of unit. To install, se­cure flue hood to access panel. Install the two pieces of the wind baffle over the flue hood. See Fig. 15.
NOTE: When properly installed, flue hood will line up with combustion fan housing. See Fig. 16.
a48-3823
Fig. 16 — Combustion Fan Housing Location
(48AJ,AK,AW,AY020-050 Shown)
Step 6 — Trap Condensate Drain — See Fig. 4-9
for drain location. Condensate drain is open to atmosphere and must be trapped. Install a trapped drain at the drain location. One 1-in. FPT coupling is provided inside the unit evaporator section for condensate drain connection. A trap at least 4-in. deep must be used. See Fig. 17. Trap must be installed to pre­vent freeze-up.
Condensate pans are sloped so that water will completely drain from the condensate pan to comply with indoor air quali­ty guidelines. The condensate drain pans are not insulated.
Fig. 14 — Flue Hood Location
(48AJ,AK,AW,AY020-050 Units)
GAS SECTION ACCESS PANEL
FLUE HOOD
WIND BAFFLE
TOP VIEW SIDE VIEW
Fig. 15 — Flue Hood Location
(48AJ,AK,AW,AY051 and 060 Units)
a48-3712
a48-4076
a48-3714
Fig. 17 — Condensate Drain Trap Piping Details
(Typical Roof Curb or Slab Mount Shown)
Step 7 — Install Gas Piping — Unit is equipped for
use with natural gas. Installation must conform with local building codes or, in the absence of local codes, with the Na­tional Fuel Gas Code, ANSI Z223.1.
Install manual gas shutoff valve with a tap for test gage connection at unit. Field gas piping must in­clude sediment trap and union. See Fig. 18. An
1
/8-in. NPT pressure
1
/8-in. NPT is
also located on the gas manifold adjacent to the gas valve.
WARNING
Do not pressure test gas supply while connected to unit. Always disconnect union before servicing. Serious injury could result.
19
Page 20
a48-2524
Fig. 18 — Field Gas Piping
IMPORTANT: Natural gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13.5 in. wg.
Size gas-supply piping for 0.5-in. wg maximum pressure
drop. Do not use supply pipe smaller than unit gas connection. OPTIONAL STAGED GAS UNITS — See Table 7 for staged
gas information. Staging pattern is selected during controls start-up.
For complete information and service instructions for Staged Gas Control Units, see Control Operation and Trouble­shooting literature.
Table 7 — 48A Series Staged Gas Control
MODEL NUMBER POSITION
5 6,7,8
020 025 027
S
T
T
T 051,060 9 stages High S 051,060 11 stages Low
030 035 036 040 041 050
035 036 040 041 050
020 025 027 030
NUMBER OF
STAGES
5 stages
7 stages High
HEAT SIZE
Low
High
local codes) in branch circuit wiring remote from unit. Observe requirements of NEC Article 440. Install service switch upstream of remote fuses if required.
The main power terminal block is suitable for use with aluminum or copper wire. See Fig. 19. Units have circuit breakers for compressors, fan motors, and control circuit. The unit must be electrically grounded in accordance with local codes, or in absence of local codes, with NEC, ANSI C1-latest year.
FIELD POWER SUPPLY — Unit is factory wired for volt­age shown on unit nameplate. See Tables 8A and 8B for elec­trical data.
Field wiring can be brought into the unit from bottom (through basepan and roof curb) or through side of unit (corner post next to control box).
1
A 3
/2-in. NPT coupling for field power wiring and a 3/4-in. NPT coupling for 24-v control wiring are provided in basepan. In the side post, there are two 2
1
/2-in. (48A020-035) or 3-in. (48A036-060) knockouts for the field power wiring. See Fig. 4-9. If control wiring is to be brought in through the side of
7
unit, a
/8-in. diameter hole is provided in the condenser side
post next to the control box.
Do not route control wiring in the same conduit as power
wiring.
If disconnect box is mounted to corner post, be careful not
to drill or screw into the condenser coil.
TB1
FIELD
POWER
SUPPLY
FIELD SUPPLIED
DISCONNECT PER NEC
FIELD-INSTALLED DISCONNECT
11
21
22
12
13
23
EQUIP GND
OPTIONAL
FACTORY-INSTALLED
DISCONNECT
11
12
13
21
22
23
Step 8 — Make Electrical Connections
POWER WIRING — Units are factory wired for the voltage shown on the unit nameplate.
Provide a unit safety disconnect switch in the main power supply to each unit (see Fig. 19). Select switch size and mount­ing location in accordance with applicable local codes or National Electrical Code (NEC). If combining the functions of safety disconnect with maximum overcurrent protection (MOCP) fuses (“fused disconnect”), coordinate safety switch size with MOCP size data as marked on unit informative plate.
Unit may be equipped with optional factory-installed non­fused disconnect switch (see Fig. 19). Provide maximum overcurrent protection devices (fuses or HACR breakers, per
FIELD POWER WIRING
FACTORY-INSTALLED DISCONNECT
LEGEND
GND — Ground NEC — National Electrical Code TB Terminal Block
Fig. 19 — Field Power Wiring Connections
20
GND
a48-6977
Page 21
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
208 187 229 23 184 23 184 23 184 2
230 207 253 23 184 23 184 23 184 2
020
460 414 508 10.2 90 10.2 90 10.2 90 2
575 518 632 9 73 9 73 9 73 2
208 187 229 21.8 184 25.6 190 25.6 190 2
230 207 253 21.8 184 25.6 190 25.6 190 2
025
460 414 508 11 90 13.5 95 13.5 95 2
575 518 632 9 73 10.2 75 10.2 75 2
208 187 229 25.6 190 25.6 190 25.6 190 2
230 207 253 25.6 190 25.6 190 25.6 190 2
027
460 414 508 13.5 95 13.5 95 13.5 95 2
575 518 632 10.2 75 10.2 75 10.2 75 2
See Legend and Notes on page 24.
