Carrier 42BHE user guide manual

Fig. 1 — Component Identification (42BHE Units Shown)
A42-3984
AirStream™
42BHE,BVE06-40
System Fan Coil Air Conditioners
Installation, Start-Up and Service Instructions

CONTENTS

Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Step 2 — Protect Unit from Damage . . . . . . . . . . . . . . 2
Step 3 — Prepare Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 4 — Prepare Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 5 — Position Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Step 6 — Make Piping Connections . . . . . . . . . . . . . 11
Step 7 — Make Electrical Connections . . . . . . . . . . 13
Step 8 — Make Duct Connections . . . . . . . . . . . . . . . 14
Step 9 — Install Mixing Box . . . . . . . . . . . . . . . . . . . . . 14
Step 10 — Make Final Preparations . . . . . . . . . . . . . 15
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Air System Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean Coils. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Check Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fan and Motor Bearings. . . . . . . . . . . . . . . . . . . . . . . . . 16
Align Pulley . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Adjust Fan Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean Fan Wheel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Clean or Replace Air Filters . . . . . . . . . . . . . . . . . . . . . 16
Recommended Maintenance . . . . . . . . . . . . . . . . . . 16
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Excessive Condensation on Fan Coil Unit
Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Motor Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
START-UP CHECKLIST . . . . . . . . . . . . . . . . . CL-1,CL-2

SAFETY CONSIDERATIONS

Air-handling equipment is designed to provide safe and reliable service when operated within design specifications. To avoid injury to personnel and damage to property or equip­ment, use good judgment and follow safe practices as outlined below when installing and operating this equipment.
DANGER
NEVER REACH INTO a unit while the fan is running. LOCK OPEN AND TAG the fan motor power disconnect
switch before working on unit. In addition, remove the fuses and take them with you after noting this on tag.
DISCONNECT ALL POWER before attempting any installation or service. More than one power source may be supplied to a unit. Power to remote mounted control devices may not be supplied through the unit.
CHECK THE WEIGHT of assembly and components to be sure that rigging equipment can handle them safely.
NEVER PRESSURIZE a coil with a non-liquid for leak testing. A dangerous burst may occur.
DO NOT STEAM CLEAN coils until you are sure all per­sonnel are clear of the area.
Failure to follow these warnings will result in severe per­sonal injury or death.

INTRODUCTION

The following contains general installation instructions for the 42BHE,BVE fan coil units. See Fig. 1 for components. Re­fer to the unit wiring diagram installed on the blower housing or specific manufacturer literature for any other type of factory­mounted controls.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53420009-01 Printed in U.S.A. Form 42B-4SI Pg 1 11-13 Replaces: 42B-3SI
See drawings for unit configurations, dimensions, clearanc-
WIDTH
E
2
K
J
TOP VIEW
SEE DETAIL 1
DEPTH
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND BOTTOM
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1/2
1/2
DETAIL 1
SCALE 0.250
1-3/8
1" SUPPLY
AIR COLLAR
SUPPLY AIR
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT
SECONDARY]
4 X 4 JBOX AND MOTOR MOUNTED SAME SIDE AS COIL CONNECTIONS
SIDE VIEW
1
F RETURN AIR
1" RETURN AIR COLLAR
COIL SUPPLY CONN.
COIL RETURN CONN.
4-3/8 ADD 2" FOR MERV11 FILTER
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
FRONT VIEW 2-1/16
D
A
C
B
HEIGHT
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
71/
8
101/
2
141/
2
21/424 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
81/
2
101/
2
137/
8
21/424 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
71/
8
115/
8
151/
4
21/433 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
10 115/
8
137/
8
21/433 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
133/
8
123/
4
163/
4
21/443 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 121/
2
133/
4
173/
4
21/444 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
157/
8
133/
4
16 71/444 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
161/
2
161/
8
223/
4
61/458 29 613/
4
421/
2
Fig. 2 — Unit Dimensions — 42BHE Fan Coil Base Unit (No Controls)
es, and pipe connections. Refer to unit wiring label for all elec­trical connections. Follow NEC (National Electrical Code) and local codes.