VO LTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) MCA MOCP*
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
COMPRESSOR
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN M OTO R
516.7
10 30.8
15 46.2
515.2
10 28.0
15 42.0
57.6
10 14.0
15 21.0
56.1
10 11.0
15 17.0
516.7
10 30.8
15 46.2
515.2
10 28.0
15 42.0
57.6
10 14.0
15 21.0
56.1
10 11.0
15 17.0
10 30.8
15 46.2
20 59.4
10 28.0
15 42.0
20 54.0
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
POWER
EXHAUST
23.6 128.1 150
23.6 144.1 150
23.6 163.4 200
23.6 126.8 150
23.6 140.8 150
23.6 158.3 200
12.6 60.0 70
12.6 67.3 80
12.6 76.1 90
23.6 132.7 150
23.6 148.1 175
23.6 167.4 200
23.6 131.4 150
23.6 144.8 150
23.6 162.3 200
12.6 68.2 80
12.6 74.7 80
12.6 83.5 100
23.6 151.9 175
23.6 171.2 200
23.6 187.7 225
23.6 148.6 175
23.6 166.1 200
23.6 181.1 225
12.6 77.2 90
12.6 86.0 100
12.6 93.5 110
12.6 62.6 70
12.6 69.7 80
12.6 75.9 90
POWER SUPPLY
104.5 125
120.5 150
139.8 175
103.2 125
117.2 125
134.7 175
—47.450
—54.760
—63.580
—40.650
9.6 50.2 60
—46.050
9.6 55.6 60
—53.570
9.6 63.1 80
109.1 125
124.5 150
143.8 175
107.8 125
121.2 125
138.7 175
—55.660
—62.170
—70.990
—43.350
9.6 52.9 60
—48.450
9.6 58.0 60
—55.970
9.6 65.5 80
128.3 150
147.6 175
164.1 200
125.0 150
142.5 175
157.5 200
—64.670
—73.490
80.9 100
—49.660
—57.170
—63.380
21
Page 22
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
208 187 229 23 184 23 184 21.8 184 21.8 184 2
230 207 253 23 184 23 184 21.8 184 21.8 184 2
030
460 414 508 10.2 90 10.2 90 11 90 11 90 2
575 518 632 9 73 9 73 9 73 9 73 2
208 187 229 21.8 184 25.6 190 25.6 190 25.6 190 2
230 207 253 21.8 184 25.6 190 25.6 190 25.6 190 2
035
460 414 508 11 90 13.5 95 13.5 95 13.5 95 2
575 518 632 9 73 10.2 75 10.2 75 10.2 75 2
208 187 229 21.8 184 25.6 190 25.6 190 25.6 190 4
230 207 253 21.8 184 25.6 190 25.6 190 25.6 190 4
036
460 414 508 11 90 13.5 95 13.5 95 13.5 95 4
575 518 632 9 73 10.2 75 10.2 75 10.2 75 4
See Legend and Notes on page 24.
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) MCA MOCP*
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
COMPRESSOR
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN M OTO R
10 30.8
15 46.2
20 59.4
10 28.0
15 42.0
20 54.0
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
POWER
EXHAUST
23.6 164.7 175
23.6 184.0 225
23.6 200.5 250
23.6 161.4 175
23.6 178.9 200
23.6 193.9 225
12.6 79.1 90
12.6 87.9 100
12.6 95.4 110
12.6 68.0 80
12.6 75.1 90
12.6 81.3 100
23.6 193.6 225
23.6 209.5 250
23.6 228.7 300
23.6 187.9 225
23.6 202.9 250
23.6 220.4 250
12.6 97.0 110
12.6 104.5 125
12.6 113.2 125
12.6 78.7 90
12.6 84.9 100
12.6 91.2 110
23.6 206.0 250
23.6 222.5 250
23.6 241.7 300
23.6 201.1 225
23.6 216.1 250
23.6 233.6 300
12.6 103.6 110
12.6 111.1 125
12.6 119.8 150
POWER SUPPLY
141.1 150
160.4 200
176.9 225
137.8 150
155.3 175
170.5 200
—66.580
—75.390
82.8 100
—55.060
—62.570
—68.790
169.4 200
185.9 225
205.1 250
164.3 200
179.3 225
196.8 250
84.4 100
91.9 110
100.6 125
—66.180
—72.390
78.6 100
182.4 225
198.9 250
218.1 250
177.5 200
192.5 225
210.0 250
91.0 110
98.5 125
107.2 125
—71.380
9.6 80.9 90
—77.590
9.6 87.1 100
83.8 110
9.6 93.4 110
22
Page 23
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
208 187 229 25.6 190 25.6 190 34.3 265 34.3 265 4
230 207 253 25.6 190 25.6 190 34.3 265 34.3 265 4
040
460 414 508 13.5 95 13.5 95 16 120 16 120 4
575 518 632 10.2 75 10.2 75 12.9 80 12.9 80 4
208 187 229 25.6 190 25.6 190 34.3 265 34.3 265 4
230 207 253 25.6 190 25.6 190 34.3 265 34.3 265 4
041
460 414 508 13.5 95 13.5 95 16 120 16 120 4
575 518 632 10.2 75 10.2 75 12.9 80 12.9 80 4
208 187 229 34.3 265 34.3 265 34.3 265 47 380 4
230 207 253 34.3 265 34.3 265 34.3 265 47 380 4
050
460 414 508 16 120 16 120 16 120 22.4 175 4
575 518 632 12.9 80 12.9 80 12.9 80 18.6 140 4
See Legend and Notes on page 24.
VO LTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) MCA MOCP*
COMPRESSOR
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN M OTO R
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
20 59.4
25 74.8
30 88.0
20 54.0
25 68.0
30 80.0
20 27.0
25 34.0
30 40.0
20 22.0
25 27.0
30 32.0
POWER
EXHAUST
23.6 227.2 250
23.6 243.7 300
23.6 262.4 300
23.6 222.3 250
23.6 237.3 250
23.6 254.8 300
12.6 111.1 125
12.6 118.6 125
12.6 127.3 150
12.6 90.5 100
12.6 96.7 110
12.6 103.0 125
23.6 227.2 250
23.6 243.7 300
23.6 262.9 300
23.6 222.3 250
23.6 237.3 250
23.6 254.8 300
12.6 111.1 125
12.6 118.6 125
12.6 127.3 150
23.6 273.8 300
23.6 293.0 350
23.6 309.5 350
23.6 267.4 300
23.6 284.9 300
23.6 299.9 350
12.6 130.0 150
12.6 138.7 150
12.6 146.2 175
12.6 107.8 125
12.6 114.1 125
12.6 120.3 150
POWER SUPPLY
203.6 225
220.1 250
239.3 300
198.7 225
213.7 250
231.2 250
98.5 110
106.0 125
114.7 125
—77.990
84.1 100
90.4 110
203.6 225
220.1 250
239.3 300
198.7 225
213.7 250
231.2 250
98.5 110
106.0 125
114.7 125
—77.990
9.6 87.5 100
84.1 100
9.6 93.7 110
90.4 110
9.6 100.0 125
250.2 300
269.4 300
285.9 350
243.8 250
261.3 300
276.3 350
117.4 125
126.1 150
133.6 150
95.2 110
101.5 125
107.7 125
23
Page 24
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
208 187 229 34.3 265 34.3 265 34.3 265 34.3 265 6
230 207 253 34.3 265 34.3 265 34.3 265 34.3 265 6
051
460 414 508 16 120 16 120 16 120 16 120 6
575 518 632 12.9 80 12.9 80 12.9 80 12.9 80 6
208 187 229 40.8 265 47 380 40.8 265 47 380 6
230 207 253 40.8 265 47 380 40.8 265 47 380 6
060
460 414 508 20.2 135 22.4 175 20.2 135 22.4 175 6
575 518 632 16.6 120 18.6 140 16.6 120 18.6 140 6
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA — Minimum Circuit Amps MOCP — Maximum Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps
*Fuse or HACR circuit breaker per NEC. NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent
of voltage imbalance. % Voltage imbalance
= 100 x
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) MCA MOCP*
max voltage deviation from average voltage
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
average voltage
COMPRESSOR
CONDENSER
FAN MOTOR
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the max­imum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
EVAPORATOR
FAN M OTO R
20 59.4
25 74.8
6.5
(ea)
30 88
40 114
20 54
25 68
6.6
(ea)
30 80
40 104
20 27
25 34
3.3
(ea)
30 40
40 52
20 22
25 27
2.6
(ea)
30 32
40 41
25 75.0
6.5 30 88.0
(ea)
40 114.0
25 68.0
6.6 30 80.0
(ea)
40 104.0
25 34.0
3.3 30 40.0
(ea)
40 52.0
25 27.0
2.6 30 32.0
(ea)
40 41.0
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
= 1.53%
POWER
EXHAUST
250.5 300
35.4 285.9 300 — 269.7 300
35.4 305.1 350 — 286.2 350
35.4 321.6 400 — 318.7 400
35.4 354.1 450 — 244.3 250
35.4 279.7 300 — 261.8 300
35.4 297.2 350 — 276.8 350
35.4 312.2 350 — 306.8 400
35.4 342.2 400 — 117.6 125
18.9 136.5 150 — 126.3 150
18.9 145.2 175 — 133.8 150
18.9 152.7 175 — 148.8 200
18.9 167.7 200 — 94.7 110
14.4 109.1 125 — 101.0 125
14.4 115.4 125 — 107.2 125
14.4 121.6 150 — 118.5 150
14.4 132.9 150 — 308.1 350
35.4 343.5 400 — 324.6 400
35.4 360.0 400 — 357.1 450
35.4 392.5 450 — 300.2 350
35.4 335.6 350 — 315.2 350
35.4 350.6 400 — 345.2 400
35.4 380.6 450 — 147.5 175
18.9 166.4 175 — 155.0 175
18.9 173.9 200 — 170.0 200
18.9 188.9 225 — 119.8 125
18.9 138.7 150 — 126.0 150
18.9 144.9 175 — 137.3 175
18.9 156.2 175
452 + 464 + 455
3
1371
=
3
= 457
7 457
POWER SUPPLY
24
Page 25
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet
UNIT
VOLTAGE
SIZE
3 PH, 60 Hz
48A
020
025
027
See Legend and Notes on page 28.
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) FLA MCA
208 187 229 23 184 23 184 23 184 2
230 207 253 23 184 23 184 23 184 2
460 414 508 10.2 90 10.2 90 10.2 90 2
575 518 632 9 73 9 73 9 73 2
208 187 229 21.8 184 25.6 190 25.6 190 2
230 207 253 21.8 184 25.6 190 25.6 190 2
460 414 508 11 90 13.5 95 13.5 95 2
575 518 632 9 73 10.2 75 10.2 75 2
208 187 229 25.6 190 25.6 190 25.6 190 2
230 207 253 25.6 190 25.6 190 25.6 190 2
460 414 508 13.5 95 13.5 95 13.5 95 2
575 518 632 10.2 75 10.2 75 10.2 75 2
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
COMPRESSOR
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN MOTOR
516.7
10 30.8
15 46.2
515.2
10 28.0
15 42.0
57.6
10 14.0
15 21.0
56.1
10 11.0
15 17.0
516.7
10 30.8
15 46.2
515.2
10 28.0
15 42.0
57.6
10 14.0
15 21.0
56.9
10 11.0
15 17.0
10 30.8
15 46.2
20 59.4
10 28.0
15 42.0
20 54.0
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
POWER
EXHAUST
CONVENIENCE
OUTLET
7.0 111.5 125
23.6 7.0 135.2 150 — 7.0 127.5 150
23.6 7.0 151.1 175 — 7.0 146.8 175
23.6 7.0 170.4 200 — 7.0 110.2 125
23.6 7.0 133.9 150 — 7.0 124.2 150
23.6 7.0 147.8 175 — 7.0 141.7 175
23.6 7.0 165.3 200 — 3.5 50.9 60
12.6 3.5 64.1 70 — 3.5 58.2 70
12.6 3.5 70.8 80 — 3.5 67.0 80
12.6 3.5 79.6 100 — 2.5 43.1 50
9.6 2.5 52.8 60 — 2.5 48.5 50
9.6 2.5 58.1 60 —2.556.0
9.6 2.5 65.6 80 — 7.0 116.1 125
23.6 7.0 139.7 150 — 7.0 131.5 150
23.6 7.0 155.1 175 — 7.0 150.8 175
23.6 7.0 174.4 200 — 7.0 114.8 125
23.6 7.0 138.4 150 — 7.0 128.2 150
23.6 7.0 151.8 175 — 7.0 145.7 175
23.6 7.0 169.3 200 — 3.5 59.1 70
12.6 3.5 71.7 80 — 3.5 65.6 70
12.6 3.5 78.2 90 — 3.5 74.4 90
12.6 3.5 87.0 100 — 2.5 46.6 50
6.1 2.5 52.7 60 — 2.5 50.9 60
6.1 2.5 57.0 60 — 2.5 58.4 70
6.1 2.5 64.5 80 — 7.0 135.3 150
23.6 7.0 158.9 175 — 7.0 154.6 200
23.6 7.0 178.2 200 — 7.0 171.1 225
23.6 7.0 194.7 250 — 7.0 132.0 150
23.6 7.0 155.6 175 — 7.0 149.5 175
23.6 7.0 173.1 200 — 7.0 164.5 200
23.6 7.0 188.1 225 — 3.5 68.1 80
12.6 3.5 80.7 90 — 3.5 76.9 90
12.6 3.5 89.5 110 — 3.5 84.4 110
12.6 3.5 97.0 110 — 2.5 52.1 60
9.6 2.5 61.7 70 — 2.5 59.6 70
9.6 2.5 69.2 80 — 2.5 65.8 80
9.6 2.5 75.4 90
POWER SUPPLY
Fuse or
HACR Brkr*
70
25
Page 26
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
030
035
036
See Legend and Notes on page 28.