INSTALLATION

Step 1 — Unpack and Inspect Unit —
ping wraps from unit and check shipment against shipping list. Check for concealed shipping damage. If shipment is damaged or incomplete, file claim with transportation company and contact your local Carrier representative immediately.
Remove ship-
Step 2 — Protect Unit from Damage — To main-
tain warranty, protect unit against adverse weather conditions, theft or vandalism on the jobsite.
The described equipment IS NOT suitable for outdoor in­stallations. The equipment should never be stored or installed where it may be subjected to a hostile environment such as rain, snow, or extreme temperatures.
Step 3 — Prepare Jobsite — To save time and to re-
duce the possibility of costly errors, set up a complete sample installation in a typical room at jobsite. Check all critical di­mensions such as pipe, wire and duct connection requirements. Refer to job drawings and product dimension drawings as re­quired. Instruct all trades in the appropriate part of the installa­tion. For unit component identification, refer to Fig. 1. For unit dimensions, refer to Fig. 2-4 for 42BHE units. Refer to Fig. 5-7 for 42BVE units.
2
WIDTH
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. Control box size and position may vary.
6. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
71/
8
101/
2
141/
2
21/
4
24 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
81/
2
101/
2
137/
8
21/
4
24 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
71/
8
115/
8
151/
4
21/
4
33 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
10 115/
8
137/
8
21/
4
33 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
133/
8
123/
4
163/
4
21/
4
43 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 121/
2
133/
4
173/
4
21/
4
44 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
157/
8
133/
4
16 71/
4
44 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
163/
8
161/
8
223/
4
61/
4
58 29 613/
4
421/
2
a42-4241
Fig. 3 — Unit Dimensions — 42BHE Fan Coil Base Unit with Motor Control Option
E
2
FILTER RACK WITH
TOOLLESS ACCESS
FROM SIDES
AND BOTTOM
K
18 DOOR OPEN
J
TOP VIEW
A
D
B
FRONT VIEW
DEPTH
8-11/16
SEE DETAIL 1
MOTOR CONTROLS AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
C
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1-3/8
1" SUPPLY
AIR COLLAR
HEIGHT
SUPPLY AIR
COIL DRAIN CONN.
[FEMALE 1/2-14 NPT SECONDARY]
[1MALE 3/4-14 NPT]
DETAIL 1 SCALE 0.250
1/2
1/2
SIDE VIEW
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
F
COIL SUPPLY CONN.
1
RETURN AIR
1" RETURN
AIR COLLAR
3
WIDTH
E
K
9-11/16
1" SUPPLY
AIR COLLAR
J
TOP VIEW
2
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND BOTTOM
DEPTH
SEE DETAIL 1
20
DOOR OPEN
ELECTRIC HEAT AND MOTOR MOUNTED SAME SIDE AS COIL CONNECTIONS
1-3/8
HEIGHT
SUPPLY AIR
FRONT VIEW
A
C
13-3/4
HANGER ROD
KNOCKOUT Ø5/8
TYP 4 PLCS
1/2
1/2
DETAIL 1 SCALE 0.250
BOTH SIDE PANELS WITH TOOLLESS CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
COIL SUPPLY CONN.
SIDE VIEW
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[FEMALE 1/2-14 NPT SECONDARY]
1
1" RETURN AIR COLLAR
RETURN AIR
D
B
NOTES:
1. All dimensions are in inches (±1/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Right hand shown, left hand opposite.
4. Hanger rods, which are field-supplied, are shown for reference only.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BHE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct Mounting Holes
AB CDEF J K
06 9 x 4 36 28 19
3
/
4
87/
8
101/
2
141/
2
21/424 161/
2
271/
4
351/
4
08 9 x 6 36 28 193/
4
87/
8
101/
2
137/
8
21/424 161/
2
271/
4
351/
4
10 10 x 4 371/
2
37 211/
2
103/8115/
8
151/
4
21/433 181/
4
361/
4
37
12 10 x 7 37
1
/
2
37 211/
2
103/
8
115/
8
137/
8
21/433 181/
4
361/
4
37
16 11 x 10 37
3
/
4
47 211/
2
137/
8
123/
4
163/
4
21/433 181/
4
461/
4
37
20 12 x 9 40
1
/
4
48 24 13 133/
4
173/
4
21/444 203/
4
471/
4
391/
2
30 12 x 12 401/
4
48 321/
4
161/
4
133/
4
16 71/444 29 471/
4
391/
2
40 15 x 12 431/
2
62 321/
4
163/
4
161/
8
223/
4
61/458 29 613/
4
421/
2
Fig. 4 — Unit Dimensions — 42BHE Fan Coil Base Unit with Electric Heat Option
A42-661EF
4
C
A
7-7/16
TOP VIEW
2-1/16
B
4 X 4 JBOX AND MOTOR
MOUNTED SAME SIDE AS
COIL CONNECTIONS
DEPTH
1-7/16
1" SUPPLY AIR COLLAR
SUPPLY AIR
BOTH SIDES AND FRONT PANEL WITH CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
HEIGHT
RETURN AIR
COIL RETURN CONN.
COIL SUPPLY CONN.
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND TOP
1" RETURN AIR COLLAR
2
E
WIDTH
FRONT VIEW
F
1"
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct
AB CEF
06 9 x 4 20 28 36
1
/
2
71/
8
101/
2
163/
4
24 161/
2
08 9 x 6 20 28 361/
2
81/
2
101/
2
151/
4
24 161/
2
10 10 x 4 22 37 393/
8
71/
8
115/
8
241/
2
33 181/
4
12 10 x 7 22 37 393/
8
10 115/
8
211/
2
33 181/
4
16 11 x 10 22 47 393/
8
133/
8
123/
4
163/
4
43 181/
4
20 12 x 9 24 48 451/
8
121/
2
133/
4
173/
4
44 203/
4
30 12 x 12 28 48 541/
4
157/
8
133/
4
16 44 29
40 15 x 12 28 62 57
5
/
8
161/
2
161/
8
223/
4
58 29
A42-4242
Fig. 5 — Unit Dimensions — 42BHV Fan Coil Base Unit (No Controls)
5
A
C
B
1"
TOP VIEW
8-3/4"
17-15/16"
DOOR OPEN
HEIGHT
2"
F
1"
E
WIDTH
FRONT VIEW
MOTOR CONTROLS
AND MOTOR MOUNTED
SAME SIDE AS
COIL CONNECTIONS
SUPPLY AIR
DEPTH
1" SUPPLY AIR COLLAR
BOTH SIDES AND FRONT PANEL WITH CAMLOCK ACCESS
4-3/8 ADD 2" FOR MERV11 FILTER
COIL RETURN CONN.
COIL SUPPLY CONN.
RETURN AIR
1" RETURN AIR COLLAR
COIL DRAIN CONN.
[MALE 3/4-14 NPT]
[MALE 1/2-14 NPT SECONDARY]
SIDE VIEW
FILTER RACK WITH TOOLLESS ACCESS FROM SIDES AND TOP
NOTES:
1. All dimensions are in inches (±
1
/4 in.).
2. Any modifications to product specifications by any person are subject to acceptance of the factory. Product specifications are subject to change without notice.
3. Left hand shown, right hand opposite.
4. Drain pan removal is on the piping side of the unit.
5. “C” dimension is measured from coil side of the unit.
UNIT
42BVE
DIMENSIONS (in.)
Fan Size Depth Width Height
Supply Duct Return Duct
AB CEF
06 9 x 4 20 28 36
1
/
2
71/
8
101/
2
163/
4
24 161/
2
08 9 x 6 20 28 361/
2
81/
2
101/
2
151/
4
24 161/
2
10 10 x 4 22 37 393/
8
71/
2
115/
8
241/
2
33 181/
3
12 10 x 7 22 37 393/
8
10 115/
8
211/
2
33 181/
3
16 11 x 10 22 47 393/
8
133/
8
123/
4
163/
4
43 181/
3
20 12 x 9 24 48 451/
8
121/
2
133/
4
173/
4
44 203/
4
30 12 x 12 28 48 543/
16
157/
8
133/
4
16 44 29
40 15 x 12 28 62 57
5
/
8
167/
16
161/
8
223/
4
58 29
a42-4243
Fig. 6 — Unit Dimensions — 42BHV Fan Coil Base Unit with Motor Control Option
6