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) FLA MCA
208 187 229 23 184 23 184 21.8 184 21.8 184 2
230 207 253 23 184 23 184 21.8 184 21.8 184 2
460 414 508 10.2 90 10.2 90 11 90 11 90 2
575 5186329739739739732
208 187 229 21.8 184 25.6 190 25.6 190 25.6 190 2
230 207 253 21.8 184 25.6 190 25.6 190 25.6 190 2
460 414 508 11 90 13.5 95 13.5 95 13.5 95 2
575 518 632 9 73 10.2 75 10.2 75 10.2 75 2
208 187 229 21.8 184 25.6 190 25.6 190 25.6 190 4
230 207 253 21.8 184 25.6 190 25.6 190 25.6 190 4
460 414 508 11 90 13.5 95 13.5 95 13.5 95 4
575 518 632 9 73 10.2 75 10.2 75 10.2 75 4
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
COMPRESSOR
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN MOTOR
10 30.8
15 46.2
20 59.4
10 28.0
15 42.0
20 54.0
10 14.0
15 21.0
20 27.0
10 11.0
15 17.0
20 22.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
POWER
EXHAUST
CONVENIENCE
OUTLET
7.0 148.1 175
23.6 7.0 171.7 200 — 7.0 167.4 200
23.6 7.0 191.0 225 — 7.0 183.9 225
23.6 7.0 207.5 250 — 7.0 144.8 150
23.6 7.0 168.4 175 — 7.0 162.3 200
23.6 7.0 185.9 225 — 7.0 177.3 225
23.6 7.0 200.9 250 — 3.5 70.0 80
12.6 3.5 82.6 90 — 3.5 78.8 90
12.6 3.5 91.4 110 — 3.5 86.3 110
12.6 3.5 98.9 125 — 2.5 57.5 60
9.6 2.5 67.1 70 — 2.5 65.0 80
9.6 2.5 74.6 90 — 2.5 71.2 90
9.6 2.5 80.8 100 — 7.0 176.4 200
23.6 7.0 200.0 225 — 7.0 192.9 250
23.6 7.0 216.5 250 — 7.0 212.1 250
23.6 7.0 235.7 300 — 7.0 171.3 200
23.6 7.0 194.9 225 — 7.0 186.3 225
23.6 7.0 209.9 250 — 7.0 203.8 250
23.6 7.0 227.4 250 — 3.5 87.9 100
12.6 3.5 100.5 110 — 3.5 95.4 110
12.6 3.5 108.0 125 — 3.5 104.1 125
12.6 3.5 116.7 150 — 2.5 68.6 80
9.6 2.5 78.2 90 — 2.5 74.8 90
9.6 2.5 84.4 100 — 2.5 81.1 100
9.6 2.5 90.7 110 — 7.0 189.4 225
23.6 7.0 213.0 250 — 7.0 205.9 250
23.6 7.0 229.5 250 — 7.0 225.1 250
23.6 7.0 248.7 300 — 7.0 184.5 225
23.6 7.0 208.1 250 — 7.0 199.5 250
23.6 7.0 223.1 250 — 7.0 217.0 250
23.6 7.0 240.6 300 — 3.5 94.5 110
12.6 3.5 107.1 125 — 3.5 102.0 125
12.6 3.5 114.6 125 — 3.5 110.7 125
12.6 3.5 123.3 150 — 2.5 73.8 90
9.6 2.5 83.4 100 — 2.5 80.0 100
9.6 2.5 89.6 110 — 2.5 86.3 110
9.6 2.5 95.9 110
POWER SUPPLY
Fuse or
HACR Brkr*
26
Page 27
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
040
041
050
See Legend and Notes on page 28.
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) FLA MCA
208 187 229 25.6 190 25.6 190 34.3 265 34.3 265 2
230 207 253 25.6 190 25.6 190 34.3 265 34.3 265 2
460 414 508 13.5 95 13.5 95 16.0 120 16.0 120 2
575 518 632 10.2 75 10.2 75 12.9 80 12.9 80 2
208 187 229 25.6 190 25.6 190 34.3 265 34.3 265 4
230 207 253 25.6 190 25.6 190 34.3 265 34.3 265 4
460 414 508 13.5 95 13.5 95 16 120 16 120 4
575 518 632 10.2 75 10.2 75 12.9 80 12.9 80 4
208 187 229 34.3 265 34.3 265 34.3 265 47 380 4
230 207 253 34.3 265 34.3 265 34.3 265 47 380 4
460 414 508 16 120 16 120 16 120 22.4 175 4
575 518 632 12.9 80 12.9 80 12.9 80 18.6 140 4
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
COMPRESSOR
CONDENSER
FAN MOTOR
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
6.5
(ea)
6.6
(ea)
3.3
(ea)
2.6
(ea)
EVAPORATOR
FAN MOTOR
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
15 46.2
20 59.4
25 74.8
15 42.0
20 54.0
25 68.0
15 21.0
20 27.0
25 34.0
15 17.0
20 22.0
25 27.0
20 59.0
25 75.0
30 88.0
20 54.0
25 68.0
30 80.0
20 27.0
25 34.0
30 40.0
20 22.0
25 27.0
30 32.0
POWER
EXHAUST
CONVENIENCE
OUTLET
7.0 210.6 250
23.6 7.0 234.2 250 — 7.0 227.1 250
23.6 7.0 250.7 300 — 7.0 246.3 300
23.6 7.0 269.9 300 — 7.0 205.7 225
23.6 7.0 229.3 250 — 7.0 220.7 250
23.6 7.0 244.3 250 — 7.0 238.2 300
23.6 7.0 261.8 300 — 3.5 102.0 110
12.6 3.5 114.6 125 — 3.5 109.5 125
12.6 3.5 122.1 125 — 3.5 118.2 150
12.6 3.5 130.8 150 — 2.5 80.4 90
9.6 2.5 90.0 100
2.5 86.6 100
9.6 2.5 96.2 110
2.5 92.9 110
9.6 2.5 102.5 125
7.0 210.6 250
23.6 7.0 234.2 250 — 7.0 227.1 250
23.6 7.0 250.7 300 — 7.0 246.3 300
23.6 7.0 269.9 300 — 7.0 205.7 225
23.6 7.0 229.3 250 — 7.0 220.7 250
23.6 7.0 244.3 250 — 7.0 238.2 300
23.6 7.0 261.8 300 — 3.5 102.0 110
12.6 3.5 114.6 125 — 3.5 109.5 125
12.6 3.5 122.1 125 — 3.5 118.2 150
12.6 3.5 130.8 150 — 2.5 80.4 90
9.6 2.5 90.0 100
2.5 86.6 100
9.6 2.5 96.2 110
2.5 92.9 110
9.6 2.5 102.5 125
7.0 257.2 300
23.6 7.0 280.8 300 — 7.0 276.4 350
23.6 7.0 300.0 350 — 7.0 292.9 350
23.6 7.0 316.5 400 — 7.0 250.8 300
23.6 7.0 274.4 300 — 7.0 268.3 300
23.6 7.0 291.9 350 — 7.0 283.3 350
23.6 7.0 306.9 350 — 3.5 120.9 125
12.6 3.5 133.5 150 — 3.5 129.6 150
12.6 3.5 142.2 175 — 3.5 137.1 175
12.6 3.5 149.7 175 — 2.5 97.7 110
9.6 2.5 107.3 125
2.5 104.0 125
9.6 2.5 113.6 125
2.5 110.2 125
9.6 2.5 119.8 150
POWER SUPPLY
Fuse or
HACR Brkr*
27
Page 28
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)
UNIT
VO LTAGE
SIZE
3 PH, 60 Hz
48A
051
060
LEGEND
FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA Minimum Circuit Amps NEC National Electrical Code RLA Rated Load Amps
*Fuse or HACR circuit breaker per NEC. NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The Canadian units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of volt-
age imbalance. % Voltage imbalance
= 100 x
VOLTAGE
RANGE
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty FLA Hp FLA FLA (total) FLA MCA
208 187 229 34.3 265 34.3 265 34.3 265 34.3 265 6
230 207 253 34.3 265 34.3 265 34.3 265 34.3 265 6
460 414 508 16 120 16 120 16 120 16 120 6
575 518 632 12.9 80 12.9 80 12.9 80 12.9 80 6
208 187 229 40.8 265 47 380 40.8 265 47 380 6
230 207 253 40.8 265 47 380 40.8 265 47 380 6
460 414 508 20.2 135 22.4 175 20.2 135 22.4 175 6
575 518 632 16.6 120 18.6 140 16.6 120 18.6 140 6
max voltage deviation from average voltage
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2
average voltage
COMPRESSOR
CONDENSER
FAN MOTOR
EVAPORATOR
FAN MOTOR
20 59.4
25 74.8
6.5
(ea)
30 88
40 114
20 54
25 68
6.6
(ea)
30 80
40 104
20 27
25 34
3.3
(ea)
30 40
40 52
20 22
25 27
2.6
(ea)
30 32
40 41
25 75.0
6.5 30 88.0
(ea)
40 114.0
25 68.0
6.6 30 80.0
(ea)
40 104.0
25 34.0
3.3 30 40.0
(ea)
40 52.0
25 27.0
2.6 30 32.0
(ea)
40 41.0
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v (BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER
EXHAUST
35.4 7.0 292.9 350
35.4 7.0 312.1 350
35.4 7.0 328.6 400
35.4 7.0 361.1 450
35.4 7.0 286.7 300
35.4 7.0 304.2 350
35.4 7.0 319.2 350
35.4 7.0 349.2 450
18.9 3.5 140.0 150
18.9 3.5 148.7 175
18.9 3.5 156.2 175
18.9 3.5 171.2 200
14.4 2.5 111.6 125
14.4 2.5 117.9 125
14.4 2.5 124.1 150
14.4 2.5 135.4 175
35.4 7.0 350.5 400
35.4 7.0 367.0 450
35.4 7.0 399.5 500
35.4 7.0 342.6 400
35.4 7.0 357.6 400
35.4 7.0 387.6 450
18.9 3.5 169.9 200
18.9 3.5 177.4 200
18.9 3.5 192.4 225
14.4 2.5 136.7 150
14.4 2.5 142.9 150
14.4 2.5 154.2 175
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
= 1.53%
CONVENIENCE
OUTLET
7.0 257.5 300
7.0 276.7 350
7.0 293.2 350
7.0 325.7 400
7.0 251.3 300
7.0 268.8 300
7.0 283.8 350
7.0 313.8 400
3.5 121.1 125
3.5 129.8 150
3.5 137.3 175
3.5 152.3 200
2.5 97.2 110
2.5 103.5 125
2.5 109.7 125
2.5 121.0 150
7.0 315.1 350
7.0 331.6 400
7.0 364.1 450
7.0 307.2 350
7.0 322.2 400
7.0 352.2 450
3.5 151.0 175
3.5 158.5 175
3.5 173.5 225
2.5 122.3 125
2.5 128.5 150
2.5 139.8 175
452 + 464 + 455
1371
=
3
= 457
7 457
POWER SUPPLY
3
Fuse or
HACR Brkr*
28
Page 29
Routing Through Bottom of Unit through bottom of unit, use field-supplied watertight conduit to route power wiring through the 3
— If wiring is brought in
1
/2-in. diameter hole provided
in the unit basepan.
Install conduit connector in unit basepan as shown in Fig. 4-9. Route power and ground lines through connector to terminal connections in unit control box as shown on unit wiring diagram and Fig. 19.
Use strain relief going into control box through 3
5
/8-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wiring section on page 20).
Low-voltage wiring must be run in watertight conduit from
the basepan to control box and through
7
/8-in. diameter hole provided in bottom of unit control box. Field-supplied strain relief must be used going into the box. After wiring is in control box, make connections to proper terminals on terminal blocks (see Field Control Wiring section on this page).
Routing Through Side of Unit field-supplied watertight conduit into unit through 2
— Route power wiring in
1
/2-in. (siz-
es 020-035) or 3-in. (sizes 036-060) hole.
Use field-supplied strain relief going into control box
through 3
5
/8-in. diameter hole provided. After wires are in unit control box, connect to power terminal block (see Power Wir­ing section on page 20).
Bring low-voltage control wiring through the ter hole provided in the condenser section side post. Use strain relief going into
7
/8-in. diameter hole in bottom of unit control
7
/8-in. diame-
box.
After wiring is in control box, make connection to proper terminals on terminal blocks (see Field Control Wiring section below).
IMPORTANT: The VAV (variable air volume) units use variable frequency drives, which generate and can radiate radio frequency energy. If units are not installed and used in accordance with these instructions, they may cause radio interference. They have been tested and found to comply with limits of a Class A computing device as defined by FCC (Federal Communications Commission) regulations, Subpart J of Part 15, which are designed to provide reason­able protection against such interference when operated in a commercial environment.
WARNING
The unit must be electrically grounded in accordance with local codes and NEC ANSI/NFPA 70 (National Fire Protection Association). Electrical shock could cause per­sonal injury.
Affix crankcase heater sticker (located in the installers packet) to unit disconnect switch.
Voltage to compressor terminals during compressor operation must be within the voltage range indicated on the unit name­plate. Phases must be balanced within 2%.
Use the formula in Tables 8A and 8B to determine the per­centage of voltage imbalance.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.
IMPORTANT: On 208/230-v units, transformers 1-5 are wired for 230-v. If 208/230-v unit is to be run with 208-v power supply, the transformers must be rewired as follows:
For transformer 1 move the black wires connected to termi-
nal H2 and connect it to terminal H3.
For transformers 2-4, that are used for the 24-volt control
circuits, connect as follows:
1. Remove cap from red (208 v) wire.
2. Remove cap from spliced orange (230 v) wire. Discon­nect orange wire from black unit power wire.
3. Cap orange wire.
4. Splice red wire and black unit power wire. Cap wires.
If the unit is equipped with the optional convenience outlet
connect the yellow wire to H2 on transformer 5.
IMPORTANT: BE CERTAIN UNUSED WIRES ARE CAPPED. Failure to do so may damage the transformers.
FIELD CONTROL WIRING — The 48A Series units sup­port a large number of control options that can impact the field control wiring.
The control options that the unit can provide relate to the
following parameters:
• CV (constant volume), VAV (variable air volume),
®
VVT
(variable volume variable temperature) or
Carrier TEMP system control operation.
• Stand-alone with a thermostat (CV) or with a space sen­sor (CV and VAV)
• Network application with CCN (Carrier Comfort Network
• Demand ventilation with CO
®
) or other networks
sensor
2
• Economizer and economizer with changeover control
• Staged gas heat
• Building and duct static pressure control
• Fire shutdown and smoke control
• Diagnostics and monitoring For constant volume applications a thermostat (T-Stat) or
space temperature sensor (SPT) will be required. T-STAT (Conventional Thermostat)
— Unit can be con­trolled with a Carrier-approved accessory electro-mechanical or electronic thermostat that has two stages of cooling, two stages of heating control and an output for indoor fan control. It may also include time of day scheduling or use the scheduling routines built into the ComfortLink™ controls.
Install thermostat according to the installation instructions included with accessory thermostat and the unit wiring dia­grams. Locate thermostat assembly on a solid interior wall in the conditioned space to sense average temperature.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through conduit into unit to low­voltage connection in the main control box. For thermostat TB4 connections see Fig. 20.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C Minimum). All wire larger than no. 18 AWG cannot be directly connected at the thermostat and will require a junction box and splice at the thermostat. Set heat anticipator settings as follows:
SIZE
020-050 0.24 0.13 051, 060 0.36 0.13
STAGE 1 (W1) ON
STAGE 2
(W1 and W2) ON
Settings may be changed slightly to provide a greater degree of comfort for a particular installation.
29
Page 30
Staged Gas Control Option Thermistors
— If the unit is equipped with the staged gas heat option, supply-air ther­mistors must be installed. Three supply-air thermistors are shipped with staged gas units and are inside the heating sec­tion. The supply-air thermistors should be located in the supply duct with the following criteria:
• Downstream of the heat exchanger cells
• Equally spaced as far as possible from the heat
exchanger cells
• In a duct location where none of the supply-air ther-
mistors are within sight of the heat exchanger cells
• In a duct location with good mixed supply-air portion of
the unit.
SPT (Space Temperature Sensor)
— For constant volume ap­plications the ComfortLink™ controls can also be used with T55 and T56 space temperature sensors that use a 10K ther­mistor. The T56 sensor also has the capability for a config­urable temperature set point offset. For variable air volume ap­plications only the T55 sensor can be used.
Install sensor according to the installation instructions included with accessory sensor. Locate sensor assembly on a solid interior wall in the conditioned space to sense average temperature.
Run wiring to the space sensor as shown in Fig. 21.
Note that when the remote sensor is used, the red jumper wires provided must be connected from TB4 terminal 4 to 5 and TB4 terminal 5 to 1.
Both the T55 and T56 have a CCN communications port and this should be wired to the CCN Communications TB3 board if it is desired to have access to the CCN through the sensor. If more than one T-55 sensor is being used and averaged, sensors must be wired in multiples of 4 or 9 as shown in Fig. 22.
FIELD-SUPPLIED THERMOSTAT
LIGHT
Y1 Y2 W1 W2 G C X
RC
R
R
a48-8243
1
Y1 Y2 W1 W2 G C X
2 3 45
TB4
6
7
Fig. 20 — Field Control Thermostat Wiring
T56 SPTT55 SPT
TH
10
C
SN
13
11
9
12
14
UNIT TB5
T1
1
3
24
T2
5
7
8
6
a48-6854
Fig. 21 — Space Temperature Sensor Wiring
8
15
16
TB5
TB5
RED
3
BLK
4
SENSOR 1
SPACE TEMPERATURE AVERAGING (4 SENSOR APPLICATION)
3
4
SENSOR 1
SENSOR 4
SENSOR 2
SENSOR 2 SENSOR 3
SENSOR 5
SENSOR 3
SENSOR 4
SENSOR 6
a48-6855
NOTE: Use T55 sensor only.
Fig. 22 — Space Temperature Averaging Wiring
SENSOR 7
SPACE TEMPERATURE AVERAGING (9 SENSOR APPLICATION)
SENSOR 8
SENSOR 9
30
Page 31
T58 Communicating Thermostat
— Carrier also has a fully communicating thermostat which, if used, will be wired to the CCN communication connections on TB3 as described in the Carrier Comfort Network
Carrier Comfort Network Interface
®
Interface section below.
— The rooftop units can be connected to the CCN system. The communication bus wiring is supplied and installed in the field. Wiring consists of shielded, 3-conductor cable with drain wire. The system elements are connected to the communication bus in a daisy chain arrangement. The positive pin of each system element communication connector must be wired to the positive pins of the system element on either side of it, the negative pins must be wired to the negative pins, and the signal pins must be wired to signal ground pins. Wiring connections for CCN should be made at the TB3 terminal block using the screw terminals. The TB3 board also contains an RJ14 CCN plug that can be used to connect a field service computer or other CCN device tempo­rarily. There is also an RJ14 LEN (local equipment network) connection that is used to connect a Navigator
device or
download software.
Conductors and drain wire must be 20 AWG minimum stranded, tinned copper. Individual conductors must be insulat­ed with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An aluminum/polyester 100% foil shield and an outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum operating temperature range of –20 C to 60 C (–4 F to 140 F) is required. Table 9 lists cables that meet the requirements.
Table 9 — CCN Connection Approved Shield Cable
MANUFACTURER CABLE PART NO.
Alpha 2413 or 5463 American A22503 Belden 8772 Columbia 02525
IMPORTANT: When connecting to CCN communi­cation bus to system elements, use color coding system for the entire network to simplify installation and checkout. See Table 10.
Table 10 — Color Code Recommendations
SIGNAL TYPE
Positive (+) RED 1
Ground WHITE 2
Negative (–) BLACK 3
CCN BUS CONDUCTOR
INSULATION COLOR
CCN PLUG PIN
NO.
If a cable with a different color scheme is selected, a similar color code should be adopted for the entire network. At each system element, the shields of the communication bus cables must be tied together. If the communication bus is entirely within one building, the resulting continuous shield must be connected to a ground at one point only. If the communication bus cable exits from one building and enters another, the shields must be connected to grounds at the lightning suppres­sor in each building where the cable enters or exits the building (one point per building only).
To connect the unit to the network:
1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white (ground), and black (–) conductors. (If a different net­work color scheme is used, substitute appropriate colors.)
3. Remove the 3-pin male plug from the base control board in the main control box, and connect the wires as follows:
a. Insert and secure the red (+) wire to terminal 1 of
the 3-pin plug.
b. Insert and secure the white (ground) wire to termi-
nal 2 of the 3-pin plug.
c. Insert and secure the black (–) wire to terminal 3 of
the 3-pin plug.
4. Insert the plug into the existing 3-pin mating connector on the base module in the main control box.
VAV Units with Heat
— For variable air volume units that will use heat, the variable air volume terminals should be interlocked with the unit at TB5 terminals 1 and 2.
Demand Ventilation
— The unit can be equipped with a CO sensor for use in demand ventilation. This can be factory supplied and will be mounted in the return duct. It can also be field supplied and mounted in the return duct or in the space. Connect the field-installed 4 to 20 mA sensor to TB5 terminal 6 and 7. Do not remove the factory-installed 182-ohm resistor.
If an outdoor air quality sensor is used then it should be wired to terminal 11 and 12 on TB6. This will require the use of the optional controls expansion module.
Remote IAQ Override
— If the control is being used with non Carrier building management system it supports the use of the remote IAQ override switch. This should be connected to TB6 terminal 13 and 14. Use of this will require the optional controls expansion module.
Remote Economizer Position Control
— The ComfortLink™ controls will normally control the position of the economizer, but it can also support field control of the economizer position through a 4 to 20 mA signal. If this is used it should be con­nected to TB5 terminal 6 and 7. If the signal is a 4 to 20 mA signal then leave the 182-ohm resistor in place.
Remote Economizer Enable
— If the control is being used with other building management systems and the system will control the enabling and disabling of the economizer free cool­ing, this switch input can be connected to TB6 terminals 1 and
2. Note that the controls also support integrated economizer changeover using outdoor dry bulb, differential dry bulb, outdoor enthalpy and differential enthalpy.
Remote Occupancy Switch
— For interface to other building management systems the control also supports a switch input for remote occupancy signals. This wiring should be connected to terminal TB6 terminal 1 and 3.
Remote Economizer Minimum Position Control
— If the ComfortLink control is controlling the economizer, but a remote minimum position is required, then an external 100K potentiom­eter can be connected to TB5 terminal 6 and 7. Remove the factory-installed 182-ohm resistor.
Smoke Sensor Interface
— The ComfortLink control includes an optional factory-installed return air smoke detector. Remote alarm circuits can be wired to TB5 terminal 8 and 9.
Fire Shutdown and Smoke Control
— The control supports interface to fire and smoke control systems and allows for the following system overrides from remote switch inputs.
• Fire Shutdown — Connect to TB6 terminals 8 and 9.
• Smoke Pressurization — Connect to TB6 terminal 12 and 13. This requires the use of the optional controls expansion module.
• Smoke Evacuation — Connect to TB6 terminal 12 and
14. This requires the use of the optional controls expan­sion module.
• Smoke Purge — Connect to TB6 terminal 12 and 15. This requires the use of the optional controls expansion module.
Demand Limiting
— The control can also be used with demand limiting control from remote building management systems. If a two stage system is going to be used with Redline Limiting where the machine is not allowed to increase load and Load Shed where the load is decreased to a configurable limit in capacity then these can be connected to TB6 terminals 4 and 5 and 5 and
6. This requires use of the controls expansion module.
2
31
Page 32
Step 9 — Make Outdoor-Air Inlet Adjustments
ECONOMIZER AND FIXED OUTDOOR AIR DAMPER — Hoods are used on all units with economizer or adjustable self-closing fixed outdoor air damper.
NOTE: If accessory power exhaust or barometric relief pack­ages are being added to the unit, install power exhaust or baro­metric relief before installing economizer hoods.
Economizer Hood Assembly shipped in a package secured to the outside of the unit. The hood assemblies must be field-assembled. The 48AW,AY units are side supply and side return. The return duct limits access to economizer filters from below.
The 48AJ,AK,AW,AY020-050 units have two hoods on ev­ery unit. The 48AJ,AK,AW,AY051 and 060 units have 3 hoods on every unit.
NOTE: Before assembly of the economizer hood, check along the outer edges of the economizer assembly for any seal strip protruding past the flanges. Trim the excess seal strip so that it is flush with the economizer assembly flanges.
Perform the following procedure to assemble the economizer hood.
1. Apply black seal strip (provided) to outside top-edge of hood sides. Wrap seal strip over edge to cover top flange (6 hood sides). Make sure seal strip covers screw holes. Allow strip to overhang mounting flange. See Fig. 23.
2. Assemble hood sides, top, and cross member with gasketed screws provided. See Fig. 24.
3. Attach 15 green speed clips (provided) to hood top.
4. Apply black seal strip (provided) to mounting flanges of hood sides being sure to cover mounting holes. See Fig. 25.
5. Apply black seal strip (provided) to back of hood top mounting flange. Seal strip of hood top mounting flange must press tightly against seal strip of hood side mount­ing flanges. See Fig. 26.
6. Add gray foam strip (provided) to cross members on bot­tom tray. See Fig. 27.
7. Attach gray foam strip (provided) to block-off baffle on outer face of flange. See Fig. 28.
8. Remove the screws on each end and along top of damper assembly of unit. Remove top 4 screws on each side of filter panel under damper assembly. Set hood assembly in place and attach to unit using these screws.
9. Remove screws along bottom of damper assembly. Locate and mount block-off baffle using these screws.
10. Assemble 2 filter tracks side-by-side with the assembled ends together.
11. Attach one mounting angle to the assembled end of the filter track. See Fig. 29.
12. Attach 9 green speed clips (provided) to hood side panels. Engagement section of clip faces up and towards the out­side of the hood side panels.
13. Attach remaining mounting angle to other end of the filter track with no. 10 screws provided.
14. Place filter track assembly in bottom of hood by attaching to hood with speed clips and gasketed screws provided.
NOTE: Be sure the filters are installed with the airflow in the correct direction.
15. Attach black seal strip (provided) to filter cover. Seal strip should be applied centered over the holes of the one flange, making sure to fully cover holes and centered over the other large flange. See Fig. 30.
16. Slide two 20 x 25-in. filters into cross members of hood assembly. Attach filter cover over filters with screws and speed clips provided.
— The economizer hood is
1
/8-in. past the end opposite the
TOP FLANGE
BLACK SEAL STRIP
HOOD SIDE
Fig. 23 — Adding Seal Strip to Top of Hood Sides
a48-8498
Fig. 24 — Economizer Hood Assembly
(Right Side/Center Economizer Hood Shown)
MOUNTING FLANGE
HOOD SIDE
Fig. 25 — Adding Seal Strip to Sides of Hood Top
Mounting Flange
32
Page 33
HOOD TOP
MOUNTING ANGLE
HOOD SIDE
48-1104
Fig. 26 — Adding Seal Strip to Back of Hood Top
Mounting Flange
GRAY FOAM STRIP
CROSS MEMBER
FILTER TRACK ASSEMBLY
a48-8499
Fig. 29 — Mounting Angle Attached
to Filter Track Assembly
BLACK SEAL STRIP (CENTERED)
FILTER COVER
48-1110
Fig. 30 — Attaching Seal Strip to Filter Cover
48-1105
Fig. 27 — Adding Foam Strip to Cross Member
BLOCKOFF BAFFLE
GRAY FOAM STRIP
a48-4328
Fig. 28 — Adding Seal Strip to Block-Off Baffle
Step 10 — Position Power Exhaust/Barometric Relief Damper Hood — All units are shipped with the
hoods folded inside the unit in a shipping position. For 48AJ, and AK units the hood must be tilted out once the unit is in­stalled. On 48AW, AY units, (designed for horizontal supply and return) the assemblies will have to be relocated to return ductwork. See Fig. 31 for dimensions and details.
All electrical connections have been made and adjusted at the factory. The power exhaust blowers and barometric relief dampers are shipped assembled and tilted back into the unit for shipping. Brackets and extra screws are shipped in shrink wrap around the dampers. If ordered, each unit will have 4 (48AJ,AK,AW,AY020-050 units) or 6 (48AJ,AK,AW,AY051 and 060 units) power exhaust blowers and motors or baromet­ric relief dampers.
1. Remove 9 screws holding each damper assembly in place. See Fig. 32. Each damper assembly is secured with 3 screws on each side and 3 screws along the bottom.
Save screws.
CAUTION
Be careful when tilting blower assembly. Hoods and blow­ers are heavy and can cause injury if dropped.
2. Pivot each damper assembly outward until edges of damper assembly rest against inside wall of unit.
3. Secure each damper assembly to unit with 6 screws across top (3 screws provided) and bottom (3 screws from Step 1) of damper.
4. With screws saved from Step 1, install brackets on each side of damper assembly.
5. Remove tape from damper blades.
33
Page 34
LOCATION BAROMETRIC RELIEF OR POWER EXHAUST “SIDE #2
23.28” TYP
ECONOMIZER
HOOD
ECONOMIZER
HOOD
42.56”
ALTERNATE LOCATION (END)
a48-8244
END #2
42 MIN.
12.94 (UNIT
OPENING)
PLENUM RATED CABLE (FIELD SUPPLIED)
END #1
42.62 TYP
23.28”
R/A
“SIDE #1
42.62
S/A
R/A
S/A
J BOX
NOTE: 020-050 SIZES SHOWN (2 POWER EXHAUST FANS). SIZES 051 AND 060 HAVE 3 POWER EXHAUST FANS. ALL UNIT SIZES HAVE THE SAME SIZE POWER EXHAUST.
Fig. 31 — Power Exhaust Relocated to Side Return Duct
J BOX
NOTES:
1. Unless otherwise specified, all dimensions are to outside of part.
2. Dimensions are in inches.
3. On 48AW,AY units, accessory barometric relief or power exhaust must be mounted in the field-supplied return ductwork.
Fig. 32 — Barometric Relief Damper and Power Exhaust Mounting Details
Step 11 — Route VAV Static Pressure Sensors
VAV DUCT PRESSURE TRANSDUCER — The VAV duct pressure transducer (VAV inverter pressure transducer) is locat­ed behind the filter access door on the lower inner panel. See Fig. 33. A section of field-supplied be run from the high pressure tap on the differential pressure switch and connected to a field-supplied tap in the supply-air duct. The tap is usually located supply duct. Remove plug button in panel to route tubing.
VAV BUILDING PRESSURE TRANSDUCER — The VAV building pressure transducer (modulating power exhaust pres-
1
/4-in. plastic tubing must
2
/
of the way out on the main
3
lower inner panel. See Fig. 33. A section of field-supplied
1
/4-in. plastic tubing must be run from the high pressure tap on the differential pressure switch to the conditioned space. The pressure tube must be terminated in the conditioned space where a constant pressure is required. This location is usually in an entrance lobby so that the building exterior doors will open and close properly. Remove plug button in panel to route tubing.
The low pressure tap is factory-routed to the atmosphere. For a positive-pressure building, route the high tap to building air and low tap to atmosphere. For a negative-pressure
sure transducer) is located behind the filter access door on the
34
a48-3808
Page 35
building, route the high tap to atmosphere and the low tap to building air.
Step 12 — Install All Accessories — After all the
factory-installed options have been adjusted, install all field­installed accessories. Refer to the accessory installation instruc­tions included with each accessory.
The 48A Series units have a large number of factory­installed options which were previously available only as accessories. Some of the available options can also be installed in the field if needed. In most cases the units have been pre-wired so that the accessories can be easily installed. Instructions are shipped with each accessory. Configuration of the controls for these accessories as well as the factory-installed options can be found in the Controls, Start-Up, Operation, Service and Troubleshooting Book. The following is a list of some of the common accessories:
• Thermostats and space temperature sensors
• LP (liquid propane) conversion kit
• Accessory barometric relief damper
• Accessory power exhaust
• Non-modulating to modulating power exhaust
• Condenser coil hail guards
• Outdoor humidity sensor (used for economizer enthalpy changeover)
• Return air humidity sensors (used for economizer differential enthalpy changeover)
• Return air smoke detector
• Controls expansion module (used for interface to build­ing management systems, not typically needed on system with the Carrier Comfort Network tem)
• Plugged filter sensor
• Motormaster® V low ambient head pressure control
IMPORTANT: Carrier recommends the installation of field-fabricated wind baffles on all vertically oriented condenser coils when operating in environments with prevailing winds of more than 5 MPH and where tem­peratures drop below 32 F. See the Motormaster accessory installation guide for instructions.
®
[CCN] sys-
capable of supporting the weight of a person. The return ductwork connection locations on the side of the unit are higher than normal (31-in. high). Unit-mounted power exhaust or barometric relief cannot be used because of return air ductwork will cover the power exhaust or barometric relief installation locations. Power exhaust or barometric relief may be installed in the return air ductwork.
To convert the unit, perform the following:
1. Seal the bottom return openings of the unit with airtight panels capable of supporting the weight of a person.
2. Remove the panels located below the economizer outdoor-air dampers. These openings will be used for the return-air ductwork. There are 2 panels on 48AJ,AK020­050 units. There are 3 panels on 48AJ,AK051 and 060 and units. These openings are normally used for power exhaust or barometric relief.
3. Run the return air ductwork up to the openings. One single duct is recommended to connect to the unit over the return air openings. See Fig. 34. The return duct must incorporate a minimum
3
/4-in. flange for connection to the unit cabinet. The unit does not have duct flanges for this conversion.
Side Supply and Return Units (48AW,AY) with Field­Installed Power Exhaust in Return Duct — Space must be available in the return duct to mount the power exhaust fan (gravity relief) modules. Dimensions and suggested locations are shown in Fig. 34. These instructions are a guideline and not a comprehensive procedure. The design contractor must pro­vide some design initiative.
The wiring harness that is provided with the power exhaust accessory is not long enough for the fan modules to be mount­ed in the return air duct. Field-supplied wiring must be spliced into the harness. Use a junction box at each splice. The wiring may be run in the return duct, or externally in conduit. A ser­vice access panel will be needed near each power exhaust fan.
Step 13 — Field Modifications
DUCTWORK Bottom Return Units (48AJ and AK) Field-Modified for
Side Return — The 48AJ and AK units with bottom return air connections may be field-modified to accommodate side return air connections.
IMPORTANT: The following section is a guideline and not a comprehensive procedure to field modify the units. The installing contractor must provide some design initiative. Field-conversion is complex and is not recommended. Units with electric heat must not be converted because of potential heating mode operating problems.
Conversion to horizontal return requires that the bottom
return openings of the unit must be sealed with airtight panels
AUXILIARY CONTROL BOX
PRESSURE TRANSDUCERS (INSIDE OF PANEL)
Fig. 33 — Pressure Transducer Locations
a48-6976
35
Page 36
97.78” (020-050), 150.47 (051 AND 060) INSIDE DIMENSION
RA
31.25
INSIDE
a48-8245
Fig. 34 — Side Return Air Conversion
Copyright 2009 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53480067-01 Printed in U.S.A. Form 48A-7SI Pg 36 8-09 Replaces: 48A-5SI
Loading